Danfoss VLT 6002-6011, VLT 6006-6032, VLT 6002-6005, VLT 6042-6062, VLT 6075-6125 Installation, Operation And Maintenance Manual

...
Installation, Operation and
Maintenance Manual
VLT® 6000 Series
Adjustable Frequency Drive
03/00 23-6108-00 Revision G
1
DANGER
!
Rotating shafts and electrical equipment can be hazardous. Therefore, it is strongly recommended that all electrical work conform to National Electrical Code (NEC) and all local regulations. Installation, start-up and maintenance should be performed only by qualified personnel.
Factory recommended procedures, included in this manual, should be followed. Always disconnect electrical power before working on the unit.
Although shaft couplings or belt drives are generally not furnished by the manufacturer, rotating shafts, couplings and belts must be protected with securely mounted metal guards that are of sufficient thickness to provide protection against flying particles such as keys, bolts and coupling parts. Even when the motor is stopped, it should be consid­ered “alive” as long as its controller is energized. Automatic circuits may start the motor at any time. Keep hands away from the output shaft until the motor has completely stopped and power is disconnected from the controller.
Motor control equipment and electronic controls are connected to hazardous line voltages. When servicing drives and electronic controls, there will be exposed components at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit to use only one hand when checking compo­nents. Always work with another person in case of an emergency. Disconnect power whenever possible to check controls or to perform maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electric control or rotating equipment.
Safety Guidelines
1. The drive must be disconnected from the AC line before any service work is done.
2. The “Stop/Off” key on the local control panel of the drive does not disconnect the equipment from the AC line and is not to be used as a safety switch.
3. Correct protective grounding of the equipment must be estab­lished. The user must be protected against supply voltage and the motor must be protected against overload in accordance with applicable national and local regulations.
4. Ground currents are higher than 3 mA.
Warnings Against Unintended Start
1. While the drive is connected to the AC line, the motor can be brought to a stop by means of external switch closures, serial bus commands or references. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stops are not sufficient.
2. During programming of parameters, the motor may start. Be certain that no one is in the area of the motor or driven equipment when changing parameters.
3. A motor that has been stopped may start unexpectedly if faults occur in the electronics of the drive, or if an overload, a fault in the supply AC line or a fault in the motor connection or other fault clears.
4. If the “Local/Hand” key is activated, the motor can only be brought to a stop by means of the “Stop/Off” key or an external safety interlock.
NOTE It is responsibility of user or person installing drive to provide proper grounding and branch circuit protection for incoming power and motor overload according to National Electrical Code (NEC) and local codes.
Touching electrical parts may be fatal – even after equipment has
been disconnected from AC line. To be sure that capacitors have
fully discharged, wait 14 minutes after power has been removed
before touching any internal component.
2
The Electronic Thermal Relay (ETR) in UL listed VLTs provides Class 20 motor overload protection in accordance with NEC in single motor applications, when parameter 117 is set for “ETR TRIP 1”, “ETR TRIP 2”, “ETR TRIP 3”, or “ETR TRIP 4”, and parameter 105 is set for rated motor (nameplate) current.
DANGER
!
Table of Contents
Safet y Gui deli nes .................................................................................................................................................................................................... 2
Warnings Against Unintended Start.......................................................................................................................................................................... 2
General ...............................................................................................................................................................................................................5
Clearances ............................................................................................................................................................................................. 5
Plenum Mounting..................................................................................................................................................................................... 5
Grounding Plate ...................................................................................................................................................................................... 5
Shielded Wires ........................................................................................................................................................................................ 5
Cross Reference – Model Number to VLT T ype......................................................................................................................................................6
Input Fuses............................................................................................................................................................................................................. 7
Locations of Conduit Entry , T erminal Blocks and Switches ....................................................................................................................................... 8
Location of Input Power and Output Power........................................................................................................................................................... 11
Power Connections............................................................................................................................................................................................... 14
Input Power Connection ........................................................................................................................................................................ 14
Motor Wiring Connection........................................................................................................................................................................ 14
Grounding............................................................................................................................................................................................. 14
Electrical Thermal Protection.................................................................................................................................................................. 14
T erminal Tightening Torque................................................................................................................................................................... 15
Auxiliary Control Panel Tightening T orques........................................................................................................................................... 15
Multiple Motors ...................................................................................................................................................................................... 16
External DC Bus Connection................................................................................................................................................................. 16
High Voltage Form C Relay...................................................................................................................................................................16
Control Connections.............................................................................................................................................................................................. 17
Electrical Installations, Control T erminals ................................................................................................................................................17
Typical Control Connections.................................................................................................................................................................. 18
Electrical Installation, Control Wiring ....................................................................................................................................................... 19
DIP Switches 1 through 4 ...................................................................................................................................................................... 19
Ground Leakage Current ...................................................................................................................................................................... 19
Galvanic Isolation .................................................................................................................................................................................. 20
Electrical Noise ......................................................................................................................................................................................20
Application Control Connection Examples.............................................................................................................................................................. 21
Control Panel........................................................................................................................................................................................................22
Keys for Parameter Changes ................................................................................................................................................................22
Indicator Lamps .....................................................................................................................................................................................23
Local Control......................................................................................................................................................................................... 23
Display Mode........................................................................................................................................................................................23
Display Mode I................................................................................................................. .....................................................................24
Display Mode II................................................................................................................ .....................................................................24
Display mode III .................................................................................................................................................................................... 25
Display Mode IV.................................................................................................................................................................................... 25
Navigation Between Display Modes ...................................................................................................................................................... 25
Quick Menu ..........................................................................................................................................................................................................26
T o Enter or Change Quick Menu Parameter Data ................................................................................................................................. 26
Example of Changing Parameter Data................................................................................................................................................... 26
Extended Menu..................................................................................................................................................................................... 27
Changing Data......................................................................................................................................................................................27
Step Change of Numeric Values............................................................................................................................................................27
Manual Initialization of Parameters ......................................................................................................................................................... 27
Uploading Parameters........................................................................................................................................................................... 27
3
VL T 6000 Start-up................................................................................................................................................................................................. 28
Pre-installation Checks........................................................................................................................................................................... 28
Installation Checks ................................................................................................................................................................................. 28
Setting Up Drive for Motor Start ............................................................................................................................................................. 28
Operational T ests – HAND..................................................................................................................................................................... 28
Operational T ests – AUTO..................................................................................................................................................................... 28
Final Adjustments................................................................................................................................................................................... 28
General Troubleshooting.......................................................................................................................................................................28
Programming ........................................................................................................................................................................................................ 29
Description of Parameters...................................................................................................................................................................... 29
Setup Configuration ............................................................................................................................................................................... 29
Operation and Display – Parameters 000 through 017...................................................................................................................................29 - 34
Connection Examples............................................................................................................................................................................ 30
Load and Motor – Parameters 100 through 117............................................................................................................................................. 34 - 39
DC Braking ........................................................................................................................................................................................... 38
Motor Thermal Protection....................................................................................................................................................................... 39
References and Limits – Parameters 200 through 228.................................................................................................................................... 40 - 47
Reference Handling .............................................................................................................................................................................. 41
Reference Type .................................................................................................................................................................................... 44
Warning Functions................................................................................................................................................................................. 46
Input and Outputs – Parameters 300 through 328 ..........................................................................................................................................48 - 58
Analog Inputs ........................................................................................................................................................................................ 51
Analog/Digital Outputs............................................................................................................................................................................ 54
Relay Outputs........................................................................................................................................................................................ 57
Application Functions – Parameters 400 through 427 ..................................................................................................................................... 59 - 69
Sleep Mode .......................................................................................................................................................................................... 59
Feedback Signals in Open Loop............................................................................................................................................................ 63
PID for Process Regulation ...................................................................................................................................................................................64
Feedback .............................................................................................................................................................................................. 64
Reference (Set Point) ............................................................................................................................................................................ 64
Inverse Regulation ................................................................................................................................................................................ 64
Anti-Windup...........................................................................................................................................................................................64
Start-up Conditions ................................................................................................................................................................................ 64
Differentiator Gain Limit .......................................................................................................................................................................... 65
Lowpass Filter.......................................................................................................................................................................................65
Optimization of the Process Regulator .................................................................................................................................................... 65
PID Overview....................................................................................................................................................................................................... 65
Feedback Handling ............................................................................................................................................................................... 65
Serial Communication for FC Protocol ...................................................................................................................................................................70
Protocols ............................................................................................................................................................................................... 70
Packet Communication ...........................................................................................................................................................................70
Serial Communication – Parameters 500 through 566 .................................................................................................................................... 80 - 85
Warning Word, Extended Status Word and Alarm Word......................................................................................................................... 86
Service Functions – Parameters 600 through 631.......................................................................................................................................... 88 - 92
Relay Card Functions – Parameters 700 through 711........................................................................................................................................... 93
Electrical Installation of the Relay Card ..................................................................................................................................................93
Status Messages ...................................................................................................................................................................................................94
Warnings and Alarms ............................................................................................................................................................................................ 96
Calculation of Resulting Reference ...................................................................................................................................................................... 101
Factory Settings .........................................................................................................................................................................................102 - 107
Index ........................................................................................................................................................................................................ 108 - 115
SOFTWARE VERSION NOTICE: These Operating Instructions are used for all VLT 6000 Series Drives with software version 2.X and all prior versions. The software version number
4
can be determined from parameter 624,
Software Version
.
General
(
)
The specific installation instructions may vary depending upon the model of VLT 6000 Series being installed. When this occurs, the model can be identified by a “VLT T ype 6XXX” number . This number can be found on the red nameplate on the outside of the left side of the drive enclosure, or the outside of the right side of a drive with an auxiliary enclosure. A cross reference from the VLT T ype to the Danfoss Graham model number can be found on the next page.
The drive must always be installed vertically. To ensure that no injury or damage occurs, the drive must always be firmly attached to the wall or the floor before further installation work is carried out.
Clearances
The drive is cooled by means of air circula­tion. For proper cooling, the minimum distances above and below the unit must be maintained as shown in the table below. For units with an auxiliary enclosure mounted with the drive on a back panel, the required clearances are measured from the top and bottom of the drive, not the back panel.
Drive Type
VLT 6002-6005, 200-240V VLT 6002-6011, 380-460V VLT 6006-6032, 200-240V VLT 6016-6062, 380-460V VLT 6042-6062, 200-240V VLT 6075-6125, 380-460V VLT 6150-6275, 380-460V VLT 6350-6550, 380-460V 16" (400mm) floor mount
Top
Clearance
4" (100mm) 4" (100mm) No
8" (200mm) 8" (200mm) Yes
9" (225mm) 9" (225mm) Yes
300mm) 12" (300mm
12"
Bottom
Clearance
All drives can be mounted with no side clearance. VLT 6350-6550 drives require 25 inches (605 mm) front space for access.
All drives except VLT 6002-6005, 200 to 240 V and VLT 6002-6011, 380 to 460 V must be mounted directly to the wall with no spacers. This is to ensure that air flow is in contact with the heatsink all the way from the bottom of the drive. If this is not possible, a metal plate at least as large as the back of the drive must be firmly mounted to the back of the drive. See the Cross Reference T able on the next page to convert model numbers to drive type.
X
X
Must be mounted
flush to wall
Yes Yes
Sufficient space must be left in front of the drive to provide for door swing on units with a hinged door. In addition, sufficient room must be available for installation and service access. On units with an auxiliary enclosure, the auxiliary enclosure door will have a greater door swing than the drive. See the dimensional drawings of the auxiliary enclosure which are included with the drive.
Plenum Mounting
The drive is UL rated for plenum mounting. If the drive is to be mounted in the plenum, allow sufficient access for servicing. All normal clearance, temperature and humidity limitations apply.
Grounding Plate
VLT Type 6002-6005, 200 to 240 V and VLT 6002-6001, 380 to 460 V drives with a NEMA 1 enclosure have a plastic bottom cover with provision for conduit entry . T o meet UL requirements, the metal grounding plate must be in place above the plastic bottom cover. It must be grounded to the chassis, and the conduit grounded to it. If the grounding plate is not factory installed, it must be installed in the drives that have a plastic bottom panel to ensure proper grounding of the conduit to the enclosure. Connect the ground wire from the grounding plate to the ground tab marked with the ground symbol.
This tab is located near the AC line terminal strip. Mount the bottom cover on the control unit.
Shielded Wires
Wires to control signals should be shielded to reduce radio frequency noise interference.
When RFI is a concern, shielded cable should be used between the drive and the motor.
If unshielded control wires are used, control inputs are subject to signal disturbances. Such disturbances may affect drive operation. Extreme noise levels may disturb the microprocessor of the control card.
The shield of the control wires must be grounded at the cable clamp at the bottom of the drive, but the shield must continue with the cable all the way up to the control card. The shield is not to be connected to any of the terminals on the control card. For safety reasons, the insulation around the shield should only be removed where it is connected to the cable clamp. The insulation should be left on the shield between the clamp and the terminals.
All drives except VL T 6002-6005, 200 to 240 V
and VL T 6002-6011, 380 to 460 V must be
mounted directly to a solid wall with no spacers
between the drive and the wall.
Generally speaking, all conductors coming from a shielded control cable must be as short as possible. Long conductor ends attract noise. The shield must be connected to the chassis by means of the cable clamp. Long pigtails on the shield reduce the effectiveness of the shield.
5
Cross Reference Model Number to VLT Type
208 V Input
Model Number VLT Type Max. Nominal
Output HP
VLT6000C4.6 6002 1 4.6 VLT6000C6.6 6002 1½ 6.6 VLT6000C7.5 6003 2 7.5
VLT6000C11
6004
310.6 VLT6000C17 6006 5 16.7 VLT6000C24 6008 7½ 24.2 VLT6000C31 6011 10 30.8 VLT6000C46 6016 15 46.2 VLT6000C59 6022 20 59.4 VLT6000C75 6027 25 74.8 VLT6000C88 6032 30 88
VLT6000C114 6042 40 114 VLT6000C143 6052 50 143 VLT6000C169 6062 60 169
460 V Input
Model Number VLT Type Max. Nominal
Output HP
VLT6000H2.1 6002 1 2.1 VLT6000H3.0 6002 1½ 3.0 VLT6000H3.4 6003 2 3.4 VLT6000H4.8 6004 3 4.8 VLT6000H8.2 6006 5 8.2
VLT6000H11 6008 7½ 11.0 VLT6000H14 6011 10 14 VLT6000H21 6016 15 21 VLT6000H27 6022 20 27 VLT6000H34 6027 25 34 VLT6000H40 6032 30 40 VLT6000H52 6042 40 52 VLT6000H65 6052 50 65 VLT6000H77 6062 60 77
VLT6000H106 6075 75 106 VLT6000H130 6100 100 130 VLT6000H160 6125 125 160 VLT6000H190 6150 150 190 VLT6000H240 6175 200 240 VLT6000H302 6225 250 302 VLT6000H361 6275 300 361 VLT6000H443 6350 350 443 VLT6000H540 6400 450 540 VLT6000H590 6500 500 590 VLT6000H678 6550 600 678
Max. Drive
Output Current
Max. Drive
Output Current
230 V Input
Model Number VLT Type Max. Nominal
Output HP
VLT6000E4.2 6002 1 4.2 VLT6000E6.6 6002 6.6 VLT6000E7.5 6003 2 7.5
VLT6000R11 6004 3 10.6 VLT6000E17 6006 5 16.7 VLT6000E24 6008 24.2 VLT6000E31 6011 10 30.8 VLT6000E46 6016 15 46.2 VLT6000E59 6022 20 59.4 VLT6000E75 6027 25 74.8
VLT6000E88 6032 30 88 VLT6000E104 6042 40 104 VLT6000E130 6052 50 130 VLT6000E154 6062 60 154
380 V Input
Model Number VLT Type Max. Nominal
Output kW
VLT6000F3.0 6002 1.1 3.0 VLT6000F4.1 6003 1.5 4.1 VLT6000F5.6 6004 2.2 5.6 VLT6000F7.2 6005 3 7.2
VLT6000F10 6006 4 10
VLT6000F13 6008 5.5 13
VLT6000F16 6011 7.5 16
VLT6000F24 6016 11 24
VLT6000F32 6022 15 32
VLT6000F38 6027 18.5 37.5
VLT6000F44 6032 22 44
VLT6000F61 6042 30 61
VLT6000F73 6052 37 73
VLT6000F90 6062 45 90
VLT6000F106 6075 55 106 VLT6000F147 6100 75 147 VLT6000F177 6125 90 177 VLT6000F212 6150 110 212 VLT6000F260 6175 132 260 VLT6000F315 6225 160 315 VLT6000F368 6275 200 368
575 V Input
Model Number VLT Type Max. Nominal
Output HP
VLT6000J2.7 6016 2 2.7 VLT6000J3.9 6016 3 3.9 VLT6000J6.1 6016 5 6.1 VLT6000J9.0 6016 7½ 9
VLT6000J11 6016 10 11
VLT6000J17 6016 15 17
VLT6000J22 6022 20 22
VLT6000J27 6027 25 27
VLT6000J32 6032 30 32
VLT6000J41 6042 40 41
VLT6000J52 6052 50 52
VLT6000J62 6062 60 62
Max. Drive
Output Current
Max. Drive
Output Current
Max. Drive
Output Current
6
Input Fuses
All drives must have input fuses installed in the power supply to the drive. These fuses may be specified as an option to the drive and supplied by Danfoss Graham. If specified, they will be installed by Danfoss Graham in an enclosure external to the drive which may include other optional features. If not supplied by Danfoss Graham, they must be supplied by the installer of the drive at the time of installation.
The required type of fuse for each drive size is shown in the table below. The fuse rating shown is both the maximum and the recom­mended fuse rating.
The drives are suitable for use on circuits capable of delivering not more than 100,000 RMS symmetrical amps, 500 volts maximum (600 volts maximum for 575 volt drives), when used with the recommended fuses.
208 Volt Input
Maximum Fuse
Model Number VLT Type
VLT6000C4.6 6002 10 KTN-R or JJN VLT6000C6.6 6003 15 KTN-R or JJN VLT6000C7.5 6003 20 KTN-R or JJN
VLT6000C11 6004 25 KTN-R or JJN VLT6000C17 6006 50 KTN-R or JJN VLT6000C24 6008 50 KTN-R or JJN VLT6000C31 6011 50 KTN-R or JJN VLT6000C46 6016 60 KTN-R or JJN VLT6000C59 6022 80 KTN-R or JJN VLT6000C75 6027 125 K TN-R or JJN
VLT6000C88 6032 125 K TN-R or JJN VLT6000C114 6042 150 FWX or FWH VLT6000C143 6052 200 FWX or FWH VLT6000C169 6062 250 FWX or FWH
Rating Bussman Type
460 Volt Input
Maximum Fuse
Model Number VLT Type
VLT6000H2.1 6002 6 KTS -R or JJS VLT6000H3.0 6002 6 KTS -R or JJS VLT6000H3.4 6003 10 KTS-R or JJS VLT6000H4.8 6004 10 KTS-R or JJS VLT6000H8.2 6006 20 KTS-R or JJS
VLT6000H11 6008 25 KTS-R or JJS
VLT6000H14 6011 30 KTS-R or JJS
VLT6000H21 6016 40 KTS-R or JJS
VLT6000H27 6022 40 KTS-R or JJS
VLT6000H34 6027 50 KTS-R or JJS
VLT6000H40 6032 60 KTS-R or JJS
VLT6000H52 6042 80 KTS-R or JJS
VLT6000H65 6052 100 KTS-R or JJS
VLT6000H77 6062 125 KTS-R or JJS VLT6000H106 6075 150 FWH VLT6000H130 6100 200 FWH VLT6000H160 6125 250 FWH VLT6000H190 6150 300 FWH VLT6000H240 6175 350 FWH VLT6000H302 6225 400 FWH VLT6000H361 6275 500 FWH VLT6000H443 6350 600 FWH VLT6000H540 6400 700 FWH VLT6000H590 6500 800 FWH VLT6000H678 6550 800 FWH
Rati ng Bussma n Type
575 Volt Input
Model Numbe r VLT Type
VLT6000J2.7 6016 6 KTS-R or similar VLT6000J3.9 6016 6 KTS-R or similar VLT6000J6.1 6016 10 KTS-R or similar
VLT6000J9 6016 20 KTS-R or similar VLT6000J11 6016 25 KTS-R or sim ilar VLT6000J17 6016 40 KTS-R or sim ilar VLT6000J22 6022 40 KTS-R or sim ilar VLT6000J27 6027 50 KTS-R or sim ilar VLT6000J32 6032 60 KTS-R or sim ilar VLT6000J41 6042 80 KTS-R or sim ilar VLT6000J52 6052 100 KTS-R or similar VLT6000J62 6062 125 KTS-R or similar
Maximum Fuse
Rating Bussman Type
All fuse ratings are in amps
All fuse ratings are in amps
7
Locations of Conduit Entry, Terminal Blocks and Switches
NEMA 1
VLT 6002-6032, 200 to 240 V VLT 6002-6062, 380 to 575 V
VLT 6042-6062, 200 to 240 V, VLT 6075-6125, 380 to 460 V VLT 6150-6275, 380 to 460 V
8
Locations of Conduit Entry, Terminal Blocks and Switches (continued)
NEMA 12
VLT 6002-6005, 200 to 240 V, VLT 6002-6011, 380 to 460 V VLT 6006-6032, 200 to 240 V ; VLT 6016-6032, 380 to 460 V
VLT 6042-6062, 200 to 240 V ; VLT 6075-6125, 380 to 460 V VLT 6150-6275, 380 to 460 V
9
Locations of Conduit Entry, Terminal Blocks and Switches (continued)
NEMA 1 and NEMA 12
10
VLT 6350-6550, 380 to 460 V
Location of Input Power (Mains) and Output
WARNING
!
Power (Motor Terminal Blocks)
Connect input power to the terminals identified as L1, L2 and L3. Connect the motor leads to the terminals identified as U, V and W.
Connecting input power to motor terminals will result in drive failure when the power is ap­plied.
NEMA 1 and NEMA 12 VLT 6002-6005, 200-240 V VLT 6002-6011, 380-460 V
NEMA 1 VLT 6006-6032, 200-240 V VLT 6016-6062, 380-575 V
NEMA 1 VLT 6042-6062, 200-240 V VLT 6075-6125, 380-460 V
NEMA 1
VLT 6150-6275, 380-460 V
11
Location of Input Power (Mains) and Output Power (Motor Terminal Blocks), continued
Connect input power to the terminals identified as L1, L2 and L3.
NEMA 12 VLT 6006-6032, 200-240 V VLT 6016-6062, 380-460 V
NEMA 12 VLT 6042-6062, 200-240 V VLT 6075-6125, 380-460 V
NEMA 12
VLT 6150-6275, 380-460 V
12
Location of Input Power (Mains) and Output Power (Motor Terminal Blocks), continued
Connect input power to the terminals identified as L1, L2 and L3.
NEMA 1 and NEMA 12, VLT 6350-6550, 380-460 V
without disconnector and mains fuses
NEMA 1 and NEMA 12, VLT 6350-6550, 380-460 V
with disconnector and mains fuses
13
Power Connections
o
Make all power connections with 75
C rated copper wiring.
Conduit entry must be from the bottom on all drives. Conduit entries are provided on smaller drives. For drives with auxiliary enclosures, refer to the dimensional drawings provided for conduit entry locations.
T o meet UL requirements, install the metal grounding plate in all drives that have a plastic bottom. Install the grounding plate just above the plastic bottom. Ground the metal plate to the chassis and ground the conduit to the metal plate.
The conduit entries provide strain relief for the wires in drives mounted in NEMA 1 or NEMA 12 enclosures. With chassis mounted drives, the power and control wires must have strain relief supplied by the installer.
O NOT rely on the terminal blocks to provide strain relief.
D
Input Power Connection
For drives with no auxiliary enclosure, connect input power to drive terminals L1, L2, and L3, (terminal numbers 91, 92, and 93). If an auxiliary enclosure is provided, input power connections are made in the auxiliary enclosure. Refer to the connection diagrams shipped with the drive.
Size wiring to the input current of the drive as shown in the tables below. Maximum AWG wire size is also provided.
WARNING
!
Connecting input power to motor terminals will result in drive failure when power is applied.
Motor Wiring Connection
For drives with no auxiliary enclosure, connect the motor to drive terminals U, V , and W (terminal numbers 96, 97, and 98). T erminal 99 is earth ground. If an auxiliary enclosure is provided, refer to the connection diagrams shipped with the drive. Ground the shield on the motor wire, if used, at both the drive and the motor.
DANGER
!
For operator safety, it is important to ground drive properly.
Grounding
Ground the drive properly. Use a ground wire at least 7 AWG (10mm2). Connect the ground wire directly to a reliable earth ground. Do not use the conduit connecting to the drive as a replacement for a ground wire. Do not ground one drive to another in a “daisy chain” fashion.
Electronic Thermal Protection
The electronic thermal relay is UL approved for single motor thermal protection as long as the following is complied with:
CAUTION
!
Enclosures for larger drives and auxiliary en­closures are made of metal. To avoid getting metal chips into electronics, do not drill any holes after unit has been installed in a vertical position.
575 VAC Input Current/Wire Gage
208 VAC Input Current/Wire Gage
Drive Input
Current
5.0 10
6.0 10
7.0 10
10.0 10
16.0 10
23.0 6
30.0 6
46.0 6
59.2 2
74.8 2
88.0 0
101.3 1/0
126.6
149.9 4/0 C169
Maximum
AWG
3/0
Model
C4.6 C6.6 C7.5
C11 C17 C24 C31 C46 C59 C75
C88 C114 C143
All current ratings are in amps.
1. Parameter 1 17, Thermal Protection, is set to ETR TRIP .
2. Parameter 105, Motor Current, is set for the full-load nameplate
Drive Input
Current
2.5 6 J2.7
3.0 6 J3.9
6.0 6 J6.1
9.0 6 J9.0
10.0 6 J11
16.7 6 J17
21.6 6 J22
26.6 6 J27
31.5 6 J32
40.3 2 J41
51.2 2 J52
61.0 0 J62
Maximum
AWG
motor current.
Model
460 VAC Input Current/Wire Gage
Drive Input
Current
2.5 10 H2.1
2.5 10 H3.0
3.4 10 H3.4
4.8 10 H4.8
8.3 10 H8.2
10.6 10 H11
27.6 6 H27
103 1/0 H106 145 2/0 H130 174 3/0 H160 206 2x1/0 H190 256 2x1/0 H240 317 2x3/0 H302 366 2x4/0 H361 443 3x1/0 H443 540 3x3/0 H540 590 3x3/0 H590 678 3x4/0 H678
Maximum
AWG
14 10 H14 21 6 H21
34 6 H34 41 6 H40 53 2 H52 64 2 H65 77 2 H77
Model
14
y
y
Terminal Tightening Torque
Tighten terminals connecting the drive input power, output to the motor(s) and ground to the values shown in the tables below. Drives with 200 to 240 volts of 88 amps and less, and drives with 380 to 575 volts of 90 amps and less, have removable terminal blocks with screws. Larger drives have fixed bolts. (See the drive nameplate for maximum drive output current.)
200 to 240 VAC Terminal Tightening Torque
NOTE Tighten terminals of 575 volt drives of 32 amps and below to 17 in-lbs (1.8 Nm), and above 32 amps to 28 in-lbs (3.0 Nm).
380 to 460 VAC Terminal Tightening Torque
Max. Drive
Output Current
6.6 5 (0.6)
7.5 5 (0.6)
10.6 5 (0.6)
16.7 5 (0.6)
24.2 17 (1.8)
30.8 17 (1.8)
46.2 28 (3.0)
59.4 28 (3.0)
74.8 28 (3.0) 88 35 (4.0)
114 100 (11.3) 143 100 (11.3) 169 100 (11.3)
Torque
in-lbs (Nm )
Max. Drive
Output Current
All current ratings are in amps.
200 to 240 VAC Auxiliary Control Panel Tightening Torques
Max. Drive
Output Current
to 6.6 15 (1.7) 15 (1.7) 22 (2.5) 7 (0.8) 20 (2.3) 35 (4.0) 45 (5.1)
7.5 15 (1.7) 15 (1.7) 22 (2.5) 7 (0.8) 25 (2.8) 35 (4.0) 45 (5.1)
10.6 15 (1.7) 15 (1.7) 22 (2.5) 7 (0.8) 25 (2.8) 35 (4.0) 45 (5.1)
16.7 15 (1.7) 15 (1.7) 22 (2.5) 7 (0.8) 25 (2.8) 35 (4.0) 45 (5.1)
24.2 15 (1.7) 50 (5.7) 22 (2.5) 7 (0.8) 45 (5.1) 45 (5.1) 45 (5.1)
30.8 15 (1.7) 50 (5.7) 22 (2.5) 7 (0.8) 120 (13.6) 45 (5.1) 45 (5.1) 46 75 (8.5) 50 (5.7) 44 (5.0) 18 (2.0) 120 (13.6) 120 (13.6) 45 (5.1)
61.2 75 (8.5) 275 (31.1) 44 (5.0) 18 (2.0) 120 (13.6) 275 (31.1) 50 (5.6)
74.8 120 (13.6) 275 (31.1) 44 (5.0) 18 (2.0) 120 (13.6) 275 (31.1) 50 (5.6) 88 120 (13.6) 275 (31.1) 44 (5.0) 70 (8.0) 120 (13.6) 275 (31.1) 50 (5.6)
115 120 (13.6) 275 (31.1) 44 (5.0) 375 (42.4) 275 (31.1) 150 (16.9) 50 (5.6) 143 250 (28.3) 275 (31.1) 50 (5.6) 375 (42.4) 275 (31.1) 150 (16.9) 120 (13.6) 169 275 (31.4) 275 (31.1) 50 (5.6) 375 (42.4) 275 (31.1) 150 (16.9) 150 (16.9)
Overload
Rela
Power Terminal
Blocks
Circ uit
Breaker
Disconnect or
Transfer Switch
Torque
in-lbs (Nm)
to 10 5 (0.6) 147 100 (11.3)
16 5 (0.6) 177 100 (11.3) 24 17 (1.8) 212 100 (11.3) 32 17 (1.8) 260 100 (11.3)
37.5 17 (1.8) 315 100 (11.3) 44 28 (3.0) 368 100 (11.3) 61 28 (3.0) 487 372 (42.0) 73 28 (3.0) 594 372 (42.0) 90 28 (3.0) 649 372 (42.0)
106 100 (11.3) 746 372 (42.0)
Main or pass Fuse
B
Block
Drive Fuse
Block
Max. Drive
Output Current
Ground
Term inal
Torque
in-lbs (Nm)
380 to 575 VAC Auxiliary Control Panel Tightening Torques
Max. Drive
Output Current
10 15 (1.7) 15 (1.7) 22 (2.5) 7 (0.8) 20 (2.3) 25 (2.8) 45 (5.1) 16 15 (1.7) 15 (1.7) 22 (2.5) 7 (0.8) 25 (2.8) 25 (2.8) 45 (5.1) 24 75 (8.5) 15 (1.7) 22 (2.5) 7 (0.8) 25 (2.8) 45 (5.1) 45 (5.1) 32 75 (8.5) 35 (4.0) 22 (2.5) 7 (0.8) 45 (5.1) 45 (5.1) 45 (5.1)
37.5 75 (8.5) 35 (4.0) 22 (2.5) 18 (2.0) 45 (5.1) 45 (5.1) 45 (5.1) 44 75 (8.5) 50 (5.6) 44 (5.0) 18 (2.0) 45 (5.1) 120 (13.6) 45 (5.1) 61 75 (8.5) 110 (12.5) 44 (5.0) 18 (2.0) 120 (13.6) 120 (13.6) 50 (5.6) 73 75 (8.5) 110 (12.5) 44 (5.0) 55 (6.2) 120 (13.6) 275 (31.1) 50 (5.6) 90 75 (8.5) 110 (12.5) 44 (5.0) 70 (8.0) 120 (13.6) 275 (31.1) 50 (5.6)
106 120 (13.6) 110 (12.5) 50 (5.6) 375 (42.4) 275 (31.1) 150 (16.9) 50 (5.6) 147 250 (28.3) 275 (31.1) 50 (5.6) 375 (42.4) 275 (31.1) 150 (16.9) 120 (13.6) 177 275 (31.1) 275 (31.1) 50 (5.6) 375 (42.4) 275 (31.1) 150 (16.9) 150 (16.9) 212 275 (31.1) 275 (31.1) 50 (5.6) 375 (42.4) 450 (50.8) 275 (31. 1) 150 (16.9) 260 275 (31.1) 275 (31.1) 375 (42.4) 500 (56.5) 450 (50.8) 275 (31.1) 150 (16.9) 315 375 (42.4) 375 (42.4) 375 (42.4) 500 (56.5) 450 (50.8) 275 (31.1) 150 (16.9) 368 375 (42.4) 375 (42.4) 375 (42.4) 375 (42.4) 375 (42.4) 275 (31.1) 150 (16.9)
All current ratings are in amps. All torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
Overload
Relay
Power Terminal
Blocks
Circuit
Breaker
Disc onnect or
Transfer Switch
Main or
Bypass Fuse
Block
Drive Fuse
Block
Ground
Terminal
15
Multiple Motors
The VLT 6000 can control several motors at once, all changing speed together. The sum of the nameplate currents of all the motors must not exceed the current rating of the drive.
