Datalogic Automation S.r.l.
Via S. Vitalino 13
40012 - Lippo di Calderara di Reno
Bologna - Italy
C-BOX 150
Ed.: 07/2007
ALL RIGHTS RESERVED
Datalogic reserves the right to make modifications and improvements without prior notification.
Datalogic shall not be liable for technical or editorial errors or omissions contained herein, nor for incidental or
consequential damages resulting from the use of this material.
Product names mentioned herein are for identification purposes only and may be trademarks and or
registered trademarks of their respective companies.
ATTENTION: READ THIS INFORMATION BEFORE INSTALLING THE PRODUCT
- This product is intended to be installed by Qualified Personnel only.
The C-BOX 150 is intended to be supplied either by a UL Listed NEC Class 2 power
source, or a UL Listed ITE Limited Power Source (LPS), rated 10-30 V dc, minimum
0.5 A.
The overall value of power consumption of the system (C-BOX
150 + scanner) is given by adding the scanner power
consumption to that of the C-BOX 150. Refer to the manual of
CAUTION
See par. 2.4.1 for correct power supply connections.
CE COMPLIANCE
Warning: This is a Class A product. In a domestic environment this product may
cause radio interference in which case the user may be required to take adequate
measures.
WEEE COMPLIANCE
the connected scanner for details about minimum/maximum
supply voltage and power consumption.
Information for the user in accordance with the European Commission Directive 2002/96/EC
At the end of its useful life, the product marked with the crossed out wheeled wastebin must be disposed of separately
from urban waste.
Disposing of the product according to this Directive:
• avoids potentially negative consequences to the environment and human health which otherwise could be
caused by incorrect disposal
• enables the recovery of materials to obtain a significant savings of energy and resources.
For more detailed information about disposal, contact the supplier that provided you with the product in question or
consult the dedicated section at the website www.automation.datalogic.com.
iv
ENGLISH
ITALIANO
Informazione degli utenti ai sensi della Direttiva Europea 2002/96/EC
L’apparecchiatura che riporta il simbolo del bidone barrato deve essere smaltita, alla fine della sua vita utile,
separatamente dai rifiuti urbani.
Smaltire l’apparecchiatura in conformità alla presente Direttiva consente di:
• evitare possibili conseguenze negative per l’ambiente e per la salute umana che potrebbero invece
essere causati dall’errato smaltimento dello stesso;
• recuperare materiali di cui è composto al fine di ottenere un importante risparmio di energia e di risorse.
Per maggiori dettagli sulle modalità di smaltimento, contattare il Fornitore dal quale è stata acquistata
l’apparecchiatura o consultare la sezione dedicata sul sito www.automation.datalogic.com.
Benutzerinformation bezüglich Richtlinie 2002/96/EC der europäischen Kommission
Am Ende des Gerätelebenszyklus darf das Produkt nicht über den städtischen Hausmüll entsorgt werden. Eine
entsprechende Mülltrennung ist erforderlich.
Beseitigung des Produkts entsprechend der Richtlinie:
• verhindert negative Auswirkungen für die Umwelt und die Gesundheit der Menschen
• ermöglicht die Wiederverwendung der Materialien und spart somit Energie und Resourcen
Weitere Informationen zu dieser Richtlinie erhalten sie von ihrem Lieferanten über den sie das Produkt erworben
haben, oder besuchen sie unsere Hompage unter www.automation.datalogic.com.
Information aux utilisateurs concernant la Directive Européenne 2002/96/EC
Au terme de sa vie utile, le produit qui porte le symbole d'un caisson à ordures barré ne doit pas être éliminé avec les
déchets urbains.
Éliminer ce produit selon cette Directive permet de:
• éviter les retombées négatives pour l'environnement et la santé dérivant d'une élimination incorrecte
• récupérer les matériaux dans le but d'une économie importante en termes d'énergie et de ressources
Pour obtenir des informations complémentaires concernant l'élimination, veuillez contacter le fournisseur auprès
duquel vous avez acheté le produit ou consulter la section consacrée au site Web www.automation.datalogic.com.
