Danfoss VMTD-F MIX-I Operating guide

Page 1
OperatingGuide
TermixVMTD-FMIX-I

1.0TableofContents

1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotes–general............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.3Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
6.0Controls..........................................................10
6.1Heatingcircuit......................................................10
6.2DHWtemperaturecontrol........................................13
6.3Other.................................................................14
6.4Extras................................................................16
6.5Maintenance........................................................17
7.0Troubleshooting..............................................18
7.1Troubleshootingingeneral......................................18
7.2TroubleshootingDHW............................................19
7.3TroubleshootingHE...............................................20
7.4Disposal.............................................................22
8.0Declaration......................................................23
8.1Declarationofconformity........................................23
©Danfoss|2019.05VI.GP .W5.02/LUK40250|1
Page 2
OperatingGuideTermixVMTD-FMIX-I

2.0Functionaldescription

Districtheatingsubstationfordirectheatingand instantaneousdomestichotwaterwiththermostaticcontrol. Designedforwall-mounting.
Application
TheT ermixVMTD-FMIX-Iisacompletesolutionwithbuilt-in waterheaterandheatingsystemwithdifferentialpressurecontrol andmixingloop.TheTermixVMTD-FMIX-Iisapplicableforfor single-familyhousesandfordecentralizedsystemsinmulti-family houses.
Districtheating(DH)
Thesubstationisprefabricatedwithadifferentialpressure controller,fittingpieceandsensorpocketforinsertionofa heatmeteraswellasstrainerandballvalves.Furthermorethe substationisdeliveredwithamixingloopincludingpump,controls andnon-returnvalve.
Heating(HE)
Theheatingcircuitisdesignedfordirectconnection.The differentialpressurecontrollersetstheoptimumoperation conditionsforradiatorthermostatsinordertoenableindividual temperaturecontrolineachroom.Themixingloopcreatesa suitabletemperaturelevele.g.forfloorheating.Inordertoenable atimedependenttemperaturecontrolprogram,azonevalvewith actuatorandaroomthermostatcanbeincludedasanoption.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerand theheatexchangerandthetemperatureisregulatedwithaflow compensatedtemperaturecontrollerwithintegrateddifferential pressurecontroller.TheheatexchangercoolsouttheDHwater veryefficiently,therebycreatinganexcellentoperatingeconomy. TheDanfossIHPTvalveensuresastablehotwatertemperature byvaryingloads,supplytemperaturesandbyhighandvarying differentialpressurewithouttheneedforreadjustingthevalve. Thisprotectstheheatexchangeragainstoverheatingandlime scaleformation.FurthermoretheIHPTvalvehasanintegrated idletemperaturecontroller,whichkeepsthehousesupplyline warm.Thisshortensthewaitingperiodsduringsummerwhen theheatingsystemisinreducedoperation,whichisidealwhere highcomfortisrequested.
2|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 3
OperatingGuideTermixVMTD-FMIX-I

3.0Safetynotes

3.1SafetyNotes–general

Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheflowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis 110°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16 versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH. OneoftheobligationsinREACHistoinformcustomersabout presenceofCandidatelistsubstancesifany,weherebyinform youaboutonesubstanceonthecandidatelist:Theproduct containsbrasspartswhichcontainslead(CASno:7439-92-1)ina concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|3
Page 4
OperatingGuideTermixVMTD-FMIX-I

4.0Mounting

4.1Mounting

Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.Optionalhotwatercirculation(HWC)
2.Districtheating(DH)supply
3.Districtheating(DH)return
4.Coldwatermains(CWM)
5.Domesticcoldwater(DCW)
6.Domestichotwater(DHW)
7.Heating(HE)supply
8.Heating(HE)return
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
Connectionsizes:
DH+HE: CWM+DCW+DHW:
Dimensions(mm):
Withoutcover: H770xW535xD150 Withcover: H800xW540xD242
Weight(approx.):25kg
G¾”(int.thread) G¾”(int.thread)
4|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 5
OperatingGuideTermixVMTD-FMIX-I
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes andlabelsareplacedcorrectly.Ifyouwishtomountthestation differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe cleanedandrinsed.
Keyholeformounting.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha plug.Shouldtheplugsrequireremoval,thismustonlybedoneby anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording toschematicdiagram.Pleasenotethatthestrainermaybe suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe madeusingthreaded,flangedorweldedconnections.
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|5
Page 6
OperatingGuideTermixVMTD-FMIX-I

