Danfoss X5EIP01 Installation guide

X5EIP01 Ethernet IP Option Board with
115 VAC Encoder Interface
Installation Manual
DPD00111
Need Help?
This manual answers most installation and startup questions
that may arise. However, if you have any problems,
please let your first call be to us.
Chambersburg, PA 17202
Normal business hours:
(North America)
8:00 AM to 5:00 PM, Eastern time
+1 877-Vacon06
(+1 877-822-6606)
After-hours support is also available
and Vacon, Inc. are trademarks of Vacon Plc, a member of Vacon Group.
All other product names are trademarks of their respective companies.
Copyright 2009, Vacon, Incorporated. All rights reserved.
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 3
Installing the X5EIP01 Ethernet IP Option Board with 115 VAC Encoder Interface

Introduction

The X5 frequency converters can be connected to Ethernet using an Ethernet IP option board, the X5EIP01.
Every device connected to an Ethernet network has two identifiers: a MAC address and an IP address. The MAC address (formatted as xx:xx:xx:xx:xx:xx, where xx is a hexadecimal byte) is unique to the device and cannot be changed. The Ethernet board’s MAC address can be found on the sticker attached to the board or by using various network configuration tools.
In a local network, IP addresses can be defined by a user as long as all units connected to the network are given the same network portion of the address. For more information about IP addresses, contact your Network Administrator. Overlapping IP addresses cause conflicts between devices.
The X5EIP01 also provides the option of controlling the X5 AC drive from 115 VAC control signals, or of connecting a shaft-mounted encoder to the drive to improve speed regulation. Up to five channels of 115 VAC control are available for use in selecting direction, preset speeds, or other drive functions.
With this option, an encoder with a nominal rating of up to 2048 pulses per revolution can be connected to the X5 unit to improve speed load regulation of the drive. Overall encoder frequency at maximum process speed must be limited to 100kHz.
This option also provides two additional control relays, each rated for 115 VAC, 1 amp, or for 230 VAC, 0.5 amp.
NOTE: This network communication interface included with the X5 option is warranted to meet the core specifications for Modbus TCP. Many existing software applications are custom-engineered and may contain “brand-specific” communication that will not be supported by the X5 without modification. No guarantee of compatibility with any specific system is made. The user is responsible for any interface software and hardware needed to make an application function.

Applicable Documents

This manual is supplied as a supplement to the X5 AC Drive User’s Manual (DPD 00089, previously Form 1434).

Option Kit Contents

The option kit includes the following materials:
Part Number Description
25100067C Ethernet IP Option Board
32100391 Flexible cable assembly

Installation Procedures

SENSITIVE EQUIPMENT
This assembly contains static-sensitive components. It should be handled only by a static-safe installer, using a grounded wrist strap.
Failure to observe this precaution may cause premature equipment failure.
Email: usa@vacon.com • Fax 717-264-3115
!
WARNING
4 vacon X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board
!
DANGER
HAZARDOUS VOLTAGE
• Disconnect all power before servicing a drive unit or its components. WAIT 5 MINUTES until the DC bus capacitors discharge.
• Ensure that any other power sources that may feed control logic have been disconnected.
DO NOT short across DC bus capacitors or touch unshielded components or terminal strip screw connections with voltage present.
• Install all covers before applying power or starting and stopping the drive.
• The user is responsible for conforming to all applicable code requirements with respect to grounding all equipment.
• Many parts in a drive, including printed circuit boards, operate at line voltage. DO NOT TOUCH. Use only electrically-insulated tools.
Before servicing any drive.
• Disconnect all power.
• Place a “DO NOT TURN ON” label on the drive disconnect.
• Lock the disconnect in the open position.
Failure to observe these precautions will cause shock or burn, resulting in severe personal injury or death.
Figure 1 shows the option board and the location of the terminals and the power supply selector.
Encoder / 115 VAC Interface
Control Relay Terminals
Encoder Interface Power
Supply Selector
Ethernet Connector
Module Status LED
Figure 1: Option Board Layout
24-hour support 1-877-822-6606
Network Status LED
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 5
Before you can install the option board, you must first remove the drive cover.
Figure 2 shows the locations of the cover screws. The torque range for the X5 Size 1 cover is 18-26 in/lbs.
Cover screw locations
Figure 2: Cover Assembly and Screw Locations
Cover screw locations
The option board is installed just above the control board in all configurations (a Size 1 unit is shown in Figure 3 for reference). The screws labeled “A” must be removed from the X5; those labeled “B” need only to be loosened to accept the board slot.
.
B
A
B
A
Figure 3: Option Mounting Locations
Once the board is in place, tighten the screws to a maximum of 26 in-lbs.
Email: usa@vacon.com • Fax 717-264-3115
6 vacon X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board
Next, install the flexible circuit to finish the interface to the control board. (Refer to Figure 4.) To install the flexible circuit, first remove the keypad frame (necessary in this size unit). The frame is attached with two screws in opposite corners; the screws thread into fasteners in the plastic assembly. After the flexible circuit is installed, replace these screws, limiting the installation torque to 12 in-lbs..
Figure 4: Flexible Circuit Interface to Control Board