Información para el usuario de accuerdo con la Directiva Europea 2002/96/CE
Al final de su vida útil, el producto marcado con un simbolo de contenedor de bassura móvil tachado no debe
eliminarse junto a los desechos urbanos.
Eliminar este producto de accuerdo con la Directiva permite de:
• evitar posibles consecuencias negativas para el medio ambiente y la salud derivadas de una eliminación
inadecuada
• recuperar los materiales obteniendo así un ahorro importante de energía y recursos
Para obtener una información más detallada sobre la eliminación, por favor, póngase en contacto con el proveedor
donde lo compró o consultar la sección dedicada en el Web site www.automation.datalogic.com.
DEUTSCH
FRANÇAIS
ESPAÑOL
v
GENERAL VIEW
1
C-BOX 150
Figure A
25-pin scanner connector
1
3
2
vi
Compression connectors
2
Cover screws (4)
3
A
C-BOX 150
3
4
5
6
7
8
9
10
11
12
2
1
18
Figure B - Bottom Inside
Power on switch
1
Chassis grounding jumper
2
Power polarity error LED (red)
3
RS485 Bus termin.switch
4
Scanner selection switch
5
Power on LED (green)
6
INT-30 power connector
10
uxiliary port connector
11
OM4000 jumpers
12
Warning LED (red)
13
Status LED
14
Spring clamp terminal blocks
15
13
14
15
16
17
Tx LED
GET button
7
TEST button
8
SEND button
9
vii
16
Configuration switch
17
Power source jumper
18
GUIDE TO INSTALLATION
The following can be used as a checklist to verify all of the steps necessary for
complete installation of the C-BOX 150.
1) Read all information in the section "Safety Precautions" at the beginning of this
manual.
2) Correctly position and mount the C-BOX 150 within the reach of the barcode
scanner cable, according to the information in paragraph 2.3.
3) Make all electrical connections according to your application. See par. 2.4 and
2.6.
Further typical layouts are given in the Scanner Reference Manual.
4) Set all the proper configuration jumpers and switches according to your
application.
See all sub-paragraphs under 2.4.
5) Connect the scanner to the C-BOX 150.
6) Switch-on the system.
7) Wait until the Warning Led (WL, red) is switched off.
8) Through the internal 9-pin male connector, (it carries the Scanner Aux. Serial Port
signals), configure the scanner according to your specific application using either
the Genius™ or WinHost™ software configuration tool, see par. 1.2 for program
compatibility.
9) Force the 'Get Scanner Configuration' procedure using the internal keys (see
paragraph 2.5.1).
10) Wait until the Warning Led (WL, red) is switched Off.
Now the C-BOX 150 contains the scanner configuration.
The installation is complete.
viii
INTRODUCTION
1
1 INTRODUCTION
1.1 PRODUCT DESCRIPTION
The C-BOX 150 is a connection box which can be used as an accessory to several
Datalogic family scanners.
Its main feature is to make the substitution of a Datalogic scanner in an installation
plain and easy.
To achieve this goal the C-BOX 150 provides the GET command to pass the
connected scanner’s configuration to the C-BOX 150 non volatile memory. The
SEND command allows a previously saved configuration to be transferred from the
C-BOX 150 to the scanner.
By default, at every power-on, the C-BOX 150 automatically sends the configuration
stored in its memory to the connected scanner. Therefore the substituted scanner will
be correctly configured.
The C-BOX 150 allows you to perform the following functions:
• Facilitate the connection of the scanner signals using a spring clamp connector.
• Get the scanner configuration and store it in memory.
• Force the scanner to the Test operating mode.
• Send the configuration stored in memory to the scanner.
