Danfoss VLZ028, VLZ044 Installation guide

Instructions
VLZ028-VLZ044 inverter compressors
VLZ028 - VLZ044 compressors can be
A
B
C D
A: Model number B: Serial Number C: Refrigerant D: Manufacturing year E: Supply voltage range F: max operating current G: Lubricant type and nominal charge H: Electronic frequency &
powered by the dedicated variable speed drive CDS803.
E
When Danfoss drive is selected, check carefully
F
for compatibility between compressor model and variable speed drive.
G
Compressor
model
H
VLZ028-035-044 7.5 kW
Variable speed drive
rated power output
Electrical connections
Quick connect spade terminals
Operating limits
70
60
50
40
30
20
Condensing Temperature ºC
10
0
-35
-30 -25 -20 -15 -10 -5 0510 15
VLZ R448/449A Operating Map
Condition:135ºC Max DLT
50-100rps
30-100rps
Evaporating Temperature ºC
RGT20 SH10K
push
push
VLZ R404A Operating Map
Condition:135ºC Max DLT
70
60
50
40
30
20
Condensing Temperature ºC
10
0
-35
-30 -25 -20 -15 -10 -5 0510 15
Evaporating Temperature ºC
50-100rps
30-100rps
push
RGT20 SH10K
All the above limits, temperatures and speeds, are secured by parameters in the drive and application controller softwares.
Installation and servicing of the compressor by qualied personnel only. Follow these instructions and sound refrigeration engineering practice relating to installation, commissioning, maintenance and service.
The compressor must only be used for its designed purpose(s) and within its scope of application (refer to «operating limits»). Consult Application guidelines and datasheet available from cc.danfoss.com
1 | © Danfoss | DCS (CC)| 2017.07
Never operate compressor without terminal box cover in place and secured.
Under all circumstances, the EN378 (or other applicable local safety regulation) requirements must be fullled. Wear protective goggles and work gloves.
The compressor must be handled with caution in the vertical position (maximum oset from the vertical : 15°).
The compressor is delivered under nitrogen gas pressure (between
0.3 and 0.4 bar / 4 and 6 psi). Do not disassemble bolts, plugs, ttings, etc... unless all pressure has been relieved from the compressor.
8510286P01B - FRCC.PI.039.A3.02
RELAY
2
CDS803
Instructions
Basic connections
- Depending on the frequency converter ver­sion, the physical position of individual con­nectors may dier from below diagram.
- Always make sure that the compressor termi-
nals T1, T2, T3 are connected to the frequency converter terminals 96, 97, 98 respectively.
- The compressor motor cable must be shielded
L1 91 L1 U 96 T1/U
L2 92 L2 V 97 T2/V
L3 93 L3 W 98 T3/W
95 PE PE 99
45 0/4-20 mA A OUT / DIG OUT
42 0/4-20 mA A OUT / DIG OUT
50 +10 V OUT NC
53 A IN NO 02
54 A IN COM 01
55 COM A IN/OUT
12 +24 V OUT COM 04
18 DIGI IN
19 DIGI IN
27 DIGI IN
29 DIGI IN
20 COM D IN
and the armoured part must be connected to ground on both cable ends; at the side of the compressor and at the side of the frequency con­verter.
- Use an EMC cable gland for cable installation and perfect grounding; The metallic terminal box of the compressor has a paint-free surface around
1
03
RELAY
NC 06
NO 05
N RS-485 69
P RS-485 68
Com RS-485 61
the connection hole for better conductivity.
- A low pressure safety switch is mandatory
to avoid compressor vacuum operation.
- At start-up, verify that the compressor rotates in the right direction and pumps.
