Quick Menu ........................................................................................................... 23
All about VLT 6000 HVAC ............................................................................ 24
Status messages .................................................................................................... 24
List of warnings and alarms ................................................................................... 26
Index ...................................................................................................................... 27
MG.60.C7.02 - VLT is a registered Danfoss trademark
1
VLT®6000 HVAC
The voltage of the frequency converter
is dangerous whenever the equipment
is connected to mains. Incorrect
installation of the motor or the frequency converter
may cause damage to the equipment, serious
personal injury or death.
Consequently, the instructions in this manual,
as well as national and local rules and safety
regulations, must be complied with.
■Safety regulations
1. The frequency converter must be disconnected
from mains if repair work is to be carried out. Check
that the mains supply has been disconnected
and that the necessary time has passed before
removing motor and mains plugs.
2. The [OFF/STOP] key on the control panel of
the frequency converter does n
the equipment from mains and is thus n
to be used as a safety switch.
3. Correct protective earthing of the equipment
must be established, the user must be protected
against supply voltage, and the motor must be
protected against overload in accordance with
applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is included in
the factory setting. Parameter 117, Motor thermalprotection default value is ETR trip 1.
ote: The function is initialised at 1.0 x rated
N
motor current and rated motor frequency (see
parameter 117, Motor thermal protection).
6. Do n
7. Reliable galvanic isolation (PELV) is not complied
8. Please note that the frequency converter has
ot remove the plugs for the motor and mains
supply while the frequency converter is connected
to mains. Check that the mains supply has been
disconnected and that the necessary time has
passed before removing motor and mains plugs.
with if the RFI switch is placed in OFF position.
This means that all control in - and outputs
can only be considered low-voltage terminals
with basic galvanic isolation.
more voltage inputs than L1, L2 and L3, when
theDC-busterminalsareused.
Check that a
disconnected and that the necessary time has
passed before repair work is commenced.
ll voltage inputs have been
ot disconnect
ot
If personal safety considerations make it necessary
to ensure that no unintended start occurs, t
stop functions are not sufficient.
2. While parameters are being changed, the
motor may start. Consequently, t
[OFF/STOP] must always be activated, following
which data can be modified.
3. A motor that has been stopped may start if faults
occur in the electronics of the frequency converter,
or if a temporary overload or a fault in the supply
mains or the motor connection ceases.
■Use on isolated mains
See section RFI S witch regarding use on isolated mains.
It is important to follow the recommendations
regarding installation on IT-mains, since sufficient
protection of the complete installation must be
observed. Not taking care using relevant monitoring
devices for IT-mains may result in damage.
he stop key
hese
■Warning against unintended start
1. The motor can be brought to a stop by
means of digital commands, bus commands,
references or a local stop, while the frequency
converter is connected to mains.
2
MG.60.C7.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC
Warning:
Touching the electrical parts may be fatal - even after the equipment has been
disconnected from mains.
175HA490.11
Using VLT 6002 - 6005, 200-240 V: Wait at least 4 minutes
Using VLT
Using VLT
Using VLT
6006 - 6062, 200-240 V: Wait at least 15 minutes
6002 - 6005, 380-460 V: Wait at least 4 minutes
6006 - 6072, 380-460 V: Wait at least 15 minutes
Using VLT 6102 - 6352, 380-460 V: Wait at least 20 minutes
Using VLT 6400 - 6550, 380-460 V: Wait at least 15 minutes
Using VLT
Using VLT
Using VLT
6002 - 6006, 525-600 V: Wait at least 4 minutes
6008 - 6027, 525-600 V: Wait at least 15 minutes
6032 - 6275, 525-600 V: Wait at least 30 minutes
HVAC
Introduction to
MG.60.C7.02 - VLT is a registered Danfoss trademark
3
■Mechanical installation
Please pay attention to the requirements
that apply to integration and field mounting
kit, see the below list. The information given
in the list must be observed to avoid serious damage
or injury, especially when installing large units.
The frequency converter must be installed vertically.
The frequency converter is cooled by means of air
circulation. For the unit to be able to release its cooling
air, the minimum distance over and below the unit
must be as shown in the illustration below.
To protect the unit from overheating, it must be
ensured that the ambient temperature does not rise
above the max. temperature stated for the frequency
converter and that the 24-hour average temperature is
not exceeded . The max. temperature and 24-hour
average can be seen from the General Technical Data.
If the ambient temperature is in the range of 45°C -55°
C, derating of the frequency converter will become
relevant, see Derating for ambient temperature.
The service life of the frequency converter will
be reduced if derating for ambient temperature
is not taken into account.
VLT®6000 HVAC
■Installation of VLT 6002-6352
All frequency converters must be installed in a
way that ensures proper cooling.
Cooling
All Bookstyle and Compact units require a minimum
space above and below the enclosure.
Side by side/flange by flange
All frequency converters can be mounted side
by side/flange by flange.
4
MG.60.C7.02 - VLT is a registered Danfoss trademark
VLT 6152-6352, 380-460 V225Installation on a plane, vertical surface (spacers can be used). IP 54 filter
Installation on a plane, vertical surface (no spacers)
IP 54 filter mats must be changed when they are dirty.
mats must be changed when they are dirty.
■Installation of VLT 6400-6550 380-460 V Compact
IP 00, IP 20 and IP 54
CoolingSide-by-side
Installation
All units in the above-mentioned series require a
minimum spac
e of 400 mm above the enclosure
and must be installed on a plane floor. This applies
to both IP 00, IP 20 and IP 54 units.
Gaining acce
ss to VLT 6400-6550 requires a
minimum space of 605 mm in front of the frequency
converter.
■IP 00 VLT 6400-6550 380-460 V
The IP 00 unit is designed for installation in a cabinet
when installed according to the instructions in the
MG.60.C7.02 - VLT is a registered Danfoss trademark
All IP 00, IP 20 and IP 54 units in the
above-menti
oned series can be installed side by side
without any space between them, since these units
do not require cooling on the sides.
VLT 6400-6550 Installation Guide MG.56.AX.YY.
