Danfoss VLT PROFIBUS DP MCA 101, VLT FC 102 Series, VLT FC 103 Series, VLT FC 301, VLT FC 202 Programming Manual

...
MAKING MODERN LIVING POSSIBLE
Programming Guide
VLT® PROFIBUS DP MCA 101
VLT® Frequency Converter Series FC 102 • FC 103 • FC 202 • FC 301/302 • FCD 302
www.danfoss.com/drives
Contents Programming Guide
Contents
1 Introduction
1.1 Purpose of the Manual
1.2 Additional Resources
1.3 Document and Software Version
1.4 Product Overview
1.5 Approvals and Certifications
1.6 Symbols, Abbreviations and Conventions
2 Safety
2.1 Safety Symbols
2.2 Qualified Personnel
2.3 Safety Precautions
3 Configuration
3.1 Configure the PROFIBUS Network
3.2 Configure the Master
3.2.1 GSD File 9
3.3 Configure the Frequency Converter
3 3 3 3 3 4 5
6 6 6 6
8 8 9
11
3.3.1 Frequency Converter Parameters 11
3.3.2 LEDs 11
4 Control
4.1 PPO Types
4.2 Process Data
4.2.1 Process Control Data 14
4.2.2 Process Status Data 14
4.2.3 Reference Handling 15
4.2.4 Process Control Operation 15
4.2.5 Influence of the Digital Input Terminals upon FC Control Mode 16
4.3 Control Profile
4.4 PROFIdrive Control Profile
4.4.1 Control Word according to PROFIdrive Profile (CTW) 16
4.4.2 Status Word according to PROFIdrive Profile (STW) 18
4.4.3 PROFIdrive State Transition Diagram 19
4.5 Danfoss FC Control Profile
4.5.1 Control Word according to FC Profile (CTW) 20
13 13 14
16 16
20
4.5.2 Status Word according to FC Profile (STW) 21
4.6 Synchronise and Freeze
4.6.1 SYNC/UNSYNC 22
4.6.2 FREEZE/UNFREEZE 22
MG37G102 Danfoss A/S © Rev. 05/2014 All rights reserved. 1
22
Contents Programming Guide
5 Parameter Access
5.1 Parameter Access in General
5.2 DP-V1 Parameter Access
5.3 PCV Parameter Access
5.4 PROFIBUS DP Parameter and Data Type
6 Parameters
6.1 8-** PROFIBUS Parameters
6.2 9-** and 16-** PROFIBUS Parameters
6.3 PROFIBUS-specific Parameter List
7 Application Examples
7.1 Example 1: Process Data with PPO Type 6
7.2 Example 2: Control Word Telegram using PPO Type
7.3 Example 3: Status Word Telegram using PPO Type
7.4 Example 4: PLC Programming
8 Troubleshooting
23 23 23 28 31
33 33 35 42
43 43 44 45 46
48
8.1 Diagnosis
8.2 No Response to Control Signals
8.3 Warnings and Alarms
8.4 Fault Messages via DP Diagnosis
8.5 Extended Diagnosis
Index
48 48 50 53 54
55
2 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
Introduction
1 Introduction
Programming Guide
1
1
1.1 Purpose of the Manual
The VLT® PROFIBUS DP MCA 101 Programming Guide provides information about configuring the system, controlling the frequency converter, parameter access, programming, troubleshooting, as well as some typical application examples. The programming guide is intended for use by qualified
personnel who are familiar with the VLT® frequency converter, with PROFIBUS technology, and with the PC or PLC that is used as a master in the system. Read the instructions before programming and follow the procedures in this manual.
VLT® is a registered trademark.
1.2 Additional Resources
Resources available for the frequency converters and optional equipment:
The VLT® Operating Instructions provide the
necessary information for getting the frequency converter up and running.
The VLT
information about capabilities and functionality to design motor control systems.
The VLT® Programming Guide provides greater
detail on working with parameters and many application examples.
The VLT® PROFIBUS DP MCA 101 Installation Guide
provides information about installing the PROFIBUS and troubleshooting.
The VLT® PROFIBUS DP MCA 101 Programming
Guide provides information about configuring the system, controlling the frequency converter, parameter access, programming, troubleshooting, as well as some typical application examples.
