Rotating shafts and electrical equipment can
be hazardous. Therefore, it is strongly
recommended that all electrical work conform
to National Electrical Code (NEC) and all local
regulations. Installation, start-up and
maintenance should be performed only by
qualified personnel.
Factory recommended procedures, included in this manual, should be
followed. Always disconnect electrical power before working on the
unit.
Although shaft couplings or belt drives are generally not furnished by
the manufacturer, rotating shafts, couplings and belts must be protected
with securely mounted metal guards that are of sufficient thickness to
provide protection against flying particles such as keys, bolts and
coupling parts. Even when the motor is stopped, it should be considered “alive” as long as its controller is energized. Automatic circuits may
start the motor at any time. Keep hands away from the output shaft until
the motor has completely stopped and power is disconnected from the
controller.
Motor control equipment and electronic controls are connected to
hazardous line voltages. When servicing drives and electronic controls,
there will be exposed components at or above line potential. Extreme
care should be taken to protect against shock. Stand on an insulating
pad and make it a habit to use only one hand when checking components. Always work with another person in case of an emergency.
Disconnect power whenever possible to check controls or to perform
maintenance. Be sure equipment is properly grounded. Wear safety
glasses whenever working on electric control or rotating equipment.
Safety Guidelines
1.The drive must be disconnected from the AC line before any
service work is done.
2.The “Stop/Off” key on the local control panel of the drive does not
disconnect the equipment from the AC line and is not to be used as
a safety switch.
3.Correct protective grounding of the equipment must be established. The user must be protected against supply voltage and the
motor must be protected against overload in accordance with
applicable national and local regulations.
4.Ground currents are higher than 3 mA.
Warnings Against Unintended Start
1.While the drive is connected to the AC line, the motor can be
brought to a stop by means of external switch closures, serial bus
commands or references. If personal safety considerations make it
necessary to ensure that no unintended start occurs, these stops
are not sufficient.
2.During programming of parameters, the motor may start. Be
certain that no one is in the area of the motor or driven equipment
when changing parameters.
3.A motor that has been stopped may start unexpectedly if faults
occur in the electronics of the drive, or if an overload, a fault in the
supply AC line or a fault in the motor connection or other fault
clears.
4.If the “Local/Hand” key is activated, the motor can only be brought
to a stop by means of the “Stop/Off” key or an external safety
interlock.
NOTE
It is responsibility of user or person installing
drive to provide proper grounding and branch
circuit protection for incoming power and
motor overload according to National Electrical
Code (NEC) and local codes.
Touching electrical parts may be fatal – even after equipment has
been disconnected from AC line. To be sure that capacitors have
fully discharged, wait 14 minutes after power has been removed
before touching any internal component.
2
The Electronic Thermal Relay (ETR) in UL listed VLTs provides Class
20 motor overload protection in accordance with NEC in single motor
applications, when parameter 117 is set for “ETR TRIP 1”, “ETR TRIP
2”, “ETR TRIP 3”, or “ETR TRIP 4”, and parameter 105 is set for
rated motor (nameplate) current.
DANGER
!
Table of Contents
Safet y Gui deli nes .................................................................................................................................................................................................... 2
Warnings Against Unintended Start.......................................................................................................................................................................... 2
Cross Reference – Model Number to VLT T ype......................................................................................................................................................6
Locations of Conduit Entry , T erminal Blocks and Switches ....................................................................................................................................... 8
Location of Input Power and Output Power........................................................................................................................................................... 11
Power Connections............................................................................................................................................................................................... 14
Input Power Connection ........................................................................................................................................................................ 14
Motor Wiring Connection........................................................................................................................................................................ 14
T erminal Tightening Torque................................................................................................................................................................... 15
Auxiliary Control Panel Tightening T orques........................................................................................................................................... 15
External DC Bus Connection................................................................................................................................................................. 16
High Voltage Form C Relay...................................................................................................................................................................16
Control Connections.............................................................................................................................................................................................. 17
Electrical Installations, Control T erminals ................................................................................................................................................17
Typical Control Connections.................................................................................................................................................................. 18
Electrical Installation, Control Wiring ....................................................................................................................................................... 19
DIP Switches 1 through 4 ...................................................................................................................................................................... 19
Ground Leakage Current ...................................................................................................................................................................... 19
Application Control Connection Examples.............................................................................................................................................................. 21
Control Panel........................................................................................................................................................................................................22
Keys for Parameter Changes ................................................................................................................................................................22
Local Control......................................................................................................................................................................................... 23
Display mode III .................................................................................................................................................................................... 25
Navigation Between Display Modes ...................................................................................................................................................... 25
Quick Menu ..........................................................................................................................................................................................................26
T o Enter or Change Quick Menu Parameter Data ................................................................................................................................. 26
Example of Changing Parameter Data................................................................................................................................................... 26
Step Change of Numeric Values............................................................................................................................................................27
Manual Initialization of Parameters ......................................................................................................................................................... 27
VL T 6000 Start-up................................................................................................................................................................................................. 28
Setting Up Drive for Motor Start ............................................................................................................................................................. 28
Operational T ests – HAND..................................................................................................................................................................... 28
Operational T ests – AUTO..................................................................................................................................................................... 28
Final Adjustments................................................................................................................................................................................... 28
General Troubleshooting.......................................................................................................................................................................28
Description of Parameters...................................................................................................................................................................... 29
Operation and Display – Parameters 000 through 017...................................................................................................................................29 - 34
Load and Motor – Parameters 100 through 117............................................................................................................................................. 34 - 39
DC Braking ........................................................................................................................................................................................... 38
Motor Thermal Protection....................................................................................................................................................................... 39
References and Limits – Parameters 200 through 228.................................................................................................................................... 40 - 47
Reference Type .................................................................................................................................................................................... 44
Input and Outputs – Parameters 300 through 328 ..........................................................................................................................................48 - 58
Analog Inputs ........................................................................................................................................................................................ 51
Feedback Signals in Open Loop............................................................................................................................................................ 63
PID for Process Regulation ...................................................................................................................................................................................64
Differentiator Gain Limit .......................................................................................................................................................................... 65
Optimization of the Process Regulator .................................................................................................................................................... 65
Serial Communication for FC Protocol ...................................................................................................................................................................70
Packet Communication ...........................................................................................................................................................................70
Serial Communication – Parameters 500 through 566 .................................................................................................................................... 80 - 85
Warning Word, Extended Status Word and Alarm Word......................................................................................................................... 86
Service Functions – Parameters 600 through 631.......................................................................................................................................... 88 - 92
Relay Card Functions – Parameters 700 through 711........................................................................................................................................... 93
Electrical Installation of the Relay Card ..................................................................................................................................................93
Status Messages ...................................................................................................................................................................................................94
Warnings and Alarms ............................................................................................................................................................................................ 96
Calculation of Resulting Reference ...................................................................................................................................................................... 101
Index ........................................................................................................................................................................................................ 108 - 115
SOFTWARE VERSION NOTICE: These Operating Instructions are used for all VLT 6000
Series Drives with software version 2.X and all prior versions. The software version number
4
can be determined from parameter 624,
Software Version
.