Please note, that the same conditions as for NEMA
1/ IP20 and IP54 must be fulfilled.
5
VLT®6000 HVAC
■High voltage warning
The voltage of the frequency converter
is dangerous whenever the equipment is
connected to mains. Incorrect installation
of the motor or the frequency converter may cause
damage to the equipment, serious personal injury
or death. Consequently, the instructions in this
Design Guide, as well as national and local safety
regulations, must be complied with. Touching
the electrical parts may be fatal - even after
disconnection from mains: Using VLT 6002-6005,
200-240 V wait at least 4 minutes
Using VLT 6006-6062, 200-240 V wait at
least 15 minutes
Using VLT 6002-6005, 380-460 V wait at
least 4 minutes
Using VLT 6006-6072, 380-460 V wait at
least 15 minutes
Using VLT 6102-6352, 380-460 V wait at
least 20 minutes
Using VLT 6400-6550, 380-460 V wait at
least 15 minutes
Using VLT 6002-6006, 525-600 V wait at
least 4 minutes
Using VLT 6008-6027, 525-600 V wait at
least 15 minutes
Using VLT 6032-6275, 525-600 V wait at
least 30 minutes
NB!:
It is the user’s or certified electrician’s
responsibility to ensure correct earthing and
protection in accordance with applicable
national and local norms and standards.
■Earthing
The following basic issues need to be considered
when installing a frequency converter, so as to obtain
electromagnetic compatibility (EMC).
the cabinet rear plate, which must be made of
metal, should be used as a common earth reference
plate. The metal cabinets of the different devices
are mounted on the cabinet rear plate using the
lowest possible HF impedance. This avoids having
different HF voltages for the individual devices and
avoids the risk of radio interference currents running
in connection cables that may be used between
the devices. The radio interference will have been
reduced. In order to obtain a low HF impedance, use
the fastening bolts of the devices as HF connection
to the rear plate. It is necessary to remove insulating
paint or similar from the fastening points.
■Cables
Control cables and the filtered mains cable should
be installed separate from the motor cables so as to
avoid interference overcoupling. Normally, a distance
of 20 cm will be sufficient, but it is recommended
to keep the greatest possible distance wherever
possible, especially where cables are installed in
parallel over a substantial distance.
With respect to sensitive signal cables, such as
telephone cables and data cables, the greatest
possible distance is recommended with a minimum
of 1 m per 5 m of power cable (mains and
motor cable). It must be pointed out that the
necessary distance depends on the sensitivity of
the installation and the signal cables, and that
therefore no precise values can be stated.
If cable jaws are used, sensitive signal cables are not
to be placed in the same cable jaws as the motor
cable or brake cable. If signal cables are to cross
power cables, this should be done at an angle of
90 degrees. Remember that all interference-filled
in- or outgoing cables to/from a cabinet should
be screened/armoured or filtered.
See also EMC-correct electrical installation.
• Safety earthing: Please note that the frequency
converter has a high leakage current and must
be earthed appropriately for safety reasons.
Apply local safety regulations.
• High-frequency earthing: Keep the earth wire
connections as short as possible.
Connect the different earth systems at the lowest
possible conductor impedance. The lowest possible
conductor impedance is obtained by keeping the
conductor as short as possible and by using the
greatest possible surface area. A flat conductor, for
example, has a lower HF impedance than a round
conductor for the same conductor cross-section
. If more than one device is installed in cabinets,
C
VESS
6
■Screened/armoured cables
The screen must be a low HF impedance screen.
This is ensured by using a braided screen of
copper, aluminium or iron. Screen armour intended
for mechanical protection, for example, is not
suitable for an EMC-correct installation. See
also Use of EMC-correct cables.
■Extra protection with regard to indirect contact
ELCB relays, multiple protective earthing or earthing
can be used as extra protection, provided that
MG.60.C7.02 - VLT is a registered Danfoss trademark
local safety regulations are complied with. In
the case of an earth fault, a DC content may
develop in the faulty current.
Never use ELCB relays, type A, since such relays
are not suitable for DC fault currents.
If ELCB relays are used, this must be:
• Suitable for protecting equipment with a direct
current content (DC) in the faulty current
(3-phase bridge rectifier)
• Suitable for power-up with short charging
current to earth
• Suitable for a high leakage current
■RFI switch
ains supply isolated from earth:
M
If the frequency converter is supplied from an isolated
mains source ( IT mains) or TT/TN-S mains with
grounded leg, the RFI switch is recommended
to be turned off (OFF). For further reference, see
IEC 364-3. In case optimum EMC performance is
needed, parallel motors are connected or the motor
cable length is above 25 m, it is recommended
to set the switch in ON position.
In OFF position, the internal RFI capacities (filter
capacitors) between the chassis and the intermediate
circuit are cut off to avoid damage to the intermediate
circuit and to reduce the earth capacity currents
(according to IEC 61800-3).
Please also refer to the application note VLT onIT mains, MN.90.CX.02. It is important to use
isolation monitors that are capable for use together
with power electronics (IEC 61557-8).
VLT®6000 HVAC
Mains supply connected to earth:
The RFI switch must be in ON position in order for the
frequency converter to comply with the EMC standard.
Bookstyle IP 20
VLT 6002 - 6011 380 - 460 V
VLT 6002 - 6005 200 - 240 V
Installation
NB!:
The RFI switch is not to be operated with
mains connected to the unit. Check that
the mains supply has been disconnected
before operating the RFI switch.
NB!:
Open RFI switch is only allowed at factory
set switching frequencies.
NB!:
The RFI switch connects the capacitors
galvanically to earth.
The red switches are operated by means of e.g. a
screwdriver. They are set in the OFF position when
they are pulled out and in ON position when they
are pushed in. Factory setting is ON.