Supplementary publications and manuals are available from Danfoss. See www.danfoss.com/BusinessAreas/DrivesSo-
lutions/Documentations/VLT+Technical+Documentation.htm
for listings.
®
Design Guide provides detailed
Edition Remarks Software version
MG37G1xx - -
Table 1.1 Document and Software Version
1.4 Product Overview
1.4.1 Features of PROFIBUS DP-V1
2 different state machines can be selected:
PROFIdrive profile or Danfoss FC profile Communication using PROFIBUS DP-V1, Master
Class 1 and Master Class 2. Downward compatibility: New protocol
extensions retain all the functions of the previous versions.
Intelligent base for future technologies such as
OPC, FDT/DTM, PROFINET. Bus time-out reaction.
PLC/CPU stop reaction.
8 PPO types available.
Numerous relevant process data (PCD) types
available. Automatic detection of baud rate and PPO type.
Extended diagnosis available.
Alarms and warnings available as text messages
within the PLC. Configuration via MCT 10 Set-up Software.
Equidistant bus cycle time configurable in PLC
system. Improved network efficiency, since the cyclic
parameter channel is no longer required. Very short bus cycle times compared to industrial
ethernet . Backwards compatibility with DP.
Technical Overview
1.4.2
1.3
Document and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome. Table 1.1 shows the document version and the corresponding software version.
MG37G102 Danfoss A/S © Rev. 05/2014 All rights reserved. 3
PROFIBUS
PROFIBUS is an international standard for fieldbus communication in automation technology (IEC 61158 and IEC 61784). The standard is supported by the member companies of the PROFIBUS International User Community.
For information about PROFIBUS and downloads for PROFIBUS DP and the PROFIdrive profile, refer to www.Profibus.com.
PLC
130BA078.10
PLC
Master class 1
PC tool
Master class 2
130BA079.10
Introduction Programming Guide
1
PROFIBUS DP-V1
The PROFIBUS DP protocol enables communication between PROFIBUS masters and followers.
Communication can be configured via MCT 10 Set-up Software.
Cyclical/Acyclical Communication
PLC communicates with telegrams of constant
length. Fits time-critical requirements.
Cyclical transmission via PPO types.
Extended diagnosis.
Illustration 1.2 PROFIBUS DP-V1
The PROFIBUS DP extension DP-V1 permits acyclical as well as cyclical data communication. This feature can be used by a DP master class 1 (for example, PLC), as well as a DP master class 2 (for example, PC tool).
Illustration 1.1 PROFIBUS DP-V0
Features of a Master class 1 connection:
Cyclical data exchange (DP-V0).
Acyclical read/write on parameters.
Extended diagnosis.
The acyclical connection is fixed, and cannot be changed during operation.
Features of a Master class 2 connection:
Initiate/Abort acyclical connection.
Acyclical read/write on parameters.
The acyclical connection can be established (Initiate) or removed (Abort) dynamically even when a master class 1 is active on the network. The DP-V1 acyclical connection can be used for general parameter access as an alternative to the PCV parameter channel.
1.5
Approvals and Certifications
More approvals and certifications are available. For more information, contact a local Danfoss partner.
4 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
Introduction Programming Guide
1.6 Symbols, Abbreviations and Conventions
CAN Controller area network CTW Control word DP Distributed periphery DU Data unit EEPROM Electrical erasable programmable read only memory EMC Electromagnetic compatibility FDT Field device tool IND Sub index LCD Liquid crystal display LCP Local control panel LED Light emitting diode MAV Main actual value MC1 Master class 1 MC2 Master class 2 MRV Main reference value PC Personal computer PCD Process data PCA Parameter characteristics PCV Parameter characteristics value PDU Protocol data unit PLC Programmable logic control PNU Parameter number PPO Parameter-process data PVA Parameter value RC Request/Response characteristics SAP Service access point SMP Spontaneous message STW Status word
1
1
Table 1.2 Symbols and Abbreviations
Conventions
Numbered lists indicate procedures. Bullet lists indicate other information and description of illustrations. * indicates a default setting in a parameter. Italicised text indicates
cross reference
link
parameter name
MG37G102 Danfoss A/S © Rev. 05/2014 All rights reserved. 5
Safety Programming Guide
2 Safety
22
2.1 Safety Symbols
The following symbols are used in this document:
WARNING
Indicates a potentially hazardous situation which could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.2 Qualified Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble­free and safe operation of the frequency converter. Only qualified personnel are allowed to install or operate this equipment.
