Danfoss VMTD-MIX-IE Fact sheet

Fact sheet
Termix VMTD-MIX-IE
Direct heating substation for direct heating with mixing loop and instantaneous domestic hot water with flow compensated temperature controller.
Application
The Termix VMTD MIX - IE is a complete solu­tion with built - in water heater and heating system with dierential pressure control and mixing loop. The Termix VMTD MIX - IE is ap­plicable for single - family houses and for de­centralized systems in multi - family houses.
The substation is prefabricated with adier­ential pressure controller, tting piece and sensor pockets for insertion of a heat meter as well as strainer and ball valves. Furthermore the substation is delivered with a weather compensated mixing loop including pump, controls and non - return valve.
Heating (HE)
The heating circuit is designed for direct con­nection. The weather compensated mixing loop creates a suitable temperature level e.g. for underoor heating and ensures opti­mum control and monitoring of the heating system. Regardless of the weather outside, the heating system is continuously adjusted according the the selected parameters, thus preventing overconsumption.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and the temperature is regu­lated with a thermostatic and ow-compen­sated controller with integrated dierential pressure controller. The heat exchanger oers superb heat extraction of the DH water, there­by creating an excellent operating economy. The Danfoss IHPT valve insures a stable hot water temperature by varying loads, supply temperatures and by high and varying dier­ential pressure without the need for readjust­ing the valve. This protec ts the heat exchanger against overheating and lime scale formation. Furthermore the IHPT valve has an integrated idle temperature controller, which keeps the house supply line warm. This shortens the waiting periods during summer when the heating system is in reduced operation, which is ideal where high comfort is requested.
Options
The substation can be supplied with a built­in non - return valve and safety valve tted in the cold water supply.
Insulation
The Termix VMTD MIX-IE comes complete with a fully insulated cover thus minimizing heat loss both during tapping of domestic hot water but also when only space heating is required.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The Termix VMTD MIX - IE can be delivered with white - lacquered steel cover in mod­ern design.
FEATURES AND BENEFITS
• Substation for DH and decentralized systems
• Direct heating with dierential pressure controller
• DHW thermostatic and ow compensated temperature controller
• Capacity: 33 – 59 kW for DHW
• DHW in sucient quantity
• Operates independently of dierential pressure and ow temperature
• Minimum space required for installation
• Pipes and plate heat exchanger made of stainless steel
• Minimized risk of lime scale and bacteria formation
• Complete insulation ensures minimal heat loss
www.danfoss.com
CIRCUIT DIAGRAM - EXAMPLE
DHW
DCW
DH
Supply
B Heat exchanger DHW F Electronic controller 1 Ball valve 2 Non-return valve 9 Strainer 10 Circulator pump 14 Sensor pocket, heat meter 16 Outdoor sensor 18 Thermometer 19 Surface sensor 27 Actuator 29 2-way motorized valve 31 Dierential pressure
controller 39 Connection closed 41 Fitting piece, energy meter 63 Sieve 74 IHPT
HE Supply
DH
Return
Technical parameters:
Nominal pressure: PN 10 DH supply temperature: T DCW static pressure: P Brazing material (HEX): Copper
= 110 °C
max
= 1,0 bar
min
Weight incl. cover: 25 kg Cover: White-lacquered
steel sheet
Insulation: EPP λ 0.039 Insulation cover: Anthracite grey EPP Dimensions (mm):
Without cover: H 800 × W 530 × D 375 With cover: H 800 × W 540 × D 430
DHW: CAPACITY EXAMPLES
Substation type
VMTD MIX - IE-1
VMTD MIX - I E- 2
DHW capacity
[ kW ]
32,3 60 19,8 10 / 45 23 13,3 40,3 60 20,7 10 / 45 33 16,6 36,5 70 19,1 10 / 50 20 13,2
55 70 21,5 10 / 50 39 19,8
32,3 55 21,9 10 / 45 26 13,3
38 55 22,2 10 / 45 34 15,7
32,3 60 19,6 10 / 45 20 13,3
47 60 19,6 10 / 45 34 19,4
39,5 70 19,0 10 / 50 20 14,3
59 70 19,2 10 / 50 34 21,3
Supply flow
primary
[ °C ]
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Heating (HE) supply
4. Heating (HE) return
5. Domestic hot water (DHW)
6. Domestic cold water (DCW)
Return flow
primary
[ °C ]
DHW
[ °C ]
wall
HE Return
Connections sizes:
DH + HE: G ¾“ (int. thread) DCW + DHW: G ¾“ (int. thread)
Options:
• White - lacquered steel cover
• Safety valve and non - return valve (10 bar)
• Pressure equalizer GTU
Pressure loss
primary
[ kPa ]
DHW tap load
[ l / min]
Gemina Termix A/S · Member of the Danfoss Group · Navervej 15-17 · DK-7451 Sunds · Denmark Tel.: +45 9714 1444 · Fax: +45 9714 1159 · mail@termix.dk · www.heating.danfoss.com
© Danfoss | DHS-SRMT/ PL | 2016 . 09
VL.JV.Z2.02
Loading...