Danfoss VLT FC 100 LonWorks User Manual

VLT® FC 100 LonWorks Contents
Contents
1 Copyright
Copyright 3
Copyright, Limitation of Liability and Revision Rights 3
2 Safety
Safety 5
3 Introduction
Introduction 7
4 How to install
5 Configuration of the system
3
5
7
11
19
6 How to control the Frequency Converter
7 How to access FC 100 parameters
8 Parameters
41
45
49
9 Troubleshooting
MG.11.E2.02 - VLT® is a registered Danfoss trademark
57
1
Contents VLT® FC 100 LonWorks
Extended status words 60
Reference Scaling - Examples 61
Network Variables - Overview 62
Index
64
2
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 1 Copyright
1Copyright
1
1.1 Copyright
1.1.1 Copyright, Limitation of Liability and Revision Rights
This publication contains information proprietary to Danfoss. By accepting and using this manual the user agrees that the information contained herein
will be used solely for operating equipment from Danfoss or equipment from other vendors provided that such equipment is intended for communication
with Danfoss equipment over a serial communication link. This publication is protected under the Copyright laws of Denmark and most other countries.
Danfoss does not warrant that a software program produced according to the guidelines provided in this manual will function properly in every physical,
hardware or software environment.
Although Danfoss has tested and reviewed the documentation within this manual, Danfoss makes no warranty or representation, neither expressed nor
implied, with respect to this documentation, including its quality, performance, or fitness for a particular purpose.
In no event shall Danfoss be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information
contained in this manual, even if advised of the possibility of such damages. In particular, Danfoss is not responsible for any costs, including but not
limited to those incurred as a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute
these, or any claims by third parties.
Danfoss reserves the right to revise this publication at any time and to make changes to its contents without prior notice or any obligation to notify former
or present users of such revisions or changes.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
3
2
2 Safety VLT® FC 100 LonWorks
4
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 2 Safety
2Safety
2.1 Safety
2.1.1 Safety note
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect installation of the motor, frequency
converter or fieldbus may cause damage to the equipment, serious personal injury or death. Consequently, the instructions in this
manual, as well as national and local rules and safety regulations, must be complied with.
Safety Regulations
1. The frequency converter must be disconnected from mains if repair work is to be carried out. Check that the mains supply has been disconnected
and that the necessary time has passed before removing motor and mains plugs.
2. The [STOP/RESET] key on the LCP of the frequency converter does not disconnect the equipment from mains and is thus not to be used as a
safety switch.
3. Correct protective earthing of the equipment must be established, the user must be protected against supply voltage, and the motor must be
protected against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is set by par. 1-90
tion
to data value [ETR trip] (default value) or data value [ETR warning]. Note: The function is initialised at 1.16 x rated motor current and rated
motor frequency. For the North American market: The ETR functions provide class 20 motor overload protection in accordance with NEC.
6. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has
been disconnected and that the necessary time has passed before removing motor and mains plugs.
7. Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when load sharing (linking of DC intermediate circuit) and
external 24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before
commencing repair work.
Installation at High Altitudes
Installation at high altitude:
380 - 500 V, enclosure A, B and C: At altitudes above 2 km, please contact Danfoss regarding PELV.
380 - 500 V, enclosure D, E and F: At altitudes above 3 km, please contact Danfoss regarding PELV.
525 - 690 V: At altitudes above 2 km, please contact Danfoss regarding PELV.
Motor Thermal Protection
. If this function is desired, set par. 1-90
Motor Thermal Protec-
2
Warning against Unintended Start
1. The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop, while the frequency converter
is connected to mains. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stop functions are
not sufficient.
2. While parameters are being changed, the motor may start. Consequently, the stop key [STOP/RESET] must always be activated; following which
data can be modified.
3. A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or a fault in
the supply mains or the motor connection ceases.
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as
the motor connection for kinetic back up. Refer to the Operating Instructions for further safety guidelines.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
5
2
2 Safety VLT® FC 100 LonWorks
2.1.2 Safety Regulations
1. The frequency converter must be disconnected from mains if repair work is to be carried out. Check that the mains supply has been disconnected
and that the necessary time has passed before removing motor and mains plugs.
2. The [STOP/RESET] key on the LCP of the frequency converter does not disconnect the equipment from mains and is thus not to be used as a
safety switch.
3. Correct protective earthing of the equipment must be established, the user must be protected against supply voltage, and the motor must be
protected against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is not included in the factory setting. If this function is desired, set par. 1-90
data value ETR trip or data value ETR warning. Note: The function is initialised at 1.16 x rated motor current and rated motor frequency. For
the North American market: The ETR functions provide class 20 motor overload protection in accordance with NEC.
6. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has
been disconnected and that the necessary time has passed before removing motor and mains plugs.
7. Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when load sharing (linking of DC intermediate circuit) and
external 24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before
commencing repair work.
Motor Thermal Protection
2.1.3 Warning against Unintended Start
to
1. The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop, while the frequency converter
is connected to mains. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stop functions are
not sufficient.
2. While parameters are being changed, the motor may start. Consequently, the stop key [STOP/RESET] must always be activated; following which
data can be modified.
3. A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or a fault in
the supply mains or the motor connection ceases.
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as
the motor connection for kinetic back up. Refer to
VLT HVAC Drive Operating Instructions (MG.11.AX.YY)
for further safety guidelines.
6
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 3 Introduction
3Introduction
3.1 Introduction
3.1.1 About this manual
First time users can obtain the most essential information for quick installation and set-up in these chapters:
Introduction
How to Install
How to Configure the System
For more detailed information including the full range of set-up options and diagnosis tools please refer to the chapters:
How to Control the FC 100
How to Access FC 100 Parameters
Parameters
Troubleshooting
®
, LonTalk®, Neuron®, LonWorks® and LonMaker® are registered trademarks of the Echelon Corporation.
Echelon
3
3.1.2 Technical Overview
The LonWorks communications structure is similar to that of a local area network (LAN) in that messages are continually exchanged between a number
of processors. A LonWorks system is a local operating network (LON). LON technologyoffers a means for integrating various distributed systems that
perform sensing, monitoring, control, and other automated functions. A LON allows these intelligent devices to communicate with one another through
a variety of communications media using a standard protocol.
LON technology supports distributed, peer-to-peer communications. That is, individual network devices can communicate directly with one another without
the need for a central control system. A LON is designed to move sense and control messages which are typically very short and which contain commands
and status information that trigger actions. LONperformance is viewed in terms of transactions completed per second and response time. Control systems
do not require vast amounts of data, but they do demand that the messages they send and receive are absolutely correct.
Data are transported by means of standard network variable types (SNVTs) which provide a well- defined interface for communication between devices
from different manufacturers. Functional profiles defining the functionality and network variables for a particular family of devices (e.g. frequency con-
verters, pumps etc.) are also available, and supported by the LonWorks option.
3.1.3 Assumptions
These operating instructions assume, that the Danfoss LonWorks option is used in conjunction with a Danfoss FC 100 frequency converter. It is also
assumed that the installed controller supports the interfaces described in this document and that all the requirements stipulated in the controller, as well
as the frequency converter, are strictly observed along with all limitations therein.
3.1.4 Hardware
This manual relates to the
LonWorks option MCA108
, type no. 130B1106 (non-coated) and 130B1206 (coated).
MG.11.E2.02 - VLT® is a registered Danfoss trademark
7
3
3 Introduction VLT® FC 100 LonWorks
3.1.5 Background Knowledge
The Danfoss LonWorks Option Card is designed to communicate with any system complying with the FTT and 78Kbps LonWorks standard. Familiarity
with this technology is assumed. Issues regarding hardware or software produced by other manufacturers, including commissioning tools, are beyond
the scope of this manual and are not the responsibility of Danfoss.
For information regarding commissioning tools or communication with a non-Danfoss node, please consult the appropriate manuals.
3.1.6 Related Literature for the VLT HVAC Drive
Title Literature no.
VLT® HVAC Drive Operating Instructions
®
VLT
HVAC Drive Design Guide
VLT® HVAC Drive Programming Guide
The following literature is available for the FC 100 series:
MG.11.Ax.yy
MG.11.Bx.yy
MG.11.Cx.yy
Please also refer to
www.danfoss.com/BusinessAreas/DrivesSolution
for additional information.
3.1.7 LonMark Certification
The LonWorks option is conform to the LonMark standards and is certified towards LonMark ver. 3.4
8
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 3 Introduction
3.1.8 Abbreviations
ACK AC Knowledge
A Ampere
BOOL Boolean
CC Control Card
CTW Control Word
EMC Electromagnetic Compatibility
FTT Free Topology Transceiver
HF High frequency
Hz Frequency in Hertz
I/O Input / Output
IRMS Output Current Mean Value
LCP Local Control Panel
LED Light Emitting Diode
LON Local Area Network
LSB Least Significant Bit
MAV Main Active Value
MSB Most Significant Bit
MRV Main Reference Value
N/A Not Applicable
PC Personal Computer
PLC Programmable Logic Controller
PNU Parameter Number
RPM Revolutions Per Minute
RTC Real Time Clock
s Seconds
SCPT Standard Configuration Property Types
SNVT Standard Network Variable Type
SINT Signed integer
STW Status Word
V Voltage
VSD Variable Speed Drive
UDINT Unsigned double integer
UINT Unsigned integer
UNVT User-defined Network Variable Type
XIF Extended Interface File
3
MG.11.E2.02 - VLT® is a registered Danfoss trademark
9
4
4 How to install VLT® FC 100 LonWorks
10
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 4 How to install
4How to install
4.1 How to install
4.1.1 The LonWorks Option
4
The LonWorks option is equipped with two termination switches, S300 and S301, enabling double termination when using bus topology.
The push-button switch O400, activates the Service-Pin function.
The LEDs:
LED label Description
MS Service LED (red)
NS Status LED (green)
The neuron ID is printed on the option in text and in barcode (code 39).
4.1.2 Cabling
The Free Topology Transceiver (FTT) system is designed to support free topology wiring and accommodates bus, star, loop or any combination of these
topologies.
The LonWorks option is equipped with the FT-X1 transceiver for improved EMC performmance. Flexible wiring capability simplifies system installation and
makes it easy to add nodes for system expansion.
The figures below illustrate five different network topologies.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
11
4
4 How to install VLT® FC 100 LonWorks
4.1.3 Network Termination
Dependent on the type of topology, at least one of the connected nodes must be terminated (52.5). The option has two built-in termination circuits
which are activated by the terminator switches S300 and S301.
If termination is provided elsewhere in the network, the termination switches should be OFF. If a double-terminated bus topology is used, the first and
the last node should be double-terminated (105Ω).
Termination switch positions are shown in the table below.
Termination type S 300 S 301
No termination (factory setting) OFF OFF
Double termination (105 Ω)ONOFF
Single termination (52.5 Ω) ON ON
12
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 4 How to install
4.1.4 Connecting the Bus Line
Connect bus wire NET A to terminal 79 and NET B to 80 of the terminal connector.
Terminal Connection
79 NET A*
80 NET B*
61 Drain**
NB! *Note: For free topology wiring the option is insensitive to the polarity of the bus-terminals.
NB! **Note: Term. 61 (Drain) offers a RC-junction to ground and should not be used for grounding of shielded cable. Ground the shielded
cable at the de-coupling plate by removing cable insulation at contact point.