4.2Start-up

Start-up,Heatingwithmixingloop
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved asitentersservice.Visualcheckingshouldconfirmtemperatures, pressures,acceptablethermalexpansionandabsenceofleakage. Ifthesystemoperatesinaccordancewithdesign,itcanbeput toregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand electricityconsumption. Normallythechange-overswitchissetinthemidposition(default). Howeverforsystemswithunderfloorheatingorsinglepipeloop systems,itmaybenecessarytoturnthechange-overswitch upwards. Higherpumpspeedsareonlyusediftheheatingrequirement increases.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemfill.
Underfloorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderfloorheating,the circulationpumpmustbeconnectedtothepumpstopfunctionin theunderfloorheatingcontroller.Thepumpmustbestoppedif allunderfloorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenflowmustbecontinuedthroughthe by-pass.Failingthis,thepumpwillbeatriskofseizureandany remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes) onceamonthduringsummer;theshut-offvalveoftheHEsupply mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically (pleasenotemanufacturer´sinstructions).
6|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 7
OperatingGuideTermixVMTD-FMIX-I

4.3Electricalconnections

Beforemakingelectricalconnections,pleasenotethe following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording to60364-4-41:2007andIEC60364-5-54:2011. Bondingpointonthemountingplatebelowrightcornermarked withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto directsunlight.Theyshouldnotbeplacedclosetodoors,windows orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent regulationsandlocalstandards.
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|7
Page 8
OperatingGuideTermixVMTD-FMIX-I

5.0Design

5.1Design

Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
N
Circulationconnection
2
Singlecheckvalve
7
Thermostaticcontroller,HE
9
Strainer
10
Circulatorpump
8|©Danfoss|2019.05
14
Sensorpocket,energymeter
31
Differentialpressurecontroller
41A
Fittingpiece,coldwatermains 41BFittingpiece,energymeter 63
Sieve 74
IHPTcontroller,DHW
VI.GP .W5.02/LUK40250
Page 9
OperatingGuideTermixVMTD-FMIX-I

5.2Schematicdiagram

DHW
DCW
CWM
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
B
Heatexchanger,DHW
2
Singlecheckvalve
7
Thermostaticvalve
9
Strainer
DHW:DomesticHotWater DCW: CWM: DHSupply:DistrictHeatingSupply DHReturn:DistrictHeatingReturn HESupply:HeatingSupply HEReturn:HeatingReturn
DomesticColdWater ColdWaterMains
10
Circulatorpump
14
Sensorpocket,energymeter
18
Thermometer
31
Differentialpressurecontroller
39
Connectionclosed
41A
Fittingpiece,coldwatermains 41BFittingpiece,energymeter 63
Sieve 74
IHPTcontroller
HE Supply
HE Return
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:PN10(PN16versionsareavailableonenquiry) Max.DHsupplytemperature: Min.DCWstaticpressure: Brazingmaterial(HEX): Heatexchangerstestpressure:30bar Soundlevel:≤55dB
VI.GP .W5.02/LUK40250
110°C
1.0bar Copper
©Danfoss|2019.05|9
Page 10
OperatingGuideTermixVMTD-FMIX-I