Compact IP 20 and NEMA 1
VLT 6002 - 6011 380 - 460 V
VLT 6002 - 6005 200 - 240 V
VLT 6002 - 6011 525 - 600 V
MG.60.C7.02 - VLT is a registered Danfoss trademark
7
VLT®6000 HVAC
Compact IP 20 and NEMA 1
VLT 6016 - 6027 380 - 460 V
VLT 6006 - 6011 200 - 240 V
VLT 6016 - 6027 525 - 600 V
Compact IP 20 and NEMA 1
VLT 6032 - 6042 380 - 460 V
VLT 6016 - 6022 200 - 240 V
VLT 6032 - 6042 525 - 600 V
Compact IP 54
VLT 6102 - 6122 380 - 460 V
Compact IP 54
VLT 6002 - 6011 380 - 460 V
VLT 6002 - 6005 200 - 240 V
Compact IP 20 and NEMA 1
VLT 6052 - 6122 380 - 460 V
VLT 6027 - 6032 200 - 240 V
VLT 6052 - 6072 525 - 600 V
8
Compact IP 54
VLT 6016 - 6032 380 - 460 V
VLT 6006 - 6011 200 - 240 V
MG.60.C7.02 - VLT is a registered Danfoss trademark
Compact IP 54
VLT 6042 - 6072 380 - 460 V
VLT 6016 - 6032 200 - 240 V
VLT®6000 HVAC
Installation
MG.60.C7.02 - VLT is a registered Danfoss trademark
9
■High voltage test
A high voltage test can be carried out by
short-circuiting terminals U, V, W, L1, L2 and L3
and energizing by max. 2.5 kV DC for one second
between this short-circuit and the chassis.
NB!:
The RFI switch must be closed (position
ON) when high voltage tests are carried out.
The mains and motor connection must be
interrupted in the case of high voltage tests of the total
installation if the leakage currents are too high.
■Heat emission from VLT 6000 HVAC
The tables in General technical data show the
power loss P
maximum cooling air temperature t
(W) from VLT 6000 HVAC. The
, is 40°
IN MAX
at 100% load (of rated value).
VLT®6000 HVAC
■Ventilation of integrated VLT 6000 HVAC
The quantity of air required for cooling frequency
converters can be calculated as follows:
1. AddupthevaluesofP
for all the frequency
converters to be integrated in the same panel.
The highest cooling air temperature (t
must be lower than t
(40°C). The day/night
IN, MAX
IN
average must be 5°C lower (VDE 160). The
outlet temperature of the cooling air must
not exceed: t
OUT, MAX
(45° C).
2.Calculate the permissible difference between
the temperature of the cooling air (t
its outlet temperature (t
OUT
):
)and
IN
t = 45° C-tIN.
3.Calculate the required
quantity of air =
insert
tinKelvin
m3/h
The outlet from the ventilation must be placed
above the highest-mounted frequency converter.
Allowancemustbemadeforthepressureloss
across the filters and for the fact that the pressure
is going to drop as the filters are choked.
)present
10
MG.60.C7.02 - VLT is a registered Danfoss trademark
■Electrical installation - earthing of control cables
Generally speaking, control cables must be braided
screened/armoured and the screen must be
connected by means of a cable clamp at both
ends to the metal cabinet of the unit.
VLT®6000 HVAC
Correct earthing
Control cables and cables for serial communication
must be fitted with cable clamps at both ends to
ensure the best possible electrical contact
The drawing below indicates how correct earthing is
carried out and what to be done if in doubt.
Wrong earthing
Do not use twisted cable ends (pigtails), since these
increase the screen impedance at high frequencies.
Protection with respect to earth potential
between PLC and VLT
If the earth potential between the frequency converter
and the PLC (etc.) is different, electric noise may
occur that will disturb the whole system. This
problem can be solved by fitting an equalising
cable, to be placed next to the control cable.
2
Minimum cable cross-section: 16 mm
.
For 50/60 Hz earth loops
If very long control cables are used, 50/60 Hz earth
loops may occur. This problem can be solved by
connecting one end of the screen to earth via a
100nF capacitor (keeping leads short).
Cables for serial communication
Low-frequency noise currents between two frequency
converters can be eliminated by connecting one end
of the screen to terminal 61. This terminal is connected
to earth via an internal RC link. It is recommended
to use twisted-pair cables to reduce the differential
mode interference between the conductors.
Installation
■Tightening-up torque and screw sizes
The table shows the torque required when fitting
terminals to the frequency converter. For VLT
6002-6032, 200-240 V, VLT 6002-6122, 380-460
and 525-600 V the cables must be fastened
with screws. For VLT 6042-6062, 200-240 V
and for VLT 6152-6550, 380-460 V, the cables
must be fastened with bolts.
These figures apply to the following terminals:
Mains terminals (Nos.)L1, L2, L3
Motor terminals (Nos.)U, V, W
Earth terminal (Nos.)94, 95, 99
91, 92, 93
96, 97, 98
MG.60.C7.02 - VLT is a registered Danfoss trademark
11
VLT®6000 HVAC
VLT type
3 x 200 - 240 V
VLT 6002-60050.5-0.6 NmM3
VLT 6006-60111.8 Nm (IP 20)M4
VLT 6006-60161.8 Nm (IP 54)M4
VLT 6016-60273.0 Nm (IP 20)M5
VLT 6022-60273.0 Nm (IP 54)
VLT 60326.0 NmM6
VLT 6042-606211.3 NmM8 (bolt)
VLT type
3 x 380-460 V
VLT 6002-60110.5-0.6 NmM3
VLT 6016-60271.8 Nm (IP 20)M4
VLT 6016-60321.8 Nm (IP 54)M4
VLT 6032-60523.0 Nm (IP 20)M5
VLT 6042-60523.0 Nm (IP 54)
VLT 6062-60726.0 NmM6
VLT 6102-612215 Nm (IP 20)M8
VLT 6152-635219 Nm
VLT 6400-655042 NmM12 (bolt)
Tightening-up
torque
Tightening-up
torque
24 Nm (IP 54)
4)
Screw/bolt
size
2)
M5
Screw/bolt
size
2)
M5
1)3)
M10 (bolt)
3)
3)
3)
3)
3)
3)
3)
Allen
key
size
4mm
4mm
5mm
Allen
key
size
4mm
4mm
5mm
6mm
8mm
■Pre-fuses
See Technical data for correct sizing of pre-fuses.
