Parameter overview and factory settings .............................................................. 161
Index .................................................................................................................... 168
MG.61.A5.02 - VLT is a registered Danfoss trademark
3
VLT®6000 HVAC Series
VLT 6000 HVAC
Operating Instructions
Software version: 3.0x
These Operating Instructions can be used for all VLT 6000
HVAC frequency converters with software version 3.0x.
The software version number can be seen from parameter
624.
175ZA691.16
4
MG.61.A5.02 - VLT is a registered Danfoss trademark
The voltage of the frequency converter
is dangerous whenever the equipment
is connected to mains. Incorrect
installation of the motor or the frequency converter
may cause damage to the equipment, serious
personal injury or death.
Consequently, the instructions in this manual,
as well as national and local rules and safety
regulations, must be complied with.
■Safety regulations
1. The frequency converter must be disconnected
from mains if repair work is to be carried out. Check
that the mains supply has been disconnected
and that the necessary time has passed before
removing motor and mains plugs.
2. The [OFF/STOP] key on the control panel of
the frequency converter does n
the equipment from mains and is thus n
be used as a safety switch.
3. Correct protective earthing of the equipment
must be established, the user must be protected
against supply voltage, and the motor must be
protected against overload in accordance with
applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is included in
the factory setting. Parameter 117, Motor thermalprotection default value is ETR trip 1.
ote: The function is initialised at 1.0 x rated
N
motor current and rated motor frequency (see
parameter 117, Motor thermal protection).
ot disconnect
ot to
VLT®6000 HVAC Series
6. Do n
7. Reliable galvanic isolation (PELV) is not complied
8. Please note that the frequency converter has
■Warning against unintended start
1. The motor can be brought to a stop by
2. While parameters are being changed, the
3. A motor that has been stopped may start if faults
ot remove the plugs for the motor and mains
supply while the frequency converter is connected
to mains. Check that the mains supply has been
disconnected and that the necessary time has
passed before removing motor and mains plugs.
with if the RFI switch is placed in OFF position.
This means that all control in - and outputs
can only be considered low-voltage terminals
withbasicgalvanicisolation.
more voltage inputs than L1, L2 and L3, when
the DC-bus terminals are used.
Check that a
disconnected and that the necessary time has
passed before repair work is commenced.
means of digital commands, bus commands,
references or a local stop, while the frequency
converter is connected to mains.
If personal safety considerations make it necessary
to ensure that no unintended start occurs, t
stop functions are not sufficient.
motor may start. Consequently, t
[OFF/STOP] must always be activated, following
which data can be modified.
occur in the electronics of the frequency converter,
or if a temporary overload or a fault in the supply
mains or the motor connection ceases.
ll voltage inputs have been
he stop key
HVAC
Introduction to
hese
MG.61.A5.02 - VLT is a registered Danfoss trademark
■Use on isolated mains
See section RFI Switch regarding use on isolated mains.
It is important to follow the recommendations regarding
installation on IT-mains, since sufficient protection
ofthecompleteinstallationmustbeobserved.
Not taking care using relevant monitoring devices
for IT-mains may result in damage.
5
VLT®6000 HVAC Series
Warning:
Touching the electrical parts may be fatal - even after the equipment has been
disconnected from mains.
175HA490.15
Using VLT 6002 - 6005, 200-240 V: Wait at least 4 minutes
Using VLT
Using VLT
Using VLT
6006 - 6062, 200-240 V: Wait at least 15 minutes
6002 - 6005, 380-460 V: Wait at least 4 minutes
6006 - 6072, 380-460 V: Wait at least 15 minutes
Using VLT 6102 - 6352, 380-460 V: Wait at least 20 minutes
Using VLT 6402 - 6602, 380-460 V: Wait at least 40 minutes
Using VLT
Using VLT
Using VLT
Using VLT
Using VLT
6002 - 6006, 525-600 V: Wait at least 4 minutes
6008 - 6027, 525-600 V: Wait at least 15 minutes
6032 - 6072, 525-600 V: Wait at least 30 minutes
6102 - 6402, 525-600 V: Wait at least 20 minutes
6502 - 6652, 525-600 V: Wait at least 30 minutes
6
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
■Introduction to Operating Instructions
These Operating Instructions are a tool intended for persons who are to install, operate and program the
VLT 6000 HVAC.
A VLT 6000 HVAC comes with Operating Instructions as well as Quick Setup Guide. In addition, a Design
Guide can be ordered for use when designing installations that will include a VLT 6000 HVAC. See Available
literature.
Operating Instructions:These are instructions in how to ensure optimum mechanical and
electrical installation, commissioning and service. The Operating
Instructions also include a description of the software parameters,
thereby enabling easy adaptation of the VLT 6000 HVAC to your
application.
Quick Setup Guide:Helps you to quickly install and commission the VLT 6000 HVAC.
Design Guide:Used when designing installations that include a VLT 6000 HVAC. The
Design Guide gives detailed information about VLT 6000 HVAC and
HVAC installations, including a selection tool to enable you to choose
the right VLT 6000 HVAC with its relevant options and modules. The
Design Guide also contains examples of the most common HVAC
applications. Furthermore, the Design Guide has all information relating
to serial communication.
HVAC
Introduction to
These Operating Instructions are divided into four sections with information about VLT 6000 HVAC.
Introduction to HVAC:This section tells you the advantages you can obtain by using a VLT
6000 HVAC - such as AEO, Automatic Energy Optimization, RFI filters
and other HVAC-relevant functions. This section also contains examples
of application as well as information about Danfoss and CE-labelling.
Installation:This section tells you how to carry out mechanically correct installation
of the VLT 6000 HVAC. In addition, this section includes a description
of how to ensure that the installation of your VLT 6000 HVAC
is EMC-correct. Furthermore, a list is given of mains and motor
connections, together with a description of the control card terminals.
