Danfoss VLT FC 100, VLT FC 300 Series, VLT FC 200 Series Series Manual

FC 100/ 200/ 300 DeviceNet Contents
Contents
1. Introduction
Safety Note 6
Assumptions 9
Hardware 9
Background Knowledge 9
Abbreviations 11
2. How to Install
Cabling 13
Installation of Option in the Frequency 17
3. How to Configure the System
Configure the Master 21
Configure the Frequency Converter 21
DeviceNet Process Control Modes 23
I/O Assembly Instances 25
Process Data 25
5
13
19
23
ODVA Control Profile 27
Danfoss FC Control Profile 32
5. How to Access the Parameters
Explicit Messages 39
Object Classes 39
DeviceNet Object Classes 39
Danfoss Object Classes 50
Reading/Writing to Parameters with Index 51
6. Parameters
Parameter List 66
Data Types Supported 67
7. Application Examples
Example: Working with Instance 101/151 Process 69
8. Troubleshooting
Troubleshooting 73
39
53
69
73
Index
81
MG.33.D3.02 - VLT® is a registered Danfoss trademark
1
Contents FC 100/ 200/ 300 DeviceNet
Contents | Illustration
Illustration 1.1: 9
Illustration 2.1: 13
2
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet Contents
Contents | Table
Table 8.1: LED: Module Status (MS) 73
Table 8.2: LED: Network Status (NS) 74
MG.33.D3.02 - VLT® is a registered Danfoss trademark
3
1
1. Introduction FC 100/ 200/ 300 DeviceNet
4
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 1. Introduction
1. Introduction
1.1.1. Copyright, Limitation of Liability and Revision Rights
This publication contains information proprietary to Danfoss A/S. By accepting and using this manual the user agrees that the information contained herein will be used solely for operating equipment from Danfoss A/S or equipment from other vendors provided that such equipment is intended for communication with Danfoss equipment over a PROFIBUS serial communication link. This publication is protected under the Copyright laws of Denmark and most other countries.
Danfoss A/S does not warrant that a software program produced according to the guidelines pro­vided in this manual will function properly in every physical, hardware or software environment.
Although Danfoss A/S has tested and reviewed the documentation within this manual, Danfoss A/ S makes no warranty or representation, either express or implied, with respect to this documen­tation, including its quality, performance, or fitness for a particular purpose.
In no event shall Danfoss A/S be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained in this manual, even if advised of the possibility of such damages. In particular, Danfoss A/S is not responsible for any costs including but not limited to those incurred as a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third parties.
1
Danfoss A/S reserves the right to revise this publication at any time and to make changes in its contents without prior notice or any obligation to notify previous users of such revisions or changes.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
5
1
1. Introduction FC 100/ 200/ 300 DeviceNet
1.2.1. Safety Note
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect installation of the motor, frequency converter or fieldbus may cause dam­age to the equipment, serious personal injury or death. Consequently, the instruc­tions in this manual, as well as national and local rules and safety regulations, must be complied with.
1.2.2. Safety Regulations
1. The frequency converter must be disconnected from mains if repair work is to be carried out. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.
2. The [STOP/RESET] key on the control panel of the frequency converter does not dis­connect the equipment from mains and is thus not to be used as a safety switch. 3. Correct protective earthing of the equipment must be established, the user must be pro­tected against supply voltage, and the motor must be protected against overload in accordance with applicable national and local regulations.
3. Correct protective earthing of the equipment must be established, the user must be pro­tected against supply voltage, and the motor must be protected against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is not included in the factory setting. If this function is desired, set par. 1-90
ETR warning
motor frequency. For the North American market: The ETR functions provide class 20 motor overload protection in accordance with NEC.
6. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.
7. Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when load sharing (linking of DC intermediate circuit) and external 24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before commencing repair work.
. Note: The function is initialised at 1.16 x rated motor current and rated
Motor Thermal Protection
to data value
ETR trip
or data value
1.2.3. Warning Against Unintended Start
1. The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop, while the frequency converter is connected to mains. If per­sonal safety considerations make it necessary to ensure that no unintended start occurs, these stop functions are not sufficient.
2. While parameters are being changed, the motor may start. Consequently, the stop key [STOP/RESET] must always be activated; following which data can be modified.
3. A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or a fault in the supply mains or the motor con­nection ceases.
1.2.4. Warning
Touching the electrical parts may be fatal - even after the equipment has been dis­connected from mains.
6
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 1. Introduction
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back up.
Please refer to the relevant Operating Instructions for further safety guidelines.
1
MG.33.D3.02 - VLT® is a registered Danfoss trademark
7
1
1. Introduction FC 100/ 200/ 300 DeviceNet
1.3. About this Manual
First time users can obtain the most essential information for quick installation and set-up in these chapters:
Introduction How to Install How to Configure the System Application Examples
For more detailed information including the full range of set-up options and diagnosis tools please refer to the chapters:
How to Control the Frequency Converter How to Access the Parameters Parameters Troubleshooting
1.4. Technical Overview
DeviceNet is a low-level network that standardizes communications between industrial devices (sensors, limit switches, motor controls) and high-level devices (controllers). DeviceNet follows the Open Systems Interconnection (OSI) model and is based on CAN technology for Media Access Control and Physical Signalling.
DeviceNet systems can be configured to operate in a master-slave or a distributed control archi­tecture using peer-to-peer communication. Up to 63 nodes in a multi-drop network topology are supported, and communication options can be powered directly from the bus, using the same cable for communication. Nodes can be removed or inserted without powering down the network.
Each node on the network has its own unique Media Access Control IDentifier (MAC ID) to dis­tinguish it on the network. The access control is based on the CSMA/CA (Carrier Sense Multiple Access / Collision Avoidance) principle, meaning that all nodes may have access to the network at the same time. If two nodes attempt to get control of the network bus simultaneously, the CAN protocol resolves the issue by arbitration. In this way collisions on the network are avoided.
DeviceNet defines device profiles for devices belonging to specific classes. For other devices, a custom class must be defined in order to make it DeviceNet compatible. This further enhances the interchangeability and interoperability of the network.
8
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 1. Introduction
Illustration 1.1: Topology
1
1.5. Assumptions
These operating instructions assume that you are using a Danfoss FC 100, 200 or 300 frequency converter with DeviceNet. It is also assumed that as master you are using a PLC or PC equipped with a serial communication card supporting all the DeviceNet communication services required by your application. Furthermore, it is assumed that all requirements stipulated in the DeviceNet standard as well as those set up in the AC Drive Profile and those pertaining to the VLT frequency converter are strictly observed as well as all limitations therein fully respected.
1.6. Hardware
These operating instructions relate to the DeviceNet option type no. 130B1102 and 130B1201.
1.7. Background Knowledge
The Danfoss DeviceNet is designed to communicate with any master abiding by the DeviceNet standard. It is therefore assumed that you have full knowledge of the PC or PLC you intend to use as a master in your system. Any questions pertaining to hardware or software produced by any other manufacturer is beyond the scope of these operating instructions and is of no concern to Danfoss. If you have questions about how to set up master - master communication or commu­nication to a non-Danfoss slave, please consult the appropriate documentation.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
9
1
1. Introduction FC 100/ 200/ 300 DeviceNet
1.8. Available Literature
The following literature is available for the FC 100, 200 and 300 series.
Title
VLT HVAC Drive FC 100 Operating Instructions MG.11.AX.YY VLT HVAC Drive FC 100 Design Guide MG.11.BX.YY VLT HVAC Drive FC 100 Programming Guide MG.11.CX.YY VLT AQUA Drive FC 200 Operating Instructions MG.20.NX.YY VLT AQUA Drive FC 200 Design Guide MG.20.MX.YY VLT AQUA Drive FC 200 Programming Guide MG.20.OX.YY VLT AutomationDrive FC 300 Operating Instructions MG.33.AX.YY VLT AutomationDrive FC 300 Design Guide MG.33.BX.YY VLT AutomationDrive FC 300 Programming Guide MG.33.MX.YY VLT AutomationDrive FC 100, 200 and 300 PROFIBUS Operating Instructions VLT AutomationDrive FC 100, 200 and 300 DeviceNet Operating In­structions VLT AutomationDrive FC 300 MCT 10 Software Dialogue MG.33.EX.YY PROFIBUS DP V1 Design Guide MG.90.EX.YY
X = Revision number Y = Language code Please also refer to mation.
www.danfoss.com/drives
for frequently asked questions and additional infor-
Literature no.
MG.33.CX.YY
MG.33.DX.YY
10
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 1. Introduction
1.9. Abbreviations
ACK ACKnowledge BOC Bus Off Counter BOOL BOOLean expression CAN Controller Area Network CSMA/CA Carrier Sense Multiple Access/Collision Avoidance COS Change of State CTW Control Word EDS Electronic Data Sheet EMC Electromagnetic Compatibility ETR Electronic Thermal Relay FIFO First In First Out HF High Frequency HPFB High Performance Field Bus I/O Input/Output ISO International Standards Organization LCD Liquid Crystal Display LCP Local Control Panel LED Light Emitting Diode LSB Least Significant Bit MAC ID Media Access Control IDentifier MAV Main Actual Value MRV Main Reference Value MSB Most Significant Bit N/A Not Applicable ODVA Open DeviceNet Vendor Association OSI Open Systems Interconnection PC Personal Computer PCD Process Data PIW Peripheral Input Word PLC Programmable Logic Control PNU Parameter Number PPO Parameter-Process Data Object QW Peripheral Output Word SINT Signed Integer STW Status Word VSD Variable Speed Drive UDINT Unsigned Double Integer UNIT Unsigned Integer USINT Unsigned Short Integer
1
MG.33.D3.02 - VLT® is a registered Danfoss trademark
11
2
2. How to Install FC 100/ 200/ 300 DeviceNet
12
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 2. How to Install
2. How to Install
2.1. Cabling
2.1.1. Cable Lengths
Baud rate Max total cable
length
125k baud 500 meters (1640 ft.) 6 meters (20 ft.) for one drop 156 meters (512 ft.) 250k baud 250 meters (820 ft.) 78 meters (256 ft.) 500k baud 100 meters (328 ft.) 39 meters (128 ft.)
2.1.2. Cable Specifications
The cable used should be according to ODVA specifications.
Be aware that the ODVA “Flat Cable” is an unscreened cable type, and is not suited for use with frequency converters.
2
Drop length Maximum per drop Cumulative maxi-
mum
Illustration 2.1: ODVA “Thin Cable” cross sec­tion
MG.33.D3.02 - VLT® is a registered Danfoss trademark
13
2
2. How to Install FC 100/ 200/ 300 DeviceNet
2.1.3. EMC Precautions
The following EMC precautions are recommended in order to achieve interference-free operation of the DeviceNet network. Additional EMC information is available in the relevant FC 100, 200 or 300 Operating Instructions and Design Guides.
NB!
Relevant national and local regulations, for example regarding protective earth con­nection, must be observed.
The DeviceNet communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable to the other. Normally a distance of 200 mm (8 inches) is sufficient, but it is generally recommended to keep the greatest possible distance between the cables, especially where cables run in parallel over long distances. If the DeviceNet cable has to cross a motor and brake resistor cable they must cross each other at an angle of 90 degrees.
14
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 2. How to Install
2.1.4. Connection of the Cable Screen
Danfoss recommends connection of the screen of the DeviceNet cable to ground at both ends of the cable at every DeviceNet station (see Danfoss recommendation for further details). Low im­pedance ground connection of the screen is very important, also at high frequencies. Achieve this by connecting the surface of the screen to ground, for example by means of a cable clamp or a conductive cable gland. The frequency converter package includes various clamps and brackets to enable a proper ground connection of the DeviceNet cable screen. The screen connection re­quired for CE and EMC compliance is shown in the following drawing.
2.1.5. ODVA Recommendation
The Screen must be connected to ground at only one point on the network.
NB!
Please note that this recommen­dation conflicts with the correct EMC installation.
2
2.1.6. Earth Connection
It is important that all stations connected to the DeviceNet network are connected to the same earth potential. The earth connection must have a low HF (high frequency) impe­dance. This can be achieved by connecting a large surface area of the cabinet to ground, for example by mounting the frequency con­verter on a conductive rear plate.
NB!
Particularly when there are long distances between the stations in a DeviceNet network, it may be necessary to use additional potential equalizing cables, con­necting the individual stations to the same earth potential.