The C-BOX 150 mechanical dimensions are 161 x 114.5 x 40 mm (6.34 x 4.51 x 1.57
in.). The C-BOX 150 weighs about 410 g (14.48 oz).
Electrical connection is provided through spring clamp terminal blocks inside the CBOX 150.
The scanner is connected to the C-BOX 150 through a 25-pin connector placed on
the left side of the housing.
A 9-pin connector placed inside the C-BOX 150 facilitates connection between an
external PC and the auxiliary serial interface of the scanner.
1
1
C-BOX 150
1.2 C-BOX 150 COMPATIBLE DEVICES
The C-BOX 150 can be connected to the following scanners through the 25-pin
connector illustrated in Figure A.
Scanner Configuration Tool
DS1100 * WinHost™
DS2100A WinHost™
DS2100N Genius™
DS2200 * WinHost™
DS2400A WinHost™
DS2400N Genius™
DS4600A WinHost™
DS6X00 Genius™
DX6400 Genius™
DS8100A Genius™
DX8200A Genius™
*10 and 30 Vdc versions only
2
INSTALLATION
2
2 INSTALLATION
2.1 PACKAGE CONTENTS
Verify that the C-BOX 150 and all the parts supplied with the equipment are present
and intact when opening the packaging; the list of parts includes:
1) C-BOX 150
2) Installation manual
3) C-BOX 150 configuration CD-ROM
4) 2 mounting screws
5) Grounding cable
2
1
3
4
5
Figure 1 - C-BOX 150 Package Contents
3
2
C-BOX 150
2.2 OPENING THE DEVICE
To install the C-BOX 150 or during normal maintenance, it is necessary to open it by
unscrewing the four cover screws:
The C-BOX 150 must be disconnected from the power supply
during this operation.
CAUTION
Figure 2 - Opening the C-BOX 150
It is possible to perform the following operations:
• Proceed with the cable connections (see paragraph 2.4.2).
• Mount the C-BOX 150 to a wall or panel.
4
INSTALLATION
2
2.3 MECHANICAL INSTALLATION
The diagram below gives the overall dimensions of the C-BOX 150 and may be used
for its installation.
12
66
[0.47]
[2.60]
Ø3.5
[Ø0.14]
5
[0.20]
150
[5.91]
161
[6.34]
5
[0.20]
40
90
[1.57]
[3.54]
12
[0.47]
89.8
[3.54]
114.5
[4.51]
mm
inch
Figure 3 - Overall Dimensions
5
2
C-BOX 150
C-BOX 150 can be installed to operate in different positions. The two screw holes
inside the housing of the C-BOX 150 are for mechanical fixture (Figure 4).
To mount the C-BOX 150:
1) Open the C-BOX 150 by unscrewing the 4 cover screws. If necessary, using the
two mounting holes inside the device as a pattern, mark the panel with an
appropriate object and then drill two holes in the panel.
2) Align the C-BOX 150 and insert two screws and screw them into the panel until
tight (see Figure 4).
6
Figure 4 - Mounting C-BOX 150
INSTALLATION
A
2.4 ELECTRICAL CONNECTIONS AND HARDWARE SETUP
The following figure shows the typical layout.
SCANNER
C-BOX 150
UXILIARY
INTERFACE
2
SCANNER
SYSTEM CABLES
SCANNER CONFIGURATION PC
Figure 5 – System Layout
A PC can be connected to the C-BOX 150 (and consequently to the scanner auxiliary
interface) through the internal 9-pin connector. This allows both scanner
configuration and monitoring of the data transmitted by the scanner (see the scanner
Reference Manual for more details).
The scanner auxiliary interface signals are also available on the internal spring clamp
connectors.
The scanner configuration and data monitoring are possible once the warning LED is
turned OFF.
The internal 9-pin connector can also be used to configure the C-BOX 150 with a PC,
through the WinHost utility.
After making system cabling and switch settings, connect the scanner to the 25-pin
connector on the left side of the C-BOX 150 housing.