■Motor connection
The motor must be connected to terminals 96,
97, 98. Earth to terminal 94/95/99.
Nos.
96. 97. 98
U, V, W
No. 94/95/99Earth connection
Motor voltage 0-100 % of mains voltage
See Technical data for correct sizing of
cable cross-sections.
All types of three-phase asynchronous standard
motors can be used with a VLT 6000 HVAC unit.
Small-size motors are normally star-connected.
(220/380 V,
/Y). Large-size
delta-connected (380/660 V,
motors are
/Y). The correct
connection and voltage can be read from
the motor nameplate.
VLT type
3 x 525-600 V
VLT 6002-60110.5-0.6 NmM3
VLT 6016-60271.8 NmM4
VLT 6032-60423.0 Nm
VLT 6052-60726.0 NmM6
VLT 6100-615011.3 NmM8
VLT 6175-627511.3 NmM8
1. Loadsharing terminals 14 Nm/M6, 5 mm Allen key
2. IP 54 units with RFI filter line terminals 6 Nm
3. Allen screws (hexagon)
4. Loadsharing terminals 9.5 Nm/M8 (bolt)
Tightening-up
torque
2)
Screw/bolt
size
3)
M5
3)
■Mains connection
Mains must be connected to terminals 91, 92, 93.
Mains voltage 3 x 200-240 V
91, 92, 93Mains voltage 3 x 380-460 V
L1, L2, L3Mains voltage 3 x 525-600 V
NB!:
Check that the mains voltage fits the mains
voltage of the frequency converter, which
can be seen from the nameplate.
Allen
key
size
4mm
5mm
NB!:
In older motors without phase coil
insulation, a LC filter should be fitted to
the frequency con
verter output. See the
Design Guide or contact Danfoss.
See Technical data for correct sizing of
cable cross-sections.
12
MG.60.C7.02 - VLT is a registered Danfoss trademark
■Direction of motor rotation
The factory setting is for clockwise rotation with the
frequency transformer output connected as follows.
Terminal 96 connected to U-phase
Terminal 97 connected to V-phase
Terminal 98 connected to W-phase
VLT®6000 HVAC
Problemsmayariseatthestartandatlowrpmvalues
if the motor sizes are widely different. This is because
the relatively high ohmic resistance in small motors
calls for a higher voltage at the start and at low rpm
values. In systems with motors connected in parallel,
the electronic thermal relay (ETR) of the frequency
converter cannot be used as motor protection for
the individual motor. Consequently, additional motor
protection is required, such as thermistors in each
motor (or individual thermal relays).
NB!:
Parameter 107 Automatic Motor Adaptation,
AMA and Automatic Energy Optimization,AEO
in parameter 101 Torque characteristics cannot
be used if motors are connected in parallel.
■Motor cables
See Technical data for correct sizing of motor
cable cross-section and length.
Always comply with national and local regulations
on cable cross-sections.
Installation
The direction of motor rotation can be changed by
switching two phases in the motor cable.
■Parallel coupling of motors
VLT 6000 HVAC is able to control several motors
connected in parallel. If the motors are to have
different rpm values, the motors must have
different rated rpm values. Motor rpm is changed
simultaneously, which means that the ratio between
the rated rpm values is maintained across the range.
The total current consumption of the motors is
not to exceed the maximum rated output current
for the frequency converter.
I
VLT,N
NB!:
If an unscreened cable is used, some
EMC requirements are not complied with,
see EMC test results.
If the EMC specifications regarding emission are
to be complied with, the motor cable must be
screened, unless otherwise stated for the RFI filter
in question. It is important to keep the motor cable
as short as possible so as to reduce the noise level
and leakage currents to a minimum.
The motor cable screen must be connected to the
metal cabinet of the frequency converter and to the
metal cabinet of the motor. The screen connections
are to be made with the biggest possible surface (cable
clamp). This is enabled by different installation devices
in the different frequency converters. Mounting with
twisted screen ends (pigtails) is to be avoided, since
these spoil the screening effect at higher frequencies.
If it is necessary to break the screen to install a
motor isolator or motor contactor, the screen must be
continued at the lowest possible HF impedance.
MG.60.C7.02 - VLT is a registered Danfoss trademark
13
■Motor thermal protection
The electronic thermal relay in UL-approved frequency
converters has received UL approval for single
motor protection, as long as parameter 117 Motorthermal protection has been set to ETR Trip and
parameter 105 Motor current I
VLT,N
, has been
programmed for the rated motor current (can be
read from the motor nameplate).
■Earth connection
Since the leakage currents to earth may be higher
than 3.5 mA, the frequency converter must always
be earthed in accordance with applicable na-tional
and local regulations. In order to ensure good
mechanical connection of the earth cable, its cable
2
cross-section must be at least 10 mm
. For added
security, an RCD (Residual Current Device) may be
installed. This ensures that the frequency converter
will cut out if the leakage currents get too high.
See RCD instructions MI.66.AX.02.
VLT®6000 HVAC
■DC bus connection
The DC bus terminal is used for DC back-up,
with the intermediate circuit being supplied
from an external DC source.
Terminal nos.88, 89
t Danfoss if you require further information.
Contac
■High-
voltage relay
The cable for the high-voltage relay must be connected
to terminals 01, 02, 03. The high-voltage relay is
rammed in parameter 323, Relay 1, output.
prog
1
No.
Max Cross-
Torque:0.5-0.6 Nm
Screw size:M3
section:
ay ouput 1
Rel
reak, 1+2 make
1+3 b
0 V AC, 2 Amp
Max 24
VDC10mAor
Min. 24
24 V AC, 1
2
4mm
/10 AW
00 mA
G
■Control card
All terminals for the control cables are located under
the protective cover of the frequency converter. The
protective cover (see drawing below) can be removed
by means of a pointed object - a screwdriver or similar.