General
(
)
The specific installation instructions may vary depending upon the
model of VLT 6000 Series being installed. When this occurs, the model
can be identified by a “VLT T ype 6XXX” number . This number can be
found on the red nameplate on the outside of the left side of the drive
enclosure, or the outside of the right side of a drive with an auxiliary
enclosure. A cross reference from the VLT T ype to the Danfoss
Graham model number can be found on the next page.
The drive must always be installed vertically. To ensure that no injury
or damage occurs, the drive must always be firmly attached to the wall
or the floor before further installation work is carried out.
Clearances
The drive is cooled by means of air circulation. For proper cooling, the minimum
distances above and below the unit must be
maintained as shown in the table below. For
units with an auxiliary enclosure mounted with
the drive on a back panel, the required
clearances are measured from the top and
bottom of the drive, not the back panel.
All drives can be mounted with no side clearance. VLT 6350-6550
drives require 25 inches (605 mm) front space for access.
All drives except VLT 6002-6005, 200 to 240 V and VLT 6002-6011,
380 to 460 V must be mounted directly to the wall with no spacers. This
is to ensure that air flow is in contact with the heatsink all the way from
the bottom of the drive. If this is not possible, a metal plate at least as
large as the back of the drive must be firmly mounted to the back of the
drive. See the Cross Reference T able on the next page to convert
model numbers to drive type.
X
X
Must be mounted
flush to wall
Yes
Yes
Sufficient space must be left in front of the drive to provide for door
swing on units with a hinged door. In addition, sufficient room must be
available for installation and service access. On units with an auxiliary
enclosure, the auxiliary enclosure door will have a greater door swing
than the drive. See the dimensional drawings of the auxiliary enclosure
which are included with the drive.
Plenum Mounting
The drive is UL rated for plenum mounting. If the drive is to be mounted
in the plenum, allow sufficient access for servicing. All normal
clearance, temperature and humidity limitations apply.
Grounding Plate
VLT Type 6002-6005, 200 to 240 V and VLT 6002-6001, 380 to 460 V
drives with a NEMA 1 enclosure have a plastic bottom cover with
provision for conduit entry . T o meet UL requirements, the metal
grounding plate must be in place above the plastic bottom cover. It must
be grounded to the chassis, and the conduit grounded to it. If the
grounding plate is not factory installed, it must be installed in the drives
that have a plastic bottom panel to ensure proper grounding of the
conduit to the enclosure. Connect the ground wire from the grounding
plate to the ground tab marked with the ground symbol.
This tab is located near the AC line terminal strip. Mount the bottom
cover on the control unit.
Shielded Wires
Wires to control signals should be shielded to reduce radio frequency
noise interference.
When RFI is a concern, shielded cable should be used between the
drive and the motor.
If unshielded control wires are used, control inputs are subject to signal
disturbances. Such disturbances may affect drive operation. Extreme
noise levels may disturb the microprocessor of the control card.
The shield of the control wires must be grounded at the cable clamp at
the bottom of the drive, but the shield must continue with the cable all the
way up to the control card. The shield is not to be connected to any of
the terminals on the control card. For safety reasons, the insulation
around the shield should only be removed where it is connected to the
cable clamp. The insulation should be left on the shield between the
clamp and the terminals.
All drives except VL T 6002-6005, 200 to 240 V
and VL T 6002-6011, 380 to 460 V must be
mounted directly to a solid wall with no spacers
between the drive and the wall.
Generally speaking, all conductors coming from a shielded control
cable must be as short as possible. Long conductor ends attract noise.
The shield must be connected to the chassis by means of the cable
clamp. Long pigtails on the shield reduce the effectiveness of the shield.
All drives must have input fuses installed in the power supply to the
drive. These fuses may be specified as an option to the drive and
supplied by Danfoss Graham. If specified, they will be installed by
Danfoss Graham in an enclosure external to the drive which may
include other optional features. If not supplied by Danfoss Graham,
they must be supplied by the installer of the drive at the time of
installation.
The required type of fuse for each drive size is shown in the table
below. The fuse rating shown is both the maximum and the recommended fuse rating.
The drives are suitable for use on circuits capable of delivering not
more than 100,000 RMS symmetrical amps, 500 volts maximum (600
volts maximum for 575 volt drives), when used with the recommended
fuses.
208 Volt Input
Maximum Fuse
Model Number VLT Type
VLT6000C4.6600210KTN-R or JJN
VLT6000C6.6600315KTN-R or JJN
VLT6000C7.5600320KTN-R or JJN
VLT6000C11600425KTN-R or JJN
VLT6000C17600650KTN-R or JJN
VLT6000C24600850KTN-R or JJN
VLT6000C31601150KTN-R or JJN
VLT6000C46601660KTN-R or JJN
VLT6000C59602280KTN-R or JJN
VLT6000C756027125K TN-R or JJN
VLT6000C886032125K TN-R or JJN
VLT6000C1146042150FWX or FWH
VLT6000C1436052200FWX or FWH
VLT6000C1696062250FWX or FWH
Rating Bussman Type
460 Volt Input
Maximum Fuse
Model Number VLT Type
VLT6000H2.160026KTS -R or JJS
VLT6000H3.060026KTS -R or JJS
VLT6000H3.4600310KTS-R or JJS
VLT6000H4.8600410KTS-R or JJS
VLT6000H8.2600620KTS-R or JJS
VLT6000J2.760166KTS-R or similar
VLT6000J3.960166KTS-R or similar
VLT6000J6.1601610KTS-R or similar
VLT6000J9601620KTS-R or similar
VLT6000J11601625KTS-R or sim ilar
VLT6000J17601640KTS-R or sim ilar
VLT6000J22602240KTS-R or sim ilar
VLT6000J27602750KTS-R or sim ilar
VLT6000J32603260KTS-R or sim ilar
VLT6000J41604280KTS-R or sim ilar
VLT6000J526052100KTS-R or similar
VLT6000J626062125KTS-R or similar
Maximum Fuse
Rating Bussman Type
All fuse ratings are in amps
All fuse ratings are in amps
7
Locations of Conduit Entry, Terminal Blocks
and Switches
NEMA 1
VLT 6002-6032, 200 to 240 V
VLT 6002-6062, 380 to 575 V
VLT 6042-6062, 200 to 240 V, VLT 6075-6125, 380 to 460 V VLT 6150-6275, 380 to 460 V
8
Locations of Conduit Entry, Terminal Blocks
and Switches (continued)
NEMA 12
VLT 6002-6005, 200 to 240 V, VLT 6002-6011, 380 to 460 VVLT 6006-6032, 200 to 240 V ; VLT 6016-6032, 380 to 460 V
VLT 6042-6062, 200 to 240 V ; VLT 6075-6125, 380 to 460 VVLT 6150-6275, 380 to 460 V
9
Locations of Conduit Entry, Terminal Blocks
and Switches (continued)
NEMA 1 and NEMA 12
10
VLT 6350-6550, 380 to 460 V
Location of Input Power (Mains) and Output
WARNING
!
