Danfoss VLT 6000 series Operating Instructions Manual

Contents
VLT®6000 HVAC Series
Introduction to HVAC
Software version ....................................................................................................... 4
Safety regulations ..................................................................................................... 5
Introduction to Operating Instructions ....................................................................... 7
Available literature ..................................................................................................... 8
VLT 6000 Advantages in a HVAC installation ............................................................ 8
Control principle ....................................................................................................... 9
AEO - Automatic Energy Optimization .................................................................... 10
Example of application - Speed control of fan in ventilation system ......................... 11
Example of application - Constant pressure regulation in water supply system ....... 12
Fire mode ............................................................................................................... 13
CE labelling ............................................................................................................ 15
PC software and serial communication ................................................................... 15
Unpacking and ordering a VLT frequency converter ................................................ 16
Type code ordering number string ......................................................................... 16
Ordering form ......................................................................................................... 20
...................................................................................... 4
Installation ......................................................................................................... 21
Mains supply (L1, L2, L3) ....................................................................................... 21
Max. imbalance of supply voltage .......................................................................... 21
Technical data, mains supply 3 x 200-240V ............................................................ 26
Technical data, mains supply 3 x 380-460V ............................................................ 28
Technical data, mains supply 3 x 525-600 V ........................................................... 33
Fuses ..................................................................................................................... 38
Mechanical dimensions .......................................................................................... 41
Mechanical installation ............................................................................................ 45
General information about electrical installation ...................................................... 48
High voltage warning .............................................................................................. 48
Earthing .................................................................................................................. 48
Cables .................................................................................................................... 48
Screened/armoured cables .................................................................................... 48
Extra protection with regard to indirect contact ....................................................... 48
RFI switch .............................................................................................................. 50
High voltage test .................................................................................................... 53
Heat emission from VLT 6000 HVAC ...................................................................... 53
Ventilation of integrated VLT 6000 HVAC ................................................................ 53
EMC correct electrical installation ........................................................................... 53
Use of EMC-correct cables .................................................................................... 55
Electrical installation - earthing of control cables ..................................................... 56
Electrical installation, enclosures ............................................................................. 57
Tightening-up torque and screw sizes .................................................................... 64
Mains connection ................................................................................................... 64
Motor connection ................................................................................................... 64
Direction of motor rotation ...................................................................................... 65
Motor cables .......................................................................................................... 65
Motor thermal protection ........................................................................................ 66
Earth connection .................................................................................................... 66
Installation of 24 Volt external DC supply ................................................................ 66
DC bus connection ................................................................................................ 66
High-voltage relay ................................................................................................... 66
MG.61.A5.02 - VLT is a registered Danfoss trademark
1
VLT®6000 HVAC Series
Control card ........................................................................................................... 66
Electrical installation, control cables ........................................................................ 67
Switches 1-4 .......................................................................................................... 68
Bus connection ...................................................................................................... 68
Connection examples, VLT 6000 HVAC .................................................................. 69
Programming .................................................................................................... 71
Control unit LCP ..................................................................................................... 71
Control keys for parameter setup ........................................................................... 71
Indicator lamps ....................................................................................................... 72
Local control .......................................................................................................... 72
Display mode ......................................................................................................... 73
Navigation between display modes ........................................................................ 75
Changing data ........................................................................................................ 76
Manual initialisation ................................................................................................. 76
Quick Menu ............................................................................................................ 77
Operation and Display 001-017 .............................................................................. 79
The Setup configuration ......................................................................................... 79
Setup of user-defined readout ................................................................................ 80
Load and Motor 100-117 ....................................................................................... 86
Configuration .......................................................................................................... 86
Motor power factor (Cos ø) .................................................................................... 91
Reference handling ................................................................................................. 93
Reference type ....................................................................................................... 96
Inputs and outputs 300-365 ................................................................................. 101
Analogue inputs ................................................................................................... 105
Analog/digital outputs ........................................................................................... 108
Relay outputs ...................................................................................................... 111
Application functions 400-427 .............................................................................. 115
Sleep mode .......................................................................................................... 116
PID for process control ......................................................................................... 121
PID overview ........................................................................................................ 123
Feedback handling ............................................................................................... 123
Service functions 600-631 .................................................................................... 130
Electrical installation of the relay card .................................................................... 135
Description of Real Time Clock ............................................................................. 136
All about VLT 6000 HVAC .......................................................................... 139
Status messages .................................................................................................. 139
List of warnings and alarms .................................................................................. 141
Aggressive environments ...................................................................................... 147
Calculation of resulting reference .......................................................................... 147
Galvanic isolation (PELV) ....................................................................................... 148
Earth leakage current ........................................................................................... 148
Extreme running conditions .................................................................................. 149
Peak voltage on motor ......................................................................................... 150
Switching on the input .......................................................................................... 150
Acoustic noise ...................................................................................................... 151
Derating for ambient temperature ......................................................................... 151
Derating for air pressure ....................................................................................... 152
Derating for running at low speed ......................................................................... 152
Derating for long motor cables or cables with larger cross-section ....................... 152
Derating for high switching frequency ................................................................... 152
Vibration and shock .............................................................................................. 153
2
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
Air humidity ......................................................................................................... 153
Efficiency ............................................................................................................. 154
Mains supply interference/harmonics .................................................................... 155
Power factor ........................................................................................................ 155
EMC test results (Emission, Immunity) .................................................................. 156
EMC Immunity ..................................................................................................... 157
Definitions ........................................................................................................... 159
Parameter overview and factory settings .............................................................. 161
Index .................................................................................................................... 168
MG.61.A5.02 - VLT is a registered Danfoss trademark
3
VLT®6000 HVAC Series
VLT 6000 HVAC
Operating Instructions Software version: 3.0x
These Operating Instructions can be used for all VLT 6000 HVAC frequency converters with software version 3.0x. The software version number can be seen from parameter
624.
175ZA691.16
4
MG.61.A5.02 - VLT is a registered Danfoss trademark
The voltage of the frequency converter is dangerous whenever the equipment
is connected to mains. Incorrect installation of the motor or the frequency converter may cause damage to the equipment, serious personal injury or death. Consequently, the instructions in this manual, as well as national and local rules and safety regulations, must be complied with.
Safety regulations
1. The frequency converter must be disconnected
from mains if repair work is to be carried out. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.
2. The [OFF/STOP] key on the control panel of
the frequency converter does n the equipment from mains and is thus n be used as a safety switch.
3. Correct protective earthing of the equipment
must be established, the user must be protected against supply voltage, and the motor must be protected against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is included in
the factory setting. Parameter 117, Motor thermal protection default value is ETR trip 1.
ote: The function is initialised at 1.0 x rated
N motor current and rated motor frequency (see parameter 117, Motor thermal protection).
ot disconnect
ot to
VLT®6000 HVAC Series
6. Do n
7. Reliable galvanic isolation (PELV) is not complied
8. Please note that the frequency converter has
Warning against unintended start
1. The motor can be brought to a stop by
2. While parameters are being changed, the
3. A motor that has been stopped may start if faults
ot remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.
with if the RFI switch is placed in OFF position. This means that all control in - and outputs can only be considered low-voltage terminals withbasicgalvanicisolation.
more voltage inputs than L1, L2 and L3, when the DC-bus terminals are used. Check that a disconnected and that the necessary time has passed before repair work is commenced.
means of digital commands, bus commands, references or a local stop, while the frequency converter is connected to mains. If personal safety considerations make it necessary to ensure that no unintended start occurs, t stop functions are not sufficient.
motor may start. Consequently, t [OFF/STOP] must always be activated, following which data can be modified.
occur in the electronics of the frequency converter, or if a temporary overload or a fault in the supply mains or the motor connection ceases.
ll voltage inputs have been
he stop key
HVAC
Introduction to
hese
MG.61.A5.02 - VLT is a registered Danfoss trademark
Use on isolated mains
See section RFI Switch regarding use on isolated mains.
It is important to follow the recommendations regarding installation on IT-mains, since sufficient protection ofthecompleteinstallationmustbeobserved. Not taking care using relevant monitoring devices for IT-mains may result in damage.
