Danfoss VLT FC 322 Instruction Manual

MAKING MODERN LIVING POSSIBLE
IInstruction Manual
VLTp Automation VT Drive FC 322
www.danfoss.com/drives
130R0411 MG21E122 Rev. 2012-05-03
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
Safety
WARNING
HIGH VOLTAGE!
Frequency converters contain high voltage when connected to AC mains input power. Installation, start up, and maintenance should be performed by qualified personnel only. Failure to perform installation, start up, and maintenance by qualified personnel could result i n death or serious injury.
High Voltage Frequency converters are connected to hazardous mains voltages. Extreme care should be taken to protect against shock. Only trained personnel familiar with electronic equipment should install, start, or maintain this equipment.
WARNING
UNINTENDED START!
When the frequency converter is connected to AC mains, the motor may start at any time. The frequency converter, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness when the frequency converter is connected to AC mains could result in death, serious injury, equipment, or property damage.
Unintended Start When the frequency converter is connected to the AC mains, the motor may be started by means of an external switch, a serial bus command, an input reference signal, or a cleared fault condition. Use appropriate cautions to guard against an unintended start.
WARNING
DISCHARGE TIME!
Frequency converters contain DC-link capacitors that can remain charged even when the frequency converter is not powered. To avoid electrical hazards, disconnect AC mains, any permanent magnet type motors, and any remote DC­link power supplies, including battery backups, UPS and DC-link connections to other frequency converters. Wait for the capacitors to fully discharge before performing any service or repair work. The amount of wait time is listed in the Discharge Time table. Failure to wait the specified time after power has been removed before doing service or repair could result in death or serious injury.
Voltage [V] Power range [kW] Minimum waiting time
[min]
3x400 90-250 20
3x400 110-315 20
3x500 110-315 20
3x500 132-355 20
3x525 75-250 20
3x525 90-315 20
3x690 90-250 20
3x690 110-315 20
Discharge Time
Safety VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
Safety VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
Contents
1 Introduction
2-1
1.1 Exploded Views
2-1
1.2 Purpose of the Manual
2-2
1.3 Additional Resources
2-2
1.4 Product Overview
2-2
1.5 Internal Controller Functions
2-2
1.6 Frame Sizes and Power Ratings
2-3
2 Installation
3-1
2.1 Planning the Installation Site
3-1
2.2 Pre-Installation Check List
3-1
2.3 Mechanical Installation
3-1
2.3.1 Cooling 3-1
2.3.2 Lifting 3-2
2.3.3 Wall Mounting - IP21 (NEMA 1) and IP54 (NEMA 12) Units 3-2
2.4 Electrical Installation
3-3
2.4.1 General Requirements 3-3
2.4.2 Earth (Grounding) Requirements 3-5
2.4.2.1 Leakage Current (>3.5 mA) 3-5
2.4.2.2 Earthing (Grounding) IP20 Enclosures 3-6
2.4.2.3 Earthing (Grounding) IP21/54 Enclosures 3-6
2.4.3 Motor Connection 3-7
2.4.4 Motor Cable 3-10
2.4.5 Motor Rotation Check 3-10
2.4.6 AC Mains Connection 3-10
2.5 Control Wiring Connection
3-11
2.5.1 Access 3-11
2.5.2 Using Screened Control Cables 3-11
2.5.3 Earthing (Grounding) of Screened Control Cables 3-12
2.5.4 Control Terminal Types 3-13
2.5.5 Wiring to Control Terminals 3-13
2.5.6 Control Terminal Functions 3-13
2.6 Serial Communication
3-13
3 Start Up and Commissioning
4-1
3.1 Pre-start
4-1
3.2 Applying Power to the Frequency Converter
4-2
3.3 Basic Operational Programming
4-2
Contents VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
3.4 Local-control Test
4-4
3.5 System Start Up
4-4
4 User Interface
5-1
4.1 Local Control Panel
5-1
4.1.1 LCP Layout 5-1
4.1.2 Setting LCP Display Values 5-2
4.1.3 Display 5-2
4.1.4 Navigation Keys 5-3
4.1.5 Operation Keys 5-3
4.2 Back Up and Copying Parameter Settings
5-3
4.2.1 Uploading Data to the LCP 5-4
4.2.2 Downloading Data from the LCP 5-4
4.3 Restoring Default Settings
5-4
4.3.1 Recommended Initialisation 5-4
4.3.2 Manual Initialisation 5-4
5 Programming
6-1