Qualified personnel are defined as trained staff, who are authorised to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Additionally, the personnel must be familiar with the instructions and safety measures described in these operating instructions.
2.3
Safety Precautions
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC power supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
Installation, start-up, and maintenance must be
performed by qualified personnel only.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains, DC power supply, or load sharing, the motor may start at any time. Unintended start during programming, service or repair work can result in death, serious injury, or property damage. The motor can start by means of an external switch, a serial bus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 software, or after a cleared fault condition. To prevent unintended motor start:
Disconnect the frequency converter from mains.
Press [Off/Reset] on the LCP, before
programming parameters. The frequency converter, motor, and any driven
equipment must be fully wired and assembled when the frequency converter is connected to AC mains, DC power supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. Failure to wait the specified time after power has been removed before performing service or repair work, can result in death or serious injury.
Stop motor.
Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully, before
performing any service or repair work. The duration of waiting time is specified in the relevant frequency converter Operating Instructions, Chapter 2 Safety.
6 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
Safety Programming Guide
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the frequency converter properly can result in death or serious injury.
Ensure the correct grounding of the equipment
by a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment can result in death or serious injury.
Ensure that only trained and qualified
personnel perform installation, start up, and maintenance.
Ensure that electrical work conforms to national
and local electrical codes. Follow the procedures in these operating
instructions.
2 2
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result in serious injury, when the frequency converter is not properly closed.
Ensure that all safety covers are in place and
securely fastened before applying power.
MG37G102 Danfoss A/S © Rev. 05/2014 All rights reserved. 7
130BD878.10
ON
1 2
SW. ver. XX.XX
MS
NS
ON OFF
Code No. 130B1100
Termination
SN
SW
Address
ON OFF
S600
S300
LD202 LD200
LD201 LD203
ON ON
8 7 6 5 4 3 2 1
PROFIBUS Option A
1
2
130BB708.10
1
2
4
3
5
Configuration
Programming Guide
3 Configuration
3.1 Configure the PROFIBUS Network
33
Ensure that all PROFIBUS stations connected to the same bus network have a unique station address.
Select the PROFIBUS address of the frequency converter via:
Hardware switches
9-18 Node Address
The PROFIBUS command SSA (Set Station
Address)
Setting the PROFIBUS Address using
3.1.1
the DIP Switches
To set the PROFIBUS address using the DIP switches:
1. Switch off the power supply.
2. Select an address in the range 0 to 125. Factory setting is 127.
3. For location of the DIP switches, refer to Illustration 3.1 and Illustration 3.2.
4. Set the switches according to the address, see Table 3.1.
1 Termination switch 2 DIP switches
Illustration 3.1 Location and Sequence of the DIP Switches
The DIP switch in the FCD 302 are placed below the inverter part, see Illustration 3.2.
Switch 8 7 6 5 4 3 2 1
Address value 5 Not
35 Not
82 Not
Table 3.1 Examples: Setting the PROFIBUS Address using the DIP Switches
NOTICE
Not
+64 +32 +16 +8 +4 +2 +1
used
OFF OFF OFF OFF ON OFF ON
used
OFF ON OFF OFF OFF ON ON
used
ON OFF ON OFF OFF ON OFF
used
Illustration 3.2 FCD 302 Dip Switches
Switch off the power supply before changing the DIP switches.
Setting the PROFIBUS Address via 9-18 Node Address
1. Switch off the power supply.
8 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
2. Set the DIP switch to 126 or 127 (factory switch setting).
3.
Set the address via 9-18 Node Address or the PROFIBUS SSA-command.
4. The address change comes into effect at the next power-up.
130BC915.10
130BC913.11
Configuration
Setting the PROFIBUS Address with Set Station Address Command
1. Switch off the power supply.
2. Set the DIP switch to 126 or 127 (factory switch setting).
3. Set the address via the "Set Station Address" command. Use the "Set Station Address" command to lock the programmed address and to change the address. Unlock the address setting by changing the 9-18 Node Address or the address switch, followed by a power cycle. A new address is effective immediately after the "Set Station Address" command.
