The VLT® PROFIBUS DP MCA 101 Programming Guide
provides information about configuring the system,
controlling the frequency converter, parameter access,
programming, troubleshooting, as well as some typical
application examples.
The programming guide is intended for use by qualified
personnel who are familiar with the VLT® frequency
converter, with PROFIBUS technology, and with the PC or
PLC that is used as a master in the system.
Read the instructions before programming and follow the
procedures in this manual.
VLT® is a registered trademark.
1.2 Additional Resources
Resources available for the frequency converters and
optional equipment:
The VLT® Operating Instructions provide the
•
necessary information for getting the frequency
converter up and running.
The VLT
•
information about capabilities and functionality to
design motor control systems.
The VLT® Programming Guide provides greater
•
detail on working with parameters and many
application examples.
The VLT® PROFIBUS DP MCA 101 Installation Guide
•
provides information about installing the
PROFIBUS and troubleshooting.
The VLT® PROFIBUS DP MCA 101 Programming
•
Guide provides information about configuring the
system, controlling the frequency converter,
parameter access, programming, troubleshooting,
as well as some typical application examples.
Supplementary publications and manuals are available
from Danfoss. See www.danfoss.com/BusinessAreas/DrivesSo-
PROFIdrive profile or Danfoss FC profile
Communication using PROFIBUS DP-V1, Master
•
Class 1 and Master Class 2.
Downward compatibility: New protocol
•
extensions retain all the functions of the previous
versions.
Intelligent base for future technologies such as
•
OPC, FDT/DTM, PROFINET.
Bus time-out reaction.
•
PLC/CPU stop reaction.
•
8 PPO types available.
•
Numerous relevant process data (PCD) types
•
available.
Automatic detection of baud rate and PPO type.
•
Extended diagnosis available.
•
Alarms and warnings available as text messages
•
within the PLC.
Configuration via MCT 10 Set-up Software.
•
Equidistant bus cycle time configurable in PLC
•
system.
Improved network efficiency, since the cyclic
•
parameter channel is no longer required.
Very short bus cycle times compared to industrial
•
ethernet .
Backwards compatibility with DP.
•
Technical Overview
1.4.2
1.3
Document and Software Version
This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the document version and the corresponding software
version.
PROFIBUS is an international standard for fieldbus
communication in automation technology (IEC 61158 and
IEC 61784). The standard is supported by the member
companies of the PROFIBUS International User Community.
For information about PROFIBUS and downloads for
PROFIBUS DP and the PROFIdrive profile, refer to
www.Profibus.com.
PLC
130BA078.10
PLC
Master class 1
PC tool
Master class 2
130BA079.10
IntroductionProgramming Guide
1
PROFIBUS DP-V1
The PROFIBUS DP protocol enables communication
between PROFIBUS masters and followers.
Communication can be configured via MCT 10 Set-up
Software.
Cyclical/Acyclical Communication
PLC communicates with telegrams of constant
•
length.
Fits time-critical requirements.
•
Cyclical transmission via PPO types.
•
Extended diagnosis.
•
Illustration 1.2 PROFIBUS DP-V1
The PROFIBUS DP extension DP-V1 permits acyclical as well
as cyclical data communication. This feature can be used
by a DP master class 1 (for example, PLC), as well as a DP
master class 2 (for example, PC tool).
Illustration 1.1 PROFIBUS DP-V0
Features of a Master class 1 connection:
Cyclical data exchange (DP-V0).
•
Acyclical read/write on parameters.
•
Extended diagnosis.
•
The acyclical connection is fixed, and cannot be changed
during operation.
Features of a Master class 2 connection:
Initiate/Abort acyclical connection.
•
Acyclical read/write on parameters.
•
The acyclical connection can be established (Initiate) or
removed (Abort) dynamically even when a master class 1 is
active on the network. The DP-V1 acyclical connection can
be used for general parameter access as an alternative to
the PCV parameter channel.
1.5
Approvals and Certifications
More approvals and certifications are available. For more
information, contact a local Danfoss partner.
CANController area network
CTWControl word
DPDistributed periphery
DUData unit
EEPROM Electrical erasable programmable read only memory
EMCElectromagnetic compatibility
FDTField device tool
INDSub index
LCDLiquid crystal display
LCPLocal control panel
LEDLight emitting diode
MAVMain actual value
MC1Master class 1
MC2Master class 2
MRVMain reference value
PCPersonal computer
PCDProcess data
PCAParameter characteristics
PCVParameter characteristics value
PDUProtocol data unit
PLCProgrammable logic control
PNUParameter number
PPOParameter-process data
PVAParameter value
RCRequest/Response characteristics
SAPService access point
SMPSpontaneous message
STWStatus word
1
1
Table 1.2 Symbols and Abbreviations
Conventions
Numbered lists indicate procedures.
Bullet lists indicate other information and description of illustrations.
* indicates a default setting in a parameter.
Italicised text indicates
Indicates a potentially hazardous situation which could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.2 Qualified Personnel
Correct and reliable transport, storage, installation,
operation, and maintenance are required for the troublefree and safe operation of the frequency converter. Only
qualified personnel are allowed to install or operate this
equipment.
Qualified personnel are defined as trained staff, who are
authorised to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Additionally, the personnel must be familiar
with the instructions and safety measures described in
these operating instructions.
2.3
Safety Precautions
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC power supply, or load
sharing. Failure to perform installation, start-up, and
maintenance by qualified personnel can result in death
or serious injury.
Installation, start-up, and maintenance must be
•
performed by qualified personnel only.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
DC power supply, or load sharing, the motor may start at
any time. Unintended start during programming, service
or repair work can result in death, serious injury, or
property damage. The motor can start by means of an
external switch, a serial bus command, an input
reference signal from the LCP or LOP, via remote
operation using MCT 10 software, or after a cleared fault
condition.
To prevent unintended motor start:
Disconnect the frequency converter from mains.
•
Press [Off/Reset] on the LCP, before
•
programming parameters.
The frequency converter, motor, and any driven
•
equipment must be fully wired and assembled
when the frequency converter is connected to
AC mains, DC power supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. Failure to wait the specified
time after power has been removed before performing
service or repair work, can result in death or serious
injury.
Stop motor.
•
Disconnect AC mains and remote DC-link power
•
supplies, including battery back-ups, UPS, and
DC-link connections to other frequency
converters.
Disconnect or lock PM motor.
•
Wait for the capacitors to discharge fully, before
•
performing any service or repair work. The
duration of waiting time is specified in the
relevant frequency converter OperatingInstructions, Chapter 2 Safety.
2.Set the DIP switch to 126 or 127 (factory switch
setting).
3.
Set the address via 9-18 Node Address or the
PROFIBUS SSA-command.
4.The address change comes into effect at the next
power-up.
130BC915.10
130BC913.11
Configuration
Setting the PROFIBUS Address with Set Station Address
Command
1.Switch off the power supply.
2.Set the DIP switch to 126 or 127 (factory switch
setting).
3.Set the address via the "Set Station Address"
command. Use the "Set Station Address"
command to lock the programmed address and
to change the address. Unlock the address setting
by changing the 9-18 Node Address or the address
switch, followed by a power cycle. A new address
is effective immediately after the "Set Station
Address" command.
Programming Guide
3.2 Configure the Master
3.2.1 GSD File
To configure a PROFIBUS Master, the configuration tool
needs a GSD file for each type of follower on the network.
The GSD file is a PROFIBUS DP standard text file containing
the necessary communications set-up data for a follower.
Download the GSD file for the FC 102, FC 202 and FC
301/302 frequency converters at www.danfoss.com/Busines-sAreas/DrivesSolutions/.
33
Illustration 3.3 Install GSD File
PROFIBUS SW version
(15-61 Option SW Version)
1.xda01040A.GSD
2.xda02040A.GSD
FCD 302da01040B.GSD
Table 3.2 GSD File
The example below show the procedure of configuring a
PROFIBUS Master for FC 301/302, but the procedure is also
valid for the FCD 302.
1.Import the GSD file in the configuration tool.
2.Import the GSD file to the Simatic Manager
software tool. Import a GSD file once only for
each frequency converter series, following the
initial installation of the software tool. See
Illustration 3.3.
3.Use the browser for the GSD file, install all files,
and import both a GSD file and a bitmap for the
device into the hardware catalogue. See
Illustration 3.4 and Illustration 3.5.
GSD file
Illustration 3.4 Import a GSD File and a Bitmap
Illustration 3.5 Add a new GSD File
4.Import and access the FC 301/302 GSD file via
the path in the hardware catalogue, see
Illustration 3.6.
Illustration 3.8 Drag and Drop PPO Type 6 Word Consistent to
Illustration 3.6 Import and Access the GSD file via the Path in
the Hardware Catalogue
5.Open a project, set up the hardware and add a
PROFIBUS master system.
6.Select FC 300, then drag and drop it onto the
PROFIBUS in the hardware diagram.
7.A window for the address of the FC 300 appears.
Select the address from the scroll-down list.
Ensure that the address setting matches the
previous address setting in 9-18 Node Address. See
Illustration 3.7.
the first slot
The configuration tool automatically assigns addresses in
the peripheral address area. In this example, the input and
output area have the following configurations:
PPO type 6
PCD word
number
Input
address
Set-upSTWMAV
1234
256-257258-259260-261262-263
parameter 9
-16 PCD
Read
Configu-
ration.2
parameter 9
-16 PCD
Read
Configu-
ration.3
Illustration 3.7 Select the Address
8.Set up the peripheral input and output data. Data
set up in the peripheral area is transmitted
cyclically via PPO types. Drag and drop a PPO
type 6 word consistent to the first slot, see
Illustration 3.8. See the PPO types in
chapter 4 Control for more information.
Table 3.3 PCD read (VLT to PLC)
PCD word
number
Output
address
Set-upCTWMRV
Table 3.4 PCD write (PLC to VLT)
1234
256-257258-259260-261262-263
parameter 9
-15 PCD
Write
Configu-
ration.2
parameter 9
-15 PCD
Write
Configu-
ration.3
Alternative: For PROFIBUS SW version 2.x and higher, Autoconfiguration of process data is supported. This feature
makes it possible to configure the process data
(parameter 9-15 PCD Write Configuration and
parameter 9-16 PCD Read Configuration) from the PLC/
Master. To use Auto-configuration, make sure to enable the
feature under DP follower Properties. See Illustration 3.9.
Illustration 3.9 Enable Feature under DP Follower Properties
Programming Guide
NOTICE
DP V1 diagnosis is supported for PROFIBUS SW version
2.x and higher. The default setting of the PROFIBUS
option is DP V1 diagnosis. If DP V0 diagnosis is required,
change the setting under DP follower Properties.
0-40 [Hand on] Key on LCP. Pressing [Hand on]
•
disables control of the frequency converter via
PROFIBUS.
Parameter 8-02 Control Word Source. After an
•
initial power-up, the frequency converter
automatically detects whether a fieldbus option is
installed in slot A, and sets parameter 8-02 ControlWord Source to [Option A]. If an option is added
or changed in or removed from an already
commissioned frequency converter, it does not
change parameter 8-02 Control Word Source, but
enters Trip mode, and the frequency converter
displays an error.
Parameter 8-10 Control Word Profile. Select
•
between the Danfoss FC Profile and the
PROFIdrive profile.
8-50 Coasting Select to 8-56 Preset Reference Select.
•
Select how to gate PROFIBUS control commands
with digital input command of the control card.
Parameter 8-03 Control Word Timeout Time to
•
8-05 End-of-Timeout Function. Set the reaction in
the event of a bus time-out via these parameters.
9-18 Node Address.
•
Parameter 8-07 Diagnosis Trigger.
•
NOTICE
When 8-01 Control Site is set to , the settings in
8-50 Coasting Select to 8-56 Preset Reference Select are
overruled, and all act on Bus-control.
33
Illustration 3.10 DP V1 Diagnosis
Download the configuration file to the PLC. The PROFIBUS
system is able to go online, and it starts to exchange data
when the PLC is set to Run mode.
3.3
Configure the Frequency Converter
3.3.1 Frequency Converter Parameters
The following parameters are important when configuring
the frequency converter with a PROFIBUS interface:
3.3.2 LEDs
The 2 bi-colour LEDs in the PROFIBUS card indicate the
status of PROFIBUS communication.