Pin no. Termi-
nal
1 V- Black GND 2 CAN_L Blue CAN
3 Drain (bare) Screen 4 CAN_H White CAN
5 V+ Red +24 V
Colour Name
LOW
HIGH
MG.33.D3.02 - VLT® is a registered Danfoss trademark
15
2
2. How to Install FC 100/ 200/ 300 DeviceNet
2.1.7. DeviceNet Connection
It is essential to terminate the bus line prop­erly. A mismatch of impedance may result in reflections on the line that will corrupt data transmission. The DeviceNet control card is provided with a plug-cable connector. When a plug connector is used as a splice between two trunk lines, the removal of devices will not sever the network. If required, strain relief must be provided by the developer. In current installations of this type of connector, the strain relief is attached to the product.
NB!
Install wires only when the net­work is inactive. This will pre­vent problems such as shorting the network supply or disrupting communications.
2.1.8. DeviceNet Termination
Termination resistors should be installed at each end of the bus line. The resistors must be mounted between terminal 2 (CAN_L) and terminal 4 (CAN_H) and should have the fol­lowing specification: 121 Ohm, 1 % Metal film, 1/4 Watt
2.1.9. Drop Cable
An alternative to splicing two trunk lines in the connector on the control card is to use a De­viceNet connection box or a T-connector. For this kind of installation a drop cable is availa­ble as an option.
Drop cable order number: 195N3113
The connector is a micro-style, male, with ro­tating coupling nut, and fits into a Micro De­vice port.
2.1.10. Network Power Consumption
The DeviceNet option is powered via the internal power supply in the drive. The network voltage (+24 V) is detected only to determine if the bus is energized or not, thus the current draw from the network is negligible.
16
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 2. How to Install
2.2. Installation of Option in the Frequency
To install a fieldbus option in the frequency converter you will need:
- The fieldbus option
- Fieldbus option adaptor frame for the frequency converter. This frame is deeper than the
standard frame, to allow space for the fieldbus option beneath.
- Cable holders
2
Instructions:
- Remove the LCD panel from the frequency converter.
- Remove the frame located beneath and discard.
- Push the option into place. Two positions are possible, with cable terminal facing either
up or down. The cable up position is often most suitable when several frequency con­verters are installed side by side in a rack, as this position permits shorter cable lengths.
- Push the fieldbus option adaptor frame for the frequency converter into place.
- Replace the LCD panel.
- Attach cable.
- Fasten the cable in place using cable holders. The top surface of the frequency converter
has pre-drilled threaded holes for attaching the cable holders to the unit.
- If an option is installed after initial power-up the frequency converter will be tripped and
display: Alarm 67
Option Change
.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
17
3
3. How to Configure the System FC 100/ 200/ 300 DeviceNet
18
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 3. How to Configure the System
3. How to Configure the System
3.1. Configure the DeviceNet Network
All DeviceNet stations that are connected to the same bus network must have a unique station address. The DeviceNet address of the frequency converter can be selected via:
- Hardware switches (default 63)
- Parameter 10-02
63)
- Class code 0X03, Instance 1, Attrib-
ute 1
MAC ID
(default
3.1.1. Setting the DeviceNet Address using the Hardware Switches
Setting the DeviceNet Address using the Hardware Switches: Using the hardware switches it is possible to select an address range from 0-63 (factory setting 63) according to the table below:
Switch Address value - - +32 +16 +8 +4 +2 +1 Ex. address 5 - - OFF OFF OFF ON OFF ON Ex. address 20 - - OFF ON OFF ON OFF OFF Ex. address 35 - - ON OFF OFF OFF ON ON
8 7 6 5 4 3 2 1
3
NB!
Switch off the power supply before changing the hardware switches.
The address change will come into effect at the next power-up, and can be read in par. 10-02
MAC ID
.
3.1.2. Setting the DeviceNet Address via Par. 10-02
The address can be set via par. 10-02 setting). The address change will come into effect at the next power-up.
MAC ID
if the hardware switches are set to 63 (factory
MAC ID
3.1.3. Setting the DeviceNet Address with the Object Class Code 0x03, Attribute 1, Instance 1
The address can be set via the DeviceNet object class code 0x03 attribute 1 command if the hardware switch is set to 63 (factory setting). A new address becomes effective immediately after the class code 0x03, Instance 1, Attribute 1 command.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
19
3
3. How to Configure the System FC 100/ 200/ 300 DeviceNet
3.1.4. Baud Rate Setting
All DeviceNet stations connected to the same bus network must have the same Baud rate. The baud rate of the frequency converter can be selected via:
- Hardware switches
- Par. 10-01
- Object Class code 0x03, Instance 1, Attribute 2.
Baudrate Select
(default 125k Baud)
3.1.5. Setting the DeviceNet Baud Rate using the H ardware Switches
Using the hardware switches it is possible to select a baud rate of 125k baud (factory set­ting), 250k baud or 500 k baud according to the following table:
NB!
Switch off the power supply before changing the hardware switches.
The baud rate change will come into effect at the next power-up, and can be read in par. 10-01
Baudrate select
.
3.1.6. Setting the DeviceNet Baud Rate via Par. 10-01
lect
The baud rate can be set via par. 10-01 to ON (factory setting). The baud rate change will come into effect at the next power-up.
Baudrate select
Baud rate switch Par. 10-01 1 1 125 k Baud 0 0 250 k Baud 0 1 500 k Baud 1 0
8 7
Baudrate se-
if the hardware switches 1 and 2 are set
3.1.7. Setting the DeviceNet Baud Rate with the Object Class Code 0x03 Attribute 2
The baud rate can be set via the DeviceNet object class code 0x03 attribute 2 command, if the hardware switches 1 and 2 are set to ON (factory setting). A new baud rate becomes effective immediately after the class code 0x03 attribute 2 command.
20
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 3. How to Configure the System
3.2. Configure the Master
3.2.1. EDS File
A large part area of the system configuration is the setting of application related parameters. EDS (Electronic Data Sheet) files simplify the setting up of most of the DeviceNet configurable param­eters. Danfoss provides a generic English EDS file covering all voltage and power sizes, for off­line configuration. The EDS file can be downloaded from http://www.danfoss.com/drives.
NB!
The EDS-file does not contain all parameters but a selected, limited number of pa­rameters with generic minimum, maximum and default values.
3.3. Configure the Frequency Converter
3.3.1. VLT Parameters
3
Pay particular attention to the following parameters when configuring the frequency converter with a DeviceNet interface. Please refer to the Parameters chapter for more details of each pa­rameter.
Par. 0-40
•Par. 8-10
Par. 8-50 to 8-56 (see section
Par. 8-03 to 8-05. The reaction in the event of a bus time out is set via these parameters
Par.. 10-01
Par. 10-02
3.3.2. LEDs
The DeviceNet control card contains two bi-colour (green/red) LEDs for each connector hook-up port, to indicate the state of the device and the network respectively. For details of the range of communications status indicated by the LEDs, please refer to the Troubleshooting chapter.
[Hand on] key on LCP
If the Hand button on the frequency converter is activated, control of the drive via the DeviceNet interface is disabled. After initial power-up the frequency converter will auto­matically detect whether a fieldbus option is installed in slot A, and set par. 8-02
Word Source
already commissioned drive, it will not change par. 8-02 but will enter Trip Mode, and the frequency converterwill display an error.
Choose between the Danfoss FC Profile and the ODVA profile. Select the desired Devi­ceNet instance in par. 10-10
trol commands with digital input command of the control card.
to [Option A]. If an option is added to, changed in or removed from an
Control Word Profile
Baud rate
MAC ID
. Default is 125 kbps.
. Default is 63.
.
(see section
Process Data Type Selection
Parameters
How to Control the Frequency Converter
). Selection of how to gate the DeviceNet con-
Control
.
).
MG.33.D3.02 - VLT® is a registered Danfoss trademark
21
4
4. How to Control the Frequency Converter FC 100/ 200/ 300 DeviceNet
22
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 4. How to Control the Frequency Converter
4. How to Control the Frequency Converter
4.1. DeviceNet Process Control Modes
This section describes two of three possible process control modes: Polling and Change of State (COS). The third FC control mode uses the acyclical mode Explicit Messaging via the Standard DeviceNet Control Supervisory object CLASS 29H. The Control Supervisory object is described within the
DeviceNet Object Classes
4.1.1. Polling
section,
How to Access the Parameters
chapter.
4
This is a classical Master-Slave connection and the standard DeviceNet operation mode. The master controls the data exchange by sending cyclical poll-requests to the connected slaves, and the slaves answers by sending a poll-re­sponse to the master. The master can control and monitor the frequency converter by poll­ing the DeviceNet or Danfoss objects (I/O In­stances).
4.1.2. Change of State, COS
This an event-controlled operation mode used to minimize network traffic. Messages are trans­mitted only if a defined state or value has changed. The condition for triggering a COS message is determined by the insertion of COS-filters (parameters 10-20 to 10-23), for each bit in the different PCD-words. The filter acts like a logical AND-function: If a bit in the filter is set to “1”, the COS-function triggers upon a change to the corresponding bit for the PCD-word.
POLLED I/O
Master slave
Slave master
CTW MRV
STW MAV
MG.33.D3.02 - VLT® is a registered Danfoss trademark
23
4
4. How to Control the Frequency Converter FC 100/ 200/ 300 DeviceNet
The figure below shows the different PCDs and their corresponding filter parameters.
Par. 10-20 to 10-23 can be used to filter out undesired events for COS. If a filter bit is set to 0, the corresponding I/0 Instance bit will be unable to produce a COS message. By default, all bits in the COS filters are set to 0.
In order to signal that the connection has not been interrupted, or the device is not powered off, a Heartbeat Message is transmitted within a specified time interval (Heartbeat Interval). This in­terval is defined in Attribute Heartbeat Time of the connection object, Class Code 0x05.
To prevent the device from producing heavy network traffic if a value changes frequently, the Production Inhibit Time (an attribute of the connection object) is defined. This parameter defines the minimum time between two COS messages.
The Attribute Expected Package Rate defines the maximum time between two COS messages even when the value is unchanged. In the event of COS connection, the Explicit Package Rate is identical with the Heartbeat Interval mentioned above. This timer is used both as transmission trigger and inactivity watchdog, depending upon whether the connection is producer or consumer.
24
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 4. How to Control the Frequency Converter
4.2. I/O Assembly Instances
I/O Assembly Instances are a number of defined process control objects with defined content comprising control and status information. The figure below shows the I/O Assembly Instance options for controlling and monitoring the frequency converter.
4
4.3. Process Data
Process data comprises the control and status data in the I/O Assembly Instances.
The CTW, MRV and STW and MAV have defined formats and functions, depending upon the I/O Instance chosen. PCD1 and PCD2 are freely configurable for instance 101/151 via par. 10-11 and 10-12.
The VLT DeviceNet provides a flexible way for the user to customize the number of Process Data (I/O words) and the functionality of each word. To activate the user definable process data, select the I/O Instance 101/151 in par. 10-10 to four words in the input and output area. This selection uses the Danfoss-specific profile for the Control word and Status word as well for the Main Reference Value/Main Actual Value.
The first two words are fixed on the VLT DeviceNet, whereas the user can select the input and output, PCD 3 and PCD 4. The number of PCDs active in a system is fixed to 2 words.
NB!
Selection of Instance 101/151 under par. 10-10 is only possible if FC Profile has been selected in par. 8-10
To enable use of PCD data from the VLT DeviceNet, configure the contents of each single PCD word in par. 10-11 to par. 10-11 and 10-12 are effected immediately in the PCD data.
Process Data Config Write
Process Data Type Selection
Control Word Profile
and par. 10-12
.
. This will change the I/O size
Process Data Config Read
. Changes
MG.33.D3.02 - VLT® is a registered Danfoss trademark
25
4
4. How to Control the Frequency Converter FC 100/ 200/ 300 DeviceNet
26
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 4. How to Control the Frequency Converter
4.4. ODVA Control Profile
4.4.1. Control Word under Instances 20/70 and 21/71
Control Word under Instances 20/70 and 21/71 Set par. 8-10
Control Word Profile
ODVA, and select the instance in par. 10-10
Process Data Type Selection
.
to
The control word in Instances 20 and 21 is defined in the overview to the right:
NB!
Note that the bits 00 and 02 in Instance 20 are identical with bits 00 and 02 in the more extensive Instance 21.
Bit In st anc e 20 Instance 21
00 Stop Run Fwd Stop Run Fwd 01 - - Stop Run Rev 02 No func-
03 - - - ­04 - - - ­05 - - - Net Ctrl 06 - - - Net Ref 07-15 - - - -
Bit = 0 Bit = 1 Bit = 0 Bit = 1
tion
Fault re­set
No func­tion
Fault re­set
Explanation of the Bits:
Bit 0, Run Fwd: Bit 0 = "0" means that the VLT frequency converter has a stop command. Bit 0 = "1" leads to a start command and the VLT frequency converter will start to run the motor clockwise.