Legends: Ana: Analogue Dig: Digital in: Input out: Output COM: Common NC: Normally-closed NO: Normally-open
91,92,93 3 phases mains input x x
95 Earth x x
42,45 0/4-20 mA Analague Output or Digital Output - -
50 +10V DC Output - ­53 0-10V or 4-20mA Analague Input x ­54 0-10V or 4-20mA Analague Input - x 55 Com Analague In/Out x ­12 +24V output - ­18 External On/O(NO) x x 19 Digital Input - ­27 Safety Device x x 29 Digital Input - ­20 Com Digital Input - ­98 To Compressor T3 x x 97 To Compressor T2 x x 96 To Compressor T1 x x
99 Earth x x 03,02,01 Relay 1 - ­06,05,04 Relay 2 - -
69,68 RS485 Bus - -
61 RS485 Bus Com - -
-: Optional connection X: Mandatory connection
2 | © Danfoss | DCS (CC) | 2017.07
Open loop Process loop
The CDS803 frequency converter is factory preset with parameters for the open loop control principle. The process loop control principle can be selected by changing parameters in the «Quick menu».
Open loop: preset on input 53 0 - 10 V control
Frequency converter in slave mode Process loop: preset on input 54 4 - 20 mA control
Frequency converter under own PID controller
8510286P01B - FRCC.PI.039.A3.02
Instructions
1 – Introduction
These instructions pertain to the VLZ028­VLZ044 variable scroll compressors used for air­conditioning and reversible heat pump systems in residential applications. They provide neces­sary information regarding safety and proper us­age of this product.
2 – Handling and storage
• Handle the compressor with care. Use the dedi­cated handles in the packaging. Use the com­pressor lifting lug and use appropriate and safe lifting equipment.
• Store and transport the compressor in an up­right position.
• Store the compressor between -35°C and 55°C / -31°F and 131°F.
• Don’t expose the compressor and the packag­ing to rain or corrosive atmosphere.
3 – Safety measures before assembly
Never use the compressor in a ammable at-
mosphere.
• The compressor ambient temperature may
not exceed 55°C during o-cycle.
• Mount the compressor on a horizontal at sur­face with less than 7° slope.
• When installing a compressor model VLZ, use equipment specically reserved for HFC refrig­erants, which was never used for CFC or HCFC refrigerants.
• Use clean and dehydrated refrigeration-grade copper tubes and silver alloy brazing material.
• Use clean and dehydrated system components.
• The piping connected to the compressor must be exible in 3 dimensions to dampen vibra­tions.
• The compressor must always be mounted using the rubber grommets supplied with the com­pressor.
4 – Assembly
• Slowly release the nitrogen holding charge through discharge and suction ports.
• Connect the compressor to the system as soon as possible to avoid oil contamination from ambient moisture.
• Avoid material entering into the system while cutting tubes. Never drill holes where burrs cannot be removed.
• Braze with great care using state-of-the-art technique and vent piping with nitrogen gas ow.
• Connect the required safety and control de­vices.
5 – Leak detection
Never pressurize the circuit with oxygen or
dry air. This could cause re or explosion.
• Do not use leak detection dye.
• Perform a leak detection test on the complete sys­tem.
• The low side test pressure must not exceed 31 bar /450 psi.
• When a leak is discovered, repair the leak and repeat the leak detection.
6 – Vacuum dehydration
• Never use the compressor to evacuate the sys­tem.
Connect a vacuum pump to both the LP & HP sides.
• Pull down the system under a vacuum of 500 µm Hg (0.67 mbar) / 0.02 inch Hg absolute.
• Do not use a mega ohmmeter nor apply power to the compressor while it is under vacuum as this may cause internal damage.
7 – Electrical connections
• Switch o and isolate the main power supply.
• Before touching any potentially live part of the drive, wait at least 4 minutes.
• The compressor is protected against excess current by the frequency converter. Follow lo­cal regulations regarding power line protec­tion.The compressor must be connected to ground.
• Use 6.3 mm tabs for quick connect spade ter­minals.
• Use a self-tapping screw to connect the ground conductor to the compressor.