The LED marked NS (FCD 302: NS2) indicates the network
status, that is, the cyclical communication to the PROFIBUS
master. When this light is constant green, data exchange
between the master and the frequency converter is active.
The LED marked MS (FCD 302: BUS MS) indicates the
module status, that is, acyclical DP V1 communication from
either a PROFIBUS master class 1 (PLC) or a master class 2
(MCT 10, FDT tool). When this light is constant green, DP
V1 communication from master classes 1 and 2 is active.
For details of the full range of communications status
indicated by the LEDs, refer to chapter 8 Troubleshooting.
The PROFIBUS profile for frequency converters specifies a
number of communication objects (Parameter process data
objects, PPO). The PROFIBUS profile for frequency
converters is suitable for data exchange between a process
controller (for example PLC) and a frequency converter. All
PPOs are defined for cyclic data transfer (that is, DP V0), so
that process data (PCD) and parameters (PCA) can be
transferred from the master to the follower and vice versa.
Pure process data objects
PPO types 3, 4, 6, 7 and 8 are pure process data objects
for applications requiring no cyclic parameter access. The
PLC sends out process control data, and the frequency
converter then responds with a PPO of the same length,
containing process status data.
Illustration 4.1 shows the available PPO types:
PCD 1: The first 2 bytes of the process data area
•
(PCD 1) comprise a fixed part present in all PPO
types.
PCD 2: The next 2 bytes (PCD 2) are fixed for PCD
•
write entries (see parameter 9-15 PCD Write
Configuration [1]), but configurable for PCD readentries (see parameter 9-16 PCD Read Configuration [1]).
PCD 3-10: In the remaining bytes, from PCD 3
•
and on, the process data can be parameterised
with process signals, see
parameter 9-23 Parameters for Signals.
The signals for transmission from the master to the
frequency converter are determined by the setting in
parameter 9-15 PCD Write Configuration (request from
master to the frequency converter).
The signals for transmission from the frequency converter
to the master (response from the frequency converter to
master) are determined by the setting in
parameter 9-16 PCD Read Configuration .
Parameter channel and process data
PPO types 1, 2 and 5 consist of a parameter channel and
process data. Use the parameter channel for reading
and/or updating of parameters (successively). Alternatively,
for better utilisation of I/O and thus PLC capacity, access
parameters via DP V1, by selecting a pure process data
object (PPO type 3, 4, 6, 7 or 8).
Select the PPO type in the master configuration. The
selection is automatically recorded in the frequency
converter. No manual setting of PPO types in the
frequency converter is required. Read the current PPO type
in 9-22 Telegram Selection. The setting [1] Standard telegram1 is equivalent to PPO type 3.
In addition, all PPO types can be set up as word-consistent
or module-consistent. The process data area can be word
or module consistent, whereas the parameter channel
must always be module consistent.
Word-consistent data is transmitted as individual
•
independent words between the PLC and the
frequency converter.
Module-consistent data is transmitted as sets of
•
interrelated words transferred simultaneously
between the PLC and the frequency converter.
Use the process data part of the PPO to control and
monitor the frequency converter via the PROFIBUS.
4.2.1 Process Control Data
Process control data (PCD) is the process data sent from
the PLC to the frequency converter.
Master/follower
123.......10
CTWMRVPCD.......PCD
PCD write
Table 4.1 Process Control Data
PCD 1 contains a 16-bit control word, and each bit controls
a specific function of the frequency converter, see
chapter 4.3 Control Profile.
PCD 2 contains a 16-bit speed setpoint in percentage
format. See chapter 4.2.3 Reference Handling.
The content of PCD 3 to PCD 10 is determined by the
settings in parameter 9-15 PCD Write Configuration and
parameter 9-16 PCD Read Configuration.
4.2.2 Process Status Data
Process status data is the process data sent from the
frequency converter, and contains information about the
current state.
Follower master
123......10
STWMAVPCD......PCD
PCD read
Table 4.2 Process Status Data
PCD 1 contains a 16-bit status word, and each bit contains
information regarding a possible state of the frequency
converter.
PCD 2 contains per default the value of the current speed
of the frequency converter in percentage format (see
chapter 4.2.3 Reference Handling). PCD 2 can be configured
to contain other process signals.
The content of PCD 3 to PCD 10 is determined by the
settings in parameter 9-16 PCD Read Configuration.
4.2.3 Reference Handling
The reference handling is an advanced mechanism that
sums up references from different sources, as shown in
Illustration 4.2.
For more information on reference handling, refer to the
Design Guide of the relevant frequency converter.
Illustration 4.2 Reference
The actual output of the frequency converter is limited by
the speed limit parameters Motor Low/High Speed Limit
[RPM/Hz] in 4-11 Motor Speed Low Limit [RPM] to 4-14 Motor
Speed High Limit [Hz].
The final speed limit is set in 4-19 Max Output Frequency.
Table 4.3 lists the reference (MRV) and the feedback (MAV)
formats.
MRV/MAVInteger in hexInteger in decimal
100%400016,384
75%300012,288
50%20008,192
25%10004,096
0%00
-25%F000-4,096
-50%E000-8,192
-75%D000-12,288
-100%C000-16,384
Table 4.3 Reference/Feedback (MRV/MAV) Format
NOTICE
Negative numbers are formed as complement of 2.
44
The reference, or speed setpoint, is sent via PROFIBUS and
is always transmitted to the frequency converter in
percentage format as integers represented in hexadecimal
(0-4000 hex).
The reference (MRV) and feedback (MAV) are always scaled
equally. The setting of 3-00 Reference Range determines the
scaling of the reference and feedback (MAV), see
Illustration 4.3.
Illustration 4.3 Reference (MRV) and Feedback (MAV), Scaled
NOTICE
The data type for MRV and MAV is a N2 16-bit
standardised value, expressing a range from -200% to
+200% (8001 to 7FFF).
Example
The following settings determine the speed, as shown in
In process control operation, 1-00 Configuration Mode is set
to [3] Process.
The reference range in 3-00 Reference Range is always [0]
Min - Max.
Control
•
•
Programming Guide
MRV represents the process setpoint.
MAV expresses the actual process feedback
(range ±200%).
4.4
PROFIdrive Control Profile
This section describes the functionality of the control word
and status word in the PROFIdrive profile.
4.2.5 Influence of the Digital Input
Terminals upon FC Control Mode
Set the influence of the digital input terminals upon
44
control of the frequency converter in 8-50 Coasting Select
to 8-56 Preset Reference Select.
NOTICE
The setting of 8-01 Control Site overrules the settings in
8-50 Coasting Select to 8-56 Preset Reference Select. The
setting of terminal 37 Coast stop (safe) overrules any
other parameter.
Each of the digital input signals can be programmed to
logic AND, logic OR, or to have no relation to the
corresponding bit in the control word. In this way the
following signal sources initiate a specific control
command, for example stop/coast:
fieldbus only,
•
fieldbus AND digital input, or
•
either fieldbus OR digital input terminal.
•
CAUTION
To control the frequency converter via PROFIBUS, set
8-50 Coasting Select to either [1] Bus , or to [2] Logic AND,
and set 8-01 Control Site to [0] or [2].
For more detailed information and examples of logical
relationship options, see chapter 8 Troubleshooting.
4.3
Control Profile
Control the frequency converter according to
the PROFIdrive profile, see chapter 4.4 PROFIdrive
•
Control Profile, or
the Danfoss FC control profile, see
•
chapter 4.5 Danfoss FC Control Profile.
Select the desired control profile in parameter 8-10 ControlWord Profile. The choice of profile affects the control and
status word only.
Chapter 4.4 PROFIdrive Control Profile and
chapter 4.5 Danfoss FC Control Profile provide a detailed
description of control and status data.
4.4.1 Control Word according to PROFIdrive
Profile (CTW)
The control word is used to send commands from a master
(e.g. a PC) to a follower.
BitBit=0Bit=1
00OFF 1ON 1
01OFF 2ON 2
02OFF 3ON 3
03CoastingNo coasting
04Quick stopRamp
05Hold frequency outputUse ramp
06Ramp stopStart
07No functionReset
08Jog 1 OFFJog 1 ON
09Jog 2 OFFJog 2 ON
10Data invalidData valid
11No functionSlow down
12No functionCatch up
13Parameter set-upSelection lsb
14Parameter set-upSelection msb
15No functionReverse
Table 4.5 Control Word Bits
Explanation of the control bits
Bit 00, OFF 1/ON 1
Normal ramp stops using the ramp times of the actual
selected ramp.
Bit 00="0" leads to the stop and activation of the output
relay 1 or 2 if the output frequency is 0 Hz and if [Relay
123] has been selected in 5-40 Function Relay.
When bit 0="1", the frequency converter is in State 1:
“Switching on inhibited”.
Refer to Illustration 4.4.
Bit 01, OFF 2/ON 2
Coasting stop.
When bit 01="0", a coasting stop and activation of the
output relay 1 or 2 occurs if the output frequency is 0 Hz
and if [Relay 123] has been selected in 5-40 Function Relay.
When bit 01="1", the frequency converter is in State 1:
“Switching on inhibited”. Refer to Illustration 4.4.
Bit 02, OFF 3/ON 3
Quick stop using the ramp time of 3-81 Quick Stop Ramp
Time.
When bit 02="0", a quick stop and activation of the output
relay 1 or 2 occurs if the output frequency is 0 Hz and if
[Relay 123] has been selected in 5-40 Function Relay.
When bit 02="1", the frequency converter is in State 1:
“Switching on inhibited”.
Coasting stop Bit 03="0" leads to a stop.
When bit 03="1", the frequency converter can start if the
other start conditions are fulfilled.
NOTICE
The selection in 8-50 Coasting Select determines how bit
03 is linked with the corresponding function of the
digital inputs.
Bit 04, Quick stop/Ramp
Quick stop using the ramp time of 3-81 Quick Stop Ramp
Time.
When bit 04="0", a quick stop occurs.
When bit 04="1", the frequency converter can start if the
other start conditions are fulfilled.
NOTICE
The selection in parameter 8-51 Quick Stop Select
determines how bit 04 is linked with the corresponding
function of the digital inputs.
Bit 05, Hold frequency output/Use ramp
When bit 05="0", the current output frequency is being
maintained even if the reference value is modified.
When bit 05="1", the frequency converter can perform its
regulating function again; operation occurs according to
the respective reference value.
Bit 06, Ramp stop/Start
Normal ramp stop using the ramp times of the actual
ramp as selected. In addition, activation of the output relay
01 or 04 if the output frequency is 0 Hz if Relay 123 has
been selected in 5-40 Function Relay. Bit 06="0" leads to a
stop. When bit 06="1", the frequency converter can start if
the other start conditions are fulfilled.
NOTICE
The selection in 8-53 Start Select determines how bit 06
is linked with the corresponding function of the digital
inputs.
Bit 07, No function/Reset
Reset after switching off. Acknowledges event in fault
buffer.
When bit 07="0", no reset occurs.
When there is a slope change of bit 07 to "1", a reset
occurs after switching off.
Bit 08, Jog 1 OFF/ON
Activation of the pre-programmed speed in 8-90 Bus Jog 1
Speed. JOG 1 is only possible if bit 04="0" and bit
00-03="1".
Bit 09, Jog 2 OFF/ON
Activation of the pre-programmed speed in 8-91 Bus Jog 2
Speed. JOG 2 is only possible if bit 04="0" and bit
00-03="1".
Bit 10, Data invalid/valid
Used to tell the frequency converter whether the control
word is to be used or ignored. Bit 10=“0” causes the
control word to be ignored, giving the opportunity to turn
off the control word when updating/reading parameters.
Bit 10=“1” causes the control word to be used. This
function is relevant, because the control word is always
contained in the telegram, regardless of which type of
telegram is used.
Bit 11, No function/Slow down
Used to reduce the speed reference value by the amount
given in 3-12 Catch up/slow Down Value value.
When bit 11="0", no modification of the reference value
occurs.
When bit 11="1", the reference value is reduced.
Bit 12, No function/Catch up
Used to increase the speed reference value by the amount
given in 3-12 Catch up/slow Down Value.
