Danfoss VLT 8000 AQUA Operating guide

Contents
VLT®8000 AQUA
Introduction
Software version ....................................................................................................... 4
Definitions ................................................................................................................ 5
Warning against unintended start ............................................................................. 7
Introduction to Operating Instructions ....................................................................... 9
Control principle ..................................................................................................... 10
AEO - Automatic Energy Optimization .................................................................... 10
Example of application - Constant pressure regulation in water supply system ....... 12
PC software and serial communication ................................................................... 13
PC Software tools .................................................................................................. 13
Fieldbus options ..................................................................................................... 13
Profibus .................................................................................................................. 13
LON - Local Operating Network ............................................................................. 14
DeviceNet .............................................................................................................. 14
Modbus RTU .......................................................................................................... 14
Cascade Controller Option ..................................................................................... 17
Unpacking and ordering a VLT frequency converter ................................................ 25
Type code ordering number string ......................................................................... 25
TYPE CODE Table/Ordering form ........................................................................... 29
......................................................................................................... 4
Installation ......................................................................................................... 30
General technical data ............................................................................................ 30
Technical data, mains supply 3 x 200 - 240 V ......................................................... 36
Technical data, mains supply 3 x 380 - 480 V ........................................................ 38
Technical data, mains supply 3 x 525 - 600 V ......................................................... 43
Fuses ..................................................................................................................... 48
Mechanical dimensions .......................................................................................... 51
Mechanical installation ............................................................................................ 54
General information about electrical installation ...................................................... 56
High voltage warning .............................................................................................. 56
Earthing .................................................................................................................. 56
Cables .................................................................................................................... 56
Screened/armoured cables .................................................................................... 56
Extra protection with regard to indirect contact ....................................................... 57
RFI switch .............................................................................................................. 58
High voltage test .................................................................................................... 61
Heat emission from VLT 8000 AQUA ...................................................................... 61
EMC-correct electrical installation ........................................................................... 62
Earthing/Grounding of screened/armoured control cables ...................................... 64
Electrical installation, enclosures ............................................................................. 65
Use of emc-correct cables ..................................................................................... 73
Tightening torque and screw sizes ......................................................................... 74
Mains connection ................................................................................................... 75
Motor connection ................................................................................................... 75
DC bus connection ................................................................................................ 77
High-voltage relay ................................................................................................... 77
Electrical installation, control cables ........................................................................ 78
Switches 1-4 .......................................................................................................... 79
Connection example VLT 8000 AQUA .................................................................... 81
Control unit LCP ..................................................................................................... 84
MG.83.A2.02 - VLT is a registered Danfoss trademark
1
VLT®8000 AQUA
Control keys for parameter setup ........................................................................... 84
Indicator lamps ....................................................................................................... 85
Local control .......................................................................................................... 85
Display mode ......................................................................................................... 85
Navigation between display modes ........................................................................ 88
Changing data ........................................................................................................ 89
Manual initialisation ................................................................................................. 89
Quick Menu ............................................................................................................ 90
Programming .................................................................................................... 92
Operation and Display 001-017 .............................................................................. 92
The Setup configuration ......................................................................................... 92
Setup of user-defined readout ................................................................................ 93
Load and motor 100-124 ....................................................................................... 99
Configuration .......................................................................................................... 99
Motor power factor (Cos ø) .................................................................................. 105
References and limits 200-228 ............................................................................. 108
Reference handling ............................................................................................... 109
Reference type ..................................................................................................... 112
Initial ramp parameter 229 .................................................................................... 116
Fill Mode .............................................................................................................. 116
Fill Rate parameter 230 ........................................................................................ 117
Filled Setpoint parameter 231 ............................................................................... 117
Inputs and outputs 300-328 ................................................................................. 118
Analog inputs ....................................................................................................... 122
Analog/digital outputs ........................................................................................... 125
Relay outputs ....................................................................................................... 128
Application functions 400-434 .............................................................................. 131
Sleep mode .......................................................................................................... 132
PID for process control ......................................................................................... 137
PID overview ........................................................................................................ 139
Feedback handling ............................................................................................... 139
Enhanced Sleep Mode ......................................................................................... 145
Serial communication for FC protocol ................................................................... 149
Protocols .............................................................................................................. 149
Telegram communication ..................................................................................... 149
Telegram build-up under FC protocol ................................................................... 149
Data character (byte) ............................................................................................ 151
Process word ....................................................................................................... 154
Control word according to FC protocol ................................................................. 155
Status word according to FC protocol .................................................................. 156
Serial communication 500-556 ............................................................................. 159
Warning words 1+2 and Alarm word .................................................................... 167
Service functions 600-631 .................................................................................... 168
Electrical installation of the relay card .................................................................... 173
All about VLT 8000 AQUA ......................................................................... 174
Status messages .................................................................................................. 174
List of warnings and alarms .................................................................................. 176
Special conditions ................................................................................................ 181
Aggressive environments ...................................................................................... 181
Calculation of resulting reference .......................................................................... 182
Extreme running conditions .................................................................................. 184
Peak voltage on motor ......................................................................................... 185
2
MG.83.A2.02 - VLT is a registered Danfoss trademark
VLT®8000 AQUA
Derating for ambient temperature ......................................................................... 187
Switching on the input .......................................................................................... 187
Efficiency .............................................................................................................. 189
Mains supply interference/harmonics .................................................................... 190
CE labelling .......................................................................................................... 191
EMC test results (Emission, Immunity) .................................................................. 192
EMC Immunity ..................................................................................................... 194
Factory settings .................................................................................................... 196
Index .................................................................................................................... 204
MG.83.A2.02 - VLT is a registered Danfoss trademark
3
VLT®8000 AQUA
VLT 8000 AQUA
Operating Instructions Software version: 1.7x
These Operating Instructions can be used for all VLT 8000 AQUA frequency converters with software version 1.7x. The software version number can be seen from parameter 624
Software version no.
176FA145.16
4
MG.83.A2.02 - VLT is a registered Danfoss trademark
Definitions
Definitions are given in alphabetical order.
A
EO: Automatic Energy Optimization - function that dynamically adjusts the current supplied to a variable torque load to optimize motor power factor and motor efficiency.
nalog inputs:
a The analog inputs can be used for controlling various functions of the frequency converter. There are two types of analog inputs: Current input, 0-20 mA Voltage input, 0-10 V DC.
nalog ref.
a A signal transmitted to input 53, 54 or 60. Can be voltage or current.
analog outputs: There are two analog outputs, which are able to supply a signal of 0-20 mA, 4-20 mA or a digital signal.
utomatic motor adjustment, AMA:
A Automatic motor adjustment algorithm, which determines the electrical parameters for the connected motor, at standstill.
VLT®8000 AQUA
T:
C Constant torque: used for e.g. heavy, solid sludge pumps and centrifuges.
igital inputs:
D The digital inputs can be used for controlling various functions of the frequency converter.
D
igital outputs: There are four digital outputs, two of which activate a relay switch. The outputs are able to supply a24VDC(max. 40mA)signal.
f
JOG
Theoutputfrequencyfromthefrequencyconverter transmitted to the motor when the jog function is activated (via digital terminals or serial communication).
f
M
Theoutputfrequencyfromthefrequencyconverter transmitted to the motor.
f
M,N
The rated motor frequency (nameplate data).
f
MAX
Maximum output frequency transmitted to the motor.