5.1 Introduction
6-1
5.2 Programming Example
6-1
5.3 Control Terminal Programming Examples
6-3
5.4 International/North American Default Parameter Settings
6-3
5.5 Parameter Menu Structure
6-4
5.5.1 Main Menu Structure 6-5
5.6 Remote Programming with MCT 10 Set-up Software
6-9
6 Application Examples
7-1
6.1 Introduction
7-1
6.2 Application Examples
7-1
7 Status Messages
8-1
7.1 Status Display
8-1
7.2 Status Message Definitions Table
8-1
8 Warnings and Alarms
9-1
8.1 System Monitoring
9-1
8.2 Warning and Alarm Types
9-1
8.2.1 Warnings 9-1
8.2.2 Alarm Trip 9-1
8.2.3 Alarm Trip-lock 9-1
Contents VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
8.3 Warning and Alarm Displays
9-1
8.4 Warning and Alarm Definitions
9-2
8.5 Fault Messages
9-5
9 Basic Troubleshooting
10-1
9.1 Start Up and Operation
10-1
10 Specifications
11-1
10.1 Power-dependent Specifications
11-1
10.2 General Technical Data
11-2
10.3 Fuse Tables
11-7
10.3.1 Protection 11-7
10.3.2 Non UL Compliance 11-7
10.3.3 UL Compliance 11-8
10.3.4 Connection Tightening Torques 11-8
12 Index
12-1
Contents VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
Contents VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
1Introduction
1.1 Exploded Views
Figure 1.1 D1 Interior Components
Figure 1.2 Close-up View: LCP and Control Functions
Introduction VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark 1-1
1 1
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
1 LCP (Local Con trol Panel) 9 Relay 2 (04, 05, 06)
2 RS-485 serial bus connector 10 Lifting ring
3 Digital I/O and 24 V power supply 11 Mounting slot
4 Analog I/O con nector 12 Cable clamp (PE)
5 USB connector 13 Earth (ground)
6 Serial bus terminal switch 14 Motor output terminals 96 (U), 97 (V), 98 (W)
7 Analog switches (A53), (A54) 15 Mains input terminals 91 (L1), 92 (L2), 93 (L3)
8 Relay 1 (01, 02, 03)
Table 1.1
1.2 Purpose of the Manual
This manual is intended to provide detailed information for the installation and start up of the frequency converter. 2 Installation provides requirements for mechanical and electrical installation, including input, motor, control and serial communications wiring, and control terminal functions. 3 Start Up and Commissioning provides detailed procedures for start up, basic operational programming, and functional testing. The remaining chapters provide supplementary details. These details include user interface, detailed programming, application examples, start-up troubleshooting, and specifications.
1.3 Additional Resources
Other resources are available to understand advanced frequency converter functions and programming.
The VLT® Programming Guide provides greater detail on working with parameters and many application examples.
The VLT® Design Guide is intended to provide detailed capabilities and functionality to design motor control systems.
Optional equipment is available that may change some of the procedures described. Reference the instructions supplied with those options for specific requirements. Contact the local Danfoss supplier or visit the Danfoss website for downloads or additional information.
1.4 Product Overview
A frequency converter is an electronic motor controller that converts AC mains input into a variable AC waveform output. The frequency and voltage of the output are regulated to control the motor speed or torque. The frequency converter can vary the speed of the motor in response to system feedback, such as position sensors on a conveyor belt. The frequency converter can also regulate
the motor by responding to remote commands from external controllers.
In addition, the frequency converter monitors the system and motor status, issues warnings or alarms for fault conditions, starts and stops the motor, optimizes energy efficiency, and offers many more control, monitoring, and efficiency functions. Operation and monitoring functions are available as status indications to an outside control system or serial communication network.
1.5 Internal Controller Functions
Figure 1.3 is a block diagram of the frequency converter's internal components. See Table 1.2 for their functions.
