Equipment containing electrical components may not be disposed of
together with domestic waste.
It must be separately collected with Electrical and Electronic waste
according to local and currently valid legislation.
The FC 300 AutomationDrive DC link capacitors remain charged after power has
been disconnected. To avoid electrical shock hazard, disconnect the FC 300 from
the mains before carrying out maintenance. When using a PM-motor, make sure it
is disconnected. Before doing service on the frequency converter wait at least the
amount of time indicated below:
These Operating Instructions can be used for all MCO 350 Synchronising Controller for VLT
AutomationDrive FC 30x frequency converters with software version 1.1x.
The software version number can be seen from parameter 19-92.
1.1.4. High Voltage
The voltage of the frequency converter is dangerous whenever the frequency converter is connected to mains. Incorrect installation or operation of the motor or
frequency converter may cause damage to the equipment, serious personal injury
or death. The instructions in this manual must consequently be observed, as well as
applicable local and national rules and safety regulations.
Installation in high altitudes
At altitudes above 2 km, please contact Danfoss Drives regarding PELV.
1.1.5. Safety Instructions
•Make sure the FC 300 is properly connected to earth.
•Do not remove mains plugs or motor plugs while the FC 300 is connected to mains.
•Protect users against supply voltage.
•Protect the motor against overloading according to national and local regulations.
•Motor overload protection is not included in the default settings. To add this function,
set parameter 1-90
North American market: ETR functions provide class 20 motor overload protection, in
accordance with NEC.
•The earth leakage current exceeds 3.5 mA.
•The [OFF] key is not a safety switch. It does not disconnect the FC 300 from mains.
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such as loadsharing (linkage of DC intermediate circuit), as well as the motor connection for
kinetic back-up.
Using VLT
Shorter time is allowed only if indicated on the nameplate for the specific unit.
Leakage Current
The earth leakage current from the FC 300 exceeds 3.5 mA. To ensure that the earth
cable has a good mechanical connection to the earth connection (terminal 95), the
cable cross section must be at least 10 mm
separately.
Residual Current Device
This product can cause a D.C. current in the protective conductor. Where a residual
current device (RCD) is used for extra protection, only an RCD of Type B (time delayed) shall be used on the supply side of this product. See also RCD Application
Note MN.90.GX.02.
Protective earthing of the FC 300 and the use of RCD's must always follow national
and local regulations.
®
AutomationDrive FC 300: wait at least 15 minutes.
1. Safety Regulation
2
or 2 times rated earth wires terminated
1
1.1.7. Before Commencing Repair Work
1.Disconnect the frequency converter from mains
2.Wait for discharge of the DC-link. See period of time on the warning label.
3.Disconnect DC bus terminals 88 and 89
4.Remove motor cable
1.1.8. Avoid Unintended Start
While FC 300 is connected to mains, the motor can be started/stopped using digital commands,
bus commands, references or via the Local Control Panel (LCP).
•Disconnect the FC 300 from mains whenever personal safety considerations make it
necessary to avoid unintended start.
•To avoid unintended start, always activate the [OFF] key before changing parameters.
•An electronic fault, temporary overload, a fault in the mains supply, or lost motor connection may cause a stopped motor to start. FC 300 with Safe Stop (i.e. FC 301 in A1
enclosure and FC 302) provides protection against unintended start, if the Safe Stop
Terminal 37 is on low voltage level or disconnected.
1.1.9. Safe Stop of FC 300
The FC 302, and also the FC301 in A1 enclosure, can perform the safety function
(As defined by IEC 61800-5-2) or
Off
Stop Category 0
Safe Torque
(as defined in EN 60204-1).
FC 301 A1 enclosure: When Safe Stop is included in the drive, position 18 of Type Code must be
either T or U. If position 18 is B or X, Safe Stop Terminal 37 is not included!