Introduction
WG:
A AWG means American Wire Gauge, i.e. the American measuring unit for cable cross-section.
C
ontrol command: By means of the control unit and the digital inputs, it is possible to start and stop the connected motor. Functions are divided into two groups, with the following priorities:
Group 1 Reset, Coasting stop, Reset and
Coasting stop, DC braking, Stop and the [OFF/ STOP] key.
Group 2 Start, Pulse start, Reversing, Start
reversing, Jog and Freeze output
Group 1 funct
ions are called Start-disable commands. The difference between group 1 and group 2 is that in group 1 all stop signals must be cancelled for the motor to st
art. The motor can then be started by means of a single start signal in group 2. A stop command given as a group 1 command
in the display indication STOP.
results A missing stop command given as a group 2 command results in the display indication STAND BY.
f
MIN
Minimum output frequency transmitted to the motor.
I
M
The current transmitted to the motor.
I
M,N
The rated motor current (nameplate data).
I
nitializing: If initializing is carried out (see parameter 620 Operating mode), the frequency converter returns to the factory setting.
I
VLT,MAX
The maximum output current.
I
VLT,N
The rated output current supplied by the frequency converter.
CP:
L The control panel, which makes up a complete interface for control and programming of VLT 8000 AQUA. The control panel is detachable and may, as an alternative, be installed up to 3 metres away
MG.83.A2.02 - VLT is a registered Danfoss trademark
5
from the frequency converter, i.e. in a front panel, by means of the installation kit option.
L
SB: Least significant bit. Used in serial communication.
CM:
M Stands for Mille Circular Mil, an American measuring unit for cable cross-section.
SB:
M Most significant bit. Used in serial communication.
n
M,N
The rated motor speed (nameplate data).
η
VLT
The efficiency of the frequency converter is defined as the ratio between thepower output andthe power input.
O
n-line/off-line parameters: On-line parameters are activated immediately after the data value is changed. Off-line parameters are not activated until OK has been entered on the control unit.
ID:
P The PID regulator maintains the desired speed (pressure, temperature, etc.) by adjusting the output frequency to match the varying load.
P
M,N
The rated power delivered by the motor (nameplate data).
reset ref.
P A permanently defined reference, which can be set from -100% to +100% of the reference range. There are four preset references, which can be selected via the digital terminals.
ef
R
MAX
The maximum value which the reference signal may have. Set in parameter 205 Maximum
reference, Ref
MAX
.
VLT®8000 AQUA
S
etup: There are four Setups, in which it is possible to save parameter settings. It is possible to change between the four parameter Setups and to edit one Setup, while another Setup is active.
tart-disable command:
S A stop command that belongs to group 1 of the control commands - see this group.
top command:
S See Control commands.
T
hermistor: A temperature-dependent resistor placed where the temperature is to be monitored (VLT or motor).
rip:
T A state which occurs in different situations, e.g. if the frequency converter is subjected to an over-temperature. A trip can be cancelled by pressing reset or, in some cases, automatically.
rip locked:
T Trip locked is a state which occurs in different situations, e.g. if the frequency converter is subject to an over-temperature. A locked trip can be cancelled by cutting off mains and restarting the frequency converter.
U
M
The voltage transmitted to the motor.
U
M,N
The rated motor voltage (nameplate data).
U
VLT, MAX
The maximum output voltage.
V
T characteristics: Variable torque characteristics, used for pumps and fans.
R
ef
MIN
The smallest value which the reference signal may have. Set in parameter 204 Minimum reference, Ref
6
MIN
.
MG.83.A2.02 - VLT is a registered Danfoss trademark
VLT®8000 AQUA
The voltage of the frequency converter is dangerous whenever the equipment
is connected to mains. Incorrect installation of the motor or the frequency converter may cause damage to the equipment, serious personal injury or death. Consequently, the instructions in this manual, as well as national and local rules and safety regulations, must be complied with.
Safety regulations
1. The frequency converter must be disconnected
from the mains if repair work is to be carried out. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.
2. The [OFF/STOP] key on the control panel of
the frequency converter does not disconnect the equipment from mains and is thus be used as a safety switch.
3. Correct protective earthing/grounding of the
equipment must be established, the user must be protected against supply voltage, and the motor must be protected against overload in accordance with the National Electrical Code and local codes.
4. The earth leakage currents are higher than 3.5mA.
5. Protection against motor overload is n
the factory setting. If this function is required, set parameter 117, Motor thermal protection,todata value ETR trip or data value ETR warning.
ote: The function is initialised at 1.0 x rated motor
N current and rated motor frequency (see parameter
not to
ot included in
117, Motor thermal protection).InUL/cUL applications ETR provides Class 20, over-load
®
protection in accordance with the NEC
6. Do n
7. Please note that the frequency converter has more
Warning against unintended start
1. The motor can be brought to a stop by means
2. While parameters are being changed, the motor
3. A stopped motor may start if a fault occurs in
ot remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.
voltage inputs than L1, L2, L3 when the DC-bus terminals or AUX 24 V option are used. Check that a disconnected and that the necessary time has passed before repair work is commenced.
of digital commands, bus commands, references or a local stop, while the frequency converter is connected to mains. If personal safety considerations make it necessary to ensure that no unintended start occurs, t functions are not sufficient.
may start. Consequently, t STOP] must always be activated, following which data can be modified.
the electronics of the frequency converter, or if a temporary overload or a fault in the supply mains or the motor connection ceases.
ll voltage inputs have been
he stop key [OFF/
.
hese stop
Introduction
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from line.
VLT 8006-8062, 200-240 V: wait at least 15 minutes VLT 8006-8072, 380-480 V: wait at least 15 minutes VLT 8102-8352, 380-480 V: wait at least 20 minutes VLT 8452-8652, 380-480 V: wait at least 40 minutes VLT 8002-8006, 525-600 V: wait at least 4 minutes VLT 8008-8027, 525-600 V: wait at least 15 minutes VLT 8032-8072, 525-600 V: wait at least 30 minutes VLT 8052-8402, 525-690 V: wait at least 20 minutes VLT 8502-8652, 525-690 V: wait at least 30 minutes
MG.83.A2.02 - VLT is a registered Danfoss trademark
176FA159.15
7
Use on isolated mains
See section RFI Switch regarding use on isolated mains.
It is important to follow the recommendations regarding installation on IT-mains, since sufficient protection of the complete installation must be observed. Not taking care using relevant monitoring devices for IT-mains may result in damage.
It is the responsibility of the user or the person installing the VLT to provide proper
earthing/grounding, as well as motor overload and branch circuit protection according to local codes such as the Nation Electrical Code (NEC).
NB!:
Electrostatic Precaution; Electrostatic discharge (ESD). Many electronic components are
sensitive to static electricity. Voltages so low that they cannot be felt, seen or heard, can reduce the life, affect performance, or completely destroy sensitive electronic components. When performing service, proper ESD equipment should be used to prevent possible damage from occurring.