4
Bit 1, Run Rev: Bit 1 = "0" leads to a stop of the motor. Bit 1 = "1" leads to a start of the motor.
Bit 2, Fault Reset: Bit 2 = "0" means that there is no reset of a trip. Bit 2 = "1" means that a trip is reset.
Bit 3, No function: Bit 3 has no function.
Bit 4, No function: Bit 4 has no function.
Bit 5, Net Control: Bit 5 = "0" means that the drive is controlled from the standard inputs. Bit 5 = "1" means that DeviceNet controls the drive.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
27
4. How to Control the Frequency Converter FC 100/ 200/ 300 DeviceNet
NB!
Please note that changes will affect par. 8-50 to 8-56.
Bit 6, Net Reference: Bit 6 = "0" Reference is from the standard inputs. Bit 6 = "1" Reference is from DeviceNet.
4
NB!
Please note that changes will affect parameters 3-15 to 3-17 Reference source X.
For the Speed reference, see section
.
21/71
Bus Speed Reference Value under Instances 20/70 and
28
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 4. How to Control the Frequency Converter
4.4.2. Status Word under Instances 20/70 and 21/71
The status word in Instances 70 and 71 is de­fined in the overview to the right:
NB!
Note that the bits 00 and 02 in Instance 70 are identical with bits 00 and 02 in the more extensive Instance 71.
4
Bit In st anc e 70 Instance 71
00 - Fault - Fault 01 - - - Warning 02 - Running
03 - - - Running
04 - - - Ready 05 - - - Ctrl from
06 - - - Ref. from
07 - - - At ref. 08-15 - - State Attribute
Bit = 0 Bit = 1 Bit = 0 Bit = 1
1 Fwd
- Running 1 Fwd
2 Rev.
Net
Net
Explanation of the Bits:
Bit 0, Fault: Bit 0 = "0" means that there is no fault in the frequency converter. Bit 0 = "1" means that there is a fault in the frequency converter.
Bit 1, Warning: Bit 0 = "0" means that there is no unusual situation. Bit 0 = "1" means that an abnormal condition has arisen.
Bit 2, Running 1: Bit 2 = "0" means that the drive is not in one of these states or that Run 1 is not set. Bit 2 = "1" means that the drive state attribute is enabled or stopping, or that Fault-Stop and bit 0 (Run 1) of the control word are set at the same time.
Bit 3, Running 2: Bit 3 = "0" means that the drive is in neither of these states or that Run 2 is not set. Bit 3 = "1" means that the drive state attribute is enabled or stopping, or that fault-stop and bit 0 (Run 2) of the control word are set at the same time.
Bit 4, Ready: Bit 4 = "0" means that the state attribute is in another state. Bit 4 = "1" means that the state attribute is ready, enabled or stopping.
Bit 5, Control from net: Bit 5 = "0" means that the drive is controlled from the standard inputs. Bit 5 = "1" means that DeviceNet has control (start, stop, reverse) of the drive.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
29
4. How to Control the Frequency Converter FC 100/ 200/ 300 DeviceNet
Bit 6, Ref from net: Bit 6 = "0" means that the reference comes from inputs to the drive. Bit 6 = "1" means that the reference comes from DeviceNet.
Bit 7, At reference: Bit 7 = "0" means that the motor is running, but that the present speed is different from the preset speed reference, i.e. the speed is being ramped up/down during start/stop. Bit 7 = "1" means that the drive and reference speeds are equal.
4
Bit 8 - 15, State attribute: (Instance 71 only) Represents the state attribute of the drive, as indicated in the table to the right:
For more detail of the actual output speed, see the section
20/70 and 21/71
.
Bit Num­ber 8 (Vendor specific) 9 Start up 10 Not ready 11 Ready 12 Enabled 13 Stopping 14 Fault stop 15 Faulted
Meaning
Actual Output Speed under Instances
30
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 4. How to Control the Frequency Converter
4.4.3. Bus Speed Reference Value under Instances 20/70 and 21/71
The speed reference value is transmitted to the frequency converter in the form of a 16­bit word. The value is transmitted as a whole number. Negative figures are formatted by means of 2’s complement.
The bus speed reference has the following format:
Par. 3-00 = "0" [ref
MIN
-> ref
] 0 (0000 Hex) [RPM] =>+ 32767 (7FFF Hex) [RPM]
MAX
4
Par. 3-00 = "1" [-ref
The actual reference [Ref. %] in the frequency converter depends on the settings in the following parameters: Par. 1-23 Par. 1-25 Par. 3-03
Note that if the bus speed reference is negative, and the control word contains a run reverse signal, the drive will run clockwise (- - is +).
Example:
Par. 1-25 Par. 1-23 Par. 3-03
In order to run the motor at 25%, the reference transmitted must be: (1420*0,25) = 355 = 163hex
163hex => 25% => Fout = 12,5Hz
Motor Frequency Motor Nominal Speed Maximum Reference
Motor Nominal Speed Motor Frequency Maximum Reference
-> +ref
MAX
= 50 Hz
] -32767 (8001 Hex ) =>+32767 [RPM] (7FFF Hex)
MAX
= 1420 RPM
= 1420 RPM
4.4.4. Actual Output Speed under Instances 20/70 and 21/71
The value of the actual speed of the motor is transmitted in the form of a 16-bit word. The value is transmitted as a whole number. Negative figures are formed by means of 2’s complement.
The actual speed value has the following format:
-32767 (8000 Hex) [RPM] -> +32767 [RPM] (7FFF Hex) [RPM]
MG.33.D3.02 - VLT® is a registered Danfoss trademark
31
4
4. How to Control the Frequency Converter FC 100/ 200/ 300 DeviceNet
4.5. Danfoss FC Control Profile
4.5.1. Control Word under Instances 100/150 and 101/151
To select FC protocol in the control word, par.
Control Word Profile
8-10 protocol [0]. The control word is used to send commands from a master (PLC or PC) to a slave (frequency converter).
The control word in Instances 100/101 is de­fined as follows to the right:
must be set to FC
Bit Bit value = 0 Bit value = 1
00 Reference value External selection lsb 01 Reference value External selection msb 02 DC brake Ramp 03 Coasting No coasting 04 Quick stop Ramp 05 Hold output frequency Use ramp 06 Ramp stop Start 07 No function Reset 08 No function Jog 09 Ramp 1 Ramp 2 10 Data invalid Data valid 11 No function Relay 01 active 12 No function Relay 04 active 13 Parameter set-up Selection lsb 14 Parameter set-up Selection msb 15 No function Reverse
Explanation of the Control Bits:
Bits 00/01 Bits 00 and 01 are used to choose between the four reference values, which are pre-programmed in par. 3-10
Preset Reference
according to the table to the right:
Pro­gram-
Param­eter
Bit 01 Bit 00
med ref. value
1 3-10 [0] 0 0 2 3-10 [1] 0 1 3 3-10 [2] 1 0 4 3-10 [3] 1 1
NB!
In par. 8-56
Preset Reference Select
a selection is made to define how Bit 00/01
gates with the corresponding function on the digital inputs.
32
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 4. How to Control the Frequency Converter
Bit 02, DC brake: Bit 02 = ’0’ leads to DC braking and stop. Braking current and duration are set in par. 2-01
Brake Current
Bit 02 = ’1’ leads to ramping.
Bit 03, Coasting: Bit 03 = ’0’ causes the frequency converter to immediately "let go" of the motor (the output transistors are "shut off"), so that it coasts to a standstill. Bit 03 = ’1’ enables the frequency converter to start the motor if the other starting conditions have been fulfilled.
Bit 04, Quick stop: Bit 04 = ’0’ causes a stop, in which the motor speed is ramped down to stop via par. 3-81
and 2-02
NB!
In par. 8-50 corresponding function on a digital input.
Stop Ramp Time
.
DC Braking Time
Coasting Select
.
a selection is made to define how Bit 03 gates with the
DC
Quick
4
Bit 05, Hold output frequency: Bit 05 = ’0’ causes the present output frequency (in Hz) to freeze. The frozen output frequency can then be changed only by means of the digital inputs (parameters 5-10 to 5-15) programmed to Speed up and Speed down.
NB!
If Hold output is active, only the following can stop the frequency converter:
Bit 03 Coasting stop
•Bit 02 DC braking
Digital input (parameters 5-10 to 5-15) programmed to DC braking, Coast­ing stop or Reset and coasting stop.
Bit 06, Ramp stop/start:
Bit 06 = ’0’ causes a stop, in which the motor speed is ramped down to stop via the selected
ramp down
parameter.
NB!
In par. 8-53 gates with the corresponding function on a digital input.
Start Select
a selection is made to define how Bit 06 Ramp stop/start
Bit 06 = ’1’ permits the frequency converter to start the motor, if the other starting conditions have been fulfilled.
Bit 07, Reset: Bit 07 = ’0’ does not cause a reset. Bit 07 = ’1’ causes the reset of a trip. Reset is activated on the leading edge of the signal, i.e. when changing from logic ’0’ to logic ’1’.
Bit 08, Jog: Bit 08 = ’1’ causes the output frequency to be determined by par. 3-19
MG.33.D3.02 - VLT® is a registered Danfoss trademark
Jog Speed
.
33
4. How to Control the Frequency Converter FC 100/ 200/ 300 DeviceNet
Bit 09, Selection of ramp 1/2: Bit 09 = "0" means that ramp 1 is active (parameters 3-40 to 3-47). Bit 09 = "1" means that ramp 2 (parameters 3-50 to 3-57) is active.
4
Bit 10, Data not valid/Data valid: Is used to tell the frequency converter wheth­er the control word is to be used or ignored. Bit 10 = ’0’ causes the control word to be ig­nored, Bit 10 = ’1’ causes the control word to be used. This function is relevant, because the control word is always contained in the tele­gram, regardless of which type of telegram is used, i.e. it is possible to turn off the control word if you do not wish to use it in connection with updating or reading parameters.
Bit 11, Relay 01: Bit 11 = "0" Relay not activated. Bit 11 = "1" Relay 01 activated, provided Con­trol word bit 11 has been chosen in par. 5-40
Function Relay
Bit 12, Relay 04: Bit 12 = "0" Relay 04 has not been activated. Bit 12 = "1" Relay 04 has been activated, pro­vided Control word bit 12 has been chosen in par. 5-40
.
Function Relay
.
Set-up
1 0 0 2 0 1 3 1 0 4 1 1
Bit 14 Bit 13
Bit 13/14, Selection of set-up: Bits 13 and 14 are used to choose from the four menu set-ups according to the table to the right:
The function is only possible when Multi-Set-ups is selected in par. 0-10
NB!
In par. 8-55 the corresponding function on the digital inputs.
Bit 15 Reverse: Bit 15 = ’0’ causes no reversing. Bit 15 = ’1’ causes reversing.
Set-up Select
a selection is made to define how Bits 13/14 gate with
Active Set-up
.
34
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 4. How to Control the Frequency Converter
4.5.2. Status Word under Instances 100/150 and 101/151
The status word in Instance 150/151 is de­fined as follows to the right:
Bit Bit = 0 Bit = 1
00 Control not ready Control ready 01 Drive not ready Drive ready 02 Coasting Enable 03 No error Trip 04 No error Error (no trip) 05 Reserved ­06 No error Trip lock 07 No warning Warning 08 Speed reference Speed = reference 09 Local operation Bus control 10 Out of frequency limit Frequency limit ok 11 No operation In operation 12 Drive ok Stopped, auto start 13 Voltage ok Voltage exceeded 14 Torque ok Torque exceeded 15 Timer ok Timer exceeded
4
Explanation of the Statur Bits:
Bit 00, Control not ready/ready: Bit 00 = ’0’ means that the frequency converter has tripped. Bit 00 = ’1’ means that the frequency converter controls are ready, but that the power component is not necessarily receiving any power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready: Bit 01 = ’1’. The frequency converter is ready for operation, but there is an active coasting com­mand via the digital inputs or via serial communication.
Bit 02, Coasting stop: Bit 02 = ’0’. The frequency converter has released the motor. Bit 02 = ’1’. The frequency converter can start the motor when a start command is given.
Bit 03, No error/trip: Bit 03 = ’0’ means that the frequency converter is not in fault mode. Bit 03 = ’1’ means that the frequency converter is tripped, and that a reset signal is required to re-establish operation.
