■ Warning and alarm messages ................................ 35
■ Glossary and parameter list.................................... 36
Contents
■ Index ...................................................................... 39
Copyrights, Limitation of Liability and Revision Rights.
This publication contains information proprietary to Danfoss A/S. By accepting and using this manual the user
agrees that the information contained herein will be used solely for operating equipment of Danfoss A/S or
equipment from other vendors provided that such equipment is intended for communication with Danfoss
equipment over a PROFIBUS serial communication link. This publication is protected under the Copyright laws of
Denmark and most other countries.
Danfoss A/S does not warrant that a software program produced according to the guidelines provided in this
manual will function properly in every physical, hardware or software environment.
Although Danfoss A/S has tested and reviewed the documentation within this manual, Danfoss A/S makes no
warranty or representation, either express or implied, with respect to this documentation, including its quality,
performance, or fitness for a particular purpose.
In no event shall Danfoss A/S be liable for direct, indirect, special, incidental, or consequential damages arising
out of the use, or the inability to use information contained in this manual, even if advised of the possibility of such
damages. In particular, Danfoss A/S is not responsible for any costs including but not limited to those incurred as
a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the
costs to substitute these, or any claims by third parties.
Danfoss A/S reserves the right to revise this publication at any time and to make changes in its contents without
prior notice or any obligation to notify previous users of such revisions or changes.
MG.90.A2.02 – VL T is a registered Danfoss trademark
1
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
When reading through this manual, you will come
across various symbols that require special attention.
The symbols used are the following:
Indicates a general warning.
Indicates something to be noted by
the reader.
Indicates a high-voltage warning.
PROFIBUS is a registered trademark.
2
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ About this manual
This manual is intended to be used both as an
instructional and as a reference manual. It only briefly
touches on the basics of the PROFIBUS protocol
whenever it is necessary for gaining an understanding
of the PROFIDRIVE implementation of the PROFIBUS
Profile for Variable Speed Drives (VDI/VDE 3689) and
the DANFOSS PROFIBUS for the FC motor and the
VLT 2800.
The manual is also intended to serve as a guideline
when you specify and optimize your communication
system.
If you are not completely familiar with PROFIBUS or
the Profile for Variable Speed Drives, it may be
advisable to read some of the material provided on
these subjects, eg DIN 19245 parts 1 and 3 and VDI/
VDE 3689.
Even if you are an experienced PROFIBUS
programmer, we suggest that you read this manual in
its entirety before you start programming, since
important information can be found in all chapters.
Introduction
■ Assumptions
This manual assumes that you are using a DANFOSS
FCM 300 and VLT 2800 with PROFIBUS. It is also
assumed that you, as a master, are using a PLC or
PC that is equipped with a serial communication card
supporting all the PROFIBUS communication services
required by your application, and that all
requirements stipulated in the PROFIBUS standard as
well as those set up in the PROFIBUS Variable Speed
Drives Profile and its company-specific
implementation PROFIDRIVE, as well as those
pertaining to the VLT Variable Speed Drive are strictly
observed as well as all limitations therein fully
respected.
■ What you should already know
The DANFOSS PROFIBUS is designed to
communicate with any master abiding by the
PROFIBUS DP standard. It is therefore assumed that
you have full knowledge of the PC or PLC you intend
to use as a master in your system. Any questions
pertaining to hardware or software produced by any
other manufacturer is beyond the scope of this
manual and is of no concern to DANFOSS.
If you have questions about how to set up master master communication or communication to a nonDanfoss slave, the appropriate manuals should be
consulted.
MG.90.A2.02 – VL T is a registered Danfoss trademark
3
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
Programming:See the design guide:
FC motor (MG.03.Bx.02)
VLT 2800 (MG.28.Ex.02)
for descriptions on how to programme the ordinary
FC motor and VLT 2800.
Quick Setup
■ General information
Parameter 918:
Set the station address, - one unique address per
unit.
In parameters 502-508 it is possible to define how to
gate the control commands from the PROFIBUS with
the equivalent control commands of the digital inputs.
The FC motor/VLT 2800 adjusts to the baudrate and
the configuration from the master.
Communication is established by setting the
parameters stated below.