• Care must be taken during installation to ensure that the compressor operates in the correct direction. T1 (U), T2 (V) and T3 (W) ter­minals of compressor and drive U, V, W must match. Please refer to drawings for typical wir­ing connections and examine the specic wir­ing diagram located in the frequency converter package. For further details, refer to the appli­cation guidelines.
• Mounting: The base frame of the frequency converter must be very well xed to the sup­port to ensure a very good continuity between the ground potential of all electrical panels and electrical boxes of the system.
• Wiring: All control wires have to be of a screeened design. The cable for electrical mo­tor supply has to be of a shielded design as well. Correct earthing of the shield cover has to be done using the method shown on drawings, every time this one has to be earthed on each end of the cables. Distinct cable trays must be used for control and motor supply.
• The frequency converter ensures direct motor
protection and the factory set parameters are such to protect the motor over all current mal­functions. An external overload is not necessary.
• Set the frequency converter parameters in
accordance with Danfoss recommendations for the CDS803 frequency converter and VLZ variable speed compressor.
• Refer to variable speed drive manual for electri­cal connections details and installation.
• Compressor motor protection is provided by the variable speed drive.
8 – Filling the system
• Keep the compressor switched o.
• Fill the refrigerant in liquid phase into the outlet of the condenser or the liquid receiver. The charge must be as closed as possible to the nominal system charge to avoid low pres­sure operation and excessive superheat. For VLZ028-044, the refrigerant charge limit is
3.6kg.Above this limit; protect the compressor against liquid ood-back with a pump-down cycle not lower than 1.1 bar(g) for R448A/1.1 bar(g) for R449A/ 1.6 bar(g) for R404A or a suc­tion line accumulator.
• Never leave the lling cylinder connected to the circuit.
9 – Verification before commissioning
Use safety devices such as safety pressure switch and mechanical relief valve in compli­ance with both generally and locally applicable regulations and safety standards. Ensure that they are operational and properly set.
Check that the settings of high-pressure switches do not exceed the maximum service pressure of any system component.
A low-pressure switch is mandatory to avoid vacuum operation.
Refrigerant R448A R449A R404A Min. low pressure safety switch setting
• Verify that all electrical connections are prop-
erly fastened and in compliance with local regulations.
• When using a dome sensor, ensure the dome
sensor is correctly installed and tted into bracket on top of the shell. The sensor need to be well connected, especially after mainte­nance operations.
• After comissioning it is strongly recommended
to keep the frequency converter always ener­gized.
10 – Start-up
• Never start the compressor when no refriger-
ant is charged.
• Do not provide any power to the drive unless
suction and discharge service valves on com­pressor are open, if installed.
• Energize the drive. The compressor must start,
according to dened ramp-up settings. If the compressor does not start, check wiring con­formity.
• Check the frequency converter control panel:
If any alarm is displayed check the wiring and in particular the polarity of the control cables. If an alarm is shown, refer to the frequency converter application manual. Verify in particu­lar the combination of compressor, frequency converter and refrigerant.
bar(g) 0.8 0.8 1. 3
8510286P01B - FRCC.PI.039.A3.02
© Danfoss | DCS (CC) | 2017.07 | 3
• Check current draw and voltage levels on the mains. The values for the compressor electri­cal motor can be directly displayed on the fre­quency converter control panel.
• The optimum compressor suction superheat is around 6K.
• Eventual reverse rotation can be detected by following phenomena; the excessive noise, no pressure dierential between suction and discharge, and line warming rather than imme­diate cooling. A service technician should be present at initial start-up to verify that wiring from drive to compressor is properly phased and that the compressor is rotating in the cor­rect direction.
• Note that a 300 seconds period is necessary be­tween 2 starts, a shorter period will be not al­lowed by the drive. The minimum running time is 12s for each start.
11 – Check with running compressor
Check current draw and voltage. Measure­ment of amps and volts during running condi­tions must be taken at other points in the power supply, not in the compressor electrical box.
• Check suction superheat to reduce risk of slug-
ging.