115 VAC Interface / Relay / Encoder Interface Terminals

Figure 5: 115 VAC Interface / Encoder Terminals
The X5OPT01 option kit includes five 115 VAC inputs, two additional programmable relays, and an encoder interface. The details of the terminals on the board related to the 115 VAC interface and the encoder are shown in Table 1 on
page 7:
24-hour support 1-877-822-6606
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 7

Table 1: Encoder Interface Terminals

Terminal Description
DI-A DI-B DI-C DI-D DI-E
ACn The neutral connection for the 115 VAC control inputs
NO3
RC3 NC3
NO4
RC4 NC4
A+ A-
B+ B-
C+ C-
VDC
Ecom Signal common for the encoder interface
115 VAC logic input; connect input to 115 VAC to activate. The programmable functionality of these inputs is controlled by
parameters 728, 729, 730, 731, and 732. Each of these inputs can be disabled or configured to emulate the function of the FWD, REV, R/J, EN, MOL, DI1, DI2, DI3, DI4, or DI5 input terminals on the X5 control board.
Refer to the X5 User’s Manual for more information (DPD 00089).
The third auxiliary relay. The function of this relay is set by parameter 709. Functionally, it is
capable of each of the features outlined in the X5 user manual under parameters 705-708.
Terminal NO3 is a normally-open contact; it closes when the relay activates. NC3 is a normally-closed contact; it opens when the relay activates. RC3 is the common terminal associated with both contacts.
The ratings of these contacts are 115 VAC, 1 amp; and 230 VAC, 0.5 amp.
The fourth auxiliary relay. The function of this relay is set by parameter 710. Functionally, it is
capable of each of the features outlined in the X5 user manual under parameters 705-708.
Terminal NO4 is a normally-open contact; it closes when the relay activates. NC4 is a normally-closed contact; it opens when the relay activates. RC4 is the common terminal associated with both contacts.
The ratings of these contacts are 115 VAC, 1 amp; and 230 VAC, 0.5 amp.
Channel A input from the encoder. Compatible with line driver, open collector, or totem pole outputs from an encoder. If it is an open collector or totem pole-type, encoder outputs are used; connect the A- terminal to Ecom.
Channel B input from the encoder. Compatible with line driver, open collector, or totem pole outputs from an encoder. If it is an open collector or totem pole-type, encoder outputs are used; connect the B- terminal to Ecom.
Channel C input from the encoder, the home pulse. Compatible with line driver, open collector, or totem pole outputs from an encoder. If it is an open collector or totem pole-type, encoder outputs are used; connect the C- terminal to Ecom.
Power supply terminal for use with a customer-supplied encoder. It can be either +12 VDC or +5 VDC based on the position of the encoder interface power supply selector shown in Figure 1. Voltage regulation: +/- 5%; maximum current available is 100 mA.
Note that the connections described in Table 1 work only when the encoder has an internal pull-up resistor on the open collector. Alternatively, it might be preferable to pull the + channel high, and attach the open collector to the ­channel. For example, if using Channel A, A+ on the option board would be tied to VDC, and A- would be connected to the open collector coming from the encoder. The advantage in this method is that no pull-up/down resistors are needed; if the encoder has an internal pull-up, this does not affect anything.
Email: usa@vacon.com • Fax 717-264-3115
8 vacon X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board

Specifications for Encoder / 115 VAC Interface

Encoder Interface 115 VAC Interface
Speed regulation < 0.1 Hz (1) On state 90-140 VAC
Input frequency (max.) 100 kHz Off state < 10 VAC
Input voltage 10-24 VDC +/- 5% Input frequency 58-62 Hz
Suggested pull-up
resistor
Terminal block wire
limitations
(1) PID feedback plus optimal motor turning in SLV mode employed
5 VDC 500 ohms
24 VDC 3.3k ohms
12-24 AWG
On/off delay 30 ms maximum12 VDC 1k ohms
Terminal block wire limitations
12-24 AWG