Programming Guide
3.2 Configure the Master
3.2.1 GSD File
To configure a PROFIBUS Master, the configuration tool needs a GSD file for each type of follower on the network. The GSD file is a PROFIBUS DP standard text file containing the necessary communications set-up data for a follower. Download the GSD file for the FC 102, FC 202 and FC 301/302 frequency converters at www.danfoss.com/Busines- sAreas/DrivesSolutions/.
3 3
Illustration 3.3 Install GSD File
PROFIBUS SW version
(15-61 Option SW Version)
1.x da01040A.GSD
2.x da02040A.GSD
FCD 302 da01040B.GSD
Table 3.2 GSD File
The example below show the procedure of configuring a PROFIBUS Master for FC 301/302, but the procedure is also valid for the FCD 302.
1. Import the GSD file in the configuration tool.
2. Import the GSD file to the Simatic Manager software tool. Import a GSD file once only for each frequency converter series, following the initial installation of the software tool. See Illustration 3.3.
3. Use the browser for the GSD file, install all files, and import both a GSD file and a bitmap for the device into the hardware catalogue. See Illustration 3.4 and Illustration 3.5.
GSD file
Illustration 3.4 Import a GSD File and a Bitmap
Illustration 3.5 Add a new GSD File
4. Import and access the FC 301/302 GSD file via the path in the hardware catalogue, see Illustration 3.6.
MG37G102 Danfoss A/S © Rev. 05/2014 All rights reserved. 9
130BA564.11
130BC912.11
130BC911.11
Configuration
Programming Guide
33
Illustration 3.8 Drag and Drop PPO Type 6 Word Consistent to
Illustration 3.6 Import and Access the GSD file via the Path in the Hardware Catalogue
5. Open a project, set up the hardware and add a PROFIBUS master system.
6. Select FC 300, then drag and drop it onto the PROFIBUS in the hardware diagram.
7. A window for the address of the FC 300 appears. Select the address from the scroll-down list. Ensure that the address setting matches the previous address setting in 9-18 Node Address. See Illustration 3.7.
the first slot
The configuration tool automatically assigns addresses in the peripheral address area. In this example, the input and output area have the following configurations:
PPO type 6
PCD word number
Input address Set-up STW MAV
1 2 3 4
256-257 258-259 260-261 262-263
parameter 9
-16 PCD Read
Configu-
ration.2
parameter 9
-16 PCD Read
Configu-
ration.3
Illustration 3.7 Select the Address
8. Set up the peripheral input and output data. Data set up in the peripheral area is transmitted cyclically via PPO types. Drag and drop a PPO type 6 word consistent to the first slot, see
Illustration 3.8. See the PPO types in chapter 4 Control for more information.
Table 3.3 PCD read (VLT to PLC)
PCD word number
Output address Set-up CTW MRV
Table 3.4 PCD write (PLC to VLT)
1 2 3 4
256-257 258-259 260-261 262-263
parameter 9
-15 PCD Write
Configu-
ration.2
parameter 9
-15 PCD Write
Configu-
ration.3
Alternative: For PROFIBUS SW version 2.x and higher, Auto­configuration of process data is supported. This feature makes it possible to configure the process data (parameter 9-15 PCD Write Configuration and parameter 9-16 PCD Read Configuration) from the PLC/ Master. To use Auto-configuration, make sure to enable the feature under DP follower Properties. See Illustration 3.9.
10 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
130BT322.11
Configuration
Illustration 3.9 Enable Feature under DP Follower Properties
Programming Guide
NOTICE
DP V1 diagnosis is supported for PROFIBUS SW version
2.x and higher. The default setting of the PROFIBUS option is DP V1 diagnosis. If DP V0 diagnosis is required, change the setting under DP follower Properties.
0-40 [Hand on] Key on LCP. Pressing [Hand on]
disables control of the frequency converter via PROFIBUS.
Parameter 8-02 Control Word Source. After an
initial power-up, the frequency converter automatically detects whether a fieldbus option is installed in slot A, and sets parameter 8-02 Control Word Source to [Option A]. If an option is added or changed in or removed from an already commissioned frequency converter, it does not change parameter 8-02 Control Word Source, but enters Trip mode, and the frequency converter displays an error.
Parameter 8-10 Control Word Profile. Select
between the Danfoss FC Profile and the PROFIdrive profile.
8-50 Coasting Select to 8-56 Preset Reference Select.
Select how to gate PROFIBUS control commands with digital input command of the control card.