4.1.5 Maximum Cable Lengths
Network topology Maximum cable length
Free topology without repeater 500 m
Free topology with one repeater 1000 m
Free topology maximum device-to-device 500 m
Bus topology single terminated 500 m
Bus topology double terminated without repeater 2700 m
Bus topology double terminated with one repeater 5400 m
Bus topology maximum stub length 3 m
Use of the same cable type throughout the entire network is recommended in order to avoid impedance mismatch.
4
4.1.6 System Specifications
Up to 64 FT-X1/FTT-10 transceivers, are allowed per network segment.
NB! Note: The Free Topology LonWorks runs at 78 Kbps only.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
13
4
4 How to install VLT® FC 100 LonWorks
4.1.7 EMC Precautions
The following EMC precautions are recommended in order to achieve interference-free operation of the LonWorks network. Additional EMC information
is available in the
The LonWorks communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable
to the other. Normally a distance of 200 mm (8 inches) is sufficient, but maintaining the greatest possible distance between the cables is recommended,
especially where cables run in parallel over long distances. When crossing is unavoidable, the LonWorks cable must cross motor and brake resistor cables
at an angle of 90 degrees.
VLT HVAC Drive Design Guide
NB!
N.B.:
Relevant national and local regulations, for example regarding protective earth connection, must be observed.
.
14
NB!
It is highly recommended to use suitable screened cable for any LonWorks installation!
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 4 How to install
4.1.8 LED Behaviour
MS: Service LED (red)
Situation LED Description
Configured state (Nornal operation) ½ sec. ON, then continously OFF The node is configures and running nor-
mally
Non configures state Flashing ½ Hz Node is not configures but has an appli-
cation. Proceed with loading node.
Applicationlessstate 1 sec. ON, 2 sec. OFF, then continuoslyONNode has no application, the LonWorks
option needs replacing or reprogram-
ming
Watchdog resets Short flash about each 3 sec. Indicates problem with application. The
LonWorks option needs replacing
Faulty hardware Steady ON or OFF The LonWorks option needs replacing
NS: Status LED (green)
Situation LED Description
4
Node configured Steady ON The node is configures and running
normally
Wink sevice Flashing ½ Hz for 20 sec. Wink service activated in order to
identify node.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
15
4
4 How to install VLT® FC 100 LonWorks
4.1.9 How to Install Option in Frequency Converter
Items required to install a fieldbus option in the frequency converter:
- The fieldbus option
- Fieldbus option adaptor frame for the FC 100. This frame is deeper than the standard frame, to allow space for the fieldbus option beneath
- Decoupling plate (only for A1 and A2 enclosures)
16
130BT247.12
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 4 How to install
Instructions:
- Remove LCP panel from the FC 100
- Remove the frame located beneath and discard
- Push the option into place. Two positions are possible, with cable terminal facing either up or down
- Push the fieldbus option adaptor frame for the FC 100 into place
- Replace the LCP and attach cable
- On A1 and A2 enclosures with cable terminal facing up: Fasten the cable onto the de-coupling plate (the FC 100 top surface has pre-drilled
threaded holes for attaching the de-coupling plate to the unit).
4
MG.11.E2.02 - VLT® is a registered Danfoss trademark
17
5
5 Configuration of the system VLT® FC 100 LonWorks
18
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 5 Configuration of the system
5 Configuration of the system
5.1 Configuring the System
5.1.1 How to Configure the LonWorks Network
Th e Lo nWor ks op tio n car d co ntai ns a N euro n ch ip wi th a uniq ue a ddre ss. This Neur on ID is a 48 b it nu mbe r tha t ide nti fies each Neuron chip manufactured.
Addressing nodes on the LonWorks network is performed at the time of installation using an installation tool or network management tool (e.g. LonMaker).
Addressing requires the retrieval of the Neuron ID for the node.
There are several methods by which the network software can retrieve the Neuron ID and address the node:
1. Service Pin – The push-button service switch sends the Neuron ID over the network.
If the network software prompts the action, press the Service Pin switch (O400) to transmit the Neuron ID over the network. Please refer to
the How to Install section for the location of the Service Pin switch.
2. Query and Wink - Upon receiving a Wink command, both LED’s flashes (½ Hz for 20 sec.) so the installer can locate the node. The option
sends out its Neuron ID over the network in response to the query command.
3. Neuron ID Label – The installer can manually enter the Neuron ID during installation. The Neuron ID can be found on the label of the option
in text and barcode.
Resource Files
A LonMark interface file (.XIF file extension) provides the host processor with device information. Using this file it is possible to design a LonWorks network
without the adjustable frequency converter being physically present. Other resource files are:
Type file (.typ file extension)
Format file (.fmt file extension)
Language description file (.eng, .enu and other file extensions)
The resource files can be downloaded from the web site
Here you will also find a free download of an LNS plug-in for the use in the LonMaker tool.
www.danfoss.com/BusinessAreas/DrivesSolution
.
5
5.1.2 Functional Profiles
LonMark functional profiles are used to describe in detail the application layer interface, including the network variables, configuration properties, and
commonly used control functions.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
19
5
5 Configuration of the system VLT® FC 100 LonWorks
5.1.3 FC VSD Profile
The FC VSD Profile describes all Danfoss VLT specific network variables.
Input variables
Variable Function Variable Name SNVT type Profile FC 100 par.
Start/Stop nviStartStop SNVT_switch FC VSD CTW/reference
Control word nviControlword SNVT_state FC VSD CTW
Reset fault nviResetFaut SNVT_switch FC VSD CTW
Reference [%] nviRefPcnt SNVT_lev_percent FC VSD Reference
Reference [Hz] nviRefHz SNVT_freq_hz FC VSD Reference
CL Setpoint 1 nviSetpoint1 SNVT_lev_percent FC VSD 20-21
CL Setpoint 2 nviSetpoint2 SNVT_lev_percent FC VSD 20-22
CL Setpoint 3 nviSetpoint3 SNVT_lev_percent FC VSD 20-23
Bus feedback 1 nviFeedback1 SNVT_lev_percent FC VSD 8-94
Bus feedback 2 nviFeedback2 SNVT_lev_percent FC VSD 8-95
Bus feedback 3 nviFeedback3 SNVT_lev_percent FC VSD 8-96
Digital/relay outputs nviDigiOutput SNVT_state_64 FC VSD 5-90
Analog output (42) nviAnOut1 SNVT_lev_percent FC VSD 6-53
Analog output (X30/8) nvi101AnOut1 SNVT_lev_percent FC VSD 6-63
Analog output (X42/7) nvi109AnOut1 SNVT_lev_percent FC VSD 26-43
Analog output (X42/9) nvi109AnOut2 SNVT_lev_percent FC VSD 26-53
Analog output (X42/11) nvi109AnOut3 SNVT_lev_percent FC VSD 26-63
Setting of RTC nviTimeStamp SNVT_time_stamp FC VSD 0-70
ECB option Mode nviECBMode SNVT_state FC VSD 31-00
ECB By-pass activation nviECBActivation SNVT_switch FC VSD 31-19
Parameter access command nviParamRequest UNVT_param_request FC VSD -
20
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 5 Configuration of the system
Output variables
Variable function Variable name SNVT type Profile FC 100 par.
Status word nvoStatusword SNVT_state FC VSD 16-03
Drive output [%] nvoOutputPcnt SNVT_lev_percent FC VSD 16-05
Drive output [Hz] nvoOutputHz SNVT_freq_hz FC VSD 16-13
kWh counter nvoDrvEnrg SNVT_elec_kwh_l FC VSD 15-02
DC Link Voltage nvoDCVoltage SNVT_volt FC VSD 16-30
Motor thermal nvoTempMtr SNVT_lev_cont FC VSD 16-18
Inverter Thermal nvoTempInvrtr SNVT_lev_cont FC VSD 16-35
Closed loop feedback nvoFeedback SNVT_count_inc_f FC VSD 16-52
Fanbelt broken nvoBrokenBelt SNVT_switch FC VSD 16-93
Alarm flag nvoAlarm SNVT_switch FC VSD 16-90
Warning flag nvoWarning SNVT_switch FC VSD 16-03
Alarm word nvoAlarmword SNVT_state_64 FC VSD 16-90 + 16-91
Warning word nvoWarningword SNVT_state_64 FC VSD 16-92 + 16-93
Extended statusword nvoExtendedStatusword SNVT_state_64 FC VSD 16-94 + 16-95
Digital inputs nvoDigitInput SNVT_state_64 FC VSD 16-60
Analog Input (53) nvoAnIn1 SNVT_volt/SNVT_amp_mil/SNVT_lev_percent FC VSD 16-62
Analog Input (54) nvoAnIn2 SNVT_volt/SNVT_amp_mil/SNVT_lev_percent FC VSD 16-64
Analog Input (X30/11) nvo101AnIn1 SNVT_volt/SNVT_lev_percent FC VSD 16-75
Analog Input (X30/12) nvo101AnIn2 SNVT_volt/SNVT_lev_percent FC VSD 16-76
Analog Input (X42/1) nvo109AnIn1 SNVT_volt/SNVT_temp_p/SNVT_lev_percent FC VSD 18-30
Analog Input (X42/3) nvo109AnIn2 SNVT_volt/SNVT_temp_p/SNVT_lev_percent FC VSD 18-31
Analog Input (X42/5) nvo109AnIn3 SNVT_volt/SNVT_temp_p/SNVT_lev_percent FC VSD 18-32
ECB option status nvoECBstatus SNVT_state FC VSD 31-10
Parameter access cmd. nvoParamResponse UNVT_param_response FC VSD -
5
MG.11.E2.02 - VLT® is a registered Danfoss trademark
21
5 Configuration of the system VLT® FC 100 LonWorks
5.2 Network Variable Description
5.2.1 - FC VSD Profile - input
Start/Stop
5
Variable name:
nviStartStop SNVT_switch 0 (False) Any Stop (0x043C)
1 (True) 0 Running 0% (0x047C)
This variable sends a Start or Stop command to the frequency converter and a reference (0 - 100 %)
NB!
The reference value of nviStartStop will only be valid
if both nviRefPcnt and nviRefHz are = 0
Control Word
Variable name:
nviControlword SNVT_state Boolean 1 bit x 16
The input network variable nviControlWord is a 16-bit word providing additional operational control of the frequency converter.
For more information about the Control word, please refer to the
SNVT type:
SNVT type:
State: Value: Command:
1 (True) 1-200 Running 0.5 to 100.0%
1 (True) 201-255 Running100%
0xFF (default) Any AUTO (invalid, no action)
State:
Danfoss FC Control Profile
section.
NB!
Please note in the representation of the Control Word in the LonMaker Browser, the LSB is to the far left.
Reset fault
Variable name:
nviResetFault SNVT_switch 0 (False) Any No reset
This variable sends a reset command to the frequency converter via bit 7 in the Control Word (0x04BC), see the
SNVT type:
State: Value: Command:
1 (True) Any Reset (0x04B)
0xFF (default) Any AUTO (invalid, no action)
Danfoss FC Control Profile
section.
22
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 5 Configuration of the system
Reference [%]
Variable name:
nviRefPcnt SNVT_lev_percent Min. Max. Resolution:
-163.840 % +163.830 % 0.005 %
This variable sends the speed reference to the frequency converter. It represents a percentage of the reference range of the frequency converter.
In closed loop operation the reference is interpreted as the setpoint.
Reference [Hz]
Variable name:
nviRefHz SNVT_freq_hz Min.: Max.: Resulution:
0.0 Hz 6,553.5 Hz 0.1 Hz
This variable sends the speed reference to the frequency converter in Hz, in open loop mode.