Setup and Use

The encoder interface is most effective if used in conjunction with the vector mode of operation. Refer to the X5 User’s Manual (Chapter 6) for information about using the vector mode. Three additional parameters are provided to calibrate the encoder:
Parameter # Parameter Name Range Default Value
219 Encoder Pulses per Revolution 0-16383 1024
220 Encoder Filter Time 10-1000 ms 20 ms
221 Encoder Speed Protection 0-20.0% 0%
Parameter 219, Encoder Pulses per Revolution, can either be extracted from the encoder nameplate or the data sheet supplied with it. Parameter 220, Encoder Filter Time, is used to filter the encoder signal in the event of noise. Parameter 221 is for limiting the response of the drive, in the event of the loss of encoder signal.
Two other parameters are provided to allow more flexibility in encoder selection, and to improve PID application usage:
Parameter # Parameter Name Range Default Value
Quadrature
223 EncoderType
224 Encoder Range 0-24000 rpm 0 rpm
or Single Channel
Quadrature
Parameter 223, Encoder Type, allows the use of either quadrature or single-channel types of encoders.
Parameter 224, Encoder Range, improves PID application flexibility. This parameter should be used in situations where the encoder feedback signal is not always directly proportional to the motor speed, for example, a winder using an encoder mounted on an idler pulley feeding a winding spool. The PID may be attempting to maintain a constant linear speed on the wound media, but as the diameter of the media on the spool changes, the motor turning the spool needs to vary its speed to maintain the linear speed at the idler pulley.
When parameter 224 is set to 0, it is ignored, and the PID calculates the feedback percentage based on parameter 301, Maximum Frequency. When this parameter is set to a non-zero value, the PID uses instead Parameter 224’s setting to calculate the feedback percentage.
Encoder feedback works similarly to an analog input as configured in parameters 850 (PID Configure), 851 (PID Feedback), 852 (PID Prop Gain), 853 (PID Int Gain), and 859 (PID Derivative Gain). The “feed forward” options are suggested for setting parameter 850. More specific details on each of the listed parameters can be found in the X5 User’s Manual (DPD 00089).
24-hour support 1-877-822-6606
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 9
The encoder interface can easily serve as one of the inputs to the X5’s Keeper Function (data logging). See the X5 User’s Manual for more information.
Both the Vmet and Imet output from the drive can be configured to indicate the status of the encoder. Parameters 700 (Vmet) and 702 (Imet) that relate to the setup and calibration of the Vmet and Imet outputs, both have selections related to the status of the encoder input.
The Program Sequencer function can also key off the encoder’s home pulse. To make use of this function, the encoder’s home pulse (1 pulse per revolution) must be connected to the C- input of the encoder board.

Encoder Interface Troubleshooting

Any problem with the encoder interface will result in an F37 fault. Four advanced fault codes are available to help you determine whether you have an encoder calibration problem, or a defect. For more information on troubleshooting, refer to the Troubleshooting chapter in the X5 User’s Manual.

Using Ethernet Connections

Following are the specifications for Modbus / TCP connections:

Table 2: Ethernet Connection Specifications

Connections Interface RJ-45 Connector
Transfer cable Foiled CAT5e
Communications
Speed 10 / 100 Mb
Duplex half/full
Default IP address 0.0.0.0
To communicate with the drive over Ethernet, the drive’s IP address must be set. This is done with parameters 922-
925. After setting the IP address, be sure to cycle power off and back on for the new address to take effect.

LED Indications

The Ethernet / IP Option Board includes two LED status indicators: Network Status and Module Status. See Figure
1 on page 4 for the location of these LEDs on the board. Network status provides information on the network
connection status and Module status provides information on the Ethernet / IP module itself. The following tables explain the meaning of the status LEDs:

Table 3: Network Status LED

Network Status
LED
Module Status
LED
If the LED is... This means...
OFF There is no power applied to the option board.
Red The option board cannot communicate on the network.

Table 4: Module Status LED

If the LED is... This means...
OFF There is no power applied to the option board.
Green The option board is operating normally.
The option board is in Standby state or the device needs
Green (flashing)
Red (flashing) The option board has detected a recoverable fault.
Red The option board has detected an unrecoverable fault.
commissioning because of a missing, incomplete, or incorrect configuration.
Email: usa@vacon.com • Fax 717-264-3115
10 vacon X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board

Getting Started

To begin communicating with the drive over Modbus / TCP, the drive’s IP address must be set (use parameters 922-
925). After setting the IP address, cycle power off and on for the new address to take effect.
For information on setting parameters, see the X5 User’s Manual.