Parameter 8-03 Control Word Timeout Time to
8-05 End-of-Timeout Function. Set the reaction in the event of a bus time-out via these parameters.
9-18 Node Address.
Parameter 8-07 Diagnosis Trigger.
NOTICE
When 8-01 Control Site is set to , the settings in 8-50 Coasting Select to 8-56 Preset Reference Select are
overruled, and all act on Bus-control.
3 3
Illustration 3.10 DP V1 Diagnosis
Download the configuration file to the PLC. The PROFIBUS system is able to go online, and it starts to exchange data when the PLC is set to Run mode.
3.3
Configure the Frequency Converter
3.3.1 Frequency Converter Parameters
The following parameters are important when configuring the frequency converter with a PROFIBUS interface:
3.3.2 LEDs
The 2 bi-colour LEDs in the PROFIBUS card indicate the status of PROFIBUS communication.
The LED marked NS (FCD 302: NS2) indicates the network status, that is, the cyclical communication to the PROFIBUS master. When this light is constant green, data exchange between the master and the frequency converter is active.
The LED marked MS (FCD 302: BUS MS) indicates the module status, that is, acyclical DP V1 communication from either a PROFIBUS master class 1 (PLC) or a master class 2 (MCT 10, FDT tool). When this light is constant green, DP V1 communication from master classes 1 and 2 is active.
For details of the full range of communications status indicated by the LEDs, refer to chapter 8 Troubleshooting.
MG37G102 Danfoss A/S © Rev. 05/2014 All rights reserved. 11
A
130BC259.10
Configuration Programming Guide
33
Illustration 3.11 FCD 302 LED Panel
12 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
Control Programming Guide
4 Control
4.1 PPO Types
The PROFIBUS profile for frequency converters specifies a number of communication objects (Parameter process data objects, PPO). The PROFIBUS profile for frequency converters is suitable for data exchange between a process controller (for example PLC) and a frequency converter. All PPOs are defined for cyclic data transfer (that is, DP V0), so that process data (PCD) and parameters (PCA) can be transferred from the master to the follower and vice versa.
Pure process data objects
PPO types 3, 4, 6, 7 and 8 are pure process data objects for applications requiring no cyclic parameter access. The PLC sends out process control data, and the frequency converter then responds with a PPO of the same length, containing process status data.
Illustration 4.1 shows the available PPO types:
PCD 1: The first 2 bytes of the process data area
(PCD 1) comprise a fixed part present in all PPO types.
PCD 2: The next 2 bytes (PCD 2) are fixed for PCD
write entries (see parameter 9-15 PCD Write Configuration [1]), but configurable for PCD read entries (see parameter 9-16 PCD Read Configu­ration [1]).
PCD 3-10: In the remaining bytes, from PCD 3
and on, the process data can be parameterised with process signals, see parameter 9-23 Parameters for Signals.
The signals for transmission from the master to the frequency converter are determined by the setting in parameter 9-15 PCD Write Configuration (request from master to the frequency converter).
The signals for transmission from the frequency converter to the master (response from the frequency converter to master) are determined by the setting in parameter 9-16 PCD Read Configuration .
Parameter channel and process data
PPO types 1, 2 and 5 consist of a parameter channel and process data. Use the parameter channel for reading and/or updating of parameters (successively). Alternatively, for better utilisation of I/O and thus PLC capacity, access parameters via DP V1, by selecting a pure process data object (PPO type 3, 4, 6, 7 or 8).
Select the PPO type in the master configuration. The selection is automatically recorded in the frequency converter. No manual setting of PPO types in the frequency converter is required. Read the current PPO type in 9-22 Telegram Selection. The setting [1] Standard telegram 1 is equivalent to PPO type 3.
In addition, all PPO types can be set up as word-consistent or module-consistent. The process data area can be word or module consistent, whereas the parameter channel must always be module consistent.
Word-consistent data is transmitted as individual
independent words between the PLC and the frequency converter.
Module-consistent data is transmitted as sets of
interrelated words transferred simultaneously between the PLC and the frequency converter.
