Index .................................................................................................................... 125
2
MG.04.B7.02 - VLT is a registered Danfoss trademark
VLT®FCD Series
FCD 300 Series
Operating instructions
Software version: 1.5x
These operating instructions can be used for all FCD 300
Series frequency converters with software version 1.5x.
The software version number can be seen from parameter
640 Software version no.
195NA195.12
300
Introduction to FCD
NB!:
Indicates something to be noted by the reader.
tes a general warning.
Indica
Indicates a high-voltage warning.
MG.04.B7.02 - VLT is a registered Danfoss trademark
3
VLT®FCD Series
■High voltage warning
The voltage of the frequency converter
is dangerous whenever the converter
is connected to mains. Incorrect fitting
of the motor or frequency converter may cause
damage to the equipment, serious injury or death.
Consequently, it is essential to comply with the
instructions in this manual as well as local and
national rules and safety regulations.
■These rules concern your safety
1. The frequency converter must be disconnected from
the mains if repair work is to be carried out. Check
that the mains supply has been disconnected
and that the prescribed time has passed before
removing the inverter part from the installation.
2. The [STOP/RESET] key on the optional control
panel does not disconnect the equipment from
mains and is thus not to be used as a safety switch.
3. The unit must be properly connected to the
earth, the user must be protected against the
supply voltage and the motor must be protected
against overloading pursuant to prevailing
national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is not included
in the factory setting. If this function is required,
set parameter 128 Motor thermal protection to
data value ETR trip or data value ETR warning.For
the North American market: The ETR functions
provide overload protection of the motor, class
20, in accordance with NEC.
■Warning against unintended start
1. The motor can be brought to a stop by
means of digital commands, bus commands,
references or a local stop, while the frequency
converter is connected to mains. If personal
safety considerations make it necessary to
ensure that no unintended start occurs, these
stop functions are not sufficient.
2. While parameters are being changed, the
motor may start. Consequently, the stop
key [STOP/RESET] on the optional control
panel must always be activated, following
which data can be modified.
3. A motor that has been stopped may start if faults
occur in the electronics of the frequency converter,
or if a temporary overload or a fault in the supply
mains or the motor connection ceases.
Warning:
It can be extremely dangerous to touch the electrical parts
even when the AC line supply has been disconnected.
For FCD 300: wait at least 4 minutes.
195NA194.10
4
MG.04.B7.02 - VLT is a registered Danfoss trademark
■The decentral concept
The FCD 300 Adjustable speed drive is designed
for decentral mounting, e.g. in the food and
beverage industry, in the automotive industry, or
for other material handling applications.
With the FCD 300 it is possible to utilize the cost saving
potential by placing the power electronics decentrally,
and thus make the central panels obsolete saving
cost, space and effort for installation and wiring.
VLT®FCD Series
2. Mounted directly onthe motor ("motor-mounted")
The unit is flexible in its mounting options for as
well stand alone mounting and motor mounting. It
is also possible to have the unit pre-mounted on
a Danfoss Bauer geared motor (3 in one solution).
Thebasicdesignwithaplugableelectronicpartand
a flexible and "spacious" wiring box is extremely
servicefriendly and easy to change electronics
without the need for unwiring.
The FCD 300 is a part of the VLT frequency converter
family, which means similar funcionality, programming,
and operating as the other family members.
■Flexible installation options
1. Stand alone close to the motor ("wall-mounted")
300
• Fair choice of motor brands
• No need for screened motor cable
Introduction to FCD
3. "Pre-mounted" on Danfoss Bauer
geared motors
• A fixed combination of motor and electronics
supplied by one supplier
• Easy mounting, only one unit
• No need for screened motor cable
• Clear responsibility regarding the complete solution
Astheelectronicpartsarecommon-samefunction
of terminals, similar operation and similar parts
and spare parts for all drives - you are free to
mix the three mounting concepts.
• Free choice of motor brand
• Easy retrofitting to existing motor
• Easy interfacing to motor (short cable)
• Easy access for diagnosis and optimal serviceability
MG.04.B7.02 - VLT is a registered Danfoss trademark
5
■Control principle
A frequency converter rectifies AC voltage from
the mains supply into DC voltage, following which
it changes this voltage to an AC voltage with
variable amplitude and frequency.
The motor thus receives a variable voltage and
frequency, which enables infinitely variable speed
control of three-phase, standard AC motors.
1. Mains voltage
3 x 380 - 480 V AC, 50 / 60 Hz.
2
. Rectifier
Three-phase rectifier bridge which rectifies AC
voltage into DC voltage.
VLT®FCD Series
3
. Intermediate circuit
DC voltage√2 x mains voltage [V].
4
. Intermediate circuit coils
Evens out the intermediate circuit current and
limits the load on mains and components (mains
transformer, cables, fuses and contactors).
. Intermediate circuit capacitor
5
Evens out the intermediate circuit voltage.
6
. Inverter
Converts DC voltage into a variable AC voltage
withavariablefrequency.
. Motor voltage
7
Variable AC voltage depending on supply voltage.
Variable frequency: 0.2 - 132 / 1 - 1000 Hz.
8
. Control card
Here is the computer that controls the inverter
which generates the pulse pattern by which
the DC voltage is converted into variable AC
voltage with a variable frequency.