Example:
Type Code for FC 301 A1 with Safe Stop: FC-301PK75T4Z20H4TGCXXXSXXXXA0BXCXXXXD0
MG.33.Q1.02 - VLT
®
is a registered Danfoss trademark
7
1
1. Safety Regulation
It is designed and approved suitable for the requirements of Safety Category 3 in EN 954-1. This
functionality is called Safe Stop. Prior to integration and use of Safe Stop in an installation, a
thorough risk analysis on the installation must be carried out in order to determine whether the
Safe Stop functionality and safety category are appropriate and sufficient. In order to install and
use the Safe Stop function in accordance with the requirements of Safety Category 3 in EN 954-1,
the related information and instructions of the FC 300 Design Guide MG.33.BX.YY must be followed! The information and instructions of the Operating Instructions are not sufficient for a
correct and safe use of the Safe Stop functionality!
1.1.10. Safe Stop Installation (FC 302 and FC 301 - A1 enclosure only)
To carry out an installation of a Category 0 Stop (EN60204) in conformance
with Safety Category 3 (EN954-1), follow these instructions:
1.The bridge (jumper) between Terminal 37 and 24 V DC must be removed. Cutting or breaking the
jumper is not sufficient. Remove it
entirely to avoid short-circuiting. See
jumper on illustration.
2.Connect terminal 37 to 24 V DC by a
short-circuit protected cable. The 24
V DC voltage supply must be interruptible by an EN954-1 Category 3
circuit interrupt device. If the interrupt device and the frequency converter are placed in the same installation panel, you can use a regular
cable instead of a protected one.
3.Unless the FC302 itself has protection class IP54 and higher, it must be
placed in an IP 54 enclosure. Consequently, FC301 A1 must always be
placed in an IP 54 enclosure.
1. Safety Regulation
1
Illustration 1.1: Bridge jumper between terminal
37 and 24 VDC
The illustration below shows a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN
954-1). The circuit interrupt is caused by an opening door contact. The illustration also shows how
to connect a non-safety related hardware coast.
Illustration 1.2: Illustration of the essential aspects of an installation to achieve a Stopping Category 0 (EN
60204-1) with safety Category 3 (EN 954-1).
1.1.11. IT Mains
Par. 14-50
the RFI filter to ground. If this is done it will reduce the RFI performance to A2 level.
RFI 1
can on FC 102/202/302 be used to disconnect the internal RFI capacitors from
The synchronising Controller is an application option for VLT Automation Drive FC 301 and 302.
The application option consists of two parts:
•synchronising controller part
•Test Run part
2.2. Function Description
2.2.1. Introduction
The synchronising controller can be used in any application where a drive is to operate synchronously with a master drive. The synchronising controller acts as an electronic shaft. The gear ratio
is freely selectable and can also be changed during operation. The speed or the position is automatically and accurately controlled based on encoder feedback signals from both the master drive
and the slave drives.
For synchronous operation of two or more drives you can use:
•Speed synchronisation
•Position synchronisation or
•Marker synchronisation
2.2.2. Speed Synchronisation
2
This is the simplest type of synchronisation. It can be used to compensate for speed differences,
where it is not necessary to compensate for position errors.
The speed synchronisation between master and slave is done at maximum acceleration. To obtain
optimum control the slave drive should therefore be set for a quicker acceleration speed than that
of the master drive.
2.2.3. Position Synchronisation (angle synchronisation)
This is the electronic shaft ensuring a constant angle position ratio between master and slave
drives. In case of a position deviation the slave drive is automatically accelerated to a speed level
that is sufficient for regaining its position to the master drive (I-control like).
2.2.4. Marker Synchronisation
Marker synchronisation is an extended position control. Apart from ensuring a constant angle
position between master and slave drives, marker synchronisation provides the option of using
either an additional sensor or the zero track of the incremental encoder to compensate for any
deviations between master and slave that may occur during operation. Using marker synchronisation the slave is position synchronised until the markers is reached and then the control
compensates for the position difference between master marker and slave marker. This type of
control is used where precision cannot be achieved by using a motor mounted encoder. That could
be because of gearbox slack or other disturbance like belt elongation etc. that are not directly
measurable. Similarly, with marker synchronisation, the slave drive does not need to be brought
into the start position of the master drive at initial start-up, as this is affected automatically by
marker correction.
