400A Ordering Number 176F1819
VLT5125-VLT5250, 400V-500V
VLT6150-VLT6300, 460V
External RFI Filter
VLT® Series 5000/6000 HVAC
DANGER
!
English
■■
■ General
■■
With frequency converters installed, high disturbance
levels are caused by fast-acting switching transients
of IGBTs on the high voltages used in the dc link and
by parasitic capacitance. This can result in conducted
disturbances on lines.
Electronic devices connected to the same mains line
may be impaired by radio frequency interference (RFI).
The RFI filter is designed to reduce these effects.
■■
■ RFI Filter Environmental Conditions
■■
Environment Value
Maximum Ambient Temperature
Humidity 5% to 95%
-10°C to 40°C
CE Conformity
All units are CE marked.
■■
■ Additional Safety Protection
■■
See the VLT instruction manual for use of Type B
residual current device (RCD) relays for additional
earth fault protection.
■ ■
■ RFI Filter Conducted Emissions
■ ■
The RFI filter meets the conducted emission
requirements of EN55011, Class 1B.
■ ■
■ Current Ratings
■ ■
The external Class 1B RFI filters are rated at 180A
and 400A.
■■
■ Electrical Connections
■■
To insure personal safety, power must be
removed from mains during installation.
Adhere to all local and national electrical
safety standards for high voltage installations.
See VLT instruction manual for important details.
■■
■ Input Fuses
■■
All RFI filter and frequency converter combinations
must have input fuses installed in the mains power
supply. Input fuses must be supplied by the installer
of the equipment at the time of installation. See the
VLT instruction manual for the required fuse rating
for each converter size.
■■
■ Mains Voltage/Frequency Ratings
■■
Three phase AC, V
= 550 V
line
maximum, 50/60 Hz.
rms
■ ■
■ Leakage Current
■ ■
The external RFI filter, motor, and frequency
converter experience a high leakage current.
The RFI filter and converter must have reinforced
earthing in accordance with EN50178. The 180A
filter is specified at <6mA. The 400A filter is specified
at <12mA.
MI.56.F1.83 - VLT is a registered Danfoss trademark
Typical Electrical Connection
3
English
VLT® Series 5000/6000 HVAC
■ Mechanical Installation
The following must be observed.
1) The filter and frequency converter must have a
large ground-contact surface. Mount on a
common, earthed metal plate or switch gear
cabinet panel.
2) The contact surface for mounting the RFI filter
must be clean, unpainted, bright metal. Paint or
other insulating coatings must be removed prior
to mounting the filter.
3) It is important to ensure good electrical contact
from the installation back plate through the
installation screws to the metal cabinet of the
VLT frequency converter.
4) Use of star washers to assure HF connection is
recommended.
See the connection diagrams on the following pages.
■ Wiring
1) Position the toroid between the filter output and
the converter. Install tie wraps to secure the
wiring (In IP54 auxiliary enclosures, tie-down
holes are provided.)
2) Only the 3-phase wiring passes through the
toroid. The physical earth (PE) cable must
not pass through the toroid.
3) Cable connections between the RFI filter and
the frequency converter should be as short as
possible.
4) The mains maximum wire size is 95mm
2
180A filters and 120mm
X 2 for 400A filters.
2
for
5) The PE wire must have a cross-section greater
than 50% of the cross-section of the mains wire.
6) Do not install mains and motor cables parallel
and near to one another.
7) Maximum cable length of shielded motor wire for
Class 1B RFI filter performance is 50m.
MI.56.F1.83 - VLT is a registered Danfoss trademark4
VLT® Series 5000/6000 HVAC
DANGER
!
Deutsch
■■
■ Allgemeine Informationen
■■
Bei installierten Frequenzumrichtern kann es in der
Hochspannung führenden DC-Verbindung durch
schnelle transiente IGBT-Schaltströme und die
Eigenkapazität zu einem erheblichen Störniveau
kommen. Dies kann leitungsgebunden ausgestrahlte
Störungen verursachen. Elektronische Geräte, die an
die gleiche Netzleitung angeschlossen sind, können
durch Hochfrequenzstörungen (RFI) in ihrer Funktion
beeinträchtigt werden. Der Funkentstörfilter (RFI-Filter)
besitzt die konstruktionstechnische Aufgabe, diese
Störwirkung zu reduzieren.
■■
■ Betriebsbedingungen für RFI-Filter
■■
Umgebung Wert
Max. Umgebungstemperatur
Feuchtigkeit 5% bis 95%
-10°C bis 40°C
verstärkte Erdung nach EN50178 aufweisen. Der 180AFilter ist für <6mA ausgelegt. Der 400A-Filter ist für
<12mA ausgelegt
■■
■ Zusätzlicher Sicherheitsschutz
■■
Informationen über den zusätzlichen Schutz gegen
Erdschlußfehler durch Verwendung von Fehlerstromrelais (RCD-Relais Typ B) finden Sie im VLTBedienungshandbuch.
■■
■ RFI-Filter-Störspannungen
■■
Alle RFI-Filter erfüllen die Störspannungsanforderungen
der EN55011, Klasse 1B.
■ ■
■ Nennstromstärken
■ ■
Die Nennstromstärken bei RFI-Filtern der Klasse 1
betragen 180A und 400A.
.
CE-Konformität
Alle Geräte sind mit einem CE-Kennzeichen versehen.
■■
■ Elektrische Anschlüsse
■■
Zur eigenen Sicherheit muß die Netzversorgung bei
der Installation unterbrochen werden.
Alle örtlichen und im Installationsland geltenden
Sicherheitsvorschriften für Hochspannungsanlagen
sind einzuhalten. Wichtige Hinweise hierzu finden
Sie im VLT-Bedienungshandbuch.
■■
■ Eingangsicherungen
■■
Bei allen RFI-Filter- und
Frequenzumrichterkombinationen müssen Eingangssicherungen in der Netzstromversorgung installiert
werden. Die Eingangssicherungen müssen bei der
Installation vom Geräteinstallateur geliefert werden. Die
für die jeweilige Frequenzumrichtergröße erforderlichen
Sicherungsleistungsdaten finden Sie im VLTBedienungshandbuch.
■■
■ Netzspannung/Frequenz
■■
■ ■
■ Kriechstrom
■ ■
Drehstrom AC, V
Der externe RFI-Filter, der Motor und der Frequenzumrichter weisen hohe Ableitströme auf. RFI-Filter und
Frequenzumrichter müssen über eine
MI.56.F1.83 - VLT is a registered Danfoss trademark
= 550 V
line
max., 50/60 Hz.
rms
Typische elektrische Verdrahtung
5