14
MG.60.C7.02 - VLT is a registered Danfoss trademark
■Connection examples, VLT 6000 HVAC
The diagram below gives an example of a typical
VLT 6000 HVAC installation.
The mains supply is connected to terminals 91 (L1),
92 (L2) and 93 (L3), while the motor is connected to
96 (U), 97 (V) and 98 (W). These numbers can also be
seen from the terminals of the frequency converter.
An external DC supply or a 12-pulse option can
be connected to terminals 88 and 89. Please ask
Danfoss for a Design Guide to learn more.
Analogue inputs can be connected to terminals 53 [V],
54 [V] and 60 [mA]. These inputs can be programmed
for either reference, feedback or thermistor. See
Analogue inputs in parameter group 300.
VLT®6000 HVAC
There are 8 digital inputs, which can be connected
to terminals 16-19, 27, 29, 32, 33. These inputs
can be programmed in accordance with the table
in Inputs and outputs 300-328.
There are two analogue/digital outputs (terminals
42 and 45), which can be programmed to show
the present status or a process value, such as
. Relay outputs 1 and 2 can be used for
0-f
MAX
giving the present status or a warning.
On terminals 68 (P+) and 69 (N-) RS 485 interface,
the frequency converter can be controlled and
monitored via serial communication.
Installation
MG.60.C7.02 - VLT is a registered Danfoss trademark
15
■Electrical installation, control cables
Max. control cable cross section: 1.5 mm
Torque: 0.5-0.6 Nm
Screw size: M3
See Earthing of screened/armoured control cables
for correct termination of control cables.
2
/16 AWG
VLT®6000 HVAC
No.Function
04, 05Relay output 2 can be used for indicating
status and warnings.
12, 13Voltage supply to digital inputs. For the 24 V
DC to be used for digital inputs, switch 4 on
the control card must be closed, position "on".
16-33Digital inputs. See parameters 300-307 Digital
inputs.
20Ground for digital inputs.
39Ground for analogue/digital outputs. Must
be connected to terminal 55 by means of
a three-wire transmitter. See Examples of
connection.
42, 45Analogue/digital outputs for indicating
frequency, reference, current and torque. See
parameters 319-322 Analogue/digital outputs.
50Supply voltage to potentiometer and thermistor
10 V DC.
53, 54Analogue voltage input, 0 - 10 V DC.
55Ground for analogue voltage inputs.
60Analogue current input 0/4-20 mA. See
parameters 314-316 Terminal 60.
61Termination of serial communication. See
Earthing of screened/armoured con trol cables.
Th is termin al is n ot n orma lly to be u sed .
68, 69RS 485 interface, serial communication.
Where the frequency converter is connected
to a bus, switches 2 and 3 (switches 1- 4 -
see next page) must be closed on the first
and the last frequency converter. On the
remaining frequency converters, switches 2
and 3 must be open. The factory setting is
closed (position on).
16
MG.60.C7.02 - VLT is a registered Danfoss trademark
■Control unit LCP
The front of the frequency converter features a
control panel - LCP(Local Control Panel). This is a
complete interface for operation and programming
of the frequency converter.
The control panel is detachable and can - as an
alternative - be installed up to 3 metres away from
the frequency converter, e.g. on the front panel,
by means of a mounting kit option.
The functions of the control panel can be
divided into five groups:
1. Display
2. Keys for changing display mode
3. Keys for changing program parameters
4. Indicator lamps
5. Keys for local operation
All data are indicated by means of a 4-line
alphanumeric display, which, in normal operation,
is able to show 4 operating data values and 3
operating condition values continuously. During
programming, all the information required for quick,
effective parameter Setup of the frequency converter
will be displayed. As a supplement to the display, there
are three indicator lamps for voltage (ON), warning
(WARNING) and alarm (ALARM), respectively.
All frequency converter parameter Setups can be
changed immediately via the control panel, unless this
function has been programmed to be Locked [1] via
parameter 016 Lock for data change orviaadigital
input, parameters 300-307 Data change lock.
VLT®6000 HVAC
Programming
■Control keys for parameter setup
The control keys are divided into functions. This means
that the keys between display and indicator lamps
are used for parameter Setup, including selecting the
display indication during normal operation.
[DISPLAY MODE] is used for selecting
the indication mode of the display or
whenreturningtotheDisplaymode
from either the Quick menu or the
Extend menu mode.
MG.60.C7.02 - VLT is a registered Danfoss trademark
17
[QUICK MENU] gives access to the
parameters used for the Quick menu.
It is possible to switch between the
Quick menu and the Extend menu
modes.
[EXTEND MENU] gives access to all
parameters. It is possible to switch
between the Extend menu and the
Quick menu modes.
[CHANGE DATA] is used for changing
a setting selected either in the Extend
menu or the Quick menu mode.
[CANCEL] is used if a change of
the selected parameter is not to be
carried out.
[OK] is used for confirming a change
of the parameter selected.
[+/-] is used for selecting parameters
and for changing a chosen
parameter. These keys are also used
to change the local reference.
In addition, the keys are used in
Display mode to switch between
operation variable readouts.
VLT®6000 HVAC
[HAND START] is used if the frequency
converter is to be controlled via the
control unit. The frequency converter
will start the motor, since a start
command is given by means of [HAND
START].
On the control terminals, the following
control signals will still be active when
[HAND START] is activated:
• Hand start - Off stop - Auto start
• Safety Interlock
• Reset
• Coasting stop inverse
• Reversing
• Setup select lsb - Setup select msb
• Jog
• Run permissive
• Lock for data change
• Stop command from serial
communication
NB!:
If parameter 201 Output frequency low limit
is set to an output frequency greater than
f
MIN
0 Hz, the motor will start and ramp up to this
frequency when [HAND START] is activated.
[<>] is used when selecting a
parameter group and for moving
the cursor when changing numerical
values.
■Indicator lamps
At the bottom of the control panel is a red
alarm lamp and a yellow warning lamp, as
well as a green voltage LED.
If certain threshold values are exceeded, the
alarm and/or warning lamp is activated, and a
status or alarm text is displayed.