Figure 1.3 Frequency Converter Block Diagram
Area Title Functions
1Mains input•Three-phase AC mains power
supply to the frequency
converter
2Rectifier
The rectifier bridge converts
the AC input to DC current to
supply inverter power
3DC bus
Intermediate DC-bus circuit
handles the DC current
Introduction VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
1-2 MG21E122 - VLT® is a registered Danfoss trademark
1
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
Area Title Functions
4 DC reactors
Filter the intermediate DC
circuit voltage
Prove line transient protection
Reduce RMS current
Raise the power factor
reflected back to the line
Reduce harmonics on the AC
input
5 Capacitor bank
Stores the DC power
Provides ride-through
protection for short power
losses
6Inverter
Converts the DC into a
controlled PWM AC waveform
for a controlled variable
output to the motor
Area Title Functions
7 Output to motor•Regulated three-phase output
power to the motor
8 Control circuitry
Input power, internal
processing, output, and motor
current are monitored to
provide efficient operation
and control
User interface and external
commands are monitored and
performed
Status output and control can
be provided
Table 1.2 Frequency Converter Internal Components
1.6 Frame Sizes and Power Ratings
kW rated frequency converters
kW High Overload 75 90 110 132 160 200 250 315 315
kW Normal Overloa d 90 110 132 160 200 250 315 355 400
400 V D3h D3h D3h D4h D4h D4h
500 V D3h D3h D3h D4h D4h D4h
525 V D4h D3h D3h D4h D4h D4h D4h
690 V D3h D3h D3h D4h D4h D4h
Table 1.3
Horsepower rated frequency converters
HP High
Overload
100 125 150 200 250 300 350 350
HP Normal
Overload
125 150 200 250 300 350 400 450
460 V D3h D3h D3h D4h D4h D4h
575 V D3h D3h D3h D4h D4h D4h D4h
Table 1.4
Introduction VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark 1-3
1 1
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
Introduction VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
1-4 MG21E122 - VLT® is a registered Danfoss trademark
1
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
2 Installation
2.1 Planning the Installation Site
CAUTION
Before performing the installation it is important to plan the installation of the frequency converter. Neglecting this may result in extra work during and after installation.
Select the best possible operation site by considering the following (see details on the following pages, and the respective Design Guides):
Ambient operating temperature
Installation method
How to cool the unit
Position of the frequency converter
Cable routing
Ensure the power source supplies the correct voltage and necessary current
Ensure that the motor current rating is within the maximum current from the frequency converter
If the frequency converter is without built-in fuses, ensure that the external fuses are rated correctly.
Installation in High Altitudes
Voltage Altitude Restrictions
380-500 V At altitudes above 3 km, contact Danfoss regardin g
PELV
525-690 V At altitudes above 2 km, contact Danfoss regardin g
PELV.
Table 2.1
2.2 Pre-Installation Check List
Before unpacking the frequency converter, ensure the packaging is intact. If any damage has occurred, immediately contact the shipping company to claim the damage.
Before unpacking the frequency converter, locate it as close as possible to the final installation site.
Compare the model number on the nameplate to what was ordered to verify the proper equipment.
Ensure each of the following are rated for the same voltage:
Mains (power)
Frequency converter
Motor
Ensure that frequency converter output current rating is equal to or greater than motor full load current for peak motor performance.
Motor size and frequency converter power must match for proper overload protection.
If frequency converte r rating is less than motor, full motor output cannot be achieved.
2.3 Mechanical Installation
2.3.1 Cooling
Top and bottom clearance for air cooling must be provided. Generally, 225 mm (9 in) is required.
Improper mounting can result in over heating and reduced performance
Derating for temperatures starting between 45° C (113° F) and 50° C (122° F) and elevation 1000 m (3300 ft) above sea level must be considered. See
VLT
®
Design Guide for detailed information.
The high power Danfoss VLT frequency converters utilize a back-channel cooling concept that removes heatsink cooling air, which carries approximately 90% of the heat out of the back channel of the frequency converters. The back-channel air can be redirected from the panel or room using one of the kits below.