MG.33.Q1.02 - VLT
®
is a registered Danfoss trademark
11
2
Syncronising Controller MCO 350 Operating
2. Introduction
2.2.5. Mechanical Brake Control
The synchronising controller has a 24 V DC digital output (Output 4) and a relay output (Relay 1)
to control an electromechanical brake; this is very useful in applications when a motor (shaft)
must be kept in the same position for a longer time. This is usually the case in hoisting applications.
The brake output will be active (low) in case of an error and when synchronisation is stopped,
that means whenever motor control is switched off. The brake signal can be delayed when switched on and off in two individual parameters (par. 19-21
). Please note that the brake output is kept low in VLT mode (when input 8 is high). That
Delay
means the brake must be opened for example by means of the VLT mechanical brake function in
set-up 2.
Brake on Delay
and par. 19-22
2.3. Tips and Tricks for Synchronisation Tasks
2.3.1. Introduction
When configuring the drives to be synchronised please keep in mind that the ratios should be of
integer size. When using gear it is also important to know the number of teeth of the various gear
stages (ask the gear manufacturer) as gears are normally set up with infinite gear ratios. When
calculating the ratios between master and slave you must either use the figure PI for both of them
or not use PI at all.
Instructions
Brake off
2.3.2. Example
A master drive with a 4-pole motor and an incremental encoder of 1024 increments/revolution
works on a 2-stage gear. i is specified to be 30.33. At the gear output, a belt ratio of 40:20 is
placed, driving a conveyor belt on the drive side with a diameter of 102mm. Via a 3-stage gear (i
is specified to be 46,54) the slave drive is connected to an 8-toothed chain conveyor with a tooth
pitch of 200mm.
2.3.3. Calculation with Insufficient Numerical Values
The master/slave gear ratio (numerator to denominator) is now calculated as follows:
2. Introduction
Master side = increments * i1 * i2 * power take off =
1024
incr x
Slave side = increments * i1 * power take off
=
This gives a ratio of:
That gives a numerical value of 48,460995 for the numerator and 29,7856 for the denominator.
Note: It is only possible to enter integer values. The most serious error: The master expression
contains the value Pi, an infinite number sequence. Even with small numerical values for master
and slave, the effect would always be that the drives drifted apart, as the Numerator: Denominator
expression can never be an integer.
Another error arises from the gear ratios given, as the master drive was specified with a value of
i = 30.33. The correct ratio is easily found by recalculating the individual numbers of teeth. The
gear is a 2-stage gear; the first stage is formed from two pinions, 126 to 27, and the second stage
from two pinions, 117 to 18.
The ratio is calculated as:
30.33
20
x
x
40
48, 460995
29, 7856
126x117
27
102
x
mm x
18
1
π
=30,33
= 48, 460995
1024
incr x
46.54
x
1
x
200
8
mm
2
= 29, 7856
The specified value of 30.33 thus deviates by 0.1 ‰.
This may appear small; if this error is related to the encoder resolution, however, it will be seen
that even this error is serious.
From the example it can be seen that it is important to maintain the exact values of the gear
stages and to ensure that the data include Pi either for both drives or for none of them.
2.3.4. Example with Corrected Numerical Values
Master side: Gear 1st stage 126/27 2nd stage 117/18; belt ratio 40/20; drive shaft 100 mm
Slave side: Gear 1st stage 97/10, 2nd stage 43/11, 3rd stage 27/22; effective diameter of the
sprocket wheel 510mm
1024
Master side:
Slave side:
To remove Pi from the equations, substitute both equations into the combined formula:
1024
10
Masterside
Slaveside
Incr x
x
27
Incr x97x
x
11x22x510xπ
1024
=
126x117x20
18x40x102xπ
43x27
27
Incr x
x
126x117x20
18x40x102xπ
1024
÷
10
x
Incr x
11x22x510xπ
97x43x27
MG.33.Q1.02 - VLT
®
is a registered Danfoss trademark
13
2. Introduction
1024
27
Incr x
x
18x40x1024
126x117x20x510xπx10x11x22
Incr x97x
43x27x102
Syncronising Controller MCO 350 Operating
Instructions
x
π
2
Reduce by Pi and 1024 incr.:
Reduce further:
7x5x54x11x22x117
x
97x43x27
27
This gives a ratio of
This is an absolute value, as it contains no infinite number sequences and no rounded values.