Bit 04, No error/error (no trip): Bit 04 = ’0’ means that the frequency converter is not in fault mode. Bit 04 = “1” means that there is a frequency converter error but no trip.
Bit 05, Not used: Bit 05 is not used in the status word.
Bit 06, No error / trip lock: Bit 06 = ’0’ means that the frequency converter is not in fault mode. Bit 06 = “1” means that the frequency converter is tripped, and locked.
Bit 07, No warning/warning: Bit 07 = ’0’ means that there are no warnings.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
35
4
4. How to Control the Frequency Converter FC 100/ 200/ 300 DeviceNet
Bit 07 = ’1’ means that a warning has occurred.
Bit 08, Speed reference/speed = reference: Bit 08 = ’0’ means that the motor is running, but that the present speed is different from the preset speed reference. It might, for example, be the case while the speed is being ramped up/ down during start/stop. Bit 08 = ’1’ means that the present motor present speed matches the preset speed reference.
Bit 09, Local operation/bus control: Bit 09 = ’0’ means that [STOP/RESET] is activated on the control unit, or that Local control in par. 3-13
Reference site
communication. Bit 09 = ’1’ means that it is possible to control the frequency converter via the fieldbus/ serial communication.
Bit 10, Out of frequency limit: Bit 10 = ’0’, if the output frequency has reached the value in par. 4-11 par. 4-13 Bit 10 = "1" means that the output frequency is within the defined limits.
Motor Speed High Limit
is selected. It is not possible to control the frequency converter via serial
Motor Speed Low Limit
.
or
Bit 11, No operation/in operation: Bit 11 = ’0’ means that the motor is not running. Bit 11 = ’1’ means that the frequency converter has a start signal or that the output frequency is greater than 0 Hz.
Bit 12, Drive OK/stopped, auto start: Bit 12 = ’0’ means that there is no temporary over temperature on the inverter. Bit 12 = ’1’ means that the inverter has stopped because of over temperature, but that the unit has not tripped and will resume operation once the over temperature stops.
Bit 13, Voltage OK/limit exceeded: Bit 13 = ’0’ means that there are no voltage warnings. Bit 13 = ’1’ means that the DC voltage in the frequency converter’s intermediate circuit is too low or too high.
Bit 14, Torque OK/limit exceeded: Bit 14 = ’0’ means that the motor current is lower than the torque limit selected in par. 4-16
Torque Limit Motor Mode
Bit 14 = ’1’ means that the torque limit in par. 4-16 and 4-17 has been exceeded.
Bit 15, Timer OK/limit exceeded: Bit 15 = ’0’ means that the timers for motor thermal protection and VLT thermal protection, re­spectively, have not exceeded 100%. Bit 15 = ’1’ means that one of the timers has exceeded 100%.
or par. 4-17
Torque Limit Generator Mode
.
36
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 4. How to Control the Frequency Converter
4.5.3. Bus Reference Value under Instances 100/150 and 101/151
The frequency reference value is transmitted to the frequency converter in the form of a 16­bit word. The value is transmitted as a whole number (-32767 to 32767). Negative figures are formatted by means of 2’s complement.
The bus reference has the following format:
100% = 4000 Hex
Par. 3-00 = "0" ["ref
Par. 3-00 = "1" [- ref +100%
MIN
MAX
-> ref
-> + ref
"] 0 -> 16384 (4000 Hex) ~ 0 -> 100%
MAX
] -16384 (C000 Hex) -> +16384 (4000 Hex) ~ -100% ->
MAX
Master slave 16 bit
CTW Speed ref. RPM
4.5.4. Actual Output Frequency under Instances 100/150 and 101/151
The value of the actual output frequency of the frequency converter is transmitted in the form of a 16-bit word. The value is transmitted as a whole number (-32767 -> 32767) Nega­tive figures are formed by means of 2’s com­plement.
Slave master 16 bit
STW Actual ref. RPM
4
The actual output frequency has the following format:
-32767 ->+32767.
-16384 (C000 Hex) corresponds to -100%, and 16384 (4000 Hex) corresponds to 100%.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
37
5
5. How to Access the Parameters FC 100/ 200/ 300 DeviceNet
38
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 5. How to Access the Parameters
5. How to Access the Parameters
5.1. Explicit Messages
DeviceNet is based on the CAN protocol. This means that every message contains an 11-bit CAN identifier field to define the connection ID. These CAN identifiers are also used to determine access priority.
The MAC ID is stored in the header of the message, which is split into four different message groups.
10
9 8 7 6 5 4 3 2 1 0 Identifier bits 0 Group 1 ID Source MAC ID Message Group 1 1 0 MAC ID Group 2 ID Message Group 2 1 1 Group 3 iD Source MAC ID Message Group 3 1 1 1 1 1 Group 4 ID Message Group 4 1 1 1 1 1 1 1 X X X X Invalid Can Identifiers
5
FC 100, 200 and 300 parameters can be accessed by the Standard DeviceNet service Explicit Message. Two classes of explicit messages are supported: Message group 2: Explicit messages take place via pre-defined master/slave connections. Message group 3: Explicit messages take place via dynamically established lower prioritized connections.
5.2. Object Classes
The following Standard DeviceNet objects can be accessed:
Class ID 01h Identity Object Class ID 10h Parameter Group Object Class ID 03h DeviceNet Object Class ID 28h Motor Data Object Class ID 04h Assembly Object Class ID 29h Control Supervisory Object Class ID 05h Connection Object Class ID 2Ah AC/DC Drive Object Class ID 0Fh Parameter Object Class ID 2Bh Acknowledge Handler Object
The following DeviceNet Vendor Specific Objects are also available: Class ID 100d to 119d Danfoss Classes. The above Object classes are described in the following sections:
Danfoss Object Classes
.
5.3. DeviceNet Object Classes
DeviceNet Object Classes
and
5.3.1. Class ID 01h Identity Object
This is a standard DeviceNet Object for identification of the device (frequency converter). The Heartbeat Interval can be set in this Object. The attributes supported for this class are listed below.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
39
5. How to Access the Parameters FC 100/ 200/ 300 DeviceNet
5.3.2. Class ID 0x01
5
Attrib­ute
1 Get Vendor USINT 97 Danfoss Drives
2 Get Device
3 Get Product
4 Get Revision UNIT Software version
5 Get Status UNIT 6 Get Serial
7 Get Product
10 Get/Set Heartbeat
Access Name Data
type
UNIT 2 AD/DC Motor
Type
UNIT 100 See EDS File Sec-
Code
UDINT From frequency
Number
String FC 100, 200 or
Name
USINT 0-255 sec 0 Off
Interval
Min/ Max
5.3.3. Class ID 03h DeviceNet Object
This is a standard DeviceNet Object for configuration and status of the DeviceNet connection. The attributes supported for this class are listed below.
Units Default Description
Vendor Code
tion
on FC 100, 200 or 300
converter
300
5.3.4. Class ID 0x03
Attrib­ute
1 Get/Set MAC ID USINT 0-63 63 Node address 2 Get/Set Baud Rate USINT 0-2 0 0=125
4 Get BOC Bus-Off Counter 5 Get Allocate
6 Get MAC ID
7 Get Baud rate
Access Name Data
informa­tion
Switch changed
switched from last power up
Min/
type
BOOL 0-1 0 The node ad-
BOOL 0-1 0 The baud rate
Max
Units Default Description
1=250 2=500
Only required if predefined Mas­ter/Slave is im­plemented
dress switch has changed since the last power­up/reset
switch has changed since the last power­up
40
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 5. How to Access the Parameters
5.3.5. Class ID 04h Assembly Object
This is a standard DeviceNet Object for transfer of the I/O Instances (Process Data) described in the section “How to control the Frequency Converter”. Using this it is possible to send or read any of the defined Instances, either by polling or explicit messaging.
The attributes supported for this class are listed below.
5.3.6. Class ID 0x04
Attrib­ute
3 Set Data ARRAY
In­stance
20 Set 2 Words DeviceNet AC/DC Profile Instance 20/70 21 Set 2 Words DeviceNet AC/DC Profile Instance 21/71 70 Get 2 Words DeviceNet AC/DC Profile Instance 20/70 71 Get 2 Words DeviceNet AC/DC Profile Instance 21/71 100 Set 2 Words Danfoss specific, no PCD
101 Set 4 Words Danfoss specific, 2 PCD Words Instance 101/151 150 Get 2 Words Danfoss specific, no PCD
151 Get 4 Words Danfoss specific, 2 PCD Words Instance 101/151
Access Name Data
type
Access Size Description Parameters 10-10 selec-
Words
Words
Min/ Max
5.3.7. Class ID 05h Connection Object
This is a standard DeviceNet Object for allocation and managing I/O and explicit messaging con­nections. For this class three Instances are supported: Explicit Messages, Polled I/O and Change of State connections.
Units Default Description
5
tion:
Instance 100/150
Instance 100/150
The attributes supported for the different instances are listed below.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
41
5. How to Access the Parameters FC 100/ 200/ 300 DeviceNet
5.3.8. Instance 1 Attributes: Explicit Message Instance
5
Attrib­ute
1 Get State USINT State of the object 2 Get Instance
3 Get Transport
4 Get Produced
5 Get Consumed
6 Get Initial
7 Get Produced
8 Get Consumed
9 Get/Set Expected
12 Get Watchdog
13 Get Produced
14 Get Produced
15 Get Consumd
16 Get Consumed
17 Get Production
Access Name Data
type
USINT Indicates either I/O or Explicit Message
Type
USINT Defines behaviour of the connection Class Trig­ger
UINT CAN Identifier Field when the connection trans­Connec­tion ID
UINT CAN Identifier Field value that denotes message Connec­tion ID
USINT Defines the message group(s) across which pro­Communi­cation Character­istics
UINT Maximum number of bytes transmitted across Connectin size
UINT Maximum number of bytes received across this Connec­tion size
UINT Defines value used in Transmission Trigger Tim­Package Rate
USINT Defines how to handle Inactivity/Watchdog timeout action
UINT Number of Bytes in the produced connection Connec­tion Path Length
Array of Connecti­no Path
Connec­tion Path Length
Connec­tion Path
Inhibit Time
USINT
UINT Number of bytes in the consumed connection
Array of
USINT
UINT Defines minimum time between new data pro-
Description
mits
to be received
ductions and consumptions associated with this connection occur
this connection
connection
er and Inactivity/Watchdog timer
timeout
path attribute
Specifies the Application object(s) whose data is to be produced by these Connection Objects
path attribute
Specifies the Application object(s) that are to re­ceive the data consumed by this Connection ob­ject
ductin. This attribute is required for I/O Client connection.
42
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 5. How to Access the Parameters
5.3.9. Instance 2 Attributes: Polled I/O
Attrib­ute
1 Get State USINT State of the object 2 Get Instance
3 Get Transport
4 Get Produced
5 Get Consumed
6 Get Initial
7 Get Produced
8 Get Consumed
9 Get/Set Expected
12 Get Watchdog
13 Get Produced
14 Get Produced
15 Get Consumd
16 Get Consumed
17 Get Production
Access Name Data
type
USINT Indicates either I/O or Explicit Message
Type
USINT Defines behaviour of the connection Class Trig­ger
UINT CAN Identifier Field when the connection trans­Connec­tion ID
UINT CAN Identifier Field value that denotes message Connec­tion ID
USINT Defines the message group(s) across which pro­Communi­cation Character­istics
UINT Maximum number of bytes transmitted across Connectin size
UINT Maximum number of bytes received across this Connec­tion size
UINT Defines value used in Transmission Trigger Tim­Package Rate
USINT Defines how to handle Inactivity/Watchdog timeout action
UINT Number of Bytes in the produced connection Connec­tion Path Length
Array of Connecti­no Path
Connec­tion Path Length
Connec­tion Path
Inhibit Time
USINT
UINT Number of bytes in the consumed connection
Array of
USINT
UINT Defines minimum time between new data pro-
Description
mits
to be received
ductions and consumptions associated with this connection occur
this connection
connection
er and Inactivity/Watchdog timer
timeout
path attribute
Specifies the Application object(s) whose data is to be produced by these Connection Objects
path attribute
Specifies the Application object(s) that are to re­ceive the data consumed by this Connection ob­ject
ductin. This attribute is required for I/O Client connection.