VLT®8000 AQUA
The frequency converter contains dangerous voltages when connected to mains voltage. After disconnecting from mains wait at least
15 minutes for VLT 8006-8062, 200-240 V 15 minutes for VLT 8006-8072, 380-480 V 20 minutes for VLT 8102-8352, 380-480 V 40 minutes for VLT 8452-8652, 380-480 V 4 minutes for VLT 8002-8006, 525-600 V 15 minutes for VLT 8008-8027, 525-600 V 30 minutes for VLT 8032-8072, 525-600 V 20 minutes for VLT 8052-8402, 525-690 V 30 minutes for VLT 8502-8652, 525-690 V before touching any electrical components. Also make sure that other voltage inputs have been disconnected, such as external 24 VDC and load-sharing (linkage of DC intermediate circuit). Only a competent electrician should carry out the electrical installation. Improper installation of the motor or the VLT may cause equipment failure, serious injury or death. Follow this manual and National Electrical Codes (NEC) and local safety codes.
8
MG.83.A2.02 - VLT is a registered Danfoss trademark
VLT®8000 AQUA
Introduction to Operating Instructions
These Operating Instructions are divided into four sections with information about VLT 8000 AQUA.
Introduction to AQUA: This section tells you the advantages you can obtain by using a VLT
8000 AQUA - such as Automatic Energy Optimization, Constant Torque or Variable Torque and other AQUA relevant functions. This section also contains examples of applications as well as information about Danfoss.
Installation: This section tells you how to carry out a mechanically correct installation
of the VLT 8000 AQUA. Furthermore, a list is given of mains and motor connections, together with a description of the control card terminals.
Programming: This section describes the control unit and the software parameters for
the VLT 8000 AQUA. Also included is a guide to the Quick Setup menu, which allows you to get started on your application very quickly.
All about VLT 8000 AQUA: This section gives information about status, warning and error messages
from the VLT 8000 AQUA. Additionally, information is given on technical data, ser-vice, factory settings and special conditions.
Introduction
NB!:
Indicate
s something to be noted by the reader.
Indicates a general warning
Indicates a high-voltage warning
MG.83.A2.02 - VLT is a registered Danfoss trademark
9
Control principle
A frequency converter rectifies AC voltage from mains into DC voltage, after which this DC voltage is converted into a AC current with a variable amplitude and frequency.
VLT®8000 AQUA
The motor is thus supplied with variable voltage and frequency, which enables infinitely variable speed control of three-phased, standard AC motors.
1. Mains voltage 3 x 200 - 240 V AC, 50 / 60 Hz. 3 x 380 - 480 V AC, 50 / 60 Hz. 3 x 525 - 600 V AC, 50 / 60 Hz. 3 x 525 - 690 V AC, 50 / 60 Hz.
. Rectifier
2 A three-phase rectifier bridge that rectifies AC current into DC current.
3
. Intermediate circuit
DC voltage = 1.35 x mains voltage [V].
4
. Intermediate circuit coils Even out the intermediate circuit voltage the harmonic current feedback to the mains supply.
AEO - Automatic Energy Optimization
Normally, the U/f characteristics have to be set on the basis of the expec However, knowing the load at a given frequency in an installation is often a problem. This problem can be solved by usin Automatic Energy Optimization (AEO), which ensures optimum energy utilization. All VLT 8000 AQUA units feature thi not necessary to adjust the frequency converter U/f ratio in order to obtain maximum energy savings. In other voltage/frequency ratio (U/f) must be assessed to carry out correct setting of the frequency converter. Using A no longer need to calculate or assess the system characteristics of the installation, since Danfoss VLT 800 energy consumption by the motor at all times.
The figure on the right illustrates the working range of the AEO function, within which energy optimization is enabled.
s function as a factory setting, i.e. it is
frequency converters, the given load and
utomatic Energy Optimization (AEO), you
0 AQUA units guarantee optimum, load-dependent
ted load at different frequencies.
g a VLT 8000 AQUA with its integral
and reduce
5
. Intermediate circuit capacitors
Even out the intermediate circuit voltage.
6
. Inverter Converts DC voltage into variable AC voltage withavariablefrequency.
7
. Motor voltage Variable AC voltage, 0-100% of mains supply voltage.
8
. Control card This is where to find the computer that controls the inverter which generates the pulse pattern by which the DC voltage is converted into variable AC voltage with a variable frequency.
he AEO function has been selected in parameter 101,
If t Torque characteristics, this function will be constantly active. If there is a major deviation from the optimum U/f
atio, the frequency converter will quickly adjust itself.
r
Advantages of the AEO function
Automatic energy optimization
Compensation if an oversize motor is used
AEO matches operations to daily or
seasonal fluctuations
10
MG.83.A2.02 - VLT is a registered Danfoss trademark
Energy savings in a constant air volume system
Compensation in the oversynchronous
working range
Reduces acoustic motor noise
VLT®8000 AQUA
Introduction
MG.83.A2.02 - VLT is a registered Danfoss trademark
11
VLT®8000 AQUA
Example of application - Constant pressure
regulation in water supply system
The demand for water from waterworks varies considerably during the course of a day. In the night, practically no water is used, while in the morning and in the evening the consumption is high. In order to maintain a suitable pressure in the water supply lines in relation to the current demand, the water supply pumps are equipped with speed control. The use of a frequency converter enables the energy consumed by the pumps to be kept at a minimum, while optimizing the water supply to consumers. A VLT 8000 AQUA with its integral PID controller ensures simple and quick installation. For example, an IP54/NEMA 12 unit can be mounted close to the pump on the wall and the existing mains cables can be used as mains supply to the frequency converter. A Pressure transmitter (e.g. Danfoss MBS 33 or MBS
3000) can be fitted a few meters (feet) from the joint outlet point from the waterworks to obtain closed loop regulation. Danfoss MBS 33 and MBS 3000 is a two-wire transmitter (4-20 mA) that can be powered directly from a VLT 8000 AQUA. The required setpoint (e.g. 5 bar) can be set locally in parameter 418 Setpoint 1.
Assume: Transmitter is scaled 0-10 Bar, minimum flow is achieved at 30 Hz. An increase in motor speed increases the pressure.
Set the following parameters: Par. 100 Configuration Closed loop [1] Par. 201 Minimum Output Frequency 30 Hz Par. 202 Maximum Output Frequency 50 Hz (or 60 Hz) Par. 204 Minimum Reference 0 Bar Par. 205 Maximum Reference 10 Bar Par. 302 Terminal 18 Digital inputs Start [1] Par. 314 Terminal 60, analog input current Feedback signal [2] Par. 315 Terminal 60, min. scaling 4 mA Par. 316 Terminal 60, max. scaling 20 mA Par. 403 Sleep mode timer 10 sec. Par. 404 Sleep frequency 35 Hz Par. 405 Wake-up frequency 45 Hz Par. 406 Boost setpoint 125% Par. 413 Minimum Feedback 0 Bar Par. 414 Maximum Feedback 10 Bar Par. 415 Process units Bar [16] Par. 418 Setpoint 1 5 bar Par. 420 PID control action Normal Par. 423 PID Proportional gain 0.3* Par. 424 PID Integral time 30 sec.*
* The PID tuning parameters depend on the actual system dynamics.