I/O Messaging

Input / Output (I/O) polling messages are for time-critical, control-oriented data. The messages are transferred between the devices all the time and are used for continuous control of the frequency converter. They provide a dedicated, special-purpose communication path between a producing application (master) and one or more consuming applications (slaves). They are exchanged across single- or multi-cast connections and typically use high-priority identifiers.
The polling message flow is shown in Figure 6.
Data (Output Assembly)
Master
Data (Input Assembly)
Figure 6: Polling Message Diagram
Slave
X5
I/O messages 20, 21, 70, and 71 are standard Common Industrial Protocol (CIP) assemblies.
I/O messages 121, 122, 131, 132, 171, 172, 181, and 182 are vendor-specific messages that allow for customized assemblies.
The values of the following parameters indicate which drive parameters are read or written to by the I/O assembly:

Table 5: Parameter Assignments (Parameters 880-894)

Parameter # Parameter Name Range Default
880 FBus Read 1
881 FBus Read 2 104 (Output Current)
882 FBus Read 3 105 (Drive Load)
883 FBus Read 4 107 (Drive Temp)
884 FBus Read 5 909 (DI Status)
890 FBus Write 1
891 FBus Write 2 104 (Output Current)
892 FBus Write 3 105 (Drive Load)
893 FBus Write 4 107 (Drive Temp)
894 FBus Write 5 909 (DI Status)
0-65535
0-65535
103 (Output Voltage)
103 (Output Voltage)
Examples 1 and 2 on the following pages show how using the FBus Write 2 = Parameter 402 would allow the I/O assembly to set the drive’s acceleration rate.
24-hour support 1-877-822-6606
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 11
Example 1: Output Assemblies
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
20
21
121
122
131
132
0
1
2 Speed Reference (low byte)
3 Speed Reference (high byte)
0
1
2 Speed Reference (low byte)
3 Speed Reference (high byte)
0
1
2 Speed Reference (low byte)
3 Speed Reference (high byte)
4 FBus Write1 (low byte)
5 FBus Write1 (high byte)
6 FBus Write2 (low byte)
7 FBus Write2 (high byte)
0 FBus Write1 (low byte)
1 FBus Write1 (high byte)
2 FBus Write2 (low byte)
3 FBus Write2 (high byte)
0
1
2 Speed Reference (low byte)
3 Speed Reference (high byte)
4 FBus Write1 (low byte)
5 FBus Write1 (high byte)
6 FBus Write2 (low byte)
7 FBus Write2 (high byte)
8 FBus Write3 (low byte)
9 FBus Write3 (high byte)
10 FBus Write4 (low byte)
11 FBus Write4 (high byte)
12 FBus Write5 (low byte)
13 FBus Write5 (high byte)
0 FBus Write1 (low byte)
1 FBus Write1 (high byte)
2 FBus Write2 (low byte)
3 FBus Write2 (high byte)
4 FBus Write3 (low byte)
5 FBus Write3 (high byte)
6 FBus Write4 (low byte)
7 FBus Write4 (high byte)
8 FBus Write5 (low byte)
9 FBus Write5 (high byte)
NetRef NetCtrl Fault Reset Run Rev Run Fwd
NetRef NetCtrl Fault Reset Run Rev Run Fwd
NetRef NetCtrl Fault Reset Run Rev Run Fwd
Fault Reset Run Fwd
Email: usa@vacon.com • Fax 717-264-3115
12 vacon X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board
Example 2: Input Assemblies
Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
70
71
171
172
181
182
0
1
2 Speed Actual (low byte)
3 Speed Actual (high byte)
0 At Ref Ref from Net Ctrl from Net Ready Running 2 (Rev) Running 1 (Fwd) Warning Faulted
1Drive State
2 Speed Actual (low byte)
3 Speed Actual (high byte)
0 At Ref Ref from Net Ctrl from Net Ready Running 2 (Rev) Running 1 (Fwd) Warning Faulted
1Drive State
2 Speed Actual (low byte)
3 Speed Actual (high byte)
4FBus Read1 (low byte)
5FBus Read1 (high byte)
6FBus Read2 (low byte)
7FBus Read2 (high byte)
0FBus Read1 (low byte)
1FBus Read1 (high byte)
2FBus Read2 (low byte)
3FBus Read2 (high byte)
0 At Ref Ref from Net Ctrl from Net Ready Running 2 (Rev) Running 1 (Fwd) Warning Faulted
1Drive State
2 Speed Actual (low byte)
3 Speed Actual (high byte)
4FBus Read1 (low byte)
5FBus Read1 (high byte)
6FBus Read2 (low byte)
7FBus Read2 (high byte)
8FBus Read3 (low byte)
9FBus Read3 (high byte)
10 FBus Read4 (low byte)
11 FBus Read4 (high byte)
12 FBus Read5 (low byte)
13 FBus Read5 (high byte)
0FBus Read1 (low byte)
1FBus Read1 (high byte)
2FBus Read2 (low byte)
3FBus Read2 (high byte)
4FBus Read3 (low byte)
5FBus Read3 (high byte)
6FBus Read4 (low byte)
7FBus Read4 (high byte)
8FBus Read5 (low byte)
9FBus Read5 (high byte)
Running 1 (Fwd) Faulted
24-hour support 1-877-822-6606
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 13