Power (Motor Terminal Blocks)
Connect input power to the terminals identified as L1, L2 and L3.
Connect the motor leads to the terminals identified as U, V and W.
Connecting input power to motor terminals will
result in drive failure when the power is applied.
NEMA 1 and NEMA 12
VLT 6002-6005, 200-240 V
VLT 6002-6011, 380-460 V
NEMA 1
VLT 6006-6032, 200-240 V
VLT 6016-6062, 380-575 V
NEMA 1
VLT 6042-6062, 200-240 V
VLT 6075-6125, 380-460 V
NEMA 1
VLT 6150-6275, 380-460 V
11
Location of Input Power (Mains) and Output
Power (Motor Terminal Blocks), continued
Connect input power to the terminals identified as L1, L2 and L3.
NEMA 12
VLT 6006-6032, 200-240 V
VLT 6016-6062, 380-460 V
NEMA 12
VLT 6042-6062, 200-240 V
VLT 6075-6125, 380-460 V
NEMA 12
VLT 6150-6275, 380-460 V
12
Location of Input Power (Mains) and Output
Power (Motor Terminal Blocks), continued
Connect input power to the terminals identified as L1, L2 and L3.
NEMA 1 and NEMA 12, VLT 6350-6550, 380-460 V
without disconnector and mains fuses
NEMA 1 and NEMA 12, VLT 6350-6550, 380-460 V
with disconnector and mains fuses
13
Power Connections
o
Make all power connections with 75
C rated copper wiring.
Conduit entry must be from the bottom on all drives. Conduit entries are
provided on smaller drives. For drives with auxiliary enclosures, refer
to the dimensional drawings provided for conduit entry locations.
T o meet UL requirements, install the metal grounding plate in all drives
that have a plastic bottom. Install the grounding plate just above the
plastic bottom. Ground the metal plate to the chassis and ground the
conduit to the metal plate.
The conduit entries provide strain relief for the wires in drives mounted
in NEMA 1 or NEMA 12 enclosures. With chassis mounted drives, the
power and control wires must have strain relief supplied by the installer.
ONOT rely on the terminal blocks to provide strain relief.
D
Input Power Connection
For drives with no auxiliary enclosure, connect input power to drive
terminals L1, L2, and L3, (terminal numbers 91, 92, and 93). If an auxiliary
enclosure is provided, input power connections are made in the auxiliary
enclosure. Refer to the connection diagrams shipped with the drive.
Size wiring to the input current of the drive as shown in the tables
below. Maximum AWG wire size is also provided.
WARNING
!
Connecting input power to motor terminals will
result in drive failure when power is applied.
Motor Wiring Connection
For drives with no auxiliary enclosure, connect the motor to drive
terminals U, V , and W (terminal numbers 96, 97, and 98). T erminal 99
is earth ground. If an auxiliary enclosure is provided, refer to the
connection diagrams shipped with the drive. Ground the shield on the
motor wire, if used, at both the drive and the motor.
DANGER
!
For operator safety, it is important to ground
drive properly.
Grounding
Ground the drive properly. Use a ground wire at least 7 AWG (10mm2).
Connect the ground wire directly to a reliable earth ground. Do not use
the conduit connecting to the drive as a replacement for a ground wire. Do
not ground one drive to another in a “daisy chain” fashion.
Electronic Thermal Protection
The electronic thermal relay is UL approved for single motor thermal
protection as long as the following is complied with:
CAUTION
!
Enclosures for larger drives and auxiliary enclosures are made of metal. To avoid getting
metal chips into electronics, do not drill any
holes after unit has been installed in a vertical
position.
575 VAC Input Current/Wire Gage
208 VAC Input Current/Wire Gage
Drive Input
Current
5.010
6.010
7.010
10.010
16.010
23.06
30.06
46.06
59.22
74.82
88.00
101.31/0
126.6
149.94/0C169
Maximum
AWG
3/0
Model
C4.6
C6.6
C7.5
C11
C17
C24
C31
C46
C59
C75
C88
C114
C143
All current ratings are in amps.
1.Parameter 1 17, Thermal Protection, is set to ETR TRIP .
2.Parameter 105, Motor Current, is set for the full-load nameplate
Tighten terminals connecting the drive input power, output to the motor(s)
and ground to the values shown in the tables below. Drives with 200 to
240 volts of 88 amps and less, and drives with 380 to 575 volts of 90 amps
and less, have removable terminal blocks with screws. Larger drives have
fixed bolts. (See the drive nameplate for maximum drive output current.)
200 to 240 VAC Terminal Tightening Torque
NOTE
Tighten terminals of 575 volt drives of 32 amps
and below to 17 in-lbs (1.8 Nm), and above 32
amps to 28 in-lbs (3.0 Nm).
380 to 460 VAC Terminal Tightening Torque
Max. Drive
Output Current
6.65 (0.6)
7.55 (0.6)
10.65 (0.6)
16.75 (0.6)
24.217 (1.8)
30.817 (1.8)
46.228 (3.0)
59.428 (3.0)
74.828 (3.0)
8835 (4.0)
114100 (11.3)
143100 (11.3)
169100 (11.3)
Torque
in-lbs (Nm )
Max. Drive
Output Current
All current ratings are in amps.
200 to 240 VAC Auxiliary Control Panel Tightening Torques
Max. Drive
Output Current
to 6.615 (1.7)15 (1.7)22 (2.5)7 (0.8)20 (2.3)35 (4.0)45 (5.1)
All current ratings are in amps. All torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
Overload
Relay
Power Terminal
Blocks
Circuit
Breaker
Disc onnect or
Transfer Switch
Main or
Bypass Fuse
Block
Drive Fuse
Block
Ground
Terminal
15
Multiple Motors
The VLT 6000 can control several motors at once, all changing speed
together. The sum of the nameplate currents of all the motors must not
exceed the current rating of the drive.
WARNING
!
When multiple motors are used, VLT 6000 electronic thermal relay cannot be used to provide
individual motor protection. A separate motor overload must be supplied for each motor.
If the multiple motors are of significantly different sizes, starting problems
may occur. This is because the higher electrical resistance of smaller
motors will require more start voltage than larger motors.
CAUTION
!
Automatic Motor Adaptation and Automatic
Energy Optimization cannot be used for multiple motor installations.
External DC Bus Connection
T erminals 88 and 89 access the DC bus of the drive. They can provide
DC backup power for the drive or to connect to a 12-pulse input
rectifier.
DANGER
!
Terminals 88 and 89 will be at approximately
150% of line voltage and remain at high voltage for up to 14 minutes after power has been
removed from the drive.