5
VLT®6000 HVAC Series
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
175HA490.15
Using VLT 6002 - 6005, 200-240 V: Wait at least 4 minutes Using VLT Using VLT Using VLT
6006 - 6062, 200-240 V: Wait at least 15 minutes 6002 - 6005, 380-460 V: Wait at least 4 minutes
6006 - 6072, 380-460 V: Wait at least 15 minutes Using VLT 6102 - 6352, 380-460 V: Wait at least 20 minutes Using VLT 6402 - 6602, 380-460 V: Wait at least 40 minutes Using VLT Using VLT Using VLT Using VLT Using VLT
6002 - 6006, 525-600 V: Wait at least 4 minutes
6008 - 6027, 525-600 V: Wait at least 15 minutes
6032 - 6072, 525-600 V: Wait at least 30 minutes
6102 - 6402, 525-600 V: Wait at least 20 minutes
6502 - 6652, 525-600 V: Wait at least 30 minutes
6
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
Introduction to Operating Instructions
These Operating Instructions are a tool intended for persons who are to install, operate and program the VLT 6000 HVAC. A VLT 6000 HVAC comes with Operating Instructions as well as Quick Setup Guide. In addition, a Design
Guide can be ordered for use when designing installations that will include a VLT 6000 HVAC. See Available literature.
Operating Instructions: These are instructions in how to ensure optimum mechanical and
electrical installation, commissioning and service. The Operating Instructions also include a description of the software parameters, thereby enabling easy adaptation of the VLT 6000 HVAC to your application.
Quick Setup Guide: Helps you to quickly install and commission the VLT 6000 HVAC.
Design Guide: Used when designing installations that include a VLT 6000 HVAC. The
Design Guide gives detailed information about VLT 6000 HVAC and HVAC installations, including a selection tool to enable you to choose the right VLT 6000 HVAC with its relevant options and modules. The Design Guide also contains examples of the most common HVAC applications. Furthermore, the Design Guide has all information relating to serial communication.
HVAC
Introduction to
These Operating Instructions are divided into four sections with information about VLT 6000 HVAC.
Introduction to HVAC: This section tells you the advantages you can obtain by using a VLT
6000 HVAC - such as AEO, Automatic Energy Optimization, RFI filters and other HVAC-relevant functions. This section also contains examples of application as well as information about Danfoss and CE-labelling.
Installation: This section tells you how to carry out mechanically correct installation
of the VLT 6000 HVAC. In addition, this section includes a description of how to ensure that the installation of your VLT 6000 HVAC is EMC-correct. Furthermore, a list is given of mains and motor connections, together with a description of the control card terminals.
Programming: This section describes the control unit and the software parameters for
the VLT 6000 HVAC. Also included is a guide to the Quick Setup menu, which allows you to get started on your application very quickly.
All about VLT 6000 HVAC This section gives information about status, warning and error
messages from the VLT 6000 HVAC. Additionally, information is given on technical data, service, factory settings and special conditions.
es a general warning
Indicat
es a high-voltage warning
Indicat
NB!:
Indicates something to be noted by the reader
MG.61.A5.02 - VLT is a registered Danfoss trademark
7
VLT®6000 HVAC Series
Available literature
Below is a list of the literature available for VLT 6000 HVAC. It must be noted that there may be deviations from one country to the next.
Supplied with the unit:
Operating instructions ....................................................................................................................... MG.61.AX.YY
Quick Setup ...................................................................................................................................... MG.60.CX.YY
High Power Introduction Guide ........................................................................................................... MI.90.JX.YY
Communication with VLT 6000 HVAC:
Profibus Manual ................................................................................................................................ MG.90.DX.YY
Metasys N2 Manual .......................................................................................................................... MG.60.FX.YY
LonWorks Manual ............................................................................................................................. MG.60.EX.YY
Landis/Staefa Apogee FLN Manual ................................................................................................... MG.60.GX.YY
Modbus RTU Manual ........................................................................................................................ MG.10.SX.YY
DeviceNet Manual ............................................................................................................................. MG.50.HX.YY
Instructions for VLT 6000 HVAC:
LCP Remote Kit IP20 .......................................................................................................................... MI.56.AX.51
LCP Remote Kit IP54 .......................................................................................................................... MI.56.GX.52
LC-filter ............................................................................................................................................... MI.56.DX.51
IP20 terminal cover ............................................................................................................................. MI.56.CX.51
Please also refer to our web site http://drives.dan­foss.com for information about new literature.
Various literature for VLT 6000 HVAC:
Operating Instructions ....................................................................................................................... MG.60.AX.YY
Design Guide .................................................................................................................................... MG.61.BX.YY
Data sheet ........................................................................................................................................ MD.60.AX.YY
VLT 6000 HVAC Cascade Controller ................................................................................................... MG.60.IX.YY
X = version number YY = language version
VLT 6000 Advantages in a HVAC installation
One advantage involved in using a VLT 6000 HVAC is that this unit has been designed to regulate the speed of fans and rotary pumps while consuming the smallest possible amount of energy. Consequently, if a VLT 6000 HVAC is used in a HVAC installation, optimum energy savings are guaranteed, since less energy is used with a frequency converter than with the traditional HVAC regulation principles. Another advantage in using the VLT 6000 HVAC is that regulation is improved and can easily adapt to a new flow or pressure requirement in an installation. The use of a VLT 6000 HVAC offers the following additional advantages:
VLT 6000 HVAC has been designed for
HVAC applications.
A wide power range - from 1.1-500 kW
units with a unique design.
IP 20 and IP 54 enclosures that can be mounted
side by side. For power sizes 90kW ( 30kW for 200 V) IP 00 is also available.
All unit types, except 525-600 V units, are available
with an integral RFI filter, complying with EN 55011 class A1 in the case of a 150 m screened/armoured motor cable and EN 55011 class B in the case of a screened/armoured motor cable up to 50 m long.
User-friendly design, which makes VLT 6000 HVAC
easy to install, both mechanically and electrically.
Detachable LCP control panel with Hand-Off-Auto
buttons and a graphics display of local speed.
High starting torque owing to Automatic
Energy Optimization (AEO).
Automatic Motor Adaptation (AMA) ensures
optimum motor utilisation.
Integral PID regulator with option of connecting
two feedback signals (in connection with zoning), as well as setting of two set-points.
8
MG.61.A5.02 - VLT is a registered Danfoss trademark
Sleep mode, which automatically turns the
motor off, e.g. when there is no need for more pressure or flow in a system.
The "flying start" function enables the unit
to catch a rotating fan.
VLT®6000 HVAC Series
Automatic ramp up/down to ensure that
the VLT 6000 HVAC will not trip during acceleration or deceleration.
All standard units have three integral, serial protocols
- RS 485 FC protocol, Johnsons Metasys N2 and Landis/Staefa Apogee FLN. Communication option cards that can be connected are LonWorks, DeviceNet, Modbus RTU and Profibus.
Control principle
A frequency converter rectifies AC voltage from mains into DC voltage, after which this DC voltage is converted into a AC current with a variable amplitude and frequency.
1. Mains voltage 3 x 200 - 240 3 x 380 - 460 V AC, 50 / 60 Hz. 3 x 525 - 600 V AC, 50 / 60 Hz.
. Rectifier
2 A three-pha current into DC current.
3
. Intermediate circuit
DC voltage = 1.35 x mains voltage [V].
4
. Intermediate circuit coils Even out t the harmonic current feedback to the mains supply.
VAC,50/60Hz.
se rectifier bridge that rectifies AC
he intermediate circuit voltage and reduce
The motor is thus supplied with variable voltage and frequency, which enables infinitely variable speed control of three-phased, standard AC motors.
. Intermediate circuit capacitors
5 Even out the intermediate circuit voltage.
6
. Inverter Converts DC voltage into variable AC voltage withavariablefrequency.
. Motor voltage
7 Variable AC voltage, 0-100% of mains supply voltage.
8
. Control card This is where to find the computer that controls the inverter which generates the pulse pattern by which the DC voltage is converted into variable AC voltage with a variable frequency.