12
MG.83.A2.02 - VLT is a registered Danfoss trademark
VLT®8000 AQUA
PC software and serial communication
Danfoss offers various options for serial communication. Using serial communication, it is possible to monitor, program and control one or several frequency converters from a centrally located computer. All VLT 8000 AQUA units have an RS 485 port as standard with a choice of two protocols. The protocols selectable in parameter 500 protocols are:
FC Protocol
Modbus RTU
A bus option card allows higher transmission speed than RS 485. In addition, a higher number of units can be linked to the bus and alternative transmission media can be used. Danfoss offers the following option cards for communication:
Profibus
LonWorks
DeviceNet
Information on the installation of various options is not included in these operating instructions.
Using the RS 485 port enables communication,
TM
e.g. with a PC. A Windows
program, called MCT 10, is available for this purpose. It can be used to monitor, program and control one or several VLT 8000 AQUA units.
PC Software tools
PC Software - MCT 10
All drives are equipped with a serial communication port. We provide a PC tool for communication between PC and frequency converter, VLT Motion Control Tool MCT 10 Set-up Software.
MCT 10 Set-up Software
MCT 10 has been designed as an easy to use interactive tool for setting parameters in our frequency converters. The MCT 10 Set-up Software will be useful for:
Planning a communication network off-line. MCT 10
contains a complete frequency converter database
Commissioning frequency converters on line
Saving settings for all frequency converters
Replacing a drive in a network
Expanding an existing network
Future developed drives will be supported
MCT10Set-upSoftwaresupportProfibusDP-V1via a Master class 2 connection. It makes it possible to on line read/write parameters in a frequency converter via the Profibus network. This will eliminate the need for an extra communication network.
The MCT 10 Set-up Software Modules
The following modules are included in the software package:
MCT10Set-upSoftware
Setting parameters Copy to and from frequency converters Documentation and print out of parameter settings incl. diagrams
SyncPos
Creating SyncPos programme
Ordering number:
Please order your CD containing MCT 10 Set-up Software using code number 130B1000.
Introduction
Fieldbus options
The increasing need for information in building management systems makes it necessary to collect or visualise many different types of process data. Important process data can help the system technician in the day to day monitoring of the system, which means that a negative development, e. g. an increase in energy consumption, can be rectified in time.
The substantial amount of data in large buildings may generate a need for a higher transmission speed than 9600 baud.
MG.83.A2.02 - VLT is a registered Danfoss trademark
Profibus
Profibus is a fieldbus system with FMS and DP, which can be used for linking automation units, such as sensors and actuators, to the controls by means of a two-conductor cable.
Profibus FMS is used if major communication tasks are to be solved at cell and system level by means of large volumes of data.
Profibus DP is an extremely fast communication protocol, made specially for communication between the automation system and various units.
VLT 8000 AQUA only supports DP.
13
LON - Local Operating Network
LonWorks is an intelligent fieldbus system which improves the possibility of decentralising control, as communication is enabled between individual units in the same system (Peer-to-Peer). This means that there is no need for a big main station for handling all the signals of the system (Master-Slave). Signals are sent direct to the unit that needs them via a common network medium. This makes communication much more flexible and the central building state control and monitoring system can be changed into a dedicated building state monitoring system whose task is to ensure that everything is running as planned. If the potential of LonWorks is fully utilised, sensors will also be connected to the bus, which means that a sensor signal can quickly be moved to another controller. If room dividers are mobile, this is a particularly useful feature.
DeviceNet
DeviceNet is a digital, multi-drop network, based on the CAN protocol, that connects and serves as a communication network between industrial controllers and I/O devices. Each device and/or controller is a node on the network. DeviceNet is a producer-consumer network that supports multiple communication hierarchies and message prioritization. DeviceNet systems can be configured to operate in a master-slave or a distributed control architecture using peer-to-peer communication. This system offers a single point of connection for configuration and control by supporting both I/O and explicit messaging. DeviceNet also has the feature of having power on the network. This allows devices with limited power requirements to be powered directly from the network via the 5-conductor cable.
VLT®8000 AQUA
Modbus RTU
MODBUS RTU (Remote Terminal Unit) Protocol is a messaging structure developed by Modicon in 1979, used to establish master-slave/client-server communication between intelligent devices. MODBUS is used to monitor and program devices; to communicate intelligent devices with sensors and instruments; to monitor field devicesusingPCsandHMIs. MODBUS is often applied in Gas and Oil applications, but also in building, infrastructure, transportation and energy, applications are making use of its benefits.
14
MG.83.A2.02 - VLT is a registered Danfoss trademark
Accessories
IP 20 bottom cover
VLT®8000 AQUA
Introduction
Application option
Type Description Order no. IP 4x top cover IP IP 4 x top cover NEMA 12 bonding plate IP 20 terminal cover Option, VLT type 8006-8022 200-240 V 175Z4622 IP 20 terminal cover Option, VLT type 8027-8032 200-240 V 175Z4623 IP 20 terminal cover Option, VLT type 8016-8042 380-480 V 175Z4622 IP 20 terminal cover Option, VLT type 8016-8042 525-600 V 175Z4622 IP 20 terminal cover Option, VLT type 8052-8072 380-480 V 175Z4623 IP 20 terminal cover Option, VLT type 8102-8122 380-480 V 175Z4280 IP 20 terminal cover Option, VLT type 8052-8072 525-600 V 175Z4623 IP 20 bottom cover Option, VLT type 8042-8062 200-240 V 176F1800 Terminal adaptor kit VLT type 8042-8062 200-240 V, IP 54 176F1808 Terminal adaptor kit VLT type 8042-8062 200-240 V, IP 00/NEMA 1 176F1805 Control panel LCP Separate LCP 175Z7804 LCP remote-mounting kit IP 00 & 20 LCP remote-mounting kit IP 54 LCP blind cover for all IP00/IP20 drives 175Z7806 Cable for LCP Separate cable (3 m) 175Z0929 Relay card Application card with four relay outputs 175Z3691 Cascade controller card With conformal coating 175Z3692 Profibus option Without/with conformal coating 175Z3685/175Z3686 LonWorks option, Free topology Without conformal coating 176F0225 Modbus RTU option Without conformal coating 175Z3362 DeviceNet option Without conformal coating 176F0224 MCT 10 Set-up software CD-Rom 130B1000 MCT 31 Harmonic calculation CD-Rom 130B1031
1)
1)
2)
3)
4)
Option, VLT type 8006-8011 380-480 V compact 175Z0928 Option, VLT type 8002-8011 525-600 V compact 175Z0928 Option, VLT type 8006-8011 380-480 V 175H4195
Remote-mounting kit, incl. 3 m cable 175Z0850 Remote-mounting kit, incl. 3 m cable 175Z7802
MG.83.A2.02 - VLT is a registered Danfoss trademark
15
VLT®8000 AQUA
Rittal Installation Kit
Type Description Order No. Rittal TS8 enclosure for IP00 Rittal TS8 enclosure for IP00 Rittal TS8 enclosure for IP00 Rittal TS8 enclosure for IP00 Rittal TS8 enclosure for IP00 Floor stand for IP21 and IP54
5)
enclosure Mains shield kit Protection kit, VLT 8152-8352, 380-480 V; VLT 8052-8402, 525-690 V 176F0799 Mains shield kit Protection kit, VLT 8452-8652, 380-480 V; VLT 8502-8652, 525-690V 176F1851
1) IP 4x/NEMA 1 top cover is for IP 20 units only and only horizontal surfaces comply with IP 4x. The kit also contains a bonding plate (UL).
2) NEMA 12 bonding plate (UL) is only for IP 54 units.