When bit 12="0", no modification of the reference value
occurs.
When bit 12="1", the reference value is increased.
If both slowing down and accelerating are activated (bit 11
and 12="1"), slowing down has priority, and the speed
reference value is reduced.
Bits 13/14, Set-up selection
Bits 13 and 14 are used to select between the 4 parameter
set-ups according to Table 4.6.
The function is only possible if Multi Set-up has been
selected in 0-10 Active Set-up. The selection in 8-55 Set-upSelect determines how bits 13 and 14 are linked with the
corresponding function of the digital inputs. Changing setup while running is only possible if the set-ups have been
linked in 0-12 This Set-up Linked to.
Set-upBit 13Bit 14
100
210
301
411
Table 4.6 Parameter Set-ups
Bit 15, No function/Reverse
Bit 15=“0” causes no reversing.
Bit 15=“1” causes reversing.
NOTICE
In the factory setting, reversing is set to digital in
parameter 8-54 Reversing Select.
NOTICE
Bit 15 causes reversing only when Ser. communication,
Logic or or Logic and is selected.
4.4.2 Status Word according to PROFIdrive
Profile (STW)
When bit 02 of the control word is "1", bit 05="1".
Bit 06, Start possible/Start not possible
If PROFIdrive has been selected in parameter 8-10 Control
The status word is used to notify a master (e.g. a PC)
about the status of a follower.
Word Profile, bit 06 is "1" after a switch-off acknowledgment, after activation of OFF2 or OFF3, and after
switching on the mains voltage. Start not possible is reset,
BitBit=0Bit=1
00Control not readyControl ready
44
01Drive not readyDrive ready
02CoastingEnable
03No errorTrip
04OFF 2ON 2
05OFF 3ON 3
06Start possibleStart not possible
07No warningWarning
08
09Local operationBus control
10Out of frequency limit Frequency limit ok
11No operationIn operation
12Drive OKStopped, autostart
13Voltage OKVoltage exceeded
14Torque OKTorque exceeded
15Timer OKTimer exceeded
Table 4.7 Status Word Bits
Speed ≠ reference
Speed = reference
with bit 00 of the control word being set to "0" and bit 01,
02 and 10 being set to "1".
Bit 07, No warning/Warning
Bit 07=“0” means that there are no warnings.
Bit 07=“1” means that a warning has occurred.
Bit 08, Speed≠reference/Speed=reference
When bit 08="0", the current speed of the motor deviates
from the set speed reference value. This may occur, for
example, when the speed is being changed during start/
stop through ramp up/down.
When bit 08="1", the current speed of the motor
corresponds to the set speed reference value.
Bit 09, Local operation/Bus control
Bit 09="0" indicates that the frequency converter has been
stopped with [Stop] on the LCP, or that [Linked to hand]
or [Local] has been selected in 3-13 Reference Site.
When bit 09="1", the frequency converter can be
controlled through the serial interface.
Bit 10, Out of frequency limit/Frequency limit OK
Explanation of the status bits
Bit 00, Control not ready/Ready
When bit 00="0", bit 00, 01 or 02 of the control word is "0"
(OFF 1, OFF 2 or OFF 3) - or the frequency converter is
switched off (trip).
When bit 00="1", the frequency converter control is ready,
but there is not necessarily power supply to the unit
present (in the event of external 24 V supply of the control
system).
Bit 01, VLT not ready/Ready
Same significance as bit 00, however, there is a supply of
the power unit. The frequency converter is ready when it
receives the necessary start signals.
Bit 02, Coasting/Enable
When bit 02="0", bit 00, 01 or 02 of the control word is "0"
(OFF 1, OFF 2 or OFF 3 or coasting) - or the frequency
converter is switched off (trip).
When bit 02="1", bit 00, 01 or 02 of the control word is
"1"; the frequency converter has not tripped.
Bit 03, No error/Trip
When bit 03="0", no error condition of the frequency
converter exists.
When bit 03="1", the frequency converter has tripped and
requires a reset signal before it can start.
Bit 04, ON 2/OFF 2
When bit 01 of the control word is "0", bit 04="0".
When bit 01 of the control word is "1", bit 04="1".
Bit 05, ON 3/OFF 3
When bit 10="0", the output frequency is outside the limits
set in 4-52 Warning Speed Low and 4-53 Warning SpeedHigh.
When bit 10="1", the output frequency is within the
indicated limits.
Bit 11, No operation/Operation
When bit 11="0", the motor does not turn.
When bit 11="1", the frequency converter has a start
signal, or the output frequency is higher than 0 Hz.
Bit 12, Drive OK/Stopped, autostart
When bit 12="0", there is no temporary overloading of the
inverter.
When bit 12="1", the frequency converter has stopped due
to overloading. However, the frequency converter has not
switched off (trip) and starts again after the overloading
has ended.
Bit 13, Voltage OK/Voltage exceeded
When bit 13="0", the voltage limits of the frequency
converter are not exceeded.
When bit 13="1", the direct voltage in the intermediate
circuit of the frequency converter is too low or too high.
Bit 14, Torque OK/Torque exceeded
When bit 14="0", the motor torque is below the limit
selected in 4-16 Torque Limit Motor Mode and 4-17 TorqueLimit Generator Mode.
When bit 14="1", the limit selected in 4-16 Torque LimitMotor Mode or 4-17 Torque Limit Generator Mode is
exceeded.
When bit 02 of the control word is "0", bit 05="0".
When bit 15="0", the timers for the thermal motor
protection and thermal frequency converter protection
have not exceeded 100%.
When bit 15="1", one of the timers has exceeded 100%.
4.4.3 PROFIdrive State Transition Diagram
In the PROFIdrive control profile, the control bits:
0 to 3 perform the basic start-up/power down functions.
•
4-15 perform application-oriented control.
•
Illustration 4.4 shows the basic state transition diagram, where control bits 0 to 3 control the transitions, and the
corresponding status bit indicates the actual state. The black bullets indicate the priority of the control signals, where fewer
bullets indicate lower priority, and more bullets indicate higher priority.
44
Illustration 4.4 PROFIdrive State Transition Diagram
Explanation of the control bits
Bits 00/01 Reference value
Bits 00 and 01 are used to select between the 4 reference
values, which are pre-programmed in 3-10 Preset Reference
according to Table 4.9.
NOTICE
In 8-56 Preset Reference Select a selection is made to
define how bit 00/01 gates with the corresponding
function on the digital inputs.
Bit 01Bit 00Programmed
ref. value
001
012
103
114
Table 4.9 Programmed Reference Values for Bits
Bit 02, DC brake
Bit 02=“0” - leads to DC braking and stop. Braking current
and duration are set in 2-01 DC Brake Current and 2-02 DCBraking Time.
Bit 02=“1” - leads to ramping.
Bit 03=“0” - causes the frequency converter immediately to
coast the motor to a standstill.
Bit 03=“1” - enables the frequency converter to start the
motor if the other starting conditions have been fulfilled.
NOTICE
In 8-50 Coasting Select a selection is made to define how
bit 03 gates with the corresponding function on a digital
input.
Bit 04, Quick stop
Bit 04=“0” - causes a quick stop, ramping the motor speed
down to stop via 3-81 Quick Stop Ramp Time.
Bit 04=“1” - the frequency converter ramps the motor
speed down to stop via 3-42 Ramp 1 Ramp Down Time or
3-52 Ramp 2 Ramp Down Time.
Bit 05, Hold output frequency
Bit 05=“0” - causes the present output frequency (in Hz) to
freeze. The frozen output frequency can only be changed
with the digital inputs (5-10 Terminal 18 Digital Input to
5-15 Terminal 33 Digital Input) programmed to Speed up
and Speed down.
Bit 05=“1” - use ramp.
NOTICE
If Freeze output is active, stop the frequency converter
with
Bit 03 Coasting stop.
•
Bit 02 DC braking.
•
Digital input (5-10 Terminal 18 Digital Input to
•
5-15 Terminal 33 Digital Input) programmed to
DC braking, Coasting stop, or Reset and coasting
stop.
Bit 06, Ramp stop/start
Bit 06=“0” - causes a stop in which the motor speed is
ramped down to stop via the selected ramp down
parameter.
Bit 06=“1" - permits the frequency converter to start the
motor, if the other starting conditions have been fulfilled.
NOTICE
In 8-53 Start Select a selection is made to define how bit
06 Ramp stop/start gates with the corresponding
function on a digital input.
Bit 07, Reset
Bit 07="0" - does not cause a reset.
Bit 07="1" - causes the reset of a trip. Reset is activated on
the signal’s leading edge, that is, when changing from
logic "0" to logic "1".
Bit 08="1" - 3-19 Jog Speed [RPM] determines the output
frequency.
Bit 09, Selection of ramp 1/2
Bit 09="0" - ramp 1 is active (3-40 Ramp 1 Type to
3-47 Ramp 1 S-ramp Ratio at Decel. Start).
Bit 09="1" - ramp 2 (3-50 Ramp 2 Type to 3-57 Ramp 2 Sramp Ratio at Decel. Start) is active.
Bit 10, Data not valid/Data valid
Tells the frequency converter whether it should use or
ignore the control word.
Bit 10="0" - the control word is ignored.
Bit 10="1" - the control word is used. This function is
relevant, because the control word is always contained in
the telegram, regardless of which type of telegram is used.
Thus, it is possible to turn off the control word, if it is not
wished to use it when updating or reading parameters.
Bit 11, Relay 01
Bit 11="0" - relay 01 not activated.
Bit 11="1" - relay 01 activated, provided control word bit
11 has been selected in 5-40 Function Relay.
Bit 12, Relay 04
Bit 12="0" - relay 04 has not been activated.
Bit 12="1" - relay 04 has been activated, provided Controlword bit 12 has been selected in 5-40 Function Relay.
Bit 13/14, Selection of set-up
Bits 13 and 14 are used to select from the 4 menu set-ups
according to Table 4.10:
The function is only possible when Multi-Set-ups is selected
in 0-10 Active Set-up.
Set-upBit 14Bit 13
100
201
310
411
Table 4.10 Selection of Set-up
NOTICE
In 8-55 Set-up Select a selection is made to define how
bit 13/14 gates with the corresponding function on the
digital inputs.
Bit 15 Reverse
Bit 15="0" - no reversing.
Bit 15="1" - reversing.
4.5.2
Status Word according to FC Profile
(STW)
The status word is used to inform the master (e.g. a PC) of
the operation mode of the slave (frequency converter).
Refer to
chapter 7 Application Examples for an example of a
status word telegram using PPO type 3.
BitBit=0Bit=1
00Control not readyControl ready
01Frequency converter
not ready
02CoastingEnable
03No errorTrip
04No errorError (no trip)
05Reserved06No errorTriplock
07No warningWarning
08Speed referenceSpeed=reference
09Local operationBus control
10Out of frequency limitFrequency limit ok
11No operationIn operation
12Frequency converter OK Stopped, autostart
13Voltage OKVoltage exceeded
14Torque OKTorque exceeded
15Timer OKTimer exceeded
Table 4.11 Definition of Status Bits
Frequency converter ready
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00="0" - the frequency converter has tripped.
Bit 00="1" - the frequency converter controls are ready, but
the power component is not necessarily receiving any
power supply (in case of 24 V external supply to controls).
Bit 01, frequency converter ready
Bit 01="0" - the frequency converter is not ready for
operation.
Bit 01="1" - the frequency converter is ready for operation,
but there is an active coasting command via the digital
inputs or via serial communication.
Bit 02, Coasting stop
Bit 02="0" - the frequency converter has released the
motor.
Bit 02="1" - the frequency converter can start the motor
when a start command is given.
Bit 03, No error/Trip
Bit 03="0" - the frequency converter is not in fault mode.
Bit 03="1" - the frequency converter is tripped, and that a
reset signal is required to re-establish operation.
Bit 04, No error/Error (no trip)
Bit 04="0" - the frequency converter is not in fault mode.
Bit 04=“1” - there is a frequency converter error but no
trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06="0" - the frequency converter is not in fault mode.
Bit 06=“1” - the frequency converter is tripped, and locked.
Bit 07="0" - there are no warnings.