Duct cooling A back-channel cooling kit is available to direct the heatsink cooling air out of the panel when an IP20/chassis frequency converters is installed in a Rittal enclosure. Use of this kit reduces the heat in the panel and smaller door fans can be specified on the enclosure.
Cooling out the back (top and bottom covers) The back channel cooling air can be ventilated out of the room so that the heat from the back channel is not dissipated into the control room.
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark 2-1
2
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
A door fan(s) is required on the enclosure to remove the heat not contained in the backchannel of the frequency converters and any additional losses generated by other components inside the enclosure. The total re quired air flow must be calculated so that the appropriate fans can be selected.
Airflow The necessary airflow over the heat sink must be secured. The flow rate is shown in Table 2.2.
The fan runs for the following reasons:
AMA
DC Hold
Pre-Mag
DC Brake
60% of nominal current is exceeded
Specific heatsink temperature exceeded (power size dependent).
Specific Power Card ambient temperature exceeded (power size dependent)
Specific Control Card ambient temperature exceeded
Frame Door fan/top fan Heatsink fan
D1h/D3h
102 m
3
/hr (60 C FM) 420 m3/hr (250 CFM)
D2h/D4h
204 m
3
/hr (120 CFM) 8 40 m3/hr (500 CFM)
Table 2.2 Airflow
2.3.2 Lifting
Always lift the frequency converter using the dedicated lifting eyes. Use a bar to avoid bending the lifting holes.
Figure 2.1 Position Lifting Straps where Indicated
CAUTION
The angle from the top of the frequency converter to the lifting cables should be 60 ° or greater.
2.3.3 Wall Mounting - IP21 (NEMA 1) and IP54 (NEMA 12) Units
Consider the following before selecting the final instal­lation site:
Free space for cooling
Access to open the door
Cable entry from the bottom
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
2-2 MG21E122 - VLT® is a registered Danfoss trademark
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
2.4 Electrical Installation
2.4.1 General Requirements
This section contains detailed instructions for wiring the frequency converter. The following tasks are describ ed:
Wiring the motor to the frequency converter output terminals
Wiring the AC mains to the frequency converter input terminals
Connecting control and serial communication wiring
After power has been applied, checking input and motor power; programming control terminals for their intended functions
Figure 2.2
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark 2-3
2
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
WARNING
EQUIPMENT HAZARD!
Rotating shafts and electrical equipment can be haz ardous. All electrical work must conform to national and local electrical codes. It is strongly recommended that instal­lation, start up, and maintenance be performed only by trained and qualified personnel. Failure to follow these guidelines could result in death or serious injury.
CAUTION
WIRING ISOLATION!
Run input power, motor wiring and control wiring in three separate metallic conduits or use separated shielded cable for high frequency noise isolation. Failure to isolate power, motor and control wiring could result in less than optimum frequency converter and associated equipment performance.
For your safety, comply with the following requirements
Electronic controls equipment is connected to hazardous mains voltage. Extreme care should be taken to protect against electrical hazards when applying power to the unit.
Run motor cables from multiple frequency converters separately. Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out.
Field wiring terminals are not intended to receive a conductor one size larger.
Overload and Equipment Protection
An electronically activ ated function within the frequency converter provides overload protection for the motor. The overload calculates the level of increase to activate timing for the trip (controller output stop) function. The higher the current draw, the quicker the trip response. The overload provides Class 20 motor protection. See 8 Warnings and Alarms for details on the trip function.
Because the motor wiring carries high frequency current, it is important that wiring for mains, motor power, and control are run separately. Use metallic conduit or separated shielded wire. See Figure 2.3. Failure to isolate power, motor, and control wiring could result in less than optimum equipment performance.
All frequency converters must be provided with short-circuit and over-current protection. Input
fusing is required to provide this protection, see Figure 2.4. If not factory supplied, fuses must be provided by the installer as part of installation. See maximum fuse ratings in 10.3.1 Protection.
Figure 2.3 Example of Proper Electrical Installation Using Conduit
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
2-4 MG21E122 - VLT® is a registered Danfoss trademark
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
All frequency converters must be provided with short-circuit and over-current protection. Input fusing is required to provide this protection, see Figure 2.4. If not factory supplied, fuses must be provided by the installer as part of installation. See maximum fuse ratings in 10.3.1 Protection.
