Danfoss X5OPT01 Installation guide

X5OPT01 115 VAC Encoder Interface
Option Board
Installation Manual
DPD00113
Need Help?
This manual answers most installation and startup questions
that may arise. However, if you have any problems,
please let your first call be to us.
Chambersburg, PA 17202
Normal business hours:
(North America)
8:00 AM to 5:00 PM, Eastern time
+1 877-Vacon06
(+1 877-822-6606)
After-hours support is also available
and Vacon, Inc. are trademarks of Vacon Plc, a member of Vacon Group.
All other product names are trademarks of their respective companies.
Copyright 2009, Vacon, Incorporated. All rights reserved.
X5OPT01 115 VAC / Encoder Interface Option Board vacon 3

Installing the X5OPT01 115 VAC / Encoder Interface Option Board

Introduction

The X5OPT01 provides the option of controlling X5 AC drives from 115 VAC control signals, or to connect a shaft­mounted encoder to the drive to improve speed regulation. A maximum of five channels of 115 VAC control is available for use in selecting direction, preset speeds, or other drive functions.
With this option, an encoder with a nominal rating of up to 2048 pulses per revolution can be connected to the X5 unit to improve speed load regulation of the drive. Overall encoder frequency at maximum process speed must be limited to 100kHz.
This option also provides two additional control relays, each rated for 115 VAC, 1 amp, or for 230 VAC, 0.5 amp.

Applicable Documents

This manual is supplied as a supplement to the X5 AC Drive User’s Manual (DPD 00089, previously Form 1434).

Option Kit Contents

The option kit includes the following materials:
Part Number Description
25100079C 115 VAC / Encoder Option Board
32100391 Flexible cable assembly
Email: usa@vacon.com • Fax 717-264-3115
4 vacon X5OPT01 115 VAC / Encoder Interface Option Board

Installation Procedures

!
WARNING
SENSITIVE EQUIPMENT
This assembly contains static-sensitive components. It should be handled only by a static-safe installer, using a grounded wrist strap.
Failure to observe this precaution may cause premature equipment failure.
!
DANGER
HAZARDOUS VOLTAGE
• Disconnect all power before servicing a drive unit or its components. WAIT 5 MINUTES until the DC bus capacitors discharge.
• Ensure that any other power sources that may feed control logic have been disconnected.
DO NOT short across DC bus capacitors or touch unshielded components or terminal strip screw connections with voltage present.
• Install all covers before applying power or starting and stopping the drive.
• The user is responsible for conforming to all applicable code requirements with respect to grounding all equipment.
• Many parts in a drive, including printed circuit boards, operate at line voltage. DO NOT TOUCH. Use only electrically-insulated tools.
Before servicing any drive.
• Disconnect all power.
• Place a “DO NOT TURN ON” label on the drive disconnect.
• Lock the disconnect in the open position.
Failure to observe these precautions will cause shock or burn, resulting in severe personal injury or death.
Figure 1 on page 5 illustrates the option board and the location of the terminals and the power supply selector.
24-hour support 1-877-822-6606
X5OPT01 115 VAC / Encoder Interface Option Board vacon 5
Encoder / 115 VAC Interface
Control Relay Terminals
Encoder Interface Power
Supply Selector
Figure 1: Option Board Layout
Before you can install the option board, you must first remove the drive cover.
Figure 2 shows the locations of the cover screws. The torque range for the X5 Size 1 cover is 18-26 in/lbs.
Cover screw locations
Figure 2: Cover Assembly and Screw Locations
Cover screw locations
Email: usa@vacon.com • Fax 717-264-3115
6 vacon X5OPT01 115 VAC / Encoder Interface Option Board
The option board is installed just above the control board in all configurations (a Size 1 unit is shown in Figure 3 for reference). The screws labeled “A” must be removed from the drive unit; those labeled “B” need only to be loosened to accept the board slot.
.
B
B
A
Figure 3: Option Mounting Locations
Once the board is in place, tighten the screws to a maximum of 26 in-lbs.
A
Next, install the flexible circuit to finish the interface to the control board. (Refer to Figure 4 on page 6.) To install the flexible circuit, first remove the keypad frame (necessary in this size unit). The frame is attached with two screws in opposite corners; the screws thread into fasteners in the plastic assembly. After the flexible circuit is installed, replace these screws, limiting the installation torque to 12 in-lbs..
Figure 4: Flexible Circuit Interface to Control Board
24-hour support 1-877-822-6606
X5OPT01 115 VAC / Encoder Interface Option Board vacon 7

