Danfoss VLT AHF005, VLT AHF010 Design Manual

MAKING MODERN LIVING POSSIBLE
Design Guide
AHF005/010
Contents
1 How to Read this Design Guide
3
4
2.1.2 Abbreviations 4
2.1.3 CE Conformity and Labelling 4
2.1.4 EMC-Directive 2004/108/EG 5
2.1.5 Warnings 5
3 Introduction to Harmonics and Mitigation
7
3.1 What are Harmonics?
7
3.1.1 Linear Loads 7
3.1.2 Non-linear Loads 8
3.1.3 The Effect of Harmonics in a Power Distribution System 9
3.2 Harmonic Limitation Standards and Requirements
9
3.3 Harmonic Mitigation
11
4 Introduction to Advanced Harmonic Filters
12
4.1 Operation Principle
12
4.1.1 Power Factor 13
4.1.2 Capacitor Disconnect 14
5 Selection of Advanced Harmonic Filter
15
5.1 How to Select the Correct AHF
15
5.1.1 Calculation of the Correct Filter Size Needed 15
5.1.2 Calculation Example 15
5.1.3 Voltage Boost 15
5.2 Electrical Data
16
5.2.1 Accessories 26
5.3 General Specification
27
5.3.1 General Technical Data 27
5.3.2 Environmental Data 27
6 How to Install
29
6.1 Mechanical Mounting
29
6.1.1 Safety Requirements of Mechanical Installation 29
6.1.2 Mounting 29
6.1.3 Recommendations for Installation in Industrial Enclosures 29
6.1.4 Ventilation 29
6.2 Electrical Installation
32
6.2.1 Over Temperature Protection 32
6.2.2 Capacitor Disconnect 33
Contents AHF005/010 Design Guide
MG.80.C4.02 - VLT® is a registered Danfoss trademark 1
6.2.3 Wiring 34
6.2.4 Fuses 36
6.3 Mechanical Dimensions
37
6.3.1 Sketches 37
6.3.2 IP00 Enclosures 47
6.3.3 Physical Dimensions 54
6.3.4 IP00 Dimensions 54
6.3.5 Weight 55
7 How to Programme the Frequency Converter
56
7.1.1 DC-link Compensation Disabling 56
Index
57
Contents AHF005/010 Design Guide
2 MG.80.C4.02 - VLT® is a registered Danfoss trademark
1 How to Read this Design Guide
This Design Guide will introduce all aspects of the Advanced Harmonic Filters for your VLT® FC Series Drive. It describes Harmonics and how to mitigate them, provide installation instructions and guidance about how to programme the frequency converter.
Danfoss technical literature is also available online at
www.danfoss.com/BusinessAreas/DrivesSolutions/Documen­tations/Technical+Documentation.
How to Read this Design Gui... AHF005/010 Design Guide
MG.80.C4.02 - VLT® is a registered Danfoss trademark 3
1 1
2 Safety and Conformity
2.1.1 Symbols
Symbols used in this manual
NOTE
Indicates something to be noted by the reader.
CAUTION
Indicates a general warning.
WARNING
Indicates a high-voltage warning.
Indicates default setting
2.1.2 Abbreviations
Active Power P Advanced Harmonic Filter AHF Alternating current AC American wire gauge AWG Ampere/AMP A Apparent Power S Degrees Celsius
°C Direct current DC Displacement Power Factor DPF Electro Magnetic Compatibility EMC Drive FC Gram g Harmonic Calculation Software HCS Hertz Hz Kilohertz kHz Local Control Panel LCP Meter m Millihenry Inductance mH Milliampere mA Millisecond ms Minute min Motion Control Tool MCT Nanofarad nF Newton Meters Nm Nominal motor current I
M,N
Nominal motor frequency f
M,N
Nominal motor power P
M,N
Nominal motor voltage U
M,N
Parameter par. Partial Weighted Harmonic Distortion
PWHD
Point of Common Coupling PCC Power Factor PF Protective Extra Low Voltage PELV Rated Inverter Output Current I
INV
Reactive Power Q Revolutions Per Minute RPM Second sec. Short circuit ratio R
SCE
Total Demand Distortion TDD Total Harmonic Distortion THD Total Harmonic Current Distortior THiD Total Harmonic Voltage Distortior THvD True Power Factor TPF Volts V I
VLT,MAX
The maximum output current.
I
VLT,N
The rated output current supplied by the frequency converter.
