Danfoss VLT Adjustable Frequency Drive Operating guide

■■
Contents
■■
VLT® Adjustable Frequency Drive
Introduction
Safety.......................................................................3
Safety Guidelines........................................................3
Warnings Against Unintended Start ...............................3
Introduction ...............................................................4
About this manual.......................................................4
Assumptions..............................................................4
References................................................................4
Trademarks ...............................................................5
Programming the VLT 6000
Control Panel.............................................................5
Parameter Change Keys .............................................5
Local Control .............................................................6
Quick Menu ..............................................................6
To Enter or Change Quick Menu Parameter Data...........7
Example of Changing Parameter Data...........................7
Extended Menu..........................................................8
HP/kW......................................................................8
VLT 6000 Functional Features
Drive Operation..........................................................8
Motor and Drive Thermal Protection .............................8
Set-up 1-4.................................................................8
Current Monitoring and Limits.......................................9
Direction of Rotation ...................................................9
Start/Stop..................................................................9
Freeze Mode .............................................................9
Coast........................................................................9
Motor Ramp-up and Ramp-down Rate .........................9
Lock Panel................................................................9
Hand/Auto Modes.......................................................9
Run Enable................................................................9
Bus Functions............................................................9
Frequency Out High, Low Limits...................................9
Relay Out 1,2 ...........................................................9
PID Control Functions................................................10
Sleep Mode .............................................................10
Drive Control Display .................................................10
Terminals.................................................................10
Faults, Warnings and Alarms ......................................10
Error Status .............................................................10
VLT
®
Adjustable Frequency Drive
MG.60.G2.22 - VLT is a registered Danfoss Trademark
VLT 6000 Network Strategies
Strategy One ...........................................................11
Strategy Two........................................................... 11
Strategy Three .........................................................13
Strategy Four...........................................................13
1
VLT® Adjustable Frequency Drive
VLT 6000 Special Functions
Safety Interlock ...........................................................15
Analog Input Monitoring ...............................................15
Drive Relay Control 15
Network Connection
Hardware Setup..........................................................16
Electrical Control Terminals............................................17
Typical Control Connection Examples..............................18
Adjustable Frequency Drive
®
VLT
VLT 6000 Functional Features
Startup of FLN Manual .................................................20
Faults, Warnings and Alarms .........................................20
Point Mapping Table .....................................................22
Point Mapping Table Notes............................................25
Point Database Definitions.............................................26
2
MG.60.G2.22 - VLT is a registered Danfoss Trademark
■■
Safety
■■
Rotating shafts and electrical equipment can be hazardous. Therefore, it is strongly recommended that all electrical
work conform to National Electrical Code (NEC) and all local regulations. Installation, start-up and maintenance should be performed only by quali­fied personnel.
Factory recommended procedures, included in this manual, should be followed. Always disconnect electrical power before working on the unit. Although shaft couplings or belt drives are generally not furnished by the manufacturer, rotating shafts, couplings and belts must be protected with securely mounted metal guards that are of sufficient thickness to provide protection against flying particles such as keys, bolts and coupling parts. Even when the motor is stopped, it should be considered “alive” as long as its controller is energized. Automatic circuits may start the motor at any time. Keep hands away from the output shaft until the motor has completely stopped and power is disconnected from the controller. Motor control equipment and electronic controls are connected to hazardous line voltages. When servicing drives and electronic controls, there will be exposed components at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit to use only one hand when checking compo­nents. Always work with another person in case of an emergency. Disconnect power whenever pos­sible to check controls or to perform maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electric control or rotating equipment.
VLT® Adjustable Frequency Drive
3. Correct protective grounding of the equipment must be established. The user must be protec­ted against supply voltage and the motor must be protected against overload in accordance with applicable national and local regulations.
4. Ground currents are higher than 3 mA.
Warnings Against Unintended Start
1. While the drive is connected to the AC line, the motor can be brought to a stop by means of external switch closures, serial bus commands or references. If personal safety considerations make it necessary to ensure that no unin­tended start occurs, these stops are not sufficient.
2. During programming of parameters, the motor may start. Be certain that no one is in the area of the motor or driven equipment when changing parameters.
3. A motor that has been stopped may start unexpectedly if faults occur in the electronics of the drive, or if an overload, a fault in the supply AC line or a fault in the motor connection or other fault clears.
4. If the Local/Hand key is activated, the motor can only be brought to a stop by means of the Stop/Off key or an external safety interlock
NOTE:NOTE:
NOTE:
NOTE:NOTE:
It is responsibility of user or person installing drive to provide proper grounding and branch
circuit protection for incoming power and motor overload according to National Electrical Code (NEC) and local codes.
VLT
®
Adjustable Frequency Drive
Safety Guidelines
1. The drive must be disconnected from the AC line before any service work is done.
2. The Stop/Off key on the local control panel of the drive does not disconnect the equip­ment from the AC line and is not to be used as a safety switch.
MG.60.G2.22 - VLT is a registered Danfoss Trademark
The Electronic Thermal Relay (ETR) in UL listed VLTs provides Class 20 motor overload protection in accordance with NEC in single motor applica­tions, when parameter 117 is set for ETR TRIP 1, ETR TRIP 2, ETR TRIP 3, or ETR TRIP 4, and parameter 105 is set for rated motor (nameplate) current.
3
VLT® Adjustable Frequency Drive
DANGER:
TT
ouching electrical parts may be fatal - even after equipment hasouching electrical parts may be fatal - even after equipment has
T
ouching electrical parts may be fatal - even after equipment has
TT
ouching electrical parts may be fatal - even after equipment hasouching electrical parts may be fatal - even after equipment has
been disconnected frbeen disconnected fr
been disconnected fr
been disconnected frbeen disconnected fr fully discharged, wait 14 minutes for 220 and 500 V units and 30fully discharged, wait 14 minutes for 220 and 500 V units and 30
fully discharged, wait 14 minutes for 220 and 500 V units and 30
fully discharged, wait 14 minutes for 220 and 500 V units and 30fully discharged, wait 14 minutes for 220 and 500 V units and 30 minutes for 550-600 V units after power has been removedminutes for 550-600 V units after power has been removed
minutes for 550-600 V units after power has been removed
minutes for 550-600 V units after power has been removedminutes for 550-600 V units after power has been removed beforbefor
befor
beforbefor
Adjustable Frequency Drive
®
VLT
Introduction
The Siemens Floor Level Network (FLN) is a master/ slave control network for serial communication with various control devices. The FLN controller is RS­485 compatible, half duplex, with an operating rate of 4800 or 9600 baud. Recommended wiring is shielded, twisted pair. The FLN software protocol is designed to be general in nature to accommodate any unique properties of each device type. The node address system allows up to 96 devices to be used on any one system.
The Danfoss VLT 6000 is a programmable adjustable frequency drive which controls the operation of 3­phase, standard induction electrical motors in the HVAC industry. The VLT 6000 controller has FLN communication protocol software built-in. The drive uses optical isolation for fault tolerance and noise immunity.
The FLN communicates directly with the VLT 6000 drive via the RS-485 serial interface bus. In addition to being able to control the drive, most drive confi­guration and control parameters can be reviewed and changed through the FLN. Also, the operatio­nal status of the drive can be read and monitored through the bus. Diagnostic and operational infor­mation stored in the VLT 6000 is easily available, such as kWh of energy used, total operation hours, drive status, motor speed, and many other useful items which can be accessed and monitored through the FLN.
The FLN is designed to communicate with any controller node that supports the interfaces defined in this document.
om AC line. Tom AC line. T
om AC line. T
om AC line. Tom AC line. T
e touching any intere touching any inter
e touching any inter
e touching any intere touching any inter
o be suro be sur
o be sur
o be suro be sur
nal component.nal component.
nal component.
nal component.nal component.
About This Manual
The documentation in this manual provides comprehensive information on the connection, programming, and start-up of the VLT 6000 for use with the FLN. It is intended as both an instruc­tion and reference manual. Functions and features of the VLT 6000 adjustable frequency drive are also briefly reviewed to serve as a guideline to optimize your communication system. Read this manual before programming since important information is provided in each section. For detailed information on using the VLT 6000, see the VLT 6000 Operating Instructions.
Assumptions
This manual assumes that the controller node supports the interfaces in this document and that all the requirements and limitations stipulated in the controller node and the VLT 6000 are strictly ob­served. It is assumed that the user understands the general capabilities and limitation of the con­troller node and the VLT 6000 adjustable frequency drive.
References
Installation, Operation and Maintenance Manual for the VLT
Danfoss Graham document 23-6108-00. (Referred to as the VLT 6000 Operating Instructions in this manual.)
Operating Instructions VLT 6000 HVAC Frequency Converter, Danfoss document MG.60.AX.YY (International version of the VLT 6000 Operating Instructions.)
Contact Siemens for operational instructions for the Floor Level Network.
e that capacitors havee that capacitors have
e that capacitors have
e that capacitors havee that capacitors have
®
6000 Adjustable Frequency Drive,
4
MG.60.G2.22 - VLT is a registered Danfoss Trademark
Trademarks
®
FLN
is a Siemens registered trademark.
®
VLT
is a Danfoss registered trademark.
■■
Programming the VLT 6000
■■
The VLT 6000 adjustable frequency drive is delivered for installation and setup with the required applica­tion parameters already programmed at the factory. Specific motor nameplate data may have to be entered at the time of setup. The instructions in this section are intended to provide a general under­standing of programming procedures and to enter Quick Menu setup data. See the VLT 6000 Operating Instructions for detailed information.
NOTE:NOTE:
NOTE:
NOTE:NOTE: Quick menu data for commissioning drive cannot be entered via FLN serial bus.
VLT® Adjustable Frequency Drive
during normal operation, and controlling the drive speed during local speed control operation. The keys below the indicator lamps are used for Start/Stop control, selection of the operating location, and reset.