6
MG.04.B7.02 - VLT is a registered Danfoss trademark
■Mechanical dimensions, FCD, motor mounting
■Mechanical dimensions, stand alone mounting
VLT®FCD Series
Mechanical dimensions inmmFCD 303-315FCD 322-335
A192258
A1133170
B244300
B1300367
B2284346
C142151
C1145154
Cable Gland sizesM16, M20, M25 x 1.5 mm
Space for cable inlets and service switch handle 100-150 mm
■Spacing for mechanical installation
All units require a minimum of 100 mm air from other
components above and below the enclosure.
Installation
MG.04.B7.02 - VLT is a registered Danfoss trademark
7
VLT®FCD Series
■Mechanical installation
Please pay attention to the requirements
that apply to integration and remote
mounting. These must be complied
with to avoid serious injury or damage, especially
when installing large units.
The FCD 300 consists of two parts: The installation
part and the electronics part.
The two parts must be separated, and the installation
part is to be mounted first. After wiring, the electronics
is to be fixed to the installation part by the attached
6 screws. For compressing the gasket the screws
must be tightened with 2-2.4 Nm, tighten both centre
screws first, thereafter the 4 corner srews "cross over".
NB!:
Do not switch on the mains before the
6 screws are tightened.
The FCD 300 can be applied as following:
- Stand alone mounted close to the motor
- Motor mounted
or might be delivered pre mounted on a Danfoss
Bauer (geared) motor. Please contact the Danfoss
Bauer sales organisation for further information.
See Dimensional Drawings.
otor mounting
M
The installation box should be mounted on the
surface of the motor frame, typically instead of the
motor terminal box. The motor/geared motor may
be mounted with the shaft vertically or horizontally.
The unit mustnot be mounted upside down (the heat
sink pointing down). The cooling of the electronics is
independent on the motor cooling fan. For mounting
directly on Danfoss Bauer geared motors no adaption
plate is necessary. For motor mounting (non Danfoss
Bauer motors), an adaptor plate should usually be
applied. For that purpose a neutral plate incl gasket
and screws for attaching to the installation box is
available. The appropriate drillings and gasket for the
motor housing are applied locally. Please make sure,
that the mechanical strength of the mounting screws
and the threads are sufficient for the application. The
specified resistance against mechanical vibrations
does not cover the mounting onto a non Danfoss
Bauer motor, as the stability of the motor frame
and threads are outside Danfoss Drive’s control and
responsibility and the same applies to the enclosure
class. Please be aware, that the frequency converter
may not be used to lift the motor/geared motor.
The frequency converter is cooled by means of air
circulation. For the unit to be able to release its
cooling air, the minimum free distance above and
below the unit must be m
the unit from overheating, it must be ensured that the
ambient temperature does not rise above the max.
temperature stated for the frequency converter and
that the 24-hour average temperature is not exceeded.
The max. temperature and 24-hour average can
be seen in Ge neral technical data. If the ambient
temperature is higher, derating of the frequency
converter is to be carried out. See Derating forambient temperature. Pleasenotethattheservicelife
of the frequency converter will be reduced if derating
for ambient temperature is not considered.
tand alone mounting ("wall mounting")
S
For best cooling the unit should be mounted vertically,
however where space limitations require it, horizontal
mounting is allowable. The integrated 3 wall mounting
brackets in the wall mounting version can be used
for fixing the installation box to the mounting surface,
keeping a distance for possible cleaning between
the box and the mounting surface. Use the three
supplied washers to protect the paint.
inimum 100 mm.Toprotect
Bolts must be M6 for the FCD 303 - 315
and M8 for FCD 322 - 335.
8
MG.04.B7.02 - VLT is a registered Danfoss trademark
1.Prepare the adaptor plate for mounting on the motor by
drilling the fixing holes and the hole for the cables.
2.Mount the plate on the motor with the normal terminal
box gasket.
3.Knock out the 4 screw holes for mounting the adaptor
plate (outer holes).
4.Mount the terminal box onto the motor by the 4 sealing
screws and the gasket supplied.
Use the supplied star washers for securing PE
connection according to EN 60204. The screws must
be tightened with 5 Nm.
VLT®FCD Series
Universal adaptorplate
Allowed mounting positions
Installation
MG.04.B7.02 - VLT is a registered Danfoss trademark
9
VLT®FCD Series
■General information about electrical installation
■High voltage warning
The voltage of the frequency converter
is dangerous whenever the equipment is
connected to mains. Incorrect installation
of the motor or frequency converter may cause
damage to the equipment, serious injury or death.
Comply with the instructions in this manual, as well as
national and local rules and safety regulations.
Touching the electrical parts may be fatal - even after
the equipment has been disconnected from mains:
Wait at least 4 minutes for current dissipate.
NB!:
It is the responsibility of the user or installer
to ensure correct earthing and protection in
accordance with national and local standards.
■Cables
The control cable and the mains cable should be
installed separately from motor cables to prevent
noisetransfer. Asaruleadistanceof20cmis
sufficient, but it is recommended that the distance
is as great as possible, particularly when cables are
installed in parallel over large distances.
For sensitive signal cables such as telephone or data
cables the greatest possible distance is recommended.
Please note that the required distance depends on
installation and the sensitivity of the signal cables, and
that for this reason exact values cannot be given.