Switch ON the C-BOX 150 power switch (see Figure 6).
By default, after power on, an automatic connection procedure takes place between
the C-BOX 150 and the scanner. During this phase, requiring a few seconds, the
warning LED is turned ON. Once the procedure had been completed successfully,
the warning LED is turned OFF.
To disable this automatic connection procedure, refer to WinHost Help Online.
7
2
C-BOX 150
After system functioning has been verified, close the C-BOX 150 using the 4 cover
screws making sure the rubber seal is fitted correctly between the parts of the
housing.
It is recommended to use the dedicated grounding cable (included in
the package) to improve the C-BOX 150 noise immunity.
Simply connect its open end to the scanner cable’s fixing screw and
NOTE
the other end to the ground, as shown in the figure below.
2.4.1 Power Supply
Power is supplied to the C-BOX 150 through the pins provided on the spring clamp
connector.
The power switch (see Figure 6) switches the power supply ON or OFF for both the
C-BOX 150 and the connected scanner.
ON
OFF
Figure 6 - Power Switch ON/OFF Positions
8
INSTALLATION
2
C-BOX
VS
1
GND
2
USER INTERFACE
V+ (10 - 30 Vdc)
GND
Figure 7 - Power Supply Connections
The power supply must be between 10 and 30 Vdc only.
Pin 1 is also electrically connected to pins 3 and 5, just as pin 2 is
electrically connected to pins 4 and 6. This is useful for external
NOTE
trigger/inputs connections.
The C-BOX 150 is protected against polarity reversal. A dedicated red
LED signals this condition until correct polarity is restored.
NOTE
2.4.2 System Wiring
The connection and wiring procedure for C-BOX 150 is described as follows:
1) Open the C-BOX 150 as described in paragraph 2.2.
2) Verify that the C-BOX 150 power switch is off (see Figure 6).
3) Unscrew the compression connectors and pass all the system cables
through them into the C-BOX 150 housing.
4) To connect the power and input/output signals:
• Prepare the individual wires of the system cables by stripping the
insulation back approximately 1 cm.
9
2
C-BOX 150
• Using a device such as a screwdriver, push down on the lever directly
next to the clamp (see Figure 8).
• Insert the wire into the clamp and release the lever.
The wire will now be held in the spring clamp.
Figure 8 - System Cable Connections
The wiring used can be solid or stranded but must meet the following specifications.
All positions: 24 - 16 AWG 0.2 - 1.5 mm²
10
INSTALLATION
2
The C-BOX 150 spring clamp connector pinouts are indicated in the following table.
Refer to the scanner Reference Manual for details.
Scanner Pinouts
Pin Name
1, 3, 5 VS
2, 4, 6 GND
7, 8 EARTH GROUND
*9, 13 RS485 CABLE SHIELD
20, 40 RESERVED
35 TX AUX
37 RX AUX
DS1100
DS2200
21 OUT1+ OUT1+ OUT1+ OUT1+ OUT1+
22 IO REF OUT REF OUT1- OUT1- OUT123 OUT2+ OUT2+ OUT2+ OUT2+ OUT2+
24 IO REF OUT REF OUT2- OUT2- OUT225 NC NC NC RESERVED OUT 3A
26 IN1- NC NC RESERVED OUT 3B
27 EXT TRIG+ EXT TRIG+ EXT TRIG A EXT TRIG+ EXT TRIG/PS A
28 EXT TRIG- EXT TRIG- EXT TRIG B EXT TRIG- EXT TRIG/PS B
29 NC NC NC IN1+ IN 2/ENC A
30 IO REF NC IN2- IN1- IN 2/ENC B
31 NC NC NC IN2+ IN 3A
32 NC NC NC IN2- IN 4A
33 RESERVED RESERVED RESERVED RESERVED IN 3A
34 RESERVED RESERVED RESERVED RESERVED IN 4A
36 NC RTSA ID-NET- GND IN 3B/IN 4B
38 NC CTSA ID-NET+ SGND AUX GND
39 SGND SGND GND SGND GND
*11, 15 TX232 TX485+ RTX485+
*12, 16 RTS232 TX485- RTX48517 RX232 RX485+
18 CTS232 RX485-
*10, 14, 19 SGND MAIN S G N D M A I N SGND MAIN
RS232 RS485FD RS485HD 20mA CL
(with INT-30 only)
See INT-30
instructions
DS1100 DS2200
*11, 15 RTX485+
*12, 16 RTX485-
17 RESERVED
18 RESERVED
*10, 14, 19 SG N D MA IN
* The signals on pins 9, 10, 11 and 12 are repeated on pins 13, 14, 15 and 16 to facilitate network
connections (i.e. Multiplexer connections using the RS485 half-duplex Interface). In this way the network bus
can enter and exit the C-Box 150 from different spring clamps but be physically connected together.