FigurFigur
e 1 e 1
Figur
e 1 VLT 6000 Keypad
FigurFigur
e 1 e 1
VLT
®
Adjustable Frequency Drive
Control Panel
The Local Control Panel (LCP), see Figure 1, is a complete interface for programming and operating the drive. The control panel can be removed from the drive and installed up to 3 meters (10 feet) away using the remote mounting kit.
The control panel has five functions:
- Display
- Keys for changing the display
- Keys for changing programming parameters
- Keys for controlling drive operation
- Indicator lamps
The LCP uses a four-line, alpha-numeric LCD display. The display can show four operating data values and three operating condition values continuously. During programming, all the information required for quick, effective parameter setup of the drive is displayed. All drive parameters can be changed from the control panel. Three lamps indicate power on (ON), warning (WARNING) and alarm (ALARM).
Parameter Change Keys
The LCP keys are divided into groups by function. The keys above indicator lamps are used for parameter setup, selecting the display indication
The DISPLAY MODE key is used to change a display mode or to return to the Display Mode from either the Quick Menu or the Extend Menu mode.
The QUICK MENU key gives access to the parameters available for the Quick Menu setup. Parameters in this menu are the 12 most important setup parameters for the drive.
The EXTEND.MENU key gives access to all parameters.
The CHANGE DATA key is used for changing the value of a selected parameter. To change data, the desired parameter is first selected. The CHANGE DATA key is then pressed to enable editing of the parameter. An underline in the display will move under the parameters value to show that it is being edited.
MG.60.G2.22 - VLT is a registered Danfoss Trademark
5
VLT® Adjustable Frequency Drive
Adjustable Frequency Drive
®
VLT
Local Control
motor or any driven equipment.
Below the indicator lamps on the LCP are keys used to determine control of the drive. Each key can be individually enabled or disabled using parameters 012 through 015. The Hand Start and Auto Start keys are disabled if any of the control terminals are programmed for either Remote Hand or Remote Auto.
201, Output Frequency Low Limit, motor will start and ramp up to this frequency when HAND START key is pressed. If drive is already running in Auto Mode when HAND START is pressed, drive will begin running in Hand Mode and in local control.
The CANCEL key is used if a change of the selected parameter is not to be carried out.
The OK key is used to activate a change to the selected parameter.
The + and - keys are used to scroll through parameters and to increase or decrease the value of a chosen parameter. The keys are also used to change the local reference. In Display Mode, the keys are used to switch between readouts.
The t and u keys are used to select a parameter group and also to move the cursor to the desired digit when
changing numerical values.
Start signal via digital inputs may cause drive to start at any time. Remove power to drive before working on output wiring,
The HAND START key is used to start the drive from the control panel. Pressing HAND START issues a start command to the drive.
If a minimum speed is set in parameter
The OFF/STOP key is used for stopping the connected motor in either the Hand or Auto Mode. Enable or disable this function via parameter 013, OFF/START on LCP. If this stop function is activated, the second line in the LCD display will flash.
AUTO START is used if the drive is to be started via FLN serial communi­cation and/or the digital control terminals. When a remote start signal is received, the drive will start if the AUTO START key has been pressed.
NOTE:NOTE:
NOTE:
NOTE:NOTE: AUTO START key must be pressed to enable starting drive from FLN serial bus or
remote terminals.
RESET is used for manually resetting the drive after an alarm (fault trip). In this case, the top line of the display shows TRIP (RESET). If the top line of the display shows TRIP (AUTO START), the drive will automa­tically restart. If the top line of the display shows TRIPLOCK (DICS.MAINS), input power to the drive must be removed before the trip can be reset.
.
Quick Menu
The QUICK MENU key gives access to 12 of the most important setup parameters of the drive. After Quick Menu programming, in many cases the drive will be ready for operation. The 12 Quick Menu parameters are shown in Table 1. Refer to the VLT 6000 Operating Instructions for a complete description of the functions.
6
MG.60.G2.22 - VLT is a registered Danfoss Trademark
VLT® Adjustable Frequency Drive
Table 1 Quick Menu Items Description
Quick Menu Item Number
1 001 Language Selects language used for all displays.
2 102 Motor Power
3 103 Motor Voltage
4
5 105 Motor Current
6
7
8
9 206 Ramp Up Time
10
11
12
During programming of parameters, mo­tor may start. Be certain no one is in area of motor or driven equipment when changing parameters.
Parameter Name Description
Sets output characteristics of drive based on kW (HP) of motor. See Table 2 to convert HP to kW. Sets output characteristics of drive based on voltage of motor.
104 Motor
Frequency
106 Motor Nominal
Speed
201 Minimum
Frequency
202 Maximum
Frequency
207 Ramp Down
Time
323 Relay 1
Function
326 Relay 2
Function
Sets output characteristics of drive based on nominal frequency of motor. This is typically equal to line frequency. Sets output characteristics of drive based on full load current in amps (FLA) of motor. This sets overload protection for motor. Sets output characteristics of drive based on nominal full load speed of motor. Sets minimum controlled frequency at which motor will run.
Sets maximum controlled frequency at which motor will run.
Sets time to accelerate motor from 0 Hz to nominal motor frequency set in Quick Menu Item 4. Sets time to decelerate motor from nominal motor frequency set in Quick Menu Item 4 to 0 Hz.
Sets function of high voltage Form C relay.
Sets function of low voltage Form A relay.
5. Press Cancel key to disregard change, or press OK key to accept change and enter new setting.
6. Press Display key to return to normal display.
VLT
®
Adjustable Frequency Drive
To Enter or Change Quick Menu Parameter Data
Enter or change parameter data or settings in accordance with the following procedure.
1. Press Quick Menu key.
2. Use ‘+’ and ‘-’ keys to find parameter you chose to edit.
3. Press Change Data key.
4. Use ‘+’ and ‘-’ keys to select correct parameter setting. To move to a different digit within parameter, use t and u arrows.
Flashing underline indicates digit selected to change.
MG.60.G2.22 - VLT is a registered Danfoss Trademark
Example of Changing Parameter Data
Assume parameter 206, Ramp Up Time, is set at 60 seconds. Change the ramp up time to 100 seconds in accordance with the following procedure.
1. Press Quick Menu key.
2. Press “+” key until you reach Parameter 206, Ramp Up Time.
3. Press Change Data key.
4. Press t key twice – hundreds digit will flash.
5. Press “+” key once to change hundreds digit to 1.
6. Press u key once to move cursor to tens digit.
7
7. Press “-” key until ‘6’ counts down to ‘0’ and setting for Ramp Up Time reads 100 s.
8. Press OK key to enter new value into drive controller.
9. Press Display key to return to normal display.
Extended Menu
In some applications, the Quick Menu items will not set up all the desired characteristics of the drive. To access all VLT 6000 parameters, including the Quick
Adjustable Frequency Drive
®
Menu parameters, press the Extend Menu key.
VLT
NOTE:NOTE:
NOTE:
NOTE:NOTE: Programming of parameter functions available
through Extended Menu is done in accor­dance with same procedure as described for Quick Menu functions.
HP/kW Conversion
A conversion index for determining kW and HP ratings is shown in Table 2.
Table 2 HP to kW Conversion Index
kW HP kW HP
0.25 0.33 45 60
0.37 0.5 55 75
0.55 0.75 75 100
0.75 1.0 90 125
1.1 1.5 110 150
1.5 2.0 132 175
2.2 3.0 160 200
3.0 --- 200 300
4.0 5.0 250 ---
5.5 7.5 300 ---
7.5 10 315 350 11 15 355 450 15 20 400 500
18.5 25 450 600 22 30 30 40 37 50
VLT® Adjustable Frequency Drive
VLT 6000 Functional Features
The FLN protocol built into the VLT 6000 adjustable frequency drive allows programming of numerous features and monitoring of the drive via the serial bus and the standard RS-485 port. The VLT 6000 also has the capability to control closed or open loop systems on its own and has been designed specifically for HVAC applications. Always accessible in real-time are the system status, what the motor and drive are doing, and if there are any problems. The VLT 6000 continuously monitors all aspects of motor and drive status and issues alarms or warnings for adverse conditions. The FLN interacts with the drive based upon a point map database and the selected interface strategy. Many, but not all, drive features are accessible through the point map. See the VLT 6000 Operating Instructions for more drive details. Table 8 lists the map points and Table 9 supplies definitions. Below is a review of some frequently used drive features and the associated point map numbers.
Drive Operation (03-14)
These points provide the FLN with operational status information such as output frequency, motor current, output voltage, power and energy. The run time in hours that power has been supplied to the motor is also stored for display, along with cumulative energy used in kWh.
Motor and Drive Thermal Protection (15, 16, 18)
The motor and drive are protected against thermal overload. The percentage of thermal load is dis­played. Point 18 indicates if either the motor or drive thermal limit has been exceeded.
Set-up 1 - 4 (17) (29)
The drive is capable of maintaining four independent program set-ups. Each set-up supports independent point map configurations. Seasonal changes, various acceleration or deceleration rates, or other operation modes can be accommodated. Point 17 indicates which setup is active. The set-up change is programmed through the drive’s keypad or digital I/ Os. Day/night operation is implemented in the point map (29) but is not used in this application.
8
MG.60.G2.22 - VLT is a registered Danfoss Trademark
Current Monitoring and Limits (19, 30)
The maximum current that the drive provides to the motor can be limited. This tends to limit the torgue that can be produced by the motor. Data point 30 sets the current limit in amps, while data point 19 indicates if the motor is operating at that current limit.
Direction of Rotation (21-22)
The drive responds to serial commands to reverse direction of the motor. The drive can safely reverse motor rotation while in operation. Many applications benefit from this ability, such as vane axial fans reversed for smoke extraction or cooling towers for deicing. Parameter 506, Reversing, must be set to serial communication for point 22 to command the feature.
Start/Stop (23, 24)
To run the drive from the FLN or in Auto mode from the drives digital control terminals, a start command must be given at data point 24. When a stop command is given at this point, the drive will only run in Hand mode.