Equipment containing electrical components may not be disposed of together with domestic waste. It must be separately collected with electrical and electronic waste according to local and currently valid legislation.
AHF005/010
Design Guide
2.1.3 CE Conformity and Labelling
What is CE Conformity and Labelling? The purpose of CE labelling is to avoid technical trade obstacles within EFTA and the EU. The EU has introduced the CE label as a simple way of showing whether a product complies with the relevant EU directives. The CE label says nothing about the specifications or quality of the product. The low-voltage directive (73/23/EEC) Frequency converters must be CE labelled in accordance with the low-voltage directive of January 1, 1997. The directive applies to all electrical equipment and appliances used in the 50 - 1000V AC and the 75 - 1500V DC voltage ranges. Danfoss CE-labels in accordance with the directive and issues a declaration of conformity upon request.
Safety and Conformity AHF005/010 Design Guide
4 MG.80.C4.02 - VLT® is a registered Danfoss trademark
22
2.1.4 EMC-Directive 2004/108/EG
The Danfoss frequency converters comply with the requirements of the EMC -Directive. The AHF are inherently benign equipment, that means that they do not produce electromagnetic disturbances, consisting only of passive components. Therefore, AHF are not within the scope of the EMC-directive. Though, the Danfoss frequency converters in combination with AHF will observe the requirements of the EMC-Directive.
2.1.5 Warnings
WARNING
Improper installation of the filter or the frequency converter may cause equipment failure, serious injury or death. Follow this Design Guide and install according to National and Local Electrical Codes.
WARNING
Never work on a filter in operation. Touching the electrical parts may be fatal - even after the equipment has been disconnected from the drive or motor.
WARNING
Before disconnecting the filter, wait at least the voltage discharge time stated in the Design Guide for the corresponding frequency converter to avoid electrical shock hazard.
CAUTION
When in use the filter surface temperature rises. DO NOT touch filter during operation.
CAUTION
To prevent resonances in the DC-link, it is recommended to disable the dynamic DC-link compensation by setting
14-51 DC Link Compensation to OFF. See chapter 7 How to Programme the Frequency Converter.
CAUTION
Temperature contactor must be used to prevent damage of the filter chokes caused by over temperature. An immediate stop or a controlled ramp down within 30 sec. has to be performed to prevent damage of the filter chokes.
NOTE
Never attempt to repair a defect filter.
NOTE
The filters represented in this Design Guide are specially designed and tested for operation with Danfoss frequency converters (FC 102/202/301 and 302). Danfoss takes no responsibility for the use of the filters with third party frequency converters.
WARNING
Non - authorized removal of required cover, inappropriate use, incorrect installation or operation, creates the risk of severe injury to persons or damage to material assets.
CAUTION
All operations concerning transport, installation and commissioning as well as maintenance must be carried out by qualified, skilled personnel (IEC 60364 and CENELEC HD 384 or IEC 60364 and IEC-Report 664 or DIN VDE 0110. National regulations for the prevention of accidents must be observed).
NOTE
According to this basic safety information qualified skilled personnel are persons who are familiar with the assembly, commissioning and operation of the product and who have the qualifications necessary for their occupation.
NOTE
The filters are components, that are designed for installation in electrical systems or machinery. When installing in machines, commissioning of the filters (i.e. the starting of operation as directed) is prohibited until it is proven, that the machine corresponds to the regulations of the EC Directive 83/392/EEC (Machinery Directive); EN 60204 must be observed.
NOTE
Commissioning (i.e. starting operation as directed) is only allowed when there is compliance with the EMC-Directive 89/336/EEC. The filters meet the requirements of the Low-Voltage Directive 73/23/EEC. The technical data and information on the connection conditions must be obtained from the nameplate and the documentation and must be observed in all cases.
NOTE
The filter must be protected from inappropriate loads. In particular; during transport and handling: Components are not allowed to be bent. Distance between isolation must not be altered. Touching of electronic components and contacts must be avoided.
Safety and Conformity AHF005/010 Design Guide
MG.80.C4.02 - VLT® is a registered Danfoss trademark 5
2 2
NOTE
When measuring on live filters, the valid national regulations for the prevention of accidents (e.g. VBG 4) must be observed. The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross-sections, fuses, PE-connection). When using the filters with frequency converters without safe separation from the supply line (to VDE 0100) all control wiring has to be included in further protective measures (e.g. double insulated or shielded, grounded and insulated).