3) The remote-mounting kit is only for IP 00 and IP 20 units. Enclosure of the remote-mounting kit is IP 65.
4) The remote-mounting kit is only for IP 54 units. Enclosure of the remote-mounting kit is IP 65.
5) For details: See High Power Installation Guide, MI.90.JX.YY.
VLT 8000 AQUA is available with an integral fieldbus option or application option. Ordering numbers for the individual VLT types with integrated options can be seen from the relevant manuals or instructions. In addition, the ordering number system can be used for ordering a frequency converter with an option.
5)
Installation kit for 1800mm high enclosure, VLT8152-8202, 380-480V; VLT8052-8202, 525-690V 176F1824
5)
Installation kit for 2000mm high enclosure, VLT8152-8202, 380-480V; VLT8052-8202, 525-690V 176F1826
5)
Installation kit for 1800mm high enclosure, VLT8252-8352, 380-480V; VLT8252-8402, 525-690V 176F1823
5)
Installation kit for 2000mm high enclosure, VLT8252-8352, 380-480V; VLT8252-8402, 525-690V 176F1825
5)
Installation kit for 2000mm high enclosure, VLT8452-8652, 380-480V/VLT 8502-8652, 525-690V 176F1850 Option, VLT8152-8352, 380-480V; VLT 8052-8402, 525-690V 176F1827
16
MG.83.A2.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
In "Standard Mode", one motor is controlled by the drive that has the Cascade Controller Option card installed in it. Up to four additional fixed speed motors can be sequenced on & off, as required by the process, in lead-lag mode.
In "Master/Slave Mode", the drive that has the Cascade Controller option card installed in it, along with its associated motor, is designated as the master. Up to four additional motors, each with its own drive, can be operated in slave mode. The Cascade Controller functions to stage the slave drives/motors - on & off (as required), as a function of "best system operating efficiency".
In "Lead Pump Alternation Mode", it is possible to averageouttheusageofthepumps.Thisisdoneby making the frequency converter switch between the pumps (max. 4) by means of a timer. Please note that this mode requires an external relay setup.
VLT®8000 AQUA
This filter reduces the voltage rise time, the peak voltage
and the ripple current I to the motor, thereby
U
PEAK
making current and voltage almost sinusoidal. The acoustic motor noiseis thereforereducedto a minimum.
Because of the ripple current in the coils, there will be some noise from the coils. This problem can be solved entirely by integrating the filter in a cabinet or similar.
Introduction
Consult your Danfoss Sales Office for additional information.
LC filters for VLT 8000 AQUA
When a motor is controlled by a frequency converter, resonance noise will be heard from the motor. This noise, which is caused by the design of the motor, occurs each time one of the inverter switches in the frequency converter is activated. Consequently, the resonance noise frequency corresponds to the switching frequency of the frequency converter.
For the VLT 8000 AQUA, Danfoss offers a LC filter to dampen the acoustic motor noise.
Examples of the use of LC filters
ubmersible pumps
S For small motors with up to and including 5.5 kW rated motor power, use an LC filter, unless the motor is equipped with phase separation paper. This applies e.g. to all wet running motors. If these motors are used without LC filter in connection with a frequency converter, the motor windings will short-circuit. If in doubt, ask the motor manufacturer whether the motor in question is equipped with phase separation paper.
ell pumps
W If immersion pumps are used, e.g. submerged pumps or well pumps, the supplier should be contacted for clarification of requirements. It is recommended to use a LC filter if a frequency converter is used for well pump applications.
MG.83.A2.02 - VLT is a registered Danfoss trademark
17
VLT®8000 AQUA
Ordering numbers, LC filter modules
Mains supply 3 x 200 - 240 V
LC filter LC filter Rated current Max. output Power for VLT type enclosure at 200 V frequency loss Order no. 8006-8008 IP 00 25.0 A 60 Hz 110 W 175Z4600 8011 IP 00 32 A 60 Hz 120 W 175Z4601 8016 IP 00 46 A 60 Hz 150 W 175Z4602 8022 IP 00 61 A 60 Hz 210 W 175Z4603 8027 IP 00 73 A 60 Hz 290 W 175Z4604 8032 IP 00 88 A 60 Hz 320 W 175Z4605 8042 IP 00 115 A 60 Hz 600 W 175Z4702 8052 IP 00 143 A 60 Hz 600 W 175Z4702 8062 IP 00 170 A 60 Hz 700 W 175Z4703
Mainssupply3x380-480
LC filter LC filter Rated current Max. output Power for VLT type enclosure at 400/480 V frequency loss Order no. 8006-8011 IP 20 16 A / 16 A 120 Hz 175Z0832 8016 IP 00 24 A/ 21.7 A 60 Hz 170 W 175Z4606 8022 IP 00 32 A / 27.9 A 60 Hz 180 W 175Z4607 8027 IP 00 37.5 A / 32 A 60 Hz 190 W 175Z4608 8032 IP 00 44 A / 41.4 A 60 Hz 210 W 175Z4609 8042 IP 00 61 A / 54 A 60 Hz 290 W 175Z4610 8052 IP 00 73 A / 65 A 60 Hz 410 W 175Z4611 8062 IP 00 90 A / 78 A 60 Hz 480 W 175Z4612 8072 IP 20 106 A / 106 A 60 Hz 500 W 175Z4701 8102 IP 20 147 A / 130 A 60 Hz 600 W 175Z4702 8122 IP 20 177 A / 160 A 60 Hz 750 W 175Z4703 8152 IP 20 212 A / 190 A 60 Hz 750 W 175Z4704 8202 IP 20 260 A / 240 A 60 Hz 900 W 175Z4705 8252 IP 20 315 A / 302 A 60 Hz 1000 W 175Z4706 8302 IP 20 395 A / 361 A 60 Hz 1100 W 175Z4707 8352 IP 20 480 A / 443 A 60 Hz 1700 W 175Z3139 8452 IP 20 600 A / 540 A 60 Hz 2100 W 175Z3140 8502 IP 20 658 A / 590 A 60 Hz 2100 W 175Z3141 8602 IP 20 745 A / 678 A 60 Hz 2500 W 175Z3142
Regarding LC filters for 525 - 600 V and VLT 8652, 380-480 V, please contact Danfoss.
NB!:
When using LC filters, the switching frequency must be 4.5 kHz (see parameter 407).
For VLT 8452-8602 parameter 408 must be set to LC filter fitted to obtain proper operation.
18
MG.83.A2.02 - VLT is a registered Danfoss trademark
Mainssupply3x690V
VLT®8000 AQUA
VLT
8052 54 60 290 130B2223 130B2258 8062 73 60 390 130B2225 130B2260 8072 86 60 480 130B2225 130B2260 8102 108 60 600 130B2226 130B2261 8122 131 60 550 130B2228 130B2263 8152 155 60 680 130B2228 130B2263 8202 192 60 920 130B2229 130B2264 8252 242 60 750 130B2231 130B2266 8302 290 60 1000 130B2231 130B2266 8352 344 60 1050 130B2232 130B2267 8402 400 60 1150 130B2234 130B2269 8502 530 60 500 130B2241 130B2270 8602 600 60 570 130B2242 130B2271 8652 630 60 600 - -
Rated Current at 690VMax. output
frequency (Hz)
Power dissipation (W)
Ordering no. IP00
Ordering no. IP20
dU/dt filters
The dU/dt filters reduce dU/dt to approx. 500 V / µsec. These filters do not red
uce noise or Upeak.