■Extra protection
ELCB relays, multiple protective earthing or earthing
can be used as extra protection, provided that local
safety regulations are complied with. In the case of an
earth fault, a DC content may develop in the faulty
current. Never use an RCD (ELCB relay), type A, as
it is not suitable for DC faulty currents. If ELCB relays
are used, local regulations must be complied with.
If ELCB relays are used, they must be:
- Suitable for protecting equipment with a DC content
in the faulty current (3-phase bridge rectifier)
- Suitable for a pulse-shaped, brief discharge
on power-up
- Suitable for a high leakage current.
See also RCD Application Note MN.90.GX.02.
■High voltage test
A high voltage test can be performed by
short-circuitingterminalsU,V,W,L1,L2andL3,
and applying max. 2160 V DC in 1 sec. between
this short-circuit and PE-terminal.
■Electronics purchased without installation box
If the electronic part is purchased without the
Danfoss installation part, the earth connection
the
must be suitable for high leakage current. Use
of original Danfoss installation box or installation
kit 175N2207 is recommended.
When being placed in cable trays, sensitive cables
may not be placed in the same cable tray as t
motor cable. If signal cables run across power
cables, this is done at an angle of 90 degrees.
Remember that all noise-filled inlet
to a cabinet must be screened/armoured.
See also EMC-compliant electrical installation.
Cable glands
It must be assured that appropriat
glands needed for the environment are chosen
and carefully mounted.
■Screened/armoured cables
The screen must have low HF impe
achieved by a braided screen of copper, aluminium or
iron. Screen reinforcement intended for mechanical
protection, for example, is
installation. See also Use of EMC-correct cables.
10
not suitable for EMC-correct
and outlet cables
e cable
dance, which is
he
■Caution
PE connection
he metal pin in the corner(s) of the
T
electronic part and the bronze spring in the
corner(s) of the installation box are essential
for the protective earth connection. Mak
are not loosened, removed, or violated in any way.
MG.04.B7.02 - VLT is a registered Danfoss trademark
e sure they
VLT®FCD Series
NB!:
Do not plug/unplug the electronic part with
mains voltage switched on.
■Protective earth
The earth connection serves several purposes.
• Safety earth (Protective earth, PE)
The equipment must be properly earthed according
to local regulation. This equipment has a leakage
current > 3.5 mA AC. It must be connected to
an earth connection complying with the local
rules for high leakage current equipment.
Typically, this implies that the PE conductors
must be mechanically enhanced (minimum cross
2
section 10 mm
) or duplicated
• Noise "clamping" (high frequencies)
Stable communication between units call for
screening of the communication cables (1).
Cables must be properly attached to screen
clamps provided for that purpose.
• Equalisation of voltage potential (low frequencies)
To reduce alignment currents in the screen
of the communication cable, always apply a
short earthing cable between units that are
connected to the same communication cable (2)
or connect to an earthed frame (3).
• Potential equalization: All metal parts, where the
motors are fastened, must be potential equalized
PE connections, voltage equalising cables and the
screen of the communication cable should be
connected to the same potential (4).
Keep the conductor as short as possible and use
the greatest possible surface area.
The numbering refers to the figure.
Installation
Proper installation earthing
■EMC-correct electrical installation
General points to be observed to ensure
EMC-correct electrical installation.
- Use only screened/armoured motor cables and
screened/armoured control cables.
- Connect the screen to earth at both ends.
MG.04.B7.02 - VLT is a registered Danfoss trademark
- Avoid installation with twisted screen ends (pigtails),
since this ruins the screening effect at high
frequencies. Use cable clamps instead.
-Don’t remove the cable screen between the
cable clamp and the terminal.
11
■ATEX correct installation
The following issues must be taken into account when
installing the FCD 300 in ATEX zone 22 environments:
• Motor must be designed, tested and certified by the
motor manufacturer for variable speed application
• Motor must be designed for Zone 22 operation.
I.e. with type of protection "tD" acc. to
EN61241-0 and -1 or EN50281-1-1.
• Motor must be provided with thermistor protection.
The thermistor protection must either be connected
to an external thermistor relay, with EC Type
Examination Certificate or compatible with
the FCD 300 thermistor input.
If the FCD 300 thermistor protection is used,
the thermistor must be wired to terminals
31a and 31b, and thermistor trip activated by
programming parameter 128 to thermistor trip
[2]. See parameter 128 for further details.
• Cable entries must be chosen for the enclosure
protection to be maintained. It must also be
ensured that the cable entries comply with the
requirements for clamping force and mechanical
strengths as described in EN 50014:2000.
• The FCD must be installed with appropriate earth
connecting according to local/national regulations.
• The installation, inspection and maintenance of
electrical apparatus for use in combustible dusts,
must only be carried out by personnel that is
trained and familiar with the concept of protection.
VLT®FCD Series
For a declaration of conformity, please consult
your local Danfoss representative.
12
MG.04.B7.02 - VLT is a registered Danfoss trademark
■Diagram
VLT®FCD Series
* Integrated brake and mechanical brake control
and external 24 V are options.
■RFI switches J1, J2
J1 and J2 must be removed at IT mains and
delta grounded mains with phase to earth voltage
> 300 V also during earth failure.
J1 and J2 can be removed to reduce leakage current.
Caution: No correct RFI filtering.