NOTE
Systems where filters are installed, if applicable, have to be equipped with additional monitoring and protective devices according to the valid safety regulations e.g. law on technical tools, regulations for the prevention of accidents, etc.
Safety and Conformity AHF005/010 Design Guide
6 MG.80.C4.02 - VLT® is a registered Danfoss trademark
22
3 Introduction to Harmonics and Mitigation
3.1 What are Harmonics?
3.1.1 Linear Loads
On a sinusoidal AC supply a purely resistive loads (for example an incandescent light bulb) will draw a sinusoidal current, in phase with the supply voltage.
The power dissipated by the load is:
P=U×I
For reactive loads (such as an induction motor) the current will no longer be in phase with the voltage, but will lag the voltage creating a lagging true power factor with a value less than 1. In the case of capacitive loads the current is in advance of the voltage, creating a leading true power factor with a value less than 1.
In this case, the AC power has three components: real power (P), reactive power (Q) and apparent power (S). The apparent power is:
S=U×I
(where S=[kVA], P=[kW] and Q=[kVAR])
In the case of a perfectly sinusoidal waveform P, Q and S can be expressed as vectors that form a triangle:
S
2
=
P
2
+
Q
2
P
S
Q
φ
130BB538.10
The displacement angle between current and voltage is φ. The displacement power factor is the ratio between the active power (P) and apparent power (S):
DPF
=
P S
=
cos
(ϕ)
Introduction to Harmonics a... AHF005/010 Design Guide
MG.80.C4.02 - VLT® is a registered Danfoss trademark 7
3
3
3.1.2 Non-linear Loads
Non-linear loads (such as diode rectifiers) draw a non-sinusoidal current. The figure below shows the current drawn by a 6-pulse rectifier on a three phase supply.
A non-sinusoidal waveform can be decomposed in a sum of sinusoidal waveforms with periods equal to integer multiples of the fundamental waveform.
f(t
) =
a
h
×
sin(h
ω
1
t
)
See following illustrations.
1
1 2 3 4 5 6 7
0.
0
0
-
-
1
1 2 3 4 5 6 7
0.
0
0
-
-
130BB539.10
The integer multiples of the fundamental frequency ω1 are called harmonics. The RMS value of a non-sinusoidal waveform (current or voltage) is expressed as:
I
RMS
=
h
=1
h
max
I
(h)
2
The amount of harmonics in a waveform gives the distortion factor, or total harmonic distortion (THD), represented by the ratio of RMS of the harmonic content to the RMS value of the fundamental quantity, expressed as a percentage of the fundamental:
THD
=
h
=2
h
max
(
I
h
I
1
)
2
× 100 %
Using the THD, the relationship between the RMS current I
RMS
and the fundamental current I1 can be expressed as:
I
RMS
=
I
1
× 1 +
THD
2
The same applies for voltage.
The true power factor PF (λ) is:
PF
=
P S
In a linear system the true power factor is equal to the displacement power factor:
PF=DPF=cos
(ϕ)
Introduction to Harmonics a... AHF005/010 Design Guide
8 MG.80.C4.02 - VLT® is a registered Danfoss trademark
3
In non-linear systems the relationship between true power factor and displacement power factor is:
PF
=
DPF
1 +
THD
2
The power factor is decreased by reactive power and harmonic loads. Low power factor results in a high RMS current that produces higher losses in the supply cables and transformers.
In the power quality context, the total demand distortion (TDD) term is often encountered. The TDD does not charac­terize the load, but it is a system parameter. TDD expresses the current harmonic distortion in percentage of the maximum demand current IL.
TDD
=
h
=2
h
max
(
I
h
I
L
)
2
× 100 %
Another term often encountered in literature is the partial weighted harmonic distortion (PWHD). PWHD represents a weighted harmonic distortion that contains only the harmonics between the 14th and the 40th, as shown in the following definition.
PWHD
=
h
=14
40
(
I
h
I
1
)
2
× 100 %
3.1.3
The Effect of Harmonics in a Power Distribution System
In Illustration 3.1 a transformer is connected on the primary side to a point of common coupling PCC1, on the medium voltage supply. The transformer has an impedance Z
xfr
and feeds a number of loads. The point of common coupling where all loads are connected together is PCC2. Each load is connected through cables that have an impedance Z1, Z2, Z3.
