Danfoss VLT 6000 HVAC Application guide

■■
The Application
■■
Primary pumps in a primary/secondary pumping system, such as shown in Figure 1, can be used to maintain a constant flow through devices that encounter operation or control difficulties when exposed to variable flow. The primary/secondary pumping technique decouples the primary production loop from the secondary distribution loop. This allows devices such as chillers to obtain constant design flow and operate properly while allowing the rest of the system to vary in flow.
■■
The Design
■■
In Chilled Water systems, the Primary loop or production loop, consists of pumps sized to handle the chillers designed flow rate at a discharge pres­sure just high enough to circulate the water through the chiller and the rest of the primary piping loop. This loop should be as small as possible, just large enough to allow the secondary system to be attached. This minimizes the resistance of the primary loop and therefore the energy consumption of the non-regulated constant flow pumps.
The primary pump flow is traditionally controlled by throttling valves or balance valves on the discharge of the pumps, figure 1. The pumps are often oversized due to safety margin in the designs. By adding losses to the pumping circuit with the throttling valves, the proper design flow rate can be established, figure 2 (moving from flow 1 to Design flow). Another method used is to trim the pumps impeller. Once the system is operating, the balancing contractor can determine the actual pressure drop in the primary loop. Once the actual pressure requirement of the pump is established, the pumps impeller can be removed, trimmed to the proper diameter, rebalanced, and reinstalled in the pump. Decreasing the diameter of the pumps impeller reduces both the capacity and pressure of the pump as desired, but also has an impact on the pumps efficiency, figure 3.
VLT® 6000 HVAC
As the evaporator flow rate decreases in a chiller, the chilled water begins to become over-chilled. As this happens, the chiller attempts to decrease its cooling capacity. If the flow rate drops far enough, or too quickly, the chiller cannot shed its load sufficiently and the chillers low evaporator temperature safety trips the chiller requiring a manual reset. This situation is common in large installations especially when two or more chillers in parallel are installed if primary/secondary pumping is not utilized.
Primary system Secondary system
CHILLER
CHILLER
Fig. 1 - Traditional Primary/Secondary design
Pressure
Design - P2
P1
Pressure
100%
75%
Design
flow
Fig. 2 - Throttling valve
Efficiency
curves
Flow 1
86%
84%
MN.60.D1.02 - VLT is a registered Danfoss trademark
Design flow Flow 1
Fig. 3 - Impeller trimming
Impeller
curves
■■
The new standard:
■■
Depending on the size of the system and the size of the primary loop, the energy consumption of the primary loop can become substantial. A VLT frequency converter can be added to the primary system, to replace the throttling valve and/or trimming of the impellers, leading to reduced operating expenses (fig. 4). Two control methods are common:
The first method uses a flow meter. Because the desired flow rate is known and is constant, a flow meter can be installed at the discharge of each chiller can be used to control the pump directly. Using the built-in PID controller, the VLT frequency converter will always maintain the appropriate flow rate, even compensating for the changing resistance in the primary piping loop as chillers and their pumps are staged on and off.
Flowmeter
F
Flowmeter
F
VLT® 6000 HVAC
The other method is local speed determination. The operator simple decreases the output frequency until the design flow rate is achieved. Using a VLT frequency converter to decrease the pumps speed is very similar to trimming the pumps impeller, except it doesnt require any labor and the pumps efficiency remains higher, figure 5. The balancing contractor simply decreases the speed of the pump until the proper flow rate is achieved and leaves the speed fixed. The pump will operate at this speed any time the chiller is staged on. Because the primary loop doesnt have control valves or other devices that can cause the system curve to change and the variance due to staging pumps and chillers on and off is usually small, this fixed speed will remain appropriate. In the event the flow rate needs to be increased later in the systems life, the VLT frequen-cy converter can simply increase the pumps speed instead of requiring a new pump impeller.
P
VLT
CHILLER
CHILLER
Fig. 4
The VLT frequency converter solution
Flow
Fig. 5
Pump efficiencies with variable speed
(Figure courtesy of ITT Bell & Gossett)
Figure 5 shows that the pumps efficiency remains constant as the speed is reduced to obtain the design flow. This differs from the results of the trimming the impeller where the efficiency de­creases (fig. 3).
MN.60.D1.02 - VLT is a registered Danfoss trademark
Loading...
+ 2 hidden pages