Figure 2.4 Frequency Converter Fuses
Wire Type and Ratings
All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements.
Danfoss recommends that all power connections be made with a minimum 75° C rated copper wire.
2.4.2 Earth (Grounding) Requirements
WARNING
EARTHING (GROUNDING) HAZARD!
For operator safety, it is important to earth (ground) the frequency converter properly in accordance with national and local electrical codes as well as instructions contained within this document. Do not use conduit connected to the frequency converter as a replacement for p roper grounding. Earth (ground) currents are higher than 3.5 mA. Failure to earth (ground) the frequency converter pro perly could result in death or serious injury.Earthing (grounding) hazard
NOTE!
It is the responsibility of the user or certified electrical installer to ensure correct earthing (grounding) of the equipment in accordance with national and local electrical codes and standards.
Follow all local and national electrical code s to earth (ground) electrical equipment properly.
Proper protective earthing (grounding) for equipment with earth (ground) currents higher than 3.5 mA must be established, see
2.4.2.1 Leakage Current (>3.5 mA).
A dedicated earth wire (ground wire) is r equired for input power, motor power and control wiring.
Use the clamps provided with the equipment for proper earth connections (ground connections).
Do not earth (ground) one frequency converter to another in a “daisy chain” fashion.
Keep the earth (ground) wire connections as short as possible.
Using high-strand wire to reduce electrical noise is recommended.
Follow motor manufacturer wiring requirements.
2.4.2.1 Leakage Current (>3.5 mA)
Follow national and local codes regarding pro tective earthing of equipment with a leakage current > 3.5 mA. Frequency converter technology implies high frequency switching at high power. This will generate a leakage current in the earth connection. A fault curren t in the frequency converter at the output power terminals might contain a DC component, which can charge the filter capacitors and cause a transient earth current. The earth leakage current depends on various system configurations including RFI filtering, screened motor cables, and frequency converter power.
EN/IEC61800-5-1 (Power Drive System Product Standard) requires special care if the leakage current exceeds 3.5 mA. Earthing (grounding) must be reinforced in one of the following ways:
Earth (ground) wire of at least 10 mm
2
Two separate earth (ground) wires both complying with the dimensioning rules.
See EN 60364-5-54 § 543.7 for further information.
Using RCDs Where residual current devices (RCDs)–also known as earth leakage circuit breakers (ELCBs)–are used, comply with the following: residual current de vices (RCDs)
Use RCDs of type B only, which are capable of detecting AC and DC currents.
Use RCDs with an inrush delay to prevent faults due to transient earth currents.
Dimension RCDs according to the system configu­ration and environmental considerations.
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark 2-5
2
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
2.4.2.2 Earthing (Grounding) IP20 Enclosures
The frequency converter can be earthed (grounded) using conduit or shielded cable. For earthing (grounding) of the power connections, use the dedicated earthing (grounding) points as shown in Figure 2.6.
Figure 2.5 Earthing (Grounding) Points for IP20 (Chassis)
Enclosures
2.4.2.3 Earthing (Grounding) IP21/54 Enclosures
The frequency converter can be earthed (grounded) using conduit or shielded cable. For earthing (grounding) of the power connections, use the dedicated earthing (grounding) points as shown in Figure 2.6.
Figure 2.6 Earth ing (Grounding) for IP21/54 Enclosures.
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
2-6 MG21E122 - VLT® is a registered Danfoss trademark
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
2.4.3 Motor Connection
WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple frequency converters separately. Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out. Failure to run output motor cables separately could result in death or serious injury.
For maximum cable sizes, see 10.1 Power- dependent Specifications..
Comply with local and national electrical codes for cable sizes.
Gland plates are provided at the base of IP21/54 and higher (NEMA1/12) units.
Do not install power factor correction capacitors between the frequency converter and the motor.
Do not wire a starting or pole-changing device between the frequency converter and the motor.
Connect the 3-phase motor wiring to terminals 96 (U), 97 (V), and 98 (W).