Setting up the master: See the manual on the master
as well as the chapters of this manual giving details
on the PROFIBUS interface for information on how to
set up the master.
4
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ Master controlled Variable Speed Drives (VSD)
The PROFIBUS Field-bus was designed to give you
unprecedented flexibility and command over your
VSD controlled system. The PROFIBUS will perform
as an integrated part of your VLT VSD, giving you
access to all parameters relevant to your application.
The VSD will always act as a slave, and together with
a master it can exchange a multitude of information
and commands. Control signals such as speedreference, start / stop of motor, reverse operation,
etc. are transmitted from the master in the form of a
telegramme. The VSD acknowledges receipt by
transmitting status signals, such as running, onreference, motor stopped and so on to the master.
The VSD may also transmit fault indications, alarms
and warnings to the master, such as Overcurrent or
Phaseloss.
The PROFIBUS communicates according to the
PROFIBUS Protocol Standard DIN 19245 parts 1 and
3. This means that it can communicate with all
masters that comply with this standard, but it does
not necessarily mean that all services available in the
PROFIBUS standard are supported. The VDI / VDE3689 PROFIBUS Profile for Variable Speed Drives is a
subset of PROFIBUS which only supports the
services relevant to speed control applications.
PROFIDRIVE is an implementation of VDI / VDE 3689
profile created by DANFOSS and a number of other
companies.
Communication partners
In a control system the VSD will always act as a slave,
and as such it may communicate with a single master
or multiple masters depending on the nature of the
application. A master may be a PLC or a PC that is
equipped with a PROFIBUS communication card.
■ Physical layer
The field of application of a field-bus system is
primarily determined by the transmission media and
the physical bus interface selected. The type of bus
cable required for the application and its installation
(physical layer) are particularly important factors, in
addition to the required transmission reliability of the
physical level.
Though a fundamental feature of the PROFIBUS standard is the possibility of specifying several different
physical interfaces, the standard, at the time of
printing, has allowed for one universal specification
only, namely the EIA Standard RS 485-A, which has
found acceptance both in the field of factory automation and in several areas of the processing industry.
The PROFIBUS Interface
■ Cable lengths/number of nodes
The maximum cable length in one segment is
depending on the transmission speed. The total cable
length includes drop cables if any. A drop cable is the
connection from the main bus cable to each node if a
T-connection is used instead of connecting the main
bus cable directly to the nodes, see drop cable
length. The table below shows the maximum allowed
cable length and maximum number of nodes/VLT’s
with 1, 2, 3 and 4 bus segments.
Note that a repeater is a node in both of the two
segments it connects. The number of VLT is based on
a single master system. If there are more masters the
number of VLT must be reduced correspondingly.
MG.90.A2.02 – VL T is a registered Danfoss trademark
5
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
The total drop cable length for one segment is limited
as stated in the table below.
Drop cable length
Max. drop cable
length per segment
Transmission speed[m]
9.6-93.75 kBaud96
187.5 kBaud75
500 kBaud30
The PROFIBUS Interface
1.5 MBaud10
3 MBaudnone
The length statements in the tables above are valid
provided that bus cable with the following properties
is used:
-Impedance:135 to 165 ohm
at a measuring frequency from 3 to
20 MHz
-Resistance:<110 ohm/km
-Capacity:< 30pF/m
-Damping:max. 9 dB over the whole wire
length
-Cross section: max. 0.34 mm
2
,
corresponding to AWG 22
-Cable type:twisted in pairs,
1 x 2, or 2 x 2, or 1 x 4 wires
-Screening:Copper-braided screen
or braided screen and foil screen
It is recommended to use the same cable type in the
entire network to avoid impedance mismatch.
The numbers on the following drawing indicate the
maximum number of stations in each segment. They
are
not the station addresses as each station in the
network must have a unique address.
Segment 1
Segment 2
Segment 3
Segment 4
Rt = termination
resistors
6
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300:FCM 300:
FCM 300:
FCM 300:FCM 300:
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
The PROFIBUS Interface
■ Physical connection
The PROFIBUS is connected to the bus line via X100,
terminals 1 and 2.
It is recommended to use a master with a galvanic
isolated bus driver and with over voltage protection
(e.g. zenerdiode).