115 VAC Interface / Relay / Encoder Interface Terminals

The X5OPT01 option kit includes five 115 VAC inputs, two additional programmable relays, and an encoder interface. The details of the terminals on the board related to the 115 VAC interface and the encoder are shown in the following table:
Terminal Description
115 VAC logic input; connect input to 115 VAC to activate. The programmable functionality of these inputs is controlled
by parameters 728, 729, 730, 731, and 732. Each of these inputs can be disabled or configured to emulate the function of the FWD, REV, R/J, EN, MOL, DI1, DI2, DI3, DI4, or DI5 input terminals on the X5 control board.
Refer to the X5 User’s Manual for more information.
The third auxiliary relay. The function of this relay is set by parameter 709.
Functionally, it is capable of each of the features outlined in the X5 User’s Manual under parameters 705-708.
Terminal NO3 is a normally-open contact; it will close when the relay activates. NC3 is a normally-closed contact; it will open when the relay activates. RC3 is the common terminal associated with both contacts.
The ratings of these contacts are 115 VAC, 1 amp; and 230 VAC, 0.5 amp.
The fourth auxiliary relay. The function of this relay is set by parameter 710.
Functionally, it is capable of each of the features outlined in the X5 User’s Manual under parameters 705-708.
Terminal NO4 is a normally-open contact; it will close when the relay activates. NC4 is a normally-closed contact; it will open when the relay activates. RC4 is the common terminal associated with both contacts.
The ratings of these contacts are 115 VAC, 1 amp; and 230 VAC, 0.5 amp.
Channel A input from the encoder. Compatible with line driver, open collector, or totem pole outputs from an encoder. If it is an open collector or totem pole-type, encoder outputs are used; connect the A- terminal to Ecom.
Channel B input from the encoder. Compatible with line driver, open collector, or totem pole outputs from an encoder. If it is an open collector or totem pole-type, encoder outputs are used; connect the B- terminal to Ecom.
Channel C input from the encoder, the home pulse. Compatible with line driver, open collector, or totem pole outputs from an encoder. If it is an open collector or totem pole-type, encoder outputs are used; connect the C­terminal to Ecom.
Power supply terminal for use with a customer-supplied encoder. It can be either +12 VDC or +5 VDC based on the position of the encoder interface power supply selector shown in Figure 1. Voltage regulation: +/- 5%; maximum current available is 100 mA.
Figure 5: 115 VAC Interface / Encoder Terminals
Note that the connections described in Table 1 work only when the encoder has an internal pull-up resistor on the open col­lector. Alternatively, it might be preferable to pull the + channel high, and attach the open collec­tor to the - channel. For example, if using Channel A, A+ on the option board would be tied to VDC, and A- would be connected to the open collector coming from the encoder. The advantage in this method is that no pull-up/ down resistors are needed; if the encoder has an internal pull-up, this does not affect anything.
DI-A DI-B DI-C DI-D DI-E
ACn The neutral connection for the 115 VAC control inputs
NO3
RC3 NC3
NO4
RC4 NC4
A+ A-
B+ B-
C+ C-
VDC
Ecom Signal common for the encoder interface
Email: usa@vacon.com • Fax 717-264-3115
8 vacon X5OPT01 115 VAC / Encoder Interface Option Board

Specifications for Encoder / 115 VAC Interface

Encoder Interface 115 VAC Interface
Speed regulation < 0.1 Hz (1) On state 90-140 VAC
Input frequency (max.) 100 kHz Off state < 10 VAC
Input voltage 10-24 VDC +/- 5% Input frequency 58-62 Hz
Suggested pull-up
resistor
Terminal block wire
limitations
(1) PID feedback plus optimal motor turning in SLV mode employed
5 VDC 500 ohms
24 VDC 3.3k ohms
12-24 AWG
On/off delay 30 ms maximum12 VDC 1k ohms
Terminal block wire limitations
12-24 AWG