Bit 07="1" - a warning has occurred.
Bit 08, Speed reference/Speed = reference
Bit 08="0" - the motor is running, but the present speed is
different from the preset speed reference. It could, for
example, be the case while the speed is being ramped up/
down during start/stop.
44
Bit 08="1" - the present motor present speed matches the
preset speed reference.
Bit 09, Local operation/bus control
Bit 09="0" - [Stop/Reset] is pressed on the LCP, or that
Local control in 3-13 Reference Site is selected. It is not
possible to control the frequency converter via serial
communication.
Bit 09="1" - it is possible to control the frequency
converter via the fieldbus/serial communication.
Bit 10, Out of frequency limit
Bit 10="0" - the output frequency has reached the value in
4-11 Motor Speed Low Limit [RPM] or 4-13 Motor Speed High
Limit [RPM].
Bit 10="1" - the output frequency is within the defined
limits.
Bit 11, No operation/In operation
Bit 11="0" - the motor is not running.
Bit 11="1" - the frequency converter has a start signal or
the output frequency is higher than 0 Hz.
Bit 12, frequency converter OK/Stopped, auto start
Bit 12="0" - there is no temporary over-temperature on the
frequency converter.
Bit 12="1" - the frequency converter has stopped because
of over-temperature, but the frequency converter has not
tripped and resumes operation once the over-temperature
stops.
Bit 13, Voltage OK/Limit exceeded
Bit 13="0" - there are no voltage warnings.
Bit 13="1" - the DC voltage in the frequency converters
intermediate circuit is too low or too high.
Bit 14, Torque OK/Limit exceeded
Bit 14="0" - the motor current is lower than the torque
limit selected in 4-16 Torque Limit Motor Mode or
4-17 Torque Limit Generator Mode.
Bit 14="1" - the torque limits in 4-16 Torque Limit MotorMode and 4-17 Torque Limit Generator Mode have been
exceeded.
Bit 15, Timer OK/Limit exceeded
Bit 15="0" - the timers for motor thermal protection and
frequency converter thermal protection, have not
exceeded 100%.
Bit 15="1" - one of the timers has exceeded 100%.
SYNC/UNSYNC is used to synchronise control commands
and/or speed reference to all the connected frequency
converters.
FREEZE/UNFREEZE is used to freeze the status feedback in
the slaves to get synchronized feedback from all
connected slaves.
The synchronise and freeze commands affect only process
data (the PCD part of the PPO).
4.6.1 SYNC/UNSYNC
SYNC/UNSYNC can be used to obtain simultaneous
reactions in several slaves, for example synchronised start,
stop or speed change.
A SYNC command freezes the relevant control word and
speed reference. Incoming process data are stored but not
used until a new SYNC command or a UNSYNC command
is received.
An UNSYNC command stops the synchronisation
mechanism and enables normal DP data exchange.
FREEZE/UNFREEZE
4.6.2
FREEZE/UNFREEZE can be used for simultaneous reading of
process data, for example, output current, from several
slaves.
A FREEZE command freezes the actual values and upon
request the slave sends back the value that was present
when the FREEZE command was received.
Upon receipt of an UNFREEZE command the values once
again is continuously updated and the slave returns a
present value, for example, a value generated by
conditions at present time.
The values is updated when a new FREEZE or UNFREEZE
command is received.
4.6
Synchronise and Freeze
The control commands SYNC/UNSYNC and FREEZE/
UNFREEZE are broadcast functions.
In an automated system, frequency converter parameters
can be accessed either from the process controller (that is,
PLC), or from various kinds of HMI equipment. For
parameter access from controllers and HMI, observe the
following:
Parameters are located in 4 separate set-ups. Parameter
access in the frequency converter is performed via several
separated parameter channels. Use the separated channels
individually to access a certain parameter set-up. Select the
desired set-up in 0-11 Edit Set-up or 9-70 Edit Set-up.
Using the above mechanism it is possible to read or write
to and from parameters in a certain set-up from a master
class 1, for example a PLC. And it is also possible to
simultaneously access parameters in a different set-up
from a master class 2, for example a PC tool, without
interfering with the set-up selection for the programming
sources.
Parameters can be accessed via the following sites:
LCP
•
FC Protocol on RS485 or USB
•
Cyclical data access on DP-V0 (PCV Channel)
•
PROFIBUS Master Class 1
•
PROFIBUS Master Class 2 (3 connections possible)
•
Using the special request IDs 0X51 (read) and 0X52 (write),
it is possible to read and write to all parameters containing
numeric values in a general format of double word. The
value element must be right aligned and unused MSBs
filled with zeros.
Example: Read of a parameter of type U8 is transmitted as
00 00 00 xx, where xx is the value to be transmitted. The
data type signalled by the telegram is 43h (dword).
5.1.3 PROFIBUS DP-V1
Using the acyclic DP-V1 transmission, it is possible to read
and write parameter values, as well as to read a number of
descriptive attributes for each parameter. Access to
parameters via DP-V1 is described in chapter 5.2 DP-V1Parameter Access.
PROFIBUS DP-V0/PCV Channel
5.1.4
Parameter access via the PCV channel is performed using
PROFIBUS DP-V0 cyclic data exchange, where the PCV
channel is part of the PPOs described in chapter 4.1 PPOTypes. Using the PCV channel, it is possible to read and
write parameter values, as well as read a number of
descriptive attributes for each parameter. The functionality
of the PCV channel is described in chapter 5.3 PCVParameter Access.
55
NOTICE
Although the parameter channels are separated, data
conflict can occur if write to parameters is made from an
HMI unit into a set-up which is actively in use by the
frequency converter or the process controller (e.g. a
PLC).
5.1.1 Data Store
Parameters write via the PCV channel (DP-V0) is stored in
RAM only. If data has to be stored in non-volatile memory,
the 9-71 Profibus Save Data Values can be used for storing
one or more set-ups.
Using DP-V1 access, store parameters either in RAM or
non-volatile memory by choice of a specific write-request
command. At any time, store non-stored data in nonvolatile memory by activating 9-71 Profibus Save DataValues.
NOTICE
Object and data types common to both DP-V1 and PCV
parameter access are listed in chapter 5 Parameter Access.
5.2 DP-V1 Parameter Access
This section is useful for the developer with some
experience in:
PLC programs with PROFIBUS master class 1
•
functionality.
PC applications with PROFIBUS master class 2
•
functionality.
For more detailed instructions in use of the DP-V1
function, refer to the PROFIBUS master manual from the
PLC supplier.
The PROFIBUS DP extension DP-V1 offers acyclical
communication in addition to the cyclical data communication of DP-V0. This feature is possible using a DP master
class 1 (for example, PLC), as well as a DP master class 2
(for example, PC Tool).
Cyclical communication means that data transfer takes
place continuously with a certain refresh rate. This is the
known DP-V0 function normally used for quick update of
I/O process data.
In a DP cycle, the master class 1 (MC1) first updates the
cyclical process data for all slaves in the system. The MC1
then sends one acyclical message to one slave. If a master
class 2 (MC2) is connected, the MC1 hands over the bus
rights to MC2, which is then permitted to send one
acyclical message to one slave. The token is then handed
back to the MC1, and a new DP cycle begins.
55
Acyclical communication takes the form of a once-off data
transfer event, mainly used for read/write from and to
parameters from process controllers, PC-based tools or
monitoring systems.
Features of a Master Class 1
5.2.2
Connection
Cyclical data exchange (DP-V0)
•
Acyclical read/write from and to parameters
•
A master class 1 is used as the process controller (either
PLC or PC-based), responsible for commands, speed
reference, status of the application, etc. The master class 1
acyclical connection can be used for general parameter
access in the slaves. However, the acyclical connection is
fixed, and cannot be changed during operation.
Features of a Master Class 2
5.2.3
Connection
Initiate/abort acyclical connection
•
Acyclical read/write from and to parameters
•
The master class 2 acyclical connection is typically used for
configuration or commissioning tools for easy access to
each parameter in any slave in the system. The acyclical
connection can be dynamically established (initiate) or
removed (abort) even when a master class 1 is active on
the network.
Illustration 5.1 DP Cycle
MC: Master class
•
C1...Cn: Cyclical data
•
AC1: Acyclical data master class 1
•
AC2: Acyclical data master class 2
•
PROFIBUS DP services are activated via specific service
access points (SAP). Table 5.2 shows the SAP specified for
acyclical communication.
Master
SAP
50 (32H)49 (31H)Master Class 2: Initiate request
50 (32H)0..48 (0..30H)Master Class 2: Abort, read, write, data
This section describes how to use DP-V1 for accessing VLT
parameters.
The standard PROFIBUS DP-V1 read and write services are
not sufficient for accessing the many parameters and
attributes in the frequency converter. For this reason, the
PROFIdrive parameter channel is defined. Using this
parameter read/write is performed by addressing a single
DP-V1 object in the frequency converter as shown in the
example, Table 5.3.
Parameter Access
Programming Guide
For a detailed description of the DP-V1 command
handling, refer to the PROFIBUS DP-V1 Design Guide.
Example
Slot=0
Index=47
PROFIBUS
telegram
header
DU0DU1D
Table 5.3 General Structure for Telegram
Data unitPROFIBUSDP-V1
Command/
response
PROFIdrive V3.0 parameter
channel
D
Req./Res.
U
U
Header
2
3
Data
telegram
trailer
Use the DP-V1 command/response part for the standard
DP-V1 read/write on slot 0, index 47 data block.
Use the PROFIdrive V3 parameter channel to access
specific parameter data in the frequency converter.
DP-V1 Read/Write Services
5.2.7
Table 5.4 shows the content of the DP-V1 command/
Response headers and their possible attributes.
set by the master within the corresponding
request telegram
A data field, where the requested data are placed.
•
If one or more internal requests have failed, an
PROFIdrive Parameter Channel
1) U8 - Unsigned8, U16 - Unsigned16
5.2.10 Request Reference
error code is placed instead of the data values
Unique identification of request/response pair for the
DP-V1Parameter responseByte no.
Response headerRequest ref. mirrored0
Parameter valuesNo. of parameters3
55
Table 5.7 DP-V1 Parameter Response Telegram
Response ID1
Axis mirrored2
Format4
No. of values5
Values of error values6
n'th parameter value...
As the response telegram does not include parameter
addressing information, the master must identify the
structure of the response data from the request telegram.
Request/Response Attributes
5.2.9
Table 5.8 contains an overview of the possible attributes of
the PROFIdrive parameter channel.
master. The master changes the request reference with
each new request. The slave mirrors the request reference
in the response.
5.2.11 Request ID
0x01 Request parameter.
0x02 Change parameter (data is NOT stored in non-volatile memory,
lost at power cycle).
0x42 Change parameter non-volatile (data is stored in non-volatile
memory).
0x51 Request parameter value double word. All parameters are
formatted and transferred as double word size, regardless of the
actual data type.
0x52 Change parameter value double word. All parameters must be
formatted and sent as double word size, regardless of data type.
Table 5.9 Defined Request Identification
5.2.12
Response ID
Data
Field
Request
reference
Request ID U80x01Request parameter
ResponseIDU80x01Request parameter
AxisU80x00..0xFFNumber (always 0)
No. of
parameter
s
AttributeU80x10Value
No. of
elements
ValuesRemark
1)
type
U80x01..0xFF
0x02Change parameter
0x42Change parameter
0x51Request par. value
0x52Change par. value
0x02Change parameter
0x81Request parameter
0x82Change parameter (-)
U80x01..0x25 Limitation: DP-V1
0x20DescriptionData description
0x30Text
U8Limitation: DP-V1
0x01-0xFAQuantity 1-234
value
value
non-volatile
double word
double word
(+) Positive
(+) Positive
(-) Negative
Negative
Identification for
read or write
request
Identification for
the response
telegram length
telegram length
The response ID indicates if the read or write request was
successfully performed in the frequency converter. If the
response is negative, the request is answered negative
(first bit=1) and an error code is entered per partial
response, instead of the value.
5.2.13
Axis
The axis attribute should be set to 0.
5.2.14
Number of Parameters
For multi-parameter requests specifying the number of the
parameter address and/or parameter value areas. For a
single request, the number is 1.