EMC precautions
The following EMC precautions are recommended to
obtain interference free operation of the PROFIBUS
network. Additional information on EMC can be found
in the design guide on the FC motor (MG.03.Bx.02).
Please also consult the manual of the PROFIBUS
master for further installation guidelines.
If the PROFIBUS cable has to cross a motor and
brake resistor cable they must cross each other at
an angle of 90°.
-Connection of the cable screen
The screen of the PROFIBUS cable must always
be connected to ground at both ends, that means
the screen must be connected to ground in all
stations connected to the PROFIBUS network. It
is very important to have a low impedance
ground connection of the screen, also at high
frequencies.This can be obtained by connecting
the surface of the screen to ground, for example
by means of a cable clamp or a conductive cable
gland.
The FC motor Series is provided with different
clamps and brackets to enable a proper ground
connection of the PROFIBUS cable screen. The
screen connection is shown in the following
drawing.
Relevant national and local regulations, for
example regarding protective earth
connection, must be observed.
-Cable routing
The PROFIBUS communication cable must be
kept away from motor and brake resistor cables to
avoid coupling of high frequency noise from one
cable to the other. Normally a distance of 200 mm
is sufficient, but it is generally recommended to
keep the greatest possible distance between the
cables, especially where cables are running in
parallel over long distances.
-Earth connection
It is important that all stations connected to the
PROFIBUS network are connected to the same
earth potential. The earth connection must have a
low HF (high frequency) impedance. This can be
achieved by connecting a large surface area of the
cabinet to earth, for example by mounting the FC
motor on a conductive rear plate.
Especially when having long distances between
the stations in a PROFIBUS network it can be
necessary to use additional potential equalizing
cables, connecting the individual stations to the
same earth potential.
Connecting the bus line
MG.90.A2.02 – VL T is a registered Danfoss trademark
7
FCM 300:FCM 300:
FCM 300:
FCM 300:FCM 300:
The bus termination
See drawing on page 6
The PROFIBUS Interface
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
It is essential that the bus line be terminated properly.
A mismatch of impedance may result in reflections
on the line that will corrupt data transmission.
-The PROFIBUS is provided with a suitable
termination which may be activated by the
switches of the RS485 switch block located
just to the left of the terminal block X100 (see
drawing below). The switches should be on to
terminate the bus.
The switches should never be left in opposite
positions. They should either both be ON or
both be OFF!
-Most masters and repeaters are equipped with
their own termination.
-If an external termination circuit consisting of three
resistors is connected to the bus line a 5 V d.c.
power supply must be used, please note that this
must be galvanically isolated from the a.c. line.
8
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300:FCM 300:
FCM 300:
FCM 300:FCM 300:
■ LEDs
There are 2 LEDs on the PROFIBUS:
LED303:Lights up when the card is initialized
and ready to communicate. It will
flash while auto baudrate detection is
attempting to detect the actual
baudrate.
LED304:Lights up when the card is
communicating, depending on
baudrate.
A high baudrate results in dim light in LED304.
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
The PROFIBUS Interface
MG.90.A2.02 – VL T is a registered Danfoss trademark
9
VLVL
T 2800T 2800
VL
T 2800
VLVL
T 2800T 2800
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
::
:
::
■ Physical connection
The PROFIBUS is connected to the bus line via,
terminals 68 and 69.
It is recommended to use a master with a galvanic
isolated bus driver and with over voltage protection
(e.g. zenerdiode).
The PROFIBUS Interface
EMC precautions
The following EMC precautions are recommended to
obtain interference free operation of the PROFIBUS
network. Additional information on EMC can be found
in the design guide on the VLT 2800 (MG.28.Ex.02).
Please also consult the manual of the PROFIBUS
master for further installation guidelines.
If the PROFIBUS cable has to cross a motor and
brake resistor cable they must cross each other at
an angle of 90°.
-Connection of the cable screen
The screen of the PROFIBUS cable must always
be connected to ground at both ends, that means
the screen must be connected to ground in all
stations connected to the PROFIBUS network. It
is very important to have a low impedance
ground connection of the screen, also at high
frequencies.This can be obtained by connecting
the surface of the screen to ground, for example
by means of a cable clamp or a conductive cable
gland.