6.0Controls

6.1Heatingcircuit

6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsoutthefluctuationsin pressurearrivingfromthedistrictheatingnetwork.Theoperating pressureinthesubstationisthusheldsteady.
6.1.2HEtemperaturecontrol
TheHEflowtemperatureintheheatingcircuitiscontrolledbythe HEtemperaturecontroller.
6.1.3RAVKcontroller
RAVKcontroller(25-65°C).Thetemperaturesettingisasfollows: 1=25°C 2=35°C 3=45°C 4=55°C 5=65°C
Thevaluesareintendedasaguide.
Thermostaticcontrol
ThetemperatureoftheHEflowlineisadjustedasfollows: Toincreasetemperature,turnthehandleonthethermostatic controllertoselectahighernumber. Todecreasetemperature,turnthehandleonthethermostatic controllertoselectalowernumber.
10|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 11
OperatingGuideTermixVMTD-FMIX-I
6.1.4TP7000
TP7000electronic7dayprogrammableroomthermostat. Signalsfromtheroomthermostatcanbeusedtocontrolzone valves.
6.1.5CirculatorpumpUPM3
UPM3Pumpscanbecontrolledinconstantpressure,proportional pressureorconstantspeedmodedefinedbythemeansofasmart userinterface. Thevariablespeedmodulatingmodesallowthepumptomatchits performancetothesystemrequirements,helpingtoreducenoise whenthermostaticvalvesareclosingdown. EnergylabellingclassA
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|11
Page 12
OperatingGuideTermixVMTD-FMIX-I
6.1.6GrundfosUPM3AUTOLinstructions
Controlmode
Youcanswitchfromtheperformanceviewtothesettingsviewbypressingthepushbutton.Thesettingsviewshowswhichmode controlsthecirculator.After2seconds,thedisplayswitchesbacktoperformanceview.
Ifyoupressthebuttonfor2to10seconds,theuserinterfaceswitchesto"settingselection"iftheuserinterfaceisunlocked.Youcan changethesettingsastheyappear.Theselectionofthecontrolmodedependsonthesystemtypeandtheallocationofpressurelosses.
Ifyoupressthekeylockformorethan10seconds,youcantogglebetweenenabling/disablingthekeylockfunction.
Function
Proportionalpressure1
Proportionalpressure2
Proportionalpressure3
Constantpressure1
Constantpressure2
Constantpressure3
ConstantCurve1
ConstantCurve2
ConstantCurve3
ConstantCurveMax.
Operationstatus
Function
Standby**OnlyPWMcontrolled
0%≤P1≤25%
25%≤P1≤50%
50%≤P1≤75%
75%≤P1≤100%
Recommendedfor
2-pipesystems
1-pipesystems
Underfloorheating
Green
Green
YellowYellowYellowYellow
YellowYellowYellowYellow
Alarmstatus
Function
Blocked
Supplyvoltagelow
Electricalerror
RedYellowYellowYellowYellow
12|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 13
OperatingGuideTermixVMTD-FMIX-I

6.2DHWtemperaturecontrol

DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin Danfosssubstations. DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides optimalutilisationofDHwater.AtDHWtemperaturesabove55°C, thepossibilityoflimescaledepositsincreasessignificantly.
6.2.1IHPT180controller(45–65°)
IHPTisaself-actingflow-compensatedtemperaturecontrollerwith integrateddifferentialpressurecontroller. TheIHPToperatesatitsbestatDHsupplytemperaturesofupto 100°C. Byturningthehandlefortemperaturesettingin(+)direction thesettingisincreased,byturningitin(-)directionthesettingis decreased.
Turns*
0
1
2
3
4
5
6
7
*Startposition:Handleturnedfullyin(+)direction. Thevaluesareintendedasaguide.
Scale
7
661
5
455
352
248
144
043
DHWT emperatureSetting[°C]
64
58
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|13
Page 14
OperatingGuideTermixVMTD-FMIX-I