5.2.15
Attribute
The attribute determines which data to access. The
frequency converter responds to the attributes value (10
H), description (20 H) and text (30 H).
5.2.16
Attribute Value (10H)
Parameter
no.
SubindexU160x0000Number 0-65535Array pointer
FormatU8See table
No. of
values
Error no.U160x0000... Error number
The attribute value permits reading or writing of parameter
values.
Parameter Access
Programming Guide
5.2.17 Attribute Description (20H)
The attribute description permits access to the parameter
description. It is possible to read out one single description
element, or all elements for one parameter in one
telegram. Table 5.10 provides an overview of the existing
parameter description, which exists for each parameter in
the frequency converter.
Table 5.10 Parameter Description Elements (all Elements are
Read-only)
length or string
Table 5.11 explains each description element.
Identifier ID
Bit
15Reserved
14Array
13Parameter value can be reset only.
12Parameter has been changed from factory setting.
11Reserved
10Additional text array available
9Parameter is read-only.
8Standardisation factor and variable attribute not relevant.
0-7Data type
Meaning
U16
index of -1 means, that the actual value must be divided
by 10 to become a standard physical unit for example,
Volt.
Name
Contains the parameter name, limited to 16 characters, for
example, LANGUAGE for 0-01 Language. This text is
available in the language selected in 0-01 Language.
Lower limit
Contains the minimum value of the parameter. Format is
32 bit signed.
Upper limit
Contains the maximum value of the parameter. Format is
32 bit signed.
ID extension
Not supported.
PCD reference parameter
Process data may be scaled by a parameter, for example,
the max reference of 0x4000 (in %) depends on the setting
of parameter X.
To enable the master to calculate the real value of the
process data, it has to know the value of parameter X, and
therefore the process data must deliver a reference to
parameter X.
Field PCD normalisation
The field PCD normalization must express, in any case, the
value that represents the 100%, that is, the normalization
delivered back must be the set bit 15 and a value of 0xe
(14, 214 =0x4000), and the result must be 0x800e.
Complete description
Returns the complete parameter description with the fields
1 to 12 in order. Length=46 byte.
5.2.18
Attribute Text (30H)
55
Table 5.11 Additional Characteristics of a Parameter
Number of array elements
Contains the number of array elements, if the parameter is
an array; the string length, if the parameter value is a
string; or 0 if the parameter is neither.
Standardisation factor
Conversion factor for scaling a given parameter value to
standard SI units.
For example, if the given value is in mV, the standardi-
For some frequency converter parameters a descriptive
text is available, which can be read using this attribute.
The availability of a text description for a parameter is
indicated by a bit set in the identifier (ID) parameter
description element, which can be read out by the
description attribute (20H) sub-index=1. If bit 10 is set, a
descriptive text exists for each value of the parameter.
As an example, 0-01 Language has settings from 0 to 5. For
each of these values a specific text exists: 0=English,
2=Deutsch, and so on.
sation factor is 1000, which converts the given value to V.
The standardisation factor is in float format.
5.2.19
Format
Variable attribute
Consists of 2 bytes. The first byte contains the variable
index, which defines the physical unit of the parameter (for
Specifies the format type for each parameter (word, byte,
and so on), see Table 5.12.
example Ampere, Volt).
The second byte is the conversion index, which is a scaling
factor for the parameter.All parameters accessible by
PROFIBUS are organised and transmitted as real numbers.
The conversion index defines a factor for conversion the
actual value to a standard physical unit. A conversion
9Visible string
10Octet string (byte string)
33N2 (standardised value)
35V2 (bit sequence)
44Error
54Time difference without date indication
Programming Guide
Error
MeaningAdditional
code
0x16Wrong parameter address (unknown or
unsupported value for attribute, element,
parameter number or sub-index or illegal
combination)
0x17Illegal format (for writing)0
0x18Value amount not consistent0
0x65Wrong axis: action not possible with this axis0x66Unknown service request0x67This service is not possible with multi parameter
access
0x68Parameter value can not be read from bus.-
Table 5.13 Error Codes for DP-V1 Parameter Requests
Info
0
-
55
Table 5.12 Supported Data Types
5.2.21
Value
5.3 PCV Parameter Access
The PROFINET cyclical data exchange performs parameter
access via the PCV channel. The PCV channel forms part of
The value field contains the parameter value of the
the PPOs described in chapter 4 Control.
request. When the response is negative, the field contains
a corresponding error code. If the values consist of an odd
number of bytes, a zero byte is appended to maintain the
word structure of the telegrams.
For a positive partial response, the parameter value field
Use the PCV channel to read and write parameter values,
and read status for descriptive attributes of each
parameter.
PCA Handling
5.3.1
contains the following attributes:
Format=Data type or byte, word, double word
Number of values=Actual number of values
Value=Parameter value
The PCA part of PPO types 1, 2 and 5 performs several
tasks. Using PCA, the master controls and supervises
parameters, and requests a response from the follower.
Then the follower responds to a request from the master.
For a negative partial response, the parameter value field
contains the following:
Format=Error (44H)
Number of values=1
Value=Error value=Error number
Requests and responses is a handshake procedure and
cannot be batched. Therefore, when the master sends out
a read/write request, it must wait for the response before
it sends a new request. The request or response data value
is limited to maximum 4 bytes (see RC characteristics in
Table 5.14), which implies that text strings are not
5.2.22
Error Codes for Drive Profile V3.0
transferable. For further information, see
chapter 7 Application Examples.
When the parameter request is invalid, the frequency
PCA - Parameter Characteristics
converter returns a corresponding error code. Table 5.13
5.3.2
lists the full range of error codes.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
MeaningAdditional
Error
code
0x00Unknown parameter0
0x01Parameter is read-only.sub-index
0x02Value out of range due to maximum/minimum
value.
0x03Wrong sub-indexsub-index
0x04Parameter is no array.0
0x05Wrong data type (wrong data length)0
0x06This parameter may not be set, only reset.sub-index
0x07Descriptive element is read-only.sub-index
0x09No description available (only value).0
0x0bProcess control not possible.0
0x0fNo text array available (only value).0
0x11Not possible in current state.0
0x14Value out of range due to drive state/configu-
ration.
0x15Reply too long (more than 240 bytes).0
size parameter values in bytes 7 and 8,
while long word size values require
bytes 5–8 (32 bits).
IND: When the response/request
-
contains array elements, the IND carries
the array sub-index. When parameter
descriptions are involved, the IND holds
the record sub-index of the parameter
description.
5.3.4 RC Content
Request
The content of the RC portion of the PCA word for a
request is listed in Table 5.15.
ResponseFunction
0No response
1Transfer parameter value (word)
2Transfer parameter value (long word)
3Transfer description element
4Transfer parameter value (array word)
5Transfer parameter value (array long word)
6Transfer number of array elements
7Request rejected (including fault number, see
Table 5.17)
8Not serviceable by PCV interface
9Not used
10Not used
11Not used
12Not used
13-15Not used
55
RequestFunction
0No request
1Request parameter value
2Change parameter value (word)
3Change parameter value (long word)
4Request description element
5Change description element
6Request parameter value (array)
7Change parameter value (array word)
8Change parameter value (array long word)
9Request number of array elements
10-15Not used
Table 5.15 Request
Response
When the follower rejects a request from the master, the
RC word in the PPO-read indicates the rejection by
assuming the value 7. Bytes 7 and 8 in the PVA element
carry the fault number.
The content of the RC portion of the PCA word for a
response is listed in Table 5.16.
Table 5.16 Response
Fault
Interpretation
numb
er
0Illegal PNU
1Parameter value cannot be changed.
2Upper or lower limit exceeded.
3Subindex corrupted.
4No array
5Data type false
6Cannot be set by user (reset only).
7Description element cannot be changed.
8IR required PPO-write not available.
9Description data not available.
10Access group
11No parameter write access
12Key word missing.
13Text in cyclical transmission not readable.
14Name in cyclical transmission not readable.
15Text array not available
16PPO-write missing
17Request temporarily rejected
18Other fault
19Data in cyclical transmission not readable.
130There is no bus access to the parameter called.
131Data change is not possible because factory set-up has
time to 10 s, in3-41 Ramp 1 Ramp Up Time.
How to command a start and speed reference of
•
50%.
Frequency converter parameter settings:
8-50 Coasting Select: Bus
Parameter 8-10 Control Word Profile: PROFIdrive profile
5.3.5.1 PCV
55
PCA parameter characteristics
PCA part (byte 1-2).
The RC part tells what the PCV part must be used for. The
functions available are listed in chapter 5.3.1 PCA Handling.
When a parameter is changed, select value 2 or 3. In this
example, 3 is selected, because 3-41 Ramp 1 Ramp Up Time
covers a long word (32 bits).
3-41 Ramp 1 Ramp Up Time=155 hex: In this example, byte
1 and 2 are set to 3155. See the values for bytes 1 and 2
in Table 5.18.
IND (bytes 3-4)
Used when reading/changing parameters with sub-index,
for example parameter 9-15 PCD Write Configuration. In the
example bytes 3 and 4 are set to 00 hex. See the values
for bytes 3 and 4 in Table 5.18.
PVA (bytes 5-8)
The data value of 3-41 Ramp 1 Ramp Up Time must be
changed to 10.00 s. The value transmitted must be 1000,
because the conversion index for 3-41 Ramp 1 Ramp UpTime is 2. This means that the value received by the
frequency converter is divided by 100, such that the
frequency converter perceives 1000 as 10.00. Bytes
5-8=1000=03E8 hex. See chapter 5.4 PROFIBUS DP
Parameter and Data Type. See the values for bytes 5-8 in
Table 5.18.
5.3.5.2
PCD
Programming Guide
NOTICE
* For restart after power up:
Set bits 1 and 2 of the CTW to 1.
•
Toggle bit 0 from 0 to 1.
•
5.3.5.3 MRV
MRV is the speed reference, with data format Standardisedvalue. 0 hex=0% and 4000 hex=100%.
In the example, 2000 hex is used, corresponding to 50% of
maximum frequency in 3-03 Maximum Reference. See the
values for bytes 11 and 12 in Table 5.18.
The whole PPO therefore has the following values in hex:
ByteValue
PCA131
PCA255
IND300
PCV
PCD
Table 5.18 Request Example: PPO Values in Hex
The process data within the PCD part acts immediately
upon the frequency converter, and can be updated from
the master as quickly as possible. The PCV part is a
"handshake" procedure, which means that the frequency
converter has to acknowledge the command, before a new
one can be written.
Table 5.18 shows a positive response to the request
example from Table 5.18.
Control word (CTW) according to PROFIdrive profile:
Control words consist of 16 bits. The meaning of each bit
is explained in chapter 4.4.1 Control Word according to
PROFIdrive Profile (CTW) and chapter 4.4.2 Status Word
according to PROFIdrive Profile (STW). The following bit
pattern sets all necessary start commands:
0000 0100 0111 1111=047F hex.*
0000 0100 0111 1110=047E hex.*
0000 0100 0111 1111=047F hex. These are the values for
bytes 9 and 10 in Table 5.18.
Quick stop: 0000 0100 0110 1111=046F hex.
Stop: 0000 0100 0011 1111=043F hex.
The PCD part responds according to the state and parameterization of the frequency converter.
PCV part response:
PCA: As the request telegram, but here the RC
•
part is taken from Table 5.16. In this example, RC
is 2 Hex, which is a confirmation that a parameter
value of the type long word (32 bit) has been
transferred. IND is not used in this example.
PVA: 03E8 hex in the PVA part tells that the value
•
of 3-41 Ramp 1 Ramp Up Time is 1000, which
corresponds to 10.00.
STW: 0F07 hex means that the motor is running
•
and there are no warnings or faults.
MAV: 2000 hex indicates that the output
•
frequency is 50% of the maximum reference.
Table 5.20 shows a negative response to the request
example from Table 5.18.
RC is 7 hex, which means that the request has been
rejected, and the fault number can be found in the PVA
part.
In this case, the fault number is 2, which means that the
upper or lower limit of the parameter is exceeded, see
Table 5.17.