NB!:
When using dU/dt filters, the switching frequency must be 1.5 kHz (see parameter 411)
Introduction
Mains supply3x690V
VLT
8052 54 60 90 130B2154 130B2188 8062 73 60 100 130B2155 130B2189 8072 86 60 110 130B2156 130B2190 8102 108 60 120 130B2157 130B2191 8122 131 60 150 130B2158 130B2192 8152 155 60 180 130B2159 130B2193 8202 192 60 190 130B2160 130B2194 8252 242 60 210 130B2161 130B2195 8302 290 60 350 130B2162 130B2196 8352 344 60 480 130B2163 130B2197 8402 400 60 540 130B2165 130B2199 8502 530 60 500 130B2236 130B2239 8602 600 60 570 130B2237 130B2240 8652 630 60 600 - -
Rated Current at 690VMax. output
frequency (Hz)
Power dissipation (W)
Ordering no. IP 00
Ordering no. IP20
MG.83.A2.02 - VLT is a registered Danfoss trademark
19
VLT®8000 AQUA
LC filters VLT 8006-8011 380 - 480 V The drawing on the left gives the measurements of IP
20 LC filters for the above-mentioned power range. Min. space above and under enclosure: 100 mm.
IP 20 LC filters have been designed for side-by-side installation without any space between enclosures.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable If EMC standards are to be complied with:
EN 55011-1B: Max. 50 screened/armoured cable EN 55011-1A: Max. 150 m screened/armoured cable
Weight: 175Z0832 9.5 kg
Installation of LC filter IP 20
20
MG.83.A2.02 - VLT is a registered Danfoss trademark
VLT®8000 AQUA
LC filters VLT 8006-8032, 200 - 240 V /
8016-8062 380 - 480 V
The table and the drawing give the measurements of IP 00 LC filters for Compact units. IP 00 LC filters must be integrated and protected against dust, water and corrosive gases.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable If EMC standards are to be complied with:
- EN 55011-1B: Max. 50 screened/armoured cable
- EN 55011-1A: Max. 150 m screened/armoured cable
LC filter IP 00
LC type A [mm] B [mm] C [mm] D [mm] E [mm] F [mm] G [mm] Weight [kg] 175Z4600 220 135 92 190 68 170 8 10 175Z4601 220 145 102 190 78 170 8 13 175Z4602 250 165 117 210 92 180 8 17 175Z4603 295 200 151 240 126 190 11 29 175Z4604 355 205 152 300 121 240 11 38 175Z4605 360 215 165 300 134 240 11 49 175Z4606 280 170 121 240 96 190 11 18 175Z4607 280 175 125 240 100 190 11 20 175Z4608 280 180 131 240 106 190 11 23 175Z4609 295 200 151 240 126 190 11 29 175Z4610 355 205 152 300 121 240 11 38 175Z4611 355 235 177 300 146 240 11 50 175Z4612 405 230 163 360 126 310 11 65
Introduction
MG.83.A2.02 - VLT is a registered Danfoss trademark
21
VLT®8000 AQUA
LC filter VLT 8042-8062 200-240 V /
8072-8602 380 - 480 V
The table and the drawing give the measurements of IP 20 LC filters. IP 20 LC filters must be integrated and protected against dust, water and aggressive gases.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable If EMC standards are to be complied with:
- EN 55011-1B: Max. 50 m screened/armoured cable
- EN 55011-1A: Max. 150 m screened/armoured cable
LC-filter IP 20
LC type A [mm] B [mm] C [mm] D [mm] E [mm] F [mm] G [mm] Weight [kg] 175Z4701 740 550 600 70 175Z4702 740 550 600 70 175Z4703 740 550 600 110 175Z4704 740 550 600 120 175Z4705 830 630 650 220 175Z4706 830 630 650 250 175Z4707 830 630 650 250 175Z3139 1350 800 1000 350 175Z3140 1350 800 1000 400 175Z3141 1350 800 1000 400 175Z3142 1350 800 1000 470
22
MG.83.A2.02 - VLT is a registered Danfoss trademark
VLT®8000 AQUA
Harmonic filter
Harmonic currents do not directly affect the electricity consumption but has an impact on following conditions:
Higher total current to be handled by the installations
- Increases load on transformer (sometimes it will require a larger transformer, particular at retrofit)
- Increases heat losses in transformer and installation
- In some cases demands larger cables, switches and fuses
Higher voltage distortion due to higher current
- Increase risk for disturbing electronic equipment connected to same grid
A high percentage of rectifier load from eg frequency converters, will increase the harmonic current, which must be reduced to avoid the above consequences. Therefore the frequency converter has as standard, built in DC coils reducing the total current with about 40% (compared to devices without any arrangement for harmonic suppression), down to 40-45% ThiD.
In some cases there is a need for further suppression (eg retrofit with frequency converters). For this purpose Danfoss can offer two advanced harmonic filters AHF05 and AHF10, bringing the harmonic current down to around 5% and 10% respectively. For further details see instruction MG.80.BX.YY.
MCT 31
The MCT 31 harmonic calculation PC tool enables easy estimation of the harmonic distortion in a given application. Both the harmonic distortion of Danfoss frequency converters as well as non-Danfoss frequency converters with different additional harmonic reduction measurements, such as Danfoss AHF filters and 12-18-pulse rectifiers, can be calculated.
Ordering number:
Please order your CD containing the MCT 31 PC tool using code number 130B1031.
Introduction
Ordering numbers, Harmonic filters
Harmonic filters are used to reduce mains harmonics
AHF 010: 10% current distortion
AHF 005: 5% current distortion
380-415 V, 50 Hz
AHF,N
10 A 4, 5.5 175G6600 175G6622 8006, 8008 19 A 7.5 175G6601 175G6623 8011, 8016 26 A 11 175G6602 175G6624 8022 35 A 15, 18.5 175G6603 175G6625 8027 43 A 22 175G6604 175G6626 8032
72 A 30, 37 175G6605 175G6627 8042, 8052 101 A 45. 55 175G6606 175G6628 8062, 8072 144 A 75 175G6607 175G6629 8102 180 A 90 175G6608 175G6630 8122 217 A 110 175G6609 175G6631 8152 289 A 132, 160 175G6610 175G6632 8202, 8252 324 A 175G6611 175G6633 370 A 200 175G6688 175G6691 8302
Higher ratings can be achieved by paralleling the filter units
434 A 250 Two 217 A units 8352 578 A 315 Two 289 A units 8452 613 A 355 289 A and 324 A units 8502 648 A 400 Two 324 A units 8602 740 A 450 Two 370 A units 8652
Typical Motor Used [kW]
Danfoss ordering numberI AHF 005 A HF 010
VLT 8000
MG.83.A2.02 - VLT is a registered Danfoss trademark
23
VLT®8000 AQUA
Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 400 V and assuming typical motor load (4 or 2 pole motor). VLT 8000 is based on a max. 110% torque application. The pre-calculated filter current may be different than the input current ratings of VLT 8000 as stated in the respective operating instructions, as these numbers are based on different operating conditions.