Installation
MG.04.B7.02 - VLT is a registered Danfoss trademark
13
■Location of terminals
VLT®FCD Series
T11, T12, T16, T52, T56
T22, T26, T62, T66versions with service switch
14
MG.04.B7.02 - VLT is a registered Danfoss trademark
VLT®FCD Series
T73 version with motor plug and sensor plugs
Version is supplied from Danfoss with wiring as shown
Installation
versionwithserviceswitch(nomotorplug)
T63
MG.04.B7.02 - VLT is a registered Danfoss trademark
15
VLT®FCD Series
■Mains connection
No. 91 92 93 Mains voltage 3 x 380-480 V
L1 L2 L3
PEEarth connection
NB!:
Please check that the mains voltage fits the
mains voltage of the frequency converter, which
can be seen from the nameplate.
See Technical data for correct dimensioning
of cable cross-section.
■Pre-fuses
See Technical data for correct dimensioning
of pre-fuses.
■Motor connection
Connect the motor to terminal
s 96, 97, 98.
Connect earth to PE-terminal.
No. 969798Motor voltage 0-100% of mains voltage
UVW3 wires out of motor
U1W2V1U2W1V26 wires out of motor, Delta connected
■Direction of motor rotation
The factory setting is for clockwise rotation
with the frequency converter transformer output
connected as follows:
Terminal 96 connected to U-phase.
Terminal 97 connected to V-phase.
Terminal 98 connected to W-phase.
The direction of rotation can be changed by switching
two phases on the motor terminals.
U1V1 W1 6 wires out of motor, Star connected
U2, V2, W2 to be interconnected
separately (optional terminal block)
PEEarth connection
See Technical data for correct dimensioning
of cable cross-section.
All types of three-phase asynchronous standard
motors can be connected to a frequency converter.
Normally, small motors are star-connected (230/400
/ Y). Large motors are delta-connected (400/690
V,
/ Y). The correct connection mode and voltage
V,
can be read from the motor nameplate.
NB!:
In motors without phase insulation paper,
an LC filter should be fitted on the output
of the frequency converter.
■Mains and motor connection with service switch
16
MG.04.B7.02 - VLT is a registered Danfoss trademark
VLT®FCD Series
■Connection of HAN 10E motor plug for T73
HAN 10E pin no 1 - Motor phase U
HAN 10E pin no 2 - Motor phase V
HAN 10E pin no 3 - Motor phase W
HAN 10E pin no 4 - Motor brake, see OperatingInstructions MG.04.BX.YY, terminal 122
HAN 10E pin no 5 - Motor brake, see OperatingInstructions MG.04.BX.YY, terminal 123
HAN 10E pin no 9 - Motor thermistor, see OperatingInstructions MG .04.BX.YY, terminal 31A
HAN 10E pin no 10 - Motor thermistor, see
Operating Instructions MG.04.BX.YY, terminal 31B
PE = protective earth
■Parallel connection of motors
The frequency converter is able to control several
motors connected in parallel. If the motors are
to have different rpm values, use motors with
different rated rpm values. Motor rpm is changed
simultaneously, which means that the ratio between
the rated rpm values is maintained across the range.
The total current consumption of the motors is
not to exceed the maximum rated output current
for the frequency converter.
I
INV
Problems may arise at the start and at low rpm
values if the motor sizes are widely different. This
is because the small motors’ relatively high ohmic
resistance in the stator calls for a higher voltage
at the start and at low rpm values.
converter cannot be used as motor protection for
the individual motor. For this reason further motor
protection must be used, e.g. thermistors in each
motor (or an individual thermal relay).
NB!:
Parameter 107 Automatic motor tuning, AMT
cannot be used when motors are connected
in parallel. Parameter 101 Torque characteristic
must be set to Special motor characteristics [8]
when motors are connected in parallel.
■Motor cables
See Technical data for correct dimensioning of motor
cable cross-section and length. Always comply with
national and local regulations on cable cross-section.
NB!:
If an unscreened/unarmoured cable is used,
some EMC requirements are not complied with,
see EMC test results in the Design Guide.
If the EMC specifications regarding emission are
to be complied with, the motor cable must be
screened/armoured, unless otherwise stated for the
RFI filter in question. It is important to keep the motor
cable as short as possible so as to reduce the noise
level and leakage currents to a minimum. The motor
cable screen must be connected to the metal cabinet
of the frequency converter and to the metal cabinet of
the motor. The screen connections are to be made
with the biggest possible surface area (cable clamp).
This is enabled by different installation devices in
different frequency converters. Mounting with twisted
screen ends (pigtails) is to be avoided, since these
spoil the screening effect at high frequencies. If it
is necessary to break the screen to install a motor
isolator or motor relay, the screen must be continued
at the lowest possible HF impedance.
■Motor thermal protection
The electronic thermal relay in UL-approved frequency
converters has received the UL-approval for single
motor protection, when parameter 128 Motor thermalprotection has been set for ETR Trip and parameter
105 Motor current, I
has been programmed to
M, N
the rated motor current (see motor nameplate).