Freeze Mode (25, 26)
If desired, the frequency of the drive can be frozen at its present value. The mode is indicated by data point 25. It is an option available when serial interface is lost.
Coast (27, 28)
The coast command (28) shuts down the inverter and makes the motor freewheeling, which normally brings it to stand still. The drive cannot be restarted in any mode before the coast command is removed. It is, therefore, often used as a safety interlock. Data point 27 indicates when the drive is coasted.
Motor Ramp-up and Ramp-down Rate (31, 32)
The time to accelerate or decelerate the drive between 0 Hz and the motor’s nominal frequency can be programmed. The drive is capable of settings between one to 3600 seconds (one hour).
Lock Panel (33)
The local control panel on the VLT 6000 drive can be locked to ensure that program data or drive control functions cannot be changed locally. The Stop but­ton on the keypad will also be locked out and be
VLT® Adjustable Frequency Drive
incapable of stopping the drive. The serial interface continues to access drive settings.
Hand/Auto Modes (34)
The SEL HND.AUTO shows which mode the drive is in. The drive can be commanded into either Hand or Auto mode by pressing the respective keys on the keypad of the drive. Hand mode disables any pro­grammed control strategies and allows the drive keypad to be used to set the drive speed. The only serial communication command that can override Hand mode is data point 28, CMD COAST.
Run Enable (35)
Set data point 35 to ON to run the drive from the FLN with default drive parameter settings. In the OFF mode, the drive will run only in Hand mode or in Auto mode from the drives digital control terminals. Parameter 505, Start, controls the interaction of point 35 and the digital run command.
Bus Functions (36, 37)
The amount of time the drive will wait between communication packets is programmable. If the time is exceeded, the drive will assume serial communica­tion has stopped and respond with programmable choices. The drive can ignore the loss, freeze its current output, stop, run at a predetermined jog frequency, run at maximum output frequency or stop and trip while issuing an alarm. Wait time is selected at point 36 and the function after a timeout at point
37. See descriptions for parameters 565, FLN Bus
Time Interval and 566, FLN Bus Time Interval Function in the VLT 6000 Operating Instructions.
Frequency Out High, Low Limits (38, 39)
Limits to the maximum and minimum drive output frequency are programmable. For example, pump manufacturers typically recommend not to opera­te pumps below a certain speed (for example, 15 Hz) to avoid seal problems.
Relay Out 1, 2 (40, 41, 43, 44)
Two programmable relay outputs (one Form C, 240 VAC, 2 Amp; and one Form A, 30 VAC, 1 Amp) are available. These can be triggered through the serial bus by command points 40 and 41. This allows the FLN to utilize the drive’s built-in relays as additional network programmable relays. The data points 43 and 44 indicate whether the relay is triggered or not
VLT
®
Adjustable Frequency Drive
MG.60.G2.22 - VLT is a registered Danfoss Trademark
9
VLT® Adjustable Frequency Drive
(On/Off). Parameters 323 and 326, Relay 1 and Relay 2 Output Function, must be set to CONTROL
WORD 11/12.
PID Control Functions (42, 61-65, 68-74)
The VLT 6000 has a sophisticated built-in propor­tional, integral, derivative (PID) controller. The PID controller is activated by setting parameter 100, Configuration, to Closed loop through the drive’s keypad.
®
feedback values and two setpoints. The feedback can be received in the form of network bus signals
VLT
The PID controller in the VLT 6000 supports two
Adjustable Frequency Drive
and/or standard 0-10 V transmitters. The 2 setpoint controller is capable of controlling return fans based on a fixed differential flow, secondary pumping systems, and so on. This can be used to supple­ment the BMS system to save on points or ca­pacity. For details on use of the two feedback/ setpoint feature, refer to the VLT 6000 Operating Instructions. Data points 43 and 44 show the status of an FLN command to the drive.
The points PI GAIN and PI TIME are gain parameters similar to the P and I gains in the FLN TECs. The Danfoss PI loop is structured differently than the Siemens loop, so there is not a one-to-one correspondence between the gains. The following formulas allow translation between Danfoss and Siemens gains.
Sleep Mode (54-59)
Sleep mode automatically stops the drive when demand is low over a period of time. When the system demand increases, the drive restarts the motor to reach the desired output. Sleep mode has great energy savings potential and saves wear and tear on equipment. Unlike a setback timer, the drive is always available to run when a preset wakeup demand is reached. See parameters 403 through 406 in the VLT 6000 Operating Instructions for more detail.
Drive Control Display (80-86)
The operational status of the drive is readily available on the FLN serial interface bus. The drive displays various states including ready to start, waiting for run enable, run, fault reset and stop.
Terminals 53, 54, 60 (87-89)
Two analog voltage input terminals 53 and 54 (0 to 10 VDC) and one analog current terminal 60 (0 to 20 mA) are provided for reference or feedback signals. The applied electrical signal can be read by data points 87 to 89 in volts and mA. This can be very useful during commissioning to calibrate transmitters. This can also be used to convert any other analog transmitter in the installation into a digital bus signal, even if the signal is not used by the drive. In this case, the input terminal should be programmed to No Function so it does not to influence the drive’s operation.
Converting from Danfoss PI gains to Siemens P and I gains:
DANFOSS
DANFOSS
0.0015
GAIN PPPP
GAINGAIN
GAIN
GAIN IIII
GAINGAIN
SIEMENS
SIEMENS
SIEMENSSIEMENS
SIEMENS
SIEMENS
SIEMENSSIEMENS
GAIN PI
PIGAIN
=
GAINGAIN
PIPI
GAIN
GAIN PI
PI
GAINGAIN
PIPI
=
TIME
TIMEPI
PI
TIME TIME
PIPI
DANFOSSDANFOSS
DANFOSS
DANFOSSDANFOSS
DANFOSS
DANFOSS
DANFOSSDANFOSS
0.0015****GAIN
0.00150.0015
DANFOSS
0.0015
0.0015****
0.00150.0015
Converting from Siemens P and I gains to Danfoss PI gains:
667
PI
PIPI
TIME
TIME PI
PI
TIME TIME
PIPI
GAIN PI
GAINGAIN
DANFOSS
DANFOSSDANFOSS
DANFOSS
DANFOSS
DANFOSSDANFOSS
GAIN PPPPGAIN
GAINGAIN
=
GAIN PPPP
GAINGAIN
=
GAIN IIII
GAINGAIN
GAIN
SIEMENS
SIEMENSDANFOSS
SIEMENSSIEMENS
GAIN
SIEMENS
SIEMENS
SIEMENSSIEMENS
SIEMENS
SIEMENS
SIEMENSSIEMENS
667****GAIN
667667
10
Faults, Warnings and Alarms (90-94)
The drive displays a warning or tripped by a fault condition. It also can retrieve the last warning or fault trip for display. The drive can be reset through the FLN serial bus to resume normal drive operation.
Error Status (99)
Data point 99 is implemented in the point map but is not used in this application.
MG.60.G2.22 - VLT is a registered Danfoss Trademark
■■
VLT 6000 Network Strategies
■■
The VLT 6000 drive has its own internal PID closed loop controller. This can be turned on or off, depending on the requirements of the control strategy. A brief summary of possibilities follows. This is meant to illustrate possibilities rather than be all­inclusive. An actual application may combine features from a more than one of these strategies.
Strategy One
FLN FunctionFLN Function
FLN Function – Monitor drive operation
FLN FunctionFLN Function
VLVL
T 6000 ContrT 6000 Contr
VL
T 6000 Contr
VLVL
T 6000 ContrT 6000 Contr
hardwired system
VLVL
T 6000 ModeT 6000 Mode
VL
T 6000 Mode –
VLVL
T 6000 ModeT 6000 Mode
The VLT 6000 follows hard-wired run/stop signals. An external, hard-wired PID controller provides the drive with a speed reference signal. The FLN monitors the operation of the drive without control function.
Network Inputs to the VLNetwork Inputs to the VL
Network Inputs to the VL
Network Inputs to the VLNetwork Inputs to the VL is simply monitoring the operation of the drive, it provides no inputs.
ol ol
ol –
From a conventional,
ol ol
Open Loop
T 6000:T 6000:
T 6000: Because the FLN
T 6000:T 6000:
VLT® Adjustable Frequency Drive
Network Inputs to the VLNetwork Inputs to the VL
Network Inputs to the VL
Network Inputs to the VLNetwork Inputs to the VL The following drive points might be controlled by the FLN.
Speed Command:Speed Command:
Speed Command:
Speed Command:Speed Command: 5353
BUS REFBUS REF
53
BUS REF – This is the speed reference
5353
BUS REFBUS REF command. This is set as a percentage of the drive’s reference range, determined by VLT 6000 parameters 204, Minimum Reference, and 205, Maximum Reference. Setting point 53 to 0 gives the drive a reference command equal to the value stored in parameter 204. Setting point 53 to 16384 gives the drive a reference
command equal to the value stored in parameter 205.Intermediate values for point 53 change the reference linearly between these two values.
NOTE:NOTE:
NOTE:
NOTE:NOTE: In general, any other reference signal is
added to the bus reference. Disable all other drivereference inputs when using a bus reference to control drive speed.
T 6000:T 6000:
T 6000:
T 6000:T 6000:
VLT
®
Adjustable Frequency Drive
Network Outputs frNetwork Outputs fr
Network Outputs fr
Network Outputs frNetwork Outputs fr following points are monitored by the FLN to indicate system status. This list could be expanded or shortened, depending on the requirements of the system.