WARNING
!
Do not connect anything to terminals 88 and 89
without first consulting with Danfoss Graham.
High Voltage Form C Relay
The connections for the high-voltage relay are terminals 01, 02, 03.
The high-voltage relay is programmed in parameter 323, Relay
Output 1.
1+3 normally closed, 1+2 normally open
Max. 240 VAC, 2 Amp
Min. 24 VDC, 10 mA or
24 VAC, 100 mA
Max. wire gage:10 AWG (4 mm2)
T erminal Torque:5 in-lbs ( 0.5 - 0.6 Nm)
16
Electronic Control T erminals
Control Connections
All terminals for the low voltage control wires are located under the
protective cover below the keypad. Remove the cover with a
screwdriver or other pointed object as shown below.
The following is a description of the functions of the control terminals.
Many of these terminals have multiple functions determined by
parameter settings.
No.Function
01, 02, 03Form C relay output. Maximum 240 V AC, 2 A.
Minimum 24 VDC, 10 mA or 24 VAC, 100 mA.
(Location of Form C relay output varies with unit
type. See connection diagram with unit for
location.)
04, 0530 VAC, 42.5 VDC, 1 A relay output can be used
for indicating status and warnings.
12, 13Voltage supply to digital inputs and external
transducers. For the 24 VDC to be used for digital
inputs, switch 4 on the control card must be closed,
position “on.” The maximum output current is 200 mA.
16 - 33Digital inputs. R = 2 kohm. <5 V = logical “0”,
>10 V = logical “1”. See parameters 300 through
307, Digital Inputs.
Electrical Installation, Control Terminals
T orque the control terminals to 5 in-lbs (0.5-0.6 N-m)
The diagram below shows the location of the control terminals. The
programming section of the manual covers the programmable terminals
in greater depth.
20Common for digital inputs.
39Common for analog and digital outputs.
42, 45Analog and digital outputs for indicating frequency,
reference, current and torque. The analog signal
is 0 to 20 mA, or 4 to 20 mA at a maximum of
500€Ω. The digital signal is 24 VDC at a minimum
of 600 Ω . See parameters 319-322, Analog/digital Outputs.
5010 VDC, 17 mA maximum analog supply voltage
to potentiometer and thermistor.
53, 540 to 10 VDC voltage input, R = 10 kΩ.
55Common for analog inputs. This common is
isolated from the common of all other power
supplies. If, for example, the drive’s 24 VDC
power supply is used to power an external
transducer which provides an analog input signal,
terminal 55 must be wired to terminal 39.
600 to 20 mA or 4 to 20 mA, analog current input, R
= 188 Ω . See parameters 314 through 316.
61 Shield for serial communication.
68, 69RS-485 interface and serial communication. When
the drive is connected to an RS-485 serial
communication bus, DIP switch settings on the
control card may have to be reset. See DipSwitches 1 through 4 in this manual.
17
Typical Control Connections
Shown below are typical interfaces between the VLT 6000 and other
components in an HVAC system. The terminal numbers and the
functions of the terminals are identical on all VLT 6000s. An optional
relay card, not shown, can provide four additional Form C output
relays. The RS-485 connections allow direct communication through
Typical* VLT 6000 Wiring
the drive’s built-in serial communication protocols: Johnson Controls
®
Metasys
N2, Siemens System 600 FLN®, or VLT Software Dialog®.
LonWorks® and Profibus® are available through option cards that fit into
the relay output card location.
3 Phase
Power
Input
External
DC Bus
Connection
+10 V DC
0 - 10 V DC
Ref. Input*
0 - 10 V DC
Ref. Input*
4 - 20 mA
Ref. Input*
Reset*
Lockout*
Run/Stop*
Reverse*
Interlock*
Preset Speed*
91 (L1)
92 (L2)
93 (L3)
99 (PE)
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
60 (A IN)
12 (+24 V OUT)
13 (+24 V OUT)
16 (D IN)
17 (D IN)
18 (D IN)
19 (D IN)
20 (COM D IN)
27 (D IN)
29 (D IN)
SW4
Switch Mode
Power Supply
10 V DC
17 mA
+-
RS-485
Interface
+-
5 V
SW2SW3
24 V DC
200 mA
(U) 96
(V) 97
(W) 98
(PE) 95
(AUX RELAY) 01
( AUX RELAY) 02
(AUX RELAY) 03
(RELAY) 04
(RELAY) 05
(COM A OUT) 39
(A OUT) 42
0 V
(A OUT) 45
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
Motor
Fault Indication*
240 V AC, 2 A
Run Indication*
30 V AC, 1 A
Output Current Indication*
4 - 20 mA
Output Speed Indication*
4 - 20 mA
+
RS-485
-
Setup Select*
Setup Select*
32 (D IN)
33 (D IN)
* The operation of all control inputs and outputs is programmable.
* Typical terminal functions are shown.
18
CAUTION
!
Incoming power, motor wiring and control wiring should be run in three separate conduits or
raceways.
Electrical Installation, Control Wiring
Torque: 5 - 6 in-lbs
Screw size: M3
Shield control wires, when necessary, to reduce interference from
electrical noise by means of a cable clamp at both ends to the metal
enclosure of the unit. Connect the shield to earth ground. Very long
control wires may create 60 Hz interference. This problem can be
solved by connecting one end of the shield to earth with a 0.1 µF
capacitor, keeping the leads as short as possible. If this doesn’t solve
the problem, disconnect the shield’s connection to earth ground at the
end opposite to the drive.
DIP Switches 1 through 4
DIP switches are located on the control card.
They are used for serial communication and the common of digital
inputs 16 through 33. The switch positions shown are the factory
settings.
Switch 1 is not used.
Switches 2 and 3 are used for terminating serial communication. On the
first and last drive in a multiple device network, or on the only drive of a
single drive network, switches 2 and 3 must be ON (the default setting).
On all other drives in a multiple device network, set switches 2 and 3 to
OFF.
Switch 4 separates the common for the internal 24 VDC supply from the
common of the external 24 VDC supply. Normally this switch is ON and
the power supply is present at terminals 12 and 13. Set Switch 4 to the
OFF position when an external 24 VDC supply is used.
Ground Leakage Current
It is normal for there to be some leakage current from the drive to earth
ground. Paths of current leakage are shown on the drawing below.
The leakage current will exceed 3.5 mA.
Paths of Normal Current Leakage to Ground
19
Galvanic Isolation
Galvanic isolation offers protection from electric shock. All control
terminals of all VLT 6000 drives, and terminals 1 through 3 of the relay
output, offer galvanic isolation as long as the RFI switch (if provided) is
in the ON position. The galvanic isolation in the VLT 6000 conforms to
the European standard EN 50178. (See figure below.)
The components that make up the galvanic isolation are:
1.Power supply, including signal isolation.
2.Gate drive for the IGBT s, the trigger transformers and optocouplers.
