Danfoss VLT5075, VLT5100, VLT6100, VLT6125, VLT5032 Installation guide

...
Installation and Connection
Instructions
VLT® Frequency Converter
Series 5000/6000
180A Ordering Number 176F1818 VLT5075-VLT5100, 400V-500V VLT6100-VLT6125, 460V VLT5032-VLT5052, 200V-240V VLT6042-VLT6062, 200V-240V
400A Ordering Number 176F1819 VLT5125-VLT5250, 400V-500V VLT6150-VLT6300, 460V
External RFI Filter
VLT® Series 5000/6000 HVAC
DANGER
!
English
■■
General
■■
With frequency converters installed, high disturbance levels are caused by fast-acting switching transients of IGBTs on the high voltages used in the dc link and by parasitic capacitance. This can result in conducted disturbances on lines. Electronic devices connected to the same mains line may be impaired by radio frequency interference (RFI). The RFI filter is designed to reduce these effects.
■■
RFI Filter Environmental Conditions
■■
Environment Value
Maximum Ambient Temperature Humidity 5% to 95%
-10°C to 40°C
CE Conformity
All units are CE marked.
■■
Additional Safety Protection
■■
See the VLT instruction manual for use of Type B residual current device (RCD) relays for additional earth fault protection.
RFI Filter Conducted Emissions
The RFI filter meets the conducted emission requirements of EN55011, Class 1B.
Current Ratings
The external Class 1B RFI filters are rated at 180A and 400A.
■■
Electrical Connections
■■
To insure personal safety, power must be removed from mains during installation. Adhere to all local and national electrical safety standards for high voltage installations. See VLT instruction manual for important details.
■■
Input Fuses
■■
All RFI filter and frequency converter combinations must have input fuses installed in the mains power supply. Input fuses must be supplied by the installer of the equipment at the time of installation. See the VLT instruction manual for the required fuse rating for each converter size.
■■
Mains Voltage/Frequency Ratings
■■
Three phase AC, V
= 550 V
line
maximum, 50/60 Hz.
rms
Leakage Current
The external RFI filter, motor, and frequency converter experience a high leakage current. The RFI filter and converter must have reinforced earthing in accordance with EN50178. The 180A filter is specified at <6mA. The 400A filter is specified at <12mA.
MI.56.F1.83 - VLT is a registered Danfoss trademark
Typical Electrical Connection
3
English
VLT® Series 5000/6000 HVAC
Mechanical Installation
The following must be observed.
1) The filter and frequency converter must have a large ground-contact surface. Mount on a common, earthed metal plate or switch gear cabinet panel.
2) The contact surface for mounting the RFI filter must be clean, unpainted, bright metal. Paint or other insulating coatings must be removed prior to mounting the filter.
3) It is important to ensure good electrical contact from the installation back plate through the installation screws to the metal cabinet of the VLT frequency converter.
4) Use of star washers to assure HF connection is recommended.
See the connection diagrams on the following pages.
Wiring
1) Position the toroid between the filter output and the converter. Install tie wraps to secure the wiring (In IP54 auxiliary enclosures, tie-down holes are provided.)
2) Only the 3-phase wiring passes through the toroid. The physical earth (PE) cable must
not pass through the toroid.
3) Cable connections between the RFI filter and the frequency converter should be as short as possible.
4) The mains maximum wire size is 95mm
2
180A filters and 120mm
X 2 for 400A filters.
2
for
5) The PE wire must have a cross-section greater than 50% of the cross-section of the mains wire.
6) Do not install mains and motor cables parallel and near to one another.
7) Maximum cable length of shielded motor wire for Class 1B RFI filter performance is 50m.
Dimension Diagram: 180A RFI FilterDimension Diagram: 180A RFI Filter
Dimension Diagram: 180A RFI Filter
Dimension Diagram: 180A RFI FilterDimension Diagram: 180A RFI Filter
MI.56.F1.83 - VLT is a registered Danfoss trademark4
VLT® Series 5000/6000 HVAC
DANGER
!
Deutsch
■■
Allgemeine Informationen
■■
Bei installierten Frequenzumrichtern kann es in der Hochspannung führenden DC-Verbindung durch schnelle transiente IGBT-Schaltströme und die Eigenkapazität zu einem erheblichen Störniveau kommen. Dies kann leitungsgebunden ausgestrahlte Störungen verursachen. Elektronische Geräte, die an die gleiche Netzleitung angeschlossen sind, können durch Hochfrequenzstörungen (RFI) in ihrer Funktion beeinträchtigt werden. Der Funkentstörfilter (RFI-Filter) besitzt die konstruktionstechnische Aufgabe, diese Störwirkung zu reduzieren.
■■
Betriebsbedingungen für RFI-Filter
■■
Umgebung Wert
Max. Umgebungstemperatur Feuchtigkeit 5% bis 95%
-10°C bis 40°C
verstärkte Erdung nach EN50178 aufweisen. Der 180A­Filter ist für <6mA ausgelegt. Der 400A-Filter ist für <12mA ausgelegt
■■
Zusätzlicher Sicherheitsschutz
■■
Informationen über den zusätzlichen Schutz gegen Erdschlußfehler durch Verwendung von Fehlerstrom­relais (RCD-Relais Typ B) finden Sie im VLT­Bedienungshandbuch.
■■
RFI-Filter-Störspannungen
■■
Alle RFI-Filter erfüllen die Störspannungsanforderungen der EN55011, Klasse 1B.
Nennstromstärken
Die Nennstromstärken bei RFI-Filtern der Klasse 1 betragen 180A und 400A.
.
CE-Konformität
Alle Geräte sind mit einem CE-Kennzeichen versehen.
■■
Elektrische Anschlüsse
■■
Zur eigenen Sicherheit muß die Netzversorgung bei der Installation unterbrochen werden. Alle örtlichen und im Installationsland geltenden Sicherheitsvorschriften für Hochspannungsanlagen sind einzuhalten. Wichtige Hinweise hierzu finden Sie im VLT-Bedienungshandbuch.
■■
Eingangsicherungen
■■
Bei allen RFI-Filter- und Frequenzumrichterkombinationen müssen Eingangs­sicherungen in der Netzstromversorgung installiert werden. Die Eingangssicherungen müssen bei der Installation vom Geräteinstallateur geliefert werden. Die für die jeweilige Frequenzumrichtergröße erforderlichen Sicherungsleistungsdaten finden Sie im VLT­Bedienungshandbuch.
■■
Netzspannung/Frequenz
■■
Kriechstrom
Drehstrom AC, V
Der externe RFI-Filter, der Motor und der Frequenz­umrichter weisen hohe Ableitströme auf. RFI-Filter und Frequenzumrichter müssen über eine
MI.56.F1.83 - VLT is a registered Danfoss trademark
= 550 V
line
max., 50/60 Hz.
rms
Typische elektrische Verdrahtung
5