NB!:
The voltage indicator lamp is activated when
the frequency converter receives voltage.
■Local control
Underneath the indicator lamps are keys
for local control.
[OFF/STOP] is used for stopping the
connected motor. Can be selected as
Enable [1] or Disable [0] via parameter
013. If the stop function is activated,
line 2 will flash.
[AUTO START] is used if the frequency
converter is to be controlled via
the control terminals and/or serial
communication. When a start signal is
active on the control terminals and/or
the bus, the frequency converter will
start.
NB!:
An active HAND-OFF-AUTO signal via the digital
inputs will have higher priority than the control
keys [HAND START]-[AUTO START].
18
MG.60.C7.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC
[RESET] is used for resetting the
frequency converter after an alarm
(trip). Can be selected as Enable [1]
or Disable [0] via parameter 015 Reseton LCP.
See also List of warnings and alarms.
■Display mode
In normal operation, any 4 different operating variables
can be indicated continuously: 1.1 and 1.2 and
1.3 and 2. The present operating s
and warnings that have arisen are shown in line 2
in the form of a number. In the case of alarms, the
alarm in question will be sho
accompanied by an explanatory note. Warnings will
flash in line 2, with an explanatory note in line 1. In
addition, the displ
The arrow indicates the direction of rotation; here the
frequency converter has an active reversing signal. The
arrow body disapp
the output frequency falls below 0.01 Hz. The bottom
line gives the status of the frequency converter.
The scroll lis
data that can be shown for variable 2 in display
mode. Changes are made via the [+/-] keys.
ay shows the active Setup.
ears if a stop command is given or if
t on the next page gives the operating
tatus or alarms
wn in lines 3 and 4,
The left part of the status line indicates the
control element of the frequency converter that is
active. AUTO means that control is via the control
terminals, while HAND indicates that control is
via the local keys on the control unit.
OFF means that the frequency converter ignores all
control commands and stops the motor.
The centre part of the status line indicates the
reference element that is active. REMOTE means that
the reference from the control terminals is active, while
LOCAL indicates that the reference is determined
via the [+/-] keys on the control panel.
The last part of the status line indicates the current
195NA113.10
status, for example "Running", "Stop" or "Alarm".
80.0% 5.08A 2.15kW
40.0Hz
AUTO REMOTE RUNNING
HAND LOCAL STOP
OFF
LOCAL STOPRAMPING
HAND JOGGING
.
.
.
.
STAND BY
SETUP
1
175ZA701.10
1st line
2nd line
VAR 1.1 VAR 1.2 VAR 1.3
SETUP
VAR 2
1
3rd line
STATUS
4th line
■Display mode , cont.
Three operating data values can be shown in the first
display line, while one operating variable can be shown
in the second display line. To be programmed via
parameters 007, 008, 009 and 010 Display read-out.
• Status line (4th line):
■DisplaymodeI:
VLT 6000 HVAC offers different display modes depending on the mode selected for the frequency
converter. The figure on the next page shows t
to navigate between different display modes.
Below is a display mode, in which the frequency
converter is in Auto mode with remote ref
at an output frequency of 40 Hz.
In this display mode, reference and control are
determined via the control terminals.
The text in line 1 gives the operating variable
showninline2.
FREQUENCY
40.0Hz
AUTO REMOTE RUNNING
Line 2 gives the current output frequency
and the active Setup.
SETUP
1
erence
Programming
he way
175ZA683.10
MG.60.C7.02 - VLT is a registered Danfoss trademark
19
Line 4 says that the frequency converter is in Auto mode
with remote reference, and that the motor is running.
■Display mode II:
This display mode makes it possible to have three
operating data values displayed at the same time in
line 1. The operating data values are determined
in parameters 007-010 Display readout.
100% 7.8A 5.9kW
SETUP
50.0Hz
AUTO REMOTE RUNNING
■Display mode III:
This display mode is active as long as the [DISPLAY
MODE] key is kept depressed. In the first line,
operating data names and units of operating data
are displayed. In the second line, operating data 2
remains unchanged. When the key is released, the
different operating data values are shown.
1
175ZA685.10
VLT®6000 HVAC
REF% CURR.A.POW.,KW
SETUP
50.0Hz
AUTO REMOTE RUNNING
■Display mode IV:
This display mode is only active in connection with
local reference, see also Reference handling.Inthis
display mode, the reference is determined via the
[+/-] keys and control is carried out by means of the
keys underneath the indicator lamps. The first line
indicates the required reference. The third line gives
the relative value of the present output frequency at
any given time in relation to the maximum frequency.
The display is in the form of a bar graph.
USE +/- 40Hz
40.0Hz
----60
0
HAND LOCAL RUNNING
1
SETUP
1
176FA156.10
175ZA695.10
20
MG.60.C7.02 - VLT is a registered Danfoss trademark
■Navigation between display modes
Press briefly
HAND LOCAL RUNNING
USE +/- 40Hz
40.0Hz
FREQUENCY
40.0Hz
AUTO REMOTE RUNNING
▲▲
▲
▲▲
SETUP
1
Display mode I
With remote
reference
VLT®6000 HVAC
▲▲
▲
▲▲
▲▲
▲
▲▲
80% 7,8A 5,9 KW
40.0 Hz
0 ---- 60
HAND LOCAL RUNNING
Display mode IV
175ZA697.10
▲▲
▲▲
▲
With local reference
Keep the [DISPLAY
MODE] key down
AUTO REMOTE RUNNING
Display mode II
▲▲
▲
▲▲
REF% CURR.A POW.,KW
40.0 Hz
AUTO REMOTE RUNNING
Display mode III
Programming
MG.60.C7.02 - VLT is a registered Danfoss trademark
21
■Changing data
Regardless of whether a parameter has been
selected under the Quick menu or the Extended
menu, the procedure for changing data is the same.
Pressing the [CHANGE DATA] key allows change
of the selected parameter, and the underlining
in line 4 will flash on the display.
The procedure for changing data depends on whether
the selected parameter represents a numerical
data value or a functional value.