WARNING
!
When multiple motors are used, VLT 6000 elec­tronic thermal relay cannot be used to provide individual motor protection. A separate motor over­load must be supplied for each motor.
If the multiple motors are of significantly different sizes, starting problems may occur. This is because the higher electrical resistance of smaller motors will require more start voltage than larger motors.
CAUTION
!
Automatic Motor Adaptation and Automatic Energy Optimization cannot be used for mul­tiple motor installations.
External DC Bus Connection
T erminals 88 and 89 access the DC bus of the drive. They can provide DC backup power for the drive or to connect to a 12-pulse input rectifier.
DANGER
!
Terminals 88 and 89 will be at approximately 150% of line voltage and remain at high volt­age for up to 14 minutes after power has been removed from the drive.
WARNING
!
Do not connect anything to terminals 88 and 89 without first consulting with Danfoss Graham.
High Voltage Form C Relay
The connections for the high-voltage relay are terminals 01, 02, 03. The high-voltage relay is programmed in parameter 323, Relay
Output 1.
1+3 normally closed, 1+2 normally open
Max. 240 VAC, 2 Amp Min. 24 VDC, 10 mA or
24 VAC, 100 mA Max. wire gage: 10 AWG (4 mm2) T erminal Torque: 5 in-lbs ( 0.5 - 0.6 Nm)
16
Electronic Control T erminals
Control Connections
All terminals for the low voltage control wires are located under the protective cover below the keypad. Remove the cover with a screwdriver or other pointed object as shown below.
The following is a description of the functions of the control terminals. Many of these terminals have multiple functions determined by parameter settings.
No. Function
01, 02, 03 Form C relay output. Maximum 240 V AC, 2 A.
Minimum 24 VDC, 10 mA or 24 VAC, 100 mA. (Location of Form C relay output varies with unit type. See connection diagram with unit for location.)
04, 05 30 VAC, 42.5 VDC, 1 A relay output can be used
for indicating status and warnings.
12, 13 Voltage supply to digital inputs and external
transducers. For the 24 VDC to be used for digital inputs, switch 4 on the control card must be closed, position “on.” The maximum output current is 200 mA.
16 - 33 Digital inputs. R = 2 kohm. <5 V = logical “0”,
>10 V = logical “1”. See parameters 300 through 307, Digital Inputs.
Electrical Installation, Control Terminals
T orque the control terminals to 5 in-lbs (0.5-0.6 N-m) The diagram below shows the location of the control terminals. The
programming section of the manual covers the programmable terminals in greater depth.
20 Common for digital inputs. 39 Common for analog and digital outputs. 42, 45 Analog and digital outputs for indicating frequency,
reference, current and torque. The analog signal is 0 to 20 mA, or 4 to 20 mA at a maximum of 500€Ω. The digital signal is 24 VDC at a minimum of 600 . See parameters 319-322, Analog/ digital Outputs.
50 10 VDC, 17 mA maximum analog supply voltage
to potentiometer and thermistor.
53, 54 0 to 10 VDC voltage input, R = 10 kΩ. 55 Common for analog inputs. This common is
isolated from the common of all other power supplies. If, for example, the drive’s 24 VDC power supply is used to power an external transducer which provides an analog input signal, terminal 55 must be wired to terminal 39.
60 0 to 20 mA or 4 to 20 mA, analog current input, R
= 188 . See parameters 314 through 316.
61 Shield for serial communication. 68, 69 RS-485 interface and serial communication. When
the drive is connected to an RS-485 serial communication bus, DIP switch settings on the control card may have to be reset. See Dip Switches 1 through 4 in this manual.
17
Typical Control Connections
Shown below are typical interfaces between the VLT 6000 and other components in an HVAC system. The terminal numbers and the functions of the terminals are identical on all VLT 6000s. An optional relay card, not shown, can provide four additional Form C output relays. The RS-485 connections allow direct communication through
Typical* VLT 6000 Wiring
the drive’s built-in serial communication protocols: Johnson Controls
®
Metasys
N2, Siemens System 600 FLN®, or VLT Software Dialog®. LonWorks® and Profibus® are available through option cards that fit into the relay output card location.
3 Phase
Power
Input
External
DC Bus
Connection
+10 V DC
0 - 10 V DC
Ref. Input*
0 - 10 V DC
Ref. Input*
4 - 20 mA
Ref. Input*
Reset*
Lockout*
Run/Stop*
Reverse*
Interlock*
Preset Speed*
91 (L1)
92 (L2)
93 (L3)
99 (PE)
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
60 (A IN)
12 (+24 V OUT)
13 (+24 V OUT)
16 (D IN)
17 (D IN)
18 (D IN)
19 (D IN)
20 (COM D IN)
27 (D IN)
29 (D IN)
SW4
Switch Mode
Power Supply
10 V DC
17 mA
+-
RS-485
Interface
+-
5 V
SW2 SW3
24 V DC
200 mA
(U) 96
(V) 97
(W) 98
(PE) 95
(AUX RELAY) 01
( AUX RELAY) 02
(AUX RELAY) 03
(RELAY) 04
(RELAY) 05
(COM A OUT) 39
(A OUT) 42
0 V
(A OUT) 45
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
Motor
Fault Indication* 240 V AC, 2 A
Run Indication* 30 V AC, 1 A
Output Current Indication* 4 - 20 mA
Output Speed Indication* 4 - 20 mA
+
RS-485
-
Setup Select*
Setup Select*
32 (D IN)
33 (D IN)
* The operation of all control inputs and outputs is programmable.
* Typical terminal functions are shown.
18
CAUTION
!
Incoming power, motor wiring and control wir­ing should be run in three separate conduits or raceways.
Electrical Installation, Control Wiring
Torque: 5 - 6 in-lbs Screw size: M3
Shield control wires, when necessary, to reduce interference from electrical noise by means of a cable clamp at both ends to the metal enclosure of the unit. Connect the shield to earth ground. Very long control wires may create 60 Hz interference. This problem can be solved by connecting one end of the shield to earth with a 0.1 µF capacitor, keeping the leads as short as possible. If this doesn’t solve the problem, disconnect the shield’s connection to earth ground at the end opposite to the drive.
DIP Switches 1 through 4
DIP switches are located on the control card. They are used for serial communication and the common of digital
inputs 16 through 33. The switch positions shown are the factory settings.
Switch 1 is not used. Switches 2 and 3 are used for terminating serial communication. On the
first and last drive in a multiple device network, or on the only drive of a single drive network, switches 2 and 3 must be ON (the default setting). On all other drives in a multiple device network, set switches 2 and 3 to OFF.
Switch 4 separates the common for the internal 24 VDC supply from the common of the external 24 VDC supply. Normally this switch is ON and the power supply is present at terminals 12 and 13. Set Switch 4 to the OFF position when an external 24 VDC supply is used.
Ground Leakage Current
It is normal for there to be some leakage current from the drive to earth ground. Paths of current leakage are shown on the drawing below. The leakage current will exceed 3.5 mA.
Paths of Normal Current Leakage to Ground
19
Galvanic Isolation
Galvanic isolation offers protection from electric shock. All control terminals of all VLT 6000 drives, and terminals 1 through 3 of the relay output, offer galvanic isolation as long as the RFI switch (if provided) is in the ON position. The galvanic isolation in the VLT 6000 conforms to the European standard EN 50178. (See figure below.)
The components that make up the galvanic isolation are:
1. Power supply, including signal isolation.
2. Gate drive for the IGBT s, the trigger transformers and opto­couplers.
3. The output current Hall effect transducers.
Galvanic Isolation
Electrical Noise
In general, electrical noise can be divided into two forms: wire-borne electromagnetic interference (EMI), and radiating radio frequency interference (RFI).
Using shielded motor cables reduces RFI but increases EMI. This is because shielded wires have a greater capacitance than unshielded wires. Unshielded input power connections to the drive generate more noise in the radio frequency range on the AC line. The shield reduces the radiated noise, but increases the low-frequency electromagnetic noise on the AC line. But, since the noise current is taken back to the unit through the shield, only a small electromagnetic field is generated from shielded motor wires.
With an EMI filter, the noise level on the AC line will be reduced to about the same level for shielded and unshielded wires alike.
Connect the motor wiring shield, if used, in the enclosure of the drive as well as at the motor. Use shield brackets to avoid “pigtail” shield ends. Even short “pigtails” increase the shield’s impedance at higher frequencies, which reduces the shield’s effect and increases the noise produced.
It is generally easier and less complicated to use unshielded motor wires than shielded cables. If unshielded wires are used, the RFI will be greater. But, since the strength of the radiated signal decreases with distance from the signal source, radiated noise is generally not a problem.
T o reduce the noise level from the total system (drive + installation) make the motor wiring as short as possible.
Provide separate conduits, or raceways, for power, motor and control wiring to provide the greatest immunity from distortion.
20
Application Control Connection Examples Two-wire Start/Stop
In Auto mode, closing the contact to terminal 18 will make the drive run. In any mode, opening the safety interlock contact to terminal 27 will stop the drive.
Set Parameter 302 to Start. Set Parameter 304 to External Fault.
Digital Speed Up/down
Closing the switch to terminal 32 will make the drive accelerate. Closing the switch to terminal 33 will make the drive decelerate.
Run Permissive
After receiving a run command, the drive will apply power to the damper motor and wait until it receives “permission” via the switch that is connected to terminal 16.
Set Parameter 300 to Run Permissive. Set Parameter 302 to Start. Set Parameter 304 to External Fault. Set Parameter 323 to Start Signal Applied.
Two Feedback Signals
The drive processes two independent feedback signals during closed loop operation. It can respond to the sum, difference, average, minimum or maximum of these signals.
Set Parameter 306 to Speed up. Set Parameter 307 to Speed down. Set Parameter 305 to Freeze reference.
Potentiometer Reference
A manual potentiometer is used as a input reference for the drive.
Set Parameter 308, T erminal 53, Analog Input V oltage, to Reference. Set Parameter 309, T erminal 53, Min. Scaling, to 0 V. Set Parameter 310, T erminal 53, Max. Scaling, to 10 V.
Set Parameter 308 to FEEDBACK. Set Parameter 311 to FEEDBACK Set Parameter 417 for the desired operation.
Transmitter Connection
The drive’s internal 24 VDC power supply is used to power an external 4 to 20 mA transducer.
Set Parameter 314, T erminal 60, Analog Input Curent, to correspond to the purpose of the 4 to 20 mA signal. Set Parameter 315, T erminal 60, Min. Scaling, to 4 mA Set Parameter 316, T erminal 60, Max. Scaling, to 20 mA.
Because the commons of the +24 VDC power supply and the input reference follower have separate circuit commons, it is necessary to connect a jumper between terminals 39 and 55.
21
Control Panel
The Local Control Panel (LCP), normally mounted on the front of the drive, is a complete interface for programming and operating the drive. The control panel can be removed from the drive and installed up to 10 feet (3 meters) from the drive by using a remote mounting kit.
The control panel has five functions:
1. Display
2. Keys for changing the display
3. Keys for changing programming parameters
4. Keys for controlling drive operation
5. Indicator lamps
The LCP uses a four-line, alpha-numeric, back-lit, LCD display. The display can show four operating data values and three operating condition values continuously. During programming, all the information required for quick, effective parameter setup of the drive will be displayed. As a supplement to the display, there are three indicator lamps for power on (ON), warning (WARNING) and alarm (ALARM).
All drive parameters can be changed from the control panel, unless this ability has been locked out by setting parameter 016, Lock for Data Change, to Locked, or by a digital input to terminals 16 through 33. See the related parameters for more information.
Keys for Parameter Changes
The keys are divided into groups by function. The keys between the display and indicator lamps are used for parameter setup, selecting the display indication during normal operation and controlling the drive speed during local speed control operation. The keys below the indicator lamps are used for Start/Stop control and selection of the operating site.
The DISPLAY MODE key is used to select the mode of the display or to return to the Display Mode from either the Quick Menu or the Extend Menu mode.
The QUICK MENU key gives access to the parameters available for the Quick Menu setup. Parameters in this menu are the 12 most important setup parameters for the drive.
The EXTEND MENU key gives access to all parameters. The CHANGE DATA key is used for changing the value
of a parameter selected either in the Extend Menu or the Quick Menu mode. The desired parameter is first selected. Then the CHANGE DAT A key is pressed to enable the editing of the parameter. The underline in the display will move under the parameter’s value to show that it is being edited.
The CANCEL key is used if a change of the selected parameter is not to be carried out.
The OK key is used for confirming a change of the parameter selected.
22
The + and - keys are used to scroll through parameters and to change the value of a chosen parameter. These keys are also used to change the local reference. In Display Mode, these keys are used to switch between readouts.
The L and M keys are used to select a parameter group and also to move the cursor to the desired digit when changing numerical values.
Indicator Lamps
At the bottom of the control panel is a red alarm LED, a yellow warning LED, and a green power on LED.
red yellow green
The OFF/STOP key is used for stopping the connected motor in either the Hand or Auto mode. Enable or Disable via parameter 013. If this stop function is activated, the second line in the LCD display will flash.
AUTO ST ART is used if the drive is to be started via the control terminals and/or serial communication. When a remote start signal is active, the drive will start if the AUTO ST ART key has been pressed.
DANGER
!
A start signal via digital inputs may cause drive to start at any time. Remove power to drive be­fore working on output wiring, motor or any driven equipment.
If certain threshold values are exceeded, the alarm and/or warning lamps will flash and text describing the alarm or warning condition will be displayed.
Local Control
Below the indicator lamps are keys which are used to determine the point of control. Each of these keys can be individually enabled or disabled using parameter 012 through 015. The Hand Start and Auto Start keys will also be disabled if any of the control terminals are programmed for either Remote Hand or Remote Auto.
The HAND STAR T key is used if the drive is to be started from the control panel. Pressing HAND STAR T will give a start command to the drive.
WARNING
!
If a minimum speed is set in parameter 201,
Output Frequency Low Limit
and ramp up to this frequency when HAND START is pressed. If drive is already running in Auto Mode when the HAND START key is pressed, it will switch to run in Hand Mode at same speed.
, motor will start
The RESET key is used for manually resetting the drive after a fault trip (alarm). In this case, the top line of the display will show TRIP (RESET). If the top line of the display shows TRIP (AUTO START), the drive will automatically restart. If the top line of the display shows TRIPLOCK (DISC. MAINS), input power to the drive must be removed before the trip can be reset.
Display Mode
Information is displayed on the LCD by selecting one of three program­mable display modes. Pressing the Display Mode key toggles among the displays. When in Mode II, pressing and holding down the Display Mode key accesses an additional mode used to identify the data units the display is showing. (See Navigation Between Display Modes.)
In normal operation, any four meters can be shown continuously on the first and second lines of the display. Parameters 008, 009 and 010 select the three readouts displayed on the top line. Parameter 007, Large Display Readout, selects the meter displayed on line 2. In Display Mode, the + and - keys choose any meter on the LCD.
A list on the next page gives the operating data that can be shown on the three meter readouts for line 1 and the large display (line 2).
The right side of line 2 shows the active setup number and an arrow indicateing the direction of motor rotation. Clockwise indicates forward and counterclockwise indicates reverse. The arrow body disappears if a stop command is given or if the output frequency falls below 0.01 Hz.
Warnings and alarms (fault trips) will also be displayed. For an alarm, “ALARM” and the alarm number is shown in line 2 with an explanation in line 3 or in lines 3 and 4. For a warning, “WARN.” and the warning number is shown in line 2 and an explanation in 3 and/or 4. Both alarms and warnings cause the display to flash.
The line 4 automatically displays the operating status of the drive.
23
The table below gives the operating data options for the first and second lines of the display .
Data Item: Unit:
Resulting reference, % % Resulting reference unit chosen in par. 415 Frequency Hz % of maximum output frequency % Motor current A Power kW Power HP Output energy kW h Hours run hours User defined readout unit chosen in par. 006 Setpoint 1 unit chosen in par. 415 Setpoint 2 unit chosen in par. 415 Feedback 1 unit chosen in par. 415 Feedback 2 unit chosen in par. 415 Feedback unit chosen in par. 415 Motor voltage V DC link voltage V Thermal load on motor % Thermal load on VLT % Input status, digital input binary code Input status, analog terminal 53 V Input status, analog terminal 54 V Input status, analog terminal 60 mA Pulse reference Hz External reference % Heat sink temperature
o
C
Line 4 is the status line and the information is automatically generated for display by the drive in response to its operation. It shows that the drive is in auto mode, with remote reference, and that the motor is running. Some possible displays of the status line are shown below.
80.0% 5.08A
2.15kW
40.0Hz
SETUP
1
AUTO REMOTE RUN
HAND
OFF
LOCAL
STOP
RAMPING JOGGING
. . . .
STAND BY
The left part of the status line indicates where the drive Run/Stop command is from, and whether it is on or off. AUTO means that Run/ Stop control is via the control terminals and/or serial interface; HAND indicates that the drive started locally by the Hand Start key . OFF means that the drive ignores all control commands and the motor will not run.
The center part of the status line indicates the reference source that is active. REMOTE means that the reference is from the control terminals. LOCAL indicates that the reference is determined by the + and - keys on the control panel.
Display Mode I:
Below is an example of Display Mode I, in which the drive is running in setup 1, in Auto mode, with remote reference, at an output frequency of 40 Hz.
FREQUENCY
SETUP
40.0Hz
1
AUTO REMOTE RUN
The text in line 1, FREQUENCY , describes the meter shown in line 2. Line 2 shows the current output frequency (40.0Hz), direction of rotation (reverse), and active setup (1).
The right part of the status line indicates the drive’s operational status.
Display Mode II:
This display mode makes it possible to have three meters displayed at the same time on line 1. The meters displayed are selected through parameters 008, 009 and 010.
100% 7.8A 5.9kW
SETUP
50.0Hz
1
AUTO REMOTE RUN
24
Display Mode III:
This display mode is shown when the drive is in Display Mode II and the Display Mode key is pressed and held. In the first line, a description of the three top meters in Display Mode II is shown. The other lines are unchanged. When the key is released, Display Mode II is again shown.
REF% CURR.A POW. kW
Display Mode IV:
This display mode is available when local reference is selected. In this display mode, the speed reference is increased or decreased via +/- keys.
The first line shows the present speed reference. The second line shows the present drive output frequency. The third line show a bar graph of the relative value of the present drive output frequency in relation to the maximum frequency.
50.0Hz
AUTO REMOTE RUN
Navigation Between Display Modes
With local reference
SETUP
1
FREQUENCY
40.0Hz
AUTO REMOTE RUNNING
Display Mode I
USE +/- 56Hz
40Hz
0 -----60
HAND LOCAL RAMPING
SETUP
1
With remote controlled reference
SETUP
1
With local/remote reference
USE +/- 56Hz
SETUP
40.0Hz
0 ----60
HAND LOCAL RAMPING
Display Mode IV
1
With local reference
▲▲
▲▲
Keep DISPLAY MODE key down
80% 7.8A 5.9kW
SETUP
40.0Hz
AUTO REMOTE RUN
Display Mode II
▲▲
▲▲
REF% CURR.A POW. kW
40.0Hz
AUTO REMOTE RUN
Display Mode III
1
▼▼
▼▼
Release DISPLAY MODE key
SETUP
1
25
Quick Menu
The QUICK MENU key gives access to 12 of the most important setup parameters of the drive. After programming, the drive will, in many cases, be ready for operation. The 12 Quick Menu parameters are
Quick Menu Parameter Description Item Number Name
1 001 Language Selects language used for all displays. 2 102 Motor Power Sets output characteristics of drive based on kW (HP) of motor. See
chart in parameter 102, Motor Power, to convert HP to kW. 3 103 Motor Voltage Sets output characteristics of drive based on voltage of motor . 4 104 Motor Frequency Sets output characteristics of drive based on nominal frequency of
motor. This is typically equal to line frequency . 5 105 Motor Current Sets output characteristics of drive based on full load current in amps
(FLA) of motor. This sets overload protection for motor . 6 106 Motor Nominal Speed Sets output characteristics of drive based on nominal full load speed of
motor. 7 201 Minimum Frequency Sets minimum controlled frequency at which motor will run. 8 202 Maximum Frequency Sets maximum controlled frequency at which motor will run. 9 206 Ramp Up Time Sets time to accelerate motor from 0 Hz to nominal motor frequency
set in Quick Menu Item 4.
10 207 Ramp Down Time Sets time to decelerate motor from nominal motor frequency set in
Quick Menu Item 4 to 0 Hz.
1 1 323 Relay 1 Function Sets function of high voltage Form C relay.
12 326 Relay 2 Function Sets function of low voltage Form A relay.
shown in the table below. A complete description of the function is given in the parameter sections of this manual.
To Enter or Change Quick Menu Parameter Data
Enter or change parameter data or settings in accordance with the following procedure.
1. Press Quick Menu key.
2. Use ‘+’ and ‘-’ keys to find parameter you chose to edit.
3. Press Change Data key.
4. Use ‘+’ and ‘-’ keys to select correct parameter setting. T o move to a different digit within parameter , use J and K arrows. Flashing
cursor indicates digit selected to change.
5. Press Cancel key to disregard change, or press OK key to accept change and enter new setting.
Example of Changing Parameter Data
Assume Parameter 206, Ramp Up Time, is set at 60 seconds. Change the ramp up time to 100 seconds in accordance with the following procedure.
1. Press Quick Menu key.
2. Press ‘+’ key until you reach Parameter 206, Ramp Up Time.
3. Press Change Data key.
4. Press J key twice – hundreds digit will flash.
5. Press ‘+’ key once to change hundreds digit to ‘1.’
6. Press K key to change to tens digit.
7. Press ‘-’ key until ‘6’ counts down to ‘0’ and setting for Ramp Up Time reads ‘100 s.’
8. Press OK key to enter new value into drive controller.
NOTE Programming of extended parameters functions available through Extended Menu key is done in accordance with same procedure as de­scribed for Quick Menu functions.
26
Extended Menu
CAUTION
!
In some applications, the Quick Menu items will not set up all the desired characteristics of the drive. T o access all the parameters, including the Quick Menu parameters, press the Extend Menu key. The Programming section of this manual will describe in detail all the parameters available through the Extended Menu.
Step Change of Numeric Values
The values of certain numeric items can also be selected from a list. These parameters are Motor Power, parameter 102; Motor Voltage, parameter 103; and Motor Frequency, parameter 104. T o select a value not on the list, use the L and M keys to select the digit to be changed, as described above.
Changing Data
T o change any parameter in either the Quick Menu mode or the Extended Menu mode, press the CHANGE DAT A key. When the CHANGE DAT A key is pressed, the data in line four will be underlined, and a cursor will be shown if the parameter controls numeric data.
The procedure for changing data depends on whether the value of the parameter is a number or a item from a list.
FREQUENCY
SETUP
24.2 Hz
1
205 MAX. REFERENCE
000060.000 Hz
Parameter is a Number
T o change a number , move the cursor to the digit to be changed by using the LM keys. Then change the digit by using the + and - keys.
MOTOR CURRENT
SETUP
3.90 A
1
210 REFERENCE TYPE SUM
Parameter is a Value Chosen from a List
Manual Initialization of Parameters
It is possible to reset nearly all parameters back to their original default values at once. T o reset the drive parameters to their read only memory default values, remove power from the drive. Press and hold the Display Mode, Change Data and OK keys down while reapplying power. Shortly after power is reapplied, the bottom line of the display will read “Initial­ized”. After the display stops changing, release the keys. If “Initialized” did not appear, repeat the procedure.
These parameters are not reset by manual initialization:
Parameter 600 Operating hours Parameter 601 Hours run Parameter 602 kWh counter Parameter 603 Number of power-ups Parameter 604 Number of overtemperatures Parameter 605 Number of overvoltages
Initialization can also be done using Parameter 620.
Manual initialization using either this procedure or parameter 620 will reset drive to standard de­fault parameters. Any special programming for application that was performed at factory, during start-up or subsequently, will be lost. If desired parameters have been previously stored in drive’s local control panel (LCP), it may be better to down­load those parameters from LCP using parameter download functions of parameter 004.
Uploading Parameters
At any time the present parameters may be copied to the local control panel (LCP). This may be useful when setting up multiple drives. It is also useful when it is desired to return to a previous set of parameters. See parameter 004, LCP Copy, for more information.
If the selected parameter’s value is selected from a list, its value can be changed by using the + and - keys.
When the desired value is displayed, press the OK key to accept the new value. If you wish to cancel the change and return to the previously accepted value, press the CANCEL key . If neither OK nor CANCEL is pressed, the new value will be accepted after 20 seconds.
Manually initializing the drive using either the procedure described above or parameter 620, Operating Mode, does not change the values uploaded to the local control panel.
27
VLT 6000 Start-Up
Pre-installation Checks
1. Compare drive model number to what was ordered.
2. Ensure each of following are rated for same voltage:
Drive
Power line
Motor
3. Record following motor data:
Voltage
Frequency
Full load current
Full load speed
Power — convert HP to kW (See conversion table in parameter
102, Motor Power, in this manual.)
4. Ensure that rated drive current is equal to or greater than total full load current.
For multiple motor operations, add up full load current ratings of
all motors.
Drive can be at most one size smaller than motor.
If drive rating is less than motor, full motor output cannot be achieved.
5. Check motor wiring:
Any disconnect between drive and motor should be interlocked
to drive safety interlock circuit to avoid unwanted drive trips.
No power factor correction capacitors can be connected between
drive and motor.
Two speed motors must be wired permanently for full speed.
Y-start, H-run motors must be wired permanently for run.
Installation Checks
1. Input fusing in power supply for all drives must be provided (see Input Fuses section in this manual).
2. Environmental concerns — for standard NEMA 1 drive:
Clean air supply
Dry air (max 95% relative humidity , non-condensing)
o
14
F to 104oF ambient temperature operating range, or as rated
3,300 foot maximum elevation with no derating
3. Mounting
Vertical
Drives with heat sink fins exposed in back of unit must be
mounted against a solid surface (see Clearances section in this manual).
Keep any construction dirt out of drive.
4. Wiring
Wire drive in accordance with instructions and diagrams received
with drive.
Separate conduits must be provided to drive for input power,
output power, and control wiring.
Note that safety interlock and remote run/stop circuitry is 115 V AC
for drives with bypasses.
Use knockouts or conduit entry plates. Avoid metal shavings in cabinet.
Protect signal wires from noise.
Ground each drive individually.
Double check input and output power wiring for correct location.
Setting Up Drive for Motor Start
Enter motor nameplate data into drive through Quick Menu.
1. Parameter 101:
If one motor is connected to drive, set to AEO FUNCTION.
If more than one motor connected to drive, set to MULTIPLE
MOTORS. (Parameter 108, MUL TIPLE MOTOR ST ARTING VOLT AGE should be adjusted later to provide reliable starts and minimum starting current.)
2. Parameter 102, MOTOR POWER (in kW) (See conversion table in parameter 102, Motor Power, in this manual.)
3. Parameter 103, MOTOR VOLT AGE
4. Parameter 104, MOTOR FREQUENCY
5. Parameter 105, MOTOR CURRENT
6. Parameter 106, MOTOR SPEED
7. Parameter 107, (optional) select AUTOMATIC MOTOR ADAPT A­TION and run AMA in accordance with procedure in parameter 107, Automatic Motor Adaptation, in this manual.
8. Press HAND STAR T key to initiate operation in local control.
Operational Tests HAND
1. Check motor rotation from drive. If incorrect, disconnect input power from drive and reverse two leads between drive and motor.
2. If a bypass is provided, check motor rotation in bypass mode. If incorrect, disconnect input power from drive and reverse two input power leads.
3. Accelerate motor quickly to full speed and verify operation.
4. Decelerate motor quickly to stop and verify operation.
5. Operate motor over entire speed range while closely checking for resonance.
Operational Tests AUTO
1. Ensure that drive follows run/stop and safety interlock commands from system.
2. Ensure drive follows speed reference, or feedback, from system.
Final Adjustments
1. Use parameters 216 through 220 to reject any resonant points.
2. Lock out keypad functions, as required.
General Troubleshooting
1. Display Messages:
AUTO ST ART—Drive has tripped off and is in process of
automatically restarting.