3.The output current Hall effect transducers.
Galvanic Isolation
Electrical Noise
In general, electrical noise can be divided into two forms: wire-borne
electromagnetic interference (EMI), and radiating radio frequency
interference (RFI).
Using shielded motor cables reduces RFI but increases EMI. This is
because shielded wires have a greater capacitance than unshielded
wires. Unshielded input power connections to the drive generate more
noise in the radio frequency range on the AC line. The shield reduces
the radiated noise, but increases the low-frequency electromagnetic
noise on the AC line. But, since the noise current is taken back to the
unit through the shield, only a small electromagnetic field is generated
from shielded motor wires.
With an EMI filter, the noise level on the AC line will be reduced to
about the same level for shielded and unshielded wires alike.
Connect the motor wiring shield, if used, in the enclosure of the drive as
well as at the motor. Use shield brackets to avoid “pigtail” shield ends.
Even short “pigtails” increase the shield’s impedance at higher
frequencies, which reduces the shield’s effect and increases the noise
produced.
It is generally easier and less complicated to use unshielded motor
wires than shielded cables. If unshielded wires are used, the RFI will
be greater. But, since the strength of the radiated signal decreases with
distance from the signal source, radiated noise is generally not a
problem.
T o reduce the noise level from the total system (drive + installation)
make the motor wiring as short as possible.
Provide separate conduits, or raceways, for power, motor and control
wiring to provide the greatest immunity from distortion.
20
Application Control Connection Examples
Two-wire Start/Stop
In Auto mode, closing the contact to terminal 18 will make the drive run.
In any mode, opening the safety interlock contact to terminal 27 will stop
the drive.
Set Parameter 302 to Start.
Set Parameter 304 to External Fault.
Digital Speed Up/down
Closing the switch to terminal 32 will make the drive accelerate. Closing
the switch to terminal 33 will make the drive decelerate.
Run Permissive
After receiving a run command,
the drive will apply power to the
damper motor and wait until it
receives “permission” via the
switch that is connected to
terminal 16.
Set Parameter 300 to Run Permissive.
Set Parameter 302 to Start.
Set Parameter 304 to External Fault.
Set Parameter 323 to Start Signal Applied.
Two Feedback Signals
The drive processes two
independent feedback
signals during closed loop
operation. It can respond to
the sum, difference,
average, minimum or
maximum of these signals.
Set Parameter 306 to Speed up.
Set Parameter 307 to Speed down.
Set Parameter 305 to Freeze reference.
Potentiometer Reference
A manual potentiometer is used as a input reference for the drive.
Set Parameter 308, T erminal 53, Analog Input V oltage, to Reference.
Set Parameter 309, T erminal 53, Min. Scaling, to 0 V.
Set Parameter 310, T erminal 53, Max. Scaling, to 10 V.
Set Parameter 308 to FEEDBACK.
Set Parameter 311 to FEEDBACK
Set Parameter 417 for the desired operation.
Transmitter Connection
The drive’s internal 24
VDC power supply is
used to power an
external 4 to 20 mA
transducer.
Set Parameter 314, T erminal 60, Analog Input Curent, to
correspond to the purpose of the 4 to 20 mA signal.
Set Parameter 315, T erminal 60, Min. Scaling, to 4 mA
Set Parameter 316, T erminal 60, Max. Scaling, to 20 mA.
Because the commons of the +24 VDC power supply and the input
reference follower have separate circuit commons, it is necessary to
connect a jumper between terminals 39 and 55.
21
Control Panel
The Local Control Panel (LCP), normally mounted on the front of the
drive, is a complete interface for programming and operating the drive.
The control panel can be removed from the drive and installed up to 10
feet (3 meters) from the drive by using a remote mounting kit.
The control panel has five functions:
1.Display
2.Keys for changing the display
3.Keys for changing programming parameters
4.Keys for controlling drive operation
5.Indicator lamps
The LCP uses a four-line, alpha-numeric, back-lit, LCD display. The
display can show four operating data values and three operating
condition values continuously. During programming, all the information
required for quick, effective parameter setup of the drive will be
displayed. As a supplement to the display, there are three indicator
lamps for power on (ON), warning (WARNING) and alarm (ALARM).
All drive parameters can be changed from the control panel, unless this
ability has been locked out by setting parameter 016, Lock for DataChange, to Locked, or by a digital input to terminals 16 through 33. See
the related parameters for more information.
Keys for Parameter Changes
The keys are divided into groups by function. The keys between the
display and indicator lamps are used for parameter setup, selecting the
display indication during normal operation and controlling the drive
speed during local speed control operation. The keys below the
indicator lamps are used for Start/Stop control and selection of the
operating site.
The DISPLAY MODE key is used to select the mode of
the display or to return to the Display Mode from either
the Quick Menu or the Extend Menu mode.
The QUICK MENU key gives access to the parameters
available for the Quick Menu setup. Parameters in this
menu are the 12 most important setup parameters for
the drive.
The EXTEND MENU key gives access to all parameters.
The CHANGE DATA key is used for changing the value
of a parameter selected either in the Extend Menu or
the Quick Menu mode. The desired parameter is first
selected. Then the CHANGE DAT A key is pressed to
enable the editing of the parameter. The underline in the
display will move under the parameter’s value to show
that it is being edited.
The CANCEL key is used if a change of the selected
parameter is not to be carried out.
The OK key is used for confirming a change of the
parameter selected.
22
The + and - keys are used to scroll through parameters
and to change the value of a chosen parameter. These
keys are also used to change the local reference. In
Display Mode, these keys are used to switch between
readouts.
The L and M keys are used to select a parameter
group and also to move the cursor to the desired digit
when changing numerical values.
Indicator Lamps
At the bottom of the control panel is a red alarm LED, a yellow warning
LED, and a green power on LED.
red yellow green
The OFF/STOP key is used for stopping the connected
motor in either the Hand or Auto mode. Enable or
Disable via parameter 013. If this stop function is
activated, the second line in the LCD display will flash.
AUTO ST ART is used if the drive is to be started via the
control terminals and/or serial communication. When a
remote start signal is active, the drive will start if the
AUTO ST ART key has been pressed.
DANGER
!
A start signal via digital inputs may cause drive
to start at any time. Remove power to drive before working on output wiring, motor or any
driven equipment.
If certain threshold values are exceeded, the alarm and/or warning
lamps will flash and text describing the alarm or warning condition will
be displayed.
Local Control
Below the indicator lamps are keys which are used to determine the
point of control. Each of these keys can be individually enabled or
disabled using parameter 012 through 015. The Hand Start and Auto
Start keys will also be disabled if any of the control terminals are
programmed for either Remote Hand or Remote Auto.
The HAND STAR T key is used if the drive is to be
started from the control panel. Pressing HAND STAR T
will give a start command to the drive.
WARNING
!