Installation
In systems with motors connected in parallel, the
electronic thermal relay (ETR) of the frequency
MG.04.B7.02 - VLT is a registered Danfoss trademark
17
■Brake resistor
VLT®FCD Series
No.81 (optional
function)
R-R+
82 (optional
function)
Brake resistor
terminals
The connection cable to the brake resistor must
be screened/armoured. Connect the screen to the
metal cabinet of the frequency conver
ter and to the
metal cabinet of the brake resistor by means of
cable clamps. Dimension the cross-section of the
brake cable to match the brake to
See chapter Dynamic Brak
ing in the Design Guide
rque.
MG.90.FX.YY for dimensionering of brake resistors.
NB!:
Please note that voltages up to 850 V
DC occur on the te
rminals.
■Control of mechanical brake
No.122 (optional
function)
MBR+MBR-Mechanical brake
123
(optional
function)
(UDC=0.45 X Mains
Voltage) Max 0.8 A
In lifting/lowering applications you need to be able
to control an electromagnetic brake. The brake
is controlled using the special mechanical brake
control/supply terminals 122/123.
When the output frequency exceeds the brake cut
out value set in par. 138, the brake is released if the
motor current exceeds the preset value in parameter
140. When stopping the brake is engaged when
the output frequency is less than the brake engaging
frequency, which is set in par. 139.
If the frequency converter is at alarm status
or in an overvoltage situation the mechanical
brake is cut in immediately.
If not using the special mechanical brake control/supply
terminals (122-123), select Mechanical brake control
in parameter 323 or 341 for applications with
an electromagnetic brake.
A relay output or digital output (terminal 46)
can be used. See Connection of mechanicalbrake for further details.
18
MG.04.B7.02 - VLT is a registered Danfoss trademark
VLT®FCD Series
■Electrical installation, control cables
Control cables must be screened/armoured. The
screen must be connected to the frequency converter
chassis by means of a clamp. Normally, the screen
must also be connected to the chassis of the
controlling unit (use the instructions for the unit in
question). In connection with very long control cables
and analogue signals, in rare cases depending on
the installation, 50/60 Hz earth loops may occur
because of noise transmitted from mains supply
cables. In this connection, it may be necessary
to break the screen and possibly insert a 100 nF
capacitor between the screen and the chassis.
Installation
Switches S101-104
Bus line coils, leave switches ON
MG.04.B7.02 - VLT is a registered Danfoss trademark
19
■Connection of sensors to M12 plugs for
T53, T63, T73
VLT®FCD Series
For rating specifications see the Operating Instructions
MG.04.BX.YY, digital inputs terminals 18, 19, 29, 33.
Terminals 203/204 are used for sensor supply.
Terminal 203 = common
Terminal 204 = +24 V
Terminals 201/202 can be used for a
separate 24 V supply.
20
MG.04.B7.02 - VLT is a registered Danfoss trademark
VLT®FCD Series
■Electrical installation, control terminals
See section entitled Earthing of screened/armoured
control cables in the Design Guide for the correct
termination of control cables.
No.Function
01-03Relay outputs 01-03 can be used for
indicating status and alarms/warnings.
1224 V DC voltage supply.
18-33Digital inputs.
20, 55Common frame for input
and output terminals. Can be separated with switch
S100
31a,
31b
35Common (-) for external 24 V control back up
36External + 24 V control back up supply. Optional.
42Analog output for displaying frequency,
46Digital output for displaying status,
50+10 V DC supply
53Analogue voltage input 0 - +/- 10 V DC.
60Analogue current input 0/4 - 20 mA.
67+ 5 V DC supply voltage
68, 69Fieldbus serial communication*
70Ground for terminals 67, 68 and 69.
DFor future use
V+5V, red
PRS485(+), LCP2/PC, yellow
NRS485(-), LCP2/PC, green
GOV, blue
*SeeVLT 2800/FCM 300/
Motor thermistor
supply. Optional.
reference, current or torque.
warnings or alarms, as well as
frequency output.
voltage for potentiometer
to Profibus.
Normally this terminal is not to be used.
FCD 300 Profibus DP
V1 Operating Instructions (MG.90.AX.YY), VLT
2800/FCD 300 DeviceNet Operating Instructions
(MG.90.BX.YY) or FC
D 300 AS-interface Operating
Instructions (MG.04.EX.YY).
■Relay connection
See parameter 323 Relay output for programming
of relay output.
No. 01- 021 - 2 make (normally open)
01- 031-3break(normallyclosed)
■LCP 2 plug, optional
An LCP 2 control unit can be connected to a
plug which is optionally mounted in the housing.
Ordering number: 175N0131.
LCP control units with ordering number 175Z0401
are not to be connected.
■Installation of 24 Volt external supply (optional)
24 V external DC supply can be use
d as low-voltage
supply to the control card. This enables full
operation of the LCP2 and serial bus (incl. parameter
setting) without connecti
on to mains.
Please note that a warning of low voltage will
be given when 24 V DC has been connected;
however there will be n
o tripping.
NB!:
Use24VDCsupplyoftypePELVtoensure
correct galvanic isolation (type PELV) on the
control terminal
Beware of unin
s of the VLT frequency converter.
tended start of the motor, if
the mains power is applied during operation
on the external 24 V back up supply.
■Software version 1.5x
A Field bus equipped FCD shows the status Unit
ready even with bridged terminals 12-27 and cannot
be set into RUNNING mode by digital inputs alone
until one of the following parameters is set:
- Par. 502 is set to Digital input or Logic and or
- Par. 833 or 928 is set to Disable or
- Par. 678 is set to Standard version
Installation
■PC communication
Connect to terminals P and N for PC-access to single
parameters. Mot
or and field bus communication
should be stopped before performing automatic
transfer of multiple parameters.