Illustration 3.1 Small Distribution System
Harmonic currents drawn by non-linear loads cause distortion of the voltage because of the voltage drop on the impedances of the distribution system. Higher impedances result in higher levels of voltage distortion.
Current distortion relates to apparatus performance and it relates to the individual load. Voltage distortion relates to system performance. It is not possible to determine the voltage distortion in the PCC knowing only the load’s harmonic performance. In order to predict the distortion in the PCC the configuration of the distribution system and relevant impedances must be known.
A commonly used term for describing the impedance of a grid is the short circuit ratio R
sce
, defined as the ratio between the short circuit apparent power of the supply at the PCC (Ssc) and the rated apparent power of the load (S
equ
).
R
sce
=
S
ce
S
equ
where
S
sc
=
U
2
Z
supply
and
S
equ
=U×
I
equ
The negative effect of harmonics is twofold
Harmonic currents contribute to system losses (in cabling, transformer)
Harmonic voltage distortion causes disturbance to other loads and increase losses in other loads
Non-linear
Current Voltage
System
Impedance
Disturbance to
other users
Contribution to
system losses
130BB541.10
3.2
Harmonic Limitation Standards and Requirements
The requirements for harmonic limitation can be:
Application specific requirements
Requirements from standards that have to be observed
The application specific requirements are related to a specific installation where there are technical reasons for limiting the harmonics.
For example on a 250kVA transformer with two 110kW motors connected. One is connected direct on-line and the other one is supplied through a frequency converter. If the
Introduction to Harmonics a... AHF005/010 Design Guide
MG.80.C4.02 - VLT® is a registered Danfoss trademark 9
3
3
direct on-line motor should also be supplied through a frequency converter the transformer will, in this case, be undersized. In order to retrofit, without changing the transformer, the harmonic distortion from the two frequency converterhas to be mitigated using AHF filters.
There are various harmonic mitigation standards, regulations and recommendations. Different standards apply in different geographical areas and industries. The following encountered standards will be presented:
IEC/EN 61000-3-2
IEC/EN 61000-3-12
IEC/EN 61000-3-4
IEC 61000-2-2
IEC61000-2-4
IEEE 519
G5/4
IEC 61000-3-2, Limits for harmonic current emissions (equipment input current 16A per phase) The scope of IEC 61000-3-2 is equipment connected to the public low-voltage distribution system having an input current up to and including 16 A per phase. Four emission classes are defined: Class A through D. The Danfoss frequency converters are in Class A. However, there are no limits for professional equipment with a total rated power greater than 1kW.
IEC 61000-3-12, Limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and 75A The scope of IEC 61000-3-12 is equipment connected to the public low-voltage distribution system having an input current between 16A and 75A. The emission limits are currently only for 230/400V 50Hz systems and limits for other systems will be added in the future. The emission limits that apply for drives are given in Table 4 in the standard. There are requirements for individual harmonics (5th, 7th, 11th, and 13th) and for THD and PWHD. Frequency converters from the Automation Drive series (FC 102 HVAC, FC 202 Aqua and FC 302 Industry) comply with these limits without additional filtering.
IEC 61000-3-4, Limits, Limitation of emission of harmonic currents in low-voltage power supply systems for equipment with rated current greater than 16A IEC 61000-3-12 supersedes IEC 61000-3-4 for currents up to 75A. Therefore the scope of IEC 61000-3-4 is equipment with rated current greater than 75A connected to the public low­voltage distribution system. It has the status of Technical report and should not be seen as an international standard. A three-stage assessment procedure is described for the connection of equipment to the public supply and equipment above 75A is limited to stage 3 connection based on the load's agreed power. The supply authority may accept the connection of the equipment on the basis of the agreed
active power of the load's installation and local requirements of the power supply authority apply. The manufacturer shall provide individual harmonics and the values for THD and PWHD.
IEC 61000-2-2 and IEC 61000-2-4 Compatibility levels for low­frequency conducted disturbances IEC 61000-2-2 and IEC 61000-2-4 are standards that stipulate compatibility levels for low-frequency conducted distur­bances in public low-voltage supply systems (IEC 61000-2-2) and industrial plants (IEC 61000-2-4). These low-frequency disturbances include but are not limited to harmonics. The values prescribed in these standards shall be taken into consideration when planning installations. In some situations the harmonic compatibility levels can not be observed in installations with frequency converters and harmonic mitigation is needed.