In closed loop mode it is used as the Set-point.
Closed Loop Set-point 1-3
Variable name:
nviSetpoint1-3 SNVT_lev_percent Min.: Max.: Resulution:
-163.840 % 163.830 % 0.005 %
SNVT type:
SNVT type:
SNVT type:
Value:
Value:
Value:
5
This variable sends up to 3 different set-points to the frequency converter via the bus.
NB!
Please refer to section
Bus Feedback 1-3
Variable name:
nviFeedback1-3 SNVT_lev_percent Min.: Max.: Resulution:
-163.840 % 163.830 % 0.005 %
This variable sends up to 3 different feedback signals to the frequency converter via the bus.
NB!
For more information on how to manage multiple set-points and feedback sources, please refer to
MG.11.BX.YY
.
SNVT type:
Reference Handling
for more information
Value:
VLT HVAC Drive Programing Guide
MG.11.E2.02 - VLT® is a registered Danfoss trademark
23
5 Configuration of the system VLT® FC 100 LonWorks
Digital / Relay Outputs
5
Variable name:
nviDigitOutput SNVT_state_64 Boolean 1 bit x 64
This variable controls the state of the digital outputs and relays.
A logical 1, indicates that the output is On or active.
A logical 0, indicates that the output is Off or inactive.
Bit 0 CC Digital Output Terminal 27
Bit 1 CC Digital Output Terminal 29
Bit 2 GPIO Digital Output Terminal X30/6
Bit 3 GPIO Digital Output Terminal X30/7
Bit 4 CC Relay 1 output terminal
Bit 5 CC Relay 2 output terminal
Bit 6 Option B Relay 1 output terminal
Bit 7 Option B Relay 2 output terminal
Bit 8 Option B Relay 3 output terminal
Bit 9-63 Reserved for future terminals
Analog Output (42)
Variable name:
nviAnOut1 SNVT_lev_percent Min.: Max.: Resulution:
0 % 100 % 0.01 %
SNVT type:
SNVT type:
State:
Value:
This variable controls the analog output 42, 0-20 mA or 4-20 mA.
In order to control output 42 via LonWorks, par. 6-50
[139] Bus ctrl. 0-20 mA
[140] Bus crtl. 4-20 mA
[141] Bus crtl. 0-20 mA Timeout
[142] Bus crtl. 4-20 mA Timeout
Function:
Bus crtl. 0-20 mA [139]: The output is controlled via bus. In the event of bus timeout, the output level remains unchanged.
Bus crtl. 4-20 mA [140]: The output is controlled via bus. In the event of bus timeout, the output level remains unchanged.
Bus crtl. 0-20 mA [141]: The output is controlled via bus. In the event of bus timeout, the output level is set to the predefined level in par. 6-54
42 Output Timeout Preset
Bus crtl. 4-20 mA [142]: The output is controlled via bus. In the event of bus timeout, the output level is set to the predefined level in par. 6-54
42 Output Timeout Preset
.
.
Terminal 42 Output
must be set to one of the following options:
Terminal
Terminal
24
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 5 Configuration of the system
Analog Output (X30 / 8)
Variable name:
nvi101AnOut1 SNVT_lev_percent Min.: Max.: Resulution:
0 % 100 % 0.01 %
NB!
This output variable applies only if the General Purpose I/O option is installed in the frequency converter.
This variable controls the X30/8 analog output on the General Purpose I/O option 0-20 mA or 4-20 mA.
In order to control output X30/8 via LonWorks, par. 6-60
[139] Bus ctrl. 0-20 mA
[140] Bus crtl. 4-20 mA
[141] Bus crtl. 0-20 mA Timeout
[142] Bus crtl. 4-20 mA Timeout
Function:
Bus crtl. 0-20 mA [139]: The output is controlled via bus. In the event of bus timeout, the output level remains unchanged.
Bus crtl. 4-20 mA [140]: The output is controlled via bus. In the event of bus timeout, the output level remains unchanged.
Bus crtl. 0-20 mA [141]: The output is controlled via bus. In the event of bus timeout, the output level is set to the predefined level in par. 6-64
X30/8 Output Timeout Preset
Bus crtl. 4-20 mA [142]: The output is controlled via bus. In the event of bus timeout, the output level is set to the predefined level in par. 6-64
X30/8 Output Timeout Preset
.
.
SNVT type:
Value:
Terminal X30/8 Output
must be set to one of the following options:
5
Terminal
Terminal
Analog Output (X42 / 7)
Variable name:
nvi109AnOut1 SNVT_lev_percent Min.: Max.: Resulution:
0 % 100 % 0.01 %
Analog Output (X42 / 9)
Variable name:
nvi109AnOut2 SNVT_lev_percent Min.: Max.: Resulution:
0 % 100 % 0.01 %
Analog Output (X42 /11)
Variable name: SNVT type: Value:
nvi109AnOut3 SNVT_lev_percent Min.: Max.: Resulution:
0 % 100 % 0.01 %
SNVT type:
SNVT type:
Value:
Value:
MG.11.E2.02 - VLT® is a registered Danfoss trademark
25
5 Configuration of the system VLT® FC 100 LonWorks
5
These variables contain the value allocated to the analog output terminal X42/7-11 of the
commissioning tool.
NB!
This variable is available only if the Analog I/O option (MCB 109) has been installed.
Setting of RTC
Variable name:
nviTimeStamp SNVT_time_stamp Year Month Day Hour Minute Second
2000 -3000 0 - 12 0 - 31 0 - 23 0 - 59 0 - 59
Use this input to set the built-in Real Time Clock.
ECB Option Mode
Variable name:
nviECBMode SNVT_state Boolean 1 bit x 16
SNVT type:
SNVT type:
Analog I/O option
Field:
State:
. The variable type is changeable with the
Controls the operation mode of the ECB option. The binary value of this variable is mapped directly into par. 31-00
[0] Drive
[1] Bypass
ECB Remote By-pass Activation
Variable name:
nviECBActivation SNVT_state Boolean 1 bit x 16
Controls the remote activation of the ECB option.
The binary value of this variable is mapped directly into par. 31-90.
[0] Disabled
[1] Enabled
NB!
This input variable applies only if the ECB option is installed in the frequency converter.
Parameter Access Command
SNVT type:
State:
Bypass Mode
.
Variable name:
nviParamRequest SNVT_param_request
These input variables are used for for frequency converter parameter access.
For more information on parameter access, please refer to
26
SNVT type:
How to Access FC 100 Parameters
MG.11.E2.02 - VLT® is a registered Danfoss trademark
Value:
section.
VLT® FC 100 LonWorks 5 Configuration of the system
5.2.2 Network variable description - FC VSD Profile - output
Status Word
Variable name: SNVT type: State:
nvoStatusWord SNVT_state Boolean 1 bit x 16
This variable is a 16-bit word providing status information on the frequency converter. For more information on the status word, please refer to the
Danfoss FC Control Profile
section.
NB!
Please note that in the representation of the Status Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.
5
Drive Output [%]
Variable name:
nvoOutputPcnt SNVT_lev_percent Min. Max. Resolution:
-163.840 % +163.840 % 0.005 %
In open loop operation, this variable contains the frequency converter output frequency in percentage, within the reference range.
In closed loop operation, this variable contains the frequency converter feedback signal, within the reference range.
Drive Output [Hz]
Variable name:
nvoOutputHz SNVT_freq_hz Min. Max. Resolution:
0 Hz 6,500 Hz 1 Hz
This variable displays the actual output of the frequency converter motor frequency in Hz.
kWh Counter [kWh]
Variable name:
nvoDrvEnrg SNVT_elec_kwh_l Min. Max. Resolution:
0 kWh 219,748,364.8 kWh 1 kWh
SNVT type:
SNVT type:
SNVT type:
Value:
Value:
Value:
This variable contains the power consumption of the motor in kWh measured as a mean value over a one hour period.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
27
5 Configuration of the system VLT® FC 100 LonWorks
DC Link Voltage [V]
5
Variable name:
nvoDCVoltage SNVT_volt Min. Max. Resolution:
0 V 10,000 V 0.1 V
This variable contains the measured Dc-link voltage. The value is filtered and therefore may be delayed with up to 1.3 seconds before a voltage change
is reflected in the output variable.
Motor Thermal [%]
Variable name:
nvoTempMrt SNVT_lev_cont Min. Max. Resolution:
0 % 100 % 0.5 %
This variable contains the calculated / estimated thermal load on the motor.
The cut-out limit is at 100%.
Inverter Thermal [%]
Variable name:
nvoTempInvrtr SNVT_lev_cont Min. Max. Resolution:
0 % 100 % 0.5 %
SNVT type:
SNVT type:
SNVT type:
Value:
Value:
Value:
This variable contains the percentage thermal load of the inverters.
The cut-out limit is at 100%.
Closed Loop Feedback
Variable name:
nvoFeedback SNVT_count_inc_f Min. Max. Resolution:
0 % 100 % 0.5 %
This variable contains the summerized amount of network feedback in closed loop mode.
Fanbelt broken
Variable name:
nvoBrokenbelt SNVT_switch 0 (False) Any Fanbelt not broken
1 (True) Any Fanbelt broken
This variable indicates whether the fanbelt is intact or broken (indicated by bit 8 in Warning Word 2).
SNVT type:
SNVT type:
Value:
State: Value: Command:
28
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 5 Configuration of the system
Alarm Flag
Variable name:
nvoAlarm SNVT_switch 0 (False) 0 No alarm(s) present
1 (True) 100 Alarm(s) present
This variable indicates whether any alarm is present.
Warning Flag
Variable name:
nvoWarning SNVT_switch 0 (False) 0 No warning(s) present
1 (True) 100 Warning(s) present
This variable indicates whether any warning is present.
Alarm Word
Variable name:
nvoAlarmword SNVT_state_64 Boolean 1 bit x 64
This variable contains the complete alarm word.
For more detailed information on the Alarm Word, please refer to the
SNVT type:
SNVT type:
SNVT type:
State: Value: Command:
State: Value: Command:
State:
Troubleshooting
section of this manual.
5
NB!
Please note that in the representation of the Alarm Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.
Warning Word
Variable name:
nvoWarningword SNVT_state_64 Boolean 1 bit x 64
This variable contains the complete warning word.
For more detailed information on the Warning Word, please refer to the
NB!
Please note that in the representation of the Warning Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the far left.
SNVT type:
Troubleshooting
State:
section of this manual.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
29
5 Configuration of the system VLT® FC 100 LonWorks
Extended Status Word
5
Variable name:
nvoExtendedStatusword SNVT_state_64 Boolean 1 bit x 64
This variable contains the complete extended status word.
For more detailed information on the Extended Status Word, please refer to the
NB!
Please note that in the representation of the Extended Status Word in the LonMaker Browser, the Least Significant Bit (LSB) is to the
far left.
Digital Inputs
Variable name:
nvoDigitInput SNVT_state_64 Boolean 1 bit x 64
This variable contains the status of the digital inputs.
A logical 1, indicates that the input is On or active.
A logical 0, indicates that the input is Off or inactive.
SNVT type:
SNVT type:
Troubleshooting
State:
section of this manual.