03 FREQ OUTPUT 08 POWER 10 KWH 23 STOP.RUN 92 OK.FAULT
Strategy Two
FLN FunctionFLN Function
FLN Function – Control all aspects of drive
FLN FunctionFLN Function operation
VLVL
T 6000 ContrT 6000 Contr
VL
T 6000 Contr
VLVL
T 6000 ContrT 6000 Contr
VLVL
T 6000 ModeT 6000 Mode
VL
T 6000 Mode –
VLVL
T 6000 ModeT 6000 Mode
The VLT 6000 follows run/stop and speed reference signals from the FLN. The FLN receives the feedback signal from the controlled system, compares this to a setpoint value, and uses its own PID control loop to determine the required drive speed.
om the VLom the VL
om the VL
om the VLom the VL
ol ol
ol –
From FLN
ol ol
Open Loop
T 6000:T 6000:
T 6000: The
T 6000:T 6000:
Example 1: Example 1:
Example 1: In a pumping application, the
Example 1: Example 1: minimum frequency (point 38 or parameter 201) is set to 18 Hz, and the maximum frequency (point 39 or parameter 202) is set to 60 Hz. You want to command the drive’s speed with a 0 – 100% signal, where 0% commands 18 Hz and 100% commands 60 Hz. To unbundle the bus reference
(point 53) for commanding in percent:
1. Set minimum reference (point 50 or parameter 204) to 18 Hz, the minimum frequency.
2. Set maximum reference (point 51 or
parameter 205) to 60 Hz, the maximum frequency.
3. Intercept = 0 (since the minimum reference value is 0).
4. Slope can be calculated as follows:
MG.60.G2.22 - VLT is a registered Danfoss Trademark
11
VLT® Adjustable Frequency Drive
=
=
=
NOTE:NOTE:
Adjustable Frequency Drive
®
VLT
NOTE:
NOTE:NOTE: Although range listed for point 53 is 32767,
that represents a 200% speed command. Since a 100% speed command is desired here, half of value 32767 is used for range of existing point.
Example 2: Example 2:
Example 2: In a pumping application, the minimum
Example 2: Example 2: frequency (point 38 or parameter 201) is set to 18 Hz, and the maximum frequency (point 39 or parameter 202) is set to 60 Hz. You want to command the drive’s speed with a 0 – 100% signal, where 0% commands 0 Hz and 100% commands 60 Hz. Because the minimum frequency is 30% of maximum speed, speed refe-rence commands from 0 to 30% will cause the drive to run at minimum speed, 18 Hz.
To unbundle the bus reference (point 53) for commanding in percent:
1. Set minimum reference (point 50 or parameter
204) to 0 Hz.
2. Set maximum reference (point 51 or parameter
205) to 60 Hz, the maximum frequency.
3. Intercept = 0 (since the minimum reference
value is 0)
4. Slope can be calculated as follows:
=
=
=
slope
16384
0.0061
slope
16384
0.0061
×
Point) Existing of (Slope Range) (Desired
Point Existing of Range
1100
×
×
Point) Existing of (Slope Range)(Desired
Point Existing of Range
1100
×
Although the action of the reference signal is different in examples 1 and 2, the unbundled reference is the same. This is due to programming minimum and maximum reference values in the drive.
Start/Stop Command: To give a start command from the FLN, the following points must be set. The VLT 6000 can also respond to discrete run/stop control signals that are hard wired to its control terminals. The point used to stop the drive through the FLN determines the capability of these discrete command signals.
2828
CMD COASTCMD COAST
28
CMD COAST – In most cases, it isnecessary
2828
CMD COASTCMD COAST to set this point to NO to make the drive run. If this is set to COAST while the VLT 6000 is running, the drive will shut off immediately and the motor will coast to a stop. When set to COAST, the lower right corner of the drive display shows UN. READY (unit ready). The drive will not start in either HAND mode or through discrete control signals until point 28 is set to NO. VLT 6000 parameter 503, Coasting, can defeat this. See the VLT 6000 Operating Instructions for details. Because point 28 can keep the drive from operating in any mode, this is commonly used to provide a safety interlock function.
2424
CMD STPCMD STP
24
CMD STP
2424
CMD STPCMD STP point to START to make the drive run. If this is set to STOP while the drive is running, the drive will decelerate to a stop. When this is set to STOP, the drive cannot be started using a hardwired discrete run command. It can, however, be started in HAND mode from the keypad.
3535
RUN ENABLERUN ENABLE
35
RUN ENABLE – In most cases, it is
3535
RUN ENABLERUN ENABLE necessary to set this point ON to make the drive run. If this is set to OFF while the drive is running, the drive will decelerate to a stop. When set to OFF, the lower right corner of the display shows STAND BY. When OFF, the drive can be started in HAND mode from the keypad. It can also be started using a hard­wired discrete run command, as when parameter 505, Start, is set to digital input.
.STR.STR
TT
.STR
T – It is necessary the set this
.STR.STR
TT
12
MG.60.G2.22 - VLT is a registered Danfoss Trademark
Network Outputs frNetwork Outputs fr
Network Outputs fr
Network Outputs frNetwork Outputs fr The points listed in Strategy One are commonly used.
Strategy Three
FLN FunctionFLN Function
FLN Function
FLN FunctionFLN Function
VLVL
T 6000 ContrT 6000 Contr
VL
T 6000 Contr
VLVL
T 6000 ContrT 6000 Contr
system, including system feedback
VLVL
T 6000 ModeT 6000 Mode
VL
T 6000 Mode –
VLVL
T 6000 ModeT 6000 Mode The VLT 6000 follows hard-wired run/stop signals.The drive uses its internal PID controller to control motor speed. The feedback signal is hard wired to the VLT 6000 analog input and the setpoint is programmed into the drive. The FLN is used to monitor the status of the drive and the value of the VLT 6000 PID controller setpoint and feedback.
Network Inputs to the VLNetwork Inputs to the VL
Network Inputs to the VL
Network Inputs to the VLNetwork Inputs to the VL FLN is simply monitoring the operation of the drive, it provides no inputs.
Network Outputs frNetwork Outputs fr
Network Outputs fr
Network Outputs frNetwork Outputs fr to the points listed in Strategy One, it may be useful to monitor the following points related to the operation of the VLT 6000 PID controller.
Feedback:Feedback:
Feedback:
Feedback:Feedback: 6060
INPUT REFINPUT REF
60
INPUT REF – This is the setpoint for the
6060
INPUT REFINPUT REF VLT 6000 PID controller in units defined in parameter 415, Units Relating to Closed Loop.
om the VLom the VL
om the VL
om the VLom the VL
Monitor drive operation Monitor drive operation
Monitor drive operation
Monitor drive operation Monitor drive operation
ol ol
ol –
ol ol
om the VLom the VL
om the VL
om the VLom the VL
T 6000:T 6000:
T 6000:
T 6000:T 6000:
From a hard-wired
Closed Loop
T 6000:T 6000:
T 6000: Because the
T 6000:T 6000:
T 6000: T 6000:
T 6000: In addition
T 6000: T 6000:
VLT® Adjustable Frequency Drive
setpoint to the VLT 6000 PID controller. The drive compares the feedback signal with the setpoint and adjusts the speed of the drive accordingly.
Network Inputs to the VLNetwork Inputs to the VL
Network Inputs to the VL
Network Inputs to the VLNetwork Inputs to the VL start/stop control, which was discussed in Strate­gy Two, the FLN provides the drive with feedback and setpoint information using the following points.
Feedback:Feedback:
Feedback:
Feedback:Feedback: 7171
FB MINFB MIN
71
FB MIN - The VLT 6000 can display the PID
7171
FB MINFB MIN controller’s setpoint and feedback signal in units chosen in drive parameter 415, Units Relating to Closed Loop. The value that the minimum feedback signal represents can be set using either point 71 or drive parameter 413, Minimum Feedback.
7272
FB MAX FB MAX
72
FB MAX - The VLT 6000 can display the PID
7272
FB MAX FB MAX controller’s setpoint and feedback signal in units chosen in drive parameter 415. The value that the maximum feedback signal represents can be set using either point 72 or drive parameter 414, Maximum Feedback.
7373
BUS FB 1BUS FB 1
73
BUS FB 1 - A value of 0 represents the
7373
BUS FB 1BUS FB 1 minimum feedback signal, as defined by point 71 or parameter 413. A value of 16383 represents the maximum feedback signal, as defined by point 72 or parameter 414. This should be the feedback used if only one feedback signal is supplied to the drive.
T 6000:T 6000:
T 6000: In addition to
T 6000:T 6000:
VLT
®
Adjustable Frequency Drive
6262
PI FEEDBACKPI FEEDBACK
62
PI FEEDBACK – This is the value of the
6262
PI FEEDBACKPI FEEDBACK feedback signal for the VLT 6000 PID controller in the units defined in parameter 415.
Strategy Four
FLN FunctionFLN Function
FLN Function – Provide the drive with
FLN FunctionFLN Function setpoint and feedback values using the VLT 6000 PID controller to determine motor speed
VLVL
T 6000 ContrT 6000 Contr
VL
T 6000 Contr
VLVL
T 6000 ContrT 6000 Contr
VLVL
T 6000 ModeT 6000 Mode
VL
T 6000 Mode –
VLVL
T 6000 ModeT 6000 Mode
The VLT 6000 follows run/stop signals from the FLN. The FLN receives the feedback signal from the controlled system. It sends this and the desired
MG.60.G2.22 - VLT is a registered Danfoss Trademark
ol ol
ol –
From the FLN
ol ol
Closed Loop
NOTE:NOTE:
NOTE:
NOTE:NOTE: If drive terminal 53 is programmed in
parameter 308, Analog Inputs, for feedback, any signal applied to terminal 53 is added to value provided at point 73. Therefore, it is generally advisable not to program parameter 308 for feedback.
74 BUS FB 274 BUS FB 2
74 BUS FB 2 - This is used when two feedback
74 BUS FB 274 BUS FB 2
signals are supplied to the drive PID controller. VLT 6000 parameter 417, Feedback Function,determines the the function that the drive applies to these signals. Functions include minimum, maximum, sum, difference, and average. A value of 0 represents the minimum
13
VLT® Adjustable Frequency Drive
feedback signal, as defined by point 71 or
parameter 413. A value of 16383 represents the maximum feedback signal, as defined by point 72 or parameter 414. See the VLT 6000 Operating In Istructions for details.