Control Supervisor Behavior

The State Transition diagram in Figure 7 provides a graphical description of the states and corresponding state transitions for the control supervisor.
Figure 7: Control Supervisor State Transition Diagram
Table 6 on page 14 explains the state transitions pictured in the flow diagram in Figure 7.
Start Forward, Start Reverse, Change to Forward, Change to Reverse, and Stop (Not Faulted Stop) are static outputs of the control supervisor state machine. They are commands to the drive when CtrlFromNet = 1. When CtrlFromNet = 0, control commands are from another source.
When performing changes to achieve programmed Safe State:
Run / Stop / Direction can be changed because CtrlFromNet must equal 1 when in the Enabled state.
Reference in the drive can be changed to Preset Speed only if RefFromNet = 1.
Email: usa@vacon.com • Fax 717-264-3115
14 vacon X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board

Table 6: Explanation of State Transitions (Page 1 of 2)

Input Conditions Results
Old State
Run1 (Fwd)
CtrlFromNet
Idle Mode
Run 2 (Rev)
Rev Mode
Fwd Mode
Event New State Action
x x xxxxx Power_Off NonExist
x
x xxxxx Reset Startup
(except
NonExist)
Faulted = 0 Ready = 0
FwdMode = 0 RevMode = 0
Run1 Var = 0 Run2 Var = 0
Faulted = 0 Ready = 0
NonExist x xxxxx Power_On Startup
FwdMode = 0 RevMode = 0
Run1 Var = 0 Run2 Var = 0
Startup x xxxxx Drive Fault Faulted
Startup x xxxxx
Initialization
Complete
Ready Ready = 1
Faulted = 1 FaultCode = x
Faulted = 1
Ready x xxxxx Drive Fault Faulted
FaultCode = x Ready = 0
Ready 1 1 0 0 x x Run (Fwd) Enabled
Ready 1 0 1 0 x x Run (Rev) Enabled
FwdMode = 1 (Start Forward)
RevMode = 1 (Start Reverse)
Faulted = 1 FaultCode = x (Initiate Faulted
Enabled x xxxxx Drive Fault Fault_Stop
Stop)
FwdMode = 0 RevMode = 0 Ready = 0
Enabled 1 0 0 x x x Stop Stopping (Initiate Stop)
FwdMode = 1
Enabled 1 10001 ChangeDir (Fwd) Enabled
RevMode = 0 (Change to Forward)
FwdMode = 0
Enabled 1 01010 ChangeDir (Rev) Enabled
RevMode = 1 (Change to Reverse)
24-hour support 1-877-822-6606
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 15
Table 6: Explanation of State Transitions (Page 2 of 2)
Input Conditions Results
Old State
Run1 (Fwd)
CtrlFromNet
Enabled 1 x x x x x SafeFault Fault_Stop
Enabled 1 x x x x x SafeChange Enabled
Stopping x x x x x x Drive Fault Fault_Stop
Stopping 1 1 0 0 x x Run (Fwd) Enabled
Stopping 1 0 1 0 x x Run (Rev) Enabled
Stopping x 0 0 x x x Stop_Complete Ready
Fault_Stopped x x x x x x Fault_Stop_ Complete Faulted
Faulted x x x x x x Fault_Reset Ready
Idle Mode
Run 2 (Rev)
Rev Mode
Fwd Mode
Event New State Action
Faulted = 1 FaultCode = x (Initiate Faulted
Stop)
FwdMode = 0 RevMode = 0 Ready = 0
Run1 Var = 0 Run2 Var = 0
FwdMode = Run1 Var = NOT PresetDir
RevMode = 0 Run2 Var = PresetDir
SpeedRef = Preset Speed
TorqueRef = Preset Torque
Faulted = 1 FaultCode = x (Initiate Faulted
Stop)
Ready = 0
FwdMode = 1 (Start Forward)
RevMode = 1 (Start Reverse)
Faulted = 0 Ready = 1

Explicit Messaging

Explicit Messaging is used in commissioning and configuring the Ethernet / IP board. Explicit messages provide multipurpose, point-to-point communication paths between two devices. They provide the typical request / response-oriented network communication used to perform node configuration and problem diagnosis. Explicit messages typically use low-priority identifiers and contain the specific meaning of the message right in the data field. This includes the service to be performed and the specific object attribute address.
Email: usa@vacon.com • Fax 717-264-3115
16 vacon X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board

List of Object Classes

The Communication Interface supports the following object classes:

Table 7: Object Classes

Class Object
0x28 Motor Data
0x29 Control Supervisor
0x2A AC/DC Drive
0x2B Acknowledge Handler
0x65 Parameter

List of Data Types

The attribute list in Table 8 includes information on the data type of each attribute. See Table 10 on page 18 through
Table 13 on page 21 for more detailed explanations of the Data, Structure, and Array Type codes used in the Data
Type column.