RS485HD
11
2
C-BOX 150
2.4.3 Scanner Chassis Grounding Jumper Settings
The scanner chassis grounding method can be selected by positioning a jumper (see
Figure 9). In this way the scanner chassis can be connected to earth ground (only if
pins 7 or 8 are connected to a good earth ground) or to the power supply ground
signal. The scanner chassis can also be left floating but, in this case, the jumper
must be removed.
to EARTH
GROUND
(default)
Figure 9 – Chassis Grounding
to GND
floating
2.4.4 Scanner Selection
DS1100
DS2200
Other Devices
Figure 10 - Scanner Selection Switch
This switch must be set upward only when a DS1100 or a DS2200 scanner (10-30 V
version) is connected. For all the other devices the switch must be set downward.
12
INSTALLATION
2
2.4.5 RS485 Bus Termination
ON
OFF
Figure 11 - Termination Resistance Switch
This switch enables or disables the insertion of the bus termination resistor for RS485
Half Duplex Multidrop applications.
In Multiplexer applications the termination resistor must be enabled
ONLY on the last device of the chain, the farthest away from the
Multiplexer (assuming the Multiplexer is the first device of the
chain). On all the other devices this resistor MUST NOT be enabled
CAUTION
(OFF position).
2.4.6 Powering C-BOX 150 From A Scanner
In order for C-BOX 150 to accept power from the scanner through the 25-pin
connector instead of the external power supply, a jumper can be positioned as
indicated in Figure 12.
This is useful, for example, in a typical Master Slaves layout with a Power Supply
Unit connected to the scanners (see paragraph 2.6) or to pass power to connected
accessories such as Encoder and Presence Sensor from DX8200A VAC models or
other scanner layouts. See the relative scanner Reference Manual for details.
EXTERNAL
Figure 12 – C-BOX 150 Power Source Jumper
13
PWR SUP.
(default)
SCANNER PWR
2
C-BOX 150
2.4.7 OM4000 Jumper Settings
Figure 13 - OM4000 Jumpers
The jumpers allow connection to the EXT TRIG signals on separate spring clamp
terminals for applications which use the OM4000 Oscillating Mirror in Trigger Mode.
They are used together and they have the following significance:
when a jumper is in the J5 position (see Figure above) pin 40 is connected to pin 27
(EXT TRIG+); a jumper in J6 position connects pin 20 to pin 28 (EXT TRIG-).
If the jumpers are removed pin 20 and pin 40 are disconnected.
J5
J6
2.4.8 Configuration Switch And 9-Pin Internal Connector
The 9-pin internal connector may have two different functions according to the
position of the configuration switch.