NOTE:NOTE:
NOTE:
NOTE:NOTE:
If drive terminal 54 is programmed in para-
meter 311, Analog Inputs, for feedback,
any signal applied to terminal 54 is added to value provided at point 73. Therefore, it is generally
®
feedback.
advisable not to program parameter 311 for
Adjustable Frequency Drive
VLT
Example: Example:
Example: In a cooling tower application, the feed-
Example: Example: back signal comes from a temperature sensor with a range of 40 2 (point 74) for the temperature sensor:
1. Set minimum feedback (point 71 or parameter 413) to 40.
2. Set maximum feedback (point 72 or parameter 414) 140.
3. Intercept = 40 (since the minimum feedback value is 40)
4. Slope can be calculated as follows:
o
F to 140oF. To unbundle bus feedback
parameter 415. The value that the maximum reference signal represents can be set using either point 51 or drive parameter 205.
6969
SETPOINT 1SETPOINT 1
69
SETPOINT 1 - This is the PID controller’s
6969
SETPOINT 1SETPOINT 1 setpoint, expressed in the units that were chosen in parameter 415. It can be set to any value between REF MIN (point 50 or parameter 204) and REF MAX (point 51 or parameter 205). If an attempt is made to set point 69 to a value outside of this range, the setpoint will not be changed. SETPOINT 1 can also be programmed using parameter 418, Setpoint 1.
7070
SETPOINT 2SETPOINT 2
70
SETPOINT 2 - This PID controller setpoint is
7070
SETPOINT 2SETPOINT 2 used for applications where two feedback signals will be compared to independent setpoints. Refer to the VLT 6000 Operating Instructions for more details. SETPOINT 2 is expressed in the units selected in parameter 415. It can be set to any value between REF MIN (point 50 or parameter 204) and REF MAX (point 51 or parameter 205). If an attempt is made to assign point 70 to a value outside of this range, the setpoint will not change. SETPOINT 2 can also be programmed using parameter 419, Setpoint 2.
slope
=
=
0.00061
=
16383
×
PointExistingofRange
0.140)(140
×
Setpoint: 5050
REF MINREF MIN
50
REF MIN - The VLT 6000 can display the PID
5050
REF MINREF MIN controller’s setpoint and feedback signal in units. The units displayed are chosen in drive parameter 415. The value that the minimum reference signal represents can be set using either point 50 or drive parameter 204.
5151
REF MINREF MIN
51
REF MIN - The VLT 6000 can display the PID
5151
REF MINREF MIN controller’s setpoint and feedback signal in units. The units displayed are chosen in drive
14
PID Controller Adjustments:PID Controller Adjustments:
PID Controller Adjustments:
PID Controller Adjustments:PID Controller Adjustments:
Point) Existing of (Slope Range) (Desired
The following points adjust the operation of the VLT 6000 PID control loop. They are generally set during start-up and only adjusted if changes in the system require it. these values can also be set using parameters. See the VLT 6000 Operating Instructions for more details.
6161
PI STPI ST
ARAR
61
6161
PI ST
PI STPI ST
T FREQ T FREQ
AR
T FREQ (parameter 422) - This
ARAR
T FREQ T FREQ sets the frequency to which the drivewill accelerate after a start command. After it reaches this frequency, the drive will activate its PID controller. Point 61 can have a value between the drive’s minimum frequency (as set in parameter 201) and its maximum frequency (as set in parameter 202). If an attempt is made to set point 61 to a value outside of this range, the drive value will not change.
MG.60.G2.22 - VLT is a registered Danfoss Trademark
6363
PI GAINPI GAIN
63
PI GAIN (parameter 423) - This sets the value
6363
PI GAINPI GAIN of proportional gain for the VLT 6000 PID controller. It can have a value between 0 and
10.
6464
PI I TIMEPI I TIME
64
PI I TIME (parameter 424) - This sets the
6464
PI I TIMEPI I TIME integral time for the VLT 6000 PID controller. It can have a value between 0.01 seconds and 9999 (OFF). In order for the controller to function properly, this should not be rned off.
6565
PI GAIN LIMITPI GAIN LIMIT
65
PI GAIN LIMIT (parameter 426) - This sets
6565
PI GAIN LIMITPI GAIN LIMIT the maximum derivative gain for the VLT 6000 PID controller. It can have a value between 5 and 50.
6666
LOWPLOWP
66
6666
6868
68
6868
ASS FLASS FL
LOWP
ASS FL
LOWPLOWP
ASS FLASS FL the time constant for the noise filter in the VLT 6000 PID controller feedback loop. It can have values between 0.01 and 10 seconds.
FB FUNCTIONFB FUNCTION
FB FUNCTION (parameter 417) - This sets
FB FUNCTIONFB FUNCTION how the VLT 6000 PID controller responds to the drive’s two feedback signals. Its value is an integer between 0 and 6. Refer to the VLT 6000 Operating Instructions for the list of choices and an explanation of each.
TRTR
TR (parameter 427) - This sets
TRTR
VLT® Adjustable Frequency Drive
the trip. VLT 6000 parameter 503, Coasting Stop, determines the interaction of these two safety interlocks. See the VLT 6000 OperatingInstructions for details.
Analog Input Monitoring:
Points 87, 88 and 89 can be used to monitor the value of the analog control signals applied to terminals 53, 54 and 60. These points are active even when NO FUNCTION is programmed for the analog input of the drive. As a result, it is possible to use the VLT 6000 analog inputs as analog input for the FLN.
Drive Relay Control:
While relay 1 and 2 in the VLT 6000 usually provide drive status indications, these indications are generally not needed when the drive is connected to an FLN. In some applications, it can be useful to have the FLN control these relays. For example, by controlling one of the relays, the FLN could select the active pump in a pump sequencing system. For the FLN to control a drive relay, the appropriate VLT 6000 parameter (323 or 326) must be set to CONTROL WORD 11/12. Setting point 40 or 41 to ON will then activate the corresponding relay.
VLT
®
Adjustable Frequency Drive
Network Outputs frNetwork Outputs fr
Network Outputs fr
Network Outputs frNetwork Outputs fr listed in Strategy One are commonly used.
■■
VLT 6000 Special Functions
■■
In addition to the control strategies described above, the VLT 6000 provides additional control flexibility to allow it to integrate into special control systemrequirements. The following are just a few examples.
Safety Interlock:
The VLT 6000 can accept a safety interlock stop command that is hard-wired to the drive control terminals and another from the FLN. When VLT 6000 parameter 304, Digital Inputs, is set to SAFETY INTERLOCK, an open hard-wired safety interlock will cause the drive to display ALARM 60 EXTERNAL FAULT. Setting point 28 to COAST will display UN. READY in the lower right corner of the drive’s display. The individual displays for each allow the operator to determine which device caused
om the VLom the VL
om the VL
om the VLom the VL
T 6000:T 6000:
T 6000: The points
T 6000:T 6000:
■■
Network Connection
■■
Connect the VLT 6000 to the FLN in accordance with the following procedure (see Figure 2).
1. Connect signal wires to terminal 68 (P+) and terminal 69 (N-) on main control board of drive. (See tightening torque and wire size in Table 3.)
2. If shielded cabling is used, connect one end of shield to terminal 61. This terminal is connected to ground via an internal RC link.
NOTE:NOTE:
NOTE:
NOTE:NOTE: It is recommended to use shielded, twisted­pair cables to reduce noise between
conductors.
Table 3 Tightening Torque and Wire Gage
Torque Specs
Control wire
4.5 in Ib/0.5 Nm
18 24 AWG, shielded, twisted pair/1.5 mm, shielded twisted pair
MG.60.G2.22 - VLT is a registered Danfoss Trademark
15
VLT® Adjustable Frequency Drive
Adjustable Frequency Drive
®
Hardware Setup
VLT
A terminator dip switch on the main control board
of the VLT the FLN bus. It is used for serial communication and to connect and disconnect the drive’s digital inputs
NOTE:NOTE:
NOTE:
NOTE:NOTE: Terminator switch positions must be set correctly in accordance with Table 4 for
proper FLN serial communacation.
Figure 2 Network Terminal Connection
from the drive’s internal DC power supply. The
6000 is used to configure the drives on
switch positions shown in Figure 3 demonstrate the factory setting. Table 4 lists the switch functions and settings required for FLN operation.
Figure 3 VLT 6000 Terminator Switch Factory Setting
Table 4. Terminator Switch Functions and FLN Settings
Switch Setting
Switch 1 No function Switches 2 & 3 Used for terminating an RS-485 interface. On ffffir
irsssstttt and llllaaaasssstttt
irir devices in a multiple device network, or on the oooonnnnllllyyyy device in a single device network, switches 2 and 3 must be OOOONNNN.
On aaaalllll
l ooootttthhhheeeer
r ddddeeeevvvviiiicccces
l l
es in a multiple device network, 2 and 3
r r
eses
must be OOOOFFFFFFFF.
Switch 4 Separates the common of the internal 24 VDC power supply
from the common of the digital inputs.
Normally this switch is ON and the power supply is present at terminals 12 and 13 for digital inputs. When OFF, the negative of an external power supply is connected to terminal 20 and the positive output is used to turn on the desired digital inputs (terminals 16, 17, 18, 19, 27, 29, 32, and 33).
16
MG.60.G2.22 - VLT is a registered Danfoss Trademark
VLT® Adjustable Frequency Drive
Electrical Control Terminals
In most cases, the VLT 6000 will have electrical control connections (see Figure 4) already connected at equipment installation. The functional description of the drive’s electrical control terminals in Table 5 are provided primarily for system modification and expansion. Two examples of typical
Table 5 Electrical Control Terminals Functional Description
Number Function
01, 02, 03 Form C relay output. Maximum 240 VAC, 2 A. Minimum 24 VDC, 10 mA or 24 VAC, 100 mA.
(Terminal group 01, 02, and 03 is placed in various locations on the power side of the drive, depending upon the model type.)
04, 05 30 VAC, 42.5 VDC, 1 Amp relay outputs can be used for indicating status and warnings. 12, 13 Voltage supply to digital inputs and external transducers. For the 24 VDC to be used for digital
inputs, switch 4 on the control card must be closed (position on). The maximum output current is 200 mA.