IEEE519, IEEE recommended practices and requirements for harmonic control in electrical power systems IEEE519 establishes goals for the design of electrical systems that include both linear and nonlinear loads. Waveform distortion goals are established and the interface between sources and loads is described as point of common coupling (PCC).
IEEE519 is a system standard that aims the control of the voltage distortion at the PCC to a THD of 5% and limits the maximum individual frequency voltage harmonic to 3%. The development of harmonic current limits aims the limitation of harmonic injection from individual customers so they will not cause unacceptable voltage distortion levels and the limitation of the overall harmonic distortion of the system voltage supplied by the utility.
The current distortion limits are given in Table 10.3 in the standard and depend on the ratio ISC/IL where ISC is the short circuit current at the utility PCC and IL is the maximum demand load current. The limits are given for individual harmonics up to the 35th and total demand distortion (TDD). Please note that these limits apply at the PCC to the utility. While requiring individual loads to comply with these limits also ensures the compliance at the PCC, this is rarely the most economic solution, being unnecessarily expensive. The most effective way to meet the harmonic distortion requirements is to mitigate at the individual loads and measure at the PCC.
However, if in a specific application it is required that the individual drive should comply with the IEEE519 current distortion limits, an AHF can be employed to meet these limits.
G5/4, Engineering recommendation, planning levels for harmonic voltage distortion and the connection of non­linear equipment to transmission systems and distribution networks in the United Kingdom G5/4 sets planning levels for harmonic voltage distortion to be used in the process of connecting non-linear equipment. A process for establishing individual customer emission
Introduction to Harmonics a... AHF005/010 Design Guide
10 MG.80.C4.02 - VLT® is a registered Danfoss trademark
3
limits based on these planning levels is described. G5/4 is a system level standard.
For 400V the voltage THD planning level is 5% at the PCC. Limits for odd and even harmonics in 400V systems are given in Table 2 in the standard. An assessment procedure for the connection of non-linear equipment is described. The procedure follows three stages, aiming to balance the level of detail required by the assessment process with the degree of risk that the connection of particular equipment will result in unacceptable voltage harmonic distortion.
Compliance of a system containing VLT® frequency converters depends on the specific topology and population of non-linear loads. AHF can be employed to meet the requirements of G5/4.
3.3 Harmonic Mitigation
To mitigate the harmonics caused by the frequency converter 6-pulse recitifier several solutions exist and they all have their advantages and disadvantages. The choice of the right solution depends on several factors:
The grid (background distortion, mains unbalance, resonance and type of supply - transformer/ generator)
Application (load profile, number of loads and load size)
Local/national requirements/regulations (IEEE519, IEC, G5/4, etc.)
Total cost of ownership (initial cost, efficiency, maintenance, etc.)
IEC standards are harmonized by various countries or supra­national organizations. All above mentioned IEC standards are harmonized in the European Union with the prefix “EN”. For example the European EN 61000-3-2 is the same as IEC 61000-3-2. The situation is similar in Australia and New Zealand, with the prefixes AS/NZS.
Harmonic solutions can be divided into two main categories: passive and active. Where the passive solutions consist of capacitors, inductors or a combination of the two in different arrangements. The simplest solution is to add inductors/reactors of typically 3% to 5% in front of the frequency converter. This added inductance reduces the amount of harmonic currents produced by the drive. More advanced passive solutions combine capacitors and inductors in trap arrangement specially tuned to eliminate harmonics starting from e.g. the 5th harmonic.
The active solutions determine the exact current that would cancel the harmonics present in the circuit and synthesizes and injects that current into the system. Thus the active solution can mitigate the real-time harmonic disturbances, which makes these solutions very effective at any load profile. To read more about the Danfoss active solutions Low Harmonic Drive (LHD) or Active Filters (AAF) please see MG.
34.OX.YY and MG.90.VX.YY.
Introduction to Harmonics a... AHF005/010 Design Guide
MG.80.C4.02 - VLT® is a registered Danfoss trademark 11
3
3
4 Introduction to Advanced Harmonic Filters
4.1 Operation Principle
The Danfoss Advanced Harmonic Filters (AHF) consist of a main inductor L0 and a two-stage absorption circuit with the inductors L1 and L2 and the capacitors C1 and C2. The absorption circuit is specially tuned to eliminate harmonics starting with the 5th harmonic and is specific for the designed supply frequency. Consequently the circuit for 50Hz has different parameters than the circuit for 60Hz.