State:
Bit 0 Digital Input Terminal 33
Bit 1 Digital Input Terminal 32
Bit 2 Digital Input Terminal 29
Bit 3 Digital Input Terminal 27
Bit 4 Digital Input Terminal 19
Bit 5 Digital Input Terminal 18
Bit 6 Reserved for future terminals
Bit 7 Digital Input GP I/O Terminal X30/2
Bit 8 Digital Input GP I/O Terminal X30/3
Bit 9 Digital Input GP I/O Terminal X30/4
Bit 10-63 Reserved for future terminals
Analog Input (53)
Variable name:
nvoAnIn1 Changeable Min. Max. Resolution:
This variable contains the value allocated to the analog input terminal 53.
This terminal can either be configured as a voltage input (0-10 V) or as a current input (0-20 mA), depending on the setting of switch S 201. The variable
type is changeable with the commissioning tool or LNS Plug-in in order to match the appropriate unit.
SNVT type:
SNVT_volt 0 V 10 V 0.1 V
SNVT_amp_mil 0 mA 20 mA 0.1 mA
SNVT_lev_percent 0 % 100 % 0,1 %
Value:
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V/mA to par. 6-11
High Current
30
MG.11.E2.02 - VLT® is a registered Danfoss trademark
Terminal 53 High Voltage
or par. 6-13
Terminal 53
VLT® FC 100 LonWorks 5 Configuration of the system
Analog Input (54)
Variable name:
nvoAnIn1 Changeable Min. Max. Resolution:
This variable contains the value allocated to the analog input terminal 54.
This terminal can either be configured as a voltage input (0-10 V) or as a current input (0-20 mA), depending on the setting of switch S 202. The variable
type is changeable with the commissioning tool in order to match the appropriate unit.
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V/mA to par. 6-21
SNVT type:
SNVT_volt 0 V 10 V 0.1 V
SNVT_amp_mil 0 mA 20 mA 0.1 mA
SNVT_lev_percent 0 % 100 % 0,1 %
Value:
Terminal 54 High Voltage
or par. 6-23
Terminal 54
High Current
Analog Input (X30/11)
Variable name:
nvo101AnIn1 Changeable Min. Max. Resolution:
SNVT_volt 0 V 10 V 0.1 V
This variable contains the value allocated to the analog input terminal X30/11 of the
SNVT type:
SNVT_lev_percent 0 % 100 % 0,1 %
Value:
General Purpose I/O option, MCB101
.
5
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V to par. 6-31
NB!
This variable is available only if the General Purpose I/O option (MCB101) has been installed.
Analog Input (X30/12)
Variable name:
nvo101AnIn2 Changeable Min. Max. Resolution:
SNVT_volt 0 V 10 V 0.1 V
This variable contains the value allocated to the analog input terminal X30/12 of the
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V to par. 6-41
NB!
This variable is available only if the General Purpose I/O option (MCB101) has been installed.
SNVT type:
SNVT_lev_percent 0 % 100 % 0,1 %
Value:
General Purpose I/O option, MCB101
Terminal X30/11 High Voltage
Terminal X30/12 High Voltage
.
.
.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
31
5 Configuration of the system VLT® FC 100 LonWorks
Analog Input (X42/1)
5
Variable name: nvo109AnIn1 Changeable Min. Max. Resolution:
Analog Input (X42/3)
Variable name: nvo109AnIn2 Changeable Min. Max. Resolution:
Analog Input (X42/5)
Variable name: nvo109AnIn3 Changeable Min. Max. Resolution:
SNVT type:
SNVT_volt 0 V 10 V 0.1 V
SNVT_temp_p -273.15 °C 327.66 °C 0.01 °C
SNVT_lev_percent 0 % 100 % 0,1 %
SNVT type:
SNVT_volt 0 V 10 V 0.1 V
SNVT_temp_p -273.15 °C 327.66 °C 0.01 °C
SNVT_lev_percent 0 % 100 % 0,1 %
SNVT type:
SNVT_volt 0 V 10 V 0.1 V
SNVT_temp_p -273.15 °C 327.66 °C 0.01 °C
SNVT_lev_percent 0 % 100 % 0,1 %
Value:
Value:
Value:
These variables contain the value allocated to the analog input terminal X42/1-5 of the
the commissioning tool.
NB!
This variable is available only if the Analog I/O option (MCB109) has been installed.
Analog I/O option, MCB109
. The variable type is changeable with
32
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 5 Configuration of the system
ECB Option Status
Variable name:
nvoECBStatus SNVT_state Boolean 1 bit x 16
This variable displays the current status of the ECB option.
Bit 0 Test Mode
Bit 1 Drive Mode
Bit 2 Automatic By-pass Mode
Bit 3 By-pass Mode
Bit 4 Reserved
Bit 5 Motor Running from By-pass/Drive
Bit 6 Overload Trip
Bit 7 M2 Contactor Fault
Bit 8 M3 Contactor Fault
Bit 9 External Interlock
Bit 10 Manual By-pass Override
NB!
These variables are available only if the
SNVT type:
Electronic Control By-pass option
State:
(ECB) has been installed.
5
Parameter Access Response
Variable name: SNVT type:
nvoParamResponse UNVT_param_response
This output variable is used for the frequency converter access.
A special UNVT has been defined for this variable.
For more information on parameter access, please refer to the
How to Access FC 100 Parameters
section.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
33
5
5 Configuration of the system VLT® FC 100 LonWorks
5.3 VSD 6010 Profile
5.3.1 Introduction
The
Variable Speed Drive 6010
It describes how to control a variable speed frequency converter.
For example, an air handling unit controller that sends messages to facilitate control of the start/stop and speed reference of the VSD. The VSD will deliver
messages such as the actual frequency converter speed and output current to the controller, operating interfaces and energy management systems.
profile is a LonMark standardized functional profile.
5.3.2 Input Variables
Variable function Variable name SNVT type Profile FC 100 parameter
Drive speed setpoint nviDrvSpeedStpt SNVT_switch VSD 6010 CTW / Reference
5.3.3 Output Variables
Variable function Variable name SNVT type Profile FC 100 parameter
Drive speed nvoDrvSpeed SNVT_lev_percent VSD 6010 16-05
Output current nvoDrvCurnt SNVT_amp VSD 6010 16-14
Output voltage nvoDrvVolt SNVT_volt VSD 6010 16-12
Output power nvoDrvPwr SNVT_power_kilo VSD 6010 16-10
Running hours nvoDrvRunHours SNVT_time_hour VSD 6010 15-01
34
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 5 Configuration of the system
5.3.4 Configuration Properties (nci)
Variable function Variable name SNVT type Profile
Max. motor speed [%] nciMaxSpeed SNVT_lev_percent VSD 6010 4-13
Min. motor speed [%] nciMinSpeed SNVT_lev_percent VSD 6010 4-11
Nom. motor speed [RPM] nciNmlSpeed SNVT_rpm VSD 6010 1-25
Nom. motor frequency [Hz] nciNmlFreq SNVT_freq_hz VSD 6010 1-23
Min. ramp-up time [s] nciRampUpTime SNVT_time_sec VSD 6010 3-41
Min. ramp-down time [s] nciRampDownTime SNVT_time_sec VSD 6010 3-42
Heartbeat time [s] nciSndHrtBt SNVT_time_sec VSD 6010 -
A range of network configuration variables (SCPT's) is available for configuration of the frequency converter parameters. These parameters require setting
only once, usually following installation.
NB!
Please note that the settings written to configuration properties (nci's) will be stored in the non-volatile memory. Continuous writing
to configuration properties may damage the non-volatile memory.
FC 100 pa-
rameter
5.4 Network Variable Description - VSD Profile - input
5.4.1 Frequency Converter Speed Setpoint
5
Variable name: SNVT type: State: Value: Command:
nviDrvSpeedStpt SNVT_switch 0 (False) Any Stop
1 (True) 0 Running 0 %
This input variable provides start / stop control and a speed reference.
1 (True) 1-200 Running 0.5 to 100 %
1 (True) 201-255 Running 100 %
0xFF (default) Any AUTO (invalid, no action)
MG.11.E2.02 - VLT® is a registered Danfoss trademark
35
5 Configuration of the system VLT® FC 100 LonWorks
5.5 Network Variable Description - VSD Profile - Output
5.5.1 Drive Speed
5
Variable name:
nvoDrvSpeed SNVT_lev_percent Min: Max: Resolution:
-163.840 % +163.830 % 0.005 %
This variable contains the frequency converter speed as a percentage of the nominal speed.
SNVT type:
Value:
5.5.2 Output Current
Variable name:
nvoDrvCurnt SNVT_amp Min: Max: Resolution:
0 A 3,276.6 A 0.1 A
This variable contains the frequency converter output current in ampere measured as a mean value, IRMS.
The value is filtered and therefore approximately 1.3 seconds delayed before a current change is reflected in the output variable.
SNVT type:
Value:
5.5.3 Output Voltage
Variable name:
nvoDrvVolt SNVT_volt Min: Max: Resolution:
0 V 3,276.6 V 0.1 V
SNVT type:
Value:
This variable contains the frequency converter output voltage.
5.5.4 Output Power
Variable name:
nvoDrvPwr SNVT_power_kilo Min: Max: Resolution:
0 kW 6,554.4 kW 0.1 kW
This variable contains the frequency converter output power in kW, calculated on the basis of the actual motor voltage and current.
The value is filtered and therefore approximately 1.3 seconds delayed before a power change is reflected in the output variable.
SNVT type:
Value:
5.5.5 Running Hours
Variable name:
nvoDrvRunHours SNVT_time_hour Min: Max: Resolution:
0 hr 65,534 hr 1 hr
This variable contains the total running hours of the motor.
SNVT type:
Value:
36
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 5 Configuration of the system
5.6 Network Variable Description - VSD Profile - Configuration
5.6.1 Max Motor Speed [%]
Variable name:
nciMaxSpeed SNVT_lev_percent 100 % 0 % 163.830 %
This variable configures the maximum motor speed in % and associates it with par. 4-13
The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNmlSpeed) configuration value.
For more information on reference scaling, please refer to the
parameter access command.
SNVT type:
Default value: Min value: Max value:
How to Control the FC 100
Motor Speed High Limit [RPM]
section. If a value higher than 163.830% is requested, use the
(par. 4-14 in Hz mode).
5.6.2 Min Motor Speed [%]
Variable name:
nciMinSpeed SNVT_lev_percent 0 % 0 % 163.830 %
This variable configures the minimum motor speed in % and associates it with par. 4-11
The value is entered as a percent of nominal speed, as defined by the Nominal Speed (nciNmlSpeed) configuration value.
For more information on reference scaling, please refer to the
SNVT type:
Default value: Min value: Max value:
How to Control the FC 100
Motor Speed Low Limit [RPM]
section.
(par. 4-12 in Hz mode).
5.6.3 Nom Motor Speed [RPM]
Variable name:
nciNmlSpeed SNVT_rpm 1420 RPM 10 RPM 65,534 RPM
SNVT type:
Default value: Min value: Max value:
5
This variable configures the nominal motor speed in RPM and associates it with par. 1-25
NB!
Please note that this variable can be adjusted only while the frequency converter is stopped.
If a value lower than 10 RPM is entered, nciNmlSpeed will be set to 10 RPM.
Motor Nominal Speed
.
5.6.4 Nominal Motor Frequency [Hz]
Variable name:
nciNmlFreq SNVT_freq_hz 50 Hz 20 Hz 100 Hz
This variable configures the nominal motor frequency and associates it with par. 1-23
NB!
Please note that this variable can be adjusted only while the frequency converter is stopped.
If a value lower than 20 Hz is entered, nciNmlFreq will be set to 20 Hz.