TRIP—Drive has tripped off. Press RESET to start.
TRIP LOCKED—Drive has tripped off. Remove and apply
power before restarting with RESET .
2. Refer to Warnings and Alarms section in this manual.
3. Check tightness of all connections and wires for proper location.
4. Measure input signals.
5. Check drive input and output for balanced voltage and current.
28
Programming
Using the Extend Menu key, it is possible to access to all the parameters for the drive.
Operation and Display Parameters 000 through 017
This parameter group deals with the display, control keys and other general functions.
Description of Parameters
Parameters are grouped by function. The groups are:
Operation and Display Parameters 001 through 017 Load and Motor Parameters 100 through 117 References and Limits Parameters 200 through 228 Input and Outputs Parameters 300 through 328 Appli cat ion Func tio ns Parameters 400 through 427 Serial Communication Parameters 500 through 566 Service Functions Parameters 600 through 631 Relay Card Functions Parameters 700 through 711
The numbers shown in the square brackets ([ ]) after the parameter values are used in serial communications to choose the parameter value from the list. They are not shown on the local control panel when programming the drive locally.
Setup Configuration
The drive has four setups that can be programmed independently. The active setup can be selected in parameter 002, Active Setup. The active setup number is shown on the right of line two in the display under the word “Setup.”
It is also possible to set the drive to Multi-Setup to allow switching setups through digital inputs or serial communication.
More than one setup can be used. An example would be a changing setups for day/night or summer/winter operation.
Parameter 003, Copying of Setups, enables copying from one setup to another.
By means of parameter 004, LCP Copy, any setup can be transferred from one drive to another using the removable local control panel (LCP). First, upload all parameter values to the control panel installed in the drive. Insert this panel into the next drive. Download all parameter values from the control unit to the second drive. Repeat this procedure to program additional drives.
001 Language (Language) Value:
English (ENGLISH) [0]
German (DEUTSCH) [1] French (FRANCAIS) [2] Danish (DANSK) [3] Spanish (ESP A¥OL) [4] Italian (ITALIANO) [5] Swedish (SVENSKA) [6] Dutch (NEDERLANDS) [7] Portuguese (PORTUGUESA) [8]
Function:
This parameter determines the language to be used on the display .
Description of choice:
There is a choice of the languages indicated.
002 Active Setup (ACTIVE SETUP) Value:
Factory Setup (FACTOR Y SETUP) [0]
Setup 1 (SETUP 1) [1]
Setup 2 (SETUP 2) [2] Setup 3 (SETUP 3) [3] Setup 4 (SETUP 4) [4] Multi-Setup (MULTI SETUP) [5]
Function:
This parameter defines the setup number that controls the drive. All parameters can be programmed in four individual parameter setups,
Setup 1, Setup 2, Setup 3 and Setup 4. In addition, a pre-programmed read-only setup, called the Factory
Setup, exists.
Description of choice:
Factory Setup contains the parameter values preset at the factory. This setup can be used as a data source if the other setups are to be returned to a known state.
Setups 1 through 4 are four individual setups that can be selected as required.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
Multi-Setup is used if remote switching between different setups is required. T erminals 16, 17, 29, 32, 33 and the serial communication port can be used for switching between setups.
29
Connection Examples:
Setup Change
Selection of setup using terminals 32 and 33. See the descriptions of parameters 300 through 307. Parameter 306 = Selection of Setup, lsb Parameter 307 = Selection of Setup, msb Parameter 002 = Multi Setup
004 LCP Copy (LCP COPY) Value:
No copying (NO COPY) [0]
Upload all parameters (UPLOAD ALL PARAMET.) [1] Download all parameters (DOWNLOAD ALL PARAM.) [2] Download power-independent parameters (DOWNLOAD SIZE INDEP .) [3]
Function:
Parameter 004, LCP Copy, is used to copy all parameter setups to or from the Local Control Panel (LCP). This can be used to store a backup copy of all parameters in the LCP or to copy all setups from one drive to another.
Description of choice:
Select Upload all parameters if all parameter values are to be copied from the drive to the LCP .
Select Download all parameters if all parameter values are to be copied from the LCP to the drive on which the control panel has been mounted.
003 Copying of Setups (Setup Copy) Value:
No copying (NO COPY) [0]
Copy active Setup to Setup 1 (COPY TO SETUP 1) [1] Copy active Setup to Setup 2 (COPY TO SETUP 2) [2] Copy active Setup to Setup 3 (COPY TO SETUP 3) [3] Copy active Setup to Setup 4 (COPY TO SETUP 4) [4] Copy active Setup to all (COPY TO ALL) [5]
Function:
A copy is made from the active setup selected in parameter 002, Active Setup, to the setup or setups selected in parameter 003, Copying of Setups.
NOTE
Copying is only possible when drive is stopped.
Description of choice:
The copying starts when the required copying function has been selected and the OK key has been pressed.
Select Download power-independent parameters if only the power­independent parameters are to be downloaded. This allows the parameters from one drive to be easily copied to another drive of a different size.
NOTE
Copying is only possible when drive is stopped.
Setup of User-Defined Readout
Parameter 005, Maximum Value of User-Defined Readout, and Parameter 006, Unit for User-Defined Readout, allow users to design their own readout which can be seen if the User-Defined Readout has been selected as one of the displayed meters. The range is set in parameter 005, Maximum Value of User-Defined Readout and the unit is determined in parameter 006, Unit for User-Defined Readout. The choice of unit determines whether the relationship between the output frequency and the readout is a linear, square or cubed. Units representing rates (RPM, CFM, GPM, etc.) are linear. Units represent­ing pressure (PSI, in. wg., etc.) are square. Units representing power (HP , kW , etc.) are cubed.
The display indicates when copying is in progress.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
30
005 Maximum Value of User-Defined Readout
(CUSTOM READOUT )
Value:
0.01 - 999,999.99 ✭100.000
Function:
This parameter determines the value that the user defined meter will display when the drive’s output frequency is the value set in parameter 202, Output Frequency High.
Description of choice:
Set the required value for maximum output frequency.
006 Unit for User Defined Readout
(CUST. READ. UNIT)
Value:
1
No unit
%
1
Linear units (flow or speed)
2
Squared units (pressure)
3
Cubed units (power)
1
1
rpm
1
ppm pulse/s
1
l/s
1
l/min
1
l/h
1
kg/s kg/min
1
kg/h
1
m3/s m3/min
1
m3/h
1
m/s
2
mbar
2
bar
2
Pa
2
MPa MWG
3
kW
1
1
1
2
[0] GPM [1] gal/s [2] gal/min [3] gal/h [4] lb/s [5] lb/min [6] lb/h [7] CFM [8] ft3/s [9] ft3/min [10] ft3/h [11] ft3/min [12] ft/s [13] in wg [14] ft wg [15] PSI [16] lb/in [17] HP [18] [19] [20]
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
3
[21] [22] [23] [24] [25] [26] [27] [28] [29] [30] [31] [32] [33] [34] [35] [36] [37] [38]
Function:
Select a unit to be shown with the display of the User Defined Readout. If flow or speed units are selected, the relationship between readout and output frequency will be a linear one. If pressure units are selected, the ratio will be square. If power units are selected, the ratio will be cubed.
The value and the unit are shown in display mode whenever User Defined Readout has been selected in one of parameters 007 through 010, Display Readout.
Description of choice:
Select the required unit for User Defined Readout.
007 Large Display Readout (LARGE READOUT) Value:
Resulting reference [%] (REFERENCE [%]) [1] Resulting reference [unit] (REFERENCE [UNIT]) [2] Frequency [Hz] (FREQUENCY [HZ]) [3]
% of maximum output frequency [%]
(FREQUENCY [%]) [4] Motor current [A] (MOTOR CURRENT [A]) [5] Power [kW] (POWER [KW]) [6] Power [HP] (POWER [HP]) [7] Output energy [kWh] (ENERGY [UNIT]) [8] Hours run [Hours] (HOURS RUN [h]) [9] User-defined readout [-] (CUSTOM READ. [UNITS]) [10] Setpoint 1 [unit] (SETPOINT 1 [UNITS]) [11] Setpoint 2 [unit] (SETPOINT 2 [UNITS]) [12] Feedback 1 (FEEDBACK 1 [UNITS]) [13] Feedback 2 (FEEDBACK 2 [UNITS]) [14] Feedback [unit] (FEEDBACK [UNITS]) [15] Motor voltage [V] (MOTOR VOL T AGE [V]) [16] DC link voltage [V] (DC VOLTAGE [V]) [17] Thermal load, motor [%] (THERM.MOTOR LOAD [%]) [18] Thermal load, VLT [%] (THERM.DRIVE LOAD [%]) [19] Digital input [Binary code] (DIGITAL INPUT [BIN]) [20] Analog input 53 [V] (ANALOG INPUT 53 [V]) [21] Analog input 54 [V] (ANALOG INPUT 54 [V]) [22] Analog input 60 [mA] (ANALOG 60 [mA]) [23] Pulse reference [Hz] (PULSE REFERENCE [Hz]) [24] External reference [%] (EXT. REFERENCE [%]) [25] Heat sink temp. [oC] (HEATSINK TEMP [oC]) [26] Free programming array (FREE PROG. ARRAY) [27]
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
31
Function:
This parameter allows a choice of the data value to be shown in large digits on line two of the display when power is first applied to the drive. In Display Mode I, II, and III, the + and - keys allow the display on this line to be changed when the drive is in operation.
DC link voltage [V] is the drive DC bus voltage. Thermal load, motor [%] is the calculated thermal load of the motor.
100% is the cutout limit. See also parameter 117, Motor Thermal Protection.
Description of choice:
No readout can only be selected in parameters 008 through 010, Small Display Readout, but not in parameter 007, Large Display Readout.
Resulting reference [%] gives the total of all references as a percentage of parameter 205, Maximum Reference.
Reference [unit] gives the total of all references. This is displayed in Hz in open loop. In closed loop, the reference unit is selected in parameter 415, Process Units.
Frequency [Hz] gives the output frequency of the drive. % of maximum output frequency [%] is the output frequency as a
percentage of parameter 202, Output Frequency High Limit.
Motor current [A] is the average phase current of the motor. Power [kW] is the actual power, in kW , delivered to the motor . Power [HP] is the actual power, in HP, delivered to the motor. Output energy [kWh] is the energy delivered by the motor since the
latest reset was made using parameter 618, Reset of kWh Counter. Hours run [Hours] is the number of hours that the motor has run
since the latest reset was made using parameter 619, Reset of Hours
Run Counter.
User Defined readout [-] is a user defined value, calculated on the basis of the present output frequency, as well as the scaling in parameter 005, Maximum V alue of User-Defined Readout, and the unit in parameter 006, Unit for User-Defined Readout.
Setpoint 1 [unit] is the setpoint value programmed in parameter 418, Setpoint 1. The unit is selected in parameter 415, Process Units.
Setpoint 2 [unit] is the setpoint value programmed in parameter 419, Setpoint 2. The unit is selected in parameter 415, Process Units.
Thermal load, VLT [%] is the calculated thermal load of the drive. 100% is the trip point.
Digital input [Binary code] is the signal status from the 8 digital inputs (16, 17, 18, 19, 27, 29, 32 and 33). T erminal 16 corresponds to the bit at the far left. ‘0’ = no signal, ‘1’ = connected signal.
Analog input 53 [V] is the voltage applied to terminal 53. Analog input 54 [V] is the voltage applied to terminal 54. Analog input 60 [mA] is the current applied to terminal 60. Pulse reference [Hz] is the pulse frequency in Hz applied to terminal
17 or terminal 29. External reference [%] is the sum of the external references as a
percentage of parameter 205, Maximum Reference. Heat sink temp. [°C] is the present heat sink temperature of the drive.
The trip point is 90 ± 5°C for NEMA 1 units and 80 ± 5°C for NEMA 12 units.
Free Programming Array is reserved for future use. It is only available in parameter 007, Large Display Readout.
008 Small Display Readout 1.1
(SMALL READOUT 1)
Value:
See parameter 007, Large Display Readout
Reference, %
Function:
This parameter selects the meter to be displayed on the left display on line 1.
Showing three different meters on line 1 is recommended when setting up the PID. This allows tracking how the process reacts to a change of reference.
Feedback 1 [unit] is the value of the feedback signal applied to T erminal 53. The unit is selected in parameter 415, Process Units.
Feedback 2 [unit] is the value of the feedback signal applied to T erminal 54. The unit is selected in parameter 415, Process Units.
Feedback [unit] is the total feedback signal using the unit scaling selected in parameter 413, Minimum Feedback; parameter 414 Maximum Feedback; parameter 415, Process Units; and parameter 417, 2 Feedback Calc.
Motor voltage [V] is the voltage supplied to the motor.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
32
T o select the meter to display , press the Display Mode button.
Description of choice:
There is a choice of 26 different meters. See parameter 007, Large Display Readout.
009 Small Display Readout 1.2
(SMALL READOUT 2)
Value:
See parameter 007, Large Display Readout
Motor current [A]
Function:
CAUTION
!
CAUTION
!
See the functional description for parameter 008, Small Display Readout.
Description of choice:
There is a choice of 26 meters, see parameter 007 Large Display Readout.
010 Small Display Readout 1.3
(SMALL READOUT 3)
Value:
See parameter 007 Large Display Readout
Power [HP]
If
Disable
by Off/Stop key.
014 Auto Start on LCP (AUTO START BTTN) Value
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This parameter allows disabling the Auto/Start key on the keypad.
is selected, motor cannot be stopped
Function:
See the functional description for parameter 008 Small Data Readout.
Description of choice:
There is a choice of 26 different data values, see parameter 007 Large Display Readout.
011 Unit of Local Reference (UNIT OF LOC REF) Value:
Hz (HZ) [0]
% of output frequency range (%) (% OF FMAX) [1]
Function:
This parameter sets the unit that will be displayed in Display Mode IV when the drive’s speed is being controlled locally .
Description of choice:
Choose the desired unit for local reference.
012 Hand Start on LCP (HAND START BUTTON) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This parameter allows disabling the Hand/Start key on the keypad.
Description of choice:
If Disable is selected in this parameter , the Hand/Start key will be disabled.
013 OFF/STOP on LCP (STOP BUTTON) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This parameter allows disabling the Off/Stop key on the keypad.
Description of choice:
If Disable is selected in this parameter , the Off/Stop key will be disabled.
Description of choice:
If Disable is selected in this parameter , the Auto/Start key will be disabled.
P 015 015 Reset on LCP (RESET BUTTON) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
This parameter allows disabling the Reset key on the keypad.
Description of choice:
If Disable is selected in this parameter , the Reset key will be inactive.
Do not disable Reset unless a remote reset is available through digital inputs and parameters 300 through 307.
016 Lock for Data Change (DATA CHANGE LOCK) Value:
Not Locked (NOT LOCKED) [0]
Locked (LOCKED) [1]
Function:
This parameter allows locking out parameter changes at the local control panel.
Description of choice:
If Locked is selected, data modifications in the parameters cannot be made. Parameter changes will be possible through serial communica­tion.
Parameters 007 through 010, Display Readout can be changed at the local control panel.
The local control panel can also be locked or unlocked by a digital input controlled by parameters 300 through 307.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
33
017 Operating State at Power Up
(POWER UP ACTION)
Value:
Auto restart (AUTO REST ART) [0]
OFF/STOP (OFF/STOP) [1]
Function:
Selects auto or manual restart when power is reapplied after an outage occurs to a running drive.
Description of choice:
Auto restart is selected if the drive is to resume operation after a power outage.
OFF/STOP is selected if the drive is to remain stopped after a power outage. T o restart, press the Hand/Start or Auto/Start key at the keypad.
CAUTION
!
If HAND/START or AUTO/START are disabled by parameters 012 and 014, motor will not be able to restart if
OFF/STOP
is selected.
Load and Motor Parameters 100 through 117
This parameter group controls output power and other output characteristics of the drive.
For correct operation, motor nameplate data must be entered into parameters 102 through 106 either through the Quick Menu or the Extended Menu. In addition, automatic motor adaptation, DC braking and motor thermal protection can be set by this parameter group.
NOTE If Open Loop is selected, parameters associ­ated with setting up PID controller are not accessible. Therefore, it is important to prop­erly set parameter 100, closed loop operation is required.
Characteristics 101 Torque Characteristics ( VT CHARACT) Value:
Automatic Energy Optimization
(AEO FUNCTION) [0] Parallel motors (MULTIPLE MOTORS) [1]
Function:
This parameter configures the drive for single or multiple motor operation.
Description of choice:
Select Automatic Energy Optimization (AEO) for all single motor applications. When AEO has been selected, only one motor may be connected to the drive at a time.
The AEO function will automatically and continuously monitor the load and adjust the output voltage to maximize motor and drive efficiency and performance. After the motor reaches the set speed, the AEO function reduces the output voltage to the motor, if the load will allow . When the load is light, the voltage is reduced, as shown in the graph below. This lower voltage reduces motor heating and motor noise, and increases efficiency .
Select Parallel motors when more than one motor is connected in parallel to the output. In this case, it is necessary to set a start voltage in parameter 108, Start Voltage of Parallel Motors.
Configuration
, first when
100 Configuration (CONFIG. MODE) Value:
Open loop (OPEN LOOP) [0]
Closed loop (CLOSED LOOP) [1]
Function:
This parameter is used for selecting closed loop or open loop operation.
Description of choice:
If Open loop is selected, speed control is changed directly by the speed reference signal. Any feedback signal applied to the drive will have no effect on the drive’s speed.
If Closed loop is selected, the internal process regulator is available to accept feedback signal(s) to provide the desired speed regulation.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
34
CAUTION
!
It is very important that values set in param-
CAUTION
!
eters 102,
Speed,
of motor.
102 Motor Power (MOTOR POWER) Value:
0.25 kW (0.33 HP) [25]
0.37 kW (0.5 HP) [37]
0.55 kW (0.75 HP) [55]
0.75 kW (1 HP) [75]
1.1 kW (1.5 HP) [110]
1.5 kW (2 HP) [150]
2.2 kW (3 HP) [220] 3 kW -- [300] 4 kW (5 HP) [400]
5.5 kW (7.5 HP) [550]
7.5 kW (10 HP) [750] 1 1 k W (15 HP) [1 100] 15 k W (20 HP) [1500]
18.5 kW (25 HP) [1850] 22 k W (30 HP) [2200] 30 k W (40 HP) [3000] 37 k W (50 HP) [3700] 45 k W (60 HP) [4500] 55 k W (75 HP) [5500] 75 k W (100 HP) [7500] 90 k W (125 HP) [9000] 110 kW (150 HP) [11000] 132 kW (175 HP) [13200] 160 kW (200 HP) [16000] 200 kW (300 HP) [20000] 250 kW -- [25000] 300 kW -- [30000] 315 kW (350 HP) [31500] 355 kW (450 HP) [35500] 400 kW (500 HP) [40000] 500 kW (600 HP) [50000] Depends on the unit
Function:
Set the power value that corresponds to the nameplate power of the motor. The default setting is the full rating of the drive.
Description of choice:
Select a value that equals the nameplate data on the motor. It is also possible to set any power within the range of the drive.
Motor Power,
correspond accurately to nameplate data
through 106,
Rated Motor
103 Motor Voltage (MOTOR VOLTAGE) Value:
200 V [200] 208 V [208] 220 V [220] 230 V [230] 240 V [240] 380 V [380] 400 V [400] 415 V [415] 440 V [440] 460 V [460] 480 V [480] 500 V [500] 575 V [575]
Depends on the unit
Function:
Set the rated motor voltage.
Description of choice:
Select a value that equals the nameplate data on the motor. This may be less than the input voltage. It is also possible to set any voltage within the range of the drive.
104 Motor Frequency (MOTOR FREQUENCY) Value:
50 Hz (50 Hz) [50]
60 Hz (60 Hz) [60]
Function:
This is where the rated motor frequency is selected. This is usually the frequency of the power line.
Description of choice:
Select the desired value. It is also possible to set any frequency within the range of the drive.
Enter correct value in parameter 105,
rent
, since this forms part of VVC+ control. Changing values in parameter 102, or parameter 103, current has been entered in parameter 105 can automatically change the value in parameter 105.
105 Motor Current (MOTOR CURRENT) Value:
0.01 to drive rating
Function:
The rated motor current in amps is used for setting output current and providing motor thermal protection. It is important to set the motor current to the full load current rating (FLA) of the motor.
Motor Voltage,
Set based on motor nameplate.
Motor Cur-
Motor Power
after motor
,
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
Description of choice:
Set a value that equals the nameplate data on the motor.
35
CAUTION
!
It is important to set correct value in parameter 106,
Rated Motor Speed
of VVC+ control feature. Changing value in pa­rameter 104, speed has been entered in parameter 106 may automatically change the value in parameter 106.
106 Rated Motor Speed (MOTOR NOM. SPEED) Value:
100 through 60000
Depends on parameter 102, Motor Power
Function:
This is where the value is set that corresponds to the rated motor speed shown on the motor nameplate.
Description of choice:
Choose a value that corresponds to the motor nameplate data.
107 Automatic Motor Adaptation, AMA
(AUTO MOTOR ADAPT)
Value:
Optimization disable (NO AMA) [0]
Automatic adaptation (RUN AMA) [1] Automatic adaptation with LC-filter (RUN AMA WITH LC-FILT) [2]
Function:
Automatic Motor Adaptation (AMA) is an advanced procedure that measures electrical characteristics of the motor. This procedure does not run the motor.
AMA optimizes the adjustment of the drive to the motor. This feature is particularly useful with nonstandard motors, higher HP motors, and when the drive-to-motor cable length is long. Although it is not necessary to run AMA, it is highly recommended for optimum operation and increases the capability of the Automatic Energy Optimization function selectable in parameter 101, T orque Characteristics.
Motor Frequency
, since this forms part
, after rated motor
NOTE
Some motors may be unable to run AMA.
tomatic Motor Adaptation with LC-Filter
reduced AMA procedure which can be effective in such cases when run without an LC-filter in­stalled since results measure motor’s stator and effects of cable length.
The following must be noted when the AMA function is used:
- Before running AMA, the correct nameplate data for the motor must be entered in parameters 102 to 106.
- T otal automatic motor adaptation may take up to 10 minutes.
- Alarms and warnings will be shown in the display if faults occur during motor adaptation.
- AMA can only be carried out if the rated motor current of the motor is at least 35% of the rated output current of the drive.
- To cancel AMA, press the OFF/STOP key .
CAUTION
!
AMA cannot be used on multiple motor appli­cations.
Description of choice:
Select Automatic Adaptation if the drive is to carry out a complete automatic motor adaptation procedure.
Select Automatic Adaptation with LC-Filter if an LC-filter has been placed between the drive and the motor or to run a reduced AMA without an LC-filter installed.
Au-
is a
Procedure for Automatic Motor Adaptation:
1. Set motor parameters, 102 through 106, according to motor nameplate data.
2. Connect 24 VDC from terminal 12, or external to drive, to terminal 27.
3. Select either Automatic Adaptation or Automatic Adaptation with LC-Filter in parameter 107, Automatic Motor Adaptation, AMA.
4. Start drive by pressing Hand Start or connect terminal 18 (start) to terminal 12 and press Auto Start.
For the best adjustment of the drive, it is recommended to carry out AMA on a cold motor.
CAUTION
!
Repeated AMA runs may lead to a heating of motor that will result in an increase of stator resistance. This will reduce accuracy. Allow motor to cool before running AMA.
If an output LC-filter has been connected between the drive and the motor, select the Automatic Adaptation with LC-Filter. If the complete AMA procedure is desired, remove the LC-filter, run Automatic Adaptation (RUN AMA), and reinstall the filter .
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
36
If the Automatic Motor Adaptation is to be stopped prior to completion:
Press OFF/STOP key .
After a normal sequence, the display reads: AMA STOP
1. Press RESET key . Drive is now ready for operation.
NOTE RESET key must be pressed after AMA is completed to load results into drive.
If there is a fault, the display reads: ALARM 22
WARNING
!
WARNING
!
1. Press RESET key to clear fault.
2. Check alarms section in this manual for possible causes of alarm.
111 Start Delay (START DELAY) Value:
0.0 to 120.0 sec. 0.0 sec.
If there is a warning, the display reads: WARNING (39 through 42)
1. Check warnings section in this manual for possible causes of warning.
2. Press CHANGE DATA key and select Continue if AMA is to continue despite warning, or press OFF/STOP key to stop AMA.
108 Start Voltage of Parallel Motors
(MULTIM.START VOLT)
Value:
0.0 through parameter 103 Motor Voltage depends on par. 103 Motor V oltage
Function:
This parameter sets the voltage at 0 Hz for all drives with two or more motors connected in parallel.
The start voltage represents a supplementary voltage input to the motor. Increasing the start voltage will increase the starting torque. A start voltage is especially useful for small motors (<5 HP) as they have a higher stator resistance than larger motors.
This function is only active if Parallel Motors has been selected in parameter 101, T orque Characteristics.
Description of choice:
T o set the start voltage, monitor the motor current while starting the load and choose the starting voltage that gives the lowest starting current. Start with a small value and increase only as required for reliable starting.
109 Resonance Dampening (RESONANCE DAMP.) Value:
0 to 500 % 100 %
Function:
High-frequency resonances in the motor can be eliminated by adjusting this parameter.
Description of choice:
Adjust the dampening percentage for smoothest high speed operation.
110 High Breakaway Torque (HIGH START TORQ.) Value:
0.0 to 0.5 sec. OFF
Function:
This parameter allows a delayed start of the drive after the conditions for start have been fulfilled. After the start delay time has elapsed, the drive will start and ramp up to the commanded speed.
Description of choice:
Set the desired time before the drive will start.
112 Motor Preheat (MOTOR PREHEAT) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
The motor preheat function protects the motor from condensation by running a small DC current through the motor. Motor preheat is only active during stop when control voltage is applied to terminal 27.
Description of choice:
Select Disable if this function is not required. Select Enable to activate motor preheating. The amount of motor preheating is set in parameter 1 13.
Be sure to check parameter 113 if parameter 112,
Motor Preheat
rent or preheating time may damage motor.
113 Motor Preheat DC Current
(PREHEAT DC-CURR.)
Value:
0 to 100 % 50 %
The maximum value depends on the rated motor current.
Function:
The motor can be preheated when stopped by applying DC current to it. A holding torque can also be provided.
Description of choice:
The motor can be preheated by means of a DC current. At 0%, the function is inactive; at a value higher than 0%, a DC current will be supplied to the motor whenever it is stopped. A windmilling fan can be held by providing a holding toque by using this parameter.
, is enabled. Excessive cur-
Function:
The drive is able to breakaway high friction loads. This high starting torque, approximately 1.6 x rated torque is available for up to 0.5 seconds. The current level is limited by the protective circuits of the drive. OFF corresponds to 0.0 sec.
Description of choice:
Set the time for which high starting torque is desired.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
Do not apply any more current than required. Too high a current applied for too long a time will overheat motor.
37
DC Braking
Applying DC current to the motor will brake the motor. Parameter 1 14, DC Braking Current, sets the DC braking current as a percentage of the rated motor current. Parameter 115, DC Braking T ime, sets the amount of time that the DC current will be applied. Parameter 116, DC Brake Cut-in Frequency, sets the frequency at which DC braking begins when the motor decelerates during a stop.
If terminal 19 or 27 (parameters 303 or 304 Digital Input) has been programmed to DC Braking Inverse and shifts from logic ‘1’ to logic ‘0’, the DC braking will be activated immediately.
When the start signal on terminal 18 changes from logic ‘1’ to logic ‘0’, the DC braking will be activated when the output frequency becomes lower than the brake cut-in frequency.
If a DC brake current is set in parameter 114, the drive’ s switching frequency will be limited to 4 kHz during the braking.
WARNING
!
A high braking current supplied for a long time will overheat motor. Use only the DC braking current and time required.
CAUTION
!
Do not use DC braking function if inertia of driven load is more than 20 times inertia of motor.
115 DC Braking Time (DC BRAKE TIME) Value:
0.0 to 60.0 sec. 10.0 sec.
Function:
This parameter sets the time that the DC braking is active.
Description of choice:
Set the desired time.
116 DC Brake Cut-in Frequency
(DC BRAKE CUT-IN)
Value:
0.0 (OFF) to setting of parameter 202 OFF
Function:
This parameter is used for setting the frequency at which DC braking begins after a stop command is issued.
Description of choice:
Set the desired frequency for braking to begin upon deceleration.
CAUTION
!
Most HVAC applications do not required brak­ing or holding. It is suggested that parameter 114 remains set at 0 unless unusual applica­tion requirements call for braking or holding torque.
114 DC Braking Current (DC BRAKE CURRENT) Value:
0 to 100% 50 %
The maximum value depends on the rated motor current.
Function:
This parameter is used for setting the DC braking current that is applied:
1. When the DC brake frequency set in parameter 116 DC Brake Cut-in Frequency has been reached during a stop.
2. When DC brake inverse is active via terminal 19 or 27, or via the serial bus.
The DC braking current will be active for the duration of the DC braking time set in parameter 115 DC Braking T ime.
Description of choice:
T o be set as a percentage value of the rated motor current set in parameter 105 Motor Current.
100% DC braking current corresponds to the value set in parameter
105.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
38
117 Motor Thermal Protection
CAUTION
!
(MOT. THERM PROTEC)
Value:
No protection (NO PROTECTION) [0] Thermistor warning (THERMISTOR WARNING) [1] Thermistor trip (THERMISTOR FAUL T) [2] ETR Warning 1 (ETR WARNING 1) [3]
ETR Trip 1 (ETR TRIP 1) [4]
ETR Warning 2 (ETR WARNING 2) [5] ETR Trip 2 (ETR TRIP 2) [6] ETR Warning 3 (ETR WARNING 3) [7] ETR Trip 3 (ETR TRIP 3) [8] ETR Warning 4 (ETR WARNING 4) [9] ETR Trip 4 (ETR TRIP 4) [10]
Function:
The drive is able to monitor the motor temperature in two different ways:
By a thermistor installed in the motor. The thermistor is connected to one of the analog input terminals (53 or 54).
Calculation of the thermal load by the Electronic Thermal Relay (ETR) is based on current, frequency and time. This is compared with the rated motor current and the rated motor frequency. The calculations take into account the reduced cooling of the motor at low speeds.
Description of choice:
Select No protection if no warning or trip is desired when the motor is overheated.