If the chosen parameter represents a numeric data
value, the first digit can be changed by means of
the [+/-] keys. If the second digit is to be changed,
first move the cursor by using the [<>] keys, then
change the data value using the [+/-] keys.
FREQUENCY
24.2 Hz
205 MAX. REFERENCE
000060,000 Hz
5
SETUP
1
175ZA698.10
VLT®6000 HVAC
FREQUENCY
SETUP
50.0
209 JOG FREQUENCY
1
0.0 Hz
The chosen digit flashes. The bottom display
line shows the data value that will be entered
(saved) when signing off with [OK].
■Changing of data value, step-by-step
Certain parameters can be changed both step by
step and infinitely variably. This applies to Motorpower (parameter 102), Motor voltage (parameter
103) and Motor frequency (parameter 104).
This means that the parameters are changed
both as a group of numeric data values and as
numeric data values infinitely variably.
SETUP
1
1
175ZA700.10
The selected digit is indicated by a flashing cursor.
The bottom display line gives the data value that will
be entered (saved) when signing off by pressing the
[OK] button. Use [CANCEL] to cancel the change.
If the selected parameter is a functional value,
the selected text value can be changed by
means of the [+/-] keys.
MOTOR CURRENT
3.90 A
210 REFERENCE TYPE
SUM
SETUP
1
175ZA689.10
The functional value flashes until signing off by pressing
the [OK] button. The functional value has now been
selected. Use [CANCEL] to cancel the change.
■Infinitely variable change of numeric data value
If the chosen parameter represents a numeric data
value, a digit is first selected by means of the [<>] keys.
■Manual initialisation
Disconnect from mains and hold the [DISPLAY
MODE] + [CHANGE DATA] + [OK] keys down while
at the same time reconnecting the mains supply.
Release the keys; the frequency converter has now
been programmed for the factory setting.
The following parameters are not zeroed by means of man
initialisation:
Parameter500, Protocol
600, Operating hours
601, hours run
602, kWh counter
603, Number of power-ups
604, Number of overtemperatures
605, Number of overvoltages
It is also possible to carry out initialisation via
parameter 620 Operating mode.
ual
FREQUENCY
SETUP
50.0 Hz
209 JOG FREQUENCY
0
9 .0 Hz
SETUP
1
1
175ZA699.10
Then the chosen digit is changed infinitely by
means of the [+/-] keys:
22
MG.60.C7.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC
■Quick Menu
The QUICK MENU key gives access to 12 of the
most important setup parameters of the drive. After
programming, the drive will, in many cases, be ready
for operation. The 12 Quick Menu parameters are
Quick MenuParameterDescription
Item NumberName
1001 LanguageSelects language used for all displays.
2102 Motor PowerSets output characteristics of drive based on kW size
3103 Motor VoltageSets output characteristics of drive based on voltage
4104 Motor FrequencySets output characteristics of drive based on nominal
5105 Motor CurrentSets output characteristics of drive based on nominal
6106 Motor Nominal SpeedSets output characteristics of drive based on nominal
7201 Minimum FrequencySets minimum controlled frequency at which motor
8202 Maximum FrequencySets maximum controlled frequency at which motor
9206 Ramp Up TimeSets time to accelerate motor from 0 Hz to nominal
10207 Ramp Down TimeSets time to decelerate motor from nominal motor
11323 Relay 1 FunctionSets function of high voltage Form C relay.
12326 Relay 2 FunctionSets function of low voltage Form A relay.
shown in the table below. A complete description
of the function is given in the parameter
sections of this manual.
of motor.
of motor.
frequency of motor. This is typically equal to line
frequency.
current in amps of motor.
full load speed of motor.
will run.
will run.
motor frequency set in Quick Menu Item 4.
frequency set in Quick Menu Item 4 to 0 Hz.
Programming
MG.60.C7.02 - VLT is a registered Danfoss trademark
23
■Status messages
Status messages appear in the 4th line of the
display - see example below.
The left part of the status line indicates the active
type of control of the frequency converter.
The centre part of the status line indicates
the active reference.
The last part of the status line gives the present
status, e.g. "Running", "Stop" or "Stand by".
80.0% 5.08A 2.15kW
SETUP
40.0Hz
1
AUTO REMOTE RUNNING
HAND LOCAL STOP
OFF
LOCAL STOPRAMPING
HAND JOGGING
.
.
.
.
STAND BY
Ramp operation (RAMPING)
The output frequency is now changed in accordance
with the preset ramps.
Auto-ramp (AUTO RAMP)
Parameter 208 Automatic ramp-up/down is enabled,
i.e. the frequency converter is trying to avoid a trip
from overvoltage by increasing its output frequency.
Sleep Boost (SLEEP .BST)
The boost function in parameter 406 Boost
setpoint is enabled. This function is only possiblein Closed loop operation.
175ZA701.10
Sleep mode (SLEEP)
The energy saving function in parameter 403
Sleep mode timer is enabled. This means that
atpresentthemotorhasstopped,butthatitwill
restart automatically when required.
Start delay (START DEL)
A start delay time has been programmed i
parameter 111 Start delay. When the delay
has passed, the output frequency will start by
rampinguptothereference.
VLT®6000 HVAC
Auto mode (AUTO)
The frequency converter is in Auto mode, i.e. control
is carried out via the control terminals and/or serial
communication. See also Auto start.
Hand mode (HAND)
The frequency converter is in Hand mode, i.e. control
is carried out via the control keys. See Hand start.
OFF (OFF)
OFF/STOP is activated either by means of the control
key, or by the digital inputs Hand start and Auto start
both being a logic "0". See also OFF/STOP
Local reference (LOCAL)
If LOCAL has been selected, the reference is set via the
[+/-] keys on the control panel. See also Display modes.
Remote reference (REM.)
If REMOTE has been selected, the reference is set
via the control terminals or via serial communication.
See also Display modes .
Running (RUNNING)
The motor speed now corresponds to the
resulting reference.
Run request (RUN REQ.)