HVAC
Introduction to
MG.61.A5.02 - VLT is a registered Danfoss trademark
9
AEO - Automatic Energy Optimization
Normally, the U/f characteristics have to be set on the basis of the expected load at different frequencies. However, knowing the load at a given frequency in an installation is often a problem. This problem can be solved by using a VLT 6000 HVAC with its integral Automatic Energy Optimization (AEO), which ensures optimum energy utilization. All VLT 6000 HVAC units feature this function as a factory setting, i.e. it is not necessary to adjust the frequency converter U/f ratio in order to obtain maximum energy savings. In other frequency converters, the given load and voltage/frequency ratio (U/f) must be assessed to carry out correct setting of the frequency converter. Using Automatic Energy Optimization (AEO), you no longer need to calculate or assess the system characteristics of the installation, since Danfoss VLT 6000 HVAC units guarantee optimum, load-dependent energy consumption by the motor at all times.
The figure on the right illustrates the working range of the AEO function, within which energy optimization is enabled.
VLT®6000 HVAC Series
If the AEO function has been selected in parameter 101, Torque characteristics, this function will be constantly active. If there is a major deviation from the optimum U/f ratio, the frequency converter will quickly adjust itself.
Advantages of the AEO function
Automatic energy optimization
Compensation if an oversize motor is used
AEO matches operations to daily or
seasonal fluctuations
Energy savings in a constant air volume system
Compensation in the oversynchronous
working range
Reduces acoustic motor noise
10
MG.61.A5.02 - VLT is a registered Danfoss trademark
Example of application - Speed control of
fan in ventilation system
The AHU installation is able to distribute air throughout the building or to one or several parts of a building. Normally, an AHU installation consists of a fan and a motor that supply air, a fan scroll and a duct system with filters. If centralised air distribution is applied, the efficiency of the installation will increase and major energy savings can be made. A VLT 6000 HVAC enables excellent control and monitoring, thereby ensuring perfect conditions in the building at all times.
VLT®6000 HVAC Series
This example shows an application with Run permissive, warning against no load and warning for filter change. The Run permissive function ensures that the frequency converter will not start the motor until the discharge damper has opened. If the V-belt to the fan breaks and if the filter is to be changed, this application will also give a warning on an output.
HVAC
Introduction to
Set the following parameters: Par. 100 Configuration Open loop [0] Par. 221 Warning: Low current, I
LOW
Par. 224 Warning: High frequency, f
HIGH
Depends on unit
Par. 300 Terminal 16 Digital inputs Run permissive [8] Par. 302 Terminal 18 Digital inputs Start [1] Par. 308 Terminal 53, analogue input voltage Reference [1] Par. 309 Terminal 53, min. scaling 0 v Par. 310 Terminal 53, max. scaling 10 v Par. 319 Output Output frequency greater than f Par. 323 Relay 1 Start command active [27] Par. 326 Relay 2 Alarm or warning [12] Par. 409 Function at no load Warning [1]
HIGH
par. 224
MG.61.A5.02 - VLT is a registered Danfoss trademark
11
Example of application - Constant pressure
regulation in water supply system
The demand for water from waterworks varies considerably during the course of a day. In the night, practically no water is used, while in the morning and in the evening the consumption is high. In order to maintain a suitable pressure in the water supply lines in relation to the current demand, the water supply pumps are equipped with speed control. The use of frequency converters enables the energy consumed by the pumps to be kept at a minimum, while optimizing the water supply to consumers.
VLT®6000 HVAC Series
A VLT 6000 HVAC with its integral PID controller ensures simple and quick installation. For example, an IP54 unit can be mounted close to the pump on the wall and the existing line cables can be used as mains supply to the frequency converter. A Pressure transmitter (e.g. Danfoss MBS 33 0-10) bar can be fitted a couples of metres from the joint outlet point from the waterworks to obtain closed loop regulation. Danfoss MBS 33 is a two-wire transmitter (4-20 mA) that can be powered directly from a VLT 6000 HVAC. The required setpoint (e.g. 5 bar) can be set locally in parameter 418 Setpoint 1.
Set the following parameters: Par. 100 Configuration Closed loop [1] Par. 205 Maximum reference 10 bar Par. 302 Terminal 18 Digital inputs Start [1] Par. 314 Terminal 60, analog input current Feedback signal [2] Par. 315 Terminal 60, min. scaling 4 mA Par. 316 Terminal 60, max. scaling 20 mA Par. 403 Sleep mode timer 10 sec. Par. 404 Sleep frequency 15 Hz Par. 405 Wake-up frequency 20 Hz Par. 406 Boost setpoint 125% Par. 413 Minimum feedback 0 Par. 414 Maximum feedback 10 bar Par. 415 Process units Bar [16] Par. 418 Setpoint 1 5 bar Par. 420 PID normal/inverse control Normal Par. 423 PID proportional gain 0.5-1.0 Par. 424 PID integration time 3-10 Par. 427 PID low pass filter 0.5-1.5
12
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
Fire mode
NB!:
Please note the frequency converter is only one component of the HVAC system.
Correct function of Fire Mode depends on the correct design and selection of system components. Ventilation systems working in life safety applications have to be approved by the local fire Authorities.
Non-interruption of the frequency converter due to Fire Mode operation may cause over pressure and result in damage to HVAC system and components, including dampers and air ducts. The frequency converter itself may be damaged and it may cause damage or fire. Danfoss A/S accepts no responsibility for errors, malfunctions personal injur y or any damage to the frequency converter itself or components herein, HVAC systems and components herein or other property when the frequency converter has been programmed forFire Mode. In no event shall Danfossbe liable to the end u ser orany other party for any direct or indirect, special or consequential damage or loss suffered by such party, which has occurred due to the frequency converter being programmed and operated in Fire Mode
To be able to use Fire Mode please also note that input 27 must be "high" and no coast bit present via fieldbus. To ensure that no coast can interrupt Fire Mode via fieldbus please select Digital Input [0] in par.
503. Then coasting via fieldbus disabled.
HVAC
Introduction to
TheFireModefunctionismadetoensuretheVLT 6000 can run without interruption. This means most alarms and warnings will not cause a trip and trip lock is disabled. This is useful in case of fire or other emergencies. Until the motor wires or the frequency converter itself are destroyed every attempt is made to keep running. A warning will flash when these limits have been exceeded. If the warning still flashes after a power cycle please contact your local Danfoss supplier. In the following is a table to show the alarms and when the frequency converter changes state depending on selection in parameter 430. Trip and lock ([0] in parameter 430) are valid in normal operation mode.FireModetripandreset([1]or[2]inparameter
430) means that a reset is automatically performed without the need of manual resetting. Go to Fire Mode bypass ([3] in parameter 430) is valid in case one of the mentioned alarms causes a trip. After the in parameter 432 selected time delay has passed an output is set. This output is programmed in parameter 319, 321, 323 or 326. If a relay option is fitted it can also be selected in parameter 700, 703, 706 or 709. In parameter 300 and 301 it can be selected if the logic, for the Fire Mode activation, shall be active high or low. Please note parameter 430 must be different to[0]fortheFireModetobeenabled.
MG.61.A5.02 - VLT is a registered Danfoss trademark
13
VLT®6000 HVAC Series
No. Description TRIP
[0]
2 Live zero fault
(LIVE ZERO ERROR)
4 Mains imbalance
(MAINS IMBALANCE)
7 Overvoltage
(DC LINK OVERVOLT)
8 Undervoltage
(DC LINK UNDERVOLT)
9 Inverter overloaded
(INVERTER TIME)
10 Motor overloaded
(MOTOR TIME)
11 Motor thermistor(MOTOR
THERMISTOR)
12 Current limit
(CURRENT LIMIT)
13 Overcurrent
(OVERCURRENT)
14 Earth fault
(EARTH FAULT)
15 Switch mode fault
(SWITCH MODE FAULT)
16 Short-circuit
(CURR.SHORT CIRCUIT)
17 Serial communication timeout
(STD BUSTIMEOUT)
18 HPFB bus timeout
(HPFB TIMEOUT)
22 Auto-optimation fault
(AMA FAULT)
29 Heat-sink temperature too
high (HEAT SINK OVERTEMP.)