L
0
L
1
L
2
C
2
C
1
M
AHF
Supply Motor
130BB578.11
Frequency converter
AHFs are available in two variants for two performance levels: AHF005 with 5% THiD (total current harmonic distortion) and AHF010 with 10% THiD. The strategy behind the two levels is to offer a performance similar to 12 pulse rectifiers with the AHF010 and a performance similar to 18 pulse rectifiers with AHF005.
The filter performance in terms of THiD varies as a function of the load. At nominal load the performance of the filter should be equal or better than 10% THiD for AHF010 and 5% THiD for AHF005.
At partial load the THiD has higher values. However, the absolute value of the harmonic current is lower at partial loads, even if the THiD has a higher value. Consequently, the negative effect of the harmonics at partial loads will be lower than at full load.
Example: An 18.5kW frequency converter is installed on a 400V/50Hz grid with a 34A AHF010 (type code AHF-DA-34-400-50-20-A). Following values are measured for different load currents, using a harmonic analyzer:
I line RMS [A]
Fundamental current at 50Hz I1 RMS [A]
THiD [%] Total harmonic
current Ih RMS [A]
1
9.6 9.59 5.45 0.52
15.24 15.09 13.78 2.07
20.24 20.08 12.46 2.5
25.17 25 11.56 2.89
30.27 30.1 10.5 3.15
34.2 34.03 9.95 3.39
1
)The total harmonic current has been calculated. The THiD
vs. load plot is shown in the following figure.
AHF-DA-34-400-50-20-A
0
2
4
6
8
10
12
14
16
10 15 20 25 30 35
Iline [A]
THiD [%]
0
0,5
1
1,5
2
2,5
3
3,5
4
Harmonic current Ih [A]
130BB579.10
THiD [%]
Harmonic current Ih [A]
It can be observed that at partial load, 15A, the THiD is approximately 14%, compared to 10% at the nominal load of 34A. On the other hand, the total harmonic current is only
2.07A at 15A line current against 3.39A harmonic current at 34A line current. Thus, THiD is only a relative indicator of the harmonic performance. The harmonic distortion of the voltage will be less at partial load than at nominal load.
Factors such as background distortion and grid unbalance can affect the performance of AHF filters. The specific figures are different from filter to filter and the graphs below show typical performance characteristics. For specific details a harmonic design tool such as MCT 31 or Harmonic Calculation Software (HCS) should be used.
Background distortion: The design of the filters aims to achieve 10% respectively 5% THiD levels with a background distortion of THvD = 2%. Practical measurements on typical grid conditions in installations with frequency converters show that often the performance of the filter is slightly better with a 2% background distortion. However, the complexity of the grid conditions and mix of specific harmonics can not allow a general rule about the performance on a distorted grid. Therefore we have chosen to present worst-case performance deterioration character­istics with the background distortion.
Introduction to Advanced Ha... AHF005/010 Design Guide
12 MG.80.C4.02 - VLT® is a registered Danfoss trademark
44
0 20 40 60 80 100
0
5
10
15
20
25
THvD 0% THvD 2% THvD 5%
Load [%]
THiD average [%]
130BB580.10
Illustration 4.1 AHF005
0
10
20
30
40
50
60
0 20 40 60 80 100
Load [%]
THvD 0% THvD 2% THvD 5%
THiD [%]
130BB581.10
Illustration 4.2 AHF010
Performance at 10% THvD has not been plotted. However, the filters have been tested and can operate at 10% THvD but the filter performance can no longer be guaranteed.
The filter performance also deteriorates with the unbalance of the supply. Typical performance is shown in the graphs below.
0% unbalance 1% unbalance 2% unbalance 3% unbalance
0 20 40 60 80 100
Load [%]
0
2
4
6
8
10
12
14
THiD [%]
130BB582.10
Illustration 4.3 AHF005
130BB583.10
0
0 20 40 60 80 1 00
Load [%]
5
10
15
20
25
0% unbalance 1% unbalance 2% unbalance 3% unbalance
THiD average [%]
Illustration 4.4 AHF010
4.1.1 Power Factor
In no load conditions (the frequency converter is in stand-by) the frequency converter current is negligible and the main current drawn from the grid is the current through the capacitors in the harmonic filter. Therefore the power factor is close to 0, capacitive. The capacitive current is approxi­mately 25% of the filter nominal current (depends on filter size, typical values between 20 and 25%). The power factor increases with the load. Because of the higher value of the main inductor L0 in the AHF005, the power factor is slightly higher than in the AHF010.
