Danfoss VMTD-F-B Evo Fact sheet

Fact sheet
Termix VMTD-F-B Evo
Direct substation for flats, decentralized systems, single and multi-family houses
FEATURES AND BENEFITS
• Substation for DH and decentralized systems
• Direct heating and DHW temperature regulation with a thermostatic control valve
• Capacity: 33 – 85 kW for DHW
• DHW in sufficient quantity
• Operates independently of differential pressure and flow temperature
• Minimum space required for installation
• Pipes and plate heat exchanger made of stainless steel
• Minimized risk of lime scale and bacteria formation
Application
The Termix VMTD-F-B Evo is a com­plete solution with built-in water heater and a differential pressure controlled heating system. Ter­mix VMTD-F-B Evo is applicable for single and multi-family houses and for decentralized systems.
District heating (DH)
The substation is prefabricated with a differential pressure controller, a fitting piece and sensor pock­ets for insertion of a heat meter as well as strainer and ball valves.
Heating (HE)
The heating circuit is designed for di­rect generation of heat. The differential pressure control sets the optimum op­eration conditions the heating system; radiators, as well as under floor heat­ing distribution. To enable a time-de­pending temperature control program, the station is equipped with a zone valve; an actuator and a room ther­mostat can be included as an option.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and the tempera­ture is regulated with a thermostatic control valve. The patented sensor accelerator accelerates the closing of the Danfoss AVTB valve and protects the heat exchanger against over­heating and lime scale formation. The heat exchanger cools the DH water very efficiently, thereby creat­ing a very good operating economy. The sensor accelerator and AVTB valve also works as a bypass keeping the house supply line warm. This shortens the waiting periods during summer when the heating system is in reduced operation. The sensor accelerator helps to ensure a stable hot water temperature regardless of varying loads, flow temperatures and differential pressure without the need for readjusting the valve.
Options
The Termix VMTD-F-B Evo is also available with DHW circulation; including pump, built-in non-re­turn valves and safety valve. The station can also be supplied with a thermostatic circulation valve.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The Termix VMTD-F-B Evo can be delivered with white-lacquered steel cover for on-wall mounting or a recess box with door for in-wall mounting.
www.danfoss.com
CIRCUIT DIAGRAM - EXAMPLE
DHW
DCW
DCW
DH
Supply
DH
Return
Technical parameters:
Nominal pressure: PN 10 DH supply temperature: T DCW static pressure: P Brazing material (HEX): Copper
Weight incl. cover: 20 kg (incl. packing)
Cover options: - On-wall
- Built-in wall
Dimensions (mm):
Without cover: H 590 × W 530 × D 150 With cover (mount on wall variant): H 800 × W 540 × D 242 mm With cover (built-in wall variant): H 910 × W 610 × D 150 mm
41A
41B
14
9
14
= 120 °C
max
= 0.5 bar
min
B Heat exchanger DHW 7 Thermostatic valve 9 Strainer 14 Sensor pocket, heat meter 31 Differential pressure
controller 39 Connection closed 41A Fitting piece, Cold water
B
7
48
31
Connections:
1. Hot water circulation, optional (HWC)
2. Domestic cold water (DCW)
3. Domestic hot water (DHW)
4. Domestic cold water out (DCW)
5. District heating (DH) supply
6. District heating (DH) return
7. Heating (HE) supply
8. Heating (HE) return
1 2 3
25
99 65
65
9 69A
4 5 6
65
65
528
7 8
65 65
45
39
39
39
Connections sizes:
DH + HE: G ¾” (int. thread) DCW + DHW: G ¾” (int. thread)
Options:
• Mounting rail with ball valves
• White-lacquered steel cover (on-wall)
• Built-in wall cover
• Hot water circulation, incl. pump, non-return valves and safety valve (10 bar)
• Safety valve with thermostatic circulation set
• Thermostatic circulation set
• Pressure equalizer (GTU)
• Room thermostat
• Actuator for zone valve
• Return temperature limiter
• Thermometer
• Ball valves
mains ¾” × 110 mm 41B Fitting piece, heat meter
¾” × 110 mm 48 Air vent, manual 69A On / off valve, only valve
HE Supply
HE Return
CAPACITY, WEIGHT AND DIMENSIONS
CAPACITY, WEIGHT AND DIMENSIONS
Substation type
VMTD - F -B- 1
VMTD - F -B- 2
VMTD - F -B- 3
VMTD - F-B - 4
DHW capacity
[kW]
33 60 20 10 / 45 25 810 40 70 20 10 / 50 25 858 50 60 20 10 / 45 40 1228 58 70 20 10 / 50 40 1247 65 60 20 10 / 45 40 1597 75 70 20 10 / 50 40 1612 68 60 20 10 / 45 30 1653 85 70 20 10 / 50 30 1824
© Danfoss | DCS-SDGPT/ PL | 2021.09
Supply flow
primary
[°C]
Return flow
primary
[°C]
DCW / DHW
[°C]
Pressure loss
primary
[kPa]
AM235686478874en-010301
Flow rate
secondary
[l/h]