SNVT type:
Default value: Min value: Max value:
Motor Frequency
.
MG.11.E2.02 - VLT® is a registered Danfoss trademark
37
5 Configuration of the system VLT® FC 100 LonWorks
5.6.5 Min Ramp-up Time [s]
5
Variable name:
nciRampUpTime SNVT_time_sec 10 s 1 s 3,600 s
This variable configures the Ramp 1 ramp-up time and associates it with par. 3-41
SNVT type:
Default value: Min value: Max value:
Ramp 1 Ramp Up Time
.
5.6.6 Min Ramp-down Time [s]
Variable name:
nciRampDownTime SNVT_time_sec 10 s 1 s 3,600 s
This variable configures the Ramp 1 ramp-down time and compares it with par. 3-42
SNVT type:
Default value: Min value: Max value:
Ramp 1 Ramp Down Time
.
5.6.7 Heartbeat Time [s]
Variable name:
nciSndHrtBt SNVT_time_sec 0 s 0 s 6,553.4 s
This variable configures a heartbeat timer to send the following variables:
nvoDrvCurnt
nvoDrvSpeed
nvoDrvVolt
nvoDrvPwr
Setting the timer to 0.0 disables the timer.
SNVT type:
Default value: Min value: Ma x val ue :
Heartbeat timers have the purpose of sending out heartbeat signals containing specific data, enabling management systems to prove that the node is
present on the network and working correctly. Only bound variables will be transmitted.
38
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 5 Configuration of the system
5.7 Node Object
5.7.1 Node Object
These variables are used for controlling all functional blocks via the com-
missioning tool.
5.7.2 Object Request
Variable name: SNVT type: Supported functions: Description:
nviRequest SNVT_obj_request RQ_Normal Returns the specified functional block to normal operation.
RQ_Update_Status Requests the status of the specified functional block.
RQ_Report_Mask
RQ_Disabled
RQ_Enable
Requests a status mask reporting the status bits that are supported
by the specified functional block.
Requests the specified functional block to change to the disabled
state. In the disabled state, output network variables belonging to
the functional block are not propagated within the network.
Requests the specified functional block to change to the enabled
state. In the enabled state, output network variables belonging to
the functional block are propagated within the network as defined
by the functional block.
5.7.3 Object Response
Variable name: SNVT type: Description:
nvoStatus SNVT_object_status
This output network variable reports the status for any functional block on a device. It is also used to report
the status of the entire device and all functional blocks on the device.
5
5.7.4 Max. Send Time (Heartbeat)
Variable name:
nciMaxStsSendT SNVT_elapsed_tm 00:0:0:0 00:0:0:0 017:59:59:999
This variable configures a timer to send the nvoStatus object but only if bound to an input variable.
Maximum is '0 17:59:59:999' (0 days, 17 hours, 59 minutes, 59 seconds and 999 milliseconds).
Setting the timer to '0 0:0:0:0' disables it.
Network timer functions monitor node presence and control behaviour in the event of network problems occurring.
SNVT type:
Default value: Min value: Max value:
MG.11.E2.02 - VLT® is a registered Danfoss trademark
39
5
5 Configuration of the system VLT® FC 100 LonWorks
5.8 Network Timer Functions
5.8.1 Control Word Time-out Function
par.8-03
Control Timeout Time
controller node.
If a valid control word has not been received within the time specified in par. 8-03, the action specified in par. 8-04 will be performed. The default action
is OFF (no action).
The range of par. 8-03 is: 0.1 to 18,000 seconds (or 5 hours).
An update of the control word is triggered by the following SNVT's:
nviStartStop
•nviResetFault
•nviControlword
nviDrvSpeedStpt
•nviRefPcnt
•nviRefHz
nviFeedback 1,2,3
•nviSetPoint 1,2,3
and par.8-04
Control Timeout Function
provide a means for the frequency converter to control communication to a
5.8.2 Min. Send Time (Inhibit Timer)
Variable name:
nciMinSendT SNVT_elapsed_tm 00:0:0:500 0 0:0:0:100 0 0:01:05:535
Variable used for limiting bus traffic by setting a minimum sending timer (inhibit timer).
Applies for all output variables.
Format: Days Hours:Minutes:Seconds:Milliseconds.
SNVT type:
Default value: Min value: Max value:
40
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 6 How to control the Frequency Converter
6 How to control the Frequency Converter
6.1 How to Control the FC 100
6.1.1 Reference Handling
Select the frequency converter configuration mode in par. 1-00
[0] Open Loop
[3] Closed Loop
Configuration Mode
.
6.1.2 Open Loop
For open loop operation, the reference represents the desired output speed of the frequency converter.
The speed reference value is transmitted to the frequency converter as a relative value in %.
6
6.1.3 Closed Loop
In closed loop operation the feedback/reference is scaled from 1 to par. 20-14
NB!
Please refer to the
All references provided to the frequency converter are added to the total reference value.
If a reference is to be controlled by the LonWorks bus only, please ensure that all other reference inputs are zero.
This means that digital and analog input terminals should not be used for reference signals.
The default setting (0%) should be maintained for preset references in par. 3-10
Troubleshooting
section to see an example of reference scaling.
Maximum Reference/Feedb.
Preset Reference
.
2
MG.11.E2.02 - VLT® is a registered Danfoss trademark
41
6
6 How to control the Frequency Converter VLT® FC 100 LonWorks
6.2 Danfoss FC Control Profile
6.2.1 FC Control Profile
Control Word According to FC Profile (Par. 8-10 set to
Bit Bit value=0 Bit value=1
00 Reference value External selection lsb
01 Reference value External selection msb
02 DC brake Ramp
03 Coasting No coasting
04 Quick stop Ramp
05 Hold output freq. Use ramp
06 Ramp stop Start
07 No function Reset
08 No function Jog
09 Ramp 1 Ramp 2
10 Data invalid Data valid
11 No function Relay 01 active
12 No function Relay 04 active
13 Parameter set-up Selection lsb
14 Parameter set-up Selection msb
15 No function Reverse
FC Profile
)
6.2.2 Explanation of the Control Bits
Bits 00 and 01:
Bits 00 and 01 are used to choose between the four reference values,
which are pre-programmed in par. 3-10
with the following table:
Programmed ref. value Parameter Bit 01
1 3-10 [0] 0 0
2 3-10 [1] 0 1
3 3-10 [2] 1 0
4 3-10 [3] 1 1
NB!
In par.8-56
made to define how Bit 00/01 gates with the corre-
sponding function on the digital inputs.
Bit 02, DC brake:
Bit 02 set to [0] leads to DC braking and stop of the motor. Braking cur-
rent and duration are set in par. 2-01
Braking Time
Bit 02 set to [1] leads to ramping.
Bit 03, Coasting:
Bit 03 set to [0] causes the frequency converter to immediately release
of the motor (the output transistors are "shut off"), so that it coasts to a
standstill.
.
Preset Reference Select
Preset Reference
DC Brake Current
in accordance
Bit 00
, a selection is
and par. 2-02
DC
Bit 03 set to [1] enables the frequency converter to start the motor if
other starting conditions have been fulfilled.
NB!
In par.8-50
fine how Bit 03 gates with the corresponding function
on a digital input.
Bit 04, Quick Stop:
Bit 04 set to [0] causes a stop in which the motor speed is ramped down
to stop via par. 3-81
Bit 05, Hold output frequency:
Bit 05 set to [0] causes the present output frequency (Hz) to freeze. The
frozen output frequency can then be changed only by means of the digital
inputs set by par. 5-10 to 5-15, programmed to [Speed up] or [Speed
down].
NB!
If [Freeze output] is active, the frequency converter
can only be stopped by the following:
Coasting Select
Quick Stop Ramp Time
Bit 03 Coasting stop
Bit 02 DC braking
Digital input (par. 5-10 to 5-15) programmed
to DC braking, Coasting stop or Reset and
coasting stop.
, a selection is made to de-
.
42
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 6 How to control the Frequency Converter
Bit 06, Ramp stop/start:
Bit 06 set to [0] causes a stop, in which the motor speed is ramped down
to stop via the selected ramp down parameter.
Bit 06 set to [1] permits the frequency converter to start the motor, if
other starting conditions have been fulfilled.
NB!
In par.8-53
how Bit 06 Ramp stop/start gates with the correspond-
ing function on a digital input.
Bit 07, Reset:
Bit 07 set to [0] means no reset.
Bit 07 set to [1] resets a trip. Reset is activated on the leading edge of
the signal, i.e. when changing from logic ‘0’ to logic ‘1’.
Bit 08, Jog:
Bit 08 set to [1] causes the output frequency to be determined by
par. 3-19
Bit 09, Selection of ramp:
Bit 09 set to [0] means that ramp 1 is active (par. 3-40 to 3-47).
Bit 09 set to [1] means that ramp 2 (par. 3-50 to 3-57) is active.
Bit 10, Data not valid / Data valid:
This bit tells the frequency converter whether the control word is to be
used or ignored. Bit 10 set to [0] causes the control word to be ignored.
Bit 10 set to [1] causes the control word to be used.
The control word is always contained in the telegram, regardless of which
type of telegram is used, so this function is useful for ‘turning off’ the
control word when not required for updating or for reading parameters.
Bit 11, Relay 01:
Bit 11 set to [0] means that Relay is not activated.
Bit 11 set to [1] activates Relay 01, provided
been chosen in par. 5-40
Jog Speed [RPM]
Start Select
.
Function Relay
, a selection is made to define
Control word bit 11
.
[36] has
Bit 12, Relay 04:
Bit 12 set to [0] means that Relay 04 has not been activated.
Bit 12 set to [1] activates Relay 04, provided
been chosen in par. 5-40
Bit 13 and 14, Selection of set-up:
Bits 13 and 14 are used to select one of four menu set-ups according to
the following table:
Set-up Bit 14 Bit 13
1 0 0
20 1
3 1 0
41 1
The function is only possible when Multi-Set-up [9] is selected in
par. 0-10
Bit 15, Reverse:
Bit 15 set to [0] causes no reversing.
Bit 15 set to [1] causes reversing.
Note: par. 4-10
Active Set-up
Motor Speed Direction
Function Relay
.
NB!
In par.8-55
how Bit 13/14 gates with the corresponding function
on the digital inputs.
Set-up Select
Control word bit 12
.
, a selection is made to define
determines if reversing is possible.
[37] has
6
6.2.3 Status Word According to FC Profile (STW)
Parameter 8-10 set to [FC profile]
Bit Bit value=0 Bit value=1
00 Control not ready Control ready
01 Drive not ready Drive ready
02 Coasting Enable
03 No error Trip
04 No error Error (no trip)
05 Reserved -
06 No error Trip lock
07 No warning Warning
08 Speed # reference Speed = reference
09 Local operation Bus control
10
11 No operation In operation
12 Brake ok Brake warning or failure
13 Voltage ok Voltage exceeded
14 Torque ok Torque exceeded
15 Timer ok Timer exceeded
Out of frequency
limit
Frequency
limit ok
MG.11.E2.02 - VLT® is a registered Danfoss trademark
43
6 How to control the Frequency Converter VLT® FC 100 LonWorks
6.2.4 Explanation of the Status Bits
6
Bit 00, Control not ready / ready:
Bit 00 set to [0] means that the frequency converter has tripped.
Bit 00 set to [1] means that the frequency converter controls are ready,
but that the power component is not necessarily receiving any power
supply (in the event of external 24 V supply to controls).