16 - 33 Digital inputs. R = 2 kohm
<5 V = logical 0
>10 V = logical 1 16 - 33 30 VAC, 42.5 VDC, 1 A relay output can be used for indicating status and warnings.
20 Voltage supply to digital inputs and external transducers. For the 24 VDC to be used for digital
inputs, switch 4 on the control card must be closed (position on). The maximum output current
is 200 mA.
39 Digital inputs. R = 2 kohm. <5 V = logical 0 , >10 V = logical 1 42, 45 Analog and digital outputs for indicating frequency, reference, current and torque. The analog
signal is 0 to 20 mA, or 4 to 20 mA at a maximum of 500 ?. The digital signal is 24 VDC at a
minimum of 600 ?. 50 10 VDC, 17 mA maximum analog supply voltage to potentiometer and thermistor.
serial interface control connections are demonstrated in Figures 5 and 6. Many of these terminals have multiple functions that are determined by drive parameter settings. See the VLT 6000 Operating Instructions for detailed information.
VLT
®
Adjustable Frequency Drive
53, 54 0 to 10 VDC voltage input, R = 10 ?.
55 Common for analog inputs. This common is isolated from the common of all other power
supplies. If, for example, the drive s 24 VDC power supply is used to power an external
transducer which provides an analog input signal, terminal 55 must be wired to terminal 39.
60 0 to 20 mA or 4 to 20 mA, analog current input, R = 188 ? . 61 Shield for serial communication.
68, 69 RS-485 interface and serial communication. When the drive is connected to an R -485 serial
communication bus, DIP switches 2 and 3 must be closed on the first and the last device in the
serial connection. On the remaining drives, switches 2 and 3 must be open. The factory setting
is closed (position on).
MG.60.G2.22 - VLT is a registered Danfoss Trademark
17
Adjustable Frequency Drive
®
VLT® Adjustable Frequency Drive
VLT
Typical Control Connection Examples
TT
ransmitter Connection:ransmitter Connection:
T
ransmitter Connection:
TT
ransmitter Connection:ransmitter Connection: The drive’s internal 24 VDC power supply is used to power an external 4 to 20 mA transducer (see Figure 5).
Figure 4 Electrical Control Terminals
TT
wo Feedback Signals:wo Feedback Signals:
T
wo Feedback Signals:
TT
wo Feedback Signals:wo Feedback Signals: The drive processes two independent feedback signals during closed loop operation (see Figure 6). It can respond to the sum, difference, average, minimum or maximum of these signals.
FigurFigur
e 5e 5
Figur
e 5 Transmitter Connection
FigurFigur
e 5e 5
Set Parameter 314, Terminal 60, Analog Input Current, to correspond to the purpose of the 4 to 20 mA signal. Set Parameter 315, Terminal 60, Min. Scaling, to 4 mA. Set Parameter 316, Terminal 60, Max. Scaling, to 20 mA. Because the commons of the +24 VDC power supply and the input reference follower have separate circuit commons, it is necessary to connect a jumper between terminals 39 and 55.
18
FigurFigur
e 6e 6
Figur
e 6 Two Feedback Signals Connection
FigurFigur
e 6e 6
Set Parameter 308, Terminal 53, Analog Input Voltage, to FEEDBACK. Set Parameter 311, Terminal 54, Analog Input Voltage, to FEEDBACK Set Parameter 417, Feedback Function, for the desired operation.
MG.60.G2.22 - VLT is a registered Danfoss Trademark
VLT® Adjustable Frequency Drive
■■
Parameter Settings
■■
The VLT 6000 has a unique FLN address which is transmitted over the RS-485 serial bus. The network will recognize the drive, which may then be programmed for setup options. The parameters listed in Table 6 need to be set for each drive on the FLN network. FLN communication related parameters can only be set through the LCP keypad.
Table 6 VLT 6000 Parameter Settings
Parameter Description Default Desired setting
*500 Protocol FC FLN
*501 Address 1 1 through 98
*502 Baud Rate 9600 4800 or 9600 **503 Coasting Logic or **504 DC-brake Logic or **505 Start Logic or **506 Reversing Digital **507 Selection of setup Logic or **508 Selection of preset ref. Logic or
565 FLN Time Interval 60 sec 1 - 65534 sec 566 FLN Time Interval Function Off
* Minimum parameters which must be set to operate the VLT 6000 via FLN serial interface.
** When Digital input or Logic or is selected, digital inputs may interfere with serial bus
commands. The setting Serial communication allows serial bus commands only to be
carried out. See the VLT 6000 Operating Instructions for detailed descriptions.
NOTE:NOTE:
NOTE:
NOTE:NOTE: As a minimum, it is required to set
parameter 500, Protocol, to FLN; parameter 501, Address, to the proper address; and parameter 502, Baud Rate, to the proper baud rate. (See Programming the VLT 6000 in this manual.)
Parameters 503 through 508 are options that select control of the drive through the digital and/or the FLN serial port. Parameter 565, FLN Time Interval, and 566, FLN Time Interval Function, can be commanded by the data points 36 and 37 (see Table 9).
VLT
®
Adjustable Frequency Drive
NOTE:NOTE:
NOTE:
NOTE:NOTE: Drive can store preset references
programmed in parameters 211 through 214, Preset Reference (1-4). To avoid these values modifying serial bus references, set parameter 210, Reference Type, to
External/preset. See VLT 6000 Operating Instructions for detailed description.
MG.60.G2.22 - VLT is a registered Danfoss Trademark
19
VLT® Adjustable Frequency Drive
Startup of FLN Control
This procedure assumes that the VLT 6000 adjustable frequency drive has been installed properly and is operational in Hand control mode. It also assumes the Siemens FLN data bus is connected to an operational controller. Start the VLT 6000 in accordance with the following procedure.
1. Ensure that the assumptions in this procedure are correct.
Adjustable Frequency Drive
®
2. Check that the network connections are
VLT
securely fastened in accordance with Figure 2.
3. Apply power to the VLT 6000.
4. Ensure that the minimum settings listed in Table 6 are selected.
Verify compliance with all safety require­ments listed in this manual.
Faults, Warnings and Alarms
DANGER:
A stopped motor may start unexpectedly
if faults occur in electronics of drive, or if an active fault clears, such as a fault in supply AC line, or fault in motor connection, or overload.
The VLT 6000 adjustable frequency drive outputs faults, warnings and alarms on the FLN serial bus in a numerical code. The code numbers are described in Table 7. The Reset key is used for manually resetting the drive after an alarm (fault trip). In this case, the top line of the display will show TRIP (RESET). If the top line of the display shows TRIP (AUTO START), the drive will automatically restart. If the top line of the display shows TRIPLOCK (DISC. MAINS), input power to the drive must be cycled off and on again before the trip can be reset.
Refer to the VLT 6000 Operating Instructions for detailed descriptions.
5. Ensure that the switch positions in Figure 3 are set correctly.
6. Optional settings may be changed to meet or enhance the drive’s operation, depending on the application requirements.
7. For FLN control of the drive, press the AUTO START key on the VLT 6000 LCP keypad. Drive operation can then be controlled through the host network device in accordance with its operation instructions.
NOTE:NOTE:
NOTE:
NOTE:NOTE: Default setting for point number 35, Run
Enable, is OFF. Drive will not operate until
Run Enable ON signal is given through serial
communication network.
20
MG.60.G2.22 - VLT is a registered Danfoss Trademark
VLT® Adjustable Frequency Drive
TT
able 7 able 7
T
able 7 Faults, Warnings and Alarms Description
TT
able 7 able 7
Fault Description Warning Alarm
number
1 10 volts low X 2 Live zero X X 4 AC power failure X X X 5 DC link voltage hig X 6 DC link voltage low X 7 Over voltage X X 8 Under voltage X X
9 Inverter time X X 10 Motor time X X 11 Motor thermistor X X 12 Current limit X X 13 Over current X X 14 Ground fault X X 15 Switch mode fault X X 16 Current short circuit X X 17 Serial comm. timeout X X 18 HPFB timeout X X 19 EEPROM on power card X 20 EEPROM o control card X 22 AMA fault X 29 Heat sink temperature too high X X 30 Motor phase U missing X 31 Motor phase V missing X 32 Motor phase W missing X 34 HPFB comm. fault X X 37 Inverter fault X X 39 AMA check par. 104, 106 X 40 AMA check par. 103, 105 X 41 AMA motor too big X 42 AMA motor too small X 60 External fault X 61 Output frequency low X 62 Output frequency high X 63 Output current lo X X 64 Output current high X 65 Feedback low X 66 Feedback hig X 67 Reference low X 68 Reference high X 69 Thermal Auto derating X 99 Unknown alarm X X
1) Trip: Requires a reset, either manual or automatic, depending on the the setting of parameter 400, Reset Function.
2) Trip lock: Requires AC power cycled on and off and a reset. Alarms that also have a corresponding warning cannot be reset until warning has been removed, i.e., fault situation is gone.
Points 90-91 refer to warnings. Points 92-94 refer to alarms.
Trip1) Trip Lock
2)
VLT
®
Adjustable Frequency Drive
MG.60.G2.22 - VLT is a registered Danfoss Trademark
21
Point Mapping Table
The VLT 6000 parameters, along with the internal variables and readouts for controlling the drive via the FLN serial bus, are organized as a Point Map. Not all parameters and readouts are supported by the FLN protocol. FLN points 01, 02, 20, 29 and 99
TT
able 8able 8
T
able 8 Point Mapping
TT
able 8able 8
VLT® Adjustable Frequency Drive
are predefined. Available points and a description of their characteristics are listed in Table 8. Parameters which can be written to (“W” in the Read/Write column) are programmable through the FLN device, others (“R”) are read-only, or read and write (“R/W”).