440-480 V, 60 Hz
AHF,N
19 A 10, 15 175G6612 175G6634 8011, 8016
26 A 20 175G6613 175G6635 8022
35 A 25, 30 175G6614 175G6636 8027, 8032
43 A 40 175G6615 175G6637 8042
72 A 50, 60 175G6616 175G6638 8052, 8062 101 A 75 175G6617 175G6639 8072 144 A 100, 125 175G6618 175G6640 8102, 8122 180 A 150 175G6619 175G6641 8152 217 A 200 175G6620 175G6642 8202 289 A 250 175G6621 175G6643 8252 324 A 300 175G6689 175G6692 8302 370 A 350 175G6690 175G6693 8352
Higher ratings can be achieved by p
506 A 450 217 A and 289 A units 8452 578 A 500 Two 289 A units 8502 578 A 550 Two 289 A units 8602 648 A 600 Two 324 A units 8652
Typical Motor Used [HP]
aralleling the filter units
Danfoss ordering numberI AHF 005 A HF 010
VLT 8000
Please note that the matching of the Danfoss frequency converter and filter is pre-calculated based on 480 V and assuming typical motor load. VLT 8000 is based on 110 % torque application. The pre-calculated filter current may be varying from the input current ratings of VLT 8000 as stated in the respective operating instructions, as these numbers are based on different operating conditions.
690 V, 50 Hz
IAHF,N Ty p ic a l m o to r u s ed Ordering no. AHF 005 Ordering no. AHF 010 VLT 8000 110%
43 37, 45 130B2328 130B2293 8052
72 55, 75 130B2330 130B2295 8062, 8072 101 90 130B2331 130B2296 8102 144 110, 132 130B2333 130B2298 8122, 8152 180 160 130B2334 130B2299 8202 217 200 130B2335 130B2300 8252 289 250 130B2331 & 130B2333 130B2301 8302 324 315 130B2333 & 130B2334 130B2302 8352 370 400 130B2334 & 130B2335 130B2304 8402 469 500 130B2333 & 2 x
130B2334 578 560 3 x 130B2334 2 x 130B2301 8602 613 630 3 x 130B2335 130B2301 & 130B2302 8652
130B2299 & 130B2301 8502
24
MG.83.A2.02 - VLT is a registered Danfoss trademark
VLT®8000 AQUA
Unpacking and ordering a VLT frequency converter
If you are in doubt as to which frequency converter you have received and which options it contains, use the following to find out.
Type code ordering number string
On the basis of your order, the frequency converter is given an ordering number that can be seen from the nameplate on the unit. The number may look as follows:
VLT-8008-A-T4-C20-R3-DL-F10-A00-C0
This means that the frequency converter ordered is a VLT 8008 for three-phase mains voltage of 380-480 V (T4) in Compact enclosure IP 20 (C20). The hardware variant is with integral RFI filter, classes A & B (R3). The frequency converter features a control unit (DL)witha PROFIBUS option card (F10). No option card (A00) and no conformal coating (C0) Character no. 8 (A) indicates the application range of the unit: A =AQUA.
IP 00: This enclosure is only available for the larger power sizes of the VLT 8000 AQUA series. It is recommended for installation in standard cabinets. IP 20/NEMA 1: This enclosure is used as standard enclosure for VLT 8000 AQUA. It is ideal for cabinet installation in areas where a high degree of protection is required. This enclose also permits side-by-side installation. IP 54: This enclosure can be fitted direct to the wall. Cabinets are not required. IP 54 units can also be installed side-by-side.
Hardware variant Theunitsintheprogrammeareavailableinthe following hardware variants: ST: Standard unit with or without control
unit. Without DC terminals, except for VLT 8042-8062, 200-240 V
VLT 8016-8300, 525-600 V SL: Standard unit with DC terminals. EX: Extended unit with control unit, DC
terminals, connection of external 24 V
DC supply for back-up of control PCB. DX: Extended unit with control unit, DC
terminals, built-in mains fuses and
disconnector, connection of external 24
V DC supply for back-up of control PCB. PF: Standard unit with 24 V DC supply for
back-up of control PCB and built-in
main fuses. No DC terminals. PS: Standard unit with 24 V DC supply
for back-up of control PCB. No DC
terminals. PD: Standard unit with 24 V DC supply for
back-up of control PCB, built-in main
fuses and disconnect. No DC terminals.
RFI filter Units for a mains voltage of 380-480 V and a motor power of up to 7.5 kW (VLT 8011) are always supplied with an integral class A1 & B filter. Units for higher motor power than these can be ordered either with or without an RFI filter. RFI filters are not available for 525-600 V units.
Introduction
A1 RFI is not offered on the VLT 8502 -8652 525-690V
Control unit (keypad and display) All types of units in the programme, except for IP 54 units (and IP 21 VLT 8452-8652, 380-480 V and VLT 8502-8652, 525-690 V), can be ordered either with or without the control unit. IP 54 units always come with acontrolunit. All types of units in the programme are available with built-in application options including a relay card with four relays or a cascade controller card.
Conformal Coating All types of units in the programme are available with or without conformal coating of the PCB. Please note VLT 8452-8652, 380-480 V and VLT 8052-8652, 525-690 V are only available as conformal coated.