• Observe the oil level at start and during opera-
tion to conrm that the oil level remains vis­ible. Excess foaming in oil sight glass indicates refrigerant on the sump.
• Monitor the oil sight glass for 1 hour after sys-
tem equilibrium to ensure proper oil return to the compressor. This oil check has to be done over the speed range to guarantee:
- a good oil return at low speed with minimum
gas velocity.
- a good oil management at high speed with
maximum oil carry over.
• Respect the operating limits.
• Check all tubes for abnormal vibration. Move-
ments in excess of 1.5 mm / 0.06 inch require corrective measures such as tube brackets.
• When needed, additional refrigerant in liquid
phase may be added in the low-pressure side as far as possible from the compressor. The compressor must be operating during this pro­cess.
• Do not overcharge the system.
• Never release refrigerant to atmosphere.
• Before leaving the installation site, carry out
a general installation inspection regarding cleanliness, noise and leak detection.
• Record type and amount of refrigerant charge as well as operating conditions as a reference for future inspections.
• Compressor failure to build up pressure: Check all bypass valves in the system to ensure that none of these has been opened. Also check that all solenoid valves are in their proper posi­tion.
• Abnormal running noise: Ensure the absence of any liquid ood-back to the compressor by means of measuring the return gas superheat and compressor sump temperature. The sump should be at least 6K above the saturated suc­tion temperature under steady-state operating conditions.
• The high-pressure switch trips out: Check con­denser operations (condenser cleanliness, fan operation, water ow and water pressure valve, water lter, etc.). If all these are OK, the problem may be due to either refrigerant overcharging or the presence of a noncondensable (e.g. air, moisture) in the circuit.
• The low-pressure switch trips out: Check evap­orator operations (coil cleanliness, fan opera­tions, water ow, water lter, etc.), liquid refrig­erant ow and pressure drops (solenoid valve, lter dryer, expansion valve, etc.), refrigerant charge.
• Low refrigerant charge: The correct refrigerant charge is given by the liquid sight glass indica­tion, the condenser delta T in relation to the refrigerant pressure tables (pressure-tempera­ture), the superheat and the sub-cooling, etc. (if additional charge is deemed necessary, refer to section 8).
• Compressor short cycling: The number of cy­cles shall never exceed 6 starts per hour.
12 – Maintenance
Internal pressure and surface temperature are dangerous and may cause permanent injury. Main tenance operators and installers require appropri­ate skills and tools. Tubing temperature may exceed 100°C / 212°F and can cause severe burns.
Ensure that periodic service inspections to ensure system reliability and as required by local regulations are performed. To prevent system related compressor problems,
following periodic maintenance is recommend­ed:
• Verify that safety devices are operational and properly set.
• Ensure that the system is leak tight.
• Check the compressor current draw by reading one of the parameters via Modbus.
• Conrm that the system is operating in a way consistent with previous maintenance records and ambient conditions.
• Check that all electrical connections are still ad­equately fastened.
• Keep the compressor clean and verify the ab­sence of rust and oxidation on the compressor shell, tubes and electrical connections.
• Acid / moisture content in system and oil should be checked regularly.
13 - Warranty
Always transmit the model number and serial number with any claim led regarding this prod­uct. Use the fault memory of the frequency con­verter to recover the fault descriptions before initializing the system and even before shutting o the power. Variable speed drive model and serial number must also be transmitted with the claim. The product warranty may be void in following cases:
• Absence of nameplate.
• External modications; in particular, drilling, welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the compressor.
• Use of a refrigerant or lubricant not approved by Danfoss.
• Any deviation from recommended instructions pertaining to installation, application or main­tenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
-
• No model number or serial number transmit­ted with the warranty claim.
14 – Disposal
Danfoss recommends that compressors and compressor oil should be recycled by a suitable company at its site.
Danfoss A/S 6430 Nordborg Denmark
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trade­marks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
4 | © Danfoss | DCS (CC) | 2017.07
8510286P01B - FRCC.PI.039.A3.02
Loading...