On non-fieldb
us and Profibus variants, terminals
68 and 69 can be used provided Profibus
communication is stopped.
MG.04.B7.02 - VLT is a registered Danfoss trademark
The field bus status word at power up might be
different (typically 0603h instead of 0607h) until the
first valid control word is sent. After sending the first
valid control word (bit 10 = Data valid) the status
is exactly as in earlier software versions.
21
■Connection examples
VLT®FCD Series
NB!:
Avoid leading the cables over the plugs
to the electronics.
Dont loosen screw fixing the spring
for the PE connection.
22
MG.04.B7.02 - VLT is a registered Danfoss trademark
NB!:
In the connection examples below, it should
be noted, that the Switch S100 must not be
changed from factory settings (on).
■Start/stop
Start/stop using terminal 18 and coasting
stop using terminal 27.
VLT®FCD Series
■Speed up/down
Speed up/down using terminals 29/33.
Par. 302 Digital input = Start [7]
Par. 303 Digital input = Freeze reference [14]
Par. 305 Digital input = Speed up [16]
Par. 307 Digital input = Speed down [17]
Par. 302 Digital input = Start [7]
Par. 304 Digital input = Coasting stop inverted [2]
For Precise start/stop the following settings are made:
Par. 302 Digital input = Precise start/stop [27]
Par. 304 Digital input = Coasting stop inverted [2]
■Pulse start/stop
Pulse start using terminal 18 and pulse stop
using terminal 19. In addition, the jog frequency
is activated via terminal 29.
Par. 302 Digital input = Pulse start [8]
Par. 303 Digital input = Stop inverted [6]
Par. 304 Digital input = Coasting stop inverted [2]
Par. 305 Digital input = Jog [13]
MG.04.B7.02 - VLT is a registered Danfoss trademark
VLT®FCD Series
This table shows what the output frequency is:
Preset ref.,
msb
0002.5
0105
10010
11017.5
00120
01125
10135
11150
Preset ref.,
lsb
Selection of
Setup
■Connection of mechanical brake
Using terminal 122/123
Output
frequency[Hz]
Use of the relay for 230 V AC brake
Par. 302 Digital input = Start [7]
Par. 304 Digital input = Coasting stop inverted [2]
Par. 323 Relay output = Mechanicalbrake control [25]
See also par. 138, 139, 140
Mechanical brake control [25] = ’0’ => Brake is closed.
Mechanical brake control [25] = ’1’ => The
brake is open.
See more detailed parameter settings under
Control of mechanical brake.
Installation
Par. 302 Digital
input = Start [7]
Par. 304 Digital input = Coasting stop inverted [2]
See also par. 138, 139, 140
Mechanical brake with accelerator winding
Par. 302 Digital input = Start [7]
Par. 304 Digital input = Coasting stop inverted [2]
See also par. 138, 139, 140
NB!:
Do not use the internal relay for DC brakes
or brake voltages > 250 V.
■Counter stop via terminal 33
The start signal (terminal 18) must be active, i.e. logical
’1’, until the output frequency is equal to the reference.
The start signal (terminal 18 = logical ’0’) must then be
removed before the counter value in parameter 344
has managed to stop the VLT frequency converter.
Par. 307 Digital input = Pulse input [30]
Par. 343 Precise stop function = Counterstop with reset [1]
Par. 344 Counter value = 100000
MG.04.B7.02 - VLT is a registered Danfoss trademark
25
VLT®FCD Series
■The LCP 2 control unit, option
■Control keys for parameter Setup
The control keys are divided into functions, in
such a way that the keys between the display
and the indicator lamps are used for parameter
Setup, including selection of the display’sview
mode during normal operation.
[DISPLAY/STATUS] is used to select the display’s
view mode or to change back to Display mode
from either Quick Menu or Menu mode.
[QUICK MENU] provides access to the parameters
used in the Quick Menu. It is possible to switch
between Quick Menu and Menu mode.
The FCD 300 can be combined with an LCP control
unit (Local Control Panel - LCP 2) which makes up a
complete interface for operation and pro
the frequency converter. The LCP 2 control unit can
be attached up to three metres from the frequency
converter, e.g. on a front panel, usin
The control panel is divided into f
1. Display.
2. Keys used to change the display function.
3. Keys used to change the programme par
4. Indicator lamps.
5. Local control keys.
Alldataisdisplayedviaa4-linealphanumeric
display, which during normal ope
to continuously display 4 items of operating data
and 3 operating modes. During programming all
information needed for quick,
setup of the frequency converter will be displayed. As
asupplementtothedisplay,therearethreeindicator
lamps for voltage (ON), w
(ALARM). All frequency converter parameter Setups
can be changed immediately from the control panel,
unless this function h
[1] via parameter 018 Lock for data c hanges.
arning (WARNING) and alarm
as been programmed as Locked
ive functional groups:
ration will be able
effective parameter
gramming of
g an accessory kit.
ameters.
[MENU] givesaccesstoallparameters. Itispossible
to switch between Menu mode and Quick Menu.