30 Motor phase U missing
(MISSING MOT.PHASE U)
31 Motor phase V missing
(MISSING MOT.PHASE V)
32 Motor phase W missing
(MISSING MOT.PHASE W)
34 HPFB communication fault
(HPFB TIMEOUT)
37 Inverter fault (GATE DRIVE
FAULT)
60 Safety stop
(EXTERNAL FAULT)
63 Output current low
(I MOTOR < I LOW)
80 Fire mode was active
(FIREMODEWASACTIVE)
99 Unknown fault
(UNKNOWN FAULT)
X
x x x
x
x
x
x
x
x
x x x x
x x x x
x x x x
x x x x
x
x
x
x x x
x
x
x
x
x x x x
x
x
x
x x
LOCK
[0]
FIRE MODE Trip & reset
[1], [2]
Go to FIRE MODE BYPASS [3]
14
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
CE labelling
What is CE labelling?
The purpose of CE labelling is to avoid technical obstacles to trade within EFTA and the EU. The EU has introduced the CE label as a simple way of showing whether a product complies with the relevant EU directives. The CE label says nothing about the specifications or quality of the product. Frequency converters are regulated by three EU directives:
The machinery directive (98/37/EEC)
All machines with critical moving parts are covered by the machinery directive, which came into force on 1 January 1995. Since a frequency converter is largely electrical, it does not fall under the machinery directive. However, if a frequency converter is supplied for use in a machine, we provide information on safety aspects relating to the frequency converter. We do this by means of a manufacturersdeclaration.
The low-voltage directive (73/23/EEC)
Frequency converters must be CE labelled in accordance with the low-voltage directive, which came into force on 1 January 1997. The directive applies to all electrical equipment and appliances used in the 50 ­1000 Volt AC and the 75 - 1500 Volt DC voltage ranges. Danfoss CE labels in accordance with the directive and issues a declaration of conformity upon request.
The EMC directive (89/336/EEC)
EMC is short for electromagnetic compatibility. The presence of electromagnetic compatibility means that the mutual interference between different components/appliances is so small that the functioning of the appliances is not affected. The EMC directive came into force on 1 January 1996. Danfoss CE labels in accordance with the directive and issues a declaration of conformity upon request. In order that EMC-correct installation can be carried out, this manual gives detailed instructions for installation. In addition, we specify the standards which our different products comply with. We offer the filters that can be seen from the specifications and provide other types of assistance to ensure the optimum EMC result.
In the great majority of cases, the frequency converter is used by professionals of the trade as a complex component forming part of a larger appliance, system orinstallation. Itmustbenotedthattheresponsibility for the final EMC properties of the appliance, system or installation rests with the installer.
NOTE: VLT 6001-6072, 525-600 V are not CE labelled.
HVAC
Introduction to
PC software and serial communication
Danfoss offers various options for serial communication. Using serial communication, it is possible to monitor, program and control one or several frequency converters from a centrally located computer. All VLT 6000 HVAC units have a RS 485 port as standard with a choice of four protocols. The protocols selectable in parameter 500 Protocols are:
FC protocol
Johnson Controls Metasys N2
Landis/Staefa Apogee FLN
Modbus RTU
A bus option card allows higher transmission speed than RS 485. In addition, a higher number of units can be linked to the bus and alternative transmission media can be used. Danfoss offers the following option cards for communication:
Profibus
LonWorks
DeviceNet
Information on the installation of various options is not included in this manual.
available for this purpose. It can be used to monitor, program and control one or several VLT 6000 HVAC units. For further information, see the Design Guide for VLT 6000 HVAC or contact Danfoss.
500-566 Serial communication
NB!:
Information on the use of RS-485 serial interface is not included i further information, see the Design Guide for
VLT 6000 HVAC or contact Danfoss.
n this manual. For
Using the RS 485 port enables communication, e.g.
TM
with a PC. A Windows
MG.61.A5.02 - VLT is a registered Danfoss trademark
program, called MCT 10,is
15
VLT®6000 HVAC Series
Unpacking and ordering a VLT frequency c onverter
If you are in doubt as to which frequency converter you have received and which options it contains, use the following to find out.
Type code ordering number string
On the basis of your order, the frequency converter is given an ordering number that can be seen from the nameplate on the unit. The number may look as follows:
VLT-6008-H-T4-B20-R3-DL-F10-A00-C0
This means that the frequency converter ordered is a VLT 6008 for three-phase mains voltage of 380-460 V (T4) in Bookstyle enclosure IP 20 (B20). The hardware variant is with integral RFI filter, classes A & B (R3). The frequency converter features a control unit (DL)witha PROFIBUS option card (F10). No option card (A00) and no conformal coating (C0) Character no. 8 ( H) indicates the application range of the unit: H =HVAC.
IP 00: This enclosure is only available for the larger power sizes of the VLT 6000 HVAC series. It is recommended for installation in standard cabinets. IP 20 Bookstyle: This enclosure is designed for cabinet installation. It takes up a minimum of space and can be fitted side-by-side without installation of extra cooling equipment. IP 20/NEMA 1: This enclosure is used as standard enclosure for VLT 6000 HVAC. It is ideal for cabinet installation in areas where a high degree of protection is required. This enclose also permits side-by-side installation. IP 54: This enclosure can be fitted direct to the wall. Cabinets are not required. IP 54 units can also be installed side-by-side.
Hardware variant The units in the programme are available in the following hardware variants: ST: Standard unit with or without control unit.
WithoutDCterminals,exceptfor VLT 6042-6062, 200-240 V
VLT 6016-6072, 525-600 V SL: Standard unit with DC terminals. EX: Extended unit with control unit, DC terminals,
connection of external 24 V DC supply for
back-up of control PCB. DX: Extended unit with control unit, DC terminals,
built-in mains fuses and disconnector,
connection of external 24 V DC supply for
back-up of control PCB. PF: Standard unit with 24 V DC supply for back-up
of control PCB and built-in main fuses. No DC
terminals. PS: Standard unit with 24 V DC supply for back-up
of control PCB. No DC terminals. PD: Standard unit with 24 V DC supply for back-up
of control PCB, built-in main fuses and
disconnect. No DC terminals.
RFI filter Bookstyle units always come with an integral RFI filter that complies with EN 55011-B with 20 m screened/armoured motor cable and EN 55011-A1 with 150 m screened/armoured motor cable. Units for mains voltage of 240 V and a motor power of up to and including 3.0 kW (VLT 6005) and units for a mains voltage of 380-460 V and a motor power of up to 7.5 kW (VLT 6011) are always supplied with an integral class A1 & B filter. Units for higher motor power than these (3.0 and 7.5 kW, respectively) can be ordered either with or without an RFI filter.
16
Control unit (keypad and display) All types of units in the programme, except for IP21 VLT 6402-6602, 380-460 V, VLT 6502-6652, 525-600 V and IP 54 units, can be ordered either with or without the control unit. IP 54 units always come with a control unit. All types of units in the programme are available with built-in application options including a relay card with four relays or a cascade controller card.
Conformal Coating All types of units in the programme are available with or without conformal coating of the PCB. VLT 6402-6602, 380-460 V and VLT 6102-6652, 525-600 V are only available coated.