MG.83.A2.02 - VLT is a registered Danfoss trademark
25
200-240 V
VLT®8000 AQUA
Typecode
Position in string
T2
9-10
C00
11-13
C20
11-13
CN1
11-13
C54
11-13ST14-15SL14-15R016-17R116-17R316-17
4.0 kW/5.0 HP 8006 XXXXXX
5.5 kW/7.5 HP 8008 XXXXXX
7.5 kW/10 HP 8011 XXXXXX 11 kW/15 HP 8016 XXXXXX 15 kW/20 HP 8022 XXXXXX
18.5 kW/25 HP 8027 XXXXXX 22 kW/30 HP 8032 XXXXXX 30 kW/40 HP 8042 XXXX XX 37 kW/50 HP 8052 XXXX XX 45 kW/60 HP 8062 XXXX XX
380-480 V
Typecode
Position in stringT49-10
4.0 kW/5.0 HP 8006 XXXX X
5.5 kW/7.5 HP 8008 XXXX X
7.5 kW/10 HP 8011 XXXXX 11 kW/15 HP 8016 XXXX X XX 15 kW/20 HP 8022 XXXX X XX
18.5 kW/25 HP 8027 XXXX X XX 22 kW/30 HP 8032 XXXX X XX 30 kW/40 HP 8042 XXXX X XX 37 kW/50 HP 8052 XXXX X XX 45 kW/60 HP 8062 XXXX X XX 55 kW/75 HP 8072 XXXX X XX 75 kW/100 HP 8102 XXXX X XX 90 kW/125 HP 8122 XXXX X XX 110 kW/150 HP 8152 XXXXXXXXXXX 132 kW/200 HP 8202 XXXXXXXXXXX 160 kW/250 HP 8252 XXXXXXXXXXX 200 kW/300 HP 8302 XXXXXXXXXXX 250 kW/350 HP 8352 XXXXXXXXXXX 315 kW/450 HP 8452 XXXXXXXXXXX 355 kW/500 HP 8502 XXXXXXXXXXX 400 kW/550 HP 8602 XXXXXXXXXXX 450 kW/600 HP 8652 XXXXXXXXXXX
C00
11-13
C20
11-13
CN1
C54
11-13
11-13ST14-15SL14-15EX14-15DX14-15PS14-15PD14-15PF14-15R016-17R116-17R316-17
Voltage
T2: 200-240 VAC T4: 380-480 VAC
Enclosure
C00: Compact IP 00 C20: Compact IP 20 CN1: Compact NEMA 1 C54: Compact IP 54
NB!:
NEMA 1 exceeds IP 20
26
Hardware variant
ST: Standard SL: Standard with DC terminals EX: Extended with 24 V supply and DC terminals DX: Extended with 24 V supply, DC terminals, disconnect and fuse PS: Standard with 24 V supply PD: Standard with 24 V supply, fuse and disconnect PF: Standard with 24 V supply and fuse
RFI filter
R0: Without filter R1: Class A1 filter R3: Class A1 and B filter
MG.83.A2.02 - VLT is a registered Danfoss trademark
525-600 V
VLT®8000 AQUA
Typecode
Position in string
1.1 kW/1.5 HP 8002 XXX X
1.5 kW/2.0 HP 8003 XXX X
2.2 kW/3.0 HP 8004 XXX X
3.0 kW/4.0 HP 8005 XXX X
4.0 kW/5.0 HP 8006 XXX X
5.5 kW/7.5 HP 8008 XXX X
7.5 kW/10 HP 8011 XXX X 11 kW/15 HP 8016 X X X 15 kW/20 HP 8022 X X X
18.5 kW/25 HP 8027 X X X 22 kW/30 HP 8032 X X X 30 kW/40 HP 8042 X X X 37 kW/50 HP 8052 X X X 45 kW/60 HP 8062 X X X 55 kW/75 HP 8072 X X X
T6
9-10
C00
11-13
C20
11-13
CN1
11-13
ST
14-15
R0
16-17
525-690 V
Typecode
Position in string 45 kW/50 HP 8052 XXXX X X XX X XX 55 kW/60 HP 8062 XXXX X X XX X XX 75 kW/75 HP 8072 XXXX X X XX X XX
T7
9-10
C00
11-13
CN1
C54
11-13
11-13ST11-13EX11-13DX14-15PS14-15PD14-15PF14-15R016-17R116-17
Introduction
1)
90 kW/100 HP 8102 XXXX X X XX XXX 110 kW/125 HP 8122 XXXX X X XX XXX 132 kW/150 HP 8152 XXXX X X XX XXX 160 kW/200 HP 8202 XXXX X X XX XXX 200 kW/250 HP 8252 XXXX X X XX XXX 250 kW/300 HP 8302 XXXX X X XX XXX 315 kW/350 HP 8352 XXXX X X XX XXX 400 kW/400 HP 8402 XXXX X X XX XXX 500 kW/400 HP 8502 XXXX X X XX XX 560 kW/500 HP 8602 XXXX X X XX XX 630 kW/600 HP 8652 XXXX X X XX XX
1) R1 is not available with DX, PF and PD variants.
T7: 525-690 VAC C00: Compact IP 00 C20: Compact IP 20
CN1: Compact NEMA 1 ST: Standard R0: Without filter R1: Class A1 filter
NB!:
NEMA 1 exceeds IP 20
MG.83.A2.02 - VLT is a registered Danfoss trademark
27
Optional selections, 200-600 V
Display Position: 18-19
D01)Without LCP DL With LCP
Fieldbus option Position: 20-22 F00 No options F10 Profibus DP V1 F30 DeviceNet F40 LonWorks free topology
Application option Position: 23-25 A00 No options A312)Relay card 4 relays A32 Cascade Controller
Coating Position: 26-27 C03)No coating C1 With coating
1) Not available with enclosure compact IP 54
2) Not available with fieldbus options (Fxx)
3) Not available for power sizes from 8452 to 8652, 380-480 V and VLT 8052-8652, 525-690 V
VLT®8000 AQUA
28
MG.83.A2.02 - VLT is a registered Danfoss trademark
TYPE CODE Table/Ordering form
VLT®8000 AQUA
Introduction
MG.83.A2.02 - VLT is a registered Danfoss trademark
29
VLT®8000 AQUA
General technical data
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units ........................................................................ 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-480 V units ................................................................ 3 x 380/400/415/440/460/480 V ±10%
Supply voltage 525-600 V units ............................................................................... 3 x 525/550/575/600 V ±10%
Supply voltage 525-690 V units ........................................................................ 3 x 525/550/575/600/690 V ±10%
Supply frequency ......................................................................................................................... 48-62 Hz +/- 1%
Max imbalance of supply voltage:
VLT 8006-8011/380-480 V and VLT 8002-8011/525-600 V .................................... ±2.0% of rated supply voltage
VLT 8016-8072/525-600 V, 380-480 V and VLT 8006-8032/200-240 V ................. ±1.5% of rated supply voltage
VLT 8102-8652/380-480 V and VLT 8042-8062/200-240 V ................................... ±3.0% of rated supply voltage
VLT 8052-8652/525-690 V ..................................................................................... ±3.0% of rated supply voltage
Displacement factor / cos. ϕ ...................................................................................................... near unity (> 0.98)
True Power Factor (λ) ..................................................................................................... nominal 0.90 at rated load
Input Mains (L1, L2, L3) Allowable On-OFF Switching Sequences ......................................... approx. 1 time/2 min.
Max. short-circuit current ............................................................................................................................ 100 kA
VLT output data (U, V, W):
Output voltage ................................................................................................................ 0-100% of supply voltage
Output frequency 8006-8032, 200-240V ............................................................................ 0 - 120 Hz, 0-1000 Hz
Output frequency 8042-8062, 200-240V .............................................................................. 0 - 120 Hz, 0-450 Hz
Output frequency 8072-8652, 380-460V .............................................................................. 0 - 120 Hz, 0-450 Hz
Output frequency 8002-8016, 525-600V ............................................................................ 0 - 120 Hz, 0-1000 Hz
Output frequency 8022-8062, 525-600V .............................................................................. 0 - 120 Hz, 0-450 Hz
Output frequency 8072, 525-600V ....................................................................................... 0 - 120 Hz, 0-450Hz
Output frequency 8052-8352, 525-690V .............................................................................. 0 - 132 Hz, 0-200 Hz
Output frequency 8402-8652, 525-690V .............................................................................. 0 - 132 Hz, 0-150 Hz
Rated motor voltage, 200-240 V units .............................................................................. 200/208/220/230/240V
Rated motor voltage, 380-480 V units ...................................................................... 380/400/415/440/460/480 V
Rated motor voltage, 525-600 V units ............................................................................................ 525/550/575 V
Rated motor voltage, 525-690 V units ..................................................................................... 525/550/575/690 V
Rated motor frequency ............................................................................................................................ 50/60 Hz
Switching on output ................................................................................................................................. Unlimited
Ramp times ........................................................................................................................................ 1- 3600 sec.
Torque characteristics:
Starting torque ............................................................................................................................... 110% for 1 min.
Starting torque (parameter 110 High break-away torque) ....................................... Max. torque: 130% for 0.5 sec.
Acceleration torque ....................................................................................................................................... 100%
Overload torque ............................................................................................................................................ 110%
30
MG.83.A2.02 - VLT is a registered Danfoss trademark
Loading...
+ 176 hidden pages