4 4
MG37G102 Danfoss A/S © Rev. 05/2014 All rights reserved. 13
CTW/STW
REF/MAV
PCD 2 Read/
Write
PCD 3 Read/
Write
Standard telegram
1
PCD 4 Read/
Write
PCD 5
Read/
Write
PPO 4
PPO 6
PPO 7
PPO 8
Danfoss telegram
(The old PPO type 3)
PCV
CTW/STW REF/MAV
PCD 2 Read/
Write
PCD 3
Read/
Write
PCD 4 Read/
Write
PCD 5 Read/
Write
CTW/STW
REF/MAV
PCD 2 Read/
Write
PCD 3
Read/
Write
PCD 4 Read/
Write
PCD 5 Read/
Write
PCD 6 Read/
Write
PCD 7 Read/
Write
PCD 8 Read/
Write
PCD 9 Read/
Write
CTW/STW REF/MAV
PCD 2 Read/
Write
PCD 3 Read/
Write
PCD 4
Read/
Write
PCD 5
Read/
Write
PCD 6 Read/
Write
PCD 7 Read/ Write
CTW/STW REF/MAV
CTW/STW REF/MAV
PPO 3
CTW/STW REF/MAV
PCD 2 Read/
Write
PCD 3
Read/
Write
PPO 2
PCV
CTW/STW
REF/MAV
PPO 1
PCV
130BD911.10
Control Programming Guide
44
Illustration 4.1 Available PPO Types
4.2
Process Data
Use the process data part of the PPO to control and monitor the frequency converter via the PROFIBUS.
4.2.1 Process Control Data
Process control data (PCD) is the process data sent from the PLC to the frequency converter.
Master/follower
1 2 3 ....... 10
CTW MRV PCD ....... PCD
PCD write
Table 4.1 Process Control Data
PCD 1 contains a 16-bit control word, and each bit controls a specific function of the frequency converter, see chapter 4.3 Control Profile.
PCD 2 contains a 16-bit speed setpoint in percentage format. See chapter 4.2.3 Reference Handling.
The content of PCD 3 to PCD 10 is determined by the settings in parameter 9-15 PCD Write Configuration and parameter 9-16 PCD Read Configuration.
4.2.2 Process Status Data
Process status data is the process data sent from the frequency converter, and contains information about the current state.
Follower master
1 2 3 ...... 10
STW MAV PCD ...... PCD
PCD read
Table 4.2 Process Status Data
PCD 1 contains a 16-bit status word, and each bit contains information regarding a possible state of the frequency converter.
PCD 2 contains per default the value of the current speed of the frequency converter in percentage format (see chapter 4.2.3 Reference Handling). PCD 2 can be configured to contain other process signals.
14 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
Control
Programming Guide
The content of PCD 3 to PCD 10 is determined by the settings in parameter 9-16 PCD Read Configuration.
4.2.3 Reference Handling
The reference handling is an advanced mechanism that sums up references from different sources, as shown in Illustration 4.2.
For more information on reference handling, refer to the Design Guide of the relevant frequency converter.
Illustration 4.2 Reference
The actual output of the frequency converter is limited by the speed limit parameters Motor Low/High Speed Limit
[RPM/Hz] in 4-11 Motor Speed Low Limit [RPM] to 4-14 Motor Speed High Limit [Hz]. The final speed limit is set in 4-19 Max Output Frequency.
Table 4.3 lists the reference (MRV) and the feedback (MAV)
formats.
MRV/MAV Integer in hex Integer in decimal
100% 4000 16,384
75% 3000 12,288 50% 2000 8,192 25% 1000 4,096
0% 0 0
-25% F000 -4,096
-50% E000 -8,192
-75% D000 -12,288
-100% C000 -16,384
Table 4.3 Reference/Feedback (MRV/MAV) Format
NOTICE
Negative numbers are formed as complement of 2.
4 4
The reference, or speed setpoint, is sent via PROFIBUS and is always transmitted to the frequency converter in percentage format as integers represented in hexadecimal (0-4000 hex).
The reference (MRV) and feedback (MAV) are always scaled equally. The setting of 3-00 Reference Range determines the scaling of the reference and feedback (MAV), see Illustration 4.3.
Illustration 4.3 Reference (MRV) and Feedback (MAV), Scaled
NOTICE
The data type for MRV and MAV is a N2 16-bit standardised value, expressing a range from -200% to +200% (8001 to 7FFF).
Example
The following settings determine the speed, as shown in
Table 4.4:
1-00 Configuration Mode set to [0] Speed open
loop. 3-00 Reference Range set to [0] Min-Max.