Figure 14 - Configuration Switch and 9-pin Male Connector
POSITION MODE
Normal Operation (default): In this position, the C-BOX 150 is in the
normal operating mode. The configuration PC communicates with the
scanner through the 9-pin internal connector and the scanner
auxiliary serial interface. The internal connector pinout is illustrated in
the following table:
CFG: When the switch is in this position, the C-BOX 150 can be
configured. The communication with the scanner is interrupted and pins
2 and 3 are no longer dedicated to the scanner auxiliary interface but to
the C-BOX 150 configuration (see table below). The C-BOX 150 enters
configuration mode and waits to be configured through WinHost (see
WinHost Help On Line).
Once the C-BOX 150 configuration is completed, it is necessary to
return the switch in the Normal Operation position. At the end of the
reboot phase, the C-BOX 150 is ready to function with the new
configuration.
9-pin C-Box 150 connector pinout in Configuration mode
When the C-BOX 150 configuration is completed, remember to
return the Configuration switch in the Normal Operation position.
CAUTION
15
2
C-BOX 150
2.5 OPERATING MODES
With the C-BOX 150, the following operating modes are possible:
Normal Operation: At power on, the C-BOX 150 tries to connect to the scanner.
Once the connection procedure is completed the C-BOX 150 verifiesif an Automatic
SEND command must be executed. While executing the command, the serial
Auxiliary interface is not available for the user. After the command completion, the
warning LED will turn OFF and the Aux interface will become free for communication.
After the initialization procedure, in the Normal operating mode the scanner reads
barcodes and communicates with the host.
Also in this mode, through the C-BOX 150 internal buttons it is possible to
communicate with the scanner to perform one of the three GET/TEST/SEND
Functions (see paragraph 2.5.1).
Configuration (CFG): When the CFG switch is in CFG position (left) it is possible to
configure the C-BOX 150 parameters through WinHost.
2.5.1 GET/TEST/SEND Functions
The C-BOX 150 has three internal function buttons which are available in the Normal
operating mode.
C-BOX 150
GET TEST SEND
Figure 15 – Internal Function Buttons
The procedure to enable the GET/TEST/SEND function is the following:
1. Press both the left and right buttons at the same time for at least one second;
the warning LED will turn ON.
16
INSTALLATION
2
2. Release the buttons.
3. Press the left button corresponding to the GET function, the center button
corresponding to the TEST function or the right button corresponding to the
SEND function.
Once the buttons are released in step 1, a ten-second timeout starts.
If no button is pressed within this time (no function is selected), the
procedure will be cancelled.
The C-Box 150 warning LED will turn OFF at the end of each
NOTE
procedure.
Function
Description
The C-BOX 150 reads the current scanner configuration
and permanently copies it in its own memory support.
GET (left button)
The C-BOX 150 preserves this configuration also when
switched off. The GET option can be disabled through
WinHost.
The C-BOX 150 forces the WinHost™ compatible scanners
only to run the Test Operating Mode (refer to the scanner
Reference Manual for details).
TEST (center button)
Press any button to quit the Test Operating Mode and
restore the scanner normal operating mode.
For Genius™ compatible scanners you should use the
scanner keypad.
The C-BOX 150 sends the configuration previously stored
in its own permanent memory support to the scanner’s
SEND (right button)
memory.
The SEND option can be disabled through WinHost; by
default it is Automatic.
To override the eventual default Automatic SENDservice, it is possible
to preset a GET service by executing the enabling procedure
immediately at power-on.
NOTE
17
2
C-BOX 150
2.5.2 LED Indicators
Power polarity error
(red)
The internal LEDs of the C-BOX 150 (see Figure above) indicate the following:
POWER ON (PWR) (green) indicates the C-BOX 150 is connected to the
Pown)er on (gree
Figure 16 - LED Indicators
power supply and the power switch is ON.
Warning (red)
Status
(yellow)
TX
(green)
POWER POLARITY ERROR (red) indicates a wrong polarity. While activated, all other
LEDs will be off until the power feed is connected with
correct polarity.
WARNING (WL) (red) indicates a warning or error condition.