Point
Number
Adjustable Frequency Drive
®
VLT
01 CTLR ADDRESS 1 -- 1 0 255 -- -- R 501 Pre-
02 APPLICATION 2709 -- 1 0 255 -- -- R -- Pre-
{03} FREQ OUTPUT 0 HZ 0.1 0 16383 -- -- R 512 LAI
{06} CURRENT 0 A 0.1 0 16383 -- -- R 514 LAI
{08} POWER 0 KW 1 0 511 -- -- R 515 LAI
{10} KWH 0 KWH 3.1 0 32767 -- -- R 602 LAI
{12} RUN TIME 0 HRS 4.0 0 32767 -- -- R 601 LAI
{13} DC BUS VOLT 0 VOLTS 1 0 1023 -- -- R 518 LAI
{14} OUTPUT VOLT 0 VOLTS 1 0 1023 -- -- R 517 LAI
{15} MOTOR THERM 0 PCT 1 0 255 -- -- R 519 LAI
{16} DRIVE THERM 0 PCT 1 0 255 -- -- R 520 LAI
{17} CURR. SETU 0 -- 1 0 255 -- -- R -- LAI
{18} TIMERS STAT 0 -- -- -- -- LIMIT OK R 527-15 LDI
{19} CURRENT STAT 0 -- -- -- -- LIMIT OK R 527-14 LDI
20 OVRD TIME 1 HRS 1 0 255 -- -- W -- Pre-
{21} FWD.REV FWD -- -- -- -- REV FWD R 532-8 LDI
{22} CMD FWD.REV FWD -- -- -- -- REV FWD W Cmd-15 LDO
{23} STOP.RUN STOP -- -- -- -- RUN STOP R 527-11 LDI
{24} CMD STP.STRT STOP -- -- -- -- START STOP W Cmd-4 LDO
{25} FREEZE OUT NO -- -- -- -- FREEZE NO R 532-16 LDI
{26} CMD FREEZE FREEZE -- -- -- -- NO FREEZE W Cmd-5 LDO
{27} COAST COAST -- -- -- -- NO COAST R 530-3 LDI
{28} CMD COAST COAST -- -- -- -- NO COAST W Cmd-3 LDO
29 DAY.NIGHT
{30} CURRENT LIM
{31} ACCEL TIME 1 Note 4 SEC 1 1 4095 -- -- R/W 206 LAO
{32} DECEL TIME 1 Note 4 SEC 1 1 4095 -- -- R/W 207 LAO
22
Descriptor
Note 2
Note 3
Factory
Default
(SI Units)
DAY -- -- -- 255 NIGHT DAY W -- Pre-
Note 4 A 0.1 0.1 16383 -- -- W 215 LAO
SI Units Slope
(SI Units)
Readout Points
Status and Command Points
Common Configuration Points
Intercept (SI Units)
Range On Text Off Text
Read/
Write
Param.
number
Network
Type
Note 1
defined
defined
defined
defined
MG.60.G2.22 - VLT is a registered Danfoss Trademark
Port
VLT® Adjustable Frequency Drive
Point
Number
Descriptor
Factory
Default
(SI Units)
SI Units Slope
(SI Units)
Intercept (SI Units)
Range On Text Off Text
Read/
Write
Param.
number
Network
Port
Type
Note 1
{33} LOCK PANEL
{34} SEL HND.AUTO HAND -- -- -- -- AUTO HAND R 532-13 LDI
{35} RUN ENABLE OFF -- -- -- -- ON OFF W Cmd-6 LDO {36} BUS TIME 60 SEC 2 2 32767 -- -- R/W 565 LAO
{37} BUSTIME FUNC 0
{38} F OUT LOW
{39} F OUT HIGH
{40} RELAY OUT 1 OFF -- -- -- -- ON OFF W Cmd-11 LDO {41} RELAY OUT 2 OFF -- -- -- -- ON OFF W Cmd-12 LDO {42} PI STRT FR. 0 HZ 0.1 0 16383 -- -- R 422 LAI
{43} RELAY 1 STA OFF -- -- -- -- ON OFF R 530-11 LDI {44} RELAY 1 STA OFF -- -- -- -- ON OFF R 530-12 LDI
{45} CURR. LIM.S Note 4 A 0.1 0.1 16383 -- -- R 215 LAI {46} F OUT LOW.S 0 HZ 0.1 0 16383 -- -- R 201 LAI
{47} F OUT HIGH.S Note 4 HZ 0.1 0 16383 -- -- R 202 LAI {48} REF MIN.S 0 UNIT 0.1 -1638.3 32767 -- -- R 204 LAI
{49} REF MAX.S Note 4 UNIT 0.1 -1638.3 32767 -- -- R 205 LAI
{50} REF MIN
{51} REF MAX
{52} REF STAT OFFREF -- -- -- -- ON.REF OFFREF R 527-8 LDI {53} BUS REF 0 -- 1 0 32767
{54} SLEEP FREQ.S 0 HZ 0.1 0 16383 -- -- R 404 LAI
{55} WAKEUP FRQ.S Note 4 HZ 0.1 0 16383 -- -- R 405 LAI {56} SLEEP TIME 301 SEC 1 0 511 -- -- R 403 LAI
{57} SLEEP FREQ
{58} WAKEUP FREQ
{59} SLEEP MODE OFF -- -- -- -- SLEEP OFF R 532-3 LDI
{60} INPUT REF 0 UNIT 0.1 -1638.3 32767 -- -- R 510 LAI
{61} PI STRT FREQ
{62} PI FEEDBACK 0 UNIT 0.1 -1638.3 32767 -- -- R 511 LAI {63} PI GAIN 0.3 -- 0.01 0 1023 -- -- R/W 423 LAO
{64} PI I TIME 9999 SEC 0.3051543 0.01 32767 -- -- R/W 424 LAO
Note 5
Note 3
Note 3
Note 3
Note 3
Note 3
Note 3
Note 3
OPEN -- -- -- -- LOCK OPEN R/W 12-15 LDO
-- 1 0 255 -- -- R/W 566 LAO
Note 6
0 HZ 0.1 0 16383 -- -- W 201 LAO
Note 4 HZ 0.1 0 16383 -- -- W 202 LAO
Physical Output Points
Setpoint Related Points
0 UNIT 0.1 -1638.3 32767 -- -- W 204 LAO
Note 4 UNIT 0.1 -1638.3 32767 -- -- W 205 LAO
0 HZ 0.1 0 16383 -- -- W 404 LAO
Note 4 HZ 0.1 0 16383 -- -- W 405 LAO
PI Loop Related Points
0 HZ 0.1 0 16383 -- -- W 422 LAO
-- -- R/W -- LAO
Note 7
VLT
®
Adjustable Frequency Drive
MG.60.G2.22 - VLT is a registered Danfoss Trademark
23
VLT® Adjustable Frequency Drive
Point
Number
{65} PI GAIN LIM 5 -- 0.1 0 511 -- -- R/W 426 LAO
{66} LOWPASS FLTR 0.01 SEC 0.01 0 1023 -- -- R/W 427 LAO
{67} SLEEP BOOST OFF -- -- -- -- BOOST OFF R 532-2 LDI
{68} FB FUNC 1
{69} SETPOINT 1
Adjustable Frequency Drive
®
VLT
{70} SETPOINT 2
{71} FB MIN
{72} FB MAX
{73} BUS FB 1 0 -- 1 0 16383 -- -- R/W 535 LAO
{74} BUS FB 2 0 -- 1 0 16383 -- -- R/W 536 LAO
{75} AUTO RAMP OFF -- -- -- -- ACTIVE OFF R 532-0 LDI
{76} VOLT STAT OK -- -- -- -- LIMIT OK R 527-13 LDI
{77} INVERT STA OK -- -- -- -- STALL OK R 527-12 LDI
{78} FREQ STAT OUTRNG -- -- -- -- IN.RNG OUTRNG R 527-10 LDI
{79} CTRL STAT LOCAL -- -- -- -- BUS LOCAL R 527-9 LDI
{80} DRV ENA STAT NOTENA -- -- -- -- ENABLE NOTENA R 527-2 LDI
{81} DRV RDY STAT NOTRDY -- -- -- -- READY NOTRDY R 527-1 LDI
{82} DRVCTRL STAT NOTRDY -- -- -- -- READY NOTRDY R 527-0 LDI
{84} RESET NO -- -- -- -- RESET NO R 530-7 LDI
{85} START OFF -- -- -- -- ON OFF R 530-6 LDI
{86} Q.STOP Q.STOP -- -- -- -- NO Q.STOP R 530-4 LDI
{87} TERM 53 0 VOLTS 0.1 0 255 -- -- R 522 LAI
{88} TERM 54 0 VOLTS 0.1 0 255 -- -- R 523 LAI
{89} TERM 60 0 MILAMP 0.1 0 255 -- -- R 524 LAI
{90} OK.WARNING OK -- -- -- -- WARN OK R 527-7 LDI
{91} LAST WARNING 0
{92} OK.FAULT OK -- -- -- -- FAULT OK R 527-3 LDI
{93} LAST FAULT 0
{94} RESET FAULT NO -- -- -- -- RESET NO W -- LDO
{95} SETPOINT 1.S 0 UNIT 0.1 -1638.3 32767 -- -- R 418 LAI
{96} SETPOINT 2.S 0 UNIT 0.1 -1638.3 32767 -- -- R 419 LAI
{97} FB MIN.S 0 UNIT 0.1 -1638.3 32767 -- -- R 413 LAI
{98} FB MAX.S 100.0 UNIT 0.1 -1638.3 32767 -- -- R 414 LAI
99 ERROR STATUS
24
Descriptor
Note 3
Note 3
Note 3
Note 3
Note 2
Factory
Default
(SI Units)
Note 6
100.0 UNIT 0.1 -1638.3 32767 -- -- W 414 LAO
Note 8
Note 8
SI Units Slope
(SI Units)
-- 1 0 255 -- -- R/W 417 LAO
0 UNIT 0.1 -1638.3 32767 -- -- W 418 LAO
0 UNIT 0.1 -1638.3 32767 -- -- W 419 LAO
0 UNIT 0.1 -1638.3 32767 -- -- W 413 LAO
Miscellaneous Points
Error Related Points
-- 1 0 255 -- -- R -- LAI
-- 1 0 255 -- -- R 615 LAI
0 -- 1 0 255 -- -- R -- Pre-
Intercept
(SI Units)
Range On Text Off Text
Read/
Write
Param.
number
Network
Port
Type
Note 1
defined
MG.60.G2.22 - VLT is a registered Danfoss Trademark
Point Mapping Table Notes:
VLT® Adjustable Frequency Drive
VLT
Point numbers that appear in brackets { } may be unbundled at the field panel.