Earth (ground) the cable in accordance with the instructions provided.
Torque terminals in accordance with the information provided in 10.3.4 Connection
Tightening Torques
Follow motor manufacturer wiring requirements.
Figure 2.7 Termi nal Locations D1h
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark 2-7
2
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
Figure 2.8 Termi nal Locations D3h
Figure 2.9 Termi nal Locations D2h
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
2-8 MG21E122 - VLT® is a registered Danfoss trademark
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
Figure 2.10 Termina l Locations D4h
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark 2-9
2
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
2.4.4 Motor Cable
The motor must be connected to terminals U/T1/96, V/ T2/97, W/T3/98. Earth (ground) to terminal 99. All types of three-phase asynchronous standard motors can be used with a frequency converter unit. The factory settin g is for clockwise rotation with the frequency converter output connected as follows:
Terminal No. Function
96, 97, 98, 99 Mains U/T1, V/T2, W/T3
Earth (ground)
Table 2.3
2.4.5 Motor Rotation Check
The direction of rotation can be changed b y switching two phases in the motor cable or by changing the setting of 4-10 Motor Speed Direction.
Terminal U/T1/96 connected
to U-phase
Terminal V/T2/97 connected
to V-phase
Terminal W/T3/98
connected to W-phase
Table 2.4
A motor rotation check can be performed using1-28 Motor Rotation Check and following the steps shown i n the display.
2.4.6 AC Mains Connection
Size wiring is based upon the input current of the frequency converter.
Comply with local and national electrical codes for cable sizes.
Connect 3-phase AC input power wiring to terminals L1, L2, and L3 (see Figure 2.11).
Figure 2.11 Connecting to AC Mains
1 Mains connection
2 Motor connection
Table 2.5
Earth (ground) the cable in accordance with the instructions provided.
All frequency converters may be used with an isolated input source as well as with earth (ground) reference power lines. When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg (grounded delta), set 14-50 RFI Filter to OFF. When off, the internal RFI filter capacitors between the chassis and the intermediate circui t are isolated to avoid damage to the intermediate circuit and to reduce earth (ground) capacity currents in accordance with IEC 61800-3.
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
2-10 MG21E122 - VLT® is a registered Danfoss trademark
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
2.5 Control Wiring Connection
Isolate control wiring from high power components in the frequency converter.
If the frequency converter is connected to a thermistor, for PELV isolation, optional thermistor control wiring must be reinforced/double insulated. A 24 V DC supply voltage is recommended.
2.5.1 Access
All terminals to the control cables are loc ated underneath the LCP on the inside of the frequency converter. To access, open the door (IP21/54) or remove the front panel (IP20).
2.5.2 Using Screened Control Cables
Danfoss recommends braided screened/armoured cables to optimise EMC immunity of the control cables and the EMC emission from the motor cables.
The ability of a cable to reduce the incoming and outgoing radiation of electric noise depends on the transfer impedance (Z
T
). The screen of a cable is normally designed to reduce the transfer of electric noise; however, a screen with a lower transfer impedance (Z
T
) value is more effective than a screen with a higher transfer impedance (Z
T
).
Transfer impedance (Z
T
) is rarely stated by cable manufac­turers but it is often possible to estimate transfer impedance (Z
T
) by assessing the physical design of the
cable.
Transfer impedance (Z
T
) can be assessed on the basis of
the following factors:
- The conductibility of the screen material.
- The contact resistance between the individual screen conductors.
- The screen coverage, i.e. the physical area of the cable covered by the screen - often stated as a percentage value.
- Screen type, i.e. braided or twisted pattern.
a. Aluminium-clad with copper wire.
b. Twisted copper wire or armoured steel wire cable.
c. Single-layer braided co pper wire with varying
percentage screen coverage. This is the typical Danfoss reference cable.
d. Double-layer braided copper wire.
e. Twin layer of braided copper wire with a
magnetic, screened/armoured intermediate layer.
f. Cable that runs in copper tube or steel tube.
g. Lead cable with 1.1 mm wall thickness.