5
MG.33.D3.02 - VLT® is a registered Danfoss trademark
43
5. How to Access the Parameters FC 100/ 200/ 300 DeviceNet
5.3.10. Instance 4: Change of State/Cycle
5
Attrib­ute
1 Get State USINT State of the object 2 Get Instance
3 Get Transport
4 Get Produced
5 Get Consumed
6 Get Initial
7 Get Produced
8 Get Consumed
9 Get/Set Expected
12 Get Watchdog
13 Get Produced
14 Get Produced
15 Get Consumd
16 Get Consumed
17 Get Production
Access Name Data
type
USINT Indicates either I/O or Explicit Message
Type
USINT Defines behaviour of the connection Class Trig­ger
UINT CAN Identifier Field when the connection trans­Connec­tion ID
UINT CAN Identifier Field value that denotes message Connec­tion ID
USINT Defines the message group(s) across which pro­Communi­cation Character­istics
UINT Maximum number of bytes transmitted across Connectin size
UINT Maximum number of bytes received across this Connec­tion size
UINT Defines value used in Transmission Trigger Tim­Package Rate
USINT Defines how to handle Inactivity/Watchdog timeout action
UINT Number of Bytes in the produced connection Connec­tion Path Length
Array of Connecti­no Path
Connec­tion Path Length
Connec­tion Path
Inhibit Time
USINT
UINT Number of bytes in the consumed connection
Array of
USINT
UINT Defines minimum time between new data pro-
Description
mits
to be received
ductions and consumptions associated with this connection occur
this connection
connection
er and Inactivity/Watchdog timer
timeout
path attribute
Specifies the Application object(s) whose data is to be produced by these Connection Objects
path attribute
Specifies the Application object(s) that are to re­ceive the data consumed by this Connection ob­ject
ductin. This attribute is required for I/O Client connection.
5.3.11. Class ID 0F4 Parameter Object
This object is an interface to the parameters of the drive. It identifies configurable parameters and supplies their description, including min. and max. values and a descriptive text.
44
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 5. How to Access the Parameters
The attributes supported are listed below.
Attribute Access Stub/
1 Set/Get Stub Parameter value 2 Get Stub Link path size USINT Size of link path 3 Get Stub Link path ARRAY DeviceNet's path to parameter's origin
4 Get Stub Descriptor WORD Description of parameter 5 Get Stub Data type EPATH Data type code 6 Get Stub Data size USINT Number of bytes in parameter value 7 Get Full Parameter name
8 Get Full Units string SHORT
9 Get/Set Full Help string SHORT
10 Get Full Min value 11 Get Full Max value 12 Get Full Default value 13 Get Full Scaling multiplier UINT Multiplier for scaling factor 14 Get Full Scaling divisor UINT Divisor for scaling factor 15 Get Full Scaling base UINT Base for scaling formula 16 Get Full Scaling offset INT Offset for scaling formula 17 Get Full Multiplier link UINT Parameter instance of multiplier source 18 Get Full Divisor link UINT Parameter instance of divisor source 19 Get Full Base link UINT Parameter instance of base source 20 Get Full Offset link UINT Parameter instance of offset source 21 Get Full Decimal preci-
1
= Same data type as the parameter.
Full
Name Data type Description
1
Actual value of parameter
Human readable text string representing pa­rameter name Human readable text string representing pa­rameter name Human readable text string representing pa­rameter name
1
Min valid value
1
Max valid value
1
Parameters default value
Segment type/ port Segment Ad­dress
string
sion
Data type
BYTE
Path
SHORT STRING
STRING
STRING Data type Data type Data type
USINT Specifies parameter value format
5
MG.33.D3.02 - VLT® is a registered Danfoss trademark
45
5. How to Access the Parameters FC 100/ 200/ 300 DeviceNet
5.3.12. Class ID 10h Parameter Group Object
This Object defines 14 parameter groups for all FC 100, 200 and 300 parameters. One Class instance exists for each parameter group. A read out of an instance will contain the name of the current parameter group.
5
In-
Group
stance 0 1 O P E R A T I O N D I S P L . 1 2 L O A D M O T O R 2 3 B R A K E S 3 4 R E F E R E N C E R A M P S 4 5 L I M I T S W A R N I N G S 5 6 D I G I T A L I N O U T 6 7 A N A L O G I N O U T 7 8 C O N T R O L L E R S 8 9 C O M M . A N D O P T I O N 9 10 C A N F I E L D B U S
10 11 S P E C I A L F U N C T I O N
Name (max. 16 characters)
46
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 5. How to Access the Parameters
5.3.13. Class ID 28 Motor Data Object
In this object, the current motor data can be configured and read out. The Instances, attributes and services supported for this class are listed below.
5.3.14. Class ID 0/28 Motor Data Object
Attrib-
Access Name Data
ute
3 Get/set Motor
6 Get/set Rated
7 Get/set Rated
8 Get/set Rated
9 Get/set Rated
12 Get/set Pole
15 Get/set Base
type
current
voltage
power
frequen­cy
count
speed
Generic
type
maximum values
USINT 7 7 7 = Squirrel Cage Induction Motor 1-11
UNIT 0-100.00 100mA Drive dependent Stator Current rating (from motor
UNIT 200-500 volt Drive dependent Base Voltage rating (from motor
UDINT 0-18500 Watt Drive dependent Power rating at rated frequency
UNIT 1-1000 Hz Drive dependent Elec. frequency rating (from motor
UINT Drive dependent Number of poles in the motor 1-39
UNIT 100-60000 RPM Drive dependent Nominal motor speed (from motor
Units Default Description Parameter
nameplate)
nameplate)
(from motor nameplate)
nameplate)
nameplate)
reference
1-24
1-22
1-20
1-23
1-25
5
MG.33.D3.02 - VLT® is a registered Danfoss trademark
47
5. How to Access the Parameters FC 100/ 200/ 300 DeviceNet
5.3.15. Class ID 29h Control Supervisory Object
The Control Supervisory Object can be used for process control and monitoring of the frequency converter, as an alternative to the I/O Instances defined in the section “How to control the Fre­quency Converter”.
The attributes supported for this class are listed below.
5.3.16. Class ID 0x29
5
Attribute Access Name Data type Min/
3 Get/Set Run 1 Bool 0-1 Run Fwd, see note below 4 Get/Set Run 2 Bool 0-1 Run rev, see note below 5 Get/Set NetCtrl Bool 0-1 1 0 = Local Control
6 Get State USINT 0-7 0 = Vendor specific
7 Get Running 1 Bool 0-1 0 0 = Other state
8 Get Running 2 Bool 0-1 0 0 = Other state
9 Get Ready Bool 0-1 0 = Other state
10 Get Fault Bool 0-1 0 0 = No Faults Present
12 Get/Set Fault Rst Bool 0-1 0 = No Action
13 Get Fault Code UINT 15 Get Ctrl From Net Bool 0-1 1 0 = Control is local
16 Get/Set DN Fault Mode UINT 0-2 1 Action on loss of DeviceNet
Max
Default Description
1 = Control from Network
1 = Start up 2 = Not ready 3 = Ready 4 = Enabled 5 = Stopping 6 = Fault stop 7 = Fault
1 = (Enable and Run 1) or (Stopping and Running 1) or (Fault Stop and Running 1)
1 = (Enable and Run 2) or (Stopping and Running 2) or (Fault Stop and Running 2)
1 = Ready or Enabled or Stopping
1 = Fault Occured (latched)
1 ->1 = Reset Fault
1 = Control is from Network
0 = Fault + Stop 1 = Ignore (Warning Optional) 2 = Danfoss specific
NB!
The ODVA drive profile selected in par. 10-10
Process Data Type Selection
able only when Instances 20/70 or 21/71 are selected.
is avail-
48
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 5. How to Access the Parameters
The State – Transition diagram below shows how the frequency converter will respond to the various command attributes associated with Class ID 0x29.
5
5.3.17. Class ID 2Ah AC/DC Drive Object
Use this object to set and read out a range of FC 100, 200 or 300 drive control and status infor­mation. The attributes supported for this class are listed below.
5.3.18. Class ID 0x2A
Attribute Access Name Data
3 Get At Reference Bool 0-1 0 = Drive not at reference
4 Get/Set Net REf Bool 0-1 1 0 = Set reference at non-DeviceNet refer-
6 Get/Set Drive Mode USINT 0-1 1 0 = Vendor specific mode
7 Get Speed Actual INT
8 Get/Set Speed Ref INT 22 Get/Set Speed Scale SINT -128-127 Speed scaling factor 29 Get Ref from Net Bool 0-1 0 = Local speed reference
type
Min/ Max
Default Description
1 = Drive at reference
ence 1 = Set reference at DeviceNet reference
1 = Open loop speed (Frequency)
RPM/2
RPM/2
Speed Scale
Speed Scale
2 = Closed loop speed control Actual drive speed (best approximation) Speed reference
1 = DeviceNet speed reference
MG.33.D3.02 - VLT® is a registered Danfoss trademark
49
5. How to Access the Parameters FC 100/ 200/ 300 DeviceNet
5.3.19. Class ID 2Bh (Acknowledge Handler Object)
Use this object to manage message reception acknowledgements, necessary for Change-Of-State support.
The attributes supported for this class are listed below.
5.3.20. Class ID 0x2B
5
Attribute Access Name Data
1 Set ACK Timer UINT 0-65535 16 Time top wait for ACK before resending 2 Get/Set Retry Timer USINT 0-255 1 Number of ACK-timeouts to wait before
3 Get/Set COS UINT Connection instance ID
type
5.4. Danfoss Object Classes
Use the Danfoss classes for read and write of all FC 100, 200 or 300 parameter values. For each parameter group a corresponding object Class is defined. The following table shows the classes supported, and their relationship to the FC 100, 200 and 300 parameters.
Instance Description
The Danfoss VLT DeviceNet uses Instance 1 only; so always leave this at the value of 1.
Attribute Description
The attributes for the FC 100, 200 or 300 pa­rameter are the last 2 (two) digits of the pa­rameter + 100.
Min/ Max
Default Description
producing. RetryLimit_Reache event.
Danfoss Classes
Parameter range Class Parameter 0-00 - 0-99 Class 100 Parameter 1-00 - 1-99 Class 101 Parameter 2-00 - 2-99 Class 102 Parameter 3-00 - 3-99 Class 103 Parameter 4-00 - 4-99 Class 104 Parameter 5-00 - 5-99 Class 105 Parameter 6-00 - 6-99 Class 106 Parameter 7-00 - 7-99 Class 107 Parameter 8-00 - 8-99 Class 108 Parameter 10-00 - 10-99 Class 110 Parameter 11-00 - 11-99 Class 111 Parameter 13-00 - 13-99 Class 113 Parameter 14-00 - 14-99 Class 114 Parameter 15-00 - 15-99 Class 115 Parameter 16-00 - 16-99 Class 116
5.4.1. Example
To read from par. 16-62 the class, instance and attribute must be set as shown in the table to the right:
50
MG.33.D3.02 - VLT® is a registered Danfoss trademark
Analogue Input 53
,
Class
116 1 162
Instance Attribute
FC 100/ 200/ 300 DeviceNet 5. How to Access the Parameters
5.5. Reading/Writing to Parameters with Index
Indexed parameters such as 10-11 or 10-12 need special handling since DeviceNet does not sup­port indexed addressing. The way to handle this in the frequency converter is to use par. 10-30
Parameter Data Types
write of an indexed parameter.
NB!
If two masters access this feature at the same time, incorrect data may be gener­ated.
, which serves as an index pointer. Set up the pointer before each read/
5.5.1. Example
Write 16-10 in index 2 in par. 10-12
First, set up the index pointer in par. 10-30
Array Index
The next step is to write the data (in this ex­ample 16-10) to par. 10-12.
. In this example index 2:
Process Data Config Read
Class Instance Attribute Value
110 Dec 1 Dec 130 Dec 2 Dec 6E Hex 1 Hex 82 Hex 2 Hex
Class Instance Attribute Value
110 Dec 1 Dec 112 Dec 1610 Dec 6E Hex 1 Hex 70 Hex 64A Hex
5
.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
51
6
6. Parameters FC 100/ 200/ 300 DeviceNet
52
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 6. Parameters
6. Parameters
8-01 Control Site
Option: Function:
[0]
[1] Digital only Control by using digital inputs only.
[2] Control word only Control by using control word only.
The setting in this parameter overrides the settings in par. 8-50 to 8-56.
8-02 Control Word Source
Option: Function:
[0] None
[1] FC RS485
[2] FC USB
[3] Option A
[4] Option B
[5] Option C0
[6] Option C1
[30] External Can Select the source of the control word: one of two serial interfa-
Digital and ctrl. word Control by using both digital input and control word.