MG.61.A5.02 - VLT is a registered Danfoss trademark
200-240 V
VLT®6000 HVAC Series
Typecode
Position in string
T2
9-10
C00
11-13
B20
11-13
C20
11-13
CN1
11-13
C54
11-13ST14-15SL14-15R016-17R116-17R316-17
1.1 kW/1.5 HP 6002 XX XX X
1.5 kW/2.0 HP 6003 XX XX X
2.2 kW/3.0 HP 6004 XX XX X
3.0 kW/4.0 HP 6005 XX XX X
4.0 kW/5.0 HP 6006 XXXXXX
5.5 kW/7.5 HP 6008 XXXXXX
7.5 kW/10 HP 6011 XXXXXX 11 kW/15 HP 6016 XXXXXX 15 kW/20 HP 6022 XXXXXX
18.5 kW/25 HP 6027 XXXXXX 22 kW/30 HP 6032 XXXXXX 30 kW/40 HP 6042 XXXX XX
HVAC
Introduction to
37 kW/50 HP 6052 XXXX XX 45 kW/60 HP 6062 XXXX XX
380-460 V
Typecode
Position in stringT49-10
1.1 kW/1.5 HP 6002 XX XX X
1.5 kW/2.0 HP 6003 XX XX X
2.2 kW/3.0 HP 6004 XX XX X
3.0 kW/4.0 HP 6005 XX XX X
4.0 kW/5.0 HP 6006 XX XX X
5.5 kW/7.5 HP 6008 XX XX X
7.5 kW/10 HP 6011 XX XX X 11 kW/15 HP 6016 XXXX XX 15 kW/20 HP 6022 XXXX XX
18.5 kW/25 HP 6027 XXXX XX 22 kW/30 HP 6032 XXXX XX 30 kW/40 HP 6042 XXXX XX 37 kW/50 HP 6052 XXXX XX 45 kW/60 HP 6062 XXXX XX 55 kW/75 HP 6072 XXXX XX 75 kW/100 HP 6102 XXXX XX 90 kW/125 HP 6122 XXXX XX 110 kW/150 HP 6152 XXXX XXXXXXX 132 kW/200 HP 6172 XXXX XXXXXXX 160 kW/250 HP 6222 XXXX XXXXXXX 200 kW/300 HP 6272 XXXX XXXXXXX 250 kW/350 HP 6352 XXXX XXXXXXX 315 kW/450 HP 6402 XXXX XXXXXXX 355 kW/500 HP 6502 XXXX XXXXXXX 400 kW/550 HP 6552 XXXX XXXXXXX 450 kW/600 HP 6602 XXXX XXXXXXX
C00
11-13
B20
11-13
C20
11-13
CN1
C54
11-13
11-13ST14-15SL14-15EX14-15DX14-15PS14-15PD14-15PF14-15R016-17R116-17R316-17
Voltage
T2: 200-240 VAC T4: 380-460 VAC
Enclosure
C00: Compact IP 00 B20: Bookstyle IP 20
C20: Compact IP 20 CN1: Compact NEMA 1 C54: Compact IP 54
Hardware variant
ST: Standard SL: Standard with DC terminals EX: Extended with 24 V supply and DC terminals DX: Extended with 24 V supply, DC terminals, disconnect and fuse
MG.61.A5.02 - VLT is a registered Danfoss trademark
PS: Standard with 24 V supply PD: Standard with 24 V supply, fuse and disconnect PF: Standard with 24 V supply and fuse
RFI filter
R0: Without filter R1: Class A1 filter R3: Class A1 and B filter
17
NB!:
NEMA 1 exceeds IP 20
525-600 V
VLT®6000 HVAC Series
Typecode
Position in string
T6
9-10
C00
11-13
C20
11-13
CN1
11-13
ST
14-15
R0
16-17
1.1 kW/1.5 HP 6002 XXX X
1.5 kW/2.0 HP 6003 XXX X
2.2 kW/3.0 HP 6004 XXX X
3.0 kW/4.0 HP 6005 XXX X
4.0 kW/5.0 HP 6006 XXX X
5.5 kW/7.5 HP 6008 XXX X
7.5 kW/10 HP 6011 XXX X 11 kW/15 HP 6016 X X X 15 kW/20 HP 6022 X X X
18.5 kW/25 HP 6027 X X X 22 kW/30 HP 6032 X X X 30 kW/40 HP 6042 X X X 37 kW/50 HP 6052 X X X 45 kW/60 HP 6062 X X X 55 kW/75 HP 6072 X X X
VLT 6102-6652, 525-600 V
Typecode
Position in string 75 kW / 100 HP 6102 XXXXXXX XXXX 90 kW / 125 HP 6122 XXXXXXX XXXX 110 kW / 150 HP 6152 XXXXXXX XXXX 132 kW / 200 HP 6172 XXXXXXX XXXX 160 kW / 250 HP 6222 XXXXXXX XXXX 200 kW / 300 HP 6272 XXXXXXX XXXX 250 kW / 350 HP 6352 XXXXXXX XXXX 315 kW / 400 HP 6402 XXXXXXX XXXX 400 kW / 500 HP 6502 XXXXXXX XXX 450 kW / 600 HP 6602 XXXXXXX XXX 500 kW / 650 HP 6652 XXXXXXX XXX
T6
9-10
C00
11-13
CN1
11-13
C54
11-13ST14-15EX14-15DX14-15PS14-15PD14-15PF14-15R016-17R116-17
1)
1) R1 is not available with DX, PF, PD options. NB!:
NEMA 1 exceeds
IP 20
Voltage
T6: 525-6
Enclosure
C00: Compact IP 00 C20: Compac CN1: Compact NEMA 1 C54: Compact IP 54
00 VAC
tIP20
18
Hardware variant
ard
ST: Stand EX: Extended with 24 V supply and DC terminals DX: Extended with 24 V supply, DC terminals,
ct and fuse
disconne PS: Standard with 24 V supply
MG.61.A5.02 - VLT is a registered Danfoss trademark
PD: Standard with 24 V supply, fuse and disconnect
ard with 24 V supply and fuse
PF: Stand
RFI filter
R0: Without filter R1: Class A1
filter
Optional selections, 200-600 V
Display Position: 18-19
D01)Without LCP DL With LCP
Fieldbus option Position: 20-22 F00 No options F10 Profibus DP V1 F13 Profibus FMS F30 DeviceNet F40 LonWorks free topology F41 LonWorks 78 kBps F42 LonWorks 1.25 MBps
Application option Position: 23-25 A00 No options A312)Relay card 4 relays A32 Cascade Controller A40 Real Time Clock Coating Position: 26-27 C03)No coating C1 With coating
1) Not available with enclosure compact IP 54
2) Not available with fieldbus options (Fxx)
3) Not available for power sizes from 6402 to 6602, 380-460 V and 6102-6652, 525-600 V
VLT®6000 HVAC Series
HVAC
Introduction to
MG.61.A5.02 - VLT is a registered Danfoss trademark
19
Ordering form
VLT®6000 HVAC Series
20
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
Mains supply (L1, L2, L3)
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units ........................................................................ 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-460 V units ........................................................................ 3 x 380/400/415/440/460 V ±10%
Supply voltage 525-600 V units ............................................................................... 3 x 525/550/575/600 V ±10%
Supply frequency ............................................................................................................................ 48-62 Hz ± 1%
Max. imbalance of supply voltage:
VLT 6002-6011, 380-460 V and 525-600 V and VLT 6002-6005, 200-240 V .......... ±2.0% of rated supply voltage
VLT 6016-6072, 380-460 V and 525-600 V and VLT 6006-6032, 200-240 V .......... ±1.5% of rated supply voltage
VLT 6102-6602, 380-460 V and VLT 6042-6062, 200-240 V .................................. ±3.0% of rated supply voltage
VLT 6102-6652, 525-600 V ....................................................................................... ±3% of rated supply voltage
True Power factor (λ) ...................................................................................................... 0.90 nominal at rated load
Displacement Power Factor (cos. ϕ) ............................................................................................ near unity (>0.98)
No. of switches on supply input L1, L2, L3 .......................................................................... approx. 1 time/2 min.
Max. short-circuit current ....................................................................................................................... 100.000 A
VLT output data (U, V, W):
Output voltage ................................................................................................................ 0-100% of supply voltage
Output frequency:
Output frequency 6002-6032, 200-240V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6042-6062, 200-240V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6002-6062, 380-460V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6072-6602, 380-460V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6002-6016, 525-600V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6022-6062, 525-600V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6072, 525-600V ......................................................................................... 0-120 Hz, 0-450 Hz
Output frequency 6102-6352, 525-600V ................................................................................ 0-132 Hz, 0-200 Hz
Output frequency 6402-6652, 525-600V ................................................................................ 0-132 Hz, 0-150 Hz
Rated motor voltage, 200-240 V units .............................................................................. 200/208/220/230/240V
Rated motor voltage, 380-460 V units .............................................................................. 380/400/415/440/460V
Rated motor voltage, 525-600 V units ............................................................................................ 525/550/575 V
Rated motor frequency ............................................................................................................................ 50/60 Hz
Switching on output ................................................................................................................................. Unlimited
Ramp times ....................................................................................................................................... 1 - 3600 sec.