Select Thermistor warning if a warning is desired when the motor thermistor reaches its trip point.
Select Thermistor trip if a fault is desired when the motor thermistor reaches its trip point.
Select ETR Warning 1 through 4, if a warning is desired when the motor is overheated according to the ETR calculations.
The drive can also be programmed to give off a warning signal through one of the digital outputs.
Select ETR Trip 1 through 4 if a fault is desired when the motor is overheated according to the ETR calculations.
Motor Thermal Protection
The motor temperature is calculated on the basis of motor current, output frequency and time. The graph shows the amount of time that the drive can provide a current level to the motor at the rated motor frequency, 20% of rated motor frequency and 200% of rated motor frequency.
ETR Tip 1 through 4 and ETR Warning 1 through 4 correspond to the four drive setups. This enables the use of the ETR function to protect up to four different motors if a different setup is used for each different motor.
If multiple setups are used, be sure to program complete motor data (parameters 102 through
106) and parameter 117 in each setup. This can be done manually, or parameter 003 can be used to copy all data from one setup into one or more setup groups.
39
References and Limits Parameters 200 through 228
In this parameter group, the frequencies and references of the drive are set.
This parameter group includes:
202 Output Frequency High Limit
(MAX. FREQUENCY)
Value:
Parameter 201 to parameter 200 60 Hz
Function:
Set the highest speed at which the motor is to run.
- Setting of ramp times
- Choice of four preset references
- Setting four bypass frequencies
- Setting maximum current to motor
- Setting warning limits for current, frequency, reference and feedback
200 Output Frequency Range
(FREQUENCY RANGE)
Value:
0 to 120 Hz (0 - 120 HZ) [0]
0 to 1000 Hz (0 - 1000 HZ) [1]
Function:
Choose one of two maximum output frequency ranges.
Description of choice:
Select the output frequency range that includes the highest output frequency required for normal operation.
WARNING
!
HVAC applications will almost never require output frequency greater than 120 Hz. Check with Danfoss Graham, manufacturer of motor, and manufacturer of driven equipment before selecting 1000 Hz range.
NOTE Output frequency of drive can never assume value higher than 1/10th of switching frequency. See parameter 407,
Description of choice:
A value from the choice made in parameter 201 to the choice made in parameter 200 can be selected. The drive will not be able to run continuously at an output frequency below this value in any mode.
WARNING
!
HVAC applications seldom require output fre­quency greater than 60 Hz. Check with Danfoss Graham, manufacturer of motor, and manufac­turer of driven equipment before selecting maximum frequency greater than 60 Hz.
Switching Frequency
.
201 Output Frequency Low Limit
(MIN. FREQUENCY)
Value:
0.0 to parameter 202 0.0 HZ
Function:
Set the minimum speed at which the motor is to run.
Description of choice:
A value from 0.0 Hz to the Output Frequency High Limit frequency set in parameter 202 can be selected. The drive will not be able to run continuously at an output frequency below this value in any mode.
NOTE For fan applications, factory setting of param­eter 201 is 6 Hz. For pump applications, factory setting for parameter 201 is 18 Hz.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
40
Reference Handling
CAUTION
!
Reference handling is shown in the block diagram at the bottom of this page. The block diagram shows how a change in a parameter can affect the resulting reference.
Parameters 203 to 205, Reference Handling, Minimum and Maximum Reference, and parameter 210, Reference Type, define the way reference handling can be carried out. These parameters are active both in closed loop and open loop operation.
In closed loop operation, the resulting reference is affected by param­eters 418 and 419, Setpoints, as well as by remote references.
Remote references can be:
- external references, including analog inputs 53, 54 and 60; pulse
references through terminals 17 or 29 and references from serial communication.
- preset references.
The resulting reference can be shown in the display as a percentage by selecting Reference [%], or as a unit by selecting Reference [unit] in parameters 007 through 010. The sum of the external references can be shown in the display in a percentage of the range from
Minimum Reference to Maximum Reference. Select External Reference, [%] in parameters 007 through 010 Display Readout if a
readout is required.
It is possible to have both internal preset references and external references at the same time. In parameter 210, Reference Type, a choice is made of how the preset references are to be combined with the external references.
An independent local reference exists, where the resulting reference is set by means of the + and - keys. In all cases, the output frequency range is limited by parameter 201, Output Frequency Low Limit, and parameter 202, Output Frequency High Limit.
If local reference is active, drive is
Open Loop
rameter 100,
The unit of the local reference can be set either as Hz or as a percentage of the output frequency range. The unit is selected in parameter 011, Unit of Local Reference .
203 Reference Handling (REFERENCE SITE) Value:
Hand/Auto linked reference
(LINKED TO HAND/START) [0] Remote controlled reference (REMOTE) [1] Local reference (LOCAL) [2]
, regardless of choice made in pa-
Configuration
.
always
in
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
41
Function:
This parameter chooses the active resulting reference. If Hand/Auto linked reference is selected, the resulting reference will depend on
whether the drive is in Hand or Auto mode. The table below shows which reference is active when Hand/Auto
linked reference, Remote reference or Local reference has been selected. The Hand mode or Auto mode can be selected via the keypad or by a digital input set in parameters 300 through 307 Digital
Inputs.
Reference Handling Hand Mode Auto Mode
Hand/Auto Local ref . ac tive Remote ref. active Remote Remote ref. active Remote ref. active Local Local ref. active Local ref. ac tive
The unit for the reference can be seen from the following table:
Unit
Parameter 100 Configuration = Open loop Hz Parameter 100 Configuration = Closed loop Par. 415
Description of choice:
Minimum Reference is the lowest reference value that can be set for the drive.
205 Maximum Reference (MAX. REFERENCE) Value:
If parameter 100, Configuration = Open loop, parameter 204, Minimum Reference, to 1000.000 Hz 60.000 Hz
Description of choice:
If Hand/Auto linked reference is chosen, the motor speed in Hand mode will be set by the local reference, while in Auto mode it is set by the remote references and any setpoints selected.
If Remote reference is selected, the motor speed will depend on remote references and any setpoints selected, regardless of whether Hand mode or Auto mode has been chosen.
If Local reference is selected, the motor speed will only depend on the local reference set via the control panel, regardless of whether Hand mode or Auto mode has been selected.
204 Minimum Reference (MIN. REFERENCE) Value:
If parameter 100, Configuration = Open loop,
0.000Hz to parameter 205, Maximum Reference. 0.000 Hz If parameter 100 Configuration = Closed loop,
parameter 413, Minimum Feedback, to parameter 205, Maximum Reference. 0.000 Hz
Function:
The Minimum Reference sets the minimum value of the sum of all references. If Closed loop has been selected in parameter 100,
Configuration, the minimum reference is limited by parameter 413, Minimum Feedback.
If parameter 100, Configuration = Closed loop, parameter 204, Minimum Reference, to parameter 414, Maximum Feedback. 60.000 Hz
Function:
The Maximum Reference sets the maximum value of the sum of all references. If Closed loop has been selected in parameter 100, Configuration, the maximum reference cannot be set above parameter 414, Maximum Feedback. The Maximum Reference is ignored when the local reference is active.
The reference unit can be determined from the following table:
Unit Parameter 100 Configuration = Open loop Hz Parameter 100 Configuration = Closed loop Par. 415
Description of choice:
Maximum reference is the highest reference value that can be set for the drive.
Minimum reference is ignored when the local reference is active. In this case, minimum reference is determined by parameter 201, Minimum Frequency.
NOTE For fan applications, factory setting of param­eter 204 is 6 Hz. For pump applications, factory setting for parameter 204 is 18 Hz.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
42
206 Ramp Up Time (RAMP UP TIME)
CAUTION
!
Value:
1 to 3600 seconds Depends on the unit
Function:
The ramp up time is the acceleration time from 0 Hz to the rated motor frequency set in parameter 104. It is assumed that the output current does not reach the current limit set in parameter 215. This determines the maximum acceleration rate for all modes of operation.
Description of choice:
Program the desired accel time. T oo long of a ramp up time can cause sluggish drive operation. T oo short of a ramp up time can cause the drive to go into current limit during acceleration or cause unacceptable torque pulses in the controlled system.
Description of choice:
Program the desired decel time. T oo long of a ramp down time can cause sluggish operation. T oo short of a ramp down time can cause the drive to trip off due to high DC bus voltage or cause unacceptable torque pulses in the controlled system.
NOTE For fan applications, factory setting of param­eter 207 is 60 seconds. For pump applications, factory setting for parameter 207 is 10 seconds.
208 Automatic Ramp Down (AUTO RAMPING) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
NOTE For fan applications, factory setting of param­eter 206 is 60 seconds. For pump applications, factory setting for parameter 206 is 10 seconds.
207 Ramp Down Time (RAMP DOWN TIME) Value:
1 to 3600 seconds Depends on the unit
Function:
The ramp-down time is the deceleration time from the rated motor frequency set in parameter 104 to 0 Hz. This ramp-down time may be automatically extended to prevent an overvoltage trip if the load regenerates to the drive. This determines the maximum deceleration rate for all modes of operation.
Function:
This function ensures that the drive does not trip during deceleration if the decel time set is too short. If, during deceleration, the DC bus voltage increases to the maximum value permitted, the drive automati­cally extends the ramp-down time.
If auto ramping is enabled, ramp time can be considerably longer than that set in parameter
207.
Description of choice:
Program this function as Enable to avoid trips caused by too rapid a deceleration.
209 Jog Frequency (JOG FREQUENCY) Value:
Parameter 201, Output Frequency Low Limit, to parameter 202 Output Frequency High Limit 10.0 HZ
Function:
The jog frequency is the fixed output frequency at which the drive is running when the jog function is activated.
Jog can be activated via the digital inputs.
Description of choice:
Set the desired frequency.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
43
Reference Type
The example below shows how the resulting reference is calculated when Preset references are used together with Sum and Relative references set in parameter 210, Reference Type. A formula for calculating the resulting reference is given under Calculation of Resulting Reference. See the drawing under Reference Handling.
Example:
The following parameters have been set:
Parameter 204 Minimum Reference: 10 Hz Parameter 205 Maximum Reference: 60 Hz Parameter 211 Preset Reference: 15% Parameter 308 T erminal 53, Analog Input: Reference Parameter 309 T erminal 53, Min. Scaling: 0 V Parameter 310 T erminal 53, Max. Scaling: 10 V
When parameter 210 Reference Type is set to Sum, one of the adjusted Preset References, parameters 21 1 through 214, will be added to the external references as a percentage of the reference range. If terminal 53 has an analog input voltage of 4 V , the resulting reference will be:
Parameter 210 Reference type = Sum
Parameter 204 Minimum Reference = 10.0 Hz Reference contribution at 4 V = 16.0 Hz Parameter 211 Preset Reference Resulting reference = 32.0 Hz
If parameter 210 Reference Type is set to Relative, one of the adjusted Preset References parameters 211 through 214 will be totaled as a percentage of the sum of the present external references. If terminal 53 has an analog input voltage of 4 V , the resulting reference will be:
Parameter 210 Reference type = Relative
Parameter 204 Minimum Reference = 10.0 Hz Reference contribution at 4 V = 16.0 Hz Parameter 211 Preset Reference = 2.4 Hz Resulting reference = 28.4 Hz
The graph in the next column shows the resulting reference while the external reference changes from 0 to 10 V . Parameter 210, Reference
Type has been programmed for Sum and Relative. Parameter 21 1, Preset Reference 1, is programmed for 0%.
= 6.0 Hz
210 Reference Type (REF. FUNCTION) Value:
Sum (SUM) [0] Relative (RELATIVE) [1]
External/preset (EXTERNAL/PRESET) [2]
Function:
It is possible to define how the preset references are added to the other references. For this purpose, Sum or Relative is used. It is also possible, by using the External/Preset function, to select between the external references and a preset reference.
Description of choice:
If Sum is selected, one of the preset references (parameters 21 1 through 214, Preset Reference) is added to the other external references as a percentage of the reference range (minimum reference through maximum reference).
If Relative is selected, one of the adjusted preset references (param­eters 211 through 214, Preset Reference) is added as a percentage of the total external reference.
If External/Preset is selected, it is possible to shift between the external references and the preset references using terminals 16, 17, 29, 32 or 33 (parameters 300, 301, 305, 306 or 307, Digital Inputs). Preset references are a percentage value of the reference range. External reference is the sum of the analog references, pulse references and any references from serial communication.
CAUTION
!
If
Sum
or
Relative
references will always be active. If preset refer­ences are not used, they must be set to 0%.
is selected, one of preset
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
44
211 Preset Reference 1 (PRESET REF. 1) 212 Preset Reference 2 (PRESET REF. 2) 213 Preset Reference 3 (PRESET REF. 3) 214 Preset Reference 4 (PRESET REF. 4) Value:
-100.00 % to +100.00 % 0.00% of the reference range or external reference
Function:
Four different preset references can be programmed in parameters 21 1 to 214, Preset Reference. The preset reference is stated as a percentage of the reference range or as a percentage of the other external references, depending upon the choice made in parameter 210, Reference T yp e.
216 Frequency Bypass, Bandwidth
(FREQUENCY BYPASS B.W.)
Value:
0 (OFF) to 100 Hz DISABLED
Function:
Mechanical resonance in the driven system sometimes makes it desirable to avoid operation at critical speeds.
These output frequencies can be programmed in parameters 217 through 220.
In this parameter, Frequency Bypass, Bandwidth, the width of the frequency to be bypassed is defined.
The choice of preset references is made by activating terminals 16, 17, 29, 32 or 33, as shown in the table below.
Terminal 17/29/33 Terminal 16/29/32
preset reference msb preset reference lsb
0 0 Preset reference 1 0 1 Preset reference 2 1 0 Preset reference 3 1 1 Preset reference 4
Description of choice:
Set the required preset reference(s) that is/are to be used.
215 Current Limit (CURRENT LIMIT) Value:
0.1 to 1.1 x rated current Depends on the unit
Function:
This is where the maximum output current is set. If the motor attempts to draw more than this amount of current, the drive will reduce its output frequency until the current is less than or equal to the current limit value.
The factory setting corresponds to the rated output current. If the current limit is to be used as motor protection, the rated motor current must be set. If the current limit is set within the range of 1.0 to 1.1 times the rated output current of the drive, the drive can only handle current greater than its rated output intermittently. After the load has been higher than rated output current limit, it must be reduced to a level that is lower than the rated current of the drive for a period of time.
Description of choice:
The bypass bandwidth is equal to the programmed bandwidth frequency. This bandwidth will be centered around each bypass frequency.
217 Frequency Bypass 1 (BYPASS FREQ. 1) 218 Frequency Bypass 2 (BYPASS FREQ. 2) 219 Frequency Bypass 3 (BYPASS FREQ. 3) 220 Frequency Bypass 4 (BYPASS FREQ. 4) Value:
0 to 120 or 1000 HZ 120.0 Hz The frequency range depends on the selection made in parameter 200, Output Frequency Range.
Function:
Some systems require that some output frequencies be avoided because of mechanical resonance problems in the system.
Description of choice:
Enter the frequencies to be avoided. See also parameter 216, Frequency Bypass, Bandwidth.
Note that if the current limit is set to less than the maximum value of the drive, acceleration torque is reduced correspondingly.
Description of choice:
Set the required maximum output current.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
45
Warning Functions
The warning functions in parameters 221 through 228 are not active during ramp-up after a Start command, ramp down after a Stop command, or while stopped. The warning functions are activated when the output frequency has reached the resulting reference.
The signal outputs can be programmed to generate a warning signal via terminal 42 or 45 and via the relay outputs.
The reference limits in parameter 226, Warning: High Reference and parameter 227, Warning: Low Reference are only active when remote reference has been selected.
221 Warning: Low Current (WARN. LOW CURR) Value:
0.0 to parameter 222 Warning: High current 0.0 A
222 Warning: High Current (WARN. HIGH CURR) Value:
Parameter 221 to rated current
Rated current
Function:
If the motor current is above the limit programmed in this parameter, the display shows a flashing CURRENT HIGH.
Description of choice:
The upper signal limit of the motor frequency must be programmed within the normal working range of the drive. See the drawing at parameter 221, Warning: Low Current.
223 Warning: Low Frequency
(WARN. LOW FREQ)
Value:
0.0 to parameter 224 0.0 Hz
Function:
When the motor current is below the limit programmed in this parameter, the display shows a flashing CURRENT LOW, provided Warning has been selected in parameter 409, Function in Case of No Load. The drive will trip if parameter 409 has been selected as Trip. This can be used to indicate when a belt between the motor and the driven load is broken.
Description of choice:
The lower signal limit must be programmed within the normal working range of the drive.
Function:
If the output frequency is below the limit programmed in this parameter, the display will show a flashing F OUT < FLOW.
Description of choice:
The lower signal limit of the motor frequency must be programmed within the normal working range of the drive. See drawing at parameter 221 Warning: Low current.
224 Warning: High Frequency
(WARN. HIGH FREQ.)
Value:
Par. 200 Output frequency range = 0 to 120 Hz parameter 223 - 120 Hz 120.0 Hz Par. 200 Output frequency range = 0 to 1000 Hz parameter 223 - 1000 Hz 120.0 Hz
Function:
If the output frequency is above the limit programmed in this parameter, the display will show a flashing F OUT > F HIGH
Description of choice:
The higher signal limit of the motor frequency must be programmed within the normal working range of the drive. See the drawing at parameter 221, Warning: Low Current.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
46
225 Warning: Low Reference
(WARN. LOW REF)
Value:
-999,999.999 - High Reference (par. 226) -999,999.999 Hz
Function:
When the total remote reference is less than the limit programmed in this parameter, the display shows a flashing REF. < REF . LOW
The reference limits in parameter 226, Warning: High Reference and parameter 225, Warning: Low Reference are only active when remote reference has been selected.
In Open Loop, the unit for the reference is Hz, while in Closed Loop the unit is programmed in parameter 415, Process Units.
227 Warning: Low Feedback
(WARN .LOW FDBK)
Value:
-999,999.999 to High Feedback (parameter 228) -999,999.999
Function:
If the feedback signal is below the limit of Low Feedback programmed in this parameter, the display will flash FEEDBACK < FOB LOW.
The unit for feedback is programmed in parameter 415, Process Units.
Description of choice:
Set the desired value within the feedback range, parameter 413, Minimum Feedback, and parameter 414, Maximum Feedback.
Description of choice:
When parameter 100, Configuration, has been programmed for Open Loop, the lower signal limit of the reference must be programmed within
the normal working range of the drive. If parameter 100 is pro­grammed as Closed Loop, Low Reference must be within the reference range programmed in parameters 204 and 205.
226 Warning: High Reference
(WARN. HIGH REF)
Value:
Reference Low (par. 225) to 999,999.999 -999,999.999 Hz
Function:
If the resulting reference is below the limit programmed in this param­eter, the display flashes REF. > REF . HIGH.,
The reference limits in parameter 226 Warning: High Reference and parameter 225 Warning: Low Reference are only active when remote reference has been selected.
In Open Loop, the unit for the reference is Hz, while in Closed Loop the unit is programmed in parameter 415, Process Units.
Description of choice:
The high reference warning must be programmed within the normal working range of the drive, provided parameter 100 Configuration has been programmed for Open Loop. If parameter 100 has been programmed for Closed Loop, Reference High must be within the reference range programmed in parameters 204 and 205.
228 Warning: High Feedback
(WARN. HIGH FDBK)
Value:
Low Feedback (parameter 227) to 999,999.999
999,999.999
Function:
If the feedback signal is above the limit programmed in this parameter, the display will show a flashing FEEDBACK > FOB HIGH.
The unit for feedback is programmed in parameter 415, Process Units.
Description of choice:
Set the required value within the feedback range, parameter 413, Minimum Feedback, and parameter 414, Maximum Feedback.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
47
Inputs and Outputs Parameters 300 through 328
In this parameter group, the functions of the drive input and output terminals are defined. The digital inputs are through terminals 16, 17, 18, 19, 27, 32 and 33. Inputs are programmed by parameters 300 through 307. The table below shows the functions available for input.
Digital inputs require a signal of 0 or 24 VDC. A signal lower than 5 VDC is a logic ‘0’, while a signal higher than 10 VDC is a logic ‘1’.
The terminals for the digital inputs can be connected to the internal 24 VDC supply through terminals 12 and 13, or an external 24 VDC supply can be connected.
The drawings at the right show one setup using the internal 24 VDC supply and one setup using an external 24 VDC supply.
Digital Inputs Terminal No. 16 17 18 19 27 29 32 33
Parameter 300 301 302 303 304 305 306 307
Value:
No function (NO OPERATION) [0] [0] [0] [0] [0] [0] [0] Reset (RESET) [1] [1] [1] [1] [1] Coasting stop, inverse (COAST INVERSE) [0] Reset and coasting stop, inverse (RESET & COAST INVERSE) [2] Start (START) ✭[1] Reversing (REVERSE) ✭ [1] Reversing and start (START REVERSE) [2] DC-braking, inverse (DC BRAKE INVERSE) [3] [1] Safety interlock (SAFETY INTERLOCK) ✭[2] Freeze reference (FREEZE REFERENCE) [2] [2] [2] [3] [2] Freeze output (FREEZE OUTPUT) [3] [3] [3] [4] [3] Selection of Setup, lsb (SETUP SELECT LSB) [4] [4] [5] Selection of Setup, msb (SETUP SELECT MSB) [4] [5] [4] Preset reference, on (PRESET REF. ON) [5] [5] [6] [6] [5] Preset reference, lsb (PRESET REF. LSB) [6] [7] [7] Preset reference, msb (PRESET REF. MSB) [6] [8] [6] Speed down (SPEED DOWN) [7] [9] [7] Speed up (SPEED UP) [7] [10] [8] Start enabled (RUN PERMISSIVE) [8] [8] [11] [9] [8] Jog (JOG) [9] [9] [12] [10] [9] Data change lock (PROGRAMMING LOCK) [10] [10] [13] [11] [10] Pulse reference (PULSE REFERENCE) [11] [14] Pulse feedback (PULSE FEEDBACK) [11] Hand start (HAND START) [11] [12] [15] [12] [12] Auto start (AUTOSTART) [12] [13] [16] [13] [13]
Switch 4 is used for separating the common potential of the internal 24 VDC supply from the common potential of an external 24 VDC supply. Switch 4 is the DIP switch on the far right of the group of DIP switches located on the lower right of the control card, just above the control terminals.
When Switch 4 is in the OFF position, the external 24 VDC supply is galvanically isolated from the drive.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
48
Function:
WARNING
!
In parameters 300 through 307, Digital Inputs, the functions of terminals 16 through 33 are selected.
These options are shown in the table on the previous page.
Description of choice:
No Function is selected if the drive is not to react to signals transmitted to the terminal.
Reset allows reset of the drive after a resettable fault. Not all faults can be reset without removing and reapplying the input power. Faults that require the removal of input power are called trip lock faults. See “List of Warnings and Alarms” table in the back of this manual.
Coasting Stop, Inverse is used to release the motor immediately by turning off the output transistors. The motor will coast freely to a stop. Logic ‘0’ implements coasting to a stop.
Reset and Coasting Stop, Inverse is used for activating coasting stop at the same time as reset. Logic ‘0’ implements coasting stop and reset.
Freeze Reference freezes the present reference. The frozen reference can only be changed by means of Speed Up or Speed Down. The frozen reference is saved after a stop command and when power is removed.
Freeze Output freezes the present output frequency. The frozen output frequency can now only be changed by means of Speed Up or Speed Down.
If
Freeze Output
stopped via terminal 18.
T o stop the drive when Freeze Output is active, one of the four methods listed below must be used.
- Turn off the Freeze Output function and perform a normal stop.
- Press the keypad Off/Stop key.
- Remove the control voltage to terminal 27.
- If terminal 19 is programmed in prameter 303 for DC Brake Inverse, remove the control voltage to it.
is active, the drive cannot be
DC Braking, Inverse is used for stopping the motor by energizing it with a DC voltage for a given time, as set by parameters 114 and 1 15. Logic ‘0’ implements DC braking. See the DC braking parameters.
Safety Interlock is the same as Coasting Stop, Inverse, except Safety Interlock generates an alarm message on the display when terminal 27
is logic ‘0’. The alarm message will also be active through digital outputs 42 and 45 and relay outputs 1 and 2, if programmed for Safety Interlock.
WARNING
!
Do not choose software version 1.03. See parameter 624 to determine software version of drive.
Start is selected for a remote Start/Stop command. Logic ‘1’ = Start. Logic ‘0’ = Stop.
Reversing is used for changing the direction of rotation of the motor . Logic ‘0’ is for forward. Logic ‘1’ is for reverse. The drive can be safely reversed while it is driving the motor. The reversing signal only changes the direction of rotation, it does not activate the start function. It is not active in Closed Loop mode.
Reversing and Start is used for Start/Stop and reversing using the same signal. A start signal through terminal 18 starts the drive in the forward directrion. If both terminal 18 and a reversing and start terminal are given a logic ‘1’ at the same time, the drive will not start. It is not active in Closed Loop.
Safety Intelock
for drives with
Selection of Setup, Lsb* and Selection of Setup, Msb** enables digital selection of the four possible setups. T o enable this, parameter 002 Active Setup must be set to Multi Setup.
Setup, Msb Setup, Lsb Setup 1 0 0 Setup 2 0 1 Setup 3 1 0 Setup 4 1 1
*Lsb - Least significant bit. **Msb - Most significant bit. Preset Reference, on is used for switching between remote controlled
reference and preset reference. This assumes that Remote/preset has been selected in parameter 210, Reference Type. Logic ‘0’ = remote controlled references active; logic ‘1’ = one of the four preset refer­ences is active in accordance with the table below.
Preset Reference, Lsb and Preset reference, Msb enables a choice of one of the four preset references, in accordance with the table below.
Preset ref. msb Preset ref. lsb Preset ref. 1 0 0 Preset ref. 2 0 1 Preset ref. 3 1 0 Preset ref. 4 1 1
Speed Up and Speed Down are selected if digital control of the up/ down speed is desired. This function is only active if Freeze Reference or Freeze Output has been selected.
49
As long as there is a logic ‘1’ on the terminal selected for Speed Up, the reference or the output frequency will increase by the Ramp-up Time set in parameter 206.
As long as there is a logic ‘1’ on the terminal selected for Speed Down, the reference or the output frequency will decrease by the Ramp-down Time set in parameter 207.
Pulses (logic ‘1’ minimum high for 3 ms and a minimum pause of 3 ms) will lead to a change of speed of 0.1% (reference) or 0.1 Hz (output frequency).
Example:
Terminal Terminal Freeze ref./
(16) (17) Freeze output No speed change 0 0 1 Speed down 0 1 1 Speed up 1 0 1 Speed down 1 1 1
The speed reference frozen through the control panel can be changed even if the drive has stopped. In addition, the frozen reference will be retained in memory after power interruption.
Run Permissive. Run Permissive is used to require a second “run permission” signal in addition to the normal run command, either in Hand or Auto mode. When a run command alone is given, the display will show RUN REQ., but the drive will not start. The drive can also indicate that a run has been requested through one of the transistorized or relay outputs. When, in addition to the run command, a logic ‘1’ is applied to the Run Permissive terminal, the drive will run. If more than one terminal is programmed for Run Permissive, a logic ‘1’ at any of these terminals will allow the drive to run.
Pulse reference is selected if the frequency of a pulse train is to be used as a reference signal. 0 Hz corresponds to parameter 204,
Minimum Reference. The frequency set in parameter 327, Pulse Reference, Maximum Frequency corresponds to parameter 205 Maximum Reference.
Pulse feedback is selected if the frequency of a pulse train is to be used as a feedback signal. Parameter 328, Pulse Feedback, Maximum Frequency is the pulse frequency that corresponds to maximum feedback.
Hand start is selected if an external signal is used to switch the drive to Hand mode. A logic ‘1’ (Hand Start active) will start the motor. A logic ‘0’ will stop the motor. The drive will then be in OFF/STOP mode, unless there is an active Auto Start signal from an external source. Programming one of the digital inputs for Hand Start will disable the LCP Hand Start and Auto Start keys.
DANGER
!
Active puts can cause drive to start unexpectedly. Remove power from drive before servicing driven equipment.
Auto start is selected if an external signal is sent to switch the drive to Auto mode. When a start signal is active on the control terminals or the serial communication port, the drive will start the motor. If Auto Start and
Hand Start are active at the same time on the control terminals, Auto Start will have the higher priority. If Auto Start and Hand Start are not
active, the motor will stop and the drive will then be in the OFF/STOP mode. Programming one of the digital inputs for Hand Start will disable the LCP Hand Start and Auto Start keys.
Hand
and
Auto
signals from digital in-
Jog is used to start the drive and run it at the frequency set in parameter 209, Jog Frequency. Jog is active in both Hand and Auto mode.
Jog is not active if a stop command has been given through the keypad or terminal 27.
Data change lock is selected if changes to parameters are not to be made via the control panel. It is be possible to change parameters through the serial bus.
50
Analog Inputs
Two analog inputs for voltage signals, terminals 53 and 54, and an analog input for current, terminal 60, are provided for reference and feedback signals. A thermistor can be connected to the voltage inputs, terminals 53 or 54.
The two analog voltage inputs can be scaled over the range of 0 to 10 V DC. The current input can be scaled over the range of 0 to 20 mA.
The table below shows the possible analog input programming. Parameter 317, Time Out, and Parameter 318, Function After Time
Out, allow activation of a time-out function on all analog inputs. If the signal value of the reference or feedback signal connected to one of the analog input terminals drops below 50% of the minimum scaling, the function set in parameter 318, Function After Time Out, will be activated after the time-out set in parameter 317.
308 Terminal 53, Analog Input Voltage (A1 [V] 53 FUNCT.) Function:
This parameter is used to select the required function to be linked to terminal 53.
Feedback. If a feedback signal is connected, a voltage input may be connected to either terminal 53 or 54, or a current input conected to terminal 60. If a two zone PID control is used, the feedback signals must be voltage inputs and applied to terminals 53 and 54. See Feedback Handling.
Thermistor. Selected if a thermistor in the motor stops the drive in case of motor overtemperature. The cutout value is 3 kohm. A Klixon thermal switch may also be connected to this input. If parallel sensors are used, the thermistors/thermal switches can be connected in series. The drive will shut down when the total resistance exceeds 3 kohms.
Parameter 117, Motor Thermal Protection, must be programmed for Thermal Warning or Thermistor Trip, and the thermistor must be inserted between terminal 53 or 54, analog voltage input, and terminal 50, 10 V supply.
Description of choice:
No operation. Selected if the drive is not to react to signals connected to the terminal.