Programming:This section describes the control unit and the software parameters for
the VLT 6000 HVAC. Also included is a guide to the Quick Setup menu,
which allows you to get started on your application very quickly.
All about VLT 6000 HVACThis section gives information about status, warning and error
messages from the VLT 6000 HVAC. Additionally, information is given
on technical data, service, factory settings and special conditions.
es a general warning
Indicat
es a high-voltage warning
Indicat
NB!:
Indicates something to be noted by the reader
MG.61.A5.02 - VLT is a registered Danfoss trademark
7
VLT®6000 HVAC Series
■Available literature
Below is a list of the literature available for VLT
6000 HVAC. It must be noted that there may be
deviations from one country to the next.
Data sheet ........................................................................................................................................ MD.60.AX.YY
One advantage involved in using a VLT 6000 HVAC is
that this unit has been designed to regulate the speed
of fans and rotary pumps while consuming the smallest
possible amount of energy. Consequently, if a VLT 6000
HVAC is used in a HVAC installation, optimum energy
savings are guaranteed, since less energy is used with
a frequency converter than with the traditional HVAC
regulation principles. Another advantage in using the
VLT 6000 HVAC is that regulation is improved and can
easily adapt to a new flow or pressure requirement
in an installation. The use of a VLT 6000 HVAC
offers the following additional advantages:
• VLT 6000 HVAC has been designed for
HVAC applications.
• A wide power range - from 1.1-500 kW
units with a unique design.
• IP 20 and IP 54 enclosures that can be mounted
side by side. For power sizes ≥ 90kW ( ≥ 30kW
for 200 V) IP 00 is also available.
• All unit types, except 525-600 V units, are available
with an integral RFI filter, complying with EN 55011
class A1 in the case of a 150 m screened/armoured
motor cable and EN 55011 class B in the case of a
screened/armoured motor cable up to 50 m long.
• User-friendly design, which makes VLT 6000 HVAC
easy to install, both mechanically and electrically.
• Detachable LCP control panel with Hand-Off-Auto
buttons and a graphics display of local speed.
• High starting torque owing to Automatic
Energy Optimization (AEO).
• Automatic Motor Adaptation (AMA) ensures
optimum motor utilisation.
• Integral PID regulator with option of connecting
two feedback signals (in connection with zoning),
as well as setting of two set-points.
8
MG.61.A5.02 - VLT is a registered Danfoss trademark
• Sleep mode, which automatically turns the
motor off, e.g. when there is no need for more
pressure or flow in a system.
• The "flying start" function enables the unit
to catch a rotating fan.
VLT®6000 HVAC Series
• Automatic ramp up/down to ensure that
the VLT 6000 HVAC will not trip during
acceleration or deceleration.
• All standard units have three integral, serial protocols
- RS 485 FC protocol, Johnson’s Metasys N2
and Landis/Staefa Apogee FLN. Communication
option cards that can be connected are LonWorks,
DeviceNet, Modbus RTU and Profibus.
■Control principle
A frequency converter rectifies AC voltage from
mains into DC voltage, after which this DC
voltage is converted into a AC current with a
variable amplitude and frequency.
1. Mains voltage
3 x 200 - 240
3 x 380 - 460 V AC, 50 / 60 Hz.
3 x 525 - 600 V AC, 50 / 60 Hz.
. Rectifier
2
A three-pha
current into DC current.
3
. Intermediate circuit
DC voltage = 1.35 x mains voltage [V].
4
. Intermediate circuit coils
Even out t
the harmonic current feedback to the mains supply.
VAC,50/60Hz.
se rectifier bridge that rectifies AC
he intermediate circuit voltage and reduce
The motor is thus supplied with variable voltage and
frequency, which enables infinitely variable speed
control of three-phased, standard AC motors.
. Intermediate circuit capacitors
5
Even out the intermediate circuit voltage.
6
. Inverter
Converts DC voltage into variable AC voltage
withavariablefrequency.
. Motor voltage
7
Variable AC voltage, 0-100% of mains supply voltage.
8
. Control card
This is where to find the computer that controls
the inverter which generates the pulse pattern by
which the DC voltage is converted into variable
AC voltage with a variable frequency.
HVAC
Introduction to
MG.61.A5.02 - VLT is a registered Danfoss trademark
9
■AEO - Automatic Energy Optimization
Normally, the U/f characteristics have to be set on the
basis of the expected load at different frequencies.
However, knowing the load at a given frequency in an
installation is often a problem. This problem can be
solved by using a VLT 6000 HVAC with its integral
Automatic Energy Optimization (AEO), which ensures
optimum energy utilization. All VLT 6000 HVAC units
feature this function as a factory setting, i.e. it is
not necessary to adjust the frequency converter U/f
ratio in order to obtain maximum energy savings.
In other frequency converters, the given load and
voltage/frequency ratio (U/f) must be assessed to carry
out correct setting of the frequency converter.
Using Automatic Energy Optimization (AEO), you
no longer need to calculate or assess the system
characteristics of the installation, since Danfoss VLT
6000 HVAC units guarantee optimum, load-dependent
energy consumption by the motor at all times.
The figure on the right illustrates the working
range of the AEO function, within which energy
optimization is enabled.
VLT®6000 HVAC Series
If the AEO function has been selected in parameter 101,
Torque characteristics, this function will be constantly
active. If there is a major deviation from the optimum U/f
ratio, the frequency converter will quickly adjust itself.
Advantages of the AEO function
• Automatic energy optimization
• Compensation if an oversize motor is used
• AEO matches operations to daily or
seasonal fluctuations
• Energy savings in a constant air volume system
• Compensation in the oversynchronous
working range
• Reduces acoustic motor noise
10
MG.61.A5.02 - VLT is a registered Danfoss trademark
■Example of application - Speed control of
fan in ventilation system
The AHU installation is able to distribute air throughout
the building or to one or several parts of a building.