Bit 01, Drive ready:
Bit 01 set to [1] means that the frequency converter is ready for opera-
tion, but it is receiving an active coasting command via the digital inputs
or via serial communication.
Bit 02, Coasting stop:
Bit 02 set to [0] means that the frequency converter has released the
motor.
Bit 02 set to [1] means that the frequency converter can start the motor
when a start command is given.
Bit 03, No error / trip:
Bit 03 set to [0] means that the frequency converter is not in fault mode.
Bit 03set to [1] means that the frequency converter is tripped and that a
reset signal is required to re-establish operation.
Bit 04, No error / error (no trip):
Bit 04 set to [0] means that the frequency converter is not in fault mode.
Bit 04 set to [1] means that there is a frequency converter error but no
trip.
Bit 05, Not used:
Bit 05 is not used in the status word.
Bit 06, No error / trip lock:
Bit 06 set to [0] means that the frequency converter is not in fault mode.
Bit 06 set to [1] means that the frequency converter is tripped and locked.
Bit 07, No warning / warning:
Bit 07 set to [0] means that there are no warnings.
Bit 07 set to [1] means that a warning has occurred.
Bit 08, Speed # reference / speed = reference:
Bit 08 set to [0] means that the motor is running, but that the present
speed is different from the preset speed reference. For example, this
might occur while the speed is being ramped up/down during start/stop.
Bit 08 set to [1] means that the present motor speed matches the preset
speed reference.
Bit 09, Local operation / bus control:
Bit 09 set to [0] means that [STOP/RESET] is activated on the control unit
or that Local [2] control in par. 3-13
possible to control the frequency converter via serial communication.
Bit 09 set to [1] means that it is possible to control the frequency con-
verter via the fieldbus / serial communication interface.
Bit 10, Out of frequency limit:
Bit 10 set to [0] enables the output frequency to reach the value in
par. 4-11
Limit [RPM]
Bit 10 set to [1] means that the output frequency is within the defined
limits.
Bit 11, No operation / in operation:
Bit 11 set to [0] means that the motor is not running.
Motor Speed Low Limit [RPM]
.
Reference Site
or par. 4-13
is selected. It is not
Motor Speed High
Bit 11 set to [1] means that the frequency converter has received a start
signal or that the output frequency is greater than 0 Hz.
Bit 12, Brake OK / Brake warning or failure:
Bit 12 = [0] means that there is no brake warning or failure present.
Bit 12 = [1] means that the drive has stopped because of a brake warning
or failure.
Bit 13, Voltage OK / limit exceeded:
Bit 13 set to [0] means that there are no voltage warnings.
Bit 13 set to [1] means that the DC voltage in the frequency converter’s
intermediate circuit is too low or too high.
Bit 14, Torque OK / limit exceeded:
Bit 14 set to [0] means that the motor current is lower than the torque
limit selected in par. 4-18
Bit 14 set to [1] means that the torque limit in par. 4-18
has been exceeded.
Bit 15, Timer OK / limit exceeded:
Bit 15 = [0] means that the timers for motor thermal protection and VLT
thermal protection, respectively, have not exceeded 100%.
Bit 15 = [1] means that one of the timers has exceeded 100%.
Current Limit
.
Current Limit
44
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 7 How to access FC 100 parameters
7 How to access FC 100 parameters
7.1 User-defined Network Variables UNVT
7.1.1 UNVT Parameter structure
Two special User-defined Network Variables (UNVT) have been defined to enable access to FC 100 parameters via LonWorks:
Variable name: UNVT type:
nviParamRequest UNVT_param_request
nvoParamResponse UNVT_param_response
The parameter- or attribute request has the following structure:
UNVT_param_request
Field Range Type Size
Request
Par_number Parameter number Unsigned long 2 bytes
Subindex Subindex (0-255) Unsigned 1 byte
Value Parameter value Unsigned quad 4 bytes
1 = Read value
2 = Write value
Enum 1 byte
7
The parameter- or attribute response has the following structure:
UNVT_param_response
Field Range Type Size
0 = Error response
Response
Par_number Parameter number Unsigned long 2 bytes
Length Length of “value” field (0-27) Unsigned 1 byte
Value Parameter or parameter attribute value Unsigned 0-27 bytes
If an incorrect Read or Write request is encountered, an error message will be returned in the [Value] field, byte 0 and byte 3.
Error description: Error code in Value [0]: Error code in Value [3]:
Invalid request type 0xFF 1
Invalid parameter number 0xFF 2
Invalid data type 0xFF 3
No write access 0xFF 4
Exceed limits 0xFF 5
Invalid subindex 0xFF 6
Not array 0xFF 7
Only reset 0xFF 8
Not changeable 0xFF 9
Not in this mode 0xFF 10
No bus access 0xFF 11
Other error 0xFF 0xFE
1 = Read response
2 = Write response
Enum 1 byte
MG.11.E2.02 - VLT® is a registered Danfoss trademark
45
7
7 How to access FC 100 parameters VLT® FC 100 LonWorks
7.1.2 UNVT examples
Example: Read parameter 3-41
Ramp 1 Ramp-up Time
In the LonMaker browser, select the nviParamRequest and choose [Details].
130BA452.10
46
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 7 How to access FC 100 parameters
In the bottom window, select the function [READ_VALUE].
7
130BA451.10
MG.11.E2.02 - VLT® is a registered Danfoss trademark
47
7
7 How to access FC 100 parameters VLT® FC 100 LonWorks
In the [Field List:] under the section [par_number], enter the parameter number (in this example 3-41). If an indexed (array) parameter is accessed, the
[subindex] field must be filled-in.
The response may look like this:
Value [0] (1st byte) = 232
Value [1] (2nd byte) = 3
-meaning that the readout value of parameter 3-41 is: 232+(3x256) = 1000
Conversion index of par. 3-41 is: -2(0.01)
Ramp 1 Ramp-up Time = 1000x0.01 =
10 seconds
130BA454.10
48
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 8 Parameters
8 Parameters
8.1 Parameter list
8.1.1 Parameter list
Par. No. Parameter name: Default value: Range:
8-01 Control Site Dig. and control word [0] [0 - 2] - 5
8-02 Control Word Source FC Port [1] [0 - 4] - 5
8-03 Control Word Timeout Time 600 s 0.1 - 18000 1 7
8-04 Control Word Timeout Function Off [0] [0 - 10] - 5
8-05 End-of-timeout Function Hold set-up [0] [0 - 1] - 5
8-06 Reset Control Word Timeout Do not reset [0] [0 - 1] - 5
8-07 Diagnosis Trigger Disable [0] [0 - 3] - 5
8-10 Control Word Profile FC profile [0] [0 - x] - 5
8-50 Coasting Select Logic OR [3] [0 - 3] - 5
8-52 DC Brake Select Logic OR [3] [0 - 3] - 5
8-53 Start Select Logic OR [3] [0 - 3] - 5
8-54 Reversing Select Logic OR [3] [0 - 3] - 5
8-55 Set-up Select Logic OR [3] [0 - 3] - 5
8-56 Preset Reference Select Logic OR [3] [0 - 3] - 5
11-00 Neuron ID 00 00 00 00 00 00 - - 10
11-10 Drive Profile VSD 6010 [0] - - 5
11-15 Lon Warning Word 0 - - 6
11-18 LonWorks Revision [0, 10] - - 9
11-21 Store Data Values Off [0] [0 - 1] - 5
Conversion
type:
8.2 Parameter Group 8-**
Data type:
8
8-01 Control Site
Option: Function:
The setting in this parameter overrides the settings in par.8-50
Reference Select
[0] * Digital and ctrl.word Control by using both digital input and control word.
[1] Digital only Control by using digital inputs only.
[2] Controlword only Control by using control word only.
.
8-02 Control Source
Option: Function:
Select the source of the control word: one of two serial interfaces or four installed options. During
initial power-up, the frequency converter automatically sets this parameter to
detects a valid fieldbus option installed in slot A. If the option is removed, the frequency converter
detects a change in the configuration, sets par. 8-02
Port
, and the frequency converter then trips. If an option is installed after initial power-up, the
[2] FC USB
[1] Drive Port
[0] None
[1] FC Port
setting of par. 8-02
Alarm 67
Option Changed
Control Source
.
will not change but the frequency converter will trip and display:
Coasting Select
Control Source
to par.8-56
Option A
[3] if it
back to default setting
Preset
FC
MG.11.E2.02 - VLT® is a registered Danfoss trademark
49
8
8 Parameters VLT® FC 100 LonWorks
[2] USB Port
[3] * Option A
[4] Option B
[5] Option C0
[6] Option C1
NB!
This parameter cannot be adjusted while the motor is running.
8-03 Control Timeout Time
Range: Function:
60.0 s* [1.0 - 18000.0 s] Enter the maximum time expected to pass between the reception of two consecutive telegrams. If
this time is exceeded, it indicates that the serial communication has stopped. The function selected
in par.8-04
In LonWorks the following variables will trigger the Control Word Time parameter:
Control Timeout Function Control Time-out Function
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
will then be carried out.
8-04 Control Timeout Function
Option: Function:
Select the time-out function. The time-out function is activated when the control word fails to be
updated within the time period specified in par.8-03
after setting the N2 protocol.
[0] * Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
[7] Select setup 1
[8] Select setup 2
[9] Select setup 3
[10] Select setup 4
[20] N2 Override Release
In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par.8-03
Timeout Time
:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
Control Timeout Time
. Choice [20] only appears
Control
50
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 8 Parameters
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control word following a time-out. This parameter is active
only when par.8-04
Control Timeout Function
is set to [Set-up 1-4].
[0] Hold set-up Retains the set-up selected in par.8-04
8-06
Reset Control Timeout
[1] * Resume set-up Resumes the set-up active prior to the time-out.
toggles. Then the frequency converter resumes its original set-up.
Control Timeout Function
and displays a warning, until par.
8-06 Reset Control Timeout
Option: Function:
This parameter is active only when the choice
of-Timeout Function
[0] * Do not reset Retains the set-up specified in par.8-04
control time-out.
[1] Do reset Returns the frequency converter to the original set-up following a control word time-out. When the
value is set to
to the
Do not reset
.
Do reset
[1], the frequency converter performs the reset and then immediately reverts
[0] setting.
Hold set-up
Control Timeout Function
[0] has been selected in par.8-05
End-
, [Select setup 1-4] following a
8-07 Diagnosis Trigger
Option: Function:
This parameter has no function for LonWorks.
[0] * Disable
[1] Trigger on alarms
[2] Trigger alarm/warn.
8
8-10 Control Profile
Option: Function:
Select the interpretation of the control and status words corresponding to the installed fieldbus.
Only the selections valid for the fieldbus installed in slot A will be visible in the LCP display.
[0] * FC profile
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
[0] Digital input
[1] Bus Activates Start command via the serial communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals (digital input) and/or via the bus.
Option: Function:
[0] Digital Input
MG.11.E2.02 - VLT® is a registered Danfoss trademark
51
8 Parameters VLT® FC 100 LonWorks
[1] Bus
[2] Logic AND
[3] * Logic OR
NB!
This parameter is active only when par.8-01
Control Site
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via the fieldbus.
[0] Digital input
[1] Bus Activates Start command via the serial communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
is set to [0]
Digital and control word
.
8
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-53 Start Select
Option: Function:
Select control of the frequency converter start function via the terminals (digital input) and/or via
the fieldbus.
[0] Digital input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8-54 Reversing Select
Option: Function:
Select control of the frequency converter reverse function via the terminals (digital input) and/or
via the fieldbus.