Installation
Torque characteristics:
Starting torque ............................................................................................................................... 110% for 1 min.
Starting torque (parameter 110 High break-away torque) ....................................... Max. torque: 160% for 0.5 sec.
Acceleration torque ....................................................................................................................................... 100%
Overload torque ............................................................................................................................................ 110%
MG.61.A5.02 - VLT is a registered Danfoss trademark
21
VLT®6000 HVAC Series
Control card, digital inputs:
Number of programmable digital inputs ................................................................................................................ 8
Terminal nos. ............................................................................................................ 16, 17, 18, 19, 27, 29, 32, 33
Voltage level ........................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logical ’0’ ............................................................................................................................ < 5 V DC
Voltage level, logical ’1’ ........................................................................................................................... >10 V DC
Maximum voltage on input ........................................................................................................................ 28 V DC
Input resistance, R
Scanning time per input ............................................................................................................................. 3 msec.
Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV). In addition, the digital inputs can be isolated from the other terminals on the control card by connecting an external 24 V DC supply and opening switch 4. See Switches 1-4.
Control card, analogue inputs
No. of programmable analogue voltage inputs/thermistor inputs .......................................................................... 2
Terminal nos. ................................................................................................................................................ 53, 54
Voltage level .......................................................................................................................... 0 - 10 V DC (scalable)
Input resistance, R
No. of programmable analogue current inputs ..................................................................................................... 1
Terminal no ground. ............................................................................................................................................ 55
Current range ...................................................................................................................... 0/4 - 20 mA (scalable)
Input resistance, R
Resolution .......................................................................................................................................... 10 bit + sign
Accuracy on input .......................................................................................................... Max. error 1% of full scale
Scanning time per input ............................................................................................................................. 3 msec.
Reliable galvanic isolation: All analogue inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
............................................................................................................................................ 2 k
i
............................................................................................................................. approx. 10 k
i
........................................................................................................................................... 200
i
Control card, pulse input:
No. of programmable pulse inputs ........................................................................................................................ 3
Terminal nos. .......................................................................................................................................... 17, 29, 33
Max. frequency on terminal 17 ...................................................................................................................... 5 kHz
Max. frequency on terminals 29, 33 ............................................................................ 20 kHz (PNP open collector)
Max. frequency on terminals 29, 33 ........................................................................................... 65 kHz (Push-pull)
Voltage level ........................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logical ’0’ ............................................................................................................................ < 5 V DC
Voltage level, logical ’1’ ........................................................................................................................... >10 V DC
Maximum voltage on input ........................................................................................................................ 28 V DC
Input resistance, R
............................................................................................................................................ 2 k
i
Scanning time per input ............................................................................................................................. 3 msec.
Resolution .......................................................................................................................................... 10 bit + sign
Accuracy (100-1 kHz), terminals 17, 29, 33 ............................................................... Max. error: 0.5% of full scale
Accuracy (1-5 kHz), terminal 17 ................................................................................. Max. error: 0.1% of full scale
Accuracy (1-65 kHz), terminals 29, 33 ....................................................................... Max. error: 0.1% of full scale
Reliable galvanic isolation: All pulse inputs are galvanically isolated from the supply voltage (PELV). In addition, pulse inputs can be isolated from the other terminals on the control card by connecting an external 24 V DC supply and opening switch 4. See Switches 1-4.
Control card, digital/pulse and analogue outputs:
No. of programmable digital and analogue outputs .............................................................................................. 2
Terminal nos. ................................................................................................................................................ 42, 45
Voltage level at digital/pulse output ...................................................................................................... 0 - 24 V DC
Minimum load to ground (terminal 39) at digital/pulse output ............................................................................ 600
Frequency ranges (digital output used as pulse output) ............................................................................ 0-32 kHz
22
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
Current range at analogue output ........................................................................................................ 0/4 - 20 mA
Maximum load to ground (terminal 39) at analogue output ................................................................................ 500
Accuracy of analogue output ..................................................................................... Max. error: 1.5% of full scale
Resolution on analogue output. ....................................................................................................................... 8 bit
Reliable galvanic isolation: All digital and analogue outputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC supply:
Terminal nos. ................................................................................................................................................ 12, 13
Max. load .................................................................................................................................................. 200 mA
Terminal nos. ground .................................................................................................................................... 20, 39
Reliable galvanic isolation: The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analogue outputs.
Control card, RS 485 serial communication:
Terminal nos. .............................................................................................................. 68 (TX+, RX+), 69 (TX-, RX-)
Reliable galvanic isolation: Full galvanic isolation (PELV).
Relay outputs:
1)
No. of programmable relay outputs ...................................................................................................................... 2
Terminal nos., control card (resistive load only) ....................................................................................... 4-5 (make)
Max. terminal load (AC1) on 4-5, control card ........................................................................ 50 V AC, 1 A, 50 VA
Max. terminal load (DC1 (IEC 947)) on 4-5, control card ................................. 25 V DC, 2 A / 50 V DC, 1 A, 50 W
Max. terminal load (DC1) on 4-5, control card for UL/cUL applications .................... 30 V AC, 1 A / 42.5 V DC, 1A
Terminal nos., power card (resistive and inductive load) ...................................................... 1-3 (break), 1-2 (make)
Max. terminal load (AC1) on 1-3, 1-2, power card ............................................................. 250 V AC, 2 A, 500 VA
Max. terminal load (DC1 (IEC 947)) on 1-3, 1-2, power card ............................. 25 V DC, 2 A / 50 V DC, 1A, 50 W
Min. terminal load (AC/DC) on 1-3, 1-2, power card ....................................... 24 V DC, 10 mA / 24 V AC, 100 mA
1) Rated values for up to 300,000 operations. At inductive loads the number of operations are reduced by 50%, alternatively the current can be reduced by 50%, thus the 300,000 operations are maintained.
External 24 Volt DC supply (only available with V
LT 6152-6602, 380-460 V):
Terminal nos. ................................................................................................................................................ 35, 36
Voltage range ....................................................................................... 24 V DC ±15% (max. 37 V DC for 10 sec.)
Max. voltage ripple ..................................................................................................................................... 2 V DC
Power consumption .............................................................................. 15 W - 50 W (50 W for start-up, 20 m
sec.)
Min. pre-fuse ............................................................................................................................................... 6 Amp
Reliable galvanic isolation: Full galvanic isolation if the external 24 V DC supply is also of the PELV type.
Installation
Cable lengths and cross-sections:
Max. motor cable length, screened cable ..................................................................................................... 150 m
Max. motor cable length, unscreened cable ................................................................................................. 300 m
Max. motor cable length, screened cable VLT 6011 380-460 V .................................................................... 100 m
Max. motor cable length, screened cable VLT 6011 525-600 V ...................................................................... 50 m
Max. DC-bus cable length, screened cable ........................................... 25 m fro
m frequency converter to DC bar.
Max. cable cross-section to motor, see next section
2
Max. cross-section for 24 V external DC supply ........................................................................ 2.5 mm
Max. cross-section for control cables ....................................................................................... 1.5 mm
Max. cross-section for serial communication ............................................................................ 1.5 mm
/12 AWG
2
/16 A
2
/16 AWG
WG
If UL/cUL is to be complied with, copper cable withtemperatureclass60/75°Cmustbeused
MG.61.A5.02 - VLT is a registered Danfoss trademark
23
VLT®6000 HVAC Series
(VLT 6002 - 6072 380 - 460 V, 525-600 V and VLT 6002 - 6032 200 - 240 V). If UL/cUL is to be complied with, copper cable with temperature class 75°C must be used (VLT 6042 - 6062 200 - 240 V, VLT 6102 - 6602 380 - 460 V, VLT 6102 - 6652 525 - 600 V). Connectors are for use of both copper and aluminium cables, unless other is specified.
Control characteristics:
Frequency range .................................................................................................................................. 0 - 1000 Hz
Resolution on output frequency ............................................................................................................. ±0.003 Hz
System response time ............................................................................................................................... 3 msec.