5.4
PROFIBUS DP Parameter and Data Type
5.4.1 Parameter Description
PROFIBUS DP has a number of description attributes. Read/
write on parameter description is performed in the PCV
part using the RC commands 4 and 5, and the sub-index
of the desired description element.
5.4.2
Size Attribute
Find the size index and the conversion index for each
parameter from the parameter list in the respective
operating instructions. See also size and conversion indices
in Table 5.21.
9-Visible string
10-Byte string
33N2Standardised value (16 bit)
55
35V2Bit sequence
54-Time difference without date
indication
Table 5.22 Data Types Supported
Standardised Value
5.4.4
BitByte 1Byte 2
8
7
6
5
4
3
2
1
Table 5.25 Notation is Binary
157
146
135
124
113
102
91
80
The frequency reference value transmits to the frequency
converter in the form of a 16-bit word. The value transmits
in integers (0-32767). The value 16384 (4000 hex)
corresponds to 100%. Negative numbers are formed with
the aid of the 2s complement.
0%=0 (0h), 100%=214 (4000 h)
Data type
Range-200%...+200%
Resolution
Length2 bytes
Table 5.23 N2 Data Type
N2
-14
2
=0.0061%
MSB is the first bit after the sign bit in the first byte.
Sign bit=0=positive number
Sign bit=1=negative number
BitByte 1Byte 2
8
7
6
5
4
3
2
1
Table 5.24 Notation is 2s Complement
SIGN
14
2
13
2
12
2
11
2
10
2
9
2
22
2
2
2
24
2
2
2
7
6
5
3
2
1
0
Bit sequence
16 boolean values for control and presentation of user
functions.
The setting in this parameter overrides the
settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select.
[0] Digital and
ctrl.word
[1] Digital onlyControl by using digital inputs only.
[2] Controlword
only
Control by using both digital input and
control word.
Control by using control word only.
8-02 Control Word Source
Option:Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the source of the control word: 1 of 2
serial interfaces or 4 installed options. During
initial power-up, the frequency converter
automatically sets this parameter to [3] OptionA, if it detects a valid fieldbus option installed
in slot A. When the option is removed, the
frequency converter detects a configuration
change, sets parameter 8-02 Control WordSource back to default setting RS-485, and
trips. If an option is installed after initial
power-up, the setting of
parameter 8-02 Control Word Source does not
change, but the frequency converter trips and
displays: Alarm 67 Option Changed.
When retrofitting a bus option into a
frequency converter that did not have a bus
option installed to begin with, take an active
decision to move the control to bus-based.
This is required for safety reasons to avoid an
accidental change.
None
[0]
[1]FC RS485
[2]FC USB
[3]Option A
[4]Option B
[5]Option C0
[6]Option C1
[30] External Can
8-03 Control Word Timeout Time
Range:Function:
1 s* [ 0.1 -
18000 s]
Enter the maximum time expected to pass
between the reception of two consecutive
telegrams. If this time is exceeded, it indicates
that the telegram communication has stopped.
The function selected in parameter 8-04 ControlWord Timeout Functionis then carried out. A
valid control word triggers the time-out counter.
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
specified in parameter 8-03 Control Word Timeout Time.
Option:Function:
[0]OffResumes control via serial bus (fieldbus or
standard) using the most recent control
word.
[1]Freeze output Freezes output frequency until communi-
cation resumes.
[2]StopStops with auto restart when communi-
cation resumes.
[3]JoggingRuns the motor at jog frequency until
communication resumes.
[4]Max. speedRuns the motor at maximum frequency until
communication resumes.
[5]Stop and trip Stops the motor, then resets the frequency
converter to restart: Via the fieldbus, via
[Reset], or via a digital input.
[7]Select setup 1 Changes the set-up upon reestablishment of
communication following a control word
timeout. If communication resumes after a
timeout, parameter 8-05 End-of-TimeoutFunction defines whether to resume the setup used before the timeout, or to retain the
set-up endorsed by the timeout function.
[8]Select setup 2
[9]Select setup 3
[10] Select setup 4
[26] Trip
See [7] Select set-up 1
See [7] Select set-up 1
See [7] Select set-up 1
NOTICE
To change the set-up after a timeout, configure as
follows:
Set 0-10 Active Set-up to [9] Multi set-up and select the
relevant link in 0-12 This Set-up Linked to.
Select the action after receiving a valid control
word following a timeout. This parameter is
active only when 8-04 Control Timeout Function
is set to [7] Set-up 1, [8] Set-up 2, [9] Set-up 3 or
[10] Set-up 4.
[0]Hold set-
up
[1] * Resume
set-up
66
8-06 Reset Control Word Timeout
This parameter is active only when [0] Hold set-up has been
selected in parameter 8-05 End-of-Timeout Function.
Retains the set-up selected in 8-04 Control
Timeout Function and displays a warning, until
8-06 Reset Control Timeout toggles. Then the
frequency converter resumes its original set-up.
Resumes the set-up active before the timeout.
Option:Function:
[0] * Do not reset
[1]Do resetReturns the frequency converter to the
Retains the set-up specified in
parameter 8-04 Control Word Timeout Function,
following a control word timeout.
original set-up following a control word
timeout. The frequency converter performs
the reset and then immediately reverts to the
[0] Do not reset setting.
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A are visible in the LCP display.
For guidelines in selection of [0] Frequency converter profile and
[1] PROFIdrive profile, refer to the design guide of the related
product.
For additional guidelines in the selection of [1] PROFIdrive profile,
[5] ODVA and [7] CANopen DSP 402, see the installation guide for
the installed fieldbus.
Option:Function:
[8]MCO
8-50 Coasting Select
Option:Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0]Digital
input
[1]BusActivates start command via the serial
[2]Logic
AND
[3] * Logic ORActivates start command via the fieldbus/serial
Activates start command via a digital input.
communication port or fieldbus option.
Activates start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
communication port OR via one of the digital
inputs.
8-07 Diagnosis Trigger
Option:Function:
Enables and controls the frequency converter
diagnosis function.
[0] * DisableExtended diagnosis data are not sent even if
they appear in the frequency converter.
[1]Trigger on
alarms
[2]Trigger
alarm/warn.
Extended diagnosis data are sent when one
or more alarms appear.
Extended diagnosis data are sent if one or
more alarms/warnings appear.
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the bus.
Option:Function:
[0]Digital input
[1]Bus
[2]Logic AND
[3] *Logic OR
8-52 DC Brake Select
Option:Function:
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A are visible in the LCP display.
For guidelines in selection of [0] Frequency converter profile and
[1] PROFIdrive profile, refer to the design guide of the related
product.
For additional guidelines in the selection of [1] PROFIdrive profile,
[5] ODVA and [7] CANopen DSP 402, see the installation guide for
the installed fieldbus.
[3] Logic ORActivates start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-53 Start Select
Option:Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
[0]Digital
input
[1]BusActivates a start command via the serial
[2]Logic
AND
[3] * Logic OR Activates a start command via the fieldbus/serial
Activates a start command via a digital input.
communication port or fieldbus option.
Activates a start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
communication port OR via one of the digital
inputs.
8-54 Reversing Select
Option:Function:
[0]Digital
input
[1]BusActivates the reverse command via the serial
[2]Logic
AND
[3] * Logic ORActivates the reverse command via the
Select control of the frequency converter
reverse function via the terminals (digital input)
and/or via the fieldbus.
communication port or fieldbus option.
Activates the reverse command via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
fieldbus/serial communication port OR via one
of the digital inputs.
8-55 Set-up Select
Option:Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0]Digital
input
[1]BusActivates the set-up selection via the serial
[2]Logic
AND
[3] * Logic ORActivate the set-up selection via the fieldbus/
Activates the set-up selection via a digital input.
communication port or fieldbus option.
Activates the set-up selection via the fieldbus/
serial communication port, AND additionally via
one of the digital inputs.
serial communication port OR via one of the
digital inputs.
8-56 Preset Reference Select
Option:Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
fieldbus.
[0]Digital
input
[1]BusActivates preset reference selection via the
[2]Logic
AND
[3] * Logic ORActivates the preset reference selection via the
Activates preset reference selection via a digital
input.
serial communication port or fieldbus option.
Activates preset reference selection via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
fieldbus/serial communication port OR via one
of the digital inputs.
8-90 Bus Jog 1 Speed
Range:Function:
100 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
8-91 Bus Jog 2 Speed
Range:Function:
200 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
6.2 9-** and 16-** PROFIBUS Parameters
9-15 PCD Write Configuration
Array [10]
Option:Function:
Select the parameters
to be assigned to PCD
3 to 10 of the
telegrams. The number
of available PCDs
depends on the
telegram type. The
values in PCD 3 to 10
are then written to the
selected parameters as
data values. Alternatively, specify a
standard PROFIBUS
telegram in
9-22 Telegram
Selection.
[0]None
[302]Minimum Reference
[303]Maximum Reference
[312]Catch up/slow Down Value
[341]Ramp 1 Ramp Up Time
[342]Ramp 1 Ramp Down Time
[351]Ramp 2 Ramp Up Time
[352]Ramp 2 Ramp Down Time
[380]Jog Ramp Time
[381]Quick Stop Ramp Time
[411]Motor Speed Low Limit [RPM]
[412]Motor Speed Low Limit [Hz]
[413]Motor Speed High Limit [RPM]
[414]Motor Speed High Limit [Hz]
[416]Torque Limit Motor Mode
[417]Torque Limit Generator Mode
66
[553]Term. 29 High Ref./Feedb. Value
[558]Term. 33 High Ref./Feedb. Value
[590]Digital & Relay Bus Control
[593]Pulse Out #27 Bus Control
[595]Pulse Out #29 Bus Control
[597]Pulse Out #X30/6 Bus Control
[615]Terminal 53 High Ref./Feedb.
Value
[625]Terminal 54 High Ref./Feedb.
Value
[653]Term 42 Output Bus Ctrl
[663]Terminal X30/8 Bus Control
[673]Terminal X45/1 Bus Control
[683]Terminal X45/3 Bus Control
[748]PCD Feed Forward
[890]Bus Jog 1 Speed
[891]Bus Jog 2 Speed
[1680] Fieldbus CTW 1
[1682] Fieldbus REF 1
[1685] FC Port CTW 1
[1686] FC Port REF 1
9-16 PCD Read Configuration
[10] Array
Option:Function:
Select the parameters
to be assigned to
PCD 3 to 10 of the
telegrams. The
number of available
PCDs depends on the
telegram type. PCDs 3
to 10 contain the
actual data values of
the selected
parameters. For
standard PROFIBUS
telegrams, see
9-22 Telegram
Selection.
9-16 PCD Read Configuration
[10] Array
Option:Function:
[0]None
[15]Readout: actual setup
[1472] Legacy Alarm Word
[1473] Legacy Warning Word
[1474] Leg. Ext. Status Word
[1500] Operating hours
[1501] Running Hours
[1502] kWh Counter
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1605] Main Actual Value [%]
[1609] Custom Readout
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor current
[1615] Frequency [%]
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1619] KTY sensor temperature
[1620] Motor Angle
[1621] Torque [%] High Res.
[1622] Torque [%]
[1623] Motor Shaft Power [kW]
[1624] Calibrated Stator Resistance
[1625] Torque [Nm] High
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1638] SL Controller State
[1639] Control Card Temp.
[1645] Motor Phase U Current
[1646] Motor Phase V Current
[1647] Motor Phase W Current
[1648] Speed Ref. After Ramp [RPM]
[1650] External Reference
[1651] Pulse Reference
[1652] Feedback[Unit]
[1653] Digi Pot Reference
[1657] Feedback [RPM]
[1660] Digital Input
[1661] Terminal 53 Switch Setting
[1662] Analog Input 53
[1663] Terminal 54 Switch Setting
[1664] Analog Input 54
[1665] Analog Output 42 [mA]
[1666] Digital Output [bin]
[1667] Freq. Input #29 [Hz]
[1668] Freq. Input #33 [Hz]
[1669] Pulse Output #27 [Hz]
[1670] Pulse Output #29 [Hz]
[1671] Relay Output [bin]
[1672] Counter A
[1673] Counter B
[1674] Prec. Stop Counter
[1675] Analog In X30/11
[1676] Analog In X30/12
[1677] Analog Out X30/8 [mA]
[1678] Analog Out X45/1 [mA]
[1679] Analog Out X45/3 [mA]
[1684] Comm. Option STW
[1687] Bus Readout Alarm/Warning
[1689] Configurable Alarm/Warning Word
[1690] Alarm Word
[1691] Alarm Word 2
[1692] Warning Word
[1693] Warning Word 2
[1694] Ext. Status Word
[1836] Analog Input X48/2 [mA]
[1837] Temp. Input X48/4
[1838] Temp. Input X48/7
[1839] Temp. Input X48/10
[1860] Digital Input 2
9-18 Node Address
Range:Function:
126* [ 0 -
126 ]
Enter the station address in this parameter or
alternatively in the hardware switch. In order to
adjust the station address in parameter 9-18 NodeAddress, the hardware switch must be set to 126
or 127 (that is, all switches set to ‘on’). Otherwise
this parameter displays the actual setting of the
switch.