Setup and Use

The encoder interface is most effective if used in conjunction with the vector mode of operation. Refer to Chapter 6 of the X5 User’s Manual for detailed information about using the vector mode. Three additional parameters are provided to calibrate the encoder:
Parameter # Parameter Name Range Default Value
219 Encoder Pulses per Revolution 0-16383 1024
220 Encoder Filter Time 10-1000 ms 20 ms
221 Encoder Speed Protection 0-20.0% 0%
Parameter 219, Encoder Pulses per Revolution, can either be extracted from the encoder nameplate or the data sheet supplied with it. Parameter 220, Encoder Filter Time, is used to filter the encoder signal in the event of noise. Parameter 221 is for limiting the response of the drive, in the event of the loss of encoder signal.
Two other parameters are provided to allow more flexibility in encoder selection, and to improve PID application usage:
Parameter # Parameter Name Range Default Value
Quadrature
223 EncoderType
224 Encoder Range 0-24000 rpm 0 rpm
or Single Channel
Quadrature
Parameter 223, Encoder Type, allows the use of either quadrature or single-channel types of encoders.
Parameter 224, Encoder Range, improves PID application flexibility. This parameter should be used in situations where the encoder feedback signal is not always directly proportional to the motor speed, for example, a winder using an encoder mounted on an idler pulley feeding a winding spool. The PID may be attempting to maintain a constant linear speed on the wound media, but as the diameter of the media on the spool changes, the motor turning the spool needs to vary its speed to maintain the linear speed at the idler pulley.
When parameter 224 is set to 0, it is ignored, and the PID calculates the feedback percentage based on parameter 301, Maximum Frequency. When this parameter is set to a non-zero value, the PID uses instead Parameter 224’s setting to calculate the feedback percentage.
Encoder feedback works similarly to an analog input as configured in parameters 850 (PID Configure), 851 (PID Feedback), 852 (PID Prop Gain), 853 (PID Int Gain), and 859 (PID Derivative Gain). The “feed forward” options are suggested for setting parameter 850. More specific details on each of the listed parameters can be found in the X5 User’s Manual.
24-hour support 1-877-822-6606
X5OPT01 115 VAC / Encoder Interface Option Board vacon 9
The encoder interface can easily serve as one of the inputs to the X5’s Keeper Function (data logging). More information on this feature is in the X5 User’s Manual.
Both the Vmet and Imet output from the drive can be configured to indicate the status of the encoder. Parameters 700 (Vmet) and 702 (Imet) that relate to the setup and calibration of the Vmet and Imet outputs, both have selections related to the status of the encoder input.
The Program Sequencer function can also key off the encoder’s home pulse. To make use of this function, the encoder’s home pulse (1 pulse per revolution) must be connected to the C- input of the encoder board.