Table 8: Data Types

Data Type Name Data Type Code Data Type Description
WORD 1 16-bit word
UINT 2 16-bit unsigned integer
INT 3 16-bitsigned integer
BOOL 4Boolean
SINT 5Short integer
DINT 6Double integer
LINT 7Long integer
USINT 8 Unsigned short integer
UDINT 9 Unsigned double integer
ULINT 10 Unsigned long integer
REAL 11 Single floating-point format (IEEE 754)
LREAL 12 Double floating-point format (IEEE 754)
ITIME 13 Duration (short)
TIME 14 Duration
FTIME 15 Duration (high resolution)
LTIME 16 Duration (long)
DATE 17 Date (see Ethernet/IP spec)
TIME_OF_DAY 18 Time of day
DATE_AND_TIME 19 Date and time
STRING 20 8-bit-per-character string
STRING2 21 16-bit-per-character string
STRINGN 22 N-bytes-per-character string
SHORT_STRING 23 Short N-byte character string
BYTE 24 8-bit string
DWORD 25 32-bit string
LWORD 26 64-bit string
24-hour support 1-877-822-6606
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 17

Ethernet Troubleshooting

Following are the advanced fault codes for the drive fault (F38) related to the option board. For more information, see the X5 User’s Manual (Chapter 8). The option board status LEDs are described on page 9 of this manual.

Table 9: Advanced Fault Codes

Advanced
Fault Code
1 Option board loss
2 Unstable ID during power-up Option board hardware issues
3 Option board changed
4 Invalid ID Option board hardware issues
5
6 Option board software error Option board software issues
7 Option board removed
Wrong or no daughter card installed
Fault Possible Cause Corrective Measures
Option board is disconnected or damaged
Option board was changed during last power-down
Option DIMM module issues
Option board was removed during last power-down sequence
Check option board status LEDs, ribbon cable connection, and cycle power. Replace option board if necessary.
Cycle power. If problem persists, contact Vacon technical support.
If the change was intentional, cycle power.
Cycle power. If problem persists, contact Vacon technical support.
Cycle power. If problem persists, contact Vacon technical support.
Cycle power. If problem persists, contact Vacon technical support.
If the change was intentional, cycle power. Otherwise, follow corrective measures for fault code 1.
Email: usa@vacon.com • Fax 717-264-3115
18 vacon X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board