[0] * Digital input Activates Reverse command via a digital input.
[1] Bus Activates Reverse command via the serial communication port or fieldbus option.
[2] Logic AND Activates Reverse command via the fieldbus/serial communication port, AND additionally via one of
the digital inputs.
[3] Logic OR Activates Reverse command via the fieldbus/serial communication port OR via one of the digital
inputs.
52
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 8 Parameters
NB!
This parameter is active only when par.8-01
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via
the fieldbus.
[0] Digital input Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial communication port or fieldbus option.
[2] Logic AND Activates the set-up selection via the fieldbus/serial communication port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activate the set-up selection via the fieldbus/serial communication port OR via one of the digital
inputs.
NB!
This parameter is active only when par.8-01
Control Site
Control Site
is set to [0]
is set to [0]
Digital and control word
Digital and control word
.
.
8-56 Preset Reference Select
Option: Function:
Select control of the frequency converter Preset Reference selection via the terminals (digital input)
and/or via the fieldbus.
[0] Digital input Activates Preset Reference selection via a digital input.
[1] Bus Activates Preset Reference selection via the serial communication port or fieldbus option.
[2] Logic AND Activates Preset Reference selection via the fieldbus/serial communication port, AND additionally
via one of the digital inputs.
[3] * Logic OR Activates the Preset Reference selection via the fieldbus/serial communication port OR via one of
the digital inputs.
NB!
This parameter is active only when par.8-01
Control Site
is set to [0]
Digital and control word
.
8
MG.11.E2.02 - VLT® is a registered Danfoss trademark
53
8
8 Parameters VLT® FC 100 LonWorks
8.3 Parameter Group 11
11-00 Neuron ID
Range: Function:
View the Neuron chip's unique Neuron ID number.
0 N/A* [0 - 0] View the Neuron chip's unique Neuron ID number.
11-10 Drive Profile
Option: Function:
This parameter allows selecting between LONMARK Functional Profiles.
[0] * VSD profile The Danfoss Profile and the Node Object are common for all profiles.
11-15 LON Warning Word
Range: Function:
0 N/A* [0 - FFFF ] This parameter contains the LON specific warnings.
Bit Status
0 Internal fault
1 Internal fault
2 Internal fault
3 Internal fault
4 Internal fault
5 Reserved
6 Reserved
7 Reserved
8 Reserved
9 Invalid type change for changeable types
10 Initialization error
11 Internal communication error
12 Software revision mismatch
13 Bus not active
14 Option not present
15 LON input (nvi/nci) exceeds limits
11-17 XIF Revision
Range: Function:
0 N/A* [0 - 0] This parameter contains the version of the external interface file on the Neuron C chip on the LON
option.
11-18 LonWorks Revision
Range: Function:
0 N/A* [0 - 0] This parameter contains the software version of the application program on the Neuron C chip on
the LON option.
11-21 Store Data Values
Option: Function:
This parameter is used to activate storing of data in non-volatile memory.
[0] * Off Store function is inactive.
[2] Store all setups
Stores all parameter values in the E
been stored.
2
PROM. The value returns to
Off
when all parameter values have
54
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 8 Parameters
8.4 Data Types Supported by FC 100
8.4.1 Object and Data Types Supported by FC 100
Data type:
3 Integer 16
4 Integer 32
5 Unsigned 8
6 Unsigned 16
7 Unsigned 32
9 Visible string
10 Byte string
33 Standardized value (16 bit)
35 Bit sequence
41 Byte
42 Word
Description:
8.4.2 Conversion Index
This number refers to a conversion figure used when writing or reading to parameters.
Conversion index: Conversion factor:
100 1
67 1 / 60
6 1000000
5 100000
4 10000
3 1000
2 100
110
0 1
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
-5 0.00001
-6 0.000001
8
MG.11.E2.02 - VLT® is a registered Danfoss trademark
55
9 Troubleshooting VLT® FC 100 LonWorks
9
56
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 9 Troubleshooting
9 Troubleshooting
9.1 Alarm-, Warning and Extended Status Word
9.1.1 Alarm and warning messages
General
There is a clear distinction between alarms and warnings. In the event of an alarm, the frequency converter will enter a fault condition. After the cause
for the alarm has been cleared, the master must acknowledge the alarm message in order to start operation of the frequency converter again. A warning,
on the other hand, may appear when a warning condition arises, then disappear when conditions return to normal without interfering with the process.
Alarm Word and Warning Word are shown on the display in Hex format. If there is more than one warning or alarm, a sum of all warnings or alarms will
be shown. Warning Word and Alarm Word are displayed in par. 16-90 to 16-95. For more information on the individual alarms and warnings, please refer
to:
VLT HVAC Drive Design Guide
Warnings
All warnings within the frequency converter are represented by a single bit within a Warning Word. A Warning Word is always an action parameter. Bit
status FALSE [0] means no warning, while bit status TRUE [1] means warning. Each bit status has a corresponding text string message. In addition to
the Warning Word message the master will also be notified via a change to bit 7 in the status word.
.
Alarms
Following an alarm message the frequency converter will enter a fault condition. Only after the fault has been rectified and the master has acknowledged
the alarm message by setting bit 3 in the Control Word, can the FC resume operation. All alarms within the FC are represented by a single bit within an
Alarm Word. An Alarm Word is always an action parameter. Bit status FALSE [0] means no alarm, while bit status TRUE [1] means alarm.
9
MG.11.E2.02 - VLT® is a registered Danfoss trademark
57
9 Troubleshooting VLT® FC 100 LonWorks
9.1.2 Alarm words
9
Alarm word, par. 16-90
Bit
(Hex)
00000001 Brake check
00000002 Power card over temperature
00000004 Earth fault
00000008 Ctrl. card over temperature
00000010 Control word timeout
00000020 Over current
00000040 Torque limit
00000080 Motor thermistor over temp.
00000100 Motor ETR over temperature
00000200 Inverter overloaded
00000400 DC link under voltage
00000800 DC link over voltage
00001000 Short circuit
00002000 Inrush fault
00004000 Mains phase loss
00008000 AMA not OK
00010000 Live zero error
00020000 Internal fault
00040000 Brake overload
00080000 Motor phase U is missing
00100000 Motor phase V is missing
00200000 Motor phase W is missing
00400000 Fieldbus fault
00800000 24V supply fault
01000000 Mains failure
02000000 1.8V supply fault
04000000 Brake resistor short circuit
08000000 Brake chopper fault
10000000 Option change
20000000 Drive initialized
40000000 Safe Stop
80000000 Not used
Alarm Word
Alarm Word (par. 16-90
Alarm Word
Alarm word 2, par. 16-91
)
(Hex)
00000001 Service Trip, read / Write
00000002 Reserved
00000004
00000008 Reserved
00000010 Reserved
00000020 No Flow
00000040 Dry Pump
00000080 End of Curve
00000100 Broken Belt
00000200 Not used
00000400 Not used
00000800 Reserved
00001000 Reserved
00002000 Reserved
00004000 Reserved
00008000 Reserved
00010000 Reserved
00020000 Not used
00040000 Fans error
00080000 ECB error
00100000 Reserved
00200000 Reserved
00400000 Reserved
00800000 Reserved
01000000 Reserved
02000000 Reserved
04000000 Reserved
08000000 Reserved
10000000 Reserved
20000000 Reserved
40000000 Reserved
80000000 Reserved
Bit
Alarm Word 2
Alarm Word 2 (par. 16-91
2
Service Trip, Typecode /
Sparepart
Alarm Word
)
58
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 9 Troubleshooting
9.1.3 Warning words
Warning word , par. 16-92
Bit
(Hex)
00000001 Brake check
00000002 Power card over temperature
00000004 Earth fault
00000008 Ctrl. card over temperature
00000010 Control word timeout
00000020 Over current
00000040 Torque limit
00000080 Motor thermistor over temp.
00000100 Motor ETR over temperature
00000200 Inverter overloaded
00000400 DC link under voltage
00000800 DC link over voltage
00001000 DC link voltage low
00002000 DC link voltage high
00004000 Mains phase loss
00008000 No motor
00010000 Live zero error
00020000 10V low
00040000 Brake resistor power limit
00080000 Brake resistor short circuit
00100000 Brake chopper fault
00200000 Speed limit
00400000 Fieldbus comm. fault
00800000 24V supply fault
01000000 Mains failure
02000000 Current limit
04000000 Low temperature
08000000 Voltage limit
10000000 Encoder loss
20000000 Output frequency limit
40000000 Not used
80000000 Not used
Warning Word
Warning Word (par. 16-92
Warning Word
Warning word 2, par. 16-93
)
Bit
(Hex)
00000001 Start Delayed
00000002 Stop Delayed
00000004 Clock Failure
00000008 Reserved
00000010 Reserved
00000020 No Flow
00000040 Dry Pump
00000080 End of Curve
00000100 Broken Belt
00000200 Not used
00000400 Reserved
00000800 Reserved
00001000 Reserved
00002000 Reserved
00004000 Reserved
00008000 Reserved
00010000 Reserved
00020000 Not used
00040000 Fans warning
00080000 ECB warning
00100000 Reserved
00200000 Reserved
00400000 Reserved
00800000 Reserved
01000000 Reserved
02000000 Reserved
04000000 Reserved
08000000 Reserved
10000000 Reserved
20000000 Reserved
40000000 Reserved
80000000 Reserved
Warning Word 2
Warning Word 2 (par. 16-93
)
2
Warning Word
9
MG.11.E2.02 - VLT® is a registered Danfoss trademark
59
9 Troubleshooting VLT® FC 100 LonWorks
9.2 Extended Status Word
9.2.1 Extended status words
9
Extended status word, par. 16-94
Bit
(Hex)
00000001 Ramping
00000002 AMA tuning
00000004 Start CW/CCW
00000008 Not used
00000010 Not used
00000020 Feedback high
00000040 Feedback low
00000080 Output current high
00000100 Output current low
00000200 Output frequency high
00000400 Output frequency low
00000800 Brake check OK
00001000 Braking max
00002000 Braking
00004000 Out of speed range
00008000 OVC active
00010000 AC brake
00020000 Password Timelock
00040000 Password Protection
00080000 Reference high
00100000 Reference low
00200000 Local Ref./Remote Ref.
00400000 Reserved
00800000 Reserved
01000000 Reserved
02000000 Reserved
04000000 Reserved
08000000 Reserved
10000000 Reserved
20000000 Reserved
40000000 Reserved
80000000 Reserved
Extended Status Word (par. 16-94
Ext. Status Word
Ext. Status Word
Extended status word 2, par. 16-95
Bit
)
(Hex)
00000001 Off
00000002 Hand / Auto
00000004 Not used
00000008 Not used
00000010 Not used
00000020 Relay 123 active
00000040 Start Prevented
00000080 Control ready
00000100 Drive ready
00000200 Quick Stop
00000400 DC Brake
00000800 Stop
00001000 Standby
00002000 Freeze Output Request
00004000 Freeze Output
00008000 Jog Request
00010000 Jog
00020000 Start Request
00040000 Start
00080000 Start Applied
00100000 Start Delay
00200000 Sleep
00400000 Sleep Boost
00800000 Running
01000000 Bypass
02000000 Fire Mode
04000000 Reserved
08000000 Reserved
10000000 Reserved
20000000 Reserved
40000000 Reserved
80000000 Reserved
Extended Status Word 2 (par. 16-95
Ext. Status Word 2
Ext. Status Word 2
)
60
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 9 Troubleshooting
9.3 Reference Scaling - Examples
9.3.1 Reference Scaling - Open Loop
Example:
par. 3-02
Minimum Reference
Maximum Reference
par. 3-03
Reference send = 1500 hex (5376 dec)
Output:
The output can be calculated as:
= 100 RPM
= 1500 RPM
9
Reference (decimal) * (par.3−03 − par.3−02)
5376 * (1500 100)
16384
16384
+100=559 RPM
+ par.3 02 =
MG.11.E2.02 - VLT® is a registered Danfoss trademark
61
9
9 Troubleshooting VLT® FC 100 LonWorks
9.4 Network Variables - Overview
9.4.1 Output variables (nvo)
Variable function Variable name SNVT type Profile FC 100par.