Speed, control range (open loop) ..................................................................................... 1:100 of synchro. speed
Speed, accuracy (open loop) ............................................................................ < 1500 rpm: max. error ± 7.5 rpm
>1500 rpm: max. error of 0.5% of actual speed
Process, accuracy (closed loop) ....................................................................... < 1500 rpm: max. error ± 1.5 rpm
>1500 rpm: max. error of 0.1% of actual speed
All control characteristics are based on a 4-pole asynchronous motor
Accuracy of display readout (parameters 009-012, Display readout):
Motor current [5] 0-140% load ............................................................... Max. error: ±2.0% of rated output current
Power kW [6], Power HP [7], 0-90% load .................................................. Max. error: ±5% of rated output power
Externals:
Enclosure ........................................................................................................... IP 00, IP 20, IP 21/NEMA 1, IP 54
Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ............................................................ 93 % + 2 %, -3 % (IEC 68-2-3) for storage/transport
Max. relative humidity ............................................... 95 % non condensing (IEC 721-3-3; class 3K3) for operation
Aggressive environment (IEC 721-3-3) .................................................................................... Uncoated class 3C2
Aggressive environment (IEC 721-3-3) ........................................................................................ Coated class 3C3
Ambient temperature, VLT 6002-6005 200-240 V,
6002-6011 380-460 V, 6002-6011 525-600 V Bookstyle, IP 20 ............ Max. 45°C (24-hour average max. 40°C)
Ambient temperature, VLT 6006-6062 200-240 V,
6016-6602 380-460 V, 6016-6652 525-600 V IP 00, IP 20 ................... Max. 40°C (24-hour average max. 35°C)
Ambient temperature, VLT 6002-6062 200-240 V,
6002-6602 380-460 V, VLT 6102-6652, 525-600 V, IP 54 ..................... Max. 40°C (24-hour average max. 35°C)
Min. ambient temperature in full operation ........................................................................................................ 0°C
Min. ambient temperature at reduced performance ..................................................................................... -10°C
Temperature during storage/transport ............................................................................................. -25 - +65/70°C
Max. altitude above sea level ...................................................................................................................... 1000 m
EMC standards applied, Emission ......................................... EN 61000-6-3/4, EN 61800-3, EN 55011, EN 55014
EMC standards applied, Immunity ................................................................................................ EN 50082-2, EN
61000-4-2, IEC 1000-4-3, EN 61000-4-4, EN 61000-4-5, ENV 50204, EN 61000-4-6, VDE 0160/1990.12
IP54 units are not intended for direct outdoor installation. The IP54 rating does not relate to other exposures as sun, icing, wind blown driving rain. Under such circumstances Danfoss recommends to install the units in an enclosure designed for these environmental conditions. Alternatively, an installation at minimum 0.5 m above surface and covered by a shed is recommended.
24
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
NB!:
VLT 6002-6072, 525-600 V units do not comply with EMC, Low Voltage or PELV directives.
VLT 6000 HVAC protection
• Electronic motor thermal protection against overload.
• Temperature monitoring of heat-sink ensures that the frequency converter cuts out if the temperature
reaches 90°C for IP00, IP20 and NEMA 1. For IP54, the cut-out temperature is 80°C. An overtemperature can only be reset when the temperature of the heat-sink has fallen below 60°C.
For the units mentioned below, the limits are as follows:
- VLT 6152, 380-460 V, cuts out at 75° C and can be reset if the temperature is below 60 °C.
- VLT 6172, 380-460 V, cuts out at 80° C and can be reset if the temperature has fallen below 60° C.
- VLT 6222, 380-460 V, cuts out at 95° C and can be reset if the temperature has fallen below 65° C.
- VLT 6272, 380-460 V, cuts out at 95° C and can be reset if the temperature has fallen below 65° C.
- VLT 6352, 380-460 V, cuts out at 105° C and can be reset if the temperature has fallen below 75° C.
- VLT 6402-6602, 380-460 V cuts out at 85° C and can be reset if the temperature has fallen below 60
- VLT 6102-6152, 525-600 V, cuts out at 75° C and can be reset if the temperature has fallen below 60° C. VLT 6172, 525-600 V, cuts out at 80° C and can be reset if the temperature has fallen below 60° C. VLT 6222-6402, 525-600 V, cuts out at 100° C and can be reset if the temperature has fallen below 70° C. VLT 6502-6652, 525-600 V, cuts out at 75° C and can be reset if the temperature has fallen below 60° C.
°C
Installation
• The frequency converter is protected against short-circuiting on motor terminals U, V, W.
• The frequency converter is protected against earth fault on motor terminals U, V, W.
• Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the
intermediate circuit voltage gets too high or too low.
• If a motor phase is missing, the frequency converter cuts out.
• If there is a mains fault, the frequency converter is able to carry out a controlled decelleration.
• If a mains phase is missing, the frequency converter will cut out or autoderate when a load is placed on
the motor.
MG.61.A5.02 - VLT is a registered Danfoss trademark
25
VLT®6000 HVAC Series
Technical data, mains supply 3 x 200-240V
According to international requirements VLT type 6002 6003 6004 6005 6006 6008 6011
Output current
Output power (240 V) S Ty pi c al s h af t o ut p ut P Ty pi c al s h af t o ut p ut P Max. cable cross-section to motor and DC-bus
Max. input current
Max. cable cross-section power Max. pre-fuses [-]/UL1)[A] 16/10 16/15 25/20 25/25 35/30 50 60 Efficiency Weight IP 20 [kg] 7 7 9 9 23 23 23 Weight IP 54 [kg] 11.5 11.5 13.5 13.5 35 35 38 Power loss at max. load. [W] Enclosure VLT type IP 20 / IP 54
4)
I
[A] 6.6 7.5 10.6 12.5 16.7 24.2 30.8
VLT,N
I
(60 s) [A] 7.3 8.3 11.7 13.8 18.4 26.6 33.9
VLT, MAX
[kVA] 2.7 3.1 4.4 5.2 6.9 10.1 12.8
VLT,N
[kW] 1.1 1.5 2.2 3.0 4.0 5.5 7.5
VLT,N
[HP] 1.5 2 3 4 5 7.5 10
VLT,N
[mm2]/[AWG]
4/10 4/10 4/10 4/10 10/8 16/6 16/6
(200 V) (RMS)I
[mm2]/[AWG]
3)
L,N
6.0 7.0 10.0 12.0 16.0 23.0 30.0
[A]
2)
4/10 4/10 4/10 4/10 4/10 16/6 16/6
0.95 0.95 0.95 0.95 0.95 0.95 0.95
Total 76 95 126 172 194 426 545
1. Fortypeoffuse,seesectionFuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V.
26
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
Technical data, m ains supply 3x200-240V
According to international requirements VLT type 6016 6022 6027 6032 6042 6052 6062
I
[A]
Output current
4)
Output power
Typical shaft output Typical shaft output Max. cable cross-section to motor and DC-bus [mm ]/[AWG]
2
2) 5)
Min. cable cross-section to motor and DC-bus [mm
2
Max. input current (200 V) (RMS)
[A]
I
L,N
Max. cable cross-section power [mm ]/[AWG]
2
2) 5)
Max. pre-fuses [-]/UL1)[A] 60 80 125 125 150 200 250 Efficiency
3)
Weight IP 00 [kg] - - - - 90 90 90 Weight IP 20/NEMA 1 Weight IP 54 [kg] 38 49 50 55 104 104 104 Power loss at max. load. Enclosure IP 00/IP 20/NEMA 1/IP 54
1. Fortypeoffuse,seesectionFuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V.
5. Connection stud 1 x M8 / 2 x M8.
6. Aluminium cables with cross section above 35 mm
VLT,N
(200-230 V)
I
VLT, MAX
[A] (200-230 V) I
[A] (240 V) 46.0 59.4 74.8 88.0 104 130 154
VLT,N
I
VLT, MAX
[A] (240 V)
S
VLT,N
(240 V)
P
VLT,N
P
VLT,N
Copper Aluminium
2)
]/[AWG]
46.2 59.4 74.8 88.0 115 143 170
(60 s)
50.6 65.3 82.3 96.8 127 158 187
(60 s)
50.6 65.3 82.3 96.8 115 143 170
[kVA]
19.1 24.7 31.1 36.6 43.2 54 64
[kW] 11 15 18.5 22 30 37 45
[HP] 15 20 25 30 40 50 60
16/6
6)
16/6
35/2 35/2
35/2 35/2
50/0 50/0
70/1/0 95/3/0
95/3/0 90/250
5)
mcm
10/8 10/8 10/8 16/6 10/8 10/8 10/8
46.0 59.2 74.8 88.0 101.3 126.6 149.9
Copper Aluminium
16/6
6)
16/6
35/2 35/2
35/2 35/2
50/0 50/0
70/1/0 95/3/0
95/3/0 90/250
5)
mcm
0.95 0.95 0.95 0.95 0.95 0.95 0.95
[kg] 23 30 30 48 101 101 101
[W] 545 783 1042 1243 1089 1361 1613
2
must be connected by use of an Al-Cu connector.