6.3Other

6.3.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom excessivepressure. Theblow-offpipefromthesafetyvalvemustnotbeclosed.The blow-offpipeoutletshouldbeplacedsothatitdischargesfreely anditispossibletoobserveanydrippingfromthesafetyvalve. Itisrecommendedtochecktheoperationofsafetyvalvesat intervalsof6months.Thisisdonebyturningthevalveheadin directionindicated.
6.3.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The frequencyofcleaningwoulddependonoperatingconditionsand themanufacturer’sinstructions.
6.3.3GTUPressureEqualizer
TheGTUPressureEqualizerabsorbstheexpansiononthe secondarysideoftheTermixwaterheatersandcanbeusedasa substitutetothesafetyvalve. Furthermorethepressureequalizerabsorbsapossibleincreasein pressure,soadischargeoutletisomitted. TheGTUPressureEqualizermaynotbeappliedinsystemswithhot watercirculation.
14|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 15
OperatingGuideTermixVMTD-FMIX-I
6.3.4Fittingpiece
Thesubstationisequippedwithafittingpieceforenergymeter.
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater onthesystem.
2:Loosennuts
Loosenthenutsonthefittingpiece.
3:Removefittingpiece
Removethefittingpieceandreplaceitwiththeenergymeter.Do notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|15
Page 16
OperatingGuideTermixVMTD-FMIX-I

6.4Extras

6.4.1Circulationpipe
Thecirculationpipesetismounteddirectlyonthecontroller. Thesetincludescirculationpipe,singlecheckvalveandfitting. Whenmountingthehotwatercirculationdirectlyonthecontroller thehotwatercirculationtemperaturewillbeequaltotheidle temperature.Theidletemperatureisafewdegreeslowerthanthe setdomestichotwatertemperature.
16|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 17
OperatingGuideTermixVMTD-FMIX-I

6.5Maintenance

Thesubstationrequireslittlemonitoring,apartfromroutine checks.Itisrecommendedtoreadtheenergymeteratregular intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany enquiryincludesthesubstationserialnumber.
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|17
Page 18
OperatingGuideTermixVMTD-FMIX-I

7.0Troubleshooting

7.1Troubleshootingingeneral

Intheeventofoperatingdisturbances,thefollowingbasicfeatures shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel (summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal (local)differentialpressureintheDHnetwork–ifindoubt,ask theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
18|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 19
OperatingGuideTermixVMTD-FMIX-I

7.2TroubleshootingDHW

ProblemPossiblecauseSolution
ToolittleornoDHW.
Taptemperaturetoohigh;DHWtapload toohigh.
Temperaturedropduringtapping.
Thermostaticcontrolvalvedoesnotclose
Idletemperaturetoolow(forstations equippedwithIHPT).
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith toolowsetting.
Defectiveorcloggednon-returnvalve.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
Scalingoftheplateheatexchanger.
Defectivemotorizedvalve.Check(usemanualfunction)–replace.
Defectivetemperaturesensors.
Defectivecontroller.
DCWisbeingmixedwiththeDHW,e.g.ina defectivethermostaticmixingvalve.
Defectiveorcloggednon-returnvalveon circulationvalve.
Thermostaticvalveadjustedtoatoohigh level.
Scalingoftheplateheatexchanger.
LargerDHWflowthanthesubstationhas beendesignedfor.
TemperaturedifferencebetweenDH supplyandDHWsetpointtoolow.
Setpointtoolow.Turnthermostatin(+)direction.
Checkcirculationpump.
Replace–clean.
DHW,pls.noteenclosedinstructionsfor electroniccontroller.
Replace–rinseout.
Check–replace.
Check–replace.
Check–replace. Hotwaterinsometapsbutnotinall.
Replace–clean.
Check–set.
Replace–rinseout.
ReduceDHWflow.
Lowerthesetpointtemperatureorincrease theDHsupplytemperature.
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|19
Page 20
OperatingGuideTermixVMTD-FMIX-I