Following graphs show typical values for the true power factor on AHF010 and AHF005.
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
0 20 40 60 80 100
Load [%]
True Power Fac tor
130BB584.10
Illustration 4.5 AHF005
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
0 20 40 60 80 100
Load [%]
0
True Power Factor
130BB585.10
Illustration 4.6 AHF010
Introduction to Advanced Ha... AHF005/010 Design Guide
MG.80.C4.02 - VLT® is a registered Danfoss trademark 13
4 4
4.1.2 Capacitor Disconnect
If the specific application requires a higher power factor at no-load and the reduction of the capacitive current in stand­by, a capacitor disconnect should be used. A contactor can disconnect the capacitor at loads below 20%. It is important to note that the capacitors may not be connected at full load or disconnected at no load.
It is very important to consider the capacitive current in the design of applications where the harmonic filter is supplied by a generator. The capacitive current can overexcite the generator in no-load and low-load condition. The over­excitation causes an increase of the voltage that can exceed the allowed voltage for the AHF and the frequency converter. Therefore a capacitor disconnect should always be used in generator applications and the design carefully considered.
Compared to multi-pulse rectifiers, passive harmonic filter (such as AHF) are more robust against background distortion and supply imbalance. However, the performance of passive filters is inferior to the performance of active filters when it comes to partial load performance and power factor. For details about the performance positioning of the various harmonic mitigation solutions offered by Danfoss, please consult the relevant harmonic mitigation literature.
Introduction to Advanced Ha... AHF005/010 Design Guide
14 MG.80.C4.02 - VLT® is a registered Danfoss trademark
44
5 Selection of Advanced Harmonic Filter
This chapter will provide guidance about how to choose the right filter size and contains calculation examples, electrical data and the general specification of the filters.
5.1 How to Select the Correct AHF
For optimal performance the AHF should be sized for the mains input current to the frequency converter. This is the input current drawn based on the expected load of the frequency converter and not the size of the frequency converter itself.
5.1.1 Calculation of the Correct Filter Size Needed
The mains input current of the frequency converter (I
FC,L
) can
be calculated using the nominal motor current (I
M,N
) and the displacement factor (Cos φ) of the motor. Both values are normally printed on the name plate of the motor. In case the nominal motor voltage (U
M,N
) is unequal to the actual mains voltage (UL), the calculated current must be corrected with the ratio between these voltages as shown in the following
equation:
I
FC.L
= 1.1 ×
I
M,N
×
cos
(ρ)
×
U
M,N U
L
The AHF chosen must have a nominal current (I
AHF,N
) equal to or larger than the calculated frequency converter mains input current (I
FC,L
).
NOTE
Do not oversize the AHF. The best harmonic performance is obtained at nominal filter load. Using an oversized filter will most likely result in reduced THiD performance.
If several frequency converters are to be connected to the same filter, the AHF must be sized according to the sum of the calculated mains input currents.
NOTE
If the AHF is sized for a specific load and the motor is changed, the current must be recalculated to avoid overloading the AHF.
5.1.2 Calculation Example
System mains voltage (UL): 380V Motor name plate power(PM): 55kW Motor efficiency (ƞM):
0.96
FC efficiency (ƞFC):
0.97
AHF effiency (ƞ
AHF
)(worst case estimate):
0.98
Maximum line current (RMS):
P
M
× 1000
U
L
× ηM× ηFC× η
AHF
× 3
=
55 × 1000
380 × 0.96 × 0.97 × 0.98 × 3
= 91.57
A
In this case a 96A filter must be chosen.
5.1.3
Voltage Boost
In stand-by and under low condition, the AHFs will boost the input voltage with up to 5%. This means that the voltage at the frequency converter terminals is up to 5% higher than the voltage at the input of the filter. This should be considered at the design of the installation. Special care should be taken in 690V applications, where the voltage tolerance of the frequency converter is reduced to +5%, the boost voltage can, at low load and stand-by, be limited via the available capacitor disconnect. For more information see section 6.2.2.