5)
5)
120/4/0 120/300
5)
mcm
120/4/0 120/300
5)
mcm
Installation
MG.61.A5.02 - VLT is a registered Danfoss trademark
27
VLT®6000 HVAC Series
Technical data, mains supply 3 x 380-460V
According to international requirements VLT type 6002 6003 6004 6005 6006 6008 6011
I
[A] (380-440
Output current
VLT,N
I
VLT, MAX
(60 s) [A]
(380-440 V)
I
[A] (441-460
VLT, N
I
(60 s) [A]
VLT, MAX
(441-460 V)
Output power S
Typical shaft output Typical shaft output Max. cable
[kVA] (400 V) 2.2 2.9 4.0 5.2 7.2 9.3 11.5
VLT,N
S
[kVA] (460 V) 2.4 2.7 3.8 5.0 6.5 8.8 11.2
VLT,N
P
VLT,N
P
VLT,N
2
[mm
]/[AWG] cross-section to motor Max. input current (RMS) I Max. cable
[A] (380 V) 2.8 3.8 5.3 7.0 9.1 12.2 15.0
I
L,N
[A] (460 V) 2.5 3.4 4.8 6.0 8.3 10.6 14.0
L,N
2
[mm
]/[AWG] cross-section power Max. pre-fuses [-]/UL1)[A] 16/6 16/10 16/10 16/15 25/20 25/25 35/30 Efficiency
3)
Weight IP 20 [kg] 8 8 8.5 8.5 10.5 10.5 10.5 Weight IP 54 [kg] 11.5 11.5 12 12 14 14 14 Power loss at max. load. [W] Enclosure VLT type IP 20/IP 54
3.0 4.1 5.6 7.2 10.0 13.0 16.0
V)
3.3 4.5 6.2 7.9 11.0 14.3 17.6
3.0 3.4 4.8 6.3 8.2 11.0 14.0
V)
3.3 3.7 5.3 6.9 9.0 12.1 15.4
[kW] 1.1 1.5 2.2 3.0 4.0 5.5 7.5
[HP] 1.5 2 3 - 5 7.5 10
2) 4)
4/10 4/10 4/10 4/10 4/10 4/10 4/10
2) 4)
4/10 4/10 4/10 4/10 4/10 4/10 4/10
0.96 0.96 0.96 0.96 0.96 0.96 0.96
Total 67 92 110 139 198 250 295
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section.
28
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
Technical data, m ains supply 3x380-460V
According to international requirements VLT type 6016 6022 6027 6032 6042
Output current I
Output power S
Ty pi c al s h a ft o u tp u t P Ty pi c al s h a ft o u tp u t P Max. cable cross-section to motor and DC-bus, IP 20 Max. cable cross-section to motor and DC-bus, IP 54 Min. cable cross-section to motor and DC-bus Max. input current I (RMS) I Max. cable cross-section power, IP 20 Max. cable cross-section power, IP 54 Max. pre-fuses [-]/UL1)[A] 63/40 63/40 63/50 63/60 80/80 Efficiency at rated frequency 0.96 0.96 0.96 0.96 0.96 Weight IP 20 [kg] 21 21 22 27 28 Weight IP 54 [kg] 41 41 42 42 54 Power loss at max. load. [W] 419 559 655 768 1065 Enclosure IP 20/ IP 54
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section.
[A] (380-440 V) 24.0 32.0 37.5 44.0 61.0
VLT,N
I
(60 s) [A]
VLT, MAX
(380-440 V)
I
[A] (441-460 V) 21.0 27.0 34.0 40.0 52.0
VLT,N
I
(60 s) [A]
VLT, MAX
(441-460 V)
[kVA] (400 V) 17.3 23.0 27.0 31.6 43.8
VLT,N
S
[kVA] (460 V) 16.7 21.5 27.1 31.9 41.4
VLT,N
VLT,N
VLT,N
26.4 35.2 41.3 48.4 67.1
23.1 29.7 37.4 44.0 57.2
[kW] 11 15 18.5 22 30 [HP] 15 20 25 30 40
16/6 16/6 16/6 35/2 35/2
2
]/[AWG]
2) 4)
[mm
16/6 16/6 16/6 16/6 35/2
2
[mm
L,N
L,N
2) 4)
]/[AWG]
10/8 10/8 10/8 10/8 10/8
[A] (380 V) 24.0 32.0 37.5 44.0 60.0 [A] (460 V) 21.0 27.6 34.0 41.0 53.0
16/6 16/6 16/6 35/2 35/2
2
]/[AWG]
2) 4)
[mm
16/6 16/6 16/6 16/6 35/2
Installation
MG.61.A5.02 - VLT is a registered Danfoss trademark
29
VLT®6000 HVAC Series
Technical data, m ains supply 3x380-460V
According to international requirements VLT type 6052 6062 6072 6102 6122
Output current I
Output power S
Ty pi c al s h af t o u tp u t P Ty pi c al s h af t o u tp u t P Max. cable cross-section to motor and DC-bus, IP 20 Max. cable cross-section to motor and DC-bus, IP 54 Min. cable cross-section to motor and DC-bus Max. input current I (RMS) I Max. cable cross-section power, IP 20 Max. cable cross-section power, IP 54 Max. pre-fuses [-]/UL1)[A] 100/100 125/125 150/150 225/225 250/250 Efficiency at rated frequency 0.96 0.96 0.96 0.98 0.98 Weight IP 20 [kg] 41 42 43 54 54 Weight IP 54 [kg] 56 56 60 77 77 Power loss at max. load. [W] 1275 1571 1322 1467 1766 Enclosure IP 20/IP 54
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals. Always comply with national and local regulations on min. cable cross-section.
2
5. DC connection 95 mm
/AWG 3/0.
6. Aluminium cables with cross-section above 35 mm nected by use of an Al-Cu connector.
[A] (380-440 V) 73.0 90.0 106 147 177
VLT,N
I
(60 s) [A]
VLT, MAX
(380-440 V)
I
[A] (441-460 V) 65.0 77.0 106 130 160
VLT,N
I
(60 s) [A]
VLT, MAX
(441-460 V)
[kVA] (400 V) 52.5 64.7 73.4 102 123
VLT,N
S
[kVA] (460 V) 51.8 61.3 84.5 104 127
VLT,N
VLT,N
VLT,N
80.3 99.0 117 162 195
71.5 84.7 117 143 176
[kW] 37 45 55 75 90
[HP] 50 60 75 100 125
120 /
[mm
2
]/[AWG]
35/2 50/0 50/0
2) 4) 6)
35/2 50/0 50/0
250 mcm 150 / 300 mcm
[mm
2
L,N
L,N
2) 4)
]/[AWG]
10/8 16/6 16/6 25/4 25/4
[A] (380 V) 72.0 89.0 104 145 174 [A] (460 V) 64.0 77.0 104 128 158
120 /
[mm
2
]/[AWG]
35/2 50/0 50/0
2) 4) 6)
35/2 50/0 50/0
250 mcm 150 / 300 mcm
2
must be con-
5)
5)
120 / 250 mcm 150 / 300 mcm
120 / 250 mcm 150 / 300 mcm
5)
5)
30
MG.61.A5.02 - VLT is a registered Danfoss trademark
Loading...
+ 140 hidden pages