Normally, an AHU installation consists of a fan and
a motor that supply air, a fan scroll and a duct
system with filters. If centralised air distribution is
applied, the efficiency of the installation will increase
and major energy savings can be made.
A VLT 6000 HVAC enables excellent control and
monitoring, thereby ensuring perfect conditions
in the building at all times.
VLT®6000 HVAC Series
This example shows an application with Run permissive,
warning against no load and warning for filter change.
The Run permissive function ensures that the frequency
converter will not start the motor until the discharge
damper has opened. If the V-belt to the fan breaks
and if the filter is to be changed, this application
will also give a warning on an output.
HVAC
Introduction to
Set the following parameters:
Par. 100ConfigurationOpen loop [0]
Par. 221Warning: Low current, I
LOW
Par. 224Warning: High frequency, f
HIGH
Depends on unit
Par. 300Terminal 16 Digital inputsRun permissive [8]
Par. 302Terminal 18 Digital inputsStart [1]
Par. 308Terminal 53, analogue input voltageReference [1]
Par. 309Terminal 53, min. scaling0 v
Par. 310Terminal 53, max. scaling10 v
Par. 319OutputOutput frequency greater than f
Par. 323Relay 1Start command active [27]
Par. 326Relay 2Alarm or warning [12]
Par. 409Function at no loadWarning [1]
HIGH
par. 224
MG.61.A5.02 - VLT is a registered Danfoss trademark
11
■Example of application - Constant pressure
regulation in water supply system
The demand for water from waterworks varies
considerably during the course of a day. In the night,
practically no water is used, while in the morning
and in the evening the consumption is high. In order
to maintain a suitable pressure in the water supply
lines in relation to the current demand, the water
supply pumps are equipped with speed control.
The use of frequency converters enables the energy
consumed by the pumps to be kept at a minimum,
while optimizing the water supply to consumers.
VLT®6000 HVAC Series
A VLT 6000 HVAC with its integral PID controller
ensures simple and quick installation. For example,
an IP54 unit can be mounted close to the pump on
the wall and the existing line cables can be used as
mains supply to the frequency converter. A Pressure
transmitter (e.g. Danfoss MBS 33 0-10) bar can
be fitted a couples of metres from the joint outlet
point from the waterworks to obtain closed loop
regulation. Danfoss MBS 33 is a two-wire transmitter
(4-20 mA) that can be powered directly from a VLT
6000 HVAC. The required setpoint (e.g. 5 bar) can
be set locally in parameter 418 Setpoint 1.
Set the following parameters:
Par. 100ConfigurationClosed loop [1]
Par. 205Maximum reference10 bar
Par. 302Terminal 18 Digital inputsStart [1]
Par. 314Terminal 60, analog input currentFeedback signal [2]
Par. 315Terminal 60, min. scaling4 mA
Par. 316Terminal 60, max. scaling20 mA
Par. 403Sleep mode timer10 sec.
Par. 404Sleep frequency15 Hz
Par. 405Wake-up frequency20 Hz
Par. 406Boost setpoint125%
Par. 413Minimum feedback0
Par. 414Maximum feedback10 bar
Par. 415Process unitsBar [16]
Par. 418Setpoint 15 bar
Par. 420PID normal/inverse controlNormal
Par. 423PID proportional gain0.5-1.0
Par. 424PID integration time3-10
Par. 427PID low pass filter0.5-1.5
12
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
■Fire mode
NB!:
Please note the frequency converter is
only one component of the HVAC system.
Correct function of Fire Mode depends on the
correct design and selection of system components.
Ventilation systems working in life safety applications
have to be approved by the local fire Authorities.
Non-interruption of the frequency converter
due to Fire Mode operation may cause over
pressure and result in damage to HVAC system
and components, including dampers and air
ducts. The frequency converter itself may be
damaged and it may cause damage or fire.
Danfoss A/S accepts no responsibility for errors,
malfunctions personal injur y or any damage to
the frequency converter itself or components
herein, HVAC systems and components herein or
other property when the frequency converter has
been programmed forFire Mode. In no event shall
Danfossbe liable to the end u ser orany other party
for any direct or indirect, special or consequential
damage or loss suffered by such party, which has
occurred due to the frequency converter being
programmed and operated in Fire Mode
To be able to use Fire Mode please also note that
input 27 must be "high" and no coast bit present via
fieldbus. To ensure that no coast can interrupt Fire
Mode via fieldbus please select Digital Input [0] in par.
503. Then coasting via fieldbus disabled.
HVAC
Introduction to
TheFireModefunctionismadetoensuretheVLT
6000 can run without interruption. This means most
alarms and warnings will not cause a trip and trip
lock is disabled. This is useful in case of fire or other
emergencies. Until the motor wires or the frequency
converter itself are destroyed every attempt is made
to keep running. A warning will flash when these
limits have been exceeded. If the warning still flashes
after a power cycle please contact your local Danfoss
supplier. In the following is a table to show the alarms
and when the frequency converter changes state
depending on selection in parameter 430. Trip and
lock ([0] in parameter 430) are valid in normal operation
mode.FireModetripandreset([1]or[2]inparameter
430) means that a reset is automatically performed
without the need of manual resetting. Go to Fire
Mode bypass ([3] in parameter 430) is valid in case
one of the mentioned alarms causes a trip. After the
in parameter 432 selected time delay has passed an
output is set. This output is programmed in parameter
319, 321, 323 or 326. If a relay option is fitted it can
also be selected in parameter 700, 703, 706 or 709.