[CHANGE DATA] is used to change a parameter that
has been selected either in Menu mode or Quick Menu.
[CANCEL] is used if a change to the selected
parameter is not to be implemented.
[OK] is used to confirm a change to a
selected parameter.
[+ / -] are used for selecting parameters and
for changing parameter values.
These keys are also used in Display mode to switch
between the readouts of operating variables.
[< >] are used for selecting parameter group and to
move the cursor when changing a numerical value.
26
MG.04.B7.02 - VLT is a registered Danfoss trademark
VLT®FCD Series
■Indicator lamps
At the bottom of the control panel are a red
alarm lamp, a yellow warning lamp and a
green voltage indicator lamp.
If certain threshold values are exceeded, the alarm
and/or warning lamp are activated, while a status
or alarm text is shown on the display.
NB!:
The voltage indicator lamp is activated when
voltage is connected to the frequency converter.
■Local control
[STOP/RESET] is used for stopping the motor
connected or for resetting the frequency converter
after a drop-out (trip). Can be set to active or
inactive via parameter 014 Local stop.
If stop is activated Display line 2 will flash.
NB!:
If an external stop function is not selected and
the [STOP/RESET] key is set to inactive, the
motor can only be stopped by disconnecting
the voltage to the motor or the frequency converter.
[JOG] changes the output frequency to a preset
frequency while the key is held down. Can be set to
active or inactive via parameter 015 Local jog.
NB!:
If the local control keys are set to inactive,
these will both become active when the
frequency converter is set to Loc al control
and Remote control via parameter 002 Local/remoteoperation, with the exception of [FWD/REV], which
is only active in Local control.
■Display mode
VAR 1.1 VAR 1.2 VAR 1.3
SETUP
VAR 2
1
STATUS
In normal operation, up to 4 different display data
items can optionally be shown continuously: 1,1,
1,2, 1,3 and 2. The present operation status or
alarms and warnings that have been generated are
displayed in line 2 in the form of a number.
In the event of alarms this is displayed in lines
3and4withexplanatorytext.
A warning will appear flashing in line 2 with
explanatory text in line 1. The active Setup
will also appear on the display.
The arrow indicates the selected direction of rotation.
Here the frequency converter shows that it has
an active reversing signal. The body of the arrow
will disappear if a stop command is given, or if the
output frequency drops below 0.1 Hz.
The bottom line displays the frequency transformer’s
status. The scrollbar shows which operating values
can be displayed in lines 1 and 2 in Display mode.
Changes are made using the [+ / -] keys.
195NA113.10
300
Programming, FCD
[FWD / REV] changes the direction of rotation of
the motor, which is indicated by means of the arrow
on the display. Can be set to active or inactive via
parameter 016 Local reversing.The[FWD/REV]key
is only active when parameter 002 Local/remoteoperation is set to Local control.
[START] is used to start the frequency converter. Is
always active, but cannot override a stop command.
MG.04.B7.02 - VLT is a registered Danfoss trademark
Switching between AUTO and HAND modes
By activating the [CHANGE DATA] key in [DISPLAY
MODE] the display will indicate the mode of
the frequency converter.
Switch mode by using [+/-] key [HAND...AUTO]
In [HAND] mode the reference can be changed
by [+] or [-] keys.
27
VLT®FCD Series
Operating dataUnit
Resulting reference[%]
Resulting reference[unit]
Feedback[unit]
Output frequency[Hz]
Output frequency x scaling[-]
Motor current[A]
Torque[%]
Power[kW]
Power[HP]
Motor voltage[V]
DC link voltage[V]
Thermal load motor[%]
Thermal load[%]
Hours run[hours]
Digital input[binary]
Pulse input 29[Hz]
Pulse input 29[Hz]
Pulse input 33[Hz]
External reference[%]
Status word[hex]
Heatsink temperature[°C]
Alarm word[hex]
Control word[hex]
Warning word[hex]
Extended status word[hex]
Analogue input 53[V]
Analogue input 60[mA]
Three operating data items can be shown in the
first display line, and one operating variable can be
shown in the second display line. Is programmed via
parameters 009, 010, 011 and 012 Display readout .
■Display modes
The LCP control unit has different display
modes, which depend on the mode selected
for the frequency converter.
Display mode I:
This display mode is standard after startup
or initialisation.
FREQUENCY
50.0 Hz
MOTOR IS RUNNING
Line 2 shows the data value of an operating data item
with unit, and line 1 contains a text that explains line
2. In the example, Frequency has been selected as
readout via parameter 009 Large display readout.In
normal operation, another variable can be entered
immediately using the [+ / -] keys.
Display mode II:
Switch between Display modes I and II is performed
by briefly pressing the [DISPLAY / STATUS] key.
24.3% 30.2% 13.8A
50.0 Hz
MOTOR IS RUNNING
In this mode, all data values for four operating
data items with any pertaining units are shown,
see table. In the example, the following have been
selected: Frequency, Reference, Torque and Current
as readout in the first and second line.
28
Display mode III:
This display mode is called up as long as the [DISPLAY
/ STATUS] key is held down. When the key is released
it switches back to Display mode II, unless
the key is
held down for less than approx. 1 sec., in which case
the system always reverts to Display mode I.
REF% TORQUE CURR A
50.0 Hz
MOTOR IS RUNNING
SETUP
1
Here you can read out the parameter names and
units for operating data in the first and second lines.