Reference. Selected to enable change of reference by means of an analog reference signal. If reference signals are connected to several inputs, these reference signals will be summed.
Analog Inputs Terminal Number 53 (Voltage) 54 (Voltage) 60 (Current)
Parameter 308 311 314
Value:
No operation (NO OPERATION) ★[0] ★[0] [0] Reference (REFERENCE [1] [1] [1] Feedback (FEEDBACK) [2] [2] [2] Thermistor (THERMISTOR) [3] [3]
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
51
309 Terminal 53, Minimum Scaling
(AI 53 SCALE LOW)
Value:
0.0 to 10.0 V 0.0 V
312 Terminal 54, Minimum Scaling
(AI 54 SCALE LOW)
Value:
0.0 to 10.0 V 0.0 V
Function:
This parameter is used for setting the signal value that corresponds to the minimum reference or the minimum feedback, parameter 204,
Minimum Reference, or parameter 413, Minimum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage losses in long signal lines should be compensated for. If the time out functions in parameter 317, Time Out, and parameter 318, Function After Time Out, are to be used, the value must be set to > 1 V.
310 Terminal 53, Maximum Scaling
(AI 53 SCALE HIGH)
Value:
0.0 to 10.0 V 10.0 V
Function:
This parameter is used to set the signal value that corresponds to the maximum reference value or the maximum feedback, parameter 205,
Maximum Reference, or parameter 414, Maximum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage losses in long signal lines should be
compensated for.
311 Terminal 54, Analog Input Voltage
(AI [V] 54 FUNCT.)
Value:
See the description of parameter 308. No operation
Function:
This parameter selects the function of terminal 54. The input signal is scaled by parameter 312, T erminal 54, Minimum
Scaling, and by parameter 313, T erminal 54, Maximum Scaling.
Description of choice:
See description of parameter 308.
Function:
This parameter is used to set the signal value that corresponds to the minimum reference value or the minimum feedback, parameter 204,
Minimum Reference, and parameter 413, Minimum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage losses in long signal lines should be compensated for.
If the time out function is to be applied, parameter 317, Time Out, and parameter 318, Function After Time Out, the value must be set to > 1 V.
313 Terminal 54, Maximum Scaling
(AI 54 SCALE HIGH)
Value:
0.0 to 10.0 V 10.0 V
Function:
This parameter is used to set the signal value that corresponds to the maximum reference value or the maximum feedback, parameter 205,
Maximum Reference, or parameter 414, Maximum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required voltage value. For reasons of accuracy, voltage losses in long signal lines should be compensated for.
314 Terminal 60, Analog Input Current
(AI [mA] 60 FUNCT.)
Value:
See description of parameter 308. Reference
Function:
This parameter selects the function of terminal 60. Scaling of the input signal is set by parameter 315, T erminal 60,
Minimum Scaling, and by parameter 316, T erminal 60, Maximum Scaling.
Description of choice:
See description of parameter 308, T erminal 53, Analog Input V oltage.
For reasons of accuracy, voltage losses in long signal lines should be compensated for.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
52
315 Terminal 60, Minimum Scaling
(AI 60 SCALE LOW)
Value:
0.0 to 20.0 mA 4.0 mA
Function:
This parameter determines the signal value that corresponds to the minimum reference or the minimum feedback, parameter 204 Minimum
Reference, parameter 413, Minimum Feedback. See Reference Handling or Feedback Handling.
Description of choice:
Set the required current value. If the time-out function is to be used, parameter 317, Time Out, and
parameter 318, Function After Time Out, the value must be set to > 2 mA.
316 Terminal 60, Maximum Scaling
(AI 60 SCALE HIGH)
Value:
0.0 to 20.0 mA 20.0 mA
Function:
This parameter determines the signal value that corresponds to the maximum reference or maximum feedback, parameter 205, Maximum
Reference V alue, or parameter 414, Maximum Feedback. See Reference Handling or Feedback Handling.
317 Time Out (LIVE ZERO TIME) Value:
1 to 99 sec. 10 sec.
Function:
If the signal value of the reference or feedback signal connected to one of the input terminals 53, 54 or 60 drops to below 50% of the minimum scaling for a longer period than the Live Zero time, the function selected in parameter 318, Function After Time Out, will be activated.
This function will only be active if, in parameter 309 or 312, a value has been selected for T erminals 53 and 54, Minimum Scaling, that exceeds 1 V , or if, in parameter 315, Terminal 60, Minimum Scaling, a value has been selected that exceeds 2 mA.
Description of choice:
Set the desired time.
318 Function After Time Out (LIVE ZERO FUNCT.) Value:
Off (NO FUNCTION) [0]
Freeze output frequency (FREEZE OUTPUT FREQ.) [1] Stop (STOP) [2] Jog (JOG FREQUENCY) [3] Max. output frequency (MAX FREQUENCY) [4] Stop and trip (STOP AND TRIP) [5]
Description of choice:
Set the desired current value.
Function:
This is where to select the function to be activated after the end of the time-out period, parameter 317, Time Out.
If a time-out function occurs at the same time as a bus time-out function, parameter 510, Bus Time Interval Function, the time-out function in parameter 318 will be activated.
Description of choice:
The output frequency of the drive can:
- go to minimum (NO FUNCTION)
- be frozen at the present value (FREEZE OUTPUT FREQUENCY)
- stop (STOP)
- run at the jog frequency set in parameter 209 (JOG FREQUENCY)
- run at the maximum frequency set in parameter 202 (MAX. FREQUENCY)
- stop and send an alarm (STOP AND TRIP)
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
53
Analog/Digital Outputs
The two analog/digital outputs available through terminals 42 and 45 can be programmed to show a status or an analog value such as frequency. The status signal is a 24 VDC output.
For the analog output, there is a choice of three types of output signal: 0 to 20 mA, 4 to 20 mA or 0 to 32000 pulses. The pulse rate is set by parameter 322, T erminal 45, Output, Pulse Scaling.
See the Electrical Installation, Control T erminals section of this manual for the ratings of these outputs.
.
Analog/Digital OutputsAnalog/Digital Outputs
Analog/Digital Outputs
Analog/Digital OutputsAnalog/Digital Outputs Analog/Digital OutputsAnalog/Digital Outputs
Analog/Digital Outputs
Analog/Digital OutputsAnalog/Digital Outputs
Value: No function (NO FUNCTION) [0] [0] Drive ready (READY) [1] [1] Standby (STAND BY) [2] [2] Running (ENABLED & NO WARNING [3] [3] Running at ref. value (RUNNING AT REFERENCE) [4] [4] Running, no warning (RUNNING NO WARNING) [5] [5] Local reference active (DRIVE IN LOCAL REF.) [6] [6] Remote controlled references active (DRIVE IN REMOTE REF.) [7] [7] Alarm (ALARM) [8] [8] Alarm or warning (ALARM OR WARNING) [9] [9] No alarm (NO ALARM) [10] [10] Current limit (CURRENT LIMIT) [11] [11] Safety interlock (SAFETY INTERLOCK) [12] [12] Start command active (START SIGNAL APPLIED) [13] [13] Reversing (RUNNING IN REVERSE) [14] [14] Thermal warning (THERMAL WARNING) [15] [15] Hand mode active (DRIVE IN HAND MODE) [16] [16] Auto mode active (DRIVE IN AUTO MODE) [17] [17] Sleep mode (SLEEP MODE) [18] [18] Output frequency lower than parameter 223 (F OUT < F LOW) [19] [19] Output frequency higher than parameter 223 (F OUT > F HIGH) [20] [20] Out of frequency range (FREQ. RANGE WARN.) [21] [21] Output current lower than I Output current higher than I Out of current range (CURRENT RANGE WARN) [24] [24] Out of feedback range (FEEDBACK RANGE WARN.) [25] [25] Out of reference range (REFERENCE RANGE WARN) [26] [26] Relay 123 (RELAY 123) [27] [27] Input phase loss (MAINS PHASE LOSS) [28] [28] Output frequency, (OUT. FREQ. 0-20 mA) [29] [29] Output frequency, (OUT. FREQ. 4-20 mA) [30] ★ [30] Output frequency (pulse sequence), (OUT. FREQ. PULSE) [31] [31] External reference, (EXT. REF. 0-20 mA) [32] [32] External reference, (EXTERNAL REF. 4-20 mA) [33] [33] External reference (pulse sequence), (EXTERNAL REF. PULSE) [34] [34] Feedback, (FEEDBACK 0-20 mA) [35] [35] Feedback, (FEEDBACK 4-20 mA) [36] [36] Feedback (pulse sequence), (FEEDBACK PULSE) [37] [37] Output current, 0-20 mA (MOTOR CUR. 0-20mA) [38] [38] Output current, 4-20 mA (MOTOR CUR. 4-20mA) ★ [39] [39] Output current (pulse sequence), 0 - 32000 p (MOTOR CUR PULSE) [40] [40] Output power, 0-20 mA (MOTOR POWER 0-20mA) [41] [41] Output power, 4-20 mA (MOTOR POWER 4-20mA) [42] [42] Output power (pulse sequence), 0- 32000 pulses (MOTOR POWER PULSE) [43] [43]
parameter 221 (I OUT < I LOW) [22] [22]
LOW
parameter 222 (I OUT > I HIGH) [23] [23]
HIGH
TT
erminal Numbererminal Number
T
erminal Number
TT
erminal Numbererminal Number
ParameterParameter
Parameter
ParameterParameter
terminal no.terminal no.
terminal no.
terminal no.terminal no. 4242
42
4242 319319
319
319319
4545
45
4545 321321
321
321321
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
54
Function:
These outputs can act both as digital and analog outputs. If used as a digital output, a 0 or 24 VDC signal is transmitted. If used as an analog output, either a 0 to 20 mA signal, a 4 to 20 mA signal, or a pulse sequence with a frequency of 0 to up to 32,000 Hz is transmitted.
Description of choice:
No function. Selected if this output is always to remain off. Drive ready. The drive’ s control card receives a supply voltage and
the drive is ready for operation.
Output frequency lower than low frequency warning level. The output frequency is lower than the value set in parameter 223,
Warning: Low Frequency .
Output frequency higher than high frequency warning level.
The output frequency is higher than the value set in parameter 224,
Warning: High Frequency .
Out of frequency range. The output frequency is outside the frequency range programmed in parameter 223, Warning: Low Frequency, and 224, Warning: High Frequency.
Stand by . The drive is ready for operation, but no start command has been given. No warning.
Running. The drive is running or the drive is in the sleep mode. Running at ref. value. The drive is at the speed commanded by the
reference. Running, no warning. The drive is running and there are no
warnings. Local reference active. The motor’s speed is being controlled by the
local reference through the keypad. This output will also be on if the drive is set up for loal speed control but the jog function has been activated.
Remote references active. The motor’s speed is being controlled by a remote reference or a preset speed.
Alarm. The drive has been stopped by an alarm. Alarm or warning. An alarm or a waring exists in the drive. No alarm. The drive has no alarm. Current limit. The output current is greater than or equal to the value
programmed in parameter 215, Current Limit. The speed of the drive is being limited to keep the current from increasing.
Output current lower than low current warning level. The output current is lower than the value set in parameter 221, Warning: Low Current. This can be used to indicate a broken belt.
Output current higher than high current warning level. The output current is higher than the value set in parameter 222, Warning:
High Current.
Out of current range. The output current is outside the range programmed in parameter 221, Warning: Low Current, and parameter 222, Warning: High Current.
Out of feedback range. The feedback signal is outside the range programmed in parameter 227 Warning: Low Feedback, and 228
Warning: High feedback.
Out of reference range. The reference is outside the range programmed in parameter 225, Warning: Low Reference, and parameter 226, Warning: High Reference.
Relay 123. This function is only used when a Profibus option card is installed. Input phase loss. An incoming power phase is missing. Output frequency: 0 to 20 mA, 4 to 20 mA, and 0 to 32,000
pulses. An output signal proportional to the output frequency in the
range from 0 to Output Frequency , High Limit, set by parameter 202.
Safety interlock. T erminal 27 has been programmed for Safety Interlock in parameter 304, and no control voltage has been applied to it.
Start command active. The drive is either running or it has received a run command. This is commonly used in conjunction with the drive’s run permissive control.
Reversing. The drive is running in the reverse direction. Thermal warning. The temperature limit of either the motor, the drive,
or a thermistor connected to an analog input has been exceeded.
Hand mode active. The drive is operating in the Hand run/stop mode. Auto mode active. The drive is operating in the Auto run/stop mode. Sleep mode. The drive is stopped because of Sleep Mode.
External reference: 0 to 20 mA, 4 to 20 mA, and 0 to 32,000 pulses. An output signal proportional to the resulting reference value
in the range from Minimum Reference to Maximum Reference, set by parameters 204 and 205.
Feedback Minimum to Feedback Maximum: 0 to 20 mA, 4 to 20 mA, and 0 to 32,000 pulses. An output signal proportional to the
reference value in the range from Minimum Feedback to Maximum Feedback, set by parameters 412 and 413.
Output Current: to 20 mA, 4 to 20 mA, and 0 to 32,000 pulses.
An output signal proportional to the output current in the range from 0 to maximum output current as set by parameter 105, Motor Current.
Output power: 0 to 20 mA, 4 to 20 mA, and 0 to 32,000 pulses.
Generates an output signal proportional to the present output power. 20 mA corresponds to the value set by parameter 102, Motor Power.
55
319 Terminal 42, Output
(AD 42 FUNCTION)
Value:
★ MOTOR CUR. 4-20 mA
See the description of analog/digital outputs.
Function:
This output can function both as a digital and an analog output. When used as a digital output, it generates a 24 V (max. 40 mA) signal. For the analog outputs, there is a choice of 0 to 20 mA, 4 to 20 mA or a pulse sequence.
Description of choice:
See the description of analog/digital outputs.
320 Terminal 42, Output Pulse Scaling
(AO 42 PULS SCALE)
Value:
1 to 32000 Hz 5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value for the maximum pulse frequency.
321 Terminal 45, Output (AO 45 FUNCTION) Value:
OUT. FREQ. 4 - 20 mA
See the description of analog/digital outputs.
Function:
This output can function both as a digital and an analog output. When used as a digital output, it generates a 24 V (max. 40 mA) signal. For the analog outputs, there is a choice of 0 to 20 mA, 4 to 20 mA or a pulse sequence.
Description of choice:
See the description of analog/digital outputs.
322 Terminal 45, Output Pulse Scaling
(AO 45 PULS SCALE)
Value:
1 to 32000 Hz 5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value for the maximum pulse frequency.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
56
Relay Outputs
Relay outputs 1 and 2 can be used to give the present status or a warning.
Relay 1: 1 - 3 normally closed, 1 - 2 normally open Maximum: 240 VAC/DC, 2 A
Relay 2: 4 - 5 normally open Maximum: 30 VAC, 1 A,
Minimum: 24 VAC, 100 mA;
24 VDC, 10 mA The high voltage relay connections are located near the input power and motor terminals.
Relay outputsRelay outputs
Relay outputs
Relay outputsRelay outputs
Value: No function (NO FUNCTION) [0] [0] Ready signal (READY) [1] [1] Waiting for start (ENABLED & NO WARNING) [2] [2] Running (RUNNING) [3] ★ [3] Running at ref. value (RUNNING AT REFERENCE) [4] [4] Running, no warning (RUNNING NO WARNING) [5] [5] Local reference active (DRIVE IN LOCAL REF) [6] [6] Remote controlled references active (DRIVE IN REMOTE REF.) [7] [7] Alarm (ALARM) [8] [8] Alarm or warning (ALARM OR WARNING) [9] [9] No alarm (NO ALARM) ★ [10] [10] Current limit (CURRENT LIMIT) [11] [11] Safety interlock (SAFETY INTERLOCK) [12] [12] Start command active (START SIGNAL APPLIED) [13] [13] Reversing (RUNNING IN REVERSE) [14] [14] Thermal warning (THERMAL WARNING) [15] [15] Hand mode active (DRIVE IN HAND MODE) [16] [16] Auto mode active (DRIVE IN AUTO MODE) [17] [17] Sleep mode (SLEEP MODE) [18] [18] Output frequency lower than low frequency, parameter 223 (F OUT < F LOW) [19] [19] Output frequency higher than high frequency, parameter 224 (F OUT > F HIGH) [20] [20] Out of frequency range (FREQ RANGE WARN.) [21] [21] Output current lower than low current, parameter 221 (I OUT < I LOW) [22] [22] Output current higher than high current, parameter 222 (I OUT > I HIGH) [23] [23] Out of current range (CURRENT RANGE WARN.) [24] [24] Out of feedback range (FEEDBACK RANGE WARN.) [25] [25] Out of reference range (REFERENCE RANGE WARN.) [26] [26] Relay 123 (RELAY 123) [27] [27] Mains fault (MAINS PHASE LOSS) [28] [28] Control word bit 11/12 (CONTROL WORD 11/12) [29] [29]
Relay NumberRelay Number
Relay Number
Relay NumberRelay Number ParameterParameter
Parameter
ParameterParameter
11
1
11 323323
323
323323
The low voltage relay terminals are located on the control wiring terminal strips.
2 2
2
2 2 326326
326
326326
42.5 VDC, 1 A
Description of choice:
See descriptions of [0] through [28] for the Analog/Digital Outputs. Control word bit 11/12. Relay 1 and relay 2 can be activated
through serial communication. Bit 11 activates relay 1 and bit 12 activates relay 2.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
If parameter 556, Bus Time Interval Function, becomes active, relay 1 and relay 2 will cut out if they are activated through serial communica­tion.
57
323 Relay 1, Output Function
(RELAY1 FUNCTION)
Function:
NO ALARM Relay 1 is a form C relay that can be used for status indications and warnings. The relay is activated when the programmed condition occurs.
Time delays for relay 1 are programmed in parameter 324, Relay 1, ON Delay , and parameter 325, Relay 1, OFF Delay.
Description of choice:
See data choice and connections under Relay Outputs.
324 Relay 1, ON Delay
(RELAY1 ON DELAY)
Value:
0 to 600 sec. 0 sec.
Function:
This parameter determines the time delay before the relay activates.
Description of choice:
Enter the desired value.
327 Pulse Reference, Maximum Frequency
(PULSE REF. MAX)
Value:
100 to 65,000 Hz at terminal 29 5,000 Hz 100 to 5,000 Hz at terminal 17
Function:
This parameter is used to set the pulse value that corresponds to the maximum reference, parameter 205, Maximum Reference.
The pulse reference signal can be connected to terminal 17 or 29.
Description of choice:
Set the required maximum pulse reference.
328 Pulse Feedback, Maximum Frequency
(PULSE FDBK MAX.)
Value:
100 to 65,000 Hz at terminal 33 25,000 Hz
Function:
This parameter is used to set the pulse value that corresponds to the maximum feedback value. The pulse feedback signal is connected to terminal 33.
325 Relay 1, OFF Delay
(RELAY1 OFF DELAY)
Value:
0 to 600 sec. 2 sec.
Function:
This parameter determiness the time delay before the relay deacti­vates.
Description of choice:
Enter the desired value.
326 Relay 2, Output Function
(RELAY2 FUNCTION)
Value:
RUNNING See the functions of relay 1.
Function:
Relay 2 is a form A relay that can be used for status indications and warnings. The relay is activated when the programmed condition occurs.
Description of choice:
See data choice and connections under Relay Outputs.
Description of choice:
Set the desired feedback value.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
58
Application Functions
CAUTION
!
Parameters 400 through 427
Special functions of the drive are set up in this parameter group. This includes the proportional, integral,derivitative controller (PID) and setting the sleep mode function.
Additionally, this parameter group includes:
- Reset function
- Flying start
- Interference reduction
- Loss of load
- Carrier frequency
- Selection of process units
400 Reset Function (RESET FUNCTION) Value:
Manual reset (MANUAL RESET) [0] Automatic reset x 1 (AUTOMATIC X 1) [1] Automatic reset x 2 (AUTOMATIC X 2) [2] Automatic reset x 3 (AUTOMATIC X 3) [3] Automatic reset x 4 (AUTOMATIC X 4) [4] Automatic reset x 5 (AUTOMATIC X 5) [5] Automatic reset x 10 (AUTOMA TIC X 10) [6] Automatic reset x 15 (AUTOMA TIC X 15) [7] Automatic reset x 20 (AUTOMA TIC X 20) [8]
Infinite automatic reset (INFINITE AUTOMA TIC) [9]
Function:
This parameter allows a choice of manual or automatic reset after a fault trip. There is also a choice of the number of times the unit will attempt to restart. The time between each attempt is set in parameter 401, Automatic Restart Time.
Description of choice:
If Manual Reset is selected, the Reset key must be pressed or a digital input given to reset the drive.
If auto reset after a fault trip is desired, select one of the Automatic reset choices.
Description of choice:
Set the desired time before each restart attempt.
When parameter 402, motor may turn forward and reverse a few revolutions even with motor stopped. In highly dynamic pumping processes, it is recommended to disable
402 Flying Start (FLYING START) Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1] DC brake and start (DC BRAKE AND STAR T) [3]
Function:
This function makes it possible for the drive to ‘catch’ a rotating motor when the drive is started. The drive will sense the speed of rotation and direction of rotation of the motor and synchronize with it.
This function is active whenever a start command is present. For the drive to catch the spinning motor, the motor speed must be
lower than the maximum frequency set in parameter 202.
Description of choice:
Select Disable if this function is not required. Select Enable if the drive is to ‘catch’ and control a rotating motor . Select DC brake and start if the drive is to brake the motor by means of
the DC brake first, and then start. Ensure that parameters 114 through 116, DC Braking, are set appropriately. Select DC brake and start if the motor may be externally driven at a significant speed in the reverse direction.
For fan applications, factory setting for
Start
setting for
Flying Start
is Enable. For pump applications, factory
Flying Start
Flying Start
function.
NOTE
is Disable.
, is enabled,
Flying
DANGER
!
If any automatic reset choices are selected, motor can start without warning.
401 Automatic Restart Time
(AUTORESTART TIME)
Value:
0 to 600 seconds 10 sec.
Function:
This parameter sets the automatic reset time delay until each reset is attempted. One of the automatic resets must be selected in parameter 400, Reset Function.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
Sleep Mode
Sleep mode makes it possible to stop the drive when the system demand drops below a preset level. When the demand increases to a higher preset level, the drive will restart. A significant amount of energy can be saved using sleep mode. Unlike a set-back time clock, the drive is always available to run when the demand reaches the preset “wake up” level. Sleep mode is not active if Local Reference is selected in parameter 203, Reference Handling, or if the Jog function activates via digital inputs. Sleep mode operates in both Open Loop and Closed Loop.
59
Activate sleep mode in parameter 403, Sleep Mode Timer. In this parameter, set how long the output frequency must be lower than the sleep frequency set in parameter 404, Sleep Frequency , before sleep mode activates. After the set time, the drive will ramp down the motor to a stop, as controlled by parameter 207, Ramp Down Time. If the output frequency needed to meet the system demand rises above the sleep frequency during the timed period, the drive will simply ramp up to the demanded frequency.
When the sleep mode timer expires and the drive is stopped in sleep mode, a theoretical output frequency is calculated based upon the reference signal. When the theoretical output frequency rises above the
frequency set in parameter 405, Wake-up Frequency, the drive will restart the motor and ramp up to the commanded reference.
For closed loop operation, it may be useful to “over satisfy” the system before putting the drive into sleep mode. The boost setpoint parameter provides for this. After the sleep mode timer expires, the drive will reset the set point based on the value in parameter 406, Boost Setpoint. Once this new setpoint is satisfied, the drive enters sleep mode. A setting of 100% in parameter 406, Boost Setpoint, indicates no setpoint boost. Boost setpoint is only active in Closed Loop, selected in parameter 100, Configuration.
403 Sleep Mode Timer (SLEEP MODE TIMER) Value:
0 to 300 seconds (OFF) OFF
Function:
This parameter enables the drive to stop the motor if the load on the system is minimal. The timer starts when the output frequency drops below the frequency set in parameter 404, Sleep Frequency. When the time set has passed, the drive will stop. The drive will restart when the theoretical output frequency exceeds the frequency set in parameter 405, W ake-up Frequency.
Description of choice:
Select OFF if this function is not wanted. Set the amount of time that the drive must run at or below the sleep
frequency before it stops and “goes to sleep.”
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
60
404 Sleep Frequency (SLEEP FREQUENCY) Value:
0.0 to parameter 405, Wake-up Frequency 0.0 Hz
Function:
When the output frequency falls below this set value, the timer set in parameter 403, Sleep Mode Timer, will start. The drive’s speed will follow the reference signal until the timer times out.
Description of choice:
Choose the output frequency at which the drive will activate the sleep mode timer. It is generally best to set SLEEP FREQUENCY equal to the minimum frequency set in parameter 201, Output Frequency Low Limit and parameter 204, Minimum Reference. This is because the sleep mode isn’t active until after the drive output frequency equals the sleep frequency. If the sleep frequency is less than the minimums, the sleep mode cannot activate.
405 Wake-up Frequency (WAKEUP FREQUENCY)
CAUTION
!
Value:
Parameter 404 to parameter 202, Maximum Frequency
60 Hz
Function:
When the theoretical output frequency exceeds the preset value, the drive restarts the motor.
Description of choice:
Set the required frequency.
406 Boost Setpoint (BOOST SETPOINT) Value:
0 to 200 % 100 % of setpoint
Function:
This function can only be used if Closed Loop has been selected in parameter 100, Configuration.
In some systems, it may advantageous to increase the set point of the system before the drive stops the motor. This extends the time that the drive will be stopped and reduces cycling of the motor.
Description of choice:
Set the required Boost Setpoint as a percentage of the resulting reference under normal operation. 100% corresponds to the boost.
407 Switching Frequency (SWITCHING FREQ.) Value:
Depends on the current rating of the unit.
Function:
The value of this parameter determines the maximum switching frequency of the inverter. If Fixed Switching Frequency has been selected in parameter 408, Interference Reduction Method, this will be the fixed inverter switching frequency . Changing the switching frequency may reduce audible noise from the motor. The output frequency of the drive can never be a greater than 1/10 of the switching frequency.
Description of choice:
When the motor is running, the switching frequency may be adjusted by parameter 407, Switching Frequency , until the sound level is as low as possible.
Switching frequencies higher than 4.5 kHz will result in automatic derating of the maximum continuous output current of the drive. The derate is linear from 4.5 kHz to the maximum switching frequency of the drive. At maximum switching frequency, the continuous output current from the drive will be limited to 60% of the rated current. T o avoid possible problems at high load when using a high switching frequency, it may be desirable to select Automatic Switching Frequency Modulation in parameter 408, below.
Switching frequencies higher than 4.5 kHz au­tomatically derate maximum continuous output of drive.
408 Interference Reduction Method
(NOISE REDUCTION)
Value:
ASFM (ASFM) [0]
Fixed switching freq. (FIXED SWITCHING FREQ.) [1] LC filter fitted (LC-FILTER CONNECTED) [2]
Function:
Used to select different methods for reducing the amount of audible noise from the motor.
Description of choice:
ASFM (Automatic Switching Frequency Modulation) uses the maximum switching frequency possible while providing the output required by the load. The load is automatically monitored and the switching frequency set accordingly. The maximum switching frequency is set in parameter 407, Switching Frequency.
Fixed Switching Frequency makes it possible to set a fixed switching frequency . The switching frequency is set in parameter 407, Switching
Frequency . LC-filter fitted is to be used if an LC filter is installed between the drive
and the motor. This prevents excessive heating of the LC filter .
409 Function in Case of No Load
(FUNCT. LOW CURR.)
Value:
Trip (TRIP) [0]
Warning (WARNING) [1]
Function:
This parameter can be used for monitoring the V-belt of a fan or other power transmission component to make sure it has not broken. This function is activated when the output current goes below the current level set in parameter 221, Warning: Low Current. This function is not active during a start until the drive has reached the speed reference. It is also not active while the drive is stopped or while it is decelerating to a stop.
Description of choice:
In the case of a Trip, the drive will stop the motor if the output current drops below the value set in parameter 221.
If Warning is selected, the drive will give a warning if the output current drops below the value set in parameter 221.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
61
410 Function at Input Phase Loss
(MAINS FAILURE)
Value:
Trip (TRIP) ★ [0] Autoderate & Warning (AUTODERA TE & WARNING) [1] Warning (WARNING) [2]
CAUTION
!
At phase loss, the cooling fan of NEMA 12 drives cannot be powered. To avoid overheating, ex­ternal power supply can be connected. Contact Danfoss Graham for further information.
Function:
This determines the action of the drive when one of the incoming power phases is lost. Some action is required to control the level of ripple voltage on the DC bus to avoid damage to the DC bus capacitors.
Description of choice:
At Trip, the drive stops the motor within a few seconds (depending on drive size).
If Autoderate & Warning is selected, the drive will export a warning and reduce the output current to 30% of maximum current to maintain operation.
CAUTION
!
If
Warning
will be reduced when input phase loss persists.
At Warning, only a warning will be exported when an input phase loss occurs, but in severe cases, other extreme conditions might result in a trip.
Drive display will show MAINS PHASE LOSS. For drives with software version 2.0 or later, select Autoderate &
Warning. Set parameter 412, Trip Delay Overcurrent, to OFF.
is selected, life expectancy of drive
411 Function at Drive Overtemperature
(FUNCT. OVERTEMP)
Value:
Trip (TRIP) ★ [0] Autoderate & Warning (AUTODERA TE & W ARNING) [1]
Function:
Select the function to be activated when the drive is exposed to an overtemperature condition.
Description of choice:
At Trip, the drive stops the motor and exports an alarm. At Autoderate & Warning, the drive first reduces the switching
frequency to minimize internal loss. If the overtemperature condition persists, the drive reduces the output current until the heat sink temperature stabalizes. A warning is issued when the function is active.
For drives with software version 2.0 or later, select Autoderate & Warning. Set parameter 412, Trip Delay Overcurrent, to OFF.
412 Trip Delay Overcurrent (OVERLOAD DELAY) Value:
0 to 60 sec. (OFF) 60 sec.
Function:
When the output current has reached the current limit set in parameter 215, Current Limit, and remains there for the time selected in this parameter, the drive will trip.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
62
Description of choice:
Select how long the drive will run in current limit before it trips.
Feedback Signals in Open Loop
In some drives, feedback signals and feedback parameters are only used in closed loop operation. In the VLT 6000, the feedback signals are also active in open loop operation. Although they don’t effect the speed of the drive, they can be displayed on the drive’s meters. Parameters 227 and 228 can set high and low limits for the feedback signals, which can activate warnings.
For open or closed loop operation, the feedback signal is scaled in parameters 413 and 414 Minimum and Maximum Feedback, and the unit displayed is chosen in parameter 415, Process Units.