Figure 2.12
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark 2-11
2
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
2.5.3 Earthing (Grounding) of Screened Control Cables
Correct screening The preferred method in most cases is to secure control and serial communication cables with screening clamps provided at both ends to ensure best possible high frequency cable contact. If the earth (ground) potential between the frequency converter and the PLC is different, electric noise may occur that will disturb the entire system. Solve this problem by fitting an equalizing cable next to the control cable. Minimum cable cross section: 16 mm
2
.
Figure 2.13
1
Min. 16 mm
2
2Equalizing cable
Table 2.6
50/60 Hz earth (ground) loops With very long control cables, earth loops (ground loops) may occur. To eliminate earth (ground) loops, connect one end of the screen-to-earth (ground) with a 100 nF capacitor (keeping leads short).
Figure 2.14
Avoid EMC noise on serial communication This terminal is connected to earth (ground) via an internal RC link. Use twisted-pair cables to reduce interference between conductors. The recommended method is shown below:
Figure 2.15
1
Min. 16 mm
2
2 Equalizing cable
Table 2.7
Alternatively, the connection to terminal 61 can be omitted:
Figure 2.16
1
Min. 16 mm
2
2 Equalizing cable
Table 2.8
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
2-12 MG21E122 - VLT® is a registered Danfoss trademark
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
2.5.4 Control Terminal Types
Terminal functions and default settings are summarized in
2.5.6 Control Terminal Functions.
Figure 2.17 Control Terminal Locations
Connector 1 provides four programmable digital input terminals, two additional digital terminals programmable as either input or output, a 24 V DC terminal supply voltage, and a common for optional customer supplied 24 V DC voltage.
Connector 2 terminals (+)68 and (-)69 are for an RS-485 serial communications connection.
Connector 3 provides two analog inputs, one analog output, 10 V DC supply voltage, and commons for the inputs and output.
Connector 4 is a USB port available for use with the MCT 10 Set-up Software.
Also provided are two Form C relay outputs that are in various locations depending upon the frequency converter configuration and size.
Some options available for ordering with the unit may provide additional terminals. See the manual provided with the equipment option.
2.5.5 Wiring to Control Terminals
Terminal plugs can be removed for easy access.
Figure 2.18
2.5.6 Control Terminal Functions
Frequency converter functions are commanded by receiving control input signals.
Each terminal must be programmed for the function it will be supporting in the parameters associated with that terminal. See 5 Programming and 6 Application Examplesfor terminals and associated parameters.
It is important to confirm that the control terminal is programmed for the correct function. See 5 Programming for details on accessing parameters and programming.
The default terminal programming is intended to initiate frequency converter functioning in a typical operational mode.
2.6 Serial Communication
RS-485 is a two-wire bus interface compatible with multi­drop network topology, i.e. nodes can be connected as a bus, or via drop cables from a common trunk line. A total of 32 nodes can be connected to one network segment. Repeaters divide network segments. Each repeater functions as a node within the segment i n which it is installed. Each nod e connected within a giv en network must have a unique node address across all segments. Terminate each segment at both ends, using either the termination switch (S801) of the frequency converter or a biased termination resistor network. Always use screened twisted pair (STP) cable for bus cabling, and always follow good common installation practice. Low-impedance earth (ground) connection of the screen at every node is important, including at high frequencies. Thus, connect a large surface of the sc reen to earth
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
MG21E122 - VLT® is a registered Danfoss trademark 2-13
2
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
(ground), for example with a cable clamp or a conductive cable gland. It may be necessary to apply potential­equalizing cables to maintain the same earth (ground) potential throughout the network. Particularly in instal­lations with long cables. To prevent impedance mismatch, always use the same type of cable throughout the entire network. When connecting a motor to the frequency converter, always use screened motor cable.
Cable Screened twisted pair (STP)
Impedance
120
Ω
Max. cable length 1200 m (including drop lines)
500 m station-to-station
Table 2.9
Installation VLT® Automation VT Drive FC 322 D-Frame Instruction Manual
2-14 MG21E122 - VLT® is a registered Danfoss trademark
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20776-Danfoss-131X8139-VLT-Automation-VT-Drive-VFD-FC322-230V-20-HP.aspx
Loading...
+ 56 hidden pages