In parameter 300 and 301 it can be selected if the
logic, for the Fire Mode activation, shall be active high
or low. Please note parameter 430 must be different
to[0]fortheFireModetobeenabled.
MG.61.A5.02 - VLT is a registered Danfoss trademark
13
VLT®6000 HVAC Series
No.DescriptionTRIP
[0]
2Live zero fault
(LIVE ZERO ERROR)
4Mains imbalance
(MAINS IMBALANCE)
7Overvoltage
(DC LINK OVERVOLT)
8Undervoltage
(DC LINK UNDERVOLT)
9Inverter overloaded
(INVERTER TIME)
10Motor overloaded
(MOTOR TIME)
11Motor thermistor(MOTOR
THERMISTOR)
12Current limit
(CURRENT LIMIT)
13Overcurrent
(OVERCURRENT)
14Earth fault
(EARTH FAULT)
15Switch mode fault
(SWITCH MODE FAULT)
16Short-circuit
(CURR.SHORT CIRCUIT)
17Serial communication timeout
(STD BUSTIMEOUT)
18HPFB bus timeout
(HPFB TIMEOUT)
22Auto-optimation fault
(AMA FAULT)
29Heat-sink temperature too
high
(HEAT SINK OVERTEMP.)
30Motor phase U missing
(MISSING MOT.PHASE U)
31Motor phase V missing
(MISSING MOT.PHASE V)
32Motor phase W missing
(MISSING MOT.PHASE W)
34HPFB communication fault
(HPFB TIMEOUT)
37Inverter fault (GATE DRIVE
FAULT)
60Safety stop
(EXTERNAL FAULT)
63Output current low
(I MOTOR < I LOW)
80Fire mode was active
(FIREMODEWASACTIVE)
99Unknown fault
(UNKNOWN FAULT)
X
xxx
x
x
x
x
x
x
xxxx
xxxx
xxxx
xxxx
x
x
x
xxx
x
x
x
x
xxxx
x
x
x
xx
LOCK
[0]
FIRE MODE
Trip & reset
[1], [2]
Go to
FIRE MODE
BYPASS [3]
14
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
■CE labelling
What is CE labelling?
The purpose of CE labelling is to avoid technical
obstacles to trade within EFTA and the EU. The
EU has introduced the CE label as a simple way of
showing whether a product complies with the relevant
EU directives. The CE label says nothing about the
specifications or quality of the product. Frequency
converters are regulated by three EU directives:
The machinery directive (98/37/EEC)
All machines with critical moving parts are covered
by the machinery directive, which came into force
on 1 January 1995. Since a frequency converter is
largely electrical, it does not fall under the machinery
directive. However, if a frequency converter is supplied
for use in a machine, we provide information on safety
aspects relating to the frequency converter. We do
this by means of a manufacturer’sdeclaration.
The low-voltage directive (73/23/EEC)
Frequency converters must be CE labelled in
accordance with the low-voltage directive, which came
into force on 1 January 1997. The directive applies to
all electrical equipment and appliances used in the 50 1000 Volt AC and the 75 - 1500 Volt DC voltage ranges.
Danfoss CE labels in accordance with the directive and
issues a declaration of conformity upon request.
The EMC directive (89/336/EEC)
EMC is short for electromagnetic compatibility. The
presence of electromagnetic compatibility means
that the mutual interference between different
components/appliances is so small that the functioning
of the appliances is not affected.
The EMC directive came into force on 1 January 1996.
Danfoss CE labels in accordance with the directive and
issues a declaration of conformity upon request. In
order that EMC-correct installation can be carried out,
this manual gives detailed instructions for installation. In
addition, we specify the standards which our different
products comply with. We offer the filters that can be
seen from the specifications and provide other types of
assistance to ensure the optimum EMC result.
In the great majority of cases, the frequency converter
is used by professionals of the trade as a complex
component forming part of a larger appliance, system
orinstallation. Itmustbenotedthattheresponsibility
for the final EMC properties of the appliance, system
or installation rests with the installer.
NOTE: VLT 6001-6072, 525-600 V are not CE labelled.
HVAC
Introduction to
■PC software and serial communication
Danfoss offers various options for serial communication.
Using serial communication, it is possible to monitor,
program and control one or several frequency
converters from a centrally located computer.
All VLT 6000 HVAC units have a RS 485 port as
standard with a choice of four protocols. The protocols
selectable in parameter 500 Protocols are:
• FC protocol
• Johnson Controls Metasys N2
• Landis/Staefa Apogee FLN
• Modbus RTU
A bus option card allows higher transmission speed
than RS 485. In addition, a higher number of units
can be linked to the bus and alternative transmission
media can be used. Danfoss offers the following
option cards for communication:
• Profibus
• LonWorks
• DeviceNet
Information on the installation of various options
is not included in this manual.
available for this purpose. It can be used to monitor,
program and control one or several VLT 6000 HVAC
units. For further information, see the Design Guide
for VLT 6000 HVAC or contact Danfoss.
500-566Serial communication
NB!:
Information on the use of RS-485 serial
interface is not included i
further information, see the Design Guide for
VLT 6000 HVAC or contact Danfoss.
n this manual. For
Using the RS 485 port enables communication, e.g.
TM
with a PC. A Windows
MG.61.A5.02 - VLT is a registered Danfoss trademark
program, called MCT 10,is
15
VLT®6000 HVAC Series
■Unpacking and ordering a VLT frequency c onverter
If you are in doubt as to which frequency converter
you have received and which options it contains,
use the following to find out.