Off: the C-BOX 150 has terminated the Connection and/or
the Update phase; all the operations have been executed
successfully.
ON: during a connection procedure and/or the Update
phase (the system is busy) or during the C-BOX 150
Configuration Mode.
It flashes quickly when a GET command has been preset
at power on.
18
INSTALLATION
2
1 blinking/sec: a requested operation has been terminated
abnormally.
2 blinking/sec: a wrong operation has been requested (for
example the configuration in memory is not compatible
with the connected scanner).
STATUS (SL) (yellow) indicates the status of the non-volatile memory
support.
Off: the memory is empty (no configuration on board).
1 blinking/sec: the memory is not empty (a Get scanner
configuration service has been executed)*.
2 blinking/sec: the memory is not empty (a Get Scanner
Configuration service has been executed); however the
saved configuration is not compatible with the current
scanner one.
TRANSMISSION (TX) (green) indicates there is communication between the C-
BOX 150 and the scanner. This LED blinks during the
connection procedure.
* This is the typical state after correct system installation.
19
2
A
pply
C-BOX 150
2.6 TYPICAL LAYOUTS
2.6.1 1000, 2000A/N, 4000 Family Scanners
For 1000, 2000A/N and 4000 scanner families which operate in a point-to-point
single scanner configuration, a typical layout is shown below and the C-BOX 150 is
connected as follows.
C-BOX 150
2
Scanner
PWR su
3
Main serial interface
1
uxiliary serial interface (Local Echo)
2
External Trigger (for On-Line mode)
3
1
Laptop
Host
Figure 17 – Typical point-to-point scanner Layout
20
INSTALLATION
2
2.6.2 2000N Family Scanners
For 2000N scanner families which operate in an ID-NET™ network configuration, a
typical layout is shown below and the C-BOX 150/100s are connected as follows.
Figure 18 – Typical ID-NET™ scanner Layout
C-BOX 150 can perform Backup/Restore of a whole cluster under the following
conditions:
the Master/Slave network is composed of one master and up to 9
•
Slaves maximum
the Master/Slave network must be either Synchronized or Multidata
•
In order to perform Backup/Restore of Master only, the C-BOX 150 Cluster
GET/SEND parameter must be configured to "Master only", see the WinHost Help On-Line.
21
2
C-BOX 150
2.6.3 6000, 8000 Family Scanners
For the 6000 and 8000 scanner families, the C-BOX 150 can operate in both point-topoint single scanner configuration layouts, and in a network cluster of scanners in
Master/Slave layouts.
Slave 2Slave1
Master
CAB-610X CAB-610X
CAB-610X
CAB-610X
BTK-6000
Slave 5 Slave 4
Figure 19 – Typical Lonworks scanner Layout
CAB-610X
CAB-63XX
BTK-6000
CAB-60XX
CAB-63XX
Slave 3
C-BOX 150
PS
Encoder
Host
PWR-240
In a Master/Slave layout with a great number of Slaves, a Power
Supply Unit can be connected to the scanners and the C-BOX 150
can accept the scanner power by setting the Power Source Jumper
NOTE
in the right position. See paragraph 2.4.6
C-BOX 150 can perform Backup/Restore of a whole cluster under the following
conditions:
the Master/Slave network is composed of one master and up to 9
•
Slaves maximum
the Master/Slave network must be either Synchronized or Multidata
•
the A.S.R. mode must be disabled
•
22
INSTALLATION
2
In order to perform Backup/Restore of Master only, the C-BOX 150 Cluster
GET/SEND parameter must be configured to "Master only", see the WinHost Help On-Line.
2.7 SCANNER REPLACEMENT
If you have to replace the scanner with another one:
1. Switch-off the system.
2. Connect the new scanner.
3. Switch-on the system.
4. Wait until the Warning Led (WL, red) is switched Off.
Now the new scanner has been automatically (default) updated with the correct
configuration!