Appendix: X5 Communication Interface Object Profiles

In the following tables, attributes shown in bold face are stored in the non-volatile part of the drive and maintain their values after a power loss. All other settable attributes will power up at their default values.
Table 10: Motor Data Object
(Class Code 0x28, Motor Data Class (40) - Instance Attributes (1)
Default,
# Attribute Name Services
6
0x06
7
0x07
9
0x09
12
0x0C
15
0x0F
RatedCurrent[100mA]
RatedVoltage[V]
RatedFrequency[Hz]
PoleCount Get_Attribute_Single
BaseSpeed[RPM]
Get_Attribute_Single Set_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
Minimum, Maximum
(1)
360
0
65535
230 100 690
60
0
400
2 2
16
1760
1
24000
Data Type
2
2
2
2 Number of poles in the motor
2
Rated Electrical Frequency
Description
Rated Stator Current
Units: [100mA]
Rated Base Voltage
Units: [V]
Units: [Hz}
Nominal speed at rated
frequency from nameplate
Units: [RPM]
(1) The default value shown in this column is model-dependent.
24-hour support 1-877-822-6606
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 19
Table 11: Control Supervisor Object
(Class Code 0x29, Control Supervisor Class (41) - Instance Attributes (1)
# Attribute Name Services
3
0x03
4
0x04
5
0x05
6
0x06
7
0x07
8
0x08
9
0x09
10
0x0A
12
0x0C
13
0x0D
15
0x0F
Run1
Run2
NetCtrl
State Get_Attribute_Single
Running1 Get_Attribute_Single
Running2 Get_Attribute_Single
Ready Get_Attribute_Single
Faulted Get_Attribute_Single
FaultRst
FaultCode Get_Attribute_Single
CtrlFromNet Get_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
Default, Minimum, Maximum
0 0 1
0 0 1
0 0 1
N/A
0 7
N/A
0 1
N/A
0 1
N/A
0 1
N/A
0 1
0 0 1
N/A
0
65535
N/A
0 1
Data Type
Description
4 Run Forward Request
4 Run Reverse Request
4
Requests Run/Stop control to be
local or from network
State of Control Supervisor Instance:
1 = Startup
2 = Not_Ready
8
3 = Ready
4 = Enabled
5 = Stopping
6 = Fault_Stop
7 = Faulted
Running Forward Status:
4
0 = Other state
1 = Running Forward
Running Reverse Status:
4
0 = Other state
1 = Running Reverse
Ready to Accept a Run Event:
4
0 = Other state
1 = Ready to accept a Run event
Fault Occurred:
4
0 = No faults present
1 = Fault occurred (latched)
Fault Reset Request:
4
0 = No action
0 -> 1 = Fault reset request
1 = No action
If in faulted state, FaultCode
indicates the fault that caused the
2
transition to be in a faulted state. The fault codes are listed in the Ethernet/
IP specifications
Status of Run / Stop control source:
4
0 = Control is local
1 = Control is from the network
Email: usa@vacon.com • Fax 717-264-3115
20 vacon X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board
Table 12: AC/DC Drive Object
(Class Code 0x2A, AC/DC Drive Class (42) - Instance Attributes (1)
# Attribute Name Services
3
0x03
4
0x04
6
0x06
7
0x07
8
0x08
9
0x09
17
0x11
18
0x12
19
0x13
20
0x14
21
0x15
29
0x1D
AtReference Get_Attribute_Single
NetRef
Get_Attribute_Single Set_Attribute_Single
DriveMode Get_Attribute_Single
SpeedActual(RPM) Get_Attribute_Single
SpeedRef[RPM}
Get_Attribute_Single Set_Attribute_Single
CurrentActual[100mA) Get_Attribute_Single
OutputVoltage[V] Get_Attribute_Single
AccelTime[100ms]
DecelTime[100 ms]
LowSpdLimit[RPM]
HighSpdLimit[RPM]
Get_Attribute_Single Set_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
Get_Attribute_Single Set_Attribute_Single
RefFromNet Get_Attribute_Single
Default, Minimum, Maximum
N/A
0 1
0 0 1
1 1 1
N/A
0
10000
1800
0
12000
N/A
0
1000
N/A
0
690
30
1
32000
30
1
32000
0 0
12000
1800
0
12000
N/A
0 1
Data Type
Description
4 1 = Drive actual at speed reference
Requests speed reference to be local
or from the network:
0 = Set Reference to local control
4
1 = Set Reference to DN control
Note that the actual status of torque
or speed reference is reflected in
attribute 29, RefFromNet.
8 1 = Open loop speed (Frequency)
Actual drive speed (best
3
approximation)
Units: RPM
3
3
3
Speed reference
Units: RPM
Actual motor phase current
Units: 100mA
Output Voltage
Units: Volts
Acceleration time
2
Time from 0 to HighSpdLimit
Units: 100ms
Deceleration time
2
Time from HighSpdLimit to 0
Units: 100ms
2
2
Minimum speed limit
Units: RPM
Maximum speed limit
Units: RPM
Status of speed reference:
4
0 = Local speed reference
1 = Ethernet / IP speed reference
24-hour support 1-877-822-6606
X5EIP01 Ethernet IP with 115 VAC / Encoder Interface Option Board vacon 21
Table 13: Parameter Object