9-22 Telegram Selection
Option:Function:
Select a standard PROFIBUS
telegram configuration for the
frequency converter, as an
alternative to using the freely
configurable telegrams in 9-15 PCD
Write Configuration and 9-16 PCD
Read Configuration.
This parameter
contains a list of
signals available for
selection in
parameter 9-15 PCD
Write Configuration
and
parameter 9-16 PCD
Read Configuration.
[0] *None
[15]Readout: actual setup
[302]Minimum Reference
[303]Maximum Reference
[312]Catch up/slow Down Value
[341]Ramp 1 Ramp Up Time
[342]Ramp 1 Ramp Down Time
[351]Ramp 2 Ramp Up Time
[352]Ramp 2 Ramp Down Time
[380]Jog Ramp Time
[381]Quick Stop Ramp Time
[411]Motor Speed Low Limit [RPM]
[412]Motor Speed Low Limit [Hz]
[413]Motor Speed High Limit [RPM]
[414]Motor Speed High Limit [Hz]
[416]Torque Limit Motor Mode
[417]Torque Limit Generator Mode
[553]Term. 29 High Ref./Feedb. Value
[558]Term. 33 High Ref./Feedb. Value
[590]Digital & Relay Bus Control
[593]Pulse Out #27 Bus Control
[595]Pulse Out #29 Bus Control
[597]Pulse Out #X30/6 Bus Control
[615]Terminal 53 High Ref./Feedb. Value
[625]Terminal 54 High Ref./Feedb. Value
[653]Term 42 Output Bus Ctrl
[663]Terminal X30/8 Bus Control
[673]Terminal X45/1 Bus Control
[683]Terminal X45/3 Bus Control
[748]PCD Feed Forward
[890]Bus Jog 1 Speed
[891]Bus Jog 2 Speed
[1472] Legacy Alarm Word
[1473] Legacy Warning Word
[1474] Leg. Ext. Status Word
[1500] Operating hours
[1501] Running Hours
[1502] kWh Counter
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
66
[1605] Main Actual Value [%]
[1609] Custom Readout
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor current
[1615] Frequency [%]
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1619] KTY sensor temperature
[1620] Motor Angle
[1621] Torque [%] High Res.
[1622] Torque [%]
[1623] Motor Shaft Power [kW]
[1624] Calibrated Stator Resistance
[1625] Torque [Nm] High
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1638] SL Controller State
[1639] Control Card Temp.
[1645] Motor Phase U Current
[1646] Motor Phase V Current
[1647] Motor Phase W Current
[1648] Speed Ref. After Ramp [RPM]
[1650] External Reference
[1651] Pulse Reference
[1652] Feedback[Unit]
[1653] Digi Pot Reference
[1657] Feedback [RPM]
[1660] Digital Input
[1661] Terminal 53 Switch Setting
[1662] Analog Input 53
[1663] Terminal 54 Switch Setting
[1664] Analog Input 54
[1665] Analog Output 42 [mA]
9-23 Parameters for Signals
Array [1000]
Read only
Option:Function:
[1666] Digital Output [bin]
[1667] Freq. Input #29 [Hz]
[1668] Freq. Input #33 [Hz]
[1669] Pulse Output #27 [Hz]
[1670] Pulse Output #29 [Hz]
[1671] Relay Output [bin]
[1672] Counter A
[1673] Counter B
[1674] Prec. Stop Counter
[1675] Analog In X30/11
[1676] Analog In X30/12
[1677] Analog Out X30/8 [mA]
[1678] Analog Out X45/1 [mA]
[1679] Analog Out X45/3 [mA]
[1680] Fieldbus CTW 1
[1682] Fieldbus REF 1
[1684] Comm. Option STW
[1685] FC Port CTW 1
[1686] FC Port REF 1
[1687] Bus Readout Alarm/Warning
[1689] Configurable Alarm/Warning Word
[1690] Alarm Word
[1691] Alarm Word 2
[1692] Warning Word
[1693] Warning Word 2
[1694] Ext. Status Word
[1836] Analog Input X48/2 [mA]
[1837] Temp. Input X48/4
[1838] Temp. Input X48/7
[1839] Temp. Input X48/10
[1860] Digital Input 2
[3310] Sync Factor Master
[3311] Sync Factor Slave
[3401] PCD 1 Write to MCO
[3402] PCD 2 Write to MCO
[3403] PCD 3 Write to MCO
[3404] PCD 4 Write to MCO
[3405] PCD 5 Write to MCO
[3406] PCD 6 Write to MCO
[3407] PCD 7 Write to MCO
[3408] PCD 8 Write to MCO
[3409] PCD 9 Write to MCO
[3410] PCD 10 Write to MCO
[3421] PCD 1 Read from MCO
[3422] PCD 2 Read from MCO
[3423] PCD 3 Read from MCO
[3424] PCD 4 Read from MCO
[3425] PCD 5 Read from MCO
[3426] PCD 6 Read from MCO
[3427] PCD 7 Read from MCO
[3428] PCD 8 Read from MCO
[3429] PCD 9 Read from MCO
[3430] PCD 10 Read from MCO
[3440] Digital Inputs
[3441] Digital Outputs
[3450] Actual Position
[3451] Commanded Position
[3452] Actual Master Position
[3453] Slave Index Position
[3454] Master Index Position
[3455] Curve Position
[3456] Track Error
[3457] Synchronizing Error
[3458] Actual Velocity
[3459] Actual Master Velocity
[3460] Synchronizing Status
[3461] Axis Status
[3462] Program Status
[3464] MCO 302 Status
[3465] MCO 302 Control
[3470] MCO Alarm Word 1
[3471] MCO Alarm Word 2
[4280] Safe Option Status
[4285] Active Safe Func.
9-27 Parameter Edit
Option:Function:
Parameters can be edited via PROFIBUS, the
standard RS-485 interface, or the LCP.
[0]Disabled Disables editing via PROFIBUS.
[1] * Enabled Enables editing via PROFIBUS.
9-28 Process Control
Option:Function:
Process control (setting of control word, speed
reference, and process data) is possible via either
PROFIBUS or standard fieldbus but not both
simultaneously. Local control is always possible
via the LCP. Control via process control is possible
via either terminals or fieldbus depending on the
settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select.
[0]DisableDisables process control via PROFIBUS, and
enables process control via standard fieldbus or
PROFIBUS master class 2.
[1]*Enable
cyclic
master
Enables process control via PROFIBUS master class
1, and disables process control via standard
fieldbus or PROFIBUS master class 2.
9-53 Profibus Warning Word
Range:Function:
0* [0 - 65535 ] This parameter displays PROFIBUS communi-
cation warnings. Refer to the PROFIBUSOperating Instructions for further information.
Read only
BitMeaning
0Connection with DP-master is not OK.
1Not used
2FDL (fieldbus data link layer) is not OK.
3Clear data command received.
4Actual value is not updated.
5Baudrate search
6PROFIBUS ASIC is not transmitting.
7Initialisation of PROFIBUS is not OK.
8Frequency converter is tripped.
9Internal CAN error
10Wrong configuration data from PLC
11Wrong ID sent by PLC.
12Internal error occured
13Not configured
14Timeout active
15Warning 34 active
Table 6.1 PROFIBUS Warning Word
9-63 Actual Baud Rate
Option:Function:
This parameter displays the actual
PROFIBUS baud rate. The PROFIBUS
master automatically sets the baud
rate.
0* [0 - 0 ] This parameter contains the profile identification.
Byte 1 contains the profile number and byte 2 the
version number of the profile.
NOTICE
This parameter is not visible via LCP.
9-70 Programming Set-up
Option:Function:
Select the set-up to be edited.
[0]Factory setup Uses default data. This option can be used
66
[1]Set-up 1Edits Set-up 1.
[2]Set-up 2Edits Set-up 2.
[3]Set-up 3Edits Set-up 3.
[4]Set-up 4Edits Set-up 4.
[9] * Active Set-up Follows the active set-up selected in
as a data source to return the other set-ups
to a known state.
0-10 Active Set-up.
9-72 ProfibusDriveReset
Option:Function:
When reset, the frequency converter
disappears from the fieldbus, which may cause
a communication error from the master.
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range:Function:
0* [0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
PROFIBUS.
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
Range:Function:
0* [0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
PROFIBUS.
This parameter is unique for LCP and fieldbus. See
0-11 Programming Set-up.
9-71 Profibus Save Data Values
Option:Function:
Parameter values changed via PROFIBUS are not
automatically stored in non-volatile memory.
Use this parameter to activate a function that
stores parameter values in the EEPROM nonvolatile memory, so changed parameter values
are retained at power-down.
[0] * OffDeactivates the non-volatile storage function.
[1]Store all
setups
[2]Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
[0] Off when all parameter values have been
stored.
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
[0] Off when all parameter values have been
stored.
9-72 ProfibusDriveReset
Option:Function:
[0] * No action
[1]Power-on
reset
[3]Comm
option
reset
Resets frequency converter upon power-up, as
for power-cycle.
Resets the PROFIBUS option only, useful after
changing certain settings in parameter group
9-**, for example, parameter 9-18 Node Address.
9-82 Defined Parameters (3)
Array [116]
No LCP access
Read only
Range:Function:
0* [0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
PROFIBUS.
9-83 Defined Parameters (4)
Array [116]
No LCP access
Read only
Range:Function:
0* [0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
PROFIBUS.
9-90 Changed Parameters (1)
Array [116]
No LCP access
Read only
Range:Function:
0* [0 - 9999 ] This parameter displays a list of all the
frequency converter parameters deviating from
default setting.
ParameterDefault valueRangeConversion index Data type
8-01 Control Site
Parameter 8-02 Control Word Source
Parameter 8-03 Control Word Timeout Time
Parameter 8-04 Control Word Timeout Function
8-05 End-of-Timeout Function
Parameter 8-06 Reset Control Word Timeout
Parameter 8-07 Diagnosis Trigger
Parameter 8-10 Control Word Profile
8-50 Coasting Select
Parameter 8-51 Quick Stop Select
8-52 DC Brake Select
66
8-53 Start Select
Parameter 8-54 Reversing Select
8-55 Set-up Select
8-56 Preset Reference Select
8-90 Bus Jog 1 Speed
8-91 Bus Jog 2 Speed
Parameter 9-15 PCD Write Configuration
Parameter 9-16 PCD Read Configuration
9-18 Node Address
9-22 Telegram Selection
Parameter 9-23 Parameters for Signals
9-27 Parameter Edit
9-28 Process Control
9-44 Fault Message Counter
9-45 Fault Code
9-47 Fault Number
9-52 Fault Situation Counter
9-53 Profibus Warning Word
9-63 Actual Baud Rate
Parameter 9-64 Device Identification
9-65 Profile Number
9-70 Edit Set-up
9-71 Profibus Save Data Values
9-72 ProfibusDriveReset
9-80 Defined Parameters (1)
9-81 Defined Parameters (2)
9-82 Defined Parameters (3)
9-83 Defined Parameters (4)
9-90 Changed Parameters (1)
9-91 Changed Parameters (2)
9-92 Changed Parameters (3)
9-93 Changed Parameters (4)
16-84 Comm. Option STW
16-90 Alarm Word
16-92 Warning Word
[0] Dig. & ctrl. word[0-2]-Uint8
[0] FC RS485[0-4]-Uint8
10.1-18000-1Uint32
[0] Off[0-10]-Uint8
[0] Hold set-up[0-1]-Uint8
[0] Do not reset[0-1]-Uint8
[0] Disable[0-3]-Uint8
[0] FC profile[0-x]-Uint8
*[3] Logic OR[0-3]-Uint8
*[3] Logic OR[0-3]-Uint8
*[3] Logic OR[0-3]-Uint8
*[3] Logic OR[0-3]-Uint8
*[3] Logic OR[0-3]-Uint8
*[3] Logic OR[0-3]-Uint8
*[3] Logic OR[0-3]-Uint8
100 rpm0-par. 4-1367Uint16
200 rpm0-par. 4-1367Uint16
This example shows how to work with PPO type 6, which consists of control word/status Word and reference/main actual
value. The PPO also has 2 additional words, which can be programmed to monitor process signals:
The application requires monitoring of the motor torque
and digital input, so PCD 3 is set up to read the current
motor torque. PCD 4 is set up to monitor the state of an
external sensor via the process signal digital input. The
sensor is connected to digital input 18.