Note 1:Note 1:
Note 1:
Note 1:Note 1:
Note 2:Note 2:
Note 2: Points 29 and 99 are present but not used in this application.
Note 2:Note 2:
Note 3:Note 3:
Note 3: These points will accept any value within the range of the point even though the drive has
Note 3:Note 3:
LAI stands for Logical Analog Input. This is an analog value that the VLT 6000 provides to the FLN network. Itsvalue is a feedback indicating the status of a physical input to the drive. LAO stands for Logical Analog Output. This is an analog output from the FLN network to the VLT 6000. It is used to control the operation of the drive. LDI stands for Logical Digital Input. This is a digital (ON/OFF) signal from the VLT 6000 to the FLN network. It indicates the operation of the drive. LDO stands for Logical Digital Output. This is a digital (ON/OFF) signal from the FLN network to the VLT 6000. It is used to control or indicate the operation of the drive.
different upper and/or lower limits for these points. This is because the upper and lower limits for these points can vary depending on settings of other points or the drive size. Consult the VLT 6000 Operating Instructions for values.
Twelve special read-only points can be used for checking if the value actually changed or the change was rejected. These 12 read-only points should also be used for monitoring database COVs which the others cannot.The read-only points are designated by a descriptor similar to the original point with a suffix .S added.
®
Adjustable Frequency Drive
Below is a list of pairing where the points in parenthesis are the read-only points: 30 (45), 38 (46), 39 (47), 50 (48), 51 (49), 57 (54), 58 (55), 61 (42), 69 (95), 70 (96), 71 (97), 72 (98).
Note 4:Note 4:
Note 4: The default value depends on the drive. Consult the VLT 6000 Operating Instructions for values.
Note 4:Note 4:
Note 5:Note 5:
Note 5: When LOCK PANEL is set to LOCK, the Hand Start, Off Stop, Auto Start and Reset
Note 5:Note 5:
keys on the VLT 6000 keypad will be disabled. Four parameters in the drive will change simultaneously. Local programming of the drive will also be locked except for parameter 016, Lock for Data Change, which can disable the programming lock.
Note 6:Note 6:
Note 6: Consult the VLT 6000 Operating Instructions for choice options.
Note 6:Note 6:
Note 7:Note 7:
Note 7: The number 32767 equals 200% of Bus Ref range value.
Note 7:Note 7:
Note 8:Note 8:
Note 8: Use Table 7, Faults, Warnings and Alarms, to determine the FAULT or WARNING corresponding
Note 8:Note 8:
to a number.
MG.60.G2.22 - VLT is a registered Danfoss Trademark
25
VLT® Adjustable Frequency Drive
Point Database Definitions
Point Descriptor Definition Number
01 CTLR ADDRESS Predefined device address. 02 APPLICATION Predefined FLN application for use with VLT 6000 drive. 03 FREQ OUTPUT Displays drive speed in hertz. 06 CURRENT Displays drive output current in amps. 08 POWER Displays drive power output in kilowatts. 10 KWH Displays drive cumulative energy output in kilowatt-hours. 12 RUN TIME Displays number of hours drive has supplied power to motor. 13 DC BUS VOLT Displays drive voltage at DC bus in DC volts.
Adjustable Frequency Drive
®
VLT
14 OUTPUT VOLT Displays output voltage to motor in AC volts. 15 MOTOR THERM Displays motor thermal load in percentage. 16 DRIVE THERM Displays drive thermal load in percentage. 17 CURR. SETUP Displays parameter setup number currently controlling drive. 18 TIMERS STAT Displays if temperature limit of motor, drive or motor thermistor has been exceeded. 19 CURRENT STAT Displays if drive is operating in current limit. 20 OVRD TIME Not used. 21 FWD.REV Displays direction of motor rotation, forward or reverse. 22 CMD FWD.REV Commands direction of motor rotation. 23 STOP.RUN Displays drive RUN/STOP status. 24 CMD STP.STRT Commands drive to start or stop. 25 FREEZE OUT Displays if output frequency is in freeze mode at present value. 26 CMD FREEZE Commands drive to freeze present output frequency. 27 COAST Displays if drive has been given a coast to stop command. 28 CMD COAST Commands drive to make motor coast to a stop. 29 DAY.NIGHT Selects day or night mode. (Has no effect on drive operation.) 30 CURRENT LIM Sets maximum drive output current to motor in amps. 31 ACCEL TIME 1 Sets motor ramp up time in seconds. 32 DECEL TIME 1 Sets motor ramp down time in seconds. 33 LOCK PANEL Used to lock out Hand Start, Off/Start, Auto Start and Reset keys on LCP. 34 SEL HAND.AUTO Displays operation in Hand or Auto control mode function. 35 RUN ENABLE Used to enable or disable drive operation in auto mode. 36 BUS TIME Sets time limit to determine loss of serial communication in seconds. 37 BUSTIME FUNC Selects drive response to loss of serial communication. 38 F OUT LOW Sets minimum drive output frequency. 39 F OUT HIGH Sets maximum drive output frequency. 40 RELAY OUT 1 Controls drive relay output 1. Note: Set relay output to corresponding function. 41 RELAY OUT 2 Controls drive relay output 2. Note: Set relay output to corresponding function. 42 PI STRT FR.S Displays status of point 61. 43 RELAY 1 STAT Displays status of FLN command to drive relay output 1. 44 RELAY 2 STAT Displays status of FLN command to drive relay output 2. 45 CURR. LIM.S Displays status of point 30. 46 F OUT LOW.S Displays status of point 38. 47 F OUT HIGH.S Displays status of point 39. 48 REF MIN.S Displays status of point 50. 49 REF MAX.S Displays status of point 51. 50 REF MIN Sets lowest frequency reference value for drive. 51 REF MAX Sets highest frequency reference value for drive. 52 REF STAT Displays if drive is running at commanded reference.
TT
able 9able 9
T
able 9 Point Database Definitions
TT
able 9able 9
26
MG.60.G2.22 - VLT is a registered Danfoss Trademark
VLT® Adjustable Frequency Drive
Point Descriptor Definition
Number
53 BUS REF Sends drive an external reference signal in percent. 54 SLEEP FREQ.S Displays status of point 57. 55 WAKEUP FREQ.S Displays status of point 58. 56 SLEEP TIME Displays run time at low speed before sleep mode starts. 57 SLEEP FREQ Sets output frequency required to activate sleep mode timer. 58 WAKEUP FREQ Sets command frequency required to restart motor after sleep mode. 59 SLEEP MODE Displays when drive is stopped in sleep mode. 60 INPUT REF Displays drive input reference in Hz or as selected in parameter 415. 61 PI STRT FREQ Sets drive frequency after start at which PID control is activated. 62 PI FEEDBACK Displays resulting feedback value in units selected in parameter 415. 63 PI GAIN Sets proportional gain of PID controller in percentage. 64 PI TIME Sets integral time of PID controller in seconds. 65 PI GAIN LIM Sets maximum gain for differentiator of PID controller. 66 LOWPASS FILTER Sets lowpass filter time constant for feedback circuit. 67 SLEEP BOOST Displays sleep boost set point in percentage. 68 FB FUNC Selects calculation method when two feedback signals are used. 69 SETPOINT 1 Sets setpoint for feedback 1 in units selected in parameter 415. 70 SETPOINT 2 Sets setpoint for feedback 2 in units selected in parameter 415. 71 FB MIN Sets minimum feedback signal value in units selected in parameter 415. 72 FB MAX Sets maximum feedback signal value in units selected in parameter 415. 73 BUS FB 1 Supplies feedback value for bus feedback 1 in percent. 74 BUS FB 2 Supplies feedback value for bus feedback 2 in percent. 75 AUTO RAMP Displays when drive deceleration rate is extended due to auto ramping. 76 VOLT STAT Displays if drive DC bus voltage exceeds high/low warning limits. 77 INVERT STAT Displays drive inverter status, ok or stall. 78 FREQ STAT Displays if drive is running outside of frequency limits of parameters 223 and 224. 79 CTRL STAT Displays whether drive is in local control or FLN serial bus. 80 DRV ENA STAT Displays if drive is enabled to start when run command given. 81 DRV RDY STAT Displays if drive control is ready or if a trip has occurred. 82 DRVCTRL STAT Displays drive control status as ready or not ready. 84 RESET Displays if a fault reset command has been given via serial bus. 85 START Displays if a run command has been given via serial bus. 86 Q.STOP Displays if a stop command has been given via serial bus. 87 TERM 53 Displays voltage value of signal on terminal 53 in volts. 88 TERM 54 Displays voltage value of signal on terminal 54 in volts. 89 TERM 60 Displays current value of signal on terminal 60 in mA. 90 OK.WARNING Displays if drive is in a warning condition. 91 LAST WARNING Displays last drive warning. 92 OK.FAULT Displays if drive has been tripped due to a fault. 93 LAST FAULT Displays last drive fault trip. 94 RESET FAULT Resets drive faults and resumes normal drive operation. 95 SETPOINT 1.S Displays status of point 69. 96 SETPOINT 2.S Displays status of point 70. 97 FB MIN.S Displays status of point 71. 98 FB MAX.S Displays status of point 72. 99 ERROR STATUS Not used.
VLT
®
Adjustable Frequency Drive
MG.60.G2.22 - VLT is a registered Danfoss Trademark
27
Loading...