If a minimum speed is set in parameter 201,
Output Frequency Low Limit
and ramp up to this frequency when HAND
START is pressed. If drive is already running in
Auto Mode when the HAND START key is
pressed, it will switch to run in Hand Mode at
same speed.
, motor will start
The RESET key is used for manually resetting the drive
after a fault trip (alarm). In this case, the top line of the
display will show TRIP (RESET). If the top line of the
display shows TRIP (AUTO START), the drive will
automatically restart. If the top line of the display shows
TRIPLOCK (DISC. MAINS), input power to the drive
must be removed before the trip can be reset.
Display Mode
Information is displayed on the LCD by selecting one of three programmable display modes. Pressing the Display Mode key toggles among
the displays. When in Mode II, pressing and holding down the Display
Mode key accesses an additional mode used to identify the data units
the display is showing. (See Navigation Between Display Modes.)
In normal operation, any four meters can be shown continuously on the
first and second lines of the display. Parameters 008, 009 and 010
select the three readouts displayed on the top line. Parameter 007,
Large Display Readout, selects the meter displayed on line 2. In
Display Mode, the + and - keys choose any meter on the LCD.
A list on the next page gives the operating data that can be shown on
the three meter readouts for line 1 and the large display (line 2).
The right side of line 2 shows the active setup number and an arrow
indicateing the direction of motor rotation. Clockwise indicates forward
and counterclockwise indicates reverse. The arrow body disappears if
a stop command is given or if the output frequency falls below 0.01 Hz.
Warnings and alarms (fault trips) will also be displayed. For an alarm,
“ALARM” and the alarm number is shown in line 2 with an explanation
in line 3 or in lines 3 and 4. For a warning, “WARN.” and the warning
number is shown in line 2 and an explanation in 3 and/or 4. Both
alarms and warnings cause the display to flash.
The line 4 automatically displays the operating status of the drive.
23
The table below gives the operating data options for the first and
second lines of the display .
Data Item:Unit:
Resulting reference, %%
Resulting reference unit chosen in par. 415
FrequencyHz
% of maximum output frequency%
Motor currentA
PowerkW
PowerHP
Output energykW h
Hours runhours
User defined readout unit chosen in par. 006
Setpoint 1 unit chosen in par. 415
Setpoint 2 unit chosen in par. 415
Feedback 1 unit chosen in par. 415
Feedback 2 unit chosen in par. 415
Feedback unit chosen in par. 415
Motor voltageV
DC link voltageV
Thermal load on motor%
Thermal load on VLT%
Input status, digital inputbinary code
Input status, analog terminal 53V
Input status, analog terminal 54V
Input status, analog terminal 60mA
Pulse referenceHz
External reference%
Heat sink temperature
o
C
Line 4 is the status line and the information is automatically generated
for display by the drive in response to its operation. It shows that the
drive is in auto mode, with remote reference, and that the motor is
running. Some possible displays of the status line are shown below.
80.0% 5.08A
2.15kW
40.0Hz
SETUP
1
AUTO REMOTE RUN
HAND
OFF
LOCAL
STOP
RAMPING
JOGGING
.
.
.
.
STAND BY
The left part of the status line indicates where the drive Run/Stop
command is from, and whether it is on or off. AUTO means that Run/
Stop control is via the control terminals and/or serial interface; HAND
indicates that the drive started locally by the Hand Start key . OFF
means that the drive ignores all control commands and the motor will
not run.
The center part of the status line indicates the reference source that is
active. REMOTE means that the reference is from the control terminals.
LOCAL indicates that the reference is determined by the + and - keys
on the control panel.
Display Mode I:
Below is an example of Display Mode I, in which the drive is running in
setup 1, in Auto mode, with remote reference, at an output frequency of
40 Hz.
FREQUENCY
SETUP
40.0Hz
1
AUTO REMOTE RUN
The text in line 1, FREQUENCY , describes the meter shown in line 2.
Line 2 shows the current output frequency (40.0Hz), direction of
rotation (reverse), and active setup (1).
The right part of the status line indicates the drive’s operational status.
Display Mode II:
This display mode makes it possible to have three meters displayed at
the same time on line 1. The meters displayed are selected through
parameters 008, 009 and 010.
100% 7.8A 5.9kW
SETUP
50.0Hz
1
AUTO REMOTE RUN
24
Display Mode III:
This display mode is shown when the drive is in Display Mode II and the
Display Mode key is pressed and held. In the first line, a description of
the three top meters in Display Mode II is shown. The other lines are
unchanged. When the key is released, Display Mode II is again shown.
REF% CURR.A POW. kW
Display Mode IV:
This display mode is available when local reference is selected. In this
display mode, the speed reference is increased or decreased via +/- keys.
The first line shows the present speed reference. The second line
shows the present drive output frequency. The third line show a bar
graph of the relative value of the present drive output frequency in
relation to the maximum frequency.
50.0Hz
AUTO REMOTE RUN
Navigation Between
Display Modes
With local reference
SETUP
1
FREQUENCY
40.0Hz
AUTO REMOTE
RUNNING
Display Mode I
USE +/- 56Hz
40Hz
0 -----60
HAND LOCAL
RAMPING
SETUP
1
With remote
controlled reference
SETUP
1
With local/remote
reference
USE +/- 56Hz
SETUP
40.0Hz
0 ----60
HAND LOCAL
RAMPING
Display Mode IV
1
With local reference
▲▲
▲▲
▲
Keep DISPLAY
MODE key down
80% 7.8A 5.9kW
SETUP
40.0Hz
AUTO REMOTE RUN
Display Mode II
▲▲
▲
▲▲
REF% CURR.A POW. kW
40.0Hz
AUTO REMOTE RUN
Display Mode III
1
▼▼
▼
▼▼
Release DISPLAY
MODE key
SETUP
1
25
Quick Menu
The QUICK MENU key gives access to 12 of the most important setup
parameters of the drive. After programming, the drive will, in many
cases, be ready for operation. The 12 Quick Menu parameters are
Quick MenuParameterDescription
Item NumberName
1001 LanguageSelects language used for all displays.
2102 Motor PowerSets output characteristics of drive based on kW (HP) of motor. See
chart in parameter 102, Motor Power, to convert HP to kW.
3103 Motor VoltageSets output characteristics of drive based on voltage of motor .
4104 Motor FrequencySets output characteristics of drive based on nominal frequency of
motor. This is typically equal to line frequency .
5105 Motor CurrentSets output characteristics of drive based on full load current in amps
(FLA) of motor. This sets overload protection for motor .
6106 Motor Nominal SpeedSets output characteristics of drive based on nominal full load speed of
motor.
7201 Minimum FrequencySets minimum controlled frequency at which motor will run.
8202 Maximum FrequencySets maximum controlled frequency at which motor will run.
9206 Ramp Up TimeSets time to accelerate motor from 0 Hz to nominal motor frequency
set in Quick Menu Item 4.