*
ces or four installed options. During initial power-up, the fre­quency converter automatically sets this parameter to
A
[3] if it detects a valid fieldbus option installed in slot A. If the option is removed, the frequency converter detects a change in the configuration, sets par. 8-02 back to default setting
RS485
, and the frequency converter then trips. If an option is installed after initial power-up, the setting of par. 8-02 will not change but the frequency converter will trip and display: Alarm
Option Changed
67 This parameter cannot be adjusted while the motor is running.
.
Option
FC
6
8-03 Control Word Timeout Time
Range: Function:
1.0s
8-04 Control Word Timeout Function
Option: Function:
[0]
[1] Freeze Output
[2] Stop
[0.1 - 18000.0 s] Enter the maximum time expected to pass between the recep-
*
tion of two consecutive telegrams. If this time is exceeded, it indicates that the serial communication has stopped. The func­tion selected in par. 8-04 then be carried out. The time-out counter is triggered by a valid control word.
Off
*
MG.33.D3.02 - VLT® is a registered Danfoss trademark
Control Word Time-out Function
will
53
6
6. Parameters FC 100/ 200/ 300 DeviceNet
[3] Jogging
[4] Max. Speed
[5] Stop and trip
[7] Select set-up 1
[8] Select set-up 2
[9] Select set-up 3
[10] Select set-up 4 Select the time-out function. The time-out function activates
when the control word fails to be updated within the time period specified in par. 8-03
Off
-
-
-
-
-
-
-
[0]: Resume control via serial bus (Fieldbus or
standard) using the most recent control word.
Freeze output
munication resumes.
Stop
[2]: Stop with auto restart when communication
resumes.
Jogging
communication resumes.
Max. freq.
until communication resumes.
[3]: Run the motor at JOG frequency until
[4]: Run the motor at maximum frequency
Stop and trip
quency converter in order to restart: via the fieldbus, via the reset button on the LCP or via a digital input.
Select set-up 1-4
set-up upon reestablishment of communication follow­ing a control word time-out. If communication resumes causing the time-out situation to disappear, par. 8-05
End-of-time-out Function
the set-up used before the time-out or to retain the set-up endorsed by the time-out function. Note the following configuration required in order to change the set-up after a time-out: Set Par. 0-10
Multi set-up
This Set-up Linked To
0-12
Control Word Time-out Time
[1]: Freeze output frequency until com-
[5]: Stop the motor, then reset the fre-
[7] - [10]: This option changes the
defines whether to resume
[9], and select the relevant link in par.
.
.
Active set-up to
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control word following a time-out. This parameter is active only when par. 8-04 is set to [Set-up 1-4].
[0] Hold set-up Retains the set-up selected in par. 8-04 and displays a warning,
until par. 8-06 toggles. Then the frequency converter resumes its original set-up.
Resume set-up Resumes the set-up active prior to the time-out.
*
[1]
8-06 Reset Control Word Timeout
Option: Function:
*
Do not reset
[0]
54
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 6. Parameters
[1] Do reset Select
8-07 Diagnosis Trigger
Option: Function:
*
*
Disable
FC profile
[0]
[1] Trigger on alarms
[2] Trigger alarms/warn. This parameter has no function for DeviceNet.
8-10 Control Word Profile
Option: Function:
[0]
[5] ODVA When this parameter is set to [0] FC profile, Instances 100/150
Do reset
original set-up following a control word time-out. When the val­ue is set to reset and then immediately reverts to the ting. Select
Do not reset Select setup 1-4
This parameter is active only when selected in par. 8-05
and 101/151 are selectable in par. 10-10. When [3] ODVA profile is selected, Instances 20/70 and 21/71 are selectable in par. 10-10.
[1] to return the frequency converter to the
Do reset
[1], the frequency converter performs the
Do not reset
[0] to retain the set-up specified in par. 8-04,
following a control word time-out.
Hold set-up
End-of-Time-out Function
[0] has been
.
[0] set-
6
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
[0] Digital input
[1] Bus
[2] Logic AND
Logic OR
*
[3]
NB!
This parameter is active only when par. 8-01
control word
8-51 Quick Stop Select
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
Logic OR Select control of the Quick Stop function via the terminals (dig-
*
[3]
.
ital input) and/or via the bus.
Control Site
is set to [0]
Digital and
MG.33.D3.02 - VLT® is a registered Danfoss trademark
55
6
6. Parameters FC 100/ 200/ 300 DeviceNet
NB!
Con-
.
Digital and
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via the fieldbus.
[0] Digital input
[1] Bus
[2] Logic AND
Logic OR
*
[3]
NB!
This parameter is active only when par. 8-01
control word
.
This parameter is active only when par. 8-01
trol Site
is set to [0]
Control Site
Digital and control word
is set to [0]
8-53 Start Select
Option: Function:
Select control of the frequency converter start function via the terminals (digital input) and/or via the fieldbus.
[0] Digital input
[1] Bus Activates Start command via the serial communication port or
fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial communication
port, AND additionally via one of the digital inputs.
Logic OR Activates Start command via the fieldbus/serial communication
*
[3]
port OR via one of the digital inputs.
NB!
This parameter is active only when par. 8-01
control word
8-54 Reversing Select
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
Logic OR Select control of the frequency converter reverse function via
*
[3]
.
the terminals (digital input) and/or via the fieldbus.
Bus
Select communication port or fieldbus option.
Control Site
[1], to activate the Reverse command via the serial
is set to [0]
Digital and
56
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 6. Parameters
Select
Logic AND
fieldbus/serial communication port, AND additionally via one of the digital inputs.
Logic OR
Select fieldbus/serial communication port OR via one of the digital in­puts.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via the fieldbus.
[0] Digital input
[1] Bus Activates the set-up selection via the serial communication port
or fieldbus option.
[2] to activate the Reverse command via the
[3] to activate the Reverse command via the
NB!
This parameter is active only when par. 8-01
trol Site
is set to [0]
Digital and control word
Con-
.
6
[2] Logic AND Activates the set-up selection via the fieldbus/serial communi-
cation port, AND additionally via one of the digital inputs.
Logic OR Activate the set-up selection via the fieldbus/serial communica-
*
[3]
tion port OR via one of the digital inputs.
NB!
This parameter is active only when par. 8-01
control word
8-56 Preset Reference Select
Option: Function:
[0] Digital input
[1] Bus Activates Preset Reference selection via the serial communica-
[2] Logic AND Activates Preset Reference selection via the fieldbus/serial com-
.
Select control of the frequency converter Preset Reference se­lection via the terminals (digital input) and/or via the fieldbus.
tion port or fieldbus option.
munication port, AND additionally via one of the digital inputs.
Control Site
is set to [0]
Digital and
[3]
Logic OR Activates the Preset Reference selection via the fieldbus/serial
*
communication port OR via one of the digital inputs.
NB!
This parameter is active only when par. 8-01
control word
MG.33.D3.02 - VLT® is a registered Danfoss trademark
.
Control Site
is set to [0]
Digital and
57
6
6. Parameters FC 100/ 200/ 300 DeviceNet
8-90 Bus Jog 1 Speed
Range: Function:
100 RPM
8-91 Bus Jog 2 Speed
Range: Function:
200 RPM
10-00 CAN Protocol
Option: Function:
[0] CANopen
[1]
[0 - par. 4-13 RPM] Enter the jog speed. This is a fixed jog speed activated via the
*
[0 - par. 4-13 RPM] Enter the jog speed. This is a fixed jog speed activated via the
*
DeviceNet View the active CAN protocol.
*
serial port or fieldbus option.
serial port or fieldbus option.
NB!
The options depend on installed option.
10-01 Baud Rate Select
Option: Function:
[16] 10 Kbps
[17] 20 Kbps
[18] [19]
[20]
[21] 250 Kbps
[22] 500 Kbps Select the fieldbus transmission speed. The selection must cor-
10-02 MAC ID
Range: Function:
63
10-05 Readout Transmit Error Counter
Range: Function:
0
*
50 Kbps 100 Kbps
125 Kbps
*
respond to the transmission speed of the master and the other fieldbus nodes.
[0 - 127 ] Selection of station address. Every station connected to the
*
same DeviceNet network must have an unambiguous address.
[0 - 255] View the number of CAN control transmission errors since the
last power-up.
58
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 6. Parameters
10-06 Readout Receive Error Counter
Option: Function:
[0] 0 - 255 View the number of CAN control receipt errors since the last
power-up.
10-07 Readout Bus Off Counter
Range: Function:
0
*
10-10 Process Data Type Selection
Option: Function:
[0 - 255] View the number of Bus Off events since the last power-up.
Select the Instance (telegram) for data transmission. The In­stances available are dependent upon the setting of par. 8-10
Control Word Profile
When par. 8-10 is set to [0] and [1] are available. When par. 8-10 is set to [5] [3] are available. Instances 100/150 and 101/151 are Danfoss-specific. Instances 20/70 and 21/71 are ODVA-specific AC Drive profiles. For guidelines in telegram selection, please refer to the Device­Net Operating Instructions. Note that a change to this parameter will be executed immedi­ately.
.
FC profile
ODVA
, par. 10-10 options [0]
, par. 10-10 options [2] and
6
[0] Instance 100/150
[1] Instance 101/151
[2] Instance 20/70
[3] Instance 21/71
10-11 Process Data Config Write
Option: Function:
[0 ]
None
*
3-02 Minimum refer­ence
3-03 Maximum refer­ence
3-12 Catch up/slow down value
3-41 Ramp 1 ramp up time
3-42 Ramp 1 ramp down time
3-51 Ramp 2 ramp up time
3-52 Ramp 2 ramp down time
3-80 Jog ramp time
3-81 Quick stop ramp time
MG.33.D3.02 - VLT® is a registered Danfoss trademark
59
6
6. Parameters FC 100/ 200/ 300 DeviceNet
4-11 Motor speed low limit (RPM)
4-13 Motor speed high limit (RPM)
4-16 Torque limit mo­tor mode
4-17 Torque limit generator mode
7-28 Minimum Feed­back
7-29 Maximum Feed­back
8-90 Bus Jog 1 Speed
8-91 Bus Jog 2 Speed
16-80 Fieldbus CTW 1 (Fixed)
16-82 Fieldbus REF 1 (Fixed)
34-01 PCD 1 Write to MCO
34-02 PCD 2 Write to MCO
34-03 PCD 3 Write to MCO
34-04 PCD 4 Write to MCO
34-05 PCD 5 Write to MCO
34-06 PCD 6 Write to MCO
34-07 PCD 7 Write to MCO
34-08 PCD 8 Write to MCO
34-09 PCD 9 Write to MCO
34-10 PCD 10 Write to MCO
Select the process write data for I/O Assembly Instances 101/151. Elements [2] and [3] of this array can be selected. Elements [0] and [1] of the array are fixed.
10-12 Process Data Config Read
Option: Function:
None
16-00 Control Word
16-01 Reference [Unit]
16-02 Reference %
16-03 Status Word (Fixed)
60
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 6. Parameters
16-04 Main Actual Value [Unit]
16-05 Main Actual Value (%) (Fixed)
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage
16-13 Frequency
16-14 Motor Current
16-16 Torque
16-17 Speed [RPM]
16-18 Motor Thermal
16-19 KTY Sensor Temperature
16-21 Phase Angle
16-30 DC Link Voltage
16-32 BrakeEnergy/s
16-33 BrakeEnergy/2 min
16-34 Heatsink Temp.
16-35 Inverter Ther­mal
16-38 SL Control State
16-39 Controlcard Temp.
16-50 External Refer­ence
16-51 Pulse Refer­ence
16-52 Feedback [Unit]
16-53 Digi Pot Refer­ence
16-60 Digital Input
16-61 Terminal 53 Switch Setting
16-62 Analog Input 53
16-63 Terminal 54 Switch Setting
16-64 Analog Input 54
16-65 Analog Output 42 [mA]
16-66 Digital Output [bin]
16-67 Freq. Input #29 [Hz]
6
MG.33.D3.02 - VLT® is a registered Danfoss trademark
61
6
6. Parameters FC 100/ 200/ 300 DeviceNet
16-68 Freq. Input #33 [Hz]
16-69 Pulse Output #27 [Hz]
16-70 Pulse Output #29 [Hz]
16-71 Relay Output [bin]
16-84 Comm Option STW
16-85 FC Port CTW 1
16-90 Alarm Word
16-91 Alarm Word 2
16-92 Warning Word
16-93 Warning Word 2
16-94 Extended Sta­tus Word
16-95 Extended Sta­tus Word 2
34-21 PCD 1 Read from MCO
34-22 PCD 2 Read from MCO
34-23 PCD 3 Read from MCO
34-24 PCD 4 Read from MCO
34-25 PCD 5 Read from MCO
34-26 PCD 6 Read from MCO
34-27 PCD 7 Read from MCO
34-28 PCD 8 Read from MCO
34-29 PCD 9 Read from MCO
34-30 PCD 10 Read from MCO
34-40 Digital Inputs
34-41 Digital Outputs
34-50 Actual Position
34-51 Commanded Position
34-52 Actual Master Position
34-53 Slave Index Po­sition
62
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 6. Parameters
34-54 Master Index Position
34-55 Curve Position
34-56 Track Error
34-57 Synchronizing Error
34-58 Actual Velocity
34-59 Actual Master Velocity
34-60 Synchronizing Status
34-61 Axis Status
34-62 Program Status Select the process read data for I/O Assembly Instances
101/151. Elements [2] and [3] of this array can be selected. Elements [0] and [1] of the array are fixed.