413 Minimum Feedback (MIN. FEEDBACK) Value:
-999,999.999 to Maximum Feedback, Parameter 414 0.000
Function:
Parameters 413 Minimum Feedback and 414 Maximum Feedback, are used to scale the feedback signal.
Description of choice:
Set the value to be shown on the display when the feedbck signal is at its minimum value.
415 Units Relating to Closed Loop
(REF. / FDBK. UNIT)
Value:
No unit [0] °C [21]
% [1] GPM [22]
rpm [2] gal/s [23] ppm [3] gal/min [24] pulse/s [4] gal/h [25] l/s [5] lb/s [26] l/min [6] lb/min [27] l/h [7] lb/h [28] kg/s [8] CFM [29] kg/min [9] ft3/s [30] kg/h [10] ft3/min [31] m3/s [11] ft3/h [32] m3/min [12] ft/s [33] m3/h [13] in wg [34] m/ s [14] ft wg [35] mbar [15] PSI [36] bar [16] lb/in
2
Pa [17] HP [38] kPa [18] °F [39] m wg [19] kW [20]
[37]
414 Maximum Feedback (MAX. FEEDBACK) Value:
Minimum Feedback to 999,999.999 100.000
Function:
See the description of parameter 413, Minimum Feedback.
Description of choice:
Set the value to be shown on the display when the feedback signal is at its maximum.
Function:
Selects the unit shown on the feedback display. The selected unit is used if Reference [unit] or Feedback [unit] has
been selected in one of the parameters 007 through 010, as well as in the Display Mode. It will be the unit for Minimum/Maximum Feedback. In Closed Loop, the unit is also used as the unit for Minimum/Maximum Reference and Minimum/Maximum Feedback, as well as Setpoint 1 and Setpoint 2.
Description of choice:
Select the unit for the reference/feedback signal.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
63
PID for Process Regulation
The built-in proportional, integral, derivative (PID) controller in the drive maintains a constant condition (pressure, temperature, flow, etc.) in the system. It adjusts motor speed based upon a reference and/or setpoint and the feedback signal. The PID controller is activated by setting parameter 100, Configuration, to Closed loop.
Reference (Set Point)
In parameter 205, Maximum Reference, the maximum value of the sum of all reference signals is set.
The Minimum Reference, set in parameter 204, indicates the smallest value that the resulting reference can assume.
The reference range cannot exceed the feedback range.
A transmitter supplies the PID controller with a feedback signal from the process to indicate its current state. The type of feedback signal in use depends upon the type of process.
This means that deviations that occur between the reference/setpoint and the actual process state are sensed. Such deviations are compensated for by the PID regulator by adjusting the output frequency as required by the difference (or error) between the reference/setpoint and the feedback signal.
The PID controller in the drive has been designed for use in HVAC applications and to perform a number of specialized functions. Previously, it was necessary for a building management system to handle these special functions by installing extra modules to program the system.
With the VLT 6000, there is no need for extra modules to be installed. Only the reference and/or setpoint and a selected feedback signal need to be programmed. An advanced feature of the VLT 6000 is the drive’ s ability to accept two feedback signals, making two-zone regulation possible.
Voltage drop in long control cables can be compensated for by using the scaling parameters for the analog inputs.
Feedback
The feedback signal must be connected to the drive according to the table below, depending on the type of feedback signal and the settings of the associated parameters listed.
Feedback type Terminal Parameters Pulse 33 307 Voltage 53 or 54 308, 309, 310 or
311, 312, 313 Current 60 314, 315, 316 Bus feedback 1* 68 and 69 537 Bus feedback 2* 68 and 69 538 * The bus feedbacks can only be set by serial communication.
If two analog feedback signals are to be used, they both must be voltage signals.
The Minimum Feedback and Maximum Feedback, parameters 413 and 414, must be set for the feedback signals. The type of process unit for the signals is selected in parameter 415, Process Units.
If multiple Preset References are required, use multiple setups or set them in parameters 211 to 214 Preset Reference. See Reference Handling.
If a current signal is used as a feedback signal, voltage can be used as an analog reference. Use the table below to decide which terminal to use and which parameters to program.
Reference type Terminal Parameters Pulse 17 or 29 301 or 305 Voltage 53 or 54 308, 309, 310 or
311, 312, 313 Current 60 314, 315, 316 Preset reference 211, 212, 213, 214 Setpoints 418, 419 Bus reference * 68 and 69 * The bus reference can only be set by serial communication.
T erminals that are not used should be set to No function.
Inverse Regulation
Normal regulation means that the motor speed increases when the reference/setpoint is higher than the feedback signal. Inverse regula­tion means that the motor speed decreases when the reference/setpoint is higher than the feedback signal. If there is a need for inverse regulation, inverse must be programmed in parameter 420, PID
Normal/Inverse Control.
Anti-Windup
The process controller is factory set with an active anti-windup function. This function ensures that when either a frequency limit or a current limit is reached, the integrator will be reset to zero. If the frequency limit or current limit is cleared, the integrator will turn on again. This function can be disabled in parameter 421, PID Anti-windup.
Start-up Conditions
In some applications, the optimum setting of the process regulator takes a long time to reach. In such cases, a start-up frequency can be entered in parameter 422, PID Start-up Frequency. The drive will ramp directly to this frequency before PID control begins. This avoids control by deviation between the reference/setpoint and the actual state of the process during acceleration. It also avoids overshoot of the process requirement during acceleration due to lag in the feedback signal.
64
Differentiator Gain Limit
The differentiation control reacts to the rate of change of the error between the setpoint and the feedback signal. This is seldom needed for HVAC applications. If the dif ferentiation function becomes too dominant, the differentiation factor can be limited. This is done in parameter 426, PID Differentiator Gain Limit.
Lowpass Filter
Noise on the feedback signal can be reduced by using the built-in lowpass filter. Set a suitable lowpass filter time constant. This time constant determines the cutoff frequency of the filter.
If the lowpass filter has been set to 0.1s, the cut-off frequency will be 10 RAD/sec., corresponding to (10/2 x π) = 1.6 Hz. This means that any noise on the feedback signal whose frequency is greater than 1.6 Hz will be filtered out. Choose a suitable time constant in parameter 427, PID Lowpass Filter Time.
Optimization of the Process Regulator
The basic settings have now been made; all that remains to be done is to optimize the proportional gain, the integration time and, if needed, the differentiation time. These are set by parameters 423, 424 and 425. In most processes, this can be done by following the guidelines below.
1. Start the motor.
2. Set parameter 423, PID Proportional Gain, to 0.3 and increase it until the feedback signal becomes unstable. Then reduce the value until the feedback signal has stabilized. Now lower the proportional gain by about half (40% to 60%).
3. Set parameter 424, PID Integration Time, to 20 seconds and reduce the value until the feedback signal becomes unstable. Increase the integration time until the feedback signal stabilizes. Now increase the integration time from 15% to 50%.
4. Parameter 425, PID Differentiation Time, is only used in very fast-acting systems and should be left off for most HV AC applica­tions. When it is used, the typical value is 1/4th the value set in parameter 424, PID Integration Time. The differentiator should only be used when the setting of the proportional gain and the integration time have been fully optimized.
Starting and stopping the drive will produce the necessary error signal in the process to set the PID.
PID Overview
The block diagram below shows reference and setpoint in relation to the feedback signal.
As can be seen, the remote reference is added to Setpoint 1 or Setpoint 2. The setpoint that is active depends on the value of parameter 417, Feedback Function.
Feedback Handling
Handling of the feedback signal(s) can be seen from the block diagram on the next page. The block diagram shows how and by which parameters the feedback handling is affected.
Feedback signals can be voltage, current, pulse and bus feedback signals. In two zone feedback systems, both feedback signals must be voltage signals (terminals 53 and 54). Please note that Feedback 1 consists of bus feedback 1, (parameter 537) added to the feedback signal value of terminal 53. Feedback 2 consists of bus feedback 2, (parameter 538) added to the feedback signal value of terminal 54.
In addition, the drive has an internal calculator capable of converting a pressure signal into a “linear flow” feedback signal. This function is activated in parameter 416, Feedback Conversion.
The parameters for feedback handling are active both in closed and open loop modes. In open loop, the feedback signal can be displayed on one of the drive’s meters and the drive can produce warnings if the feedback signal is beyond the range set in parameters 227, Warning: Low Feedback and 228, Warning: High Feedback.
65
During closed loop operation, there are three ways to use the PID controller and setpoint and feedback signals:
1. 1 setpoint and 1 feedback
2. 1 setpoint and 2 feedbacks
3. 2 setpoints and 2 feedbacks
1 Setpoint and 1 Feedback
1 Setpoint and 2 Feedbacks
As above, parameter 418, Setpoint 1, will be added to the remote reference, if a remote reference is used. Depending on the feedback function selected in parameter 417, Feedback Function, the two feedback signals will be compared to the setpoint. A description of the individual feedback functions is given in parameter 417, Feedback Function.
If only one setpoint and one feedback signal are used, parameter 418, Setpoint 1 will be added to the remote reference, if a remote reference is used. The sum of the remote reference, if any, and Setpoint 1 becomes the resulting reference, which will then be compared with the feedback signal.
2 Setpoints and 2 Feedbacks
Parameter 418, Setpoint 1, is the setpoint for zone 1. Feedback for zone 1 is the sum the feedback signals at terminal 53 and Bus Feedback 1. Parameter 419, Setpoint 2, is the setpoint for zone 2.
Parameter 417, Feedback Function, selects whether the drive will attempt to have both feedback signals be at least equal to their respective setpoints (2 zone min.) or be at most equal to their respec­tive setpoints (2 zone max.).
66
416 Feedback Conversion (FEEDBACK CONV.) Value:
Linear (LINEAR) [0]
Square root (SQUARE ROOT) [1]
Function:
In this parameter, a function is selected which converts a feedback signal from the process to a feedback value that equals the square root of the connected signal.
417 Feedback Function (2 FEEDBACK, CALC.) Value:
Minimum (MINIMUM) [0]
Maximum (MAXIMUM) [1]
Sum (SUM) [2] Difference (DIFFERENCE) [3] Average (A VERAGE) [4 ] Two-zone minimum (2 ZONE MIN) [5] Two-zone maximum (2 ZONE MAX) [6]
This can be used where regulation of a flow is required and the feedback is from a pressure sensor (flow is proportional to the square root of pressure). This conversion makes it possible to set the reference in such a way that there is a linear connection between the reference and the flow required. See diagram below.
Feedback conversion should not be used if two-zone regulation has been selected in parameter 417, Feedback Function.
Description:
If Linear is selected, the feedback signal and the feedback value will be proportional.
If Square root is selected, the drive first takes the sqaure root of the feedback signal.
Function:
This parameter sets the calculation method whenever two feedback signals are used.
Please note that Setpoint 1 is added to the remote reference when Minimum, Maximum, Sum, Difference or Average is selected.
Description of choice:
If Minimum is selected, the drive will compare Feedback 1 with Feed­back 2 and regulate on the basis of the lower feedback value.
Feedback 1 = Sum of parameter 537, Bus Feedback 1, and the
feedback signal value of terminal 53. Feedback 2 = Sum of parameter 538, Bus Feedback 2, and the
feedback signal value of terminal 54. If Maximum is selected, the drive will compare Feedback 1 with
Feedback 2 and regulate on the basis of the higher feedback value. If Sum is selected, the drive will total Feedback 1 with Feedback 2.
Please note that Setpoint 1 will be added to the remote reference. If Difference is selected, the drive will subtract Feedback 1 from
Feedback 2. If Average is selected, the drive will calculate the average of Feedback
1 and Feedback 2. Please note that Setpoint 1 will be added to the remote reference.
If 2-zone Minimum is selected, the drive will calculate the difference between Setpoint 1 and Feedback 1 as well as Setpoint 2 and Feedback 2. The drive will regulate its output speed based on the larger difference. A positive difference, (a setpoint higher than the feedback), is always larger than a negative difference.
If 2-zone Maximum is selected, the drive will calculate the difference between Setpoint 1 and Feedback 1 as well as Setpoint 2 and Feedback 2.
After the calculation, the drive will use the smaller difference. A negative difference (a setpoint lower than the feedback) is always smaller than a positive difference.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
67
418 Setpoint 1 (SETPOINT 1) Value:
Feedback Minimum to Feedback Maximum 0.000
Function:
Setpoint 1 is used to provide the setpoint reference for 1 setpoint PID control and the setpoint for zone 1 in 2 setpoint PID control. External and preset references may be added to its value.
421 PID Anti-windup (PID ANTI WINDUP) Value:
Off (DISABLE) [0]
On (ENABLE) [1]
Function:
It is possible to choose whether the PID controller integrator is to continue to sum the error signal when it is not possible to increase or decrease the output frequency to correct the error.
In open loop, Setpoint 1 should be set to 0, to prevent parameter 417, Feedback Function, from affecting the reference.
See description of parameter 417, Feedback Function.
Description of choice:
Set the required value. The process unit is selected in parameter 415, Process Units.
419 Setpoint 2 (SETPOINT 2) Value:
Feedback minimum to Feedback maximum 0.000
Function:
Setpoint 2 is used to provide the sepoint reference for zone 2 in 2 zone PID. In open loop, Setpoint 2 should be set to 0, to prevent parameter 417, Feedback Function, from affecting the reference.
See description of parameter 417.
Description of choice:
Set the required value. The process unit is selected in parameter 415, Process Units.
420 PID Normal/Inverse Control
(PID NOR/INV. CTRL)
Value:
Normal (NORMAL) [0]
Inverse (INVERSE) [1]
Function:
This determines how the drive’s PID controller responds to an error between the setpoint and feedback.
Used in Closed Loop, (parameter 100).
Description of choice:
If the drive is to reduce the output frequency when the feedback signal increases, select Normal.
Used in Closed Loop, parameter 100.
Description of choice:
The factory setting is On, which means that the error integrator is cleared if either the current limit, the voltage limit or the maximum or minimum frequency has been reached. The integrator will not function again until regulation is possible. Select Off if the integrator is to continue integrating even if it is not possible to correct the error.
422 PID Start-up Frequency
(PID START VALUE)
Value:
Minimum frequency to maximum frequency
(set by parameters 201 and 202) 0 Hz
Function:
The drive will react to a start signal as if in open loop following the acceleration ramp. When the programmed start frequency has been reached, it will change to closed loop operation. This can enable the system to stabilize more quickly.
Used in Closed Loop, parameter 100.
Description of choice:
Set the required start frequency. For software versions prior to 2.0, do not set this frequency between 0.1 and 7.7 Hz.
CAUTION
!
If drive is running in current limit before de­sired start frequency is obtained, PID will not be activated. To avoid this, start frequency must be low enough to ensure that drive does not go into current limit. This can be done during op­eration.
If the drive is to increase the output frequency when the feedback signal increases, select Inverse.
68
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
423 PID Proportional Gain
(PID PROP. GAIN)
Value:
0.00 to 10.00 0.30
426 PID Differentiator Gain Limit
(PID DIFF. GAIN)
Value:
5.0 to 50.0 5.0
Function:
The proportional gain determines the amount of speed correction that the drive will make in response to the size of the error signal.
Used in Closed Loop, parameter 100.
Description of choice:
Quick regulation is obtained by a high gain, but, if the gain is too high, the process may become unstable. See Optimization of the Process Regulator for information on adjusting this.
424 PID Integral Time
(PID INTEGR.TIME)
Value:
0.01 to 9999.00 sec. (OFF) OFF
Function:
The integrator adds the error signal over time and uses this to correct the speed of the drive.
The integration time is the time needed by the integrator to have the same effect as the proportional gain.
Used in Closed Loop parameter 100.
Description of choice:
Fast regulation is obtained by setting a short integration time. However, if this time is too short, the process will overcorrect and become unstable. See Optimization of the Process Regulator for information on adjusting this.
425 PID Differentiation Time
(PID DIFF. TIME)
Value:
0.00 (OFF) to 10.00 sec. OFF
Function:
When the differentiator is ued, fast changes in the error can sometimes cause unstable operation. In these cases it may be useful to limit the contribution of the differentiator.
Used in Closed Loop, parameter 100.
Description of choice:
A lower limit will improve stability, but will reduce the ef fect of the differential.
427 PID Lowpass Filter Time
(PID FILTER TIME)
Value:
0.01 to 10.00 0.01
Function:
Noise on the feedback signal can be reduces by the lowpass filter. Used in Closed Loop, parameter 100.
Description of choice:
Select the desired time constant (t). The cut off frequency equals ½πt. For example, if a time constant of 0.1
s is programmed, the cut off frequency for the lowpass filter will be 1/ (2π (.1)) = 1.6 Hz.
The PID controller will then only respond to changes in the feedback signal whose frequency is less than 1.6 Hz.
Function:
The differentiator responds to the rate of change of the error signal. The quicker the error changes, the greater the response from the
differentiator. Used in Closed Loop, parameter 100.
Description of choice:
Fast regulation can be obtained by means of a long differentiation time. If this time is too long, the process may overshoot. The differentiator is generally set of OFF in HVAC appliations. See Optimization of the Process Regulator for information on adjusting this.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
69
Serial Communication for FC Protocol
ADDRESS 1
MASTER
ADDRESS 2
Protocols
All VLT 6000 drives have an RS-485 port which allows controlling the drive by one of three different serial communication protocols. The three protocols, which can be selected in parameter 500, Protocol, are:
Johnson Controls Metasys N2
Siemens FLN
Danfoss FC protocol
Metasys N2 is a registered trademark of Johnson Controls. FLN is a registered trademark of Siemens.
®
®
ADDRESS 31
REPEATER
ADDRESS 126
Packet Communication
Control and Reply Packets
The packet communication in a master/slave system is controlled by the master. The drives are the slaves. A maximum of 31 VL T 6000 drives can be connected to one master unless a repeater is used. If a repeater is used, a maximum of 126 drives can be connected to one master.
The master continuously sends packets addressed to the slaves and awaits reply packets from them. The response time of the slaves is a maximum of 50 ms.
If Danfoss FC protocol is to be selected, set parameter 500, Protocol to FC protocol .
For further information on operating the drive through N2 or FLN communication, request the N2 or FLN Operator’s Manual from Danfoss Graham.
Only a slave that has received a faultless packet addressed to that slave will respond by sending a reply packet.
Broadcast
When a master sends a packet to all slaves connected to the bus at the same time, it is called a broadcast. In broadcast communication, if the packet has been correctly received, the slaves do not send reply packets to the master.
70
Contents of a Character (byte)
Each transferred character begins with a start bit. Subsequently, eight data-bits are transferred, corresponding to one byte. Each character is sent with a parity bit to produce even parity (i.e., an even number of binary 1’s in the eight data-bits and the parity bit combined). A character ends with a stop bit and therefore consists of a total of eleven bits.
STX LGE ADR DATA BCC
= Time between characters
Packet Length (LGE)
The packet length is the number of data bytes plus address byte ADR plus data control byte BCC.
Start 0 1 234567Even Stop
bit Parity Bit
Packet Buildup with FC Protocol
Each packet begins with a start character (STX) = 02 Hex, followed by a byte that gives the packet length (LGE) and a byte that gives the drive address (ADR). Next a number of data bytes is sent. The size of the packet is variable, depending upon the packet type. The packet ends with a data control byte (BCC).
- - - - - -
- - - - - -
STX LGE ADR Data BCC
Packet Times
The speed of communication between a master and a slave depends on the baud rate. The baud rate of the drive must be the same as the baud rate of the master. Select the baud rate of the drive in parameter 502, Baud Rate.
After a reply packet from the slave, there must be a minimum pause of two characters (22 bits) before the master is able to send another packet. At a baud rate of 9600 baud, there must be a minimum pause of 2.3 msec. After the master has completed the packet, the response time of the slave back to the master is a maximum 20 msec., with a minimum pause of two characters.
Packets with four data bytes have a length of: LGE = 4 + 1 + 1 = 6 bytes
Packets with twelve data bytes have a length of: LGE = 12 + 1 + 1 = 14 bytes
Packets that contain text have a length of 10+n bytes. T en is the fixed characters, while ‘n’ is variable, depending on the length of the text.
Drive Address (ADR)
Two different address formats are used in which the address range of the drive is either from 1 through 31 or from 1 through 126.
1. Address format 1-31
The byte for this address range has the following profile:
76 543210
0
Bit 7 = 0 (address format 1 through 31 active) Bit 6 is not used Bit 5 = 1: Broadcast, address bits (0 through 4), not used Bit 5 = 0: No Broadcast
Pause
time
Master
packet
Response
Slave packet
time
Pause time, minimum: 2 characters Response time, minimum: 2 characters Response time, maximum: 20 msec.
The time between individual characters in a packet is not to exceed two characters, and the packet must be completed within 1.5 times the rated packet time.If the baud rate is 9600 and the packet length is 16 baud, the packet must be completed within 27.5 msec.
Bit 0 through 4 = Drive address 1 through 31
Pause
time
71
1. Address format 1 through 126 The byte for the 1 through 126 address range has the following profile:
76 543210
1
Bit 7 = 1 (address format 1 through 126 active) Bit 0 through 6 = Drive address 1 through 126
Data Character (byte)
The buildup of data blocks depends on the type of packet. There are three types of packets. The packet type applies to both control packets (masterslave) and reply packets (slavemaster).
The three types of packets are the following:
1. Parameter block, used for transferring parameters between master and slave. The data block has 12 bytes (6 words) and also contains the process block.
Bit 0 through 6 = 0 Broadcast
The slave sends the address byte back to the master in the reply packet in unchanged form.
Example: A packet is sent to drive address 22 using address format 1 through
31:
76 543210
00 010110
Data Control Byte (BCC)
The data control byte can be explained by means of an example: Before the first byte of the packet is received, the calculated check sum (BCS) is 0.
7 6543210 0 0000000
PKE IND PWE
Parameter block Process block
HIGH
PWE
PCD1 PCD2
LOW
2. Process block, built up as a data block with four bytes (two words), covering:
- Control word and reference value
(from master to slave)
- Status word and present output frequency
(from slave to master).
PCD 1 PCD 2
Process block
3. T ext block, used for reading or writing texts via the data block.
PKE IND Ch 1 Ch2 Ch n PCD1 PCD2
Text block Process block
After the first byte (02H) has been received: BCS = BCC EXOR “first byte”
(EXOR = exclusive-or gate)
BCS = 0 0 0 0 0 0 0 0
EXOR
“first byte” = 0 0 0 0 0 0 1 0 (02H) BCC = 0 0 0 0 0 0 1 0
Each additional, subsequent byte is gated with BCS EXOR and results
in a new BCC, such as:
BCS = 0 0 0 0 0 0 1 0
EXOR
“second byte” = 1 1 0 1 0 1 1 0 (D6H) BCC = 1 1 0 1 0 1 0 0
72
1. Parameter Bytes
PKE
AK
1514131211109876543210
Parameter
commands
and replies
Not in use
Parameter commands and replies (AK) Bits no. 12-15 are used for transferring parameter commands from master to slave and the slave's processed reply back to the master.
Parameter Commands Master
Bit no. 15 14 13 12 Parameter command
0 0 0 0 No command
0 0 0 1 Read parameter value
0 0 1 0 Write parameter value in RAM
(word)
0 0 1 1 Write parameter value in RAM
(double word)
1 1 0 1 Write parameter value in RAM
and EEPROM (double word)
1 1 1 0 Write parameter value in RAM
and EEPROM (word)
1 1 1 1 Read/write text
IND PWE
PNU
Parameter
number
Slave:
HIGH
PWE
LOW
If the command cannot be carried out, the slave will send this reply (0111) Command cannot be executed and give the following error message in the parameter value (PWE):
(reply 0111) Error message
0 The parameter number used does
not exist
1 There is no write access to the
parameter called
2 The data value exceeds the
parameter limits
3 The used sub-index does not exist
4 The parameter is not of the array type
5 The data type does not match the
parameter called
17 Data change in the parameter called is
not possible in the present mode of the drive. Some parameters can only be changed when the motor has stopped
130 There is no bus access to the
parameter called
131 Data change is not possible because
factory setup has been selected
Parameter Number (PNU)
Bits no. 0-10 are used for transmitting parameter numbers. The function of a given parameter can be seen from the parameter description in the programming section.
Index
PKE
IND
PWE
HIGH
PWE
LOW
Reply slave
Bit no. 15 14 13 12 Reply
0 0 0 0 No reply
0 0 0 1 Parameter value transferred (word)
0 0 1 0 Parameter value transferred
0 1 1 1 Command cannot be executed
1 1 1 1 Text transferred
master:
(double word)
Index is used together with the parameter number for read/write access to parameters with an index, such as parameter 615, Error Code.
Index has 2 bytes - a lowbyte and a highbyte. However, only the lowbyte is used. See the example on the following page.
73
Example - Index:
The first error code (index [1]) in parameter 615, Error code, must be read.
PKE = 1267 Hex (read parameter 615, Error Code). IND = 0001 Hex - Index no. 1.
For a read command, the index must have the following format:
04 00 H
Highbyte
Lowbyte
IND
1267 H 0001 H
PKE
IND
PWE
The drive will respond in the parameter value (PWE) block by means of an error code with a value from 1 through 99. See List of Warnings and Alarms to identify the error code.
Parameter Value (PWE)
PKE
IND
PWE
The parameter value block consists of 2 words (4 bytes). Its value depends on the command given (AK). If the master inquires about a parameter value, the PWE block contains no value.
If a parameter value is to be changed by the master (write), the new value is entered in the PWE block and sent to the slave.
If the slave responds to a parameter requirement (read command), the present parameter value is transferred in the PWE block and returned to the master.
If a parameter does not contain a numerical value, but several data selection options, for example parameter 001, Language, where [0] is English and [4] is Spanish, the data value is selected by writing the value in the PWE block. See the example on the following page.
HIGH
PWE
LOW
The drive has two parameters for which a text can be written. These are parameters 533 and 534, Display T ext. See the description in the parameter section of this manual. In order to write a text via the PWE block, the parameter command (AK) must be set to 'F' Hex.
For a write command, the index must have the following format:
05 00 H
Highbyte
Lowbyte
IND
The following data types are supported by the drive:
Data type Description
3 Integer 16 4 Integer 32 5 Unsigned 8 6 Unsigned 16 7 Unsigned 32 9 Text string
Unsigned means there is no sign included in the packet.
Through serial communication, it is only possible to read parameters with data type 9 (text string). In VLT 6000 drives, parameters 621 through 631, Nameplate Data are data type 9. For example, it is possible in parameter 621, Unit Type, to read the unit size and input voltage range.
When a text string is transferred (read), the packet length is variable, since the texts have different lengths. The packet length is stated in the 2nd byte of the packet, called LGE.
In order to read a text via the PWE block, the parameter command (AK) must be set to ‘F’ Hex.
The index character is used to indicate whether the command in question is a read or write command.
74
Example - Write a parameter value:
Example - Read a parameter value:
Parameter 202, Output Frequency , High Limit, is to be changed to 100 Hz. This value must be remembered after a power failure, so it is written in EEPROM.
PK E = E0CA Hex - Write to parameter 202, Output Frequency,
High Limit
IND = 0000 Hex PWE PWE
= 0000 Hex
HIGH
= 03E8 Hex - Data value 1000, corresponding to 100 Hz,
LOW
see Conversion .
E0CA H 0000 H 0000 H 03E8 H
PKE
IND
PWE
HIGH
PWE
LOW
The reply from the slave to the master will be:
The value in parameter 206, Ramp Up Time, is required. The master sends the following inquiry:
PK E = 10CE Hex - read parameter 206, Ramp Up Time IND = 0000 Hex PWE PWE
= 0000 Hex
HIGH
= 0000 Hex
LOW
10CE H 0000 H 0000 H 0000 H
PKE
IND
PWE
HIGH
PWE
LOW
If the value in parameter 206, Ramp Up Time, is 10 seconds, the reply from the slave to the master will be as follows:
10CE H 0000 H 0000 H 000A H
PKE
IND
PWE
HIGH
PWE
LOW
10CA H 0000 H 0000 H 03E8 H
PKE
IND
PWE
HIGH
PWE
LOW
Example - Choice of a Data Value:
kW is to be selected in parameter 415, Process Units. This value must be remembered after a power failure, so it is written in EEPROM.
PK E = E19F Hex - Write to parameter 415, Process Units IND = 0000 Hex PWE PWE
= 0000 Hex
HIGH
= 0014 Hex - Choose data choice kW [20]
LOW
E19F H 0000 H 0000 H 0014 H
PKE
IND
PWE
HIGH
PWE
LOW
The reply from the slave to the master will be:
119F H 0000 H 0000 H 0014 H
PKE
IND
PWE
HIGH
PWE
LOW
75
Conversion
The different attributes for each parameter can be seen in the section on factory settings.
Since a parameter value can only be transferred as a whole number, a conversion factor must be used to transfer decimals.
Example: Parameter 201: Minimum Frequency, conversion factor 0.1. If
parameter 201 is to be set to 10 Hz, a value of 100 must be trans­ferred, since a conversion factor of 0.1 means that the transferred value will be multiplied by 0.1. A value of 100 will therefore be understood as 10.0.
Process word
The process word block is divided into two blocks each of 16 bits, which always come in the sequence stated.
Conversion Table
Conversion Index Conversion Factor
74 3.6
2 100 110 01
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
PCD1 PCD2
Control packet Control word Reference value (masterslave)
PCD1 PCD2
Control Word per FC Protocol
The control word is used for transmitting commands from a master (PC) to a slave (drive).
MasterSlave
Control
word
1514131211109876543210Bit no.
Bit Bit = 0 Bit =1
00 Preset ref. lsb 01 Preset ref. msb 02 DC braking 03 Coasting stop 04 Quick stop 05 Freeze output frequency 06 Ramp stop Start 07 Reset 08 Jog 09 No function No function 10 Data not valid Data valid 1 1 Activate relay 1 12 Activate relay 2 13 Choice of setup lsb 14 Choice of setup msb 15 Reversing
Serial com.
ref.
Reply packet Status word Given (slavemaster) output frequency
Bit 00/01:
Bits 00 and 01 are used for choosing between the four pre-pro­grammed references parameters 211 through 214, Preset Reference, as shown in the table below.
Preset Reference Parameter Bit 01 Bit 00
121100 2 212 0 1 3 213 1 0 4 214 1 1
NOTE
Parameter 508,
Choice of Preset Reference,
is used to choose how bits 00/01 are to be gated with the corresponding functions of the digital inputs.
Bit 02, DC BRAKE:
Bit 02 = 0 enables DC braking. Set braking current and duration in parameter 114, DC Braking Current, and in parameter 1 15, DC Braking Time.