23
3
C-BOX 150
3 TECHNICAL FEATURES
ELECTRICAL FEATURES
Power
Supply voltage 10 to 30 Vdc
Power consumption max. 2.5 W + scanner
USER INTERFACE
LED indicators Power ON, Warning, Status
Tx, Polarity inversion
PHYSICAL FEATURES
Mechanical dimensions 161 x 114.5 x 40 mm (6.34 x 4.51 x 1.57 in)
Weigh t about 410 g. (14.48 oz.)
SOFTWARE FEATURES
Parameter storage Non-volatile internal memory
ENVIRONMENTAL FEATURES
Operating temperature
Storage temperature
Humidity max. 90% non condensing
Vibration resistance
IEC 68-2-6 test FC
Shock resistance
IEC 68-2-27 test EA
Protection class
-10 to 50 °C (14 to 122 °F)
-20 to 70 °C (-4 to 158 °F)
14 mm @ 2 to 10 Hz;
1.5 mm @ 13 to 55 Hz;
2 hours on each axis
3 shocks on each axis
(when correctly connected to the scanner)
2g @ 70-200 Hz
30g; 11 ms;
IP64
24
NOTE
The features given are typical at a 25 °C ambient temperature (if not
otherwise indicated).
DECLARATION OF CONFORMITY
07
Datalogic Automation S.r.l.,
Via S. Vitalino 13
40012 - Lippo di Calderara
dichiara che
declares that the
déclare que le
bescheinigt, daß das Gerät
declare que el
C-BOX-XXX Connection Box;e tutti i suoi modelliand all its models
et tous ses modèles
und seine Modelle
y todos sus modelos
sono conformi alle Direttive del Consiglio Europeo sottoelencate:
are in conformity with the requirements of the European Council Directives listed below:
sont conformes aux spécifications des Directives de l'Union Européenne ci-dessous:
der nachstehend angeführten Direktiven des Europäischen Rats:
cumple con los requisitos de las Directivas del Consejo Europeo, según la lista siguiente:
89/336/EEC EMC Directive e 92/31/EEC, 93/68/EEC emendamenti successivi
and further amendments
et ses successifs amendements
und späteren Abänderungen
y succesivas enmiendas
Basate sulle legislazioni degli Stati membri in relazione alla compatibilità elettromagnetica ed alla sicurezza dei
prodotti.
On the approximation of the laws of Member States relating to electromagnetic compatibility and product safety.
Basée sur la législation des Etats membres relative à la compatibilité électromagnétique et à la sécurité des produits.
Über die Annäherung der Gesetze der Mitgliedsstaaten in bezug auf elektromagnetische Verträglichkeit und
Produktsicherheit entsprechen.
Basado en la aproximación de las leyes de los Países Miembros respecto a la compatibilidad electromagnética y las
Medidas de seguridad relativas al producto.
Questa dichiarazione è basata sulla conformità dei prodotti alle norme seguenti:
This declaration is based upon compliance of the products to the following standards:
Cette déclaration repose sur la conformité des produits aux normes suivantes:
Diese Erklärung basiert darauf, daß das Produkt den folgenden Normen entspricht:
Esta declaración se basa en el cumplimiento de los productos con las siguientes normas:
EN 55022 (C
A
MENDMENT A1 (CLASS A ITE), October2000
EN 61000-6-2, October 2001:
Lippo di Calderara, April 2nd, 2007 Lorenzo Girotti
LASS A ITE), August 1994:
Bologna - Italy
L
IMITS AND METHODS OF MEASUREMENTS OF RADIO DISTURBANCE
CHARACTERISTICS OF INFORMATION TECHNOLOGY EQUIPMENT
LECTROMAGNETIC COMPATIBILITY (EMC).
E
P
ART 6-2: GENERIC STANDARDS – IMMUNITY FOR INDUSTRIAL
ENVIRONMENTS
Product & Process Quality Manager
www.automation.datalogic.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.