10-13 Warning Parameter
Range: Function:
0
*
[0 - 65535] View a DeviceNet-specific Warning word. One bit is assigned to
every warning. Please refer to the DeviceNet Operating Instruc­tions (MG.33.DX.YY) for further information.
6
Bit: Meaning: 0 Bus not active 1 Explicit connection timeout 2 I/O connection 3 Retry limit reached 4 Actual is not updated 5CAN bus off 6 I/O send error 7 Initialization error 8 No bus supply 9Bus off 10 Error passive 11 Error warning 12 Duplicate MAC ID Error 13 RX queue overrun 14 TX queue overrun 15 CAN overrun
10-14 Net Reference
Read only from LCP.
Select the reference source in Instance 21/71 and 20/70.
[0]
Off Enables reference via analog/digital inputs.
*
[1] On Enables reference via the fieldbus.
10-15 Net Control
Read only from LCP.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
63
6. Parameters FC 100/ 200/ 300 DeviceNet
Select the control source in Instance 21/71 and 20-70.
6
[0]
[1] On enable control via the fieldbus.
10-20 COS Filter 1
Range: Function:
0
*
10-21 COS Filter 2
Range: Function:
65535
10-22 COS Filter 3
Range: Function:
65535
Off Enables control via analog/digital inputs.
*
[0 - FFFF] Sets up the filter mask for the status word. When operating in
COS (Change-Of-State), it is possible to filter out bits in the sta­tus word that should not be sent if they change.
[0 - 65535] Sets up the filter mask for the Main Actual Value. When oper-
*
ating in COS (Change-Of-State), it is possible to filter out bits in the Main actual value that should not be sent if they change.
[0 - 65535] Sets up the filter mask for PCD 3. When operating in COS
*
(Change-Of-State), it is possible to filter out bits in PCD 3 that should not be sent if they change.
10-23 COS Filter 4
Range: Function:
65535
10-30 Array Index
Range: Function:
0
*
10-31 Store Data Values
Option: Function:
[0]
[1] Store edit set-up
[2] Store all set-ups This parameter is used to activate a function that stores all pa-
[0 - 65535] Sets up the filter mask for PCD 4. When operating in COS
*
(Change-Of-State), it is possible to filter out bits in PCD 4 that should not be sent if they change.
[0 - 255] View array parameters. This parameter is valid only when a De-
viceNet fieldbus is installed.
Off
*
rameter values in the non-volatile memory thus retaining changed parameter values at power down.
'*Off:
The store function is inactive.
-
Store edit set-up:
­will be stored in the non-volatile memory. The value returns to
All parameter values in the set-up selected
Off
when all values have been stored.
64
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 6. Parameters
-
Store all set-ups:
volatile memory. The value returns to values have been stored.
10-33 Store Always
Option: Function:
[0]
[1] On This parameter is used to select whether parameter data re-
16-90 Alarm Word
Range: Function:
0
*
Off
*
ceived via the DeviceNet option should always be stored in non­volatile memory.
[0 - FFFFFFFF] View the alarm word sent via the serial communication port in
hex code.
All parameter values will be stored in the non-
Off
when all parameter
6
16-92 Warning Word
Range: Function:
0
*
[0 - FFFFFFFF] View the warning word sent via the serial communication port
in hex code.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
65
6
6. Parameters FC 100/ 200/ 300 DeviceNet
6.2. Parameter List
Par.
Parameter description Default value Range Conversion No. # 8-00 Enabled Options All [1] [0 - 7] - 5 8-01 Control Site Dig. & ctrl. word [0] [0 - 2] - 5 8-02 Control Word Source FC RS485 [0] [0 - 4] - 5 8-03 Control Word Timeout Time 1s 0.1-18000 -1 7 8-04 Control Word Timeout Function Off [0] [0 - 10] -1 5 8-05 End ofTimeout Function Hold set-up [0] [0 - 1] - 5 8-06 Reset Control Word Timeout Do not reset [0] [0 - 1] - 5 8-07 Diagnosis Trigger Disable [0] [0 - 3] - 5 8-10 Control Word Profile FC profile [0] [0 - x] - 5 8-50 Coasting Select Logic OR [3] [0 - 3] - 5 8-51 Quick Stop Select Logic OR [3] [0 - 3] - 5 8-52 DC Brake Select Logic OR [3] [0 - 3] - 5 8-53 Start Select Logic OR [3] [0 - 3] - 5 8-54 Reversing Select Logic OR [3] [0 - 3] - 5 8-55 Set-up Select Logic OR [3] [0 - 3] - 5 8-56 Preset Reference Select Logic OR [3] [0 - 3] - 5 8-90 Bus Jog 1 Speed 100 rpm 0 - par. 4-13 67 6 8-91 Bus Jog 2 Speed 200 rpm 0 par. 4-13 67 6 10-00 CAN Protocol DeviceNet [1] [0 - 1] - 5 10-01 Baud Rate Select 125 Kbps [20] [20 - 22] - 5 10-02 MAC ID 63 0 - 63 0 5 10-05 Readout Transmit Error Counter 0 0 - 255 0 5 10-06 Readout Receive Error Counter 0 0 - 255 0 6 10-07 Readout Bus Off Counter 0 0 - 1000 0 10-10 Process Data Type Selection [0]/[2] [0 - 3] 0 5 10-11 Process Data Config Write 0 list 0 5 10-12 Process Data Config Read 0 list 0 5 10-13 Warning Parameter 0 0 - FFFF 0 5 10-14 Net Reference Off [0] [0 - 1] - 5 10-15 Net Control Off [0] [0 - 1] - 5 10-20 COS Filter 1 0 0 - FFFF 0 6 10-21 COS Filter 2 0 0 - FFFF 0 6 10-22 COS Filter 3 0 0 - FFFF 0 6 10-23 COS Filter 4 0 0 - FFFF 0 6 10-30 Array Index 0 0 - 255 0 6 10-31 Store Data Values Off [0] [0 - 2] - 5 10-32 DeviceNet Revision - - - 6 10-33 Store Always Off [0] [0 - 1] - 5 16-90 Alarm Word 0 0 - FFFF 0 7 16-92 Warning Word 0 0 - FFFF 0 7
index
Data type
66
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 6. Parameters
6.3. Data Types Supported
6.3.1. Object and Data Types Supported
Data types supported
6.3.2. Conversion Index
This number refers to a conversion figure used when writing or reading to parameters.
Data type
3 Integer 16 4 Integer 32 5 Unsigned 8 6 Unsigned 16 7 Unsigned 32 9 Visible string 10 Byte string 33 Standardized value (16 bit) 35 Bit sequence 41 Byte 42 Word
Description
Conversion
index
100 1
67 1/60
6 1000000 5 100000 4 10000 3 1000 2 100 1 10 0 1
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
-5 0.00001
-6 0.000001
Conversion
factor
6
MG.33.D3.02 - VLT® is a registered Danfoss trademark
67
7
7. Application Examples FC 100/ 200/ 300 DeviceNet
68
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 7. Application Examples
7. Application Examples
7.1. Example: Working with Instance 101/151 Process
This example shows how to work with I/O In­stance 101/151, which consists of Control Word/Status Word and Reference/Main Actual Value. The Instance 101/151 also has two ad­ditional words, which can be programmed to monitor process signals, as shown in the fig­ure.
The application requires monitoring of the motor torque and digital input, so PCD 3 is set up to read the actual motor torque. PCD 4 is set up to monitor the state of an external sen­sor via the process signal digital input. The sensor is connected to digital input 18.
7
An external device is also controlled via con­trol word bit 11 and the built-in relay of the frequency converter.
Reversing is permitted only when the revers­ing bit 15 in the control word and the digital input 19 are set to high.
For safety reasons the frequency converter will stop the motor if the DeviceNet cable is broken, the master has a system failure, or the PLC is in stop mode.
MG.33.D3.02 - VLT® is a registered Danfoss trademark
69
7. Application Examples FC 100/ 200/ 300 DeviceNet
7
Parameter
Function Setting
No.
4-10 Motor speed range/direction Both directions [2] 5-10 Digital input 18 No operation [0] 5-11 Digital input 19 Reversing [10] 5-40 Function relay Control word bit 11 [36]
8-03 Control word timeout time 1.0 sec 8-04 Control word timeout function Stop [2] 8-10 Control word profile FC Profile 8-50 Coasting select Bus [1] 8-51 Quick-stop select Bus [1] 8-52 DC-brake select Bus [1] 8-53 Start select Bus [1] 8-54 Reversing select Logic AND [2] 8-55 Set-up select Bus [1] 8-56 Preset reference select Bus [1] 10-01 Baud rate select - set to match other DeviceNet stations 10-02 MAC ID - set desired station address 10-10 Process data type selection Instance 101/151 [1] 10-12 Process Data Config Read PCD 3: Torque
7.1.1. Example of PLC Programming
Control word bit 12 [37]
PCD 4: Digital input
In this example Instance 101/151 is placed in the following Input/Output address:
Input ad­dress
0.0-0.15 0.16-0.31 1.0-1.15 1.16-1.31
Set-up Status
word
MAV Motor tor-
que
Digital in-
put
70
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 7. Application Examples
Output ad­dress
0.0-0.15 0.16-0.31 1.0-1.15 1.16-1.31
Set-up Control
Reference Not used Not used
word
7
MG.33.D3.02 - VLT® is a registered Danfoss trademark
71
8. Troubleshooting FC 100/ 200/ 300 DeviceNet
8
72
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 8. Troubleshooting
8. Troubleshooting
8.1. Troubleshooting
8.1.1. LED Status
First, check the LEDs. The DeviceNet control card contains two bi-colour (green/red) LEDs to indicate the state of the device and the network respectively.
The upper LED indicates module status (MS). The lower LED indicates network status (NS).
State Bi-colour LED Status No Power Off There is no power applied to the option Device opera­tional Standby
Minor fault Unrecoverable
fault Self test
Table 8.1: LED: Module Status (MS)
Green
Green
Red Red
Green Red
The DeviceNet option is operating in nor­mal condition. The DeviceNet option needs commission­ing due to configuration missing, incom­plete or incorrect. Recoverable fault.
Unrecoverable fault, may need replacing.
The DeviceNet option is in Self-test mode.
8
MG.33.D3.02 - VLT® is a registered Danfoss trademark
73
8. Troubleshooting FC 100/ 200/ 300 DeviceNet
State Bi-colour LED Status No Power/Not on-line On-line, not con­nected On-line and con­nected Connection time­out Critical link fail­ure
Table 8.2: LED: Network Status (NS)
Off The option has not completed “Duplicate
MAC ID” test yet or may not be powered.
Green
Green
Red
Red
The option is on-line, but not allocated to a master. The DeviceNet option is on-line and con­nected to a master. One or more I/O connections are in time­out state.
8
74
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 8. Troubleshooting
8.1.2. No Communication with the Drive
If there is no communication with the drive, proceed with the following checks:
Check 1: Is the cabling correct? Check that the cables are connected to the correct terminals as shown in the diagram.
Pin no.
1 V- Black GND 2 CAN_L Blue CAN
3 Drain (bare) Screen 4 CAN_H White CAN
5 V+ Red +24 V
Check 2: Is the 24V network voltage applied?
Check 3: Is the correct EDS file installed? Download the correct EDS file from http://www.danfoss.com/drives.
Check 4: Is the bus connection terminated at both ends? If not, terminate the bus connection with termination resistors at the initial and final nodes, as shown in the following diagram. Termination is performed between terminal 2 (CAN_L) and 4 (CAN_H) with a resistor: 121 Ohm, 1% metal film, ¼ Watt.