An external device is also controlled via control word bit
11 and the built-in relay of the frequency converter.
Reversing is permitted only when the reversing bit 15 in
the control word and the digital input 19 are set to high.
For safety reasons the frequency converter stops the motor
if:
4-10 Motor Speed Direction[2] Both directions
5-10 Terminal 18 Digital Input[0] No operation
5-11 Terminal 19 Digital Input[10] Reversing
5-40 Function Relay[36/37] Control word bit 11/12
parameter 8-03 Control Word Timeout Time
parameter 8-04 Control Word Timeout Function[2] Stop
parameter 8-10 Control Word Profile[0] FC Profile
8-50 Coasting Select[1] Bus
parameter 8-51 Quick Stop Select[1] Bus
8-52 DC Brake Select[1] Bus
8-53 Start Select[1] Bus
parameter 8-54 Reversing Select[2] Logic AND
8-55 Set-up Select[1] Bus
8-56 Preset Reference Select[1] Bus
77
parameter 9-16 PCD Read Configuration[2] Sub index 16-16 Torque [Nm]
9-18 Node Address
1 s
[3] Sub index 16-60 Digital Input
Set the address
Table 7.2 Parameter Settings
7.2
Example 2: Control Word Telegram using PPO Type
This example shows how the control word telegram relates to the PLC and the frequency converter, using FC control profile.
The control word telegram is sent from the PLC to the frequency converter. PPO Type 3 is used in the example to
demonstrate the full range of modules. All the values shown are arbitrary, and are provided for demonstration purposes
only.
Table 7.3 indicates the bits contained within the control word, and how they are presented as process data in PPO type 3
for this example.
047C2000
PQW256258260262264266268270272274
master slaveCTWMRV
Bit no.151413121110987654321 0000001000111110 0
PCAINDPVACTWMRVPCDPCDPCDPCD
047C
PCVPCD
123456
Table 7.3 Example: Control Word Telegram using PPO Type
Table 7.4 indicates the bit functions and corresponding bit values which are active for this example.
15No functionReversing0
Function active
Function inactive
Table 7.4 Active Bit Functions for Control Word Telegram using PPO Type
7.3 Example 3: Status Word Telegram using PPO Type
C
7
4
0
77
This example shows how the control word telegram relates to the PLC and the frequency converter, using FC control profile.
The control word telegram is sent from the PLC to the frequency converter. PPO type 3 is used in the example to
demonstrate the full range of modules. All the values shown are arbitrary, and are provided for demonstration purposes
only.
Table 7.5 indicates the bits contained within the status word, and how they are presented as process data in PPO type 3 for
this example.
0F072000
PIW:256258260262264266268270272274
master slaveSTWMAV
Bit no.:151413121110987654321 0000001000111110 0
Table 7.5 Example: Status Word Telegram using PPO Type
PCAINDPVACTWMRVPCDPCDPCDPCD
047C
PCVPCD
123456
Table 7.6 indicates the bit functions, and the corresponding bit values which are active for this example.
This network reads the motor torque from the frequency
converter. A new reference is sent to the frequency
converter because the motor torque (86.0%) is higher than
the compared value.
Illustration 7.4 Network Reads the Motor Torque from the
Frequency Converter
This network reads the status on the digital inputs from
the frequency converter. If digital input 18 is On, it stops
the frequency converter.
77
Illustration 7.5 Network Reads the Status on the Digital Inputs
from the Frequency Converter
This network reverses the motor when digital input 19 is
ON, because parameter 8-54 Reversing Select is
programmed to Logic AND.
Illustration 7.6 Network Reverses the Motor When Digital
Input 19 is ON
PROFIBUS-DP provides a flexible way of performing
diagnosis of slave units, based on diagnosis messages.
During normal cyclical data exchange:
1.The slave sets a diagnosis bit, which requests the
master to send a diagnosis message during the
next scan cycle, instead of the normal data
exchange.
2.The slave answers the master with a diagnosis
message consisting of standard diagnosis
information, 6 bytes, and possibly extended,
vendor specific, diagnosis information. The
standard diagnosis messages cover a limited
range of general diagnosis possibilities, whereas
the extended diagnosis function offers detailed
88
See chapter 8.3 Warnings and Alarms for the extended
diagnosis messages for the frequency converter.
A master or a network analysing tool is able to translate
these diagnosis words into real text messages using the
GSD-file.
messaging specific to the frequency converter.
NOTICE
DP V1 diagnosis is supported for PROFIBUS SW version
2.X and later versions. The default setting of the
PROFIBUS option is DP V1 diagnosis.
When DP V0 diagnosis is required, change the setting
under DP slave Properties.
Selecting control mode for
parameter 8-51 Quick Stop Select, and 8-52 DC Brake
Select:
If [0] Digital input is selected, the terminals control the
coast and DC brake functions.
NOTICE
Coasting, Quick Stop, and DC Brake functions are active
If [2] Logic AND is selected, activate both signals to perform
the function.
8-50 Coasting Select,
TerminalBit 02/03/04Function
8.2 No Response to Control Signals
Check that:
1.The control word is valid.
When bit 10=0 in the control word, the frequency
converter does not accept the control word. The
default setting is bit 10=1. Set bit 10=1 via the
PLC.
2.Relationship between bits in the control word
and the terminal I/Os is correct.
Check the logical relationship in the frequency
converter. Set the logic to bit 3=1 and digital
input=1 to achieve a successful start.
Select the FC control mode, digital input and/or serial
communication, using 8-50 Coasting Select to 8-56 PresetReference Select.
Refer to the relevant operating instructions for an overview of warning and alarm types and for the full list of warnings
and alarms.
Alarm word, warning word, and PROFIBUS warning word are shown on the frequency converter display in hex format. When
there is more than 1 warning or alarm, the sum of all warnings or alarms is shown. Alarm word, warning word, and
PROFIBUS warning word can also be displayed using the serial bus in 16-90 Alarm Word, 16-92 Warning Word, and
9-53 Profibus Warning Word.
000000011112Brake check28
000000022113Power card over temperature29
000000044114Earth fault14
000000088115Control card65
0000001016116Control word timeout18
0000002032117Over current13
0000004064118Torque limit12
00000080128119Motor thermistor over temp.11
00000100256104Motor ETR over temperature10
00000200512105Inverter overloaded9
000004001024106DC link under-voltage8
000008002048107DC link over-voltage7
000010004096108DC link voltage low6
000020008192109DC link voltage high5
0000400016384110Mains phase loss4
0000800032768111No motor3
000100006553696Live zero error2
000200001310729710 V lowKTY Warn1
0000000011Ramping
1000000022AMA running
2000000044Start CW/CCW
3000000088Slow down
40000001016Catch up
50000002032Feedback high
60000004064Feedback low
700000080128Output current high
800000100256Output current low
900000200512Output freq hgh
10000004001024Output freq low
11000008002048Brake check OK
12000010004096Braking max
13000020008192Braking
140000400016384Out of speed range
150000800032768OVC active
160001000065536AC brake
1700020000131072Password timelock
1800040000262144Password protection
1900080000524288
20001000001048576
21002000002097152
22004000004194304Unused
23008000008388608Unused
240100000016777216Unused
250200000033554432Unused
260400000067108864Unused
2708000000134217728Unused
2810000000268435456Unused
2920000000536870912Unused
30400000001073741824Unused
31800000002147483648Unused
Table 8.15 Extended Status Word
Bit (Hex)Unit
diagnose
bit
00000001160Connection with DP-master is not OK.
00000002161Unused
00000004162FDL (fieldbus data link layer) is not OK.
00000008163Clear data command received.
00000010164Actual value is not updated.
00000020165Baudrate search
00000040166PROFIBUS ASIC is not transmitting
00000080167Initialising of PROFIBUS is not OK.
00000100152Drive is tripped.
00000200153Internal CAN error
00000400154Wrong configuration data from PLC
00000800155Wrong ID sent by PLC.
00001000156Internal error occurred.
00002000157Not configured
00004000158Timeout active
00008000159Warning 34 active
Table 8.16 9-53 Profibus Warning Word
Bit (Hex)Comm. option STW (16-84 Comm. Option STW)
00000001Parameterisation OK
00000002Configuration OK
00000004Clear mode active
00000008Baudrate search
00000010Waiting for parameterisation
00000020Waiting for configuration
00000040In data exchange
00000080Not used
00000100Not used
00000200Not used
00000400Not used
00000800MCL2/1 connected
00001000MCL2/2 connected
00002000MCL2/3 connected
00004000Data transport active
00008000Unused
PROFIBUS warning word
(9-53 Profibus Warning Word)
88
Table 8.17 16-84 Comm. Option STW
NOTICE
16-84 Comm. Option STW is not part of extended
diagnosis.
Read out the alarm words, warning words and extended
status words via serial bus or optional fieldbus for
diagnosis.
8.4
Fault Messages via DP Diagnosis
The standard DP function features an on-line diagnosis,
which is active during DP initialisation as well as data
exchange mode.
Receive the extended diagnosis function, alarm and
warning information from the frequency converter. The
setting of parameter 8-07 Diagnosis Trigger determines
which frequency converter events trigger the extended
diagnosis function:
When parameter 8-07 Diagnosis Trigger is set to
•
[0] Disable, no extended diagnosis data are sent
regardless of whether they appear in the
frequency converter.
When parameter 8-07 Diagnosis Trigger is set to
•
[1] Alarms, extended diagnosis data are sent
when one or more alarms arrive in the alarm
16-90 Alarm Word or 9-53 Profibus Warning Word.
When parameter 8-06 Reset Control Word Timeout is set to
[2] Alarms/Warnings, extended diagnosis data are sent if 1
or more alarms/warnings arrive in the alarm 16-90 AlarmWord or 9-53 Profibus Warning Word, or in the warning
88
16-92 Warning Word.
The extended diagnosis sequence is as follows:
If an alarm or warning appears, the frequency converter
indicates that to the master by sending a high priority
message via the output data telegram. This causes the
master to send a request for extended diagnosis
information to the frequency converter, to which the
frequency converter replies. When the alarm or warning
disappears, the frequency converter again indicates that to
the master, and on the following request from the master,
ByteBit no.Name
0 to 5-Standard DP diagnosis data
6-PDU length
70-7Status type =0x81
88-15Slot=0
916-23Status information
1024-31
1132-39
1240-47
1348-55
1456-63Reserved for future use
1564-71Reserved for future use
1672-79Reserved for future use
1780-87Reserved for future use
1888-95
1996-103
20104-111
21112-119
22120-127 Reserved for future use
23128-135 Reserved for future use
24136-143 Reserved for future use
25144-151 Reserved for future use
26152-159
27160-167
28168-175 Reserved for future use
29176-183 Reserved for future use
30184-191 Reserved for future use
31192-199 Reserved for future use
Table 8.18 Content of the Extended Diagnosis Frame
16-90 Alarm Word
16-90 Alarm Word
16-90 Alarm Word
16-90 Alarm Word
16-92 Warning Word
16-92 Warning Word
16-92 Warning Word
16-92 Warning Word
9-53 Profibus Warning Word
9-53 Profibus Warning Word
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property
of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.