■Type code ordering number string
On the basis of your order, the frequency converter is
given an ordering number that can be seen from the
nameplate on the unit. The number may look as follows:
VLT-6008-H-T4-B20-R3-DL-F10-A00-C0
This means that the frequency converter ordered is a
VLT 6008 for three-phase mains voltage of 380-460 V
(T4) in Bookstyle enclosure IP 20 (B20). The hardware
variant is with integral RFI filter, classes A & B (R3). The
frequency converter features a control unit (DL)witha
PROFIBUS option card (F10). No option card (A00)
and no conformal coating (C0) Character no. 8 ( H)
indicates the application range of the unit: H =HVAC.
IP 00: This enclosure is only available for the larger
power sizes of the VLT 6000 HVAC series. It is
recommended for installation in standard cabinets.
IP 20 Bookstyle: This enclosure is designed for
cabinet installation. It takes up a minimum of
space and can be fitted side-by-side without
installation of extra cooling equipment.
IP 20/NEMA 1: This enclosure is used as standard
enclosure for VLT 6000 HVAC. It is ideal for
cabinet installation in areas where a high degree
of protection is required. This enclose also
permits side-by-side installation.
IP 54: This enclosure can be fitted direct to the
wall. Cabinets are not required. IP 54 units can
also be installed side-by-side.
Hardware variant
The units in the programme are available in the
following hardware variants:
ST:Standard unit with or without control unit.
WithoutDCterminals,exceptfor
VLT 6042-6062, 200-240 V
VLT 6016-6072, 525-600 V
SL: Standard unit with DC terminals.
EX: Extended unit with control unit, DC terminals,
connection of external 24 V DC supply for
back-up of control PCB.
DX: Extended unit with control unit, DC terminals,
built-in mains fuses and disconnector,
connection of external 24 V DC supply for
back-up of control PCB.
PF: Standard unit with 24 V DC supply for back-up
of control PCB and built-in main fuses. No DC
terminals.
PS: Standard unit with 24 V DC supply for back-up
of control PCB. No DC terminals.
PD: Standard unit with 24 V DC supply for back-up
of control PCB, built-in main fuses and
disconnect. No DC terminals.
RFI filter
Bookstyle units always come with an integral RFI
filter that complies with EN 55011-B with 20 m
screened/armoured motor cable and EN 55011-A1
with 150 m screened/armoured motor cable. Units
for mains voltage of 240 V and a motor power of up
to and including 3.0 kW (VLT 6005) and units for a
mains voltage of 380-460 V and a motor power of
up to 7.5 kW (VLT 6011) are always supplied with an
integral class A1 & B filter. Units for higher motor
power than these (3.0 and 7.5 kW, respectively) can
be ordered either with or without an RFI filter.
16
Control unit (keypad and display)
All types of units in the programme, except for
IP21 VLT 6402-6602, 380-460 V, VLT 6502-6652,
525-600 V and IP 54 units, can be ordered either
with or without the control unit. IP 54 units always
come with a control unit. All types of units in the
programme are available with built-in application
options including a relay card with four relays or a
cascade controller card.
Conformal Coating
All types of units in the programme are available with
or without conformal coating of the PCB.
VLT 6402-6602, 380-460 V and VLT 6102-6652,
525-600 V are only available coated.
MG.61.A5.02 - VLT is a registered Danfoss trademark
C20: Compact IP 20
CN1: Compact NEMA 1
C54: Compact IP 54
Hardware variant
ST: Standard
SL: Standard with DC terminals
EX: Extended with 24 V supply and DC terminals
DX: Extended with 24 V supply, DC terminals,
disconnect and fuse
MG.61.A5.02 - VLT is a registered Danfoss trademark
PS: Standard with 24 V supply
PD: Standard with 24 V supply, fuse and disconnect
PF: Standard with 24 V supply and fuse
RFI filter
R0: Without filter
R1: Class A1 filter
R3: Class A1 and B filter
3) Not available for power sizes from 6402 to 6602, 380-460 V and
6102-6652, 525-600 V
VLT®6000 HVAC Series
HVAC
Introduction to
MG.61.A5.02 - VLT is a registered Danfoss trademark
19
■Ordering form
VLT®6000 HVAC Series
20
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
■Mains supply (L1, L2, L3)
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units ........................................................................ 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-460 V units ........................................................................ 3 x 380/400/415/440/460 V ±10%
Supply voltage 525-600 V units ............................................................................... 3 x 525/550/575/600 V ±10%
Supply frequency ............................................................................................................................ 48-62 Hz ± 1%
Max. imbalance of supply voltage:
VLT 6002-6011, 380-460 V and 525-600 V and VLT 6002-6005, 200-240 V .......... ±2.0% of rated supply voltage
VLT 6016-6072, 380-460 V and 525-600 V and VLT 6006-6032, 200-240 V .......... ±1.5% of rated supply voltage
VLT 6102-6602, 380-460 V and VLT 6042-6062, 200-240 V .................................. ±3.0% of rated supply voltage
VLT 6102-6652, 525-600 V ....................................................................................... ±3% of rated supply voltage
True Power factor (λ) ...................................................................................................... 0.90 nominal at rated load
Displacement Power Factor (cos. ϕ) ............................................................................................ near unity (>0.98)
No. of switches on supply input L1, L2, L3 .......................................................................... approx. 1 time/2 min.
Max. short-circuit current ....................................................................................................................... 100.000 A
VLT output data (U, V, W):
Output voltage ................................................................................................................ 0-100% of supply voltage
Output frequency:
Output frequency 6002-6032, 200-240V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6042-6062, 200-240V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6002-6062, 380-460V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6072-6602, 380-460V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6002-6016, 525-600V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6022-6062, 525-600V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6072, 525-600V ......................................................................................... 0-120 Hz, 0-450 Hz
Output frequency 6102-6352, 525-600V ................................................................................ 0-132 Hz, 0-200 Hz
Output frequency 6402-6652, 525-600V ................................................................................ 0-132 Hz, 0-150 Hz
Rated motor voltage, 200-240 V units .............................................................................. 200/208/220/230/240V
Rated motor voltage, 380-460 V units .............................................................................. 380/400/415/440/460V
Rated motor voltage, 525-600 V units ............................................................................................ 525/550/575 V
Rated motor frequency ............................................................................................................................ 50/60 Hz
Switching on output ................................................................................................................................. Unlimited
Ramp times ....................................................................................................................................... 1 - 3600 sec.