Termi­nal
Colour Name
LOW
HIGH
8
MG.33.D3.02 - VLT® is a registered Danfoss trademark
75
8. Troubleshooting FC 100/ 200/ 300 DeviceNet
8.1.3. Drive Will Not Respond to Control Signals
- Danfoss Control Word profile (instances 100/150 and 101/151)
Check 1: Is the Control word valid? If bit 10=0 in the Control word, then the frequency converter will not accept the Control word, because the default setting is bit 10=1. Set bit 10=1 via the PLC.
Check 2: Is the relationship between bits in the Control word and the terminal I/Os correct? Check the logical relationship in the frequency converter. Set the logic to bit 3=1 AND digital input=1 in order to achieve a successful start.
Define the desired logical relationship in par. 8-50 to 8-56 according to the following range of options. Select the FC control mode, digital input and/or bus communication, using par. 8-50 to 8-56.
The tables below show the effect upon the frequency converter of a coast command for the full range of par. 8-50 settings.
8
The effect of control mode upon the function of par. 8-50
and 8-52
lect
Digital input
If will control the Coast and DC Brake functions.
If Bus [1] is selected, commands will be acti­vated only when given via the control word.
If Logic AND [2] is selected, both signals must be activated to perform the function.
If Logic OR [3] is selected, activation of one signal will activate the function.
DC Brake Select
is as follows:
[0] is selected, the terminals
Par. 8-50/51/52 setting: Terminal Bit 02/03/04 Function 0 0 Coast/DC brake/Q-Stop 0 1 Coast/DC brake/Q-Stop 1 0 No Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Par. 8-50/51/52 setting: Terminal Bit 02/03/04 Function 0 0 Coast/DC brake/Q-Stop 0 1 No Coast/DC brake/Q-Stop 1 0 Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Par. 8-50/51/52 setting: Terminal Bit 02/03/04 Function 0 0 Coast/DC brake/Q-Stop 0 1 No Coast/DC brake/Q-Stop 1 0 No Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Par. 8-50/51/52 setting: Terminal Bit 02/03/04 Function 0 0 Coast/DC brake/Q-Stop 0 1 Coast/DC brake/Q-Stop 1 0 Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Coasting Select
Digital Input [0]
Bus [1]
Logic AND [2]
Logic OR [3]
, 8-51
Quick Stop Se-
NB!
Please note that Coasting, Quick Stop and DC brake functions are active for logic “0’’.
76
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 8. Troubleshooting
The effect of control mode upon the function of par. 8-53
lect
:
Digital Input
If will control the start and reversing functions
If
Bus
[1] is selected, commands will be acti-
vated only when given via the control word.
If
Logic AND
be activated to perform the function.
If
Logic OR
signal will activate the function.
[0] is selected, the terminals
[2] is selected, both signals must
[3] is selected, activation of one
Par. 8-53/54 setting: Terminal Bit 06/15 Function 0 0 Stop/Anti-clockwise 0 1 Stop/Anti-clockwise 1 0 Start/Clockwise 1 1 Start/Clockwise
Par. 8-53/54 setting: Terminal Bit 02/03/04 Function 0 0 Stop/Anti-clockwise 0 1 Start/Clockwise 1 0 Stop/Anti-clockwise 1 1 Start/Clockwise
Par. 8-53/54 setting: Terminal Bit 02/03/04 Function 0 0 Stop/Anti-clockwise 0 1 Stop/Anti-clockwise 1 0 Stop/Anti-clockwise 1 1 Start/Clockwise
Par. 8-53/54 setting: Terminal Bit 02/03/04 Function 0 0 Stop/Anti-clockwise 0 1 Start/Clockwise 1 0 Start/Clockwise 1 1 Start/Clockwise
Start Select
and 8-54
Digital input [0]
Bus [1]
Logic AND [2]
Logic OR [3]
Reversing Se-
8
The effect of control mode upon the function of par. 8-55
:
Select
Digital input
If will control the set-up and preset reference functions.
[0] is selected, the terminals
Par. 8-55/56 setting: Terminal Bit 00/01,
Msb Lsb Msb Lsb Preset ref., Set-up no. 0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 2 0 1 0 1 2 0 1 1 0 2 0 1 1 1 2 1 0 0 0 3 1 0 0 1 3 1 0 1 0 3 1 0 1 1 3 1 1 0 0 4 1 1 0 1 4 1 1 1 0 4 1 1 1 1 4
Set-up Select
13/14
and 8-56
Digital input [0]
Preset Reference
Function
MG.33.D3.02 - VLT® is a registered Danfoss trademark
77
8
8. Troubleshooting FC 100/ 200/ 300 DeviceNet
If
Bus
[1] is selected, commands will be acti-
vated only when given via the control word.
If
Logic AND
[2] is selected, both signals must
be activated to perform the function.
Par. 8-55/56 setting: Terminal Bit 00/01,
Msb Lsb Msb Lsb Preset ref., Set-up no. 0 0 0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 1 0 1 0 1 2 0 1 1 0 3 0 1 1 1 4 1 0 0 0 1 1 0 0 1 2 1 0 1 0 3 1 0 1 1 4 1 1 0 0 1 1 1 0 1 2 1 1 1 0 3 1 1 1 1 4
Par. 8-55/56 setting: Terminal Bit 00/01,
Msb Lsb Msb Lsb Preset ref., Set-up no. 0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 2 0 1 1 0 1 0 1 1 1 2 1 0 0 0 1 1 0 0 1 1 1 0 1 0 3 1 0 1 1 3 1 1 0 0 1 1 1 0 1 2 1 1 1 0 3 1 1 1 1 4
Bus [1]
Function
13/14
Logic AND [2]
Function
13/14
If
Logic OR
[3] is selected, activation of one
signal will activate the function.
Par. 8-55/56 setting: Terminal Bit 00/01,
Msb Lsb Msb Lsb Preset ref., Set-up no. 0 0 0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 2 0 1 0 1 2 0 1 1 0 4 0 1 1 1 4 1 0 0 0 3 1 0 0 1 4 1 0 1 0 3 1 0 1 1 4 1 1 0 0 4 1 1 0 1 4 1 1 1 0 4
Logic OR [3]
Function
13/14
78
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet 8. Troubleshooting
8.1.4. Alarm Word and Warning Word
Alarm word and Warning word are shown on the display in Hex format. If there is more than one warning or alarm, a sum of all warnings or alarms will be shown. Alarm word and warning word can also be displayed using the field bus in par. 16-05, 16-06 and 16-04.
Bit (Hex) Alarm word
(Par. 16-90) 00000001 Unused - - ­00000002 Drive over temperature 29 Major Recoverable 00000004 Earth fault 14 Major Unrecoverable 00000008 Unused - - ­00000010 Control word timeout 18 Minor Recoverable 00000020 Over current 13 Major Unrecoverable 00000040 Torque limit 12 Major Recoverable 00000080 Motor thermistor over
temp. 00000100 Motor ETR over tempera-
ture 00000200 Inverter overloaded 9 Major Recoverable 00000400 DC link under voltage 8 Major Recoverable 00000800 DC link over voltage 7 Major Recoverable 00001000 Short circuit 16 Major Unrecoverable 00002000 Inrush fault 33 Major Recoverable 00004000 Mains phase loss 4 Major Unrecoverable 00008000 AMA not OK 50 Major Recoverable 00010000 Live zero error 2 Major Recoverable 00020000 Internal fault 38 Major Unrecoverable 00040000 Brake resistor power limit 26 Major Unrecoverable 00080000 Motor phase U is missing 30 Major Unrecoverable 00100000 Motor phase V is missing 31 Major Unrecoverable 00200000 Motor phase W is missing 32 Major Unrecoverable 00400000 Fieldbus comm. fault 34 Major Recoverable 00800000 24 V supply fault 47 Major Unrecoverable 01000000 Mains failure 36 Major Recoverable 02000000 1.8 V supply fault 48 Major Unrecoverable 04000000 Brake resistor short circuit 25 Major Recoverable 08000000 Brake chopper fault 27 Major Recoverable 10000000 Unused - - ­20000000 Unused - - ­40000000 Unused - - ­80000000 Unused - - -
FC 100/ 200/ 300
Alarm no. Major /
minor alarm
11 Major Recoverable
10 Major Recoverable
Recoverable / unrecoverable alarm
8
MG.33.D3.02 - VLT® is a registered Danfoss trademark
79
8. Troubleshooting FC 100/ 200/ 300 DeviceNet
8
Bit (Hex) Warning word (Par. 16-92) Warning no.
FC 100/ 200/ 300
00000001 Unused ­00000002 Drive over temperature 29 00000004 Earth fault 14 00000008 Unused ­00000010 Control word timeout 18 00000020 Over current 13 00000040 Torque limit 12 00000080 Motor thermistor over temp. 11 00000100 Motor ETR over temperature 10 00000200 Inverter overloaded 9 00000400 DC link under voltage 8 00000800 DC link over voltage 7 00001000 DC link voltage low 6 00002000 DC link voltage high 5 00004000 Mains phase loss 4 00008000 No motor 3 00010000 Live zero error 2 00020000 10 V low 1 00040000 Brake resistor power limit 26 00080000 Brake resistor short circuit 25 00100000 Brake chopper fault 27 00200000 Speed limit 49 00400000 Fieldbus comm. fault 34 00800000 24 V supply fault 47 01000000 Mains failure 36 02000000 Current limit 59 04000000 Unused ­08000000 Unused ­10000000 Unused ­20000000 Unused ­40000000 Unused ­80000000 Warning word 2 (ext. stat. word) -
8.2. Alarm/Warning Limits
8.2.1. Warnings and Alarm Messages
There is a clear distinction between alarms and warnings. In the event of an alarm, The frequency converter will enter a fault condition. After the cause for the alarm has been cleared, the master will have to acknowledge the alarm message for the frequency converter to start operating again. A warning on the other hand may come when a warning condition appears, and disappear when conditions return to normal without interfering with the process.
8.2.2. Warnings
All warnings within the frequency converter are represented by a single bit within a warning word. A warning word is always an action parameter. Bit status FALSE [0] means no warning, while bit status TRUE [1] means warning. To each bit and each bit status there is a corresponding text string. In addition to the warning word message the master will also be notified through a change of bit 7 in the Status Word.
8.2.3. Alarms
Following an Alarm message, the frequency converter will enter Fault condition. Only after the fault has been alleviated and the master has acknowledged the alarm message by setting bit 3 in the Control Word, can the frequency converter resume operation. All alarms within the frequency converter are represented by a single bit within an alarm word. An alarm word is always an action parameter. Bit status FALSE [0] means no alarm, while bit status TRUE [1] means alarm.
80
MG.33.D3.02 - VLT® is a registered Danfoss trademark
FC 100/ 200/ 300 DeviceNet Index
Index
A
Abbreviations 11
Alarm Word 79
Alarm Word, 16-90 65
Alarms 80
Array Index 10-30 64
B
Bus Jog 2 Speed 58
C
Cable Lengths 13
Cable Specifications 13
Change Of State, Cos 23
Coasting Select, 8-50 55
Connection Of The Cable Screen 15
Control Site, 8-01 53
Control Word Timeout Function 53
Conversion Index 67
D
Danfoss Fc Control Profile 32
Danfoss Object Classes 50
Dc Brake Select, 8-52 56
Devicenet Connection 16
Devicenet Object Classes 39
Devicenet Termination 16
Drive Will Not Respond To Control Signals 76
Drop Cable 16
E
Earth Connection 15
Eds File 21
Emc Precautions 14
I
I/o Assembly Instances 25
Installation Of Option In The Frequency Converter 17
L
Led Status 73
Leds 21
M
Mac Id, 10-02 58
N
Net Control 10-15 63
Net Reference 10-14 63
Network Power Consumption 16
No Communication With The Drive 75
O
Object And Data Types Supported 67
Odva Control Profile 27
Odva Recommendation 15
MG.33.D3.02 - VLT® is a registered Danfoss trademark
81
Index FC 100/ 200/ 300 DeviceNet
P
Polling 23
Preset Reference Select, 8-56 57
Q
Quick Stop Select 55
R
Reset Control Word Timeout 54
S
Safety Note 6
Setting The Devicenet Address 19
Setting The Devicenet Baud Rate 20
Start Select, 8-53 56
T
Topology 9
V
Vlt Parameters 21
W
Warning Parameter 10-13 63
Warning Word 79
Warning Word, 16-92 65
Warnings 80
82
MG.33.D3.02 - VLT® is a registered Danfoss trademark
Loading...