Line 2 in the display remains unchanged.
MG.04.B7.02 - VLT is a registered Danfoss trademark
DisplaymodeIV:
This display mode can be called up during operation
if a change has to be made in another Setup without
stopping the frequency converter. This function is
activated in parameter 005 Programming Setup.
24.3% 30.2% 13.8A
SETUP
50.0 Hz
MOTOR IS RUNNING
12
Here the programming Setup number 2 will flash
to the right of the active Setup.
■Parameter Setup
A frequency converter’s comprehensive work area can
be accessed via a large number of parameters, making
it possible to adapt its functionality for a specific
application. To provide a better overview of the many
parameters, there is a choice of two programming
modes - Menu mode and Quick Menu mode. The
former provides access to all parameters. The latter
takes the user through the parameters, which make
it possible to start operating the frequency converter
in most cases, in accordance with the Setup made.
Regardless of the mode of programming, a change
of a parameter will take effect and be visible both in
the Menu mode and in the Quick menu mode.
Structure for Quick menu m ode v Menu mode
In addition to having a name, each parameter is linked
up with a number which is the same regardless of
the programming mode. In Menu mode, paramet
will be split into groups, with the first digit (left)
of the parameter number indicating the group
number of the parameter in question.
VLT®FCD Series
■Quick m enu with LCP 2 control unit
Start Quick Setup by pressing the [QUICK MENU] key,
which will bring out the following display values:
QUICK MENU X OF Y
50.0 Hz
001 LANGUAGE
ENGLISH
At the bottom of the display, the parameter number
and name are given together with the status/value
of the first parameter under the Quick menu. The
first time the [QUICK MENU] key is pressed after
the unit has been switched on, the readouts always
start in pos. 1 - see table below.
Pos. Parameter no.Unit
1001 Language
2102 Motor power[kW]
3103 Motor voltage[V]
4104 Motor frequency[Hz]
5105 Motor current[A]
6106 Rated motor speed[rpm]
7107 AMT
8204 Minimum reference[Hz]
9205 Maximum reference[Hz]
10207 Ramp-up time[sec]
11208 Ramp-down time[sec]
12002 Local/remote operation
13003 Local reference[Hz]
■Parameter selection
Menu mode is started by pressing the [MENU] key,
which produces the following readout on the display:
ers
FREQUENCY
50.0 Hz
0 KEYB.&DISPLAY
SETUP
1
300
Programming, FCD
• Using the [QUICK MENU] key, it is possibl
eto
get access to the most important parameters
of the frequency converter. After programming,
the frequency converter is in most
cases ready
for operation. Scroll through the Quick menu
using the [+ / -] keys and change the data values
by pressing [CHANGE DATA] + [OK
].
• The Menu mode allows choosing and changing
all parameters as required. However, some
parameters will be "shaded
off", depending on the
choice in parameter 100 Configuration .
MG.04.B7.02 - VLT is a registered Danfoss trademark
Line 3 on the display shows the parameter
group number and name.
In Menu mode, the parameters are divided
into groups. Selection of parameter group is
effected using the [< >] keys.
The following parameter groups will be accessible:
When the required parameter group has been
selected, each parameter can be chosen by
means of the [+ / -] keys:
FREQUENCY
50.0 Hz
001 LANGUAGE
ENGLISH
The 3rd line of the display shows the parameter
number and name, while the status/value of the
selected parameter is shown in line 4.
Changing data
Regardless of whether a parameter has been
selected under the Quick menu or the Menu mode,
theprocedureforchangingdatawillbethesame.
Pressing the [CHANGE DATA] key gives access
to changing the selected parameter, following
which the underlining in line 4 will flash on the
display. The procedure for changing data depends
on whether the selected parameter represents a
numerical data value or a text value.
Changing a data value
If the selected parameter is a text value, the text
value is changed by means of the [+ / -] keys.
The chosen digit is indicated by the digit flashing. The
bottom display line shows the data value that will be
entered (saved) when signing off with [OK].
■ Manual initialisation
NB!:
Manual initialisation is n
the LCP 2 175N0131 control unit. It is,
however, possible to perform an initialisation
via par. 620 Operation mode:
The following parameters are not changed when
initialising via par. 620 Operation mode.
- par. 500 Address
- par. 501 Baud rate
- par. 600 Operat ing hours
- par. 601 Hours run
- par. 602 kWh counter
- par. 603 Number of power-ups
- par. 604 Number of overtemperatures
- par. 605 Number of overvoltages
- par. 615-617 Fault log
- par. 678 Configure Control Card
ot possible on
FREQUENCY
50.0 Hz
001 LANGUAGE
ENGLISH
The bottom display line will show the value that will be
entered (saved) when acknowledgment is given [OK].
Changeofnumericdatavalue
If the selected parameter is represented by a numerical
data value, a digit is first chosen using the [< >] keys.
FREQUENCY
50.0 Hz
130 START FREQUENCY
09.0 HZ
The selected digit can then be changed infinitely
variably using the [+ / -] keys:
FREQUENCY
50.0 Hz
130 START FREQUENCY
10.0 HZ
SETUP
1
SETUP
1
30
MG.04.B7.02 - VLT is a registered Danfoss trademark
Loading...
+ 97 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.