NOTE
Parameter 504,
DC Brake,
is used for selecting how bit 02 is to be gated with the correspond­ing function of terminal 27.
76
Bit 03, Coasting Stop:
Bit 03 = 0 means that the drive will coast to a stop. Bit 03 = 1 means that the drive is able to start the motor, provided the other conditions for starting are fulfilled.
NOTE
In parameter 503,
Coasting Stop,
the choice is made of how bit 03 is to be gated with the cor­responding function of terminal 27.
Bit 04, Quick Stop:
Bit 04 = 0 leads to a stop in which the motor speed is ramped down to a stop as set in parameter 207, Ramp Down Time.
Bit 05, Freeze Output Frequency:
Bit 05 = 0 means that the given output frequency is frozen. The frozen output frequency can now only be changed with the digital inputs programmed for Speed Up and Speed Down.
NOTE
If
Freeze Output
stopped via Bit 06,
is active, drive cannot be
Start,
or through terminal
18. Drive can only be stopped in following ways:
Bit 03, Coasting Stop
Terminal 27
Bit 02, DC Braking
Terminal 19 programmed for DC Braking
Bit 06, Ramp Stop/Start:
Bit 06 = 0 leads to a stop in which the motor speed is ramped down to stop through parameter 207, Ramp Down Time. Bit 06 = 1 means that the drive is able to start the motor, provided the other conditions for starting are fulfilled.
NOTE
Parameter 505,
Ramp Stop/Start,
Start,
determines how bit 06,
is gated and corresponding
function of terminal 18.
Bit 07, Reset:
Bit 07 = 0 leads to no reset. Bit 07 = 1 means that a trip is reset. Reset is activated on the leading edge of the signal, at the time the signal changes from logic 0 to logic 1.
Bit 08, Jog:
Bit 08 = 1 means that the output frequency is determined by parameter 209, Jog Frequency.
Bit 09, No function:
Bit 09 has no function.
Bit 10, Data Not Valid/Data Valid:
Used for telling the drive whether the control is to be used or ignored. Bit 10 = 0 means that the control word is ignored. Bit 10 = 1 means that the control word is used. This function is relevant because the control word is always contained in the packet, regardless of the type of packet used. Therefore it is possible to disconnect the control word if it is not to be used in connection with updating or reading of parameters.
Bit 11, Relay 1:
Bit 11 = 0 Relay 1 is not activated. Bit 11 = 1 Relay 1 is activated, provided Control Word Bits 1 1/12 has been selected in parameter 323, Relay Outputs.
Bit 12, Relay 2:
Bit 12 = 0 Relay 2 is not activated. Bit 12 = 1 Relay 2 is activated, provided Control Word Bits 1 1/12 has been selected in parameter 326, Relay Outputs.
NOTE
If time-out period set in parameter 556,
Interval Function,
is exceeded, relays 1 and 2
Bus Time
will have voltage removed if activated via se­rial communication.
Bits 13/14, Choice of Setup:
Bits 13 and 14 are used to choose among the four menu setups in accordance with the following table:
Setup Bit 14 Bit 13
100 201 310
411 This function is only possible if Multi Setup has been selected in parameter 004.
NOTE
In parameter 507,
Choice of Setup,
a choice is made of how bits 13/14 are gated with corre­sponding function of digital inputs.
Bit 15, No function/reversing:
Bit 15 = 0 leads to no reversing Bit 15 = 1 leads to reversing In the factory setting, reversing has been selected as digital in parameter 506, Reversing. Bit 15 will only allow reversing, if bus or logic or has been selected, or logic and has been selected and a signal is present at terminal 19.
77
Status Word per FC Protocol
The status word is used to inform the master (e.g., a PC) of the condition of the slave (drive).
SlaveMaster
Status
word
Output
frequency
Bit 06, Not in use:
Bit 06 is not used in the status word.
Bit 07, No warning/warning:
Bit 07 = 0 means there is no warning. Bit 07 = 1 means a warning has occurred.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no.
Bit Bit = 0 Bit =1
00 Trip Control ready 01 Drive ready 02 Stand by 03 No trip Trip 04 Not in use 05 Not in use 06 Not in use 07 No warning Warning 08 Speed reference Speed = reference 09 Local operation Serial comm. control 10 Out of frequency range 1 1 Running 12 No function No function 13 Voltage warning
high/low 14 Current limit 15 Thermal warning
Bit 00, Control Ready:
Bit 00 = 1 The drive is ready for operation. Bit 00 = 0 The drive has tripped.
Bit 01, Drive Ready:
Bit 01 = 1 The drive is ready for operation, but terminal 27 is a logic 0 and/or a coasting command has been received via serial communication.
Bit 02, Standby:
Bit 02 = 1 The drive is able to start the motor when a start command is given.
Bit 03, No Trip/Trip:
Bit 03 = 0 means that the drive is not in an error state. Bit 03 = 1 means that the drive has tripped and needs a reset signal in order for operation to be resumed.
Bit 04, Not in use:
Bit 04 is not used in the status word.
Bit 05, Not in use:
Bit 05 is not used in the status word.
Bit 08, Speed
≠≠
Reference/Speed = Reference:
≠≠
Bit 08 = 0 means that the motor is running, but that the present speed is different from the preset speed reference. This may be the case when the speed is being ramped up or down after a start or stop command. Bit 08 = 1 means that the present motor speed equals the preset speed reference.
Bit 09, Local Operation/Serial Communication Control:
Bit 09 = 0 means that OFF/STOP has been activated on the control unit, or that the drive is in Hand mode. It is not possible to control the drive through serial communication. Bit 09 = 1 means that it is possible to control the drive through serial communication.
Bit 10, Out of Frequency Range:
Bit 10 = 0 if the output frequency is outside the range established by the values in parameter 201, Output Frequency Low Limit, and parameter 202, Output Frequency High Limit. Bit 10 = 1 means that the output frequency is within the limits of those parameters.
Bit 11, Not Running/Running:
Bit 11 = 0 means that there is no output from the drive. Bit 11 = 1 means that the drive has a start signal, or that the output frequency is greater than 0 Hz.
Bit 12, No Function:
Bit 12 has no function.
Bit 13, Voltage Warning High/Low:
Bit 13 = 0 means that there is no voltage warning. Bit 13 = 1 means that the DC voltage of the drive intermediate circuit is too low or too high.
Bit 14, Current Limit:
Bit 14 = 0 means that the output current is less than or equal to the value in parameter 215, Current Limit. Bit 14 = 1 means that the output current is higher than the value in parameter 215, Current Limit, and the drive will trip after the time set in parameter 412, Trip Delay Overcurrent, has passed if the output current is not reduced.
Bit 15, Thermal Warning:
Bit 15 = 0 means there is no thermal warning. Bit 15 = 1 means that the temperature limit has been exceeded either in the motor, in the drive or from a thermistor connected to an analog input.
78
Serial Communication Reference
Present Output Frequency
MasterSlave
Control
word
Serial com.
ref.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no.
The serial communication reference is transmitted to the drive in the form of a 16-bit word. The value is transmitted as whole numbers 0 through ±32767 (±200 %). 16384 (4000 Hex) corresponds to 100 %.
The serial communication reference has the following format: 0 through 16384 (4000 Hex) - 0 through 100% (parameter 204,
Minimum Reference - Par. 205, Maximum Reference). It is possible to change the direction of rotation through the serial
reference. This is done by converting the binary reference value to 2's complement. See example in next column.
SlaveMaster
Status
word
Output
frequency
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no. The value of the output frequency of the drive at any given time is
transmitted as a 16-bit word. The value is transmitted in the form of whole numbers 0 through ±32767 (±200%).
16384 (4000 Hex) corresponds to 100%. The output frequency has the following format:
0 through 16384 (4000 Hex) @ 0 to 100% (Parameter 201,
Output Frequency Low limit - Parameter 202, Output Frequency High Limit).
Example - Status Word and Present Output Frequency:
The master receives a status message from the drive that the
present output frequency is 50% of the output frequency range. Example - Control word and serial communication reference: The drive must receive a start command, and the reference is to be set
to 50% (2000 Hex) of the reference range. Control word = 047F Hex. Start command
Reference = 2000 Hex. 50 % reference 047F H 2000 H
Control word
Reference
The drive is to receive a start command, and the reference is to be set to -50% (-2000 Hex) of the reference range. The reference value is first converted to the first complement; then 1 binary is added to get 2’s complement:
2000 Hex= 0010 0000 0000 0000 binary 1´ complement = 1101 1111 1111 1111 binary
+ 1 binary
2´ complement = 1110 0000 0000 0000 binary Control word = 047F Hex. Start command
Reference = E000 Hex. -50 % reference
Parameter 201, Output Frequency Low Limit = 0 Hz
Parameter 202, Output Frequency High Limit = 60 Hz
Status word = 0F03 Hex. Status message
Output frequency = 2000 Hex. 50% of the frequency range, cor-
responding to 30 Hz.
0F03 H 2000 H
Status word
Output
frequency
047F H E0000 H
Control word
Reference
79
Serial Communication Parameters 500 through 536
This parameter group sets up the drive for serial communication. There is a choice of three protocols: FC (VLT protocol), Johnson
Controls Metasys N2 and Siemens FLN. In order to use serial communication to control the drive, address and baud rate must always be set. In addition to controlling the drive, operational data from the drive including reference, feedback, motor temperature and others can be read through serial communication.
500 Protocol (PROTOCOL) Value:
FC protocol (FC PROTOCOL) [0]
Metasys N2 (METASYS N2) [1] Landis & Staefa FLN (FLN) [2]
Function:
There is a choice of three different protocols.
Description of choice:
Select the required control word protocol.
Description of choice:
The transmission speed of the drive must be set at a value that corresponds to the transmission speed of the master. Parameter 502, Baud Rate, cannot be selected through serial communication; it must be set by the keypad. The data transmission time itself, which is determined by the baud rate selected, is only part of the total communication time.
503 Coasting Stop (COASTING) Value:
Digital input (DIGITAL INPUT) [0] Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
In parameters 503 through 508, a choice can be made to control the drive via the digital inputs and/or by serial communication.
If Digital input is selected, the command can only be carried out through digital input.
If Serial communication is selected, the command can only be carried out through serial communication.
501 Address (ADRESSE) Value:
Parameter 500 Protocol = FC protocol
0 through 126 ★ 1
Parameter 500 Protocol = Metasys N2
1 through 255 1
Parameter 500 Protocol = FLN
0 through 98 1
Function:
In this parameter it is possible to allocate an address in a serial communication network to each drive.
Description of choice:
The individual drive must be given a unique address. If the number of drives exceeds 31, a repeater must be used. Parameter 501, Address, cannot be chosen via serial communication but is set via the keypad.
502 Baud Rate (BAUDRATE) Value:
300 Baud (300 BAUD) [0] 600 Baud (600 BAUD) [1] 1200 Baud (1200 BAUD) [2] 2400 Baud (2400 BAUD) [3] 4800 Baud (4800 BAUD) [4]
9600 Baud (9600 BAUD) [5]
Function:
In this parameter, the speed at which data is transmitted via serial communication is programmed. Baud rate is defined as the number of bits transmitted per second.
If Logic and is selected, the command must be by both serial communi­cation and a digital input.
If Logic or is selected, the command can be made by either digital or serial communication.
Description of choice:
The tables below show whether the motor is running or coasting when Digital Input, Serial Communication, Logic and or Logic or has been selected.
NOTE Terminal 27 and bit 03 of control word are active when logic 0 is selected.
Digital Input Serial Communication
Serial Serial
Term. 27 Comm. Function Term. 27 Comm . Function
0 0 Coasting 0 0 Coasting 0 1 Coasting 0 1 Motor run 1 0 Motor run 1 0 Coasting 1 1 Motor run 1 1 Motor run
Logic and Logic or
Serial Serial
Term. 27 Comm. Function Term. 27 Comm. Function
0 0 Coasting 0 0 Coasting 0 1 Motor run 0 1 Coasting 1 0 Motor run 1 0 Coasting 1 1 Motor run 1 1 Motor run
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
80
504 DC Brake (DC BRAKE) Value:
Digital input (DIGITAL INPUT) [0] Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
505 Start (START) Value:
Digital input (DIGITAL INPUT) [0] Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
See the functional description under parameter 503, Coasting.
Description of choice:
The table below shows when the motor is running and is DC-braking when Digital input, Serial communication, Logic and or Logic or has been selected.
NOTE
DC braking inverse,
through terminals 19 and 27, and bit 03 of the control word, is active when logic 0 is selected.
Digital Input Serial Communication
Term. Serial Term. Serial 19/27 Comm. Function 19/27 Comm. Function
0 0 DC brake 0 0 DC brake 0 1 DC brake 0 1 Motor run 1 0 Motor run 1 0 DC brake 1 1 Motor run 1 1 Motor run
Logic and Logic or
Term. Serial Term. Serial 19/27 Comm. Function 19/27 Comm. Function
0 0 DC brake 0 0 DC brake 0 1 Motor run 0 1 DC brake 1 0 Motor run 1 0 DC brake 1 1 Motor run 1 1 Motor run
Function:
See the functional description under parameter 503 Coasting.
Description of choice:
The table below shows when the motor has stopped and gives the situations in which the drive has a start command when Digital input,
Serial communication, Logic and or Logic or has been selected.
Digital Input Serial Communication
Serial Serial
Term. 18 Comm. Function Term. 18 Comm. Function
0 0 Stop 0 0 Stop 0 1 Stop 0 1 Start 1 0 Start 1 0 Stop 1 1 Start 1 1 Stop
Logic and Logic or
Serial Serial
Term. 18 Comm. Function Term. 18 Comm. Function
0 0 Stop 0 0 Stop 0 1 Stop 0 1 Start 1 0 Stop 1 0 Start 1 1 Start 1 1 Start
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
81
506 Reversing (REVERSING) Value:
Digital input (DIGITAL INPUT) [0]
Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2] Logic or (LOGIC OR) [3]
Function:
See the functional description under parameter, 503 Coasting.
Description of choice:
The table below shows when the motor is running forward and reverse when Digital input, Serial communication, Logic and or Logic or has been selected.
Digital Input Serial Communication
Serial Serial
Term. 19 Comm. Function Term. 19 Comm. Function
0 0 Forward 0 0 Forward 0 1 Forward 0 1 Forward 1 0 Reverse 1 0 Forward 1 1 Reverse 1 1 Reverse
Logic and Logic or
Serial Serial
Term. 19 Comm. Function Term. 19 Comm. Function
0 0 Forward 0 0 Forward 0 1 Forward 0 1 Reverse 1 0 Forward 1 0 Reverse 1 1 Start 1 1 Reverse
507 Selection of Setup (SELECTING OF SETUP) 508 Selection of Preset Reference
(SELECTING OF SPEED)
Value:
Digital input (DIGITAL INPUT) [0] Serial communication (SERIAL PORT) [1] Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
See the functional description under parameter 503 Coasting.
Description of choice:
The table below shows the Setup (parameter 002 Active Setup) that has been selected via Digital input, Serial communication, Logic and or Logic or. The table also shows the preset reference (parameters 211 through 214, Preset reference) that has been selected via Digital
input, Serial communication , Logic and or Logic or.
Digital Input
Bus Bus Setup/Preset Setup/Preset Setup No. Msb L s b Msb Ls b Preset Ref. No.
00 0 0 1 00 0 1 2 00 1 0 3 00 1 1 4 01 0 0 1 01 0 1 2 01 1 0 3 01 1 1 4 10 0 0 1 10 0 1 2 10 1 0 3 10 1 1 3 11 0 0 1 11 0 1 2 11 1 0 3 11 1 1 4
Serial Communication
Bus Bus Setup/Preset Setup/Preset Setup No. Msb L s b Msb Ls b Preset Ref. No.
00 0 0 1 00 0 1 1 00 1 0 1 00 1 1 1 01 0 0 2 01 0 1 2 01 1 0 2 01 1 1 2 10 0 0 3 10 0 1 3 10 1 0 3 10 1 1 3 11 0 0 4 11 0 1 4 11 1 0 4 11 1 1 4
Logic and
Bus Bus Setup/Preset Setup/Preset Setup No. Msb L s b Msb Ls b Preset Ref. No.
00 0 0 1 00 0 1 1 00 1 0 1 00 1 1 1 01 0 0 1 01 0 1 2 01 1 0 1 01 1 1 2 10 0 0 1 10 0 1 1 10 1 0 3 10 1 1 3 11 0 0 1 11 0 1 2 11 1 0 3 11 1 1 4
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
82
Logic or
Bus Bus Setup/Preset Setup/Preset Setup No.
Msb L s b Msb Ls b Preset Ref. No.
00 0 0 1 00 0 1 2 00 1 0 3 00 1 1 4 01 0 0 2 01 0 1 4 01 1 0 2 01 1 1 3 10 0 0 3 10 0 1 4 10 1 0 3 10 1 1 4 11 0 0 4 11 0 1 4 11 1 0 4 11 1 1 4
509 through 532 Data Read-Out
Value:
Parameter Description Display Text Unit
No. Interval
509 Resulting reference (REFERENCE %) % 80 msec. 510 Resulting reference [unit] (REFERENCE [UNIT]) Hz, rpm 80 msec.
51 1 Feedback [unit] (FEEDBACK) Par. 415 80 msec. 512 Frequency [Hz] (FREQUENCY) Hz 80 msec. 513 User-defined readout (CUSTOM READOUT) Hz x scaling 80 msec. 514 Motor current [A] (CURRENT) Amp 80 msec. 515 Power [kW] (POWER KW) kW 80 msec. 516 Power [HP] (POWER HP) HP 80 msec. 517 Motor voltage [V] (MOTOR VOL T) VA C 80 msec. 518 DC link voltage [V] (DC LINK VOLT AGE) VDC 80 msec. 519 Thermal load, motor [%] (MOTOR TEMPERATURE) % 80 msec. 520 Thermal load, VL T [%] (VLT TEMPERATURE) % 80 msec. 521 Digital input (DIGITAL INPUT) Binary 80 msec. 522 T erminal 53, analog input [V] (TERMINAL 53, ANALOG INPUT) Volt 20 msec. 523 T erminal 54, analog input [V] (TERMINAL 54, ANALOG INPUT) Volt 20 msec. 524 T erminal 60, analog input [mA] (TERMINAL 60, ANALOG INPUT) mA 20 msec. 525 Pulse reference [Hz] (PULSE REFERENCE) Hz 20 msec. 526 External reference [%] (EXTERNAL REFERENCE) % 2 0 msec. 527 Status word (STATUS WORD HEX) Hex 20 msec. 528 Heat sink temperature [°C] (HEAT SINK TEMP.) °C 1.2 sec. 529 Alarm word (ALARM WORD, HEX) Hex 20 msec. 530 Control word (VL T CONTROL WORD, HEX) Hex 2 msec. 531 Warning word (WARNING WORD) Hex 20 msec. 532 Extended status word (ST A TUS WORD) Hex 20 msec.
Updating
83
Function:
These parameters can be read through the serial communication port and the display. See also parameters 007 through 010, Display
Readout.
Description of choice:
Resulting Reference, parameter 509 gives a percentage for the resulting reference in the range from Minimum Reference to Maximum
reference. See also Reference Handling. Resulting reference [unit], parameter 510 gives the resulting reference
by means of the unit Hz in Open Loop, parameter 100. In Closed Loop, the reference unit is selected in parameter 415, Units with Closed Loop.
Feedback [unit], parameter 51, gives the resulting feedback value by
means of the unit/scaling selected in parameters 413, 414 and 415. See also Feedback Handling.
Frequency [Hz], parameter 512, gives the output frequency of the drive.
User Defined Read Out, parameter 513, gives a user defined value calculated on the basis of the present output frequency and unit, as well as the scaling in selected in parameter 005, Maximum V alue of User
Defined Read Out. The unit is selected in parameter 006, Unit for User Defined Read Out.
Motor Current [A], parameter 514, gives the motor current in A.
T erminal 53, Analog Input [V], parameter 522, gives the voltage value
of the signal on terminal 53. T erminal 54, Analog Input [V], parameter 523, gives the voltage value
of the signal on terminal 54. T erminal 60, Analog Input [mA], parameter 524, gives the current
value of the signal on terminal 60. Pulse Reference [Hz], parameter 525, gives a pulse frequency in Hz
connected to one of the terminals 17 and 29. External Reference, parameter 526, gives the sum of external
references as a percentage (sum of analog/pulse/serial communication) in the range from Minimum Reference, Ref to Maximum reference.
Status Word, parameter 527, gives the present status word of the drive in hex.
Heat Sink Temperature, parameter 528, gives the present heat sink temperature of the drive.
Alarm Word, parameter 529, gives a hex code for the alarm on the drive.
Control Word, parameter 530, gives the present control word of the drive in hex.
Warning Word, parameter 531, indicates in hex warnings from the drive.
Power [kW], parameter 515, gives the present power provided to the motor in kW.
Power [HP], parameter 516, gives the present power provided to the motor in HP .
Motor Voltage, parameter 517, gives the voltage fed to the motor . DC Link Voltage, parameter 518, gives the intermediate circuit voltage
of the drive. Thermal Load, Motor [%], parameter 519, gives the calculated/
estimated thermal load on the motor. 100% is the trip point. See also parameter 117, Motor Thermal Protection.
Thermal Protection, VL T [%], parameter 520, gives the calculated/ estimated thermal load on the drive. 100% is the trip point.
Digital Input, parameter 521, gives the signal status of the 8 inputs (16, 17, 18, 19, 27, 29, 32 and 33). Input 16 corresponds to the bit to the extreme left. 0 = no signal, 1 = signal connected.
Extended Status Word, parameter 532, indicates in hex code whether there is a warning from the drive.
533 Display Text 1 (DISPLAY TEXT ARRAY 1)
Non-functional.
534 Display Text 2 (DISPLAY TEXT ARRAY 2)
Non-functional.
535 Bus Feedback 1 (BUS FEEDBACK1) Value:
0 through 16384 decimal (0 through 4000 Hex) ★ 0
Function:
Via the serial communication port, this parameter allows writing of a bus feedback value which will then form part of the feedback handling. Bus Feedback 1 will be added to any feedback value registered on terminal
53.
Description of choice:
Write the required bus feedback value via serial communication.
84
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
536 Bus Feedback 2 (BUS FEEDBACK 2) Value:
0 through 16384 decimal (0 through 4000 Hex) ★ 0
Function:
Via serial communication, a bus feedback value can be written in this parameter that will become part of the feedback handling system. Bus Feedback 2 will be added to any feedback value on terminal 54.
Description of choice:
Write the required bus feedback value via the serial communication.
NOTE
Parameters 555,
Time Interval Function, FC Protocol
500,
Protocol.
Bus Time Interval,
and 556,
Bus
are only active when
has been selected in parameter
555 Bus Time Interval (BUS TIME INTERVAL) Value:
1 to 99 sec. 60 sec.
Function:
In this parameter, the maximum time allowed between the receipt of two packets in a row is set. If this time is exceeded, the serial communication is assumed to have stopped and the choice made in parameter 556, Bus Time Interval Function, will be carried out.
Description of choice:
Set the required time.
556 Bus Time Interval Function
(BUS TIME INTERVAL FUNCTION)
Value:
Off (NO FUNCTION) [0]
Freeze output (FREEZE OUTPUT) [1] Stop (STOP) [2] Jogging (JOG FREQUENCY) [3] Max. output frequency (MAX FREQUENCY) [4] Stop and trip (STOP AND TRIP) [5]
Function:
In this parameter, the required reaction from the drive is selected when the time set in parameter 555, Bus Time Interval, has been exceeded.
Description of choice:
The output frequency of the drive can be frozen at the present value, frozen as selected in parameter 211, Preset Reference 1, frozen as selected in parameter 202, Maximum Output Frequency, or stop and show a fault.
560 N2 override release time
(N2 OVER.REL.TIME)
Value:
1 - 65534 (OFF) sec. OFF
Function
The maximum time is set between the receipt of two N2 messages. If the time is exceeded, serial communication is assumed stopped and all points in the N2 point-map which are overridden will be released in the following order:
1. Release analog outputs from point address (NPA) 0 to 255.
2. Release binary outputs from point address (NPA) 0 to 255.
3. Release internal floating points from point address (NPA) 0 to 255.
4. Release internal integer points from point address (NPA) 0 to 255.
5. Release internal byte points from point address (NPA) 0 to 255.
Description of choice:
Set the required time.
565 FLN bus time interval (FLN TIME INTER.) Value:
1 - 65534 sec. 60 sec.
Function
The maximum time is set between the receipt of two FLN messages. If the time is exceeded, serial communication is assumed stopped and the required reaction is set in parameter 566, FLN Bus Time Interval
Function.
Description of choice:
Set the required time.
566 FLN bus time interval function (FLN TIME FUNCT.) Value:
Off (NO FUNCTION) [0]
Freeze output (FREEZE OUTPUT) [1] Stop (STOP) [2] Jogging (JOG FREQUENCY) [3] Max. output frequency (MAX.SPEED) [4] Stop and trip (STOP AND TRIP) [5]
Function
The required reaction from the adjustable frequency drive is selected when the time set in parameter 565, FLN Bus Time Interval, has been exceeded.
Description of choice:
The output frequency of the adjustable frequency drive can be frozen at the present value at any given time, frozen at parameter 211, Preset Reference 1, frozen at parameter 202, Max. Output Frequency, or stop output and show a fault.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
85
Warning Words, Extended Status Word and Alarm Word
Warning Word, Extended Status Word and Alarm Word are shown in hex format on the display. If there is more than one warning or alarm, the sum of the warnings or alarms will be shown.
The descriptions of the Extended Status Words, Warning Words and Alarm Words can be read out via the serial bus in parameter 531, Warning Word; 532, Extended Status Word; and 529, Alarm Word.
Hex Code Extended Status Word
00000001 Overvoltage control active 00000002 Start delay 00000004 Sleep boost active 00000008 Sleep mode active 00000010 Automatic motor adaptation completed 00000020 Automatic motor adaptation running 00000040 Reversing and start 00000080 Ramp operation 00000100 Reversing 00000200 Speed = reference 00000400 Running 00000800 Local reference = 1
Remote controlled reference = 0 00001000 OFF mode = 1 00002000 Auto mode = 0, Hand mode = 1 00004000 Start blocked 00008000 Start blocked signal missing 00010000 Freeze output 00020000 Freeze output blocked 00040000 Jogging 00080000 Jog blocked 00100000 Stand by 00200000 Stop 00400000 DC stop 00800000 Drive ready 01000000 Relay 123 active 02000000 Drive ready 04000000 Control ready 08000000 Start prevented 10000000 Profibus OFF3 active 20000000 Profibus OFF2 active 40000000 Profibus OFF1 active 80000000 Reserved
86
Hex Code Warning Word
00000001 Reference high 00000002 Fault in EEprom on control card 00000004 Fault in EEprom on power card 00000008 HPFB bus timeout 00000010 Serial communication timeout 00000020 Overcurrent 00000040 Current limit 00000080 Motor thermistor 00000100 Motor overtemperature 00000200 Inverter overtemperature 00000400 Undervoltage 00000800 Overvoltage 00001000 Voltage warning low 00002000 Voltage warning high 00004000 Mains phase fault 00008000 Live zero fault 00010000 Under 10 Volt (terminal 50) 00020000 Reference low 00040000 Feedback high 00080000 Feedback low 00100000 Output current high 00200000 Out of frequency range 00400000 Profibus communication fault 00800000 Output current low 01000000 Output frequency high 02000000 Output frequency low 04000000 AMA - motor too small 08000000 AMA - motor too big 10000000 AMA - check par. 102, 103, 105 20000000 AMA - check par. 102, 104, 106 40000000 Reserved 80000000 Reserved
Hex Code Alarm Word
00000001 Unknown fault 00000002 Trip locked 00000004 Auto-optimization not OK 00000008 HPFB bus timeout 00000010 Serial communication timeout 00000020 ASIC fault 00000040 HPFP bus timeout 00000080 Standard bus timeout 00000100 Short-circuiting 00000200 Switchmode fault 00000400 Earth fault 00000800 Current limit 00001000 Overcurrent 00002000 Motor thermistor 00004000 Motor overheated 00008000 Inverter overheated 00010000 Undervoltage 00020000 Overvoltage 00040000 Mains phase fault 00080000 Live zero fault 00100000 Heat sink temperature too high 00200000 Motor phase W missing 00400000 Motor phase V missing 00800000 Motor phase U missing 01000000 Profibus communication fault 02000000 Inverter fault 04000000 Output current low 08000000 Safety stop 10000000 Reserved
87
Service Functions Parameters 600 through 631
This parameter group contains functions useful for troubleshooting the drive including operating data, data log and fault log.
Parameter 602, kWh Counter
Shows the output power of the drive. The calculation is based on the mean value in kWh over one hour. This value can be reset using parameter 618, Reset of kWh Counter.
Parameter 603 Number of Power Ups.
It also has information on the nameplate data of the drive.
Function:
These parameters can be read out through the serial communication port as well as on the control panel display.
Description of choice:
Parameter 600, Operating Hours
Shows the number of hours the drive has had power applied. The value is saved every hour and when the power is removed. This value cannot be reset.
Parameter 601, Hours Run
Shows the number of hours the drive has powered the motor. This parameter can be reset in parameter 619, Reset of Hours Run Counter. The value is saved every hour and when the power is removed.
Shows the number of times power has been applied to the drive.
Parameter 604, Number of Overtemperature Trips
Shows the number of overtemperature trips from the heatsink tempera­ture sensor on the drive.
Parameter 605, Number of Overvoltage Trips
Shows the number of overvoltage trips from the sensor of DC link voltage of the drive. The count is only taken when Alarm 7 Overvolt- age is activated.
600-605 Operating Data Value:
Value:
Parameter Description Display Unit Range Number Operating Data: Text
600 Operating Hours (OPERATING HOURS) Hours 0 through 130,000.0 601 Hours Run (RUNNING HOURS) Hours 0 through 130,000.0 602 kWh Counter (KWH COUNTER) kWh ­603 Number of Power-ups (POWER UPS) Occurences 0 through 9999 604 Number of Overtemp Trips (OVER TEMPS) Occurences 0 through 9999 605 Number of Overvoltage Trips (OVER VOLTS) Occurences 0 through 9999
88
606 - 614 Data Log
Value:
Parameter Description Display Unit Range no. Data log: Text
606 Digital Input (LOG: DIGITAL INP) Decimal 0 through 255 607 Control Word (LOG: BUS COMMAND) Decimal 0 through 65535 608 Status Word (LOG: BUS STAT WD) Decimal 0 through 65535 609 Reference (LOG: REFERENCE) % 0 through 100 610 Feedback (LOG: FEEDBACK) Par. 414 -999,999.999 through 999,999.999 611 Output Frequency (LOG: MOTOR FREQ.) Hz 0.0 through 999.9 612 Output Voltage (LOG: MOTOR VOLT) Volt 50 through 1000 613 Output Current (LOG: MOTOR CURR.) Amp 0.0 through 999.9 614 DC Link Voltage (LOG: DC LINK VOLT) Volt 0.0 through 999.9
Function:
With these parameters, it is possible to see up to twenty saved values, or data logs. Data log [1] is the most recent and [20] the oldest log. When a start command has been given, a new entry to the data log is made every 160 ms. If there is a trip or if the drive is stopped, the 20 latest data log entries will be saved and the values will be visible in the display. This is useful to view the operation of the drive just before a trip. These values will be lost if power is removed from the drive.