Selection of Advanced Harmo... AHF005/010 Design Guide
MG.80.C4.02 - VLT® is a registered Danfoss trademark 15
5 5
5.2 Electrical Data
Code number
AHF005
IP00
IP20
Code number
AHF010
IP00
IP20
Filter current
rating
Typical motor VLT power and current
ratings
Losses Acoustic noise Frame size
AHF005 AHF010
A kW kW A W W dBA AHF005 AHF010
130B1392
130B1229
130B1262
130B1027
10 3 PK37-P4K0 1.2-9 131 93 <70 X1 X1
130B1393
130B1231
130B1263
130B1058
14 7.5 P5K5-P7K5 14.4 184 118 <70 X1 X1
130B1394
130B1232
130B1268
130B1059
22 11 P11K 22 258 206 <70 X2 X2
130B1395
130B1233
130B1270
130B1089
29 15 P15K 29 298 224 <70 X2 X2
130B1396
130B1238
130B1273
130B1094
34 18.5 P18K 34 335 233 <72 X3 X3
130B1397
130B1239
130B1274
130B1111
40 22 P22K 40 396 242 <72 X3 X3
130B1398
130B1240
130B1275
130B1176
55 30 P30K 55 482 274 <72 X3 X3
130B1399
130B1241
130B1281
130B1180
66 37 P37K 66 574 352 <72 X4 X4
130B1442
130B1247
130B1291
130B1201
82 45 P45K 82 688 374 <72 X4 X4
130B1443
130B1248
130B1292
130B1204
96 55 P55K 96 747 428 <75 X5 X5
130B1444
130B1249
130B1293
130B1207
133 75 P75K 133 841 488 <75 X5 X5
130B1445
130B1250
130B1294
130B1213
171 90 P90K 171 962 692 <75 X6 X6
130B1446
130B1251
130B1295
130B1214
204 110 P110 204 1080 742 <75 X6 X6
130B1447
130B1258
130B1369
130B1215
251 132 P132 251 1195 864 <75 X7 X7
130B1448
130B1259
130B1370
130B1216
304 160 P160 304 1288 905 <75 X7 X7
130B3153
130B3152
130B3151
130B3136
325 Paralleling for 355kW 1406 952 <75 X8 X7
130B1449
130B1260
130B1389
130B1217
381 200 P200 381 1510 1175 <77 X8 X7
130B1469
130B1261
130B1391
130B1228
480 250 P250 472 1852 1542 <77 X8 X8
Table 5.1 380-415V, 50Hz
Selection of Advanced Harmo... AHF005/010 Design Guide
16 MG.80.C4.02 - VLT® is a registered Danfoss trademark
55
Code number
AHF005
IP00
IP20
Code number
AHF010
IP00
IP20
Filter current
rating
Typical motor VLT power and
current ratings
Losses Acoustic noise Frame size
AHF005 AHF010
A kW kW A W W dBA AHF005 AHF010
2 x 130B1448
2 x 130B1259
2 x 130B1370
2 x 130B1216
608 315 P315 590 2576 1810 <80
2 x 130B3153
2 x 130B3152
2 x 130B3151
2 x 130B3136
650 355 P355 647 2812 1904 <80
130B1448 + 130B1449
130B1259 + 130B1260
130B1370 + 130B1389
130B1216 + 130B1217
685 400 P400 684 2798 2080 <80
2 x 130B1449
2 x 130B1260
2 x 130B1389
2 x 130B1217
762 450 P450 779 3020 2350 <80
130B1449 + 130B1469
130B1260 + 130B1261
130B1389 + 130B1391
130B1217 + 130B1228
861 500 P500 857 3362 2717 <80
2 x 130B1469
2 x 130B1261
2 x 130B1391
2 x 130B1228
960 560 P560 964 3704 3084 <80
3 x 130B1449
3 x 130B1260
3 x 130B1389
3 x 130B1217
1140 630 P630 1090 4530 3525 <80
2 x 130B1449 + 130B1469
2 x 130B1260 + 130B1261
2 x 130B1389 + 130B1391
2 x 130B1217 + 130B1228
1240 710 P710 1227 4872 3892 <80
3 x 130B1469
3 x 1301261
3 x 130B1391
3 x 130B1228
1440 800 P800 1422 5556 4626 <80
2 x 130B1449 + 2 x 130B1469
2 x 130B1260 + 2 x 130B1261
2 x 130B1389 + 2 x 130B1391
2 x 130B1217 + 2 x 130B1228
1720 1000 P1000 1675 6724 5434 <80
Table 5.2 380-415V, 50Hz
Selection of Advanced Harmo... AHF005/010 Design Guide
MG.80.C4.02 - VLT® is a registered Danfoss trademark 17
5 5
Loading...
+ 41 hidden pages