Installation
Torque characteristics:
Starting torque ............................................................................................................................... 110% for 1 min.
Starting torque (parameter 110 High break-away torque) ....................................... Max. torque: 160% for 0.5 sec.
MG.61.A5.02 - VLT is a registered Danfoss trademark
21
VLT®6000 HVAC Series
Control card, digital inputs:
Number of programmable digital inputs ................................................................................................................ 8
Voltage level ........................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logical ’0’ ............................................................................................................................ < 5 V DC
Voltage level, logical ’1’ ........................................................................................................................... >10 V DC
Maximum voltage on input ........................................................................................................................ 28 V DC
Input resistance, R
Scanning time per input ............................................................................................................................. 3 msec.
Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV). In
addition, the digital inputs can be isolated from the other terminals on the control card by connecting
an external 24 V DC supply and opening switch 4. See Switches 1-4.
Control card, analogue inputs
No. of programmable analogue voltage inputs/thermistor inputs .......................................................................... 2
Voltage level .......................................................................................................................... 0 - 10 V DC (scalable)
Input resistance, R
No. of programmable analogue current inputs ..................................................................................................... 1
Terminal no ground. ............................................................................................................................................ 55
Current range ...................................................................................................................... 0/4 - 20 mA (scalable)
Input resistance, R
Resolution .......................................................................................................................................... 10 bit + sign
Accuracy on input .......................................................................................................... Max. error 1% of full scale
Scanning time per input ............................................................................................................................. 3 msec.
Reliable galvanic isolation: All analogue inputs are galvanically isolated from the supply
voltage (PELV) and other high-voltage terminals.
............................................................................................................................................ 2 k
i
............................................................................................................................. approx. 10 k
Max. frequency on terminal 17 ...................................................................................................................... 5 kHz
Max. frequency on terminals 29, 33 ............................................................................ 20 kHz (PNP open collector)
Max. frequency on terminals 29, 33 ........................................................................................... 65 kHz (Push-pull)
Voltage level ........................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logical ’0’ ............................................................................................................................ < 5 V DC
Voltage level, logical ’1’ ........................................................................................................................... >10 V DC
Maximum voltage on input ........................................................................................................................ 28 V DC
Input resistance, R
............................................................................................................................................ 2 k
i
Scanning time per input ............................................................................................................................. 3 msec.
Resolution .......................................................................................................................................... 10 bit + sign
Accuracy (100-1 kHz), terminals 17, 29, 33 ............................................................... Max. error: 0.5% of full scale
Accuracy (1-5 kHz), terminal 17 ................................................................................. Max. error: 0.1% of full scale
Accuracy (1-65 kHz), terminals 29, 33 ....................................................................... Max. error: 0.1% of full scale
Reliable galvanic isolation: All pulse inputs are galvanically isolated from the supply voltage (PELV). In
addition, pulse inputs can be isolated from the other terminals on the control card by connecting an
external 24 V DC supply and opening switch 4. See Switches 1-4.
Control card, digital/pulse and analogue outputs:
No. of programmable digital and analogue outputs .............................................................................................. 2
Voltage level at digital/pulse output ...................................................................................................... 0 - 24 V DC
Minimum load to ground (terminal 39) at digital/pulse output ............................................................................ 600
Frequency ranges (digital output used as pulse output) ............................................................................ 0-32 kHz
22
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
Current range at analogue output ........................................................................................................ 0/4 - 20 mA
Maximum load to ground (terminal 39) at analogue output ................................................................................ 500
Accuracy of analogue output ..................................................................................... Max. error: 1.5% of full scale
Resolution on analogue output. ....................................................................................................................... 8 bit
Reliable galvanic isolation: All digital and analogue outputs are galvanically isolated from the
supply voltage (PELV) and other high-voltage terminals.
Max. load .................................................................................................................................................. 200 mA
Reliable galvanic isolation: The 24 V DC supply is galvanically isolated from the supply voltage
(PELV), but has the same potential as the analogue outputs.
Reliable galvanic isolation: Full galvanic isolation (PELV).
Relay outputs:
1)
No. of programmable relay outputs ...................................................................................................................... 2
Terminal nos., control card (resistive load only) ....................................................................................... 4-5 (make)
Max. terminal load (AC1) on 4-5, control card ........................................................................ 50 V AC, 1 A, 50 VA
Max. terminal load (DC1 (IEC 947)) on 4-5, control card ................................. 25 V DC, 2 A / 50 V DC, 1 A, 50 W
Max. terminal load (DC1) on 4-5, control card for UL/cUL applications .................... 30 V AC, 1 A / 42.5 V DC, 1A
Terminal nos., power card (resistive and inductive load) ...................................................... 1-3 (break), 1-2 (make)
Max. terminal load (AC1) on 1-3, 1-2, power card ............................................................. 250 V AC, 2 A, 500 VA
Max. terminal load (DC1 (IEC 947)) on 1-3, 1-2, power card ............................. 25 V DC, 2 A / 50 V DC, 1A, 50 W
Min. terminal load (AC/DC) on 1-3, 1-2, power card ....................................... 24 V DC, 10 mA / 24 V AC, 100 mA
1) Rated values for up to 300,000 operations.
At inductive loads the number of operations are reduced by 50%, alternatively the current can be reduced by
50%, thus the 300,000 operations are maintained.