Troubleshooting

Any problem with the encoder interface will result in an F37 fault. Four advanced fault codes are available to help you determine whether you have an encoder calibration problem, or a defect. For more information on troubleshooting, refer to the Troubleshooting chapter in the X5 User’s Manual.
Email: usa@vacon.com • Fax 717-264-3115
head office and production:
Vaasa
Vacon Plc Runsorintie 7 65380 Vaasa firstname.lastname@vacon.com telephone: +358 (0)201 2121 fax: +358 (0)201 212 205
production:
Suzhou, China
Vacon Suzhou Drives Co. Ltd. Building 11A 428# Xinglong Street, SIP Suchun Industrial Square Suzhou 215126 telephone: + 86 512 62836630 fax: + 86 512 62836618
Naturno, Italy
Vacon S.R.I Via Zone Industriale, 11 39025 Naturno
sales companies and representative offices:
production:
Chambersburg, USA
3181 Black Gap Road Chambersburg, PA 17202
TB Wood's (India) Pvt. Ltd.
#27, 'E' Electronics City Hosur Road Bangalore - 560 100 India Tel. +91-80-30280123 Fax. +91-80-30280124
finland
Helsinki
Vacon Plc Äyritie 8 01510 Vantaa telephone: +358 (0)201 212 600 fax: +358 (0)201 212 699
Tampere
Vacon Plc Vehnämyllynkatu 18 33580 Tampere telephone: +358 (0)201 2121 fax: +358 (0)201 212 750
australia
Vacon Pacific Pty Ltd 5/66-74, Micro Circuit Dandenong South, VIC 3175 telephone: +61 (0)3 9238 9300 fax: +61 (0)3 92389310
austria
Vacon AT Antriebssysteme GmbH Aumühlweg 21 2544 Leobersdorf telephone: +43 2256 651 66 fax: +43 2256 651 66 66
belgium
Vacon Benelux NV/SA Interleuvenlaan 62 3001 Heverlee (Leuven) telephone: +32 (0)16 394 825 fax: +32 (0)16 394 827
brazil
Vacon Brazil Alameda Mamoré, 535 Alphaville - Barueri -SP Tel. +55 11 4166-5707 Fax. +55 11 4166-5567
canada
Vacon Canada 221 Griffith Road Stratford, Ontario N5A 6T3 telephone: +1 (519) 508-2323 fax: +1 (519) 508-2324
china
Vacon Suzhou Drives Co. Ltd. Beijing Branch A528, Grand Pacific Garden Mansion 8A Guanghua Road Beijing 100026 telephone: + 86 10 51280006 fax: +86 10 65813733
czech republic
Vacon s.r.o. Kodanska 1441/46 110 00 Prague 10 telephone: +420 234 063 250 fax: +420 234 063 251
france
Vacon France ZAC du Fresne 1 Rue Jacquard - BP72 91280 Saint Pierre du Perray CDIS telephone: +33 (0)1 69 89 60 30 fax: +33 (0)1 69 89 60 40
germany
Vacon GmbH Gladbecker Strasse 425 45329 Essen telephone: +49 (0)201 806 700 fax: +49 (0)201 806 7099
Vacon OEM Business Center GmbH Industriestr. 13 51709 - Marienheide Germany Tel. +49 02264 17-17 Fax. +49 02264 17-126
india
Vacon Drives & Control Plc Plot No 352 Kapaleeshwar Nagar East Coast Road Neelangarai Chennai-600041 Tel. +91 44 244 900 24/25
italy
Vacon S.p.A. Via F.lli Guerra, 35 42100 Reggio Emilia telephone: +39 0522 276811 fax: +39 0522 276890
the netherlands
Vacon Benelux BV Weide 40 4206 CJ Gorinchem telephone: +31 (0)183 642 970 fax: +31 (0)183 642 971
norway
Vacon AS Bentsrudveien 17 3080 Holmestrand telephone: +47 330 96120 fax: +47 330 96130
romania
Vacon Romania - Reprezentanta Cuza Voda 1 400107 Cluj Napoca Tel. +40 364 118 981 Fax. +40 364 118 981
russia
ZAO Vacon Drives Ul. Letchika Babushkina 1, Stroenie 3 129344 Moscow telephone: +7 (495) 363 19 85 fax: +7 (495) 363 19 86
ZAO Vacon Drives 2ya Sovetskaya 7, office 210A 191036 St. Petersburg telephone: +7 (812) 332 1114 fax: +7 (812) 279 9053
slovakia
Vacon s.r.o. (Branch) Seberiniho 1 821 03 Bratislava Tel. +421 243 330 202 Fax. +421 243 634 389
spain
Vacon Drives Ibérica S.A. Miquel Servet, 2. P.I. Bufalvent 08243 Manresa telephone: +34 93 877 45 06 fax: +34 93 877 00 09
sweden
Vacon AB Anderstorpsvägen 16 171 54 Solna telephone: +46 (0)8 293 055 fax: +46 (0)8 290 755
thailand
Vacon South East Asia 335/32 5th-6th floor Srinakarin Road, Prawet Bangkok 10250 Tel. +66 (0)2366 0768
ukraine
Vacon Drives Ukraine (Branch) 42-44 Shovkovychna Str. Regus City Horizon Tower Kiev 01601, Ukraine Tel. +380 44 459 0579 Fax +380 44 490 1200
united arab emirates
Vacon Middle East and Africa Block A, Office 4A 226 P.O.Box 54763 Dubai Airport Free Zone Dubai Tel. +971 (0)4 204 5200 Fax: +971 (0)4 204 5203
united kingdom
Vacon Drives (UK) Ltd. 18, Maizefield Hinckley Fields Industrial Estate Hinckley LE10 1YF Leicestershire telephone: +44 (0)1455 611 515 fax: +44 (0)1455 611 517
united states
Vacon, Inc. 3181, Black Gap Road Chambersburg, PA 17202 telephone: +1 (877) 822-6606 fax: +1 (717) 267-0140
Loading...