Danfoss VMTD-F-I PTCII P Fact sheet

Fact sheet
Termix VMTD-F-I PTCII+P with complete insulation
Direct substation for flats and single family houses
Application
The Termix VMTD-F-I PTCII+P is a com­plete solution with a built-in water heat­er and a differential pressure controlled heating system. Termix VMTD-F-I PTCII+P is applicable for single family houses and for decentralized systems.
District heating (DH)
The substation is prefabricated with a dif­ferential pressure controller, a fitting piece and a sensor pocket for insertion of a heat meter as well as strainer and ball valves. The display of the heat meter is to be mounted next to the station.
Heating (HE)
The heating circuit is designed for direct generation of heat. The differential pres­sure controller sets the optimum opera­tion conditions for radiator thermostatic valves enabling individual temperature control in each room. In order to enable a time-depending temperature control program, a zone valve with actuator and a room thermostat can be included as an option.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and the temperature is reg­ulated with a flow-compensated tempera­ture controller with integrated differential pressure controller.
The DH water is cooled very efficiently by the heat exchanger, thereby creating an excellent operating economy. The Danfoss PTCII+P valve ensures a stable domestic hot water temperature by varying loads, var ying supply temperatures and by high and vary­ing differential pressure without the need for readjusting the valve. This protects the heat exchanger against overheating and lime scale formation. A separate thermostat­ic bypass enables tapping of hot water with­out any delay, – ensuring the best possible efficiency and economy.
Options
The Termix VMTD-F-I PTCII+P can be supplied with a connection for DHW cir­culation. DHW circulation pump can be ordered separately. (to be mounted un­derneath the station).
Construction
All pipes are made of stainless steel. The connections are made by nuts and gas­kets.
Insulation
The Termix VMTD-F-I PTCII+P comes complete with a fully insulated cover thus minimizing the heat loss both during tap­ping of domestic hot water but also when only space heating is required.
FEATURES AND BENEFITS
• Substation for DH and decentralized systems
• Direct heating with differential pressure controller
• DHW flow-compensated temperature controller
• Capacity: 33 – 61 kW for DHW
• DHW in sufficient quantity
• Operates independently of differential pressure and flow temperature
• Minimum space required for installation
• Pipes and plate heat exchanger made of stainless steel
• Minimized risk of lime scale and bacteria formation
• Optimum temperature regulation up to DH supply temperature 100 °C
• Low heat loss
www.danfoss.com
CIRCUIT DIAGRAM
DHW
DCW
CWM
B Heat exchanger 2 Single check valve 7A FJVR Return temperature limiter 9 Strainer 14 Sensor pocket, energy meter 31 Differential pressure controller 39 Connection closed 41A Fitting piece, Cold water mains ¾” × 80 mm 41B Fitting piece, energy meter ¾” × 110 mm 48 Air vent, manual 63 Sieve 69A On / Off valve without actuator 75 PTC2+P
DH
Supply
DH
Return
Technical parameters:
Nominal pressure: PN 10 DH supply temperature: Tmax = 120 °C DCW static pressure: Pmin = 1 bar Brazing material (HEX): Copper
Weight incl. insulation: 20 kg (incl. packing)
Insulation cover: Anthracite grey EPP
Dimensions (mm):
Without cover (including ball valves): H 745 × W 528 × D 110 mm With cover (mount on wall variant): H 800 × W 540 × D 242 mm With cover (built-in wall variant) H 915–980 × W 610 × D 150 (110) mm
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Cold water mains (CWM)
4. Domestic cold water (DCW)
5. Domestic hot water (DHW)
6. Heating (HE) supply
7. Heating (HE) return
Connections sizes:
DH + HE: G ¾” (int. thread) DCW + DHW: G ¾” (int. thread)
Options:
• Mounting rail with ball valves
• Room thermostat
• Actuator for zone valve
• Connection for hot water circulation
• Hot water circulation pump (mounted outside the unit)
• Ball valve set
DHW: CAPACITY EXAMPLES
Substation type
CAPACITY, WEIGHT AND DIMENSIONS
VMTD-F-I-1
VMTD-F-I-2
* Heat meter not incl.
DHW Capacity
[ kW ]
32,3 60 19 10 / 45 22 13,3 40,3 60 20 10 / 45 32 16,6 36,5 70 18 10 / 50 20 13,2
55 70 21 10 / 50 39 19,8
32,3 55 19 10 / 45 22 13,3
38 55 20 10 / 45 30 15,7
32,3 60 16 10 / 45 18 13,3
47 60 18 10 / 45 32 19,4
39,5 70 16 10 / 50 20 14,3
59 70 19 10 / 50 33 21,3
Supply flow
primary
[ °C ]
Return flow
primary
[ °C ]
DHW
[ °C ]
Pressure loss
primary
Gemina Termix A/S · Member of the Danfoss Group · Navervej 15-17 · DK-7451 Sunds · Denmark Tel.: +45 9714 1444 · Fax: +45 9714 1159 · mail@termix.dk · www.heating.danfoss.com
HE Supply
HE Return
[ kPa* ]
DHW
tap load
[ l/min ]
© Danfoss | DHS-SRMT/ PL | 2016 . 05