Voltage range ....................................................................................... 24 V DC ±15% (max. 37 V DC for 10 sec.)
Max. voltage ripple ..................................................................................................................................... 2 V DC
Power consumption .............................................................................. 15 W - 50 W (50 W for start-up, 20 m
sec.)
Min. pre-fuse ............................................................................................................................................... 6 Amp
Reliable galvanic isolation: Full galvanic isolation if the external 24 V DC supply is also of the PELV type.
Installation
Cable lengths and cross-sections:
Max. motor cable length, screened cable ..................................................................................................... 150 m
Max. motor cable length, unscreened cable ................................................................................................. 300 m
Max. motor cable length, screened cable VLT 6011 380-460 V .................................................................... 100 m
Max. motor cable length, screened cable VLT 6011 525-600 V ...................................................................... 50 m
Max. DC-bus cable length, screened cable ........................................... 25 m fro
m frequency converter to DC bar.
Max. cable cross-section to motor, see next section
2
Max. cross-section for 24 V external DC supply ........................................................................ 2.5 mm
Max. cross-section for control cables ....................................................................................... 1.5 mm
Max. cross-section for serial communication ............................................................................ 1.5 mm
/12 AWG
2
/16 A
2
/16 AWG
WG
If UL/cUL is to be complied with, copper cable withtemperatureclass60/75°Cmustbeused
MG.61.A5.02 - VLT is a registered Danfoss trademark
23
VLT®6000 HVAC Series
(VLT 6002 - 6072 380 - 460 V, 525-600 V and VLT 6002 - 6032 200 - 240 V).
If UL/cUL is to be complied with, copper cable with temperature class 75°C must be used
(VLT 6042 - 6062 200 - 240 V, VLT 6102 - 6602 380 - 460 V, VLT 6102 - 6652 525 - 600 V).
Connectors are for use of both copper and aluminium cables, unless other is specified.
Control characteristics:
Frequency range .................................................................................................................................. 0 - 1000 Hz
Resolution on output frequency ............................................................................................................. ±0.003 Hz
System response time ............................................................................................................................... 3 msec.
Speed, control range (open loop) ..................................................................................... 1:100 of synchro. speed
All control characteristics are based on a 4-pole asynchronous motor
Accuracy of display readout (parameters 009-012, Display readout):
Motor current [5] 0-140% load ............................................................... Max. error: ±2.0% of rated output current
Power kW [6], Power HP [7], 0-90% load .................................................. Max. error: ±5% of rated output power
Externals:
Enclosure ........................................................................................................... IP 00, IP 20, IP 21/NEMA 1, IP 54
Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ............................................... 95 % non condensing (IEC 721-3-3; class 3K3) for operation
Aggressive environment (IEC 721-3-3) .................................................................................... Uncoated class 3C2
Aggressive environment (IEC 721-3-3) ........................................................................................ Coated class 3C3
Ambient temperature, VLT 6002-6005 200-240 V,
6002-6011 380-460 V, 6002-6011 525-600 V Bookstyle, IP 20 ............ Max. 45°C (24-hour average max. 40°C)
Ambient temperature, VLT 6006-6062 200-240 V,
6016-6602 380-460 V, 6016-6652 525-600 V IP 00, IP 20 ................... Max. 40°C (24-hour average max. 35°C)
Ambient temperature, VLT 6002-6062 200-240 V,
6002-6602 380-460 V, VLT 6102-6652, 525-600 V, IP 54 ..................... Max. 40°C (24-hour average max. 35°C)
Min. ambient temperature in full operation ........................................................................................................ 0°C
Min. ambient temperature at reduced performance ..................................................................................... -10°C
Temperature during storage/transport ............................................................................................. -25 - +65/70°C
Max. altitude above sea level ...................................................................................................................... 1000 m
EMC standards applied, Emission ......................................... EN 61000-6-3/4, EN 61800-3, EN 55011, EN 55014
EMC standards applied, Immunity ................................................................................................ EN 50082-2, EN
61000-4-2, IEC 1000-4-3, EN 61000-4-4, EN 61000-4-5, ENV 50204, EN 61000-4-6, VDE 0160/1990.12
IP54 units are not intended for direct outdoor installation. The IP54 rating does not relate to other
exposures as sun, icing, wind blown driving rain. Under such circumstances Danfoss recommends to
install the units in an enclosure designed for these environmental conditions. Alternatively, an installation
at minimum 0.5 m above surface and covered by a shed is recommended.
24
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
NB!:
VLT 6002-6072, 525-600 V units do not comply
with EMC, Low Voltage or PELV directives.
VLT 6000 HVAC protection
• Electronic motor thermal protection against overload.
• Temperature monitoring of heat-sink ensures that the frequency converter cuts out if the temperature
reaches 90°C for IP00, IP20 and NEMA 1. For IP54, the cut-out temperature is 80°C. An overtemperature
can only be reset when the temperature of the heat-sink has fallen below 60°C.
For the units mentioned below, the limits are as follows:
- VLT 6152, 380-460 V, cuts out at 75° C and can be reset if the temperature is below 60 °C.
- VLT 6172, 380-460 V, cuts out at 80° C and can be reset if the temperature has fallen below 60° C.
- VLT 6222, 380-460 V, cuts out at 95° C and can be reset if the temperature has fallen below 65° C.
- VLT 6272, 380-460 V, cuts out at 95° C and can be reset if the temperature has fallen below 65° C.
- VLT 6352, 380-460 V, cuts out at 105° C and can be reset if the temperature has fallen below 75° C.
- VLT 6402-6602, 380-460 V cuts out at 85° C and can be reset if the temperature has fallen below 60
- VLT 6102-6152, 525-600 V, cuts out at 75° C and can be reset if the temperature has fallen below
60° C.
VLT 6172, 525-600 V, cuts out at 80° C and can be reset if the temperature has fallen below 60° C.
VLT 6222-6402, 525-600 V, cuts out at 100° C and can be reset if the temperature has fallen below 70° C.
VLT 6502-6652, 525-600 V, cuts out at 75° C and can be reset if the temperature has fallen below 60° C.
°C
Installation
• The frequency converter is protected against short-circuiting on motor terminals U, V, W.
• The frequency converter is protected against earth fault on motor terminals U, V, W.
• Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the
intermediate circuit voltage gets too high or too low.
• If a motor phase is missing, the frequency converter cuts out.
• If there is a mains fault, the frequency converter is able to carry out a controlled decelleration.
• If a mains phase is missing, the frequency converter will cut out or autoderate when a load is placed on
the motor.
MG.61.A5.02 - VLT is a registered Danfoss trademark
25
VLT®6000 HVAC Series
■Technical data, mains supply 3 x 200-240V
According to international requirementsVLT type 6002600360046005600660086011
Output current
Output power (240 V)S
Ty pi c al s h af t o ut p utP
Ty pi c al s h af t o ut p utP
Max. cable
cross-section to
motor
and DC-bus
Max. input current
Max. cable
cross-section power
Max. pre-fuses[-]/UL1)[A] 16/1016/1525/2025/2535/305060
Efficiency
Weight IP 20[kg] 7799232323
Weight IP 54[kg] 11.511.513.513.5353538
Power loss at
max. load. [W]
EnclosureVLT type IP 20 / IP 54
4)
I
[A] 6.67.510.612.516.724.230.8
VLT,N
I
(60 s) [A] 7.38.311.713.818.426.633.9
VLT, MAX
[kVA] 2.73.14.45.26.910.112.8
VLT,N
[kW] 1.11.52.23.04.05.57.5
VLT,N
[HP] 1.523457.510
VLT,N
[mm2]/[AWG]
4/104/104/104/1010/816/616/6
(200 V) (RMS)I
[mm2]/[AWG]
3)
L,N
6.07.010.012.016.023.030.0
[A]
2)
4/104/104/104/104/1016/616/6
0.950.950.950.950.950.950.95
Total 7695126172194426545
1. Fortypeoffuse,seesectionFuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V.
26
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
■Technical data, m ains supply 3x200-240V
According to international requirementsVLT type6016602260276032604260526062
I
[A]
Output current
4)
Output power
Typical shaft
output
Typical shaft
output
Max. cable
cross-section
to motor and
DC-bus [mm
]/[AWG]
]/[AWG]
cross-section to
motor
Max. input
current
(RMS)I
Max. cable
[A] (380 V) 2.83.85.37.09.112.215.0
I
L,N
[A] (460 V) 2.53.44.86.08.310.614.0
L,N
2
[mm
]/[AWG]
cross-section
power
Max. pre-fuses[-]/UL1)[A] 16/616/10 16/1016/1525/2025/2535/30
Efficiency
3)
Weight IP 20[kg] 888.58.510.510.510.5
Weight IP 54[kg] 11.511.51212141414
Power loss at
max. load. [W]
EnclosureVLT type IP 20/IP 54
3.04.15.67.210.013.016.0
V)
3.34.56.27.911.014.317.6
3.03.44.86.38.211.014.0
V)
3.33.75.36.99.012.115.4
[kW] 1.11.52.23.04.05.57.5
[HP] 1.523-57.510
2) 4)
4/104/104/104/104/104/104/10
2) 4)
4/104/104/104/104/104/104/10
0.960.960.960.960.960.960.96
Total 6792110139198250295
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
28
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT®6000 HVAC Series
■Technical data, m ains supply 3x380-460V
According to international requirementsVLT type60166022602760326042
Output currentI
Output powerS
Ty pi c al s h a ft o u tp u tP
Ty pi c al s h a ft o u tp u tP
Max. cable cross-section to
motor and DC-bus, IP 20
Max. cable cross-section to
motor and DC-bus, IP 54
Min. cable cross-section to
motor and DC-bus
Max. input currentI
(RMS)I
Max. cable cross-section
power, IP 20
Max. cable cross-section
power, IP 54
Max. pre-fuses[-]/UL1)[A] 63/4063/4063/5063/6080/80
Efficiency at rated frequency0.960.960.960.960.96
Weight IP 20[kg] 2121222728
Weight IP 54[kg] 4141424254
Power loss at max. load.[W] 4195596557681065
EnclosureIP 20/ IP 54
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Max. cable
cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
MG.61.A5.02 - VLT is a registered Danfoss trademark
29
VLT®6000 HVAC Series
■Technical data, m ains supply 3x380-460V
According to international requirementsVLT type60526062607261026122
Output currentI
Output powerS
Ty pi c al s h af t o u tp u tP
Ty pi c al s h af t o u tp u tP
Max. cable
cross-section to motor
and DC-bus, IP 20
Max. cable
cross-section to motor
and DC-bus, IP 54
Min. cable cross-section
to motor and DC-bus
Max. input currentI
(RMS)I
Max. cable
cross-section power,
IP 20
Max. cable
cross-section power,
IP 54
Max. pre-fuses[-]/UL1)[A] 100/100125/125 150/150 225/225 250/250
Efficiency at rated frequency0.960.960.960.980.98
Weight IP 20[kg] 4142435454
Weight IP 54[kg] 5656607777
Power loss at max. load.[W]12751571132214671766
EnclosureIP 20/IP 54
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be
fitted on the terminals. Max. cable cross section is the maximum possible
cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
2
5. DC connection 95 mm
/AWG 3/0.
6. Aluminium cables with cross-section above 35 mm
nected by use of an Al-Cu connector.