3-02 Minimum Reference set to 100 RPM.
3-03 Maximum Reference set to 3000 RPM.
MRV/MAV Actual speed [RPM]
0% 0 hex 100 25% 1000 hex 825 50% 2000 hex 1550 75% 3000 hex 2275 100% 4000 hex 3000
Table 4.4 Actual Speed for MRV/MAV
4.2.4
NOTICE
When 3-00 Reference Range is set to [0] Min - Max, a negative reference is handled as 0%.
MG37G102 Danfoss A/S © Rev. 05/2014 All rights reserved. 15
Process Control Operation
In process control operation, 1-00 Configuration Mode is set to [3] Process. The reference range in 3-00 Reference Range is always [0]
Min - Max.
Control
Programming Guide
MRV represents the process setpoint. MAV expresses the actual process feedback
(range ±200%).
4.4
PROFIdrive Control Profile
This section describes the functionality of the control word and status word in the PROFIdrive profile.
4.2.5 Influence of the Digital Input Terminals upon FC Control Mode
Set the influence of the digital input terminals upon
44
control of the frequency converter in 8-50 Coasting Select to 8-56 Preset Reference Select.
NOTICE
The setting of 8-01 Control Site overrules the settings in 8-50 Coasting Select to 8-56 Preset Reference Select. The
setting of terminal 37 Coast stop (safe) overrules any other parameter.
Each of the digital input signals can be programmed to logic AND, logic OR, or to have no relation to the corresponding bit in the control word. In this way the following signal sources initiate a specific control command, for example stop/coast:
fieldbus only,
fieldbus AND digital input, or
either fieldbus OR digital input terminal.
CAUTION
To control the frequency converter via PROFIBUS, set 8-50 Coasting Select to either [1] Bus , or to [2] Logic AND, and set 8-01 Control Site to [0] or [2].
For more detailed information and examples of logical relationship options, see chapter 8 Troubleshooting.
4.3
Control Profile
Control the frequency converter according to
the PROFIdrive profile, see chapter 4.4 PROFIdrive
Control Profile, or the Danfoss FC control profile, see
chapter 4.5 Danfoss FC Control Profile.
Select the desired control profile in parameter 8-10 Control Word Profile. The choice of profile affects the control and status word only.
Chapter 4.4 PROFIdrive Control Profile and chapter 4.5 Danfoss FC Control Profile provide a detailed
description of control and status data.
4.4.1 Control Word according to PROFIdrive Profile (CTW)
The control word is used to send commands from a master (e.g. a PC) to a follower.
Bit Bit=0 Bit=1
00 OFF 1 ON 1 01 OFF 2 ON 2 02 OFF 3 ON 3 03 Coasting No coasting 04 Quick stop Ramp 05 Hold frequency output Use ramp 06 Ramp stop Start 07 No function Reset 08 Jog 1 OFF Jog 1 ON 09 Jog 2 OFF Jog 2 ON 10 Data invalid Data valid 11 No function Slow down 12 No function Catch up 13 Parameter set-up Selection lsb 14 Parameter set-up Selection msb 15 No function Reverse
Table 4.5 Control Word Bits
Explanation of the control bits Bit 00, OFF 1/ON 1
Normal ramp stops using the ramp times of the actual selected ramp. Bit 00="0" leads to the stop and activation of the output relay 1 or 2 if the output frequency is 0 Hz and if [Relay 123] has been selected in 5-40 Function Relay. When bit 0="1", the frequency converter is in State 1: “Switching on inhibited”. Refer to Illustration 4.4.
Bit 01, OFF 2/ON 2
Coasting stop. When bit 01="0", a coasting stop and activation of the output relay 1 or 2 occurs if the output frequency is 0 Hz and if [Relay 123] has been selected in 5-40 Function Relay. When bit 01="1", the frequency converter is in State 1: “Switching on inhibited”. Refer to Illustration 4.4.
Bit 02, OFF 3/ON 3
Quick stop using the ramp time of 3-81 Quick Stop Ramp Time.
When bit 02="0", a quick stop and activation of the output relay 1 or 2 occurs if the output frequency is 0 Hz and if [Relay 123] has been selected in 5-40 Function Relay. When bit 02="1", the frequency converter is in State 1: “Switching on inhibited”.
16 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
Loading...
+ 42 hidden pages