7.3TroubleshootingHE

ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DHsupplytemperaturetoohigh.
DHsupplytemperaturetoolow.
(radiatorcircuit).
ThefilterintheenergymeteronDHcircuit clogged.
Defectiveorwronglyadjusteddifferential pressurecontroller.
Sensordefective–orpossiblydirtinthe valvehousing.
Automaticcontrols,ifany,wronglysetor defective-possiblypowerfailure.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
Thepumpissetattoolowspeedof rotation.
Pressuredrop–thepressuredropon theradiatorcircuitshowslowerthan recommendedoperatingpressure.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperatureadjusted toolow.
Defectiveradiatorvalves.
Unevenheatdistributioninbuilding becauseofincorrectlysetbalancingvalves, orbecausetherearenobalancingvalves.
Diameterofpipetosubstationtoosmallor branchpipetoolong.
Wrongsettingofthermostatorof automaticcontrols,ifany.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Defectivesensoronself-actingthermostat.
Wrongsettingofautomaticcontrols,ifany.
Defectivecontroller.Thecontrollerdoes notreactasitshouldaccordingtothe instructions.
Defectivesensoronself-actingthermostat.
Wrongplacement/fittingofoutdoor temperaturesensor.
Strainerclogged.Cleangate/strainer.
Cleangate/strainer(s).
Cleanthefilter(afterconsultingtheDH plantoperator).
Checktheoperationofthedifferential pressurecontroller–cleanthevalveseatif required.
Checktheoperationofthethermostat– cleanthevalveseatifrequired.
Checkifthesettingofthecontroller iscorrect–seeseparateinstructions. Checkthepowersupply.Temporary settingofmotorto“manual”control–see instructionsonautomaticcontrols.
thatitturns.Checkifthereisairtrappedin thepumphousing–seepumpmanual.
Setthepumpathigherspeedofrotation.
Fillwateronthesystemandcheckthe functioningofthepressureexpansion vesselifrequired.
Adjustaccordingtoinstructions.
Check–replace.
Adjust/installbalancingvalves.
Checkpipedimensions.
Adjustautomaticcontrols,–see instructionsforautomaticcontrols.
Callautomaticcontrolsmanufactureror replacetheregulator.
Replacethermostat–orsensoronly.
Adjustautomaticcontrols–seeinstructions forautomaticcontrols.
Callinautomaticcontrolsmanufactureror replacecontroller.
Replacethermostat–orsensoronly.
Adjustlocationofoutdoortemperature sensor.
20|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 21
OperatingGuideTermixVMTD-FMIX-I
ToohighDHreturntemperature.
Noiseinsystem.
Heatloadtoohigh.
Toosmallheatingsurface/toosmall radiatorscomparedtothetotalheating requirementofthebuilding.
Poorutilizationofexistingheatingsurface. Defectivesensoronself-actingthermostat.
Thesystemissinglepipeloop.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Defectiveorincorrectlysetradiatorvalve(s). Singlepipeloopsystemsrequirespecial one-piperadiatorvalves.
Dirtinthemotorizedvalveorinthe differentialpressurecontroller.
Defectivemotorizedvalve,sensoror automaticcontroller.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Defectivemotorizedvalve,sensoror electroniccontroller.
Increasetotalheatingsurface.
Makesuretheheatisdistributedevenly acrossthefullheatingsurface–openall radiatorsandkeeptheradiatorsinthe systemfromheatingupatthebottom.It isextremelyimportanttokeepthesupply temperaturetotheradiatorsaslowas possible,whilemaintainingareasonable levelofcomfort.
Thesystemshouldfeatureelectronic controlsaswellasreturnsensors.
Ventthesystem.
Check–set/replace.
Check–cleanout.
Check–replace.
Check–replace.
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|21
Page 22
OperatingGuideTermixVMTD-FMIX-I

7.4Disposal

Disposal
Thisproductshouldbedismantledanditscomponents sorted,ifpossible,invariousgroupsbeforerecycling ordisposal.
Alwaysfollowthelocaldisposalregulations.
22|©Danfoss|2019.05
VI.GP .W5.02/LUK40250
Page 23
OperatingGuideTermixVMTD-FMIX-I

8.0Declaration

8.1Declarationofconformity

Category0withelectricalequipment
VI.GP .W5.02/LUK40250
©Danfoss|2019.05|23