A start command has been given, but the motor
will be stopped until a Run permissive signal
is received via a digital input.
Jogging (JOG)
Jog has been enabled via a digital input or
via serial communication.
Jog request (JOG REQ.)
A JOG command has been given, but the motor
will remain stopped until a Run permissive signal
is received via a digital input.
Freeze output (FRZ.OUT.)
Freeze output has been enabled via a digital input.
Freeze output request (FRZ.REQ.)
A freeze output command has been given, but the
motor will remain stopped until a Run permissive
signal is received via a digital input.
Reversing and start (START F/R)
Reversing and start [2] on terminal 19 (parameter
303 Digital inputs)andStart [1] on terminal 18
(parameter 302 Digital inputs) are enabled at the
same time. The motor will remain stopped until
one of the signals becomes a logic ‘0’.
24
MG.60.C7.02 - VLT is a registered Danfoss trademark
Automatic Motor Adaptation running (AMA RUN)
Automatic motor adaptation has been enabled in
parameter 107 Automatic Motor Adaptation, AMA.
Automatic Motor Adaptation completed
(AMA STOP)
Automatic motor adaptation has been completed.
The frequency converter is now ready for operation
after the Reset signal has been enabled. Please
note that the motor will start after the frequency
converter has received the Reset signal.
Stand by (STANDBY)
The frequency converter is able to start the motor
when a start command is received.
Stop (STOP)
The motor has been stopped via a stop
signal from a digital input, [OFF/STOP] button
or serial communication.
VLT®6000 HVAC
DC stop (DC STOP)
The DC brake in parameter 114-116 has been enabled.
DRIVE ready (UN. READY)
The frequency converter is ready for operation, but
terminal 27 is a logic "0" and/or a Coasting command
has been received via the serial communication.
Not ready (NOT READY)
The frequency converter is not ready for operation,
because of a trip or because OFF1, OFF2
or OFF3 is a logic ‘0’.
Start disabled (START IN.)
This status will only be displayed if, in parameter
599 Statemachine, Profidrive [1] has been selected
and OFF2 or OFF3 is a logic ‘0’.
Exceptions XXXX (EXCEPTIONS XXXX)
The microprocessor of the control card has stopped
and the frequency converter is out of operation.
The cause may be noise on the mains, motor
or control cables, leading to a stop of the
control card microprocessor.
Check for EMC-correct connection of these cables.
HVAC
All about VLT 6000
MG.60.C7.02 - VLT is a registered Danfoss trademark
25
VLT®6000 HVAC
■List of warnings and alarms
The table gives the different warnings and alarms
and indicates whether the fault locks the frequency
converter. After Trip locked, the mains supply must be
cut and the fault must be corrected. Reconnect the
mains supply and reset the frequency converter before
being ready. A Trip can be reset manually in three ways
1. Via the control key [RESET]
2. Via a digital input
3. Via serial communication In addition, an
automatic reset may be selected in parameter
400 Reset function.
Wherever a cross is placed under both Warning and
Alarm, this can mean that a warning precedes the
alarm. It can also mean that it is possible to program
whether a given fault is to result in a warning or an
alarm. This is possible, e.g. in parameter 117 Motorthermal protection. Afteratrip,themotorwillbe
coasting and on the frequency converter alarm and
warning will flash. If the fault is removed, only the
alarm will flash. After a reset, the frequency converter
will be ready to start operation again.
No.DescriptionWarningAlarmTrip locked
110 Volts low (10 VOLT LOW)x
2Live zero fault (LIVE ZERO ERROR)xx
4Mains imbalance (MAINS IMBALANCE)xxx
5Voltage warning high (DC LINK VOLTAGE HIGH)x
6Voltage warning low (DC LINK VOLTAGE LOW)x
7Overvoltage (DC LINK OVERVOLT)xx
8Undervoltage (DC LINK UNDERVOLT)xx
9Inverter overloaded (INVERTER TIME)xx
10Motor overloaded (MOTOR TIME)xx
11Motor thermistor (MOTOR THERMISTOR)xx
12Current limit (CURRENT LIMIT)xx
13Overcurrent (OVERCURRENT)xxx
14Earth fault (EARTH FAULT)xx
15Switch mode fault (SWITCH MODE FAULT)xx
16Short-circuit (CURR.SHORT CIRCUIT)xx
17Serial communication timeout (STD BUSTIMEOUT)xx
18HPFB bus timeout (HPFB TIMEOUT)xx
19Fault in EEprom on power card (EE ERROR POWER)x
20Fault in EEprom on control card (EE ERROR CONTROL)x
22Auto-optimisation not OK (AMA FAULT)x
29Heat-sink temperature too high (HEAT SINK OVERTEMP.)x
30Motor phase U missing (MISSING MOT.PHASE U)x
31Motor phase V missing (MISSING MOT.PHASE V)x
32Motor phase W missing (MISSING MOT.PHASE W)x
34HPFB communication fault (HPFB COMM. FAULT)xx
37Inverter fault (GATE DRIVE FAULT)xx
39Check parameters 104 and 106 (CHECK P.104 & P.106)x
40Check parameters 103 and 105 (CHECK P.103 & P.106)x
41Motor too big (MOTOR TOO BIG)x
42Motor too small (MOTOR TOO SMALL)x
60Safety stop (EXTERNAL FAULT)x
61Output frequency low (FOUT < FLOW)x
62Output frequency high (FOUT > FHIGH)x
63Output current low (I MOTOR < I LOW)xx
64Output current high (I MOTOR > I HIGH)x
65Feedback low (FEEDBACK < FDB LOW)x
66Feedback high (FEEDBACK > FDB HIGH)x
67Reference low (REF. < REF. LOW)x
68Reference high (REF. > REF. HIGH)x
69Temperature auto derate (TEMP.AUTO DERATE)x
80Fire mode was active (FIRE MODE WAS ACTIVE)xx
81RTC not ready (RTC NOT READY)x
99Unknown fault (UNKNOWN ALARM)xx
26
MG.60.C7.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC
■Index
C
control panel - LCP....................................................... 17