The VLT 2800 Series is provided with different
clamps and brackets to enable a proper ground
connection of the PROFIBUS cable screen. The
screen connection is shown in the following
drawing.
Relevant national and local regulations, for
example regarding protective earth
connection, must be observed.
-Cable routing
The PROFIBUS communication cable must be
kept away from motor and brake resistor cables to
avoid coupling of high frequency noise from one
cable to the other. Normally a distance of 200 mm
is sufficient, but it is generally recommended to
keep the greatest possible distance between the
cables, especially where cables are running in
parallel over long distances.
-Earth connection
It is important that all stations connected to the
PROFIBUS network are connected to the same
earth potential. The earth connection must have a
low HF (high frequency) impedance. This can be
achieved by connecting a large surface area of the
cabinet to earth, for example by mounting the VLT
2800 on a conductive rear plate.
Especially when having long distances between
the stations in a PROFIBUS network it can be
necessary to use additional potential equalizing
cables, connecting the individual stations to the
same earth potential.
Connecting the bus line
10
MG.90.A2.02 – VL T is a registered Danfoss trademark
VLVL
T 2800T 2800
VL
T 2800
VLVL
T 2800T 2800
The bus termination
See drawing on page 6
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
The PROFIBUS Interface
::
:
::
It is essential that the bus line be terminated properly.
A mismatch of impedance may result in reflections on
the line that will corrupt data transmission.
-The PROFIBUS is provided with a suitable
termination which may be activated by the
switches of the RS485 switch block located
just to the left of the terminal block X100 (see
drawing below). The switches should be on to
terminate the bus.
The switches should never be left in opposite
positions. They should either both be ON or
both be OFF!
-Most masters and repeaters are equipped with
their own termination.
-If an external termination circuit consisting of three
resistors is connected to the bus line a 5 V d.c.
power supply must be used, please note that this
must be galvanically isolated from the a.c. line.
MG.90.A2.02 – VL T is a registered Danfoss trademark
11
VLVL
T 2800T 2800
VL
T 2800
VLVL
T 2800T 2800
■ LEDs
There are 2 LEDs on the PROFIBUS:
LD851:Lights up when the card is initialized
and ready to communicate. It will
flash while auto baudrate detection is
attempting to detect the actual
The PROFIBUS Interface
LD852:Lights up when the card is
A high baudrate results in dim light in LD852.
baudrate.
communicating, depending on
baudrate.
::
:
::
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
12
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ Bus topology
Single master operation with DP
FeaturFeatur
es of DPes of DP
Featur
es of DP (Distributed Periphery)
FeaturFeatur
es of DPes of DP
-Is used by several PLC manufacturers for remote
peripheral I/O communication.
-Supports cyclical communication.
-SRD service gives fast cyclical exchange of
process data between master and slaves.
-Freeze and synchronize function is supported
-Fixed data structure.
-Fixed telegramme size.
-Occupies I/O memory space in PLC proportional
to the number of slaves employed, which may limit
the number of participants. Additional data
require additional I/O memory space.
-Single master
-PLC communicates with telegrams of constant
length
-Fits to time critical requirements
-No need for equidistant transmissions of
set points
Cyclical transmission
1. Set point transmission
2. Actual value feed back
3. New setpoints computed
4. New setpoint transfer
DP should be used when fast cyclical process control
is needed. Such a concept would typically call for
single master operation with a limited number of slave
stations. (A high number of slaves will reduce the
system response).
This could also be the case where control loops are
closed over the bus.
As a very fast alternative it is of course possible to
close the control loop outside the bus.
System layout
Transferring large amount of data where rapid transfer
of process data does not have highest priority
MG.90.A2.02 – VL T is a registered Danfoss trademark
13
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
Closing the control loop over the bus
System layout
Closing the control loop outside the fieldbus
for extremely fast feed-back
Rapid Cyclical transmission with PPO using DP
Parameter up-/downloads can be achieved by using
the so-called Parameter / Process Objects - PPOs of 12, 20 or 28 bytes length as specified in the VDI/
VDE 3689 profile, see drawing page 16.