4954950
3040659
126x117x20x510x10x11x22
x
18x40x97x43x27x102
27
2.4. Hardware
2.4.1. VLT Control Card Terminals
The terminals on the control card are allocated for synchronising controller functions the following
parameter settings should therefore not be changed in synchronising mode (set-up 1):
Digital inputs 18, 19, 27, 32 and 33
Parameters 510–515 are set to
control card but they are used as inputs for the synchronising controller.
No operation
(default setting), then the inputs are ignored by the
Analogue inputs 53, 54
Parameters 315, 316 and 317 are set to
card but they are used as inputs to the synchronising controller.
Digital/analogue outputs 42
Parameters 650 are set to:
MCO 0 … 20 mA [52] analogue output
2.5. Technical Data
2.5.1. Introduction
Technical data on the control card terminals can be found in the VLT Automation Drive FC 300
Design Guide.
2.5.2. Option Card Terminals
There are two encoder interfaces, which coveers the following functions:
There are 2 digital input/output terminal blocks, 10 inputs and 8 outputs. (See figure below)
MG.33.Q1.02 - VLT
®
is a registered Danfoss trademark
15
2
2. Introduction
Syncronising Controller MCO 350 Operating
Instructions
2.5.3. Encoder Monitor
Both encoder interfaces are equipped with a monitoring circuit that can detect open circuit as well
as short circuit of each encoder channel. Each encoder channel has a LED showing the status:
Green light means OK, no light means fault. An encoder fault will result in an ”Option error” 192
if encoder monitoring is activated via parameter 3239 (master) and 3209 (slave).
2.5.4. Option Card Layout
MCO 350 control terminals are plug connectors with screw terminals; the terminal blocks are
duplicated to enable use of the same MCO 350 in all frame sizes. See illustration to locate the
terminal blocks:
(1) is used with frame sizes A2 and A
(2) is used with frame sizes A5, B1 and B2
X55 = Encoder 2
X56 = Encoder 1
X57 = Digital inputs
X58 = 24VDC supply
X59 = Digital outputs
2.5.5. General Technical Data
− All inputs, outputs and supply voltages are protected against short circuit.
− All inputs, outputs and supply voltages are galvanic isolated from high voltages such as mains
supply and motor voltage (PELV).
− Encoder signals are monitored during operation and standstill.
− All MCO 350 parameters including user defined application parameters are accessible via the
FC 300 Local Control Panel.
− MCO 350 can be combined with other FC 300 options, namely PROFIBUS and DeviceNet interface.
− All digital inputs and outputs are galvanic isolated from the internal electronics and can be
sourced from an external 24V power supply.
2. Introduction
2
Connection Terminals:
Maximum cross section, rigid wire1.5 mm2/AWG 16
Maximum cross section, flexible wire1.5 mm2/AWG 16
Maximum cross section, wire with enclosed core1.5 mm2/AWG 16
Minimum cross section0.082/AWG 28
Digital inputs:
Number of programmable digital inputs10
Terminal blockX57
Terminal number11),21),3,4,5,6,7,8,9,10
LogicPNP or NPN
Voltage level0 - 24 V DC
Voltage level0 - 24 V DC
Voltage level, logic '0' PNP< 5 DC
Voltage level, logic'1' PNP> 10 V DC
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input28 V DC
2)
2)
> 19 V DC
< 14 V DC
1) ) Selected in parameter 5-00 Digital I/O mode.
The digital inputs are galvanic isolated from the internal electronics and can be sourced by an
external 24V power supply.
Digital outputs:
Number of programmable digital outputs8 (6)
Terminal blockX59
Terminal number11), 21),3,4,5,6,7,8
Driver typepush/pull
LogicPNP or NPN
Voltage level0 - 24 V DC
Max. output current (sink or source) with internal power supply (total Σ)40 mA
Max. output current (sink or source) with external power supply (per output)100 mA
Terminals X59-1 and X59-2 can be programmed as input, parameter 33-60.
1)
1
2)
MG.33.Q1.02 - VLT
®
is a registered Danfoss trademark
17
2. Introduction
Syncronising Controller MCO 350 Operating
Instructions
2
Combined Digital Inputs/Outputs:
Number of digital outputs which can be used as digital inputs2
Terminal blockX59
Terminal number1,2
LogicPNP or NPN
Voltage level0 - 24 V DC
Voltage level0 - 24 V DC
Voltage level, logic '0' PNP< 10 V DC
Voltage level, logic'1' PNP> 17 V DC
Voltage level, logic '0' NPN> 13 V DC
Voltage level, logic '1' NPN< 6 V DC
Maximum voltage on input28 V DC
1) Terminals X59-1 and X59-2 can be programmed as input, parameter 33-60.
2) Selected in parameter 5-00 Digital I/O mode.
24 V DC Supply Output
Terminal blockX58
Terminal number1,2
Maximum load65 mA
The internal 24V power supply can be disconnected via parameter 33-85, an external 24V power
supply must then be connected to X58-1 and X58-2.
Encoder Inputs
Number of encoder inputs2
Terminal blockX55 and X56
Terminal number5,6,7,8,9,10,11,12
Input impedance120Ω
Maximum voltage on inputs5 V DC
Cable typeScreened cable with a twisted pair of wires for each encoder channel
Incremental encoder typeRS422/TTL
Maximum frequency410 kHz
Phase displacement between A and B90°±30°
Maximum cable length300 m
Absolute encoder typeSSI
Data codingGray
Data length12 - 37 bit
Clock frequency78 kHz - 2 MHz
Absolute encoder typeSSI
Maximum cable length150 m
1) Always observe specifications/limitations prescribed by the encoder supplier.
2) 150 m cable is possible up to 500 kHz clock frequency, above 500 kHz cable length must be
limited further.
1)
2)
1)
1)
1)
1)
Encoder Output
Number of encoder outputs1
Terminal blockX56
Terminal number5,6,7,8,9,10,11,12
Signal typeRS 422Ω
Maximum frequency410 kHz
Maximum number of slaves31 (more with repeater)
Maximum cable length400 m
Encoder Output
Number of supply voltages3
Terminal blockX55 and X56
Terminal number1,2,3,4
24 V, max load250 mA
8 V, max load250 mA
5 V, max load400 mA
Absolute encoder typeSSI
Maximum cable length150 m
1) This is maximum load when only one supply voltage is used; when 2 or 3 supply voltages are
used simultaneously the load must be reduced accordingly. The following must be observed:
load24V + load8V + load5V ≤ 6W and load8V + load5V ≤ 2W.
2) 8 V is only available at terminal block X55.
2.6. Example of Encoder Interface connections
1) 2)
1)
1)
1)
2
MG.33.Q1.02 - VLT
®
is a registered Danfoss trademark
19
2
2. Introduction
2.7. Description of Terminals
I/O NumberDesignationDescription
1224 V DC24V power supply for switches etc.
1324 V DC24V power supply for switches etc.
18Disable ResyncThe Resync function (to be enabled by param
19Home runStarts the homing.
20GNDGround for 24 V.
27Reset/EnableError reset on rising edge. To enable opera-
32Test run reverseTest run; Program 1:
Speed/Pos -Synchronous operation; Program 2:
Syncronising Controller MCO 350 Operating
Instructions
1924) can be temporarily disabled by setting
this input to 1
tion, this input must be switched to “1”. “0” =
motor coast.
Test run reverse at the speed defined in Parameter 19-01
In velocity synchronous mode (P. 1901 = 0, 3,
6 or 7) the gear ratio and thus the velocity of
the slave can be changed by the value specified in parameter 1912.
In position synchronous and marker synchronous operation (P. 1901 = 1, 2, 4 or 5), the
position offset of the slave can be changed by
the value specified in Parameter 1912. The
sign of the value in parameter 1912 selects the
offset type to be absolute or relative.
Absolute offset means that the fixed offset of
parameter 1912 is changed and this offset is
executed when restarting synchronisation.
Relative offset means that the actual slave position is displaced but the fixed offset of parameter 1912 is unchanged. This again means
that the actual slave position is maintained
when restarting synchronisation. Relative offset is useful when always changing the offset
in the same direction as this would give a very
high fixed offset when using absolute offset.
This high fixed offset would then be executed
when restarting synchronisation and the min.
or max. limit of parameter 1912 would eventually be reached.
05NO
06NC
39GNDGround for analogue inputs/outputs.
42Slave/Master velocity The output value is scaled to maximum slave
5010V DC 15mAPower supply for reference value potentiome-
530 - 10V InServes as reference input for the virtual mas-
540 - 10V InServes as numerator for the gear ratio if “6” or
2. Introduction
Test run forward at the speed defined in Parameter 1901
2
In velocity synchronous mode (P. 1901 = 0, 3,
6 or 7) the gear ratio and thus the velocity of
the slave can be changed by the value specified in parameter 19-12.
In position synchronous and marker synchronous operation (par. 19-01 = 1, 2, 4 or 5), the
position offset of the slave can be changed by
the value specified in Parameter 1912. The
sign of the value in parameter 1912 selects the
offset type to be absolute or relative.
Absolute offset means that the fixed offset of
parameter 19-12 is changed and this offset is
executed when restarting synchronisation.
Relative offset means that the actual slave position is displaced but the fixed offset of parameter 19-12 is unchanged. This again
means that the actual slave position is maintained when restarting synchronisation. Relative offset is useful when always changing the
offset in the same direction as this would give
a very high fixed offset when using absolute
offset. This high fixed offset would then be
executed when restarting synchronisation and
the min. or max. limit of parameter 1912
would eventually be reached.
Relay 1 is open (brake activated) during power
off, and start-up of the frequency converter.
Afterwards the brake-control depends on the
selected Sync mode.
Relay output 2:
Function can be configured by means of Parameter 540.
velocity (parameter 32-80);
The output can be selected between slave or
master velocity by means of parameter 19-25
ter
ter if “0“ is selected in Parameter 19-16.
“7” is selected in parameter 19-01.
MG.33.Q1.02 - VLT
®
is a registered Danfoss trademark
21
2
2. Introduction
2.7.1. Standard RS 485-Interface
I/O NumberDesignationDescription
61Ground RS 485Not used
68RS 485-PNot used
69RS 485-NNot used
2.7.2. MCO 350 Terminal X57
I/O Number DesignationDescription
1I1 - Sync-StartStart and stop of synchronisation. Input
2I2 - Take over gear ratioActivates the gear ratio selected at Ter-
3I3 - Start/Stop virtual masterTest run; Program 1: Start test run
4I4 - HoldThe drive is held at a programmable
5I5 - Master marker inputWhen using external marker signal for
6I6 - Slave marker inputWhen using external marker signal for
7I7 - Measuring of the master marker
interval
Home switchSynchronous operation; Program
8I8 - measuring of the slave marker
interval
I8 - VLT mode selectionSynchronous operation; Program
9
10
Gear ratio 2
Gear ratio 2
0
1
Syncronising Controller MCO 350 Operating
Instructions
1 must be toggled if synchronisation
was interrupted by an error or by input
27 (motor coast). Behaviour at stop can
be selected via parameter 1901.
minals 9 and 10.
with virtual master. Synchronous op-eration; Program 2: The virtual master is accelerated up to the set pulse
frequency, or stopped, with the set
ramp time.
(parameter 1903) speed, or the current
speed (parameter 1902 = 1). Synchronous control is not activated.
the master drive it must be connected
to this input.
the slave drive it must be connected to
this input.
Test run; Program 1:
Measuring of the master marker interval
is started.
2:
If a home position is to be attained, the
home switch must be connected here.
The signal must show a rising edge
Test run; Program 1:
Measurement of the slave marker interval is started.
2:
Switches the VLT to normal frequency
converter operation. The settings for
this operating mode are to be made in
Parameter set-up 2. Refer to the VLT
Automation Drive Product Manual.
Gear ratio least significant bit
Gear ratio most significant bit
1O1 - READYReady, i.e. for the number of marker signals that were
2O2 - FAULTFault, i.e. for the number of marker signals that were
3O3 - ACCURACYThe drive runs within the tolerance specified in Param-
4O4 - Brake controlThis output can be used to control a mechanical brake.
5O5 - SavingThis output stays high while saving is in progress. The
6O6 - Drive runningSignal “1” when the drive is running.
7O7 - Home reached If the data value “1” was chosen in Parameter 3300, this
8O8 - Ready, no error The synchronising controller is ready for operation.
2. Introduction
specified in Parameter 3325, the slave drive has run
within the tolerance (Accuracy).
specified in Parameter 3324, the slave drive has run outside the tolerance (Accuracy). OR when the number of
marker signals have been missing when marker monitor
is activated in parameter 1923.
eter 3313.
“0” means that the brake must be closed (braking) “1”
means that the brake must be open (not braking)
saving is initiated by Parameter 1900, Input 4 or fieldbus
bit 4.
output shows “1” when homing is completed.
2
2.8. Description of Fieldbus Interface
NB!
This section is only relevant if the VLT is equipped with a Field bus interface (option)
as well as the synchronising controller.
The synchronising controller can be controlled via the digital/analogue inputs or via field bus. The
control source can be selected individually for test-run and synchronising in the parameters 1919
(test-run) and 1920 (synchronising). There can only be one control source at a time meaning that
the digital/analogue inputs are inactive when Field bus is selected as control source and visa versa.
The only exception is input 27, which is always stop/enable also when Field bus is selected as
control source. In synchronising mode three signals are only available as digital inputs even when
Field bus is selected as control source that is the marker signals for marker synchronisation and
the Home switch. This is because these signals are too time-critical for Field bus control. Status
signals are always available on the digital/analogue outputs but they are only available via Field
bus when Field bus is selected as control source.
2.8.1. Data Layout
Control and status signals are transferred via the so-called process data channel (PCD) of the
various fieldbus interfaces. The telegram structure and the available number of data words depends on the Fieldbus used, please refer to the manual of the Fieldbus option in use for further
details. The below example is based on the layout of a PROFIBUS telegram, the so-called PPO:
Here you can save the gear-ratio data permanently in the EEPROM
[0]no function
[1]Gear data is being
saved
19-01 Test run; Program 1
Option:Function:
19-01 Synchronous operation; Program 2
Option:Function:
While saving, the value remains “1“; when saving is finished,
the value automatically reverts to “0“. At the same time, during
saving, Output O5 “Saving“ is set to “1“. Saving is not possible
during operation, but only in the stopped state.
Test run speed: Specify here the speed at which the test runs
are to be carried out. The speed is specified as a percentage of
the maximum speed defined in par. 32-80.
Type of operation: Select here the type of operation of the synchronising Controller
3
[0]Speed synchronising
[1]Position synchronising
[2]Marker synchronising
[3]Speed synchronising with motor coast after stop
[4]Position synchronising with motor coast after stop
[5]Marker synchronising with motor coast after stop
[6].Speed synchronising with motor coast after stop and setting of
gear ratio via analogue input 54
[7]Speed synchronising with setting of gear ratio via analogue in-
put 54.
With the selections “0” - “2” and “7” the motor is always controlled keeping the actual position
when stopping synchronisation (input 1 = “0”).
MG.33.Q1.02 - VLT
®
is a registered Danfoss trademark
27
3
3. Programming
19-02 Test run; Program 1
Option:Function:
[0]If “0“ is set, the slave drive is brought to the speed set in par.
[1]If “1“ is set, the actual speed is maintained. While these signals
Syncronising Controller MCO 350 Operating
Instructions
Test run acceleration: Specify here the acceleration for the
test run as a percentage of the maximum acceleration. 100 %
means that the drive accelerates with the minimum ramp specified in par. 32- 8 1 . 5 0 % m e a ns that the drive only proceeds with
half the acceleration, i.e. the acceleration takes twice as long as
with the minimum ramp specified in par. 32-81.