10207 Ramp Down TimeSets time to decelerate motor from nominal motor frequency set in
Quick Menu Item 4 to 0 Hz.
1 1323 Relay 1 FunctionSets function of high voltage Form C relay.
12326 Relay 2 FunctionSets function of low voltage Form A relay.
shown in the table below. A complete description of the function is given
in the parameter sections of this manual.
To Enter or Change Quick Menu Parameter Data
Enter or change parameter data or settings in accordance with the
following procedure.
1.Press Quick Menu key.
2.Use ‘+’ and ‘-’ keys to find parameter you chose to edit.
3.Press Change Data key.
4.Use ‘+’ and ‘-’ keys to select correct parameter setting. T o move to
a different digit within parameter , use J and K arrows. Flashing
cursor indicates digit selected to change.
5.Press Cancel key to disregard change, or press OK key to accept
change and enter new setting.
Example of Changing Parameter Data
Assume Parameter 206, Ramp Up Time, is set at 60 seconds. Change
the ramp up time to 100 seconds in accordance with the following
procedure.
1.Press Quick Menu key.
2.Press ‘+’ key until you reach Parameter 206, Ramp Up Time.
3.Press Change Data key.
4.Press J key twice – hundreds digit will flash.
5.Press ‘+’ key once to change hundreds digit to ‘1.’
6.Press K key to change to tens digit.
7.Press ‘-’ key until ‘6’ counts down to ‘0’ and setting for Ramp UpTime reads ‘100 s.’
8.Press OK key to enter new value into drive controller.
NOTE
Programming of extended parameters functions
available through Extended Menu key is done
in accordance with same procedure as described for Quick Menu functions.
26
Extended Menu
CAUTION
!
In some applications, the Quick Menu items will not set up all the
desired characteristics of the drive. T o access all the parameters,
including the Quick Menu parameters, press the Extend Menu key. The
Programming section of this manual will describe in detail all the
parameters available through the Extended Menu.
Step Change of Numeric Values
The values of certain numeric items can also be selected from a list.
These parameters are Motor Power, parameter 102; Motor Voltage,
parameter 103; and Motor Frequency, parameter 104. T o select a
value not on the list, use the L and M keys to select the digit to be
changed, as described above.
Changing Data
T o change any parameter in either the Quick Menu mode or the
Extended Menu mode, press the CHANGE DAT A key. When the
CHANGE DAT A key is pressed, the data in line four will be underlined,
and a cursor will be shown if the parameter controls numeric data.
The procedure for changing data depends on whether the value of the
parameter is a number or a item from a list.
FREQUENCY
SETUP
24.2 Hz
1
205 MAX. REFERENCE
000060.000 Hz
Parameter is a Number
T o change a number , move the cursor to the digit to be changed by
using the LM keys. Then change the digit by using the + and - keys.
MOTOR CURRENT
SETUP
3.90 A
1
210 REFERENCE
TYPE SUM
Parameter is a Value Chosen from a List
Manual Initialization of Parameters
It is possible to reset nearly all parameters back to their original default
values at once. T o reset the drive parameters to their read only memory
default values, remove power from the drive. Press and hold the Display
Mode, Change Data and OK keys down while reapplying power. Shortly
after power is reapplied, the bottom line of the display will read “Initialized”. After the display stops changing, release the keys. If “Initialized” did
not appear, repeat the procedure.
These parameters are not reset by manual initialization:
Parameter 600Operating hours
Parameter 601 Hours run
Parameter 602 kWh counter
Parameter 603Number of power-ups
Parameter 604Number of overtemperatures
Parameter 605Number of overvoltages
Initialization can also be done using Parameter 620.
Manual initialization using either this procedure
or parameter 620 will reset drive to standard default parameters. Any special programming for
application that was performed at factory, during
start-up or subsequently, will be lost. If desired
parameters have been previously stored in drive’s
local control panel (LCP), it may be better to download those parameters from LCP using parameter
download functions of parameter 004.
Uploading Parameters
At any time the present parameters may be copied to the local control
panel (LCP). This may be useful when setting up multiple drives. It is
also useful when it is desired to return to a previous set of parameters.
See parameter 004, LCP Copy, for more information.
If the selected parameter’s value is selected from a list, its value can be
changed by using the + and - keys.
When the desired value is displayed, press the OK key to accept the new
value. If you wish to cancel the change and return to the previously
accepted value, press the CANCEL key . If neither OK nor CANCEL is
pressed, the new value will be accepted after 20 seconds.
Manually initializing the drive using either the procedure described
above or parameter 620, Operating Mode, does not change the
values uploaded to the local control panel.
27
VLT 6000 Start-Up
Pre-installation Checks
1. Compare drive model number to what was ordered.
2. Ensure each of following are rated for same voltage:
• Drive
• Power line
• Motor
3. Record following motor data:
• Voltage
• Frequency
• Full load current
• Full load speed
• Power — convert HP to kW (See conversion table in parameter
102, Motor Power, in this manual.)
4. Ensure that rated drive current is equal to or greater than total full
load current.
• For multiple motor operations, add up full load current ratings of
all motors.
• Drive can be at most one size smaller than motor.
• If drive rating is less than motor, full motor output cannot be achieved.
5. Check motor wiring:
• Any disconnect between drive and motor should be interlocked
to drive safety interlock circuit to avoid unwanted drive trips.
• No power factor correction capacitors can be connected between
drive and motor.
• Two speed motors must be wired permanently for full speed.
• Y-start, H-run motors must be wired permanently for run.
Installation Checks
1. Input fusing in power supply for all drives must be provided (see
Input Fuses section in this manual).
2. Environmental concerns — for standard NEMA 1 drive:
• Clean air supply
• Dry air (max 95% relative humidity , non-condensing)
o
• 14
F to 104oF ambient temperature operating range, or as rated
• 3,300 foot maximum elevation with no derating
3. Mounting
• Vertical
• Drives with heat sink fins exposed in back of unit must be
mounted against a solid surface (see Clearances section in this
manual).
• Keep any construction dirt out of drive.
4. Wiring
• Wire drive in accordance with instructions and diagrams received
with drive.
• Separate conduits must be provided to drive for input power,
output power, and control wiring.
• Note that safety interlock and remote run/stop circuitry is 115 V AC
for drives with bypasses.
• Use knockouts or conduit entry plates. Avoid metal shavings in cabinet.
• Protect signal wires from noise.
• Ground each drive individually.
• Double check input and output power wiring for correct location.
Setting Up Drive for Motor Start
Enter motor nameplate data into drive through Quick Menu.
1. Parameter 101:
• If one motor is connected to drive, set to AEO FUNCTION.
• If more than one motor connected to drive, set to MULTIPLE
MOTORS. (Parameter 108, MUL TIPLE MOTOR ST ARTING
VOLT AGE should be adjusted later to provide reliable starts and
minimum starting current.)
2. Parameter 102, MOTOR POWER (in kW) (See conversion table in
parameter 102, Motor Power, in this manual.)