The drawing below shows a display. The data log number is shown in the square brackets at the left of the forth line of the display.
EXT. REFERENCE, %
SETUP
63.0 %
606 DATALOG: DIGITAL
INPUT
[1] 40
Data logs [1] through [20] can be read by first pressing CHANGE DATA, followed by the + and - keys to change data log numbers.
1
The table can be used for converting a decimal number into a binary code. For example, digital 40 corresponds to binary 00101000. The nearest smaller decimal number is 32, corresponding to a signal on terminal 18. 40-32 = 8, corresponds to the signal on terminal 27.
Terminal 16 17 18 19 27 29 32 33 Decimal number 128 64 32 16 8 4 2 1
Parameter 607 Data Log: Control Word:
This is where the latest log data is given in decimal code for the control word of the drive. The control word can only be changed via serial communication. The control word is read as a decimal number which is to be converted into hex. See the control word profile under the section
Serial communications.
Parameter 608, Data Log: Status Word:
This gives the latest log data in decimal code for the status word. The status word is read as a decimal number which is to be converted into hex. See the status word profile under the section Serial communica-
tion. Parameter 609, Data Log: Reference:
This gives the latest log data for the resulting reference.
Parameters 606 through 614, Data Log, can also be read out via the serial communication port.
Description of choice:
Parameter 606 Data Log: Digital Input:
This is where the latest log data is shown in decimal code, representing the status of the digital inputs. Translated into binary code, terminal 16 corresponds to the bit to the extreme left and to decimal code 128. T erminal 33 corresponds to the bit to the extreme right and to decimal code 1.
Parameter 610, Data Log: Feedback:
This gives the latest log data for the feedback signal.
Parameter 611, Data Log: Output Frequency:
This gives the latest log data for the output frequency .
Parameter 612, Data Log: Output Voltage:
This gives the latest log data for the output voltage.
Parameter 613, Data Log: Output Current:
This gives the latest log data for the output current.
Parameter 614, Data Log: DC Link Voltage:
This gives the latest log data for the intermediate circuit voltage.
89
615 Fault Log: Error Code
(F. LOG: ERROR CODE)
Value:
[Index 1-10] Error Code: 0 - 99
618 Reset of kWh Counter (RESET KWH COUNT) Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
This parameter makes it possible to see the reason why a fault trip occurs. T en log values, indicated as [1] through [10] are stored.
The lowest log number [1] contains the most recently saved data value; the highest log number [10] contains the oldest data value.
If there is a fault trip, it is possible to see its cause, the time and possibly the values or output current or output voltage. See the section on Warnings and Alarms for a table explaining the error codes.
Description of choice:
The fault log is only reset after manual initialization.
616 Fault Log: Time (F. LOG: TIME) Value:
[Index 1-10] Hours: 0 - 130,000.0
Function:
This parameter makes it possible to see the total number of hours run in connection with the 10 most recent fault trips. T en log values, indicated as [1] through [10] are stored.
The lowest log number [1] contains the most recently saved data value: the highest log number [10] contains the oldest data value.
Description of choice:
The fault log is only reset after manual initialization.
617 Fault Log: Value (F. LOG: VALUE) Value:
[Index 1 - 10] Value: 0 - 9999
Function:
This parameter makes it possible to see the value at which a fault trip occurred. The unit of the value depends on the alarm active in parameter 615, Fault Log: Error Code.
Function:
Reset to zero of parameter 602, kWh Counter.
Description of choice:
If Reset has been selected and the OK key is pressed, the kWh counter of the drive is reset. This parameter cannot be selected via the serial port.
619 Reset of Hours Run Counter
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Reset to zero of parameter 601, Hours Run.
Description of choice:
If Reset has been selected and the OK key is pressed, parameter 601 Hours-run is reset to zero. This parameter cannot be selected via the
serial port.
620 Operating Mode (OPERATION MODE) Value:
Normal function (NORMAL OPERA TION) [0]
Function with deactivated inverter (OPER. W/INVERT .DISAB) [1] Control card test (CONTROL CARD TEST) [2] Initialization (INITIALIZE) [3]
Function:
In addition to its normal function, this parameter can be used for two different tests.
It is possible to reset to the default factory settings for all Setups, except parameters 500, Address; 501 Baud Rate; 600-605, Operating Data; and 615-617, Fault Log.
Description of choice:
The fault log is only reset after manual initialization.
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
90
Description of choice:
Normal function is used for normal operation of the motor. Function with deactivated inverter is selected to operate the control
card using its control signals without running the motor. Control card test is used to test the analog and digital inputs, analog
and digital outputs, relay output and the power supplies of the control card.
A test connector with the connections shown below is required for this
CAUTION
!
test.
Set test connector set up as follows:
1. Connect 4, 16, 17, 18, 19, 27, 29, 32 and 33.
2. Connect 5 and 12.
3. Connect 39, 20 and 55.
4. Connect 42 and 60.
5. Connect 45, 53 and 54
Initialization is selected to reset the drive to its factory default settings without resetting parameters 501 Address, 502 Baud Rate; 600-605, Operating Data; and 615-617, Fault Log.
Choosing memory default parameter values. This erases any special programming which may have been done to drive. It may be preferrable to use parameter 004 to download all parameters from local control panel (LCP).
Iinitialization the drive to factory default settings in accordance with the following procedues:
1. Select Initialization.
2. Press OK key.
3. Remove input power and wait for light in display to go out.
4. Connect input power.
5. Initialization of all parameters will be carried out in all Setups with exception of parameters 501, Address; 502, Baud Rate; 600-605, Operating Data; and 615-617, Fault Log.
Initialization
resets drive to read-only
T est the control card in accordance with the following procedure:
1. Select Control Card Test.
2. Remove input power and wait for light in display to go out.
3. Insert test connector described above.
4. Reconnect input power.
5. Press OK key. (Test cannot run without control panel in place.)
6. Drive automatically tests control card.
7. Remove test connector and press OK key when drive displays “TEST COMPLETED.”
8. Parameter 620, Operating Mode, is automatically set to Normal Function.
If the control card test fails, the drive will display “TEST FAILED.” Replace the control card.
91
621 - 631 Nameplate
Value:
Parameter Description Display text Number Nameplate:
621 Unit Type (DRIVE TYPE) 622 Power Component (POWER SECTION) 623 VLT Ordering No. (ORDERING NO) 624 Software Version No. (SOFTWARE VERSION) 625 Control Panel Identification No. (LCP ID NO.) 626 Database Identification No. (PARAM DB ID) 627 Power Component Identification No. (POWER UNIT DB ID) 628 Application Option Type (APPLIC. OPTION) 629 Application Option Ordering No. (APPLIC. ORDER NO) 630 Communication Option Type (COM. OPTION) 631 Communication Option Ordering No. (COM. ORDER NO)
Function:
Identification information for the drive can be read from parameters 621 through 631, Nameplate via the display or the serial communication port.
Description of choice:
Parameter 621, Nameplate: Unit Type:
VL T type gives the unit size and input voltage. See Cross Reference ­Model Number to VLT T ype to convert this do the drive’ s model number.
Parameter 622, Nameplate: Power Component:
This gives the type of power card installed in the drive.
Parameter 623, Nameplate: VLT Ordering Number:
This gives the ordering number for the specific drive. Because this number does not specify any special options or programming that was provided with the drive, it is better to refer to the serial number printed on the Danfoss Graham nameplate when contacting the factory about the drive.
Parameter 624, Nameplate: Software Version Number:
This gives the present software version number of the drive.
Parameter 625, Nameplate: LCP Identification Number:
This gives the identification number of the keypad (LCP) of the unit.
Parameter 626, Nameplate: Database identification Number:
This gives the identification number of the software’s database.
Parameter 627, Nameplate: Power Component Identification Number:
This gives the identification number of the database of the drive.
Parameter 628, Nameplate: Application Option Type:
This gives the type of application options fitted to the basic drive.
Parameter 629, Nameplate: Application Option Ordering Number:
This gives the ordering number for the application option of the basic drive. Because this number does not specify any special options or programming that was provided with the drive, it is better to refer to the serial number printed on the Danfoss Graham nameplate when contacting the factory about the drive.
Parameter 630, Nameplate: Communication Option Type:
This gives the type of communication option card installed in the drive, if any.
Parameter 631, Nameplate: Communication Option Ordering Number:
This gives the ordering number for the communication option.
92
Relay Card Functions Parameters 700 through 711
Parameters 700 through 711 are only activated if a relay option card is installed in the drive. A relay card can be field installed in the drive if desired.
Activation/deactivation can be programmed in parameters 701, 704, 707 and 710, Relay 6, 7, 8 and 9, ON Delay; and parameters 702, 705, 708 and 711 Relay 6, 7, 8 and 9, OFF Delay.
700 Relay 6, Function (RELAY6 FUNCTION) 703 Relay 7, Function (RELAY7 FUNCTION) 706 Relay 8, Function (RELAY8 FUNCTION) 709 Relay 9, Function (RELAY9 FUNCTION) Function:
This output activates a relay . Relay outputs 6, 7, 8 and 9 can be used for showing status and
warnings. The relay is activated when the conditions for the relevant data values have been fulfilled. Because these have the same possible functions as relay 1, see the description under parameter 323.
701 Relay 6, ON Delay (RELAY6 ON DELAY) 704 Relay 7, ON Delay (RELAY7 ON DELAY) 707 Relay 8, ON Delay (RELAY8 ON DELAY) 710 Relay 9, ON Delay (RELAY9 ON DELAY) Value:
0 to 600 sec. 0 sec.
Electrical Installation of the Relay Card
The relays are connected as shown below. Relay 6-9
A-B make, A-C break Max. 240 VAC, 2 Amp
Function:
This parameter allows a delay of the activation of relays 6, 7, 8 and 9 (terminals 1, and 2).
Description of choice:
Enter the desired value.
702 Relay 6, OFF Delay (RELAY6 OFF DELAY) 705 Relay 7, OFF Delay (RELAY7 OFF DELAY) 708 Relay 8, OFF Delay (RELAY8 OFF DELAY) 711 Relay 9, OFF Delay (RELAY9 OFF DELAY) Value:
0 to 600 sec. 0 sec.
Function:
This parameter is used to delay the deactivation time of relays 6, 7, 8 and 9 (terminals 1 and 2).
Description of choice:
Enter the desired value. This parameter allows a delay of the activation of relays 6, 7, 8 and 9
(terminals 1, and 2).
T o achieve double isolation, mount the plastic foil as shown below .
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
93
Status Messages
Status messages appear in the fourth line of the display as shown below.
Auto Ramp (AUTO RAMP)
Parameter 208, Automatic Ramp Up/Down, is enabled. The drive is attempting to avoid a trip from overvoltage by extending its decel ramp time.
The left part of the status line indicates the control point of the drive. The center part of the status line indicates the reference location. The last part of the status line gives the present status of the drive.
80.0% 5.08A 2.15kW
SETUP
40.0Hz
1
AUTO REMOTE RUN
HAND
OFF
LOCAL
STOP
RAMPING JOGGING
. . . .
STAND BY
Auto Mode (AUTO)
The drive is in Auto mode, which means that Run/Stop control is carried out via the control terminals and/or serial communication. See also Auto Start .
Hand Mode (HAND)
The drive is in Hand mode, which means that Run/Stop control is carried out via the keys on the keypad. See also Hand Start.
Sleep Boost (SLEEP .BST)
The boost function in parameter 406, Boost Setpoint, is enabled. This function can only be enabled in Closed Loop operation.
DANGER
!
When in time without warning.
Sleep Mode (SLEEP)
The energy saving function in parameter 403, Sleep Mode Timer , is enabled. This status message shows that at present the motor has been stopped by sleep mode. It can restart automatically.
!
When in at any time without warning.
Start Delay (START DEL)
A start delay time has been programmed in parameter 1 1 1, Start Delay. When the delay has passed, the drive will start and ramp up to the reference frequency .
!
When in at any time without warning.
Sleep Mode
DANGER
Start Delay
DANGER
Run Request
, motor may restart at any
mode, motor may restart
mode, motor may restart
OFF (OFF)
OFF/STOP is activated either by means of the keypad, or by the digital inputs Hand Start and Auto Start, both being a logic ‘0’. See also OFF/ STOP .
Local Reference (LOCAL)
If LOCAL has been selected, the reference is set via the + and - keys on the keypad. See also Display Modes.
Remote Controlled Reference (REM.)
If REMOTE has been selected, the reference is set via the control terminals or via serial communication. See also Display Modes.
Running (RUNNING)
The motor speed now corresponds to the resulting reference.
Ramp Operation (RAMPING)
The output frequency is changing.
Run Request (RUN REQ.)
A start command has been given, but the motor will not be started until a Run Permission signal is received via a digital input.
Jogging (JOG)
Jog has been enabled via a digital input or via serial communication.
DANGER
!
When in time without warning.
Jog Request (JOG REQ.)
A start command has been given, but the motor will remain stopped until a Run Permission signal is received via a digital input.
Jog Request
, motor may restart at any
94
Freeze Output (FRZ.OUT.)
The ouput frequency has been frozen.
DANGER
!
When in start at any time without warning.
Freeze Output Request (FRZ.REQ.)
A start command has been given, but the motor will remain stopped until a Run Permission signal is received via a digital input.
Reversing and Start (START F/R)
Reversing and start 2 on terminal 19, parameter 303, Digital Inputs; and Start on terminal 18, parameter 302, Digital Inputs are enabled at the same time. The motor will remain stopped until one of the signals becomes a logic ‘0’.
Automatic Motor Adaptation Running (AMA RUN)
Automatic motor adaptation has been enabled in parameter 107, Automatic Motor Adaptation, AMA.
Automatic Motor Adaptation Completed (AMA STOP)
Automatic motor adaptation has been completed. The drive is now ready for operation after the Reset signal has been given. Note that the motor will start after the drive has received the Reset signal.
Freeze Output Request
, motor may re-
Stand by (STANDBY)
The drive is able to start the motor when a start command is received.
Stop (STOP)
The motor has been stopped via a stop signal from serial communica­tion.
DC stop (DC STOP)
The DC brake in parameter 114 through 116 has been enabled.
Drive Ready (UN. READY)
The drive is ready for operation, but terminal 27 is a logic ‘0’ and/or a Coasting Command has been received via the serial communication.
Control Ready (CTR.READY)
This status is only active when a Profibus option card is installed.
Not Ready (NOT READY)
The drive is not ready for operation, because of a trip or because OFF1, OFF2 or OFF3 is a logic ‘0’.
Start Inhibited (START IN.)
This status will only be displayed if, in parameter 599, Profidrive [1] has been selected and OFF2 or OFF3 is a logic ‘0’.
Exceptions XXXX
The microprocessor of the control has stopped and the drive is not operating. The cause may be noise on the power line, motor leads or control wires.
95
Warnings and Alarms
The table below gives the drive’s warnings and alarms and indicates whether the fault trip locks the drive. After a Trip Lock Fault, the input power must be removed, the cause of the fault corrected, and input power restored to reset the drive. A Trip can be reset manually in any one of three ways.
1) Pressing the keypad key RESET
2) A digital input
3) Serial communication
No. Description Warning Alarm Trip Locked
1 10 Volts low (10 VOL T LOW) X 2 Live zero fault (LIVE ZERO ERROR) X X 4 Mains failure (MAINS PHASE LOSS) X X X 5 Voltage warning high (DC LINK VOL T AGE HIGH) X 6 Voltage warning low (DC LINK VOL T AGE LOW) X 7 Overvoltage (DC LINK OVERVOLT) X X 8 Undervoltage (DC LINK UNDERVOLT) X X 9 Inverter overloaded (INVERTER TIME) X X 10 Motor overloaded (MOTOR TIME) X X 1 1 Motor thermistor (MOTOR THERMISTOR) X X 12 Current limit (CURRENT LIMIT) X X 13 Over current (OVERCURRENT) X X 14 Earth fault (EARTH FAUL T) X X 15 Switch mode fault (SWITCH MODE FAULT) X X 16 Short-circuit (CURR.SHORT CIRCUIT) X X 17 Serial communication timeout (STD BUSTIMEOUT) X X 18 HPFB bus timeout (HPFB TIMEOUT) X X 19 Fault in EEprom on power card (EE ERROR POWER) X 20 Fault in EEprom on control card (EE ERROR CONTROL) X 22 Auto-optimisation not OK (AMA FAUL T) X 29 Heat-sink temperature too high (HEAT SINK OVERTEMP .) X X 30 Motor phase U missing (MISSING MOT.PHASE U) X 31 Motor phase V missing (MISSING MOT.PHASE V) X 32 Motor phase W missing (MISSING MOT.PHASE W) X 34 HPFB communication fault (HPFB COMM. FAULT) X X 35 Out of frequency range (OUT FREQ RNG/ROT LIM) X 37 Inverter fault (GATE DRIVE FAULT) X X 39 Check parameters 104 and 106 (CHECK P.104 & P.106) X 40 Check parameters 103 and 105 (CHECK P.103 & P.106) X 41 Motor too large (MOTOR TOO BIG) X 42 Motor too small (MOTOR TOO SMALL) X 60 Safety stop (EXTERNAL FAULT) X 61 Output frequency low (FOUT < FLOW) X 62 Output frequency high (FOUT > FHIGH) X 63 Output current low (I MOTOR < I LOW) X X 64 Output current high (I MOTOR > I HIGH) X 65 Feedback low (FEEDBACK < FDB LOW) X 66 Feedback high (FEEDBACK > FDB HIGH) X 67 Reference low (REF. < REF. LOW) X 68 Reference high (REF. > REF. HIGH) X 69 Temperature auto derate (TEMP.AUTO DERA TE) X 99 Unknown fault (UNKNOWN ALARM) X X
96
In addition, an automatic reset may be selected in parameter 400, Reset Function which will reset all non-trip lock faults.
Wherever an “X” is placed under both Warning and Alarm in the table below, this means that a W arning precedes the Alarm. It can also mean that it is possible to program whether a given fault is to result in a Warning or an Alarm. This is possible, for example, through parameter 117, Motor Thermal Protection. After a trip, the motor will be coasting and the drive’s Alarm and Warning indications will flash. If the fault is removed, only the Alarm will flash. After a reset, the drive will be ready to start operation again.
Warnings
Alarms
A warning will flash in line 2, while an explanation is given in line 1.
MAINS PHASE LOSS
SETUP
WARN. 4
WARNING 1 Under 10 V (10 VOLT LOW)
The 10 V voltage from terminal 50 on the control card is below 10 V. Remove some of the load from terminal 50, as the 10 volts supply is
overloaded. Maximum load is 17 mA, minimum resistance is 590 Ω.
WARNING/ALARM 2 Live Zero Fault (LIVE ZERO ERROR)
The current or voltage signal on terminal 53, 54 or 60 is below 50% of the value preset in parameter 309, 312 and 315 T erminal, Minimum
Scaling.
WARNING/ALARM 4 Mains Failure (MAINS PHASE LOSS)
Phase missing on the input power. Check the supply voltage to the drive.
WARNING 5 Voltage Warning High (DC LINK VOLTAGE HIGH)
The intermediate DC circuit voltage is higher than Voltage W arning High, see table below. The drive is still controlling the motor .
1
If an alarm is given, the present alarm number will be shown in line 2. Lines 3 and 4 of the display will offer an explanation.
TRIP (RESET)
SETUP
ALARM:12
1
TORQUE LIMIT
WARNING 6 Voltage Warning Low (DC LINK VOLTAGE LOW)
The intermediate DC circuit voltage is lower than Voltage W arning Low, see table below. The drive is still controlling the motor .
WARNING/ALARM 7 Overvoltage (DC LINK OVERVOLT)
If the intermediate circuit voltage (DC) is higher than the Overvoltage Limit of the drive (see table below), the drive will trip after a fixed
period. The length of this period depends upon the unit.
WARNING/ALARM 8 Undervoltage (DC LINK UNDERVOLT)
If the intermediate circuit voltage (DC) drops below the Undervoltage Limit of the inverter, the drive will trip after a fixed period. The length of
the period depends upon the unit. The voltage will be stated in the display. Check whether the supply
voltage matches the drive rating.
WARNING/ALARM 9 Inverter Overload (INVERTER TIME)
The electronic thermal inverter protection reports that the drive is about to trip because of an overload. The counter for electronic thermal inverter protection gives a warning at 98% and trips at 100% showing an alarm. The drive cannot be reset until the counter drops below 90%.
Alarm/Warning limits: Drive 208 to 230 volt 380 to 460 volt 575 volt
Undervoltage alarm 211 164 402 313 621 Voltage warning, low 222 173 423 329 641 Voltage warning, high 384 270 737 519 965 Overvoltage alarm 425 299 765 538 975
VDC VAC VDC VAC VDC
97
WARNING/ALARM 10 Motor Overtemperature (MOTOR TIME)
According to the electronic thermal protection, the motor is overheated. Parameter 117, Motor Thermal Protection, allows a choice of whether the drive is to give a warning or an alarm when the Motor Thermal Projection reaches 100%. The fault is that the motor is overloaded to more than 100% of the preset rated motor current for too long. Check that the motor parameters 102 through 106 have been set correctly.
WARNING/ALARM 11 Motor Thermistor (MOTOR THERMISTOR)
The thermistor or the thermistor connection has been disconnected. Parameter 117, Motor Thermal Protection, allows a choice of whether the drive is to give a warning or an alarm. Check that the thermistor has been correctly connected between terminal 53 or 54 (analog voltage input) and terminal 50 (+ 10 V supply).
WARNING/ALARM 12 Current Limit (CURRENT LIMIT)
The current is higher than the value in parameter 215, Current Limit, and the drive trips after the time set in parameter 412, Trip Delay Overcurrent, has passed.
WARNING/ALARM 13 Overcurrent (OVER CURRENT)
The inverter peak current limit, approximately 200% of the rated current, has been exceeded. The warning will last approximately 1 or 2 seconds, and then the drive will trip and signal an alarm.
Turn off the drive and check for free rotation of the motor shaft and other causes of the overload.
ALARM 14 Earth Fault (EARTH FAULT)
There is current leakage from the output phases to earth, either in the leads between the drive and the motor or in the motor itself.
Remove power to the drive and correct the earth fault.
ALARM 15 Switch Mode Fault (SWITCH MODE FAULT)
Fault in the switch mode power supply (internal ±15 V supply).
WARNING/ALARM 17 Serial Communication Timeout (STD BUSTIMEOUT)
There is no serial communication with the drive. This warning will only be enabled if parameter 510, Bus Time Interval
Function, has been set to a value different from OFF . If parameter 510, Bus Time Interval Function, has been set to Stop
and Trip [5], the drive will first give off an alarm, then ramp down and finally trip while giving an alarm. It is possible to increase parameter 509, Bus Time Interval.
WARNING/ALARM 18 HPFB Bus Timeout (HPFB TIMEOUT)
There is no serial communication with the communication option card in the drive.
The warning will only be enabled if parameter 804, Bus Time Interval
Function, has been set to anything but OFF . If parameter 804, Bus Time Interval Function, has been set to Stop and Trip, the drive will
first give an alarm, then ramp down and finally trip while giving an alarm.
Parameter 803, Bus Time Interval could possibly be increased. Parameter 803 is only available when a communicaion option card is installed in the drive.
WARNING 19 Fault in the EEprom on the Power Card (EE ERROR POWER)
There is a fault on the power card EEPROM. The drive will continue to function, but is likely to fail at the next power-up. Contact the Danfoss Graham service department.
WARNING 20 Fault in the EEprom on the control card (EE ERROR CONTROL)
There is a fault in the EEPROM on the control card. The drive will continue to function, but is likely to fail at the next power-up. Contact the Danfoss Graham service department.
Contact the Danfoss Graham service department.
ALARM 16 Short Circuiting (CURR. SHORT CIRCUIT)
There is a short circuit in the output from the drive. Remove power to the drive and correct the short circuit.
98
ALARM 22 Automatic Motor Adaptation Failed (AMA FAULT)
A fault has been found during automatic motor adaptation. The text shown in the display indicates a fault message.
AMA can only be carried out if there are no alarms during the AMA process.
CHECK 103, 105
Parameter 103 or 105 has a wrong setting. Correct the setting and repeat AMA.
LOW P 105
The motor is too small for AMA to be carried out. If AMA is to be enabled, the rated motor current, parameter 105, must be higher than 35% of the rated output current of the drive.
ASYMMETRICAL IMPEDANCE
AMA has detected an asymmetrical impedance in the motor connected to the system. The motor could be defective.
MOTOR TOO BIG
The motor connected to the system is too big for AMA to be carried out. The setting in parameter 102 does not match the motor used.
MOTOR TOO SMALL
The motor connected to the system is too small for AMA to be carried out. The setting in parameter 102 does not match the motor used.
TIME OUT
AMA fails because of noisy measuring signals. Retry until AMA is successfully completed. Please note that repeated AMA runs may heat the motor to a level where the stator resistance is increased.
ALARM 29 Heat Sink Temperature Too High (HEAT SINK OVER TEMP.):
The heatsink temperature became too high. For NEMA 1 drives, the limit is 90°C. For NEMA 12 drives, the limit is 80°C. The tolerance is ±5°C. The fault cannot be reset until the temperature of the heatsink has fallen below 60°C.
The fault could be due to the following:
- Ambient temperature too high
- Air obstructed
- Cooling fan(s) not operating
- Motor leads too long
- T oo high a switching frequency
ALARM 30 Motor phase U missing (MISSING MOT.PHASE U):
Motor phase U, as indicated by the letters on the output terminal block is missing or has a high impedance.
Remove power to the drive and check motor phase U.
ALARM 31 Motor Phase V Missing (MISSING MOT.PHASE V):
Motor phase V , as indicated by the letters on the output terminal block is missing or has a high impedance.
Remove power to the drive and check motor phase V .
ALARM 32 Motor Phase W Missing (MISSING MOT.PHASE W):
Motor phase W, as indicated by the letters on the output terminal block is missing or has a high impedance.
Remove power to the drive and check motor phase W.
INTERRUPTED BY USER
AMA has been interrupted by the user.
INTERNAL FAULT
An internal fault has occurred in the drive. Contact Danfoss Graham service department.
LIMIT VALUE FAULT
The parameter values found for the motor are outside the acceptable range within which the drive is able to work.
MOTOR ROTATES
The motor shaft is rotating. Make sure that the load is not able to make the motor shaft rotate while the AMA is being performed. Then start AMA all over.
WARNING/ALARM 34 HPFB Communication Fault (HPFB COMM. FAULT)
The serial communication on the communication option card is not working.
WARNING 35 Out of Frequency Range (OUT FREQ RNG/ROT LIM):
This warning will occur if the output frequency has reached its Output Frequency Low Limit , parameter 201, or Output Frequency High Limit, parameter 202. If the drive is in Closed Loop, parameter 100, the
warning will show in the display .
99
ALARM 37 Inverter fault (GATE DRIVE FAULT):
An output IGBT or the power card is defective. Contact the Danfoss Graham service department.
WARNING 62 Output Frequency High (FOUT > FHIGH)
The output frequency is higher than parameter 224, Warning: High Frequency.
Auto Optimization Warnings 39 through 42
Automatic motor adaptation has stopped, because some parameters have probably been improperly set, or the motor used in too large or small for AMA to be carried out.
A choice must be made by pressing CHANGE DAT A and choosing ‘Continue’ + OK or ‘Stop’ + OK.
If parameters need to be changed, select ‘Stop’, change the parameters and run AMA again.
WARNING 39 CHECK PAR. 104, 106
Parameters 104, Motor Frequency, or 106, Rated Motor Speed, have probably not been set correctly. Correct the setting and run AMA again.
WARNING 40 CHECK PAR. 103, 105
Parameter 103 Motor Voltage, or 105 Motor Current, has not been set correctly. Correct the setting and run AMA again.
WARNING 41 Motor Too Large (MOTOR TOO BIG)
The motor used is probably too large for AMA to be carried out. The setting in parameter 102 Motor Power, may not match the motor . Check the motor and select ‘Continue’ or [STOP].
WARNING 42 Motor Too Small (MOTOR TOO SMALL)
The motor used is probably too small for AMA to be carried out. The setting in parameter 102 Motor Power, may not match the motor . Check the motor and select ‘Continue’ or [STOP].
ALARM 60 Safety Stop (EXTERNAL FAULT)
T erminal 27, parameter 304, Digital Inputs, has been programmed for a Safety Interlock and is a logic ‘0’.
WARNING 61 Output Frequency Low (FOUT < FLOW)
The output frequency is lower than parameter 223, Warning: Low Frequency.
WARNING/ALARM 63 Output Current Low (I MOTOR < I LOW)
The output current is lower than parameter 221, Warning: Low Current. Select the required function in parameter 409, Function in Case of No Load.
WARNING 64 Output Current High (I MOTOR > I HIGH)
The output current is higher than parameter 222, Warning: High Current.
WARNING 65 Feedback Low (FEEDBACK < FDB LOW)
The resulting feedback value is lower than parameter 227, Warning: Low Feedback.
WARNING 66 Feedback High (FEEDBACK > FDB HIGH)
The resulting feedback value is higher than parameter 228, Warning: High Feedback.
WARNING 67 Remote Reference Low (REF. < REF LOW)
The remote controlled reference is lower than parameter 225, Warning: Low Reference.
WARNING 68 Remote Reference High (REF. > REF HIGH)
The remote controlled reference is higher than parameter 226, Warning: High Reference.
WARNING 69 Temperature auto derate (TEMP.AUTO DERATE)
The heat sink temperature has exceeded the maximum value and the auto derating function in parameter 411 is active. W arning: Temp.auto
Derate.
WARNING 99 Unknown Fault (UNKNOWN ALARM)
An unknown fault has occurred which the software is not able to handle. Contact Danfoss Graham service department.
100
Loading...