Synchronous operation; Program 2: Hold function:
If the contact at Terminal 29 is closed, the slave drive is disengaged, i.e. it no longer runs in synchrony with the master.
19-03.
are present, the current Hold speed can be changed by means
of Inputs 32 and 33.
19-03 Test run; Program 1
Option:Function:
Test run distance: Specify the distance for the test run in quad
counts.
Synchronous operation; Program 2:
Hold speed: If Hold function “0“ was selected, enter here the
speed as a percentage of the maximum speed (par. 32-80).
19-04 Test run, program 1: synchronising type (Sync type)
Option:Function:
This parameter is used to specify the type of synchronisation
used when optimising the PID controller for synchronisation by
means of the virtual master.
[0]Speed synchronisingSelect “0” if speed synchronising should be used in synchronous
mode
[1]Position synchronis-
ing
Select “1” if position or marker synchronising should be used in
synchronous mode.
Synchronous operation; Program 2:
Delta hold speed: Specify the percentage by which the hold
speed is to change when Input 32 or 33 is activated during Hold
mode.
19-05 Test run, program 1: Activate feed forward and PID calculation (FFVEL calc.)
Option:Function:
This parameter is used to trigger automatic calculation of the
optimal value for velocity feed forward (par. 32-65) as well as
PID sample time (par. 32-69), proportional factor (par. 32-60)
and derivative factor (par. 32-61).
sample time (par. 32-69), Proportional factor (par. 32-60) and
derivative factor (par. 32-61). The calculations are based on the
following parameters that must be set before the calculation is
started:
Par. 32-00/32-02 “Slave encoder type”,
Par. 32-01/32-03 “Slave encoder resolution”,
Par. 32-80 “Maximum velocity”,
3
Synchronous operation; Program 2:
Gear ratio no.: Select the number of the gear ratio that you want to edit in parameters 19-06
to 19-10.
19-06 Gear ratio numerator
Option:Function:
Enter the numerator for the gear ratio selected in par. 19-05.
Ensure that the gear ratio matches the marker ratio.
19-07 Gear ratio denominator
Option:Function:
Enter the denominator for the gear ratio selected in par. 19-05.
Ensure that the gear ratio matches the marker ratio.
19-08 Slave marker quantity
Option:Function:
Enter the number of slave markers for the marker ratio. Ensure
that the gear ratio matches the marker ratio.
MG.33.Q1.02 - VLT
NB!
This parameter is only used in marker synchronising mode (par. 19-01 = 2 or 5).
®
is a registered Danfoss trademark
29
3
3. Programming
19-09 Master marker quantity
Option:Function:
19-10 Fixed offset
Option:Function:
Syncronising Controller MCO 350 Operating
Instructions
Enter the number of master markers for the marker ratio. Ensure that the marker ratio matches the gear ratio.
NB!
This parameter is only used in marker synchronising mode (par. 1901 = 2 or 5).
Enter the position offset. This makes it possible to compensate
for differences in the placing of the encoder or markers. Input
is in quad counts.
Offset_slave
19-11 Step time
Option:Function:
Enter the time after which
•with the Hold function activated and the presence of
•in the engaged state, without Hold, the next change of
Input is in milliseconds.
19-12 Step Length
Option:Function:
Enter the step value for changing the position offset in quad
counts. Par. 19-10 is changed accordingly. The sign of this parameter selects the offset type when changing the offset via the
position + and - inputs:
A positive value selects absolute offset (see Input 32/33).
A negative value selects relative offset (see Input 32/33).
NB!
Offset is related to the master position. Offset related to the slave position can be calculated as
follows:
O ffest x Parameter
:
one of the signals at Terminal 32 or 33, a change in
speed takes place;
the slave position takes place.
Parameter
19 − 06
19 − 07
30
MG.33.Q1.02 - VLT
®
is a registered Danfoss trademark
Loading...
+ 72 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.