3. Parameter 103, MOTOR VOLT AGE
4. Parameter 104, MOTOR FREQUENCY
5. Parameter 105, MOTOR CURRENT
6. Parameter 106, MOTOR SPEED
7. Parameter 107, (optional) select AUTOMATIC MOTOR ADAPT ATION and run AMA in accordance with procedure in parameter
107, Automatic Motor Adaptation, in this manual.
8.Press HAND STAR T key to initiate operation in local control.
Operational Tests — HAND
1. Check motor rotation from drive. If incorrect, disconnect input
power from drive and reverse two leads between drive and motor.
2. If a bypass is provided, check motor rotation in bypass mode. If
incorrect, disconnect input power from drive and reverse two input
power leads.
3. Accelerate motor quickly to full speed and verify operation.
4. Decelerate motor quickly to stop and verify operation.
5. Operate motor over entire speed range while closely checking for
resonance.
Operational Tests — AUTO
1. Ensure that drive follows run/stop and safety interlock commands
from system.
2. Ensure drive follows speed reference, or feedback, from system.
Final Adjustments
1. Use parameters 216 through 220 to reject any resonant points.
2. Lock out keypad functions, as required.
General Troubleshooting
1. Display Messages:
• AUTO ST ART—Drive has tripped off and is in process of
automatically restarting.
• TRIP—Drive has tripped off. Press RESET to start.
• TRIP LOCKED—Drive has tripped off. Remove and apply
power before restarting with RESET .
2. Refer to Warnings and Alarms section in this manual.
3. Check tightness of all connections and wires for proper location.
4. Measure input signals.
5. Check drive input and output for balanced voltage and current.
28
Programming
Using the Extend Menu key, it is possible to access to all
the parameters for the drive.
Operation and Display
Parameters 000 through 017
This parameter group deals with the display, control keys and other
general functions.
Description of Parameters
Parameters are grouped by function. The groups are:
Operation and DisplayParameters 001 through 017
Load and MotorParameters 100 through 117
References and LimitsParameters 200 through 228
Input and OutputsParameters 300 through 328
Appli cat ion Func tio nsParameters 400 through 427
Serial CommunicationParameters 500 through 566
Service FunctionsParameters 600 through 631
Relay Card FunctionsParameters 700 through 711
The numbers shown in the square brackets ([ ]) after the parameter
values are used in serial communications to choose the parameter
value from the list. They are not shown on the local control panel when
programming the drive locally.
Setup Configuration
The drive has four setups that can be programmed independently. The
active setup can be selected in parameter 002, Active Setup. The
active setup number is shown on the right of line two in the display
under the word “Setup.”
It is also possible to set the drive to Multi-Setup to allow switching
setups through digital inputs or serial communication.
More than one setup can be used. An example would be a changing
setups for day/night or summer/winter operation.
Parameter 003, Copying of Setups, enables copying from one setup to
another.
By means of parameter 004, LCP Copy, any setup can be transferred
from one drive to another using the removable local control panel
(LCP). First, upload all parameter values to the control panel installed
in the drive. Insert this panel into the next drive. Download all
parameter values from the control unit to the second drive. Repeat this
procedure to program additional drives.
001 Language(Language)
Value:
✭ English (ENGLISH)[0]
German (DEUTSCH)[1]
French (FRANCAIS)[2]
Danish (DANSK)[3]
Spanish (ESP A¥OL)[4]
Italian (ITALIANO)[5]
Swedish (SVENSKA)[6]
Dutch (NEDERLANDS)[7]
Portuguese (PORTUGUESA)[8]
Function:
This parameter determines the language to be used on the display .
This parameter defines the setup number that controls the drive.
All parameters can be programmed in four individual parameter setups,
Setup 1, Setup 2, Setup 3 and Setup 4.
In addition, a pre-programmed read-only setup, called the Factory
Setup, exists.
Description of choice:
Factory Setup contains the parameter values preset at the factory. This
setup can be used as a data source if the other setups are to be
returned to a known state.
Setups 1 through 4 are four individual setups that can be selected as
required.
✭ Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
Multi-Setup is used if remote switching between different setups is
required. T erminals 16, 17, 29, 32, 33 and the serial communication
port can be used for switching between setups.
29
Connection Examples:
Setup Change
Selection of setup using terminals 32 and 33.
See the descriptions of parameters 300 through 307.
Parameter 306 = Selection of Setup, lsb
Parameter 307 = Selection of Setup, msb
Parameter 002 = Multi Setup
004LCP Copy(LCP COPY)
Value:
✭ No copying (NO COPY)[0]
Upload all parameters
(UPLOAD ALL PARAMET.)[1]
Download all parameters
(DOWNLOAD ALL PARAM.)[2]
Download power-independent parameters
(DOWNLOAD SIZE INDEP .)[3]
Function:
Parameter 004, LCP Copy, is used to copy all parameter setups to or
from the Local Control Panel (LCP). This can be used to store a
backup copy of all parameters in the LCP or to copy all setups from
one drive to another.
Description of choice:
Select Upload all parameters if all parameter values are to be copied
from the drive to the LCP .
Select Download all parameters if all parameter values are to be
copied from the LCP to the drive on which the control panel has been
mounted.
003Copying of Setups(Setup Copy)
Value:
✭ No copying (NO COPY)[0]
Copy active Setup to Setup 1
(COPY TO SETUP 1)[1]
Copy active Setup to Setup 2
(COPY TO SETUP 2)[2]
Copy active Setup to Setup 3
(COPY TO SETUP 3)[3]
Copy active Setup to Setup 4
(COPY TO SETUP 4)[4]
Copy active Setup to all (COPY TO ALL)[5]
Function:
A copy is made from the active setup selected in parameter 002, Active
Setup, to the setup or setups selected in parameter 003, Copying of
Setups.
NOTE
Copying is only possible when drive is stopped.
Description of choice:
The copying starts when the required copying function has been
selected and the OK key has been pressed.
Select Download power-independent parameters if only the powerindependent parameters are to be downloaded. This allows the
parameters from one drive to be easily copied to another drive of a
different size.
NOTE
Copying is only possible when drive is stopped.
Setup of User-Defined Readout
Parameter 005, Maximum Value of User-Defined Readout, and
Parameter 006, Unit for User-Defined Readout, allow users to design
their own readout which can be seen if the User-Defined Readout has
been selected as one of the displayed meters. The range is set in
parameter 005, Maximum Value of User-Defined Readout and the unit
is determined in parameter 006, Unit for User-Defined Readout. The
choice of unit determines whether the relationship between the output
frequency and the readout is a linear, square or cubed. Units
representing rates (RPM, CFM, GPM, etc.) are linear. Units representing pressure (PSI, in. wg., etc.) are square. Units representing power
(HP , kW , etc.) are cubed.
The display indicates when copying is in progress.
✭ Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
30
Loading...
+ 88 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.