Status word nvoStatusword SNVT_state FC VSD 16-03
Drive output [%] nvoOutputPcnt SNVT_lev_percent FC VSD 16-05
Drive output [Hz] nvoOutputHz SNVT_freq_hz FC VSD 16-13
kWh counter nvoDrvEnrg SNVT_elec_kwh_l FC VSD 15-02
DC Link Voltage nvoDCVoltage SNVT_volt FC VSD 16-30
Motor thermal nvoTempMtr SNVT_lev_cont FC VSD 16-18
Inverter Thermal nvoTempInvrtr SNVT_lev_cont FC VSD 16-35
Closed loop feedback nvoFeedback SNVT_count_inc_f FC VSD 16-52
Fanbelt broken nvoBrokenBelt SNVT_switch FC VSD 16-93
Alarm flag nvoAlarm SNVT_switch FC VSD 16-90
Warning flag nvoWarning SNVT_switch FC VSD 16-03
Alarm word nvoAlarmword SNVT_state_64 FC VSD 16-90 + 16-91
Warning word nvoWarningword SNVT_state_64 FC VSD 16-92 + 16-93
Extended statusword nvoExtendedStatusword SNVT_state_64 FC VSD 16-94 + 16-95
Digital inputs nvoDigitInput SNVT_state_64 FC VSD 16-60
Analog Input (53) nvoAnIn1 SNVT_volt/SNVT_amp_mil/SNVT_lev_percent FC VSD 16-62
Analog Input (54) nvoAnIn2 SNVT_volt/SNVT_amp_mil/SNVT_lev_percent FC VSD 16-64
Analog Input (X30/11) nvo101AnIn1 SNVT_volt/SNVT_lev_percent FC VSD 16-75
Analog Input (X30/12) nvo101AnIn2 SNVT_volt/SNVT_lev_percent FC VSD 16-76
Analog Input (X42/1) nvo109AnIn1 SNVT_volt/SNVT_temp_p/SNVT_lev_percent FC VSD 18-30
Analog Input (X42/3) nvo109AnIn2 SNVT_volt/SNVT_temp_p/SNVT_lev_percent FC VSD 18-31
Analog Input (X42/5) nvo109AnIn3 SNVT_volt/SNVT_temp_p/SNVT_lev_percent FC VSD 18-32
ECB option status nvoECBstatus SNVT_state FC VSD 31-10
Parameter access cmd. nvoParamResponse UNVT_param_response FC VSD -
Drive Speed nvoDrvSpeed SNVT_lev_percent VSD 6010 16-05
Output current nvoDrvCurnt SNVT_amp VSD 6010 16-14
Output voltage nvoDrvVolt SNVT_volt VSD 6010 16-12
Output power nvoDrvPwr SNVT_power_kilo VSD 6010 16-10
Running hours nvoDrvRunHours SNVT_time_hour VSD 6010 15-01
Object Status nvoStatus SNVT_obj_status Node obj. -
62
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks 9 Troubleshooting
9.4.2 Input variables (nvi)
Variable Function Variable Name SNVT type Profile FC 100 par.
Start/Stop nviStartStop SNVT_switch FC VSD CTW/reference
Control word nviControlword SNVT_state FC VSD CTW
Reset fault nviResetFaut SNVT_switch FC VSD CTW
Reference [%] nviRefPcnt SNVT_lev_percent FC VSD Reference
Reference [Hz] nviRefHz SNVT_freq_hz FC VSD Reference
CL Setpoint 1 nviSetpoint1 SNVT_lev_percent FC VSD 20-21
CL Setpoint 2 nviSetpoint2 SNVT_lev_percent FC VSD 20-22
CL Setpoint 3 nviSetpoint3 SNVT_lev_percent FC VSD 20-23
Bus feedback 1 nviFeedback1 SNVT_lev_percent FC VSD 8-94
Bus feedback 2 nviFeedback2 SNVT_lev_percent FC VSD 8-95
Bus feedback 3 nviFeedback3 SNVT_lev_percent FC VSD 8-96
Digital/relay outputs nviDigiOutput SNVT_state_64 FC VSD 5-90
Analog output (42) nviAnOut1 SNVT_lev_percent FC VSD 6-53
Analog output (X30/8) nvi101AnOut1 SNVT_lev_percent FC VSD 6-63
Analog output (X42/7) nvi109AnOut1 SNVT_lev_percent FC VSD 26-43
Analog output (X42/9) nvi109AnOut2 SNVT_lev_percent FC VSD 26-53
Analog output (X42/11) nvi109AnOut3 SNVT_lev_percent FC VSD 26-63
Setting of RTC nviTimeStamp SNVT_time_stamp FC VSD 0-70
ECB option Mode nviECBMode SNVT_state FC VSD 31-00
ECB By-pass activation nviECBActivation SNVT_switch FC VSD 31-19
Parameter access command nviParamRequest UNVT_param_request FC VSD -
Drive speed setpoint nviDrvSpeedStpt SNVT_switch VSD 6010 CTW / Reference
Standard Node Object nviRequest SNVT_obj_request Node obj. -
9.4.3 Configuration properties (nci)
Variable function Variable name SNVT type Profile
Max. motor speed [%] nciMaxSpeed SNVT_lev_percent VSD 6010 4-13
Min. motor speed [%] nciMinSpeed SNVT_lev_percent VSD 6010 4-11
Nom. motor speed [RPM] nciNmlSpeed SNVT_rpm VSD 6010 1-25
Nom. motor frequency [Hz] nciNmlFreq SNVT_freq_hz VSD 6010 1-23
Min. ramp-up time [s] nciRampUpTime SNVT_time_sec VSD 6010 3-41
Min. ramp-down time [s] nciRampDownTime SNVT_time_sec VSD 6010 3-42
Heartbeat time [s] nciSndHrtBt SNVT_time_sec VSD 6010 -
Max Send Time (Heartbeat) nciMaxStsSendT SNVT_elapsed_tm Node obj. -
Min Send Time (Inhibit timer) nciMinSendT SNVT_elapsed_tm Virtual obj. -
parameter
9
FC 100
MG.11.E2.02 - VLT® is a registered Danfoss trademark
63
Index VLT® FC 100 LonWorks
Index
A
Abbreviations 9
About This Manual 7
Alarm And Warning Messages 57
Alarm Flag 29
Alarm Word 58
Alarm Word 29
Analog Input (53) 30
Analog Input (54) 31
Analog Input (x30/11) 31
Analog Input (x30/12) 31
Analog Input (x42/1) 32
Analog Input (x42/3) 32
Analog Input (x42/5) 32
Analog Output (42) 24
Analog Output (x30 / 8) 25
Analog Output (x42 / 7) 25
Analog Output (x42 / 9) 25
Analog Output (x42 /11) 25
Assumptions 7
B
Background Knowledge 8
Bus Feedback 1-3 23
Bus Line 13
C
Cable Lengths 13
Cabling 11
Closed Loop Feedback 28
Closed Loop Set-point 1-3 23
Coasting Select 8-50 51
Configuration Properties (nci) 63
Configuration Properties (nci) 35
Configure The Lonworks Network 19
Control Site 8-01 49
Control Timeout Function 8-04 50
Control Timeout Time 8-03 50
Control Word 22
Control Word Time-out Function 40
Conversion Index 55
Copyright, Limitation Of Liability And Revision Rights 3
D
Dc Brake Select 8-52 52
[Dc Link Voltage V] 28
Diagnosis Trigger 8-07 51
Digital / Relay Outputs 24
Digital Inputs 30
[Drive Output %] 27
[Drive Output Hz] 27
Drive Speed 36
E
Ecb Option Mode 26
Ecb Option Status 33
Ecb Remote By-pass Activation 26
Emc Precautions 14
End-of-timeout Function 8-05 51
Example: Read Parameter 3-41 46
Explanation Of The Control Bits 42
Explanation Of The Status Bits 44
Extended Status Word 60
64
MG.11.E2.02 - VLT® is a registered Danfoss trademark
VLT® FC 100 LonWorks Index
Extended Status Word 30
Extended Status Word 2 60
F
Fanbelt Broken 28
Fc Control Profile 42
Fc Vsd Profile 20
Fc Vsd Profile - Input 22
Fieldbus Option 16
Frequency Converter Speed Setpoint 35
Functional Profiles 19
H
Hardware 7
[Heartbeat Time S] 38
How To Install Option In Frequency Converter 16
I
Input Variables 20
Input Variables 34
Input Variables (nvi) 63
Installation At High Altitudes 5
[Inverter Thermal %] 28
K
[Kwh Counter Kwh] 27
L
Least Significant Bit (lsb) 27, 29, 30
Led Behaviour 15
Lon 7, 0
Lon Technology 7, 0
Lonmark Certification 8
Lonworks Communication Structure 0
Lonworks Option 11
M
[Max Motor Speed %] 37
Max. Send Time (heartbeat) 39
[Min Motor Speed %] 37
[Min Ramp-down Time S] 38
[Min Ramp-up Time S] 38
Min. Send Time (inhibit Timer) 40
[Motor Thermal %] 28
N
Network Termination 12
Network Variable Description 22
Neuron Id Label 19
Node Object 39
[Nom Motor Speed Rpm] 37
[Nominal Motor Frequency Hz] 37
Non-volatile Memory 35
O
Object And Data Types Supported By 55
Object Request 39
Object Response 39
Output Current 36
Output Power 36
Output Variables 21
Output Variables 34
MG.11.E2.02 - VLT® is a registered Danfoss trademark
65
Index VLT® FC 100 LonWorks
Output Variables (nvo) 62
Output Voltage 36
P
Parameter Access Command 26
Parameter Access Response 33
Parameter List 49
Preset Reference Select 8-56 53
Q
Query And Wink 19
Quick Stop Select 8-51 51
R
[Reference %] 23
Reference Handling 41
[Reference Hz] 23
Reference Scaling - Open Loop 61
Related Literature For The 8
Reset Control Timeout 8-06 51
Reset Fault 22
Resource Files 19
Reversing Select 8-54 52
Running Hours 36
S
Safety Note 5
Safety Regulations 5
Service Pin 19
Setting Of Rtc 26
Set-up Select 8-55 53
Start Select 8-53 52
Start/stop 22
Status Word 27
Status Word According To Fc Profile (stw) 43
Store Data Values 11-21 54
System Specifications 13
T
Technical Overview 7
U
Unvt Parameter Structure 45
Unvt_param_request 45
Unvt_param_response 45
W
Warning Against Unintended Start 5
Warning Flag 29
Warning Word 59
Warning Word 29
Warning Word 2 59
66
MG.11.E2.02 - VLT® is a registered Danfoss trademark
Loading...