(Class Code 0x65, Parameter Class (101) - Class Attributes (1-999)
# Attribute Name Services
1
0x01
N/A
Get_Attribute_Single Set_Attribute_Single
Default, Minimum, Maximum
N/A N/A N/A
Data Type
2
Description
These instances give direct access to
all drive parameters where the
instance number corresponds to the
parameter number. See the X5 User’s Manual (Ch. 7) for more
information on specific drive
parameters.
Email: usa@vacon.com • Fax 717-264-3115
head office and production:
Vaasa
Vacon Plc Runsorintie 7 65380 Vaasa firstname.lastname@vacon.com telephone: +358 (0)201 2121 fax: +358 (0)201 212 205
production:
Suzhou, China
Vacon Suzhou Drives Co. Ltd. Building 11A 428# Xinglong Street, SIP Suchun Industrial Square Suzhou 215126 telephone: + 86 512 62836630 fax: + 86 512 62836618
Naturno, Italy
Vacon S.R.I Via Zone Industriale, 11 39025 Naturno
sales companies and representative offices:
production:
Chambersburg, USA
3181 Black Gap Road Chambersburg, PA 17202
TB Wood's (India) Pvt. Ltd.
#27, 'E' Electronics City Hosur Road Bangalore - 560 100 India Tel. +91-80-30280123 Fax. +91-80-30280124
finland
Helsinki
Vacon Plc Äyritie 8 01510 Vantaa telephone: +358 (0)201 212 600 fax: +358 (0)201 212 699
Tampere
Vacon Plc Vehnämyllynkatu 18 33580 Tampere telephone: +358 (0)201 2121 fax: +358 (0)201 212 750
australia
Vacon Pacific Pty Ltd 5/66-74, Micro Circuit Dandenong South, VIC 3175 telephone: +61 (0)3 9238 9300 fax: +61 (0)3 92389310
austria
Vacon AT Antriebssysteme GmbH Aumühlweg 21 2544 Leobersdorf telephone: +43 2256 651 66 fax: +43 2256 651 66 66
belgium
Vacon Benelux NV/SA Interleuvenlaan 62 3001 Heverlee (Leuven) telephone: +32 (0)16 394 825 fax: +32 (0)16 394 827
brazil
Vacon Brazil Alameda Mamoré, 535 Alphaville - Barueri -SP Tel. +55 11 4166-5707 Fax. +55 11 4166-5567
canada
Vacon Canada 221 Griffith Road Stratford, Ontario N5A 6T3 telephone: +1 (519) 508-2323 fax: +1 (519) 508-2324
china
Vacon Suzhou Drives Co. Ltd. Beijing Branch A528, Grand Pacific Garden Mansion 8A Guanghua Road Beijing 100026 telephone: + 86 10 51280006 fax: +86 10 65813733
czech republic
Vacon s.r.o. Kodanska 1441/46 110 00 Prague 10 telephone: +420 234 063 250 fax: +420 234 063 251
france
Vacon France ZAC du Fresne 1 Rue Jacquard - BP72 91280 Saint Pierre du Perray CDIS telephone: +33 (0)1 69 89 60 30 fax: +33 (0)1 69 89 60 40
germany
Vacon GmbH Gladbecker Strasse 425 45329 Essen telephone: +49 (0)201 806 700 fax: +49 (0)201 806 7099
Vacon OEM Business Center GmbH Industriestr. 13 51709 - Marienheide Germany Tel. +49 02264 17-17 Fax. +49 02264 17-126
india
Vacon Drives & Control Plc Plot No 352 Kapaleeshwar Nagar East Coast Road Neelangarai Chennai-600041 Tel. +91 44 244 900 24/25
italy
Vacon S.p.A. Via F.lli Guerra, 35 42100 Reggio Emilia telephone: +39 0522 276811 fax: +39 0522 276890
the netherlands
Vacon Benelux BV Weide 40 4206 CJ Gorinchem telephone: +31 (0)183 642 970 fax: +31 (0)183 642 971
norway
Vacon AS Bentsrudveien 17 3080 Holmestrand telephone: +47 330 96120 fax: +47 330 96130
romania
Vacon Romania - Reprezentanta Cuza Voda 1 400107 Cluj Napoca Tel. +40 364 118 981 Fax. +40 364 118 981
russia
ZAO Vacon Drives Ul. Letchika Babushkina 1, Stroenie 3 129344 Moscow telephone: +7 (495) 363 19 85 fax: +7 (495) 363 19 86
ZAO Vacon Drives 2ya Sovetskaya 7, office 210A 191036 St. Petersburg telephone: +7 (812) 332 1114 fax: +7 (812) 279 9053
slovakia
Vacon s.r.o. (Branch) Seberiniho 1 821 03 Bratislava Tel. +421 243 330 202 Fax. +421 243 634 389
spain
Vacon Drives Ibérica S.A. Miquel Servet, 2. P.I. Bufalvent 08243 Manresa telephone: +34 93 877 45 06 fax: +34 93 877 00 09
sweden
Vacon AB Anderstorpsvägen 16 171 54 Solna telephone: +46 (0)8 293 055 fax: +46 (0)8 290 755
thailand
Vacon South East Asia 335/32 5th-6th floor Srinakarin Road, Prawet Bangkok 10250 Tel. +66 (0)2366 0768
ukraine
Vacon Drives Ukraine (Branch) 42-44 Shovkovychna Str. Regus City Horizon Tower Kiev 01601, Ukraine Tel. +380 44 459 0579 Fax +380 44 490 1200
united arab emirates
Vacon Middle East and Africa Block A, Office 4A 226 P.O.Box 54763 Dubai Airport Free Zone Dubai Tel. +971 (0)4 204 5200 Fax: +971 (0)4 204 5203
united kingdom
Vacon Drives (UK) Ltd. 18, Maizefield Hinckley Fields Industrial Estate Hinckley LE10 1YF Leicestershire telephone: +44 (0)1455 611 515 fax: +44 (0)1455 611 517
united states
Vacon, Inc. 3181, Black Gap Road Chambersburg, PA 17202 telephone: +1 (877) 822-6606 fax: +1 (717) 267-0140
Loading...