This procedure, however, occupies 8 bytes additional
I/O memory space in the PLC bytes per slave, and
slows down the system (see also “Timing” page 15).
Control of the drives during normal operation is often
very time critical, but it involves very few data, such
as control commands and speed reference. DP is
optimized for fast cyclical communication.
■ Features and services supported by FC motor
and the VLT 2800
Features available as described by the unit
classification
The unit classification as layed out in the PROFIBUS
Profile for VSDs describes the functionality of the unit.
There are 4 classes where class 1 signifies the lowest
performance class, and class 4 the highest.
The FC motor / VLT 2800 is a class 3 unit except for
the following features:
-Fault buffer
-Change access rights for parameter write
-Change access rights for process control
-Time difference
-Hardware configuration ident.
The FC motor / VLT 2800 complies with the following
class 4 features:
-Baudrate > 500 kBaud
-Programmable content of PCD 3 through 6 (10) of
the PPO’s
-PPO type 5
14
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■■
■ FC motor / VLT 2800 response time
■■
The update time via the PROFIBUS connection can
be divided in two parts:
1) The communication time, which is the time it takes
to transmit data from the master to the slave (FC
motor / VLT 2800 with PROFIBUS), and 2) the
internal update time, which is the time it takes to
transmit data between the FC motor / VLT 2800
control card and the PROFIBUS.
Communication time (t
) depends on the actual
com
transmission speed (baudrate) and the type of master
in use. The minimum obtainable communication time
with the FC motor / VLT 2800 with PROFIBUS is
approx. 100 µsec per slave, when using DP
communication with 4 bytes of data (PPO type 3) at 3
Mbaud. More data or lower transmission speed will
increase the communication time.
The internal update time (t
) depends on the type of
int
data in question as there are different channels for the
data transfer where time critical data e.g. control
word has highest priority. The internal update time for
the different types of data are stated below.
Update
Datatime, t
Control word/Main reference
(part of PPO) 42 msec
Status word/Actual output frequency
The system update time is the time it takes to
update all the slaves in the network when using
cyclical communication. The drawing below shows
the value which is obtainable in theory at 2 input
and 2 output bytes.
MG.90.A2.02 – VL T is a registered Danfoss trademark
15
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ DP communication relations
DP
Communication according to PROFIBUS DP, i.e. DIN
19245 part 1 & 3, is supported. Consequently a
master that supports PROFIBUS DP must be used.
■ PPO description
A special feature of the PROFIBUS Profile for VSD’s is
the communication object called a PPO, meaning
Parameter-Process Data Object.
The PPO is well suited for fast cyclical data transfer,
and may, as the name implies, carry both process
data and parameters.
The selection of PPO type is made according to the
master request.
A PPO may consist of a parameter part and process
data part. The parameter part can be used for
reading and/or updating the parameters one by one.
PPO. Parameter-Process Data Object
By DP one of the following shown PPO’s must be used:
By DP communication one of the parameter-process
data objects (PPO’s) described below must be used.
The process data part consists of a fixed part (4
bytes) and a parametrable part (8 or 16 bytes). In the
fixed part control word and speed reference are
transfered to the VLT while status word and actual
output frequency feedback are transfered from the
VLT. In the parametrable part the user chooses which
parameters have to be transfered to (parameter 915)
and which from (parameter 916) the VLT.
Type 1, 2 and 5 consist of the parameter part and 4,
12 and 20 byte process data, respectively.
Type 3 and 4 consist of 4 and 12 byte process data,
respectively.
PCD: Process Data
PCV: Parameter-Characteristics-Value
PCA: Parameter-Characteristics (Bytes 1, 2)
PCA handling below
IND:Subindex (Byte 3), (Byte 4 is not used)
PVA: Parameter value (Bytes 5 to 8)
CTW: Control word
STW: Status word
MRV: Main reference value
MAV: Main actual value (Actual output frequency)
see page 22
16
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ PCA handling
The PCA portion of the PPO types 1, 2 and 5 will
handle a number of tasks. The master may control
and supervise parameters and request a response
from the slave, while the slave, apart from responding
to a request from the master may transmit a
spontaneous message.
Requests and responses is a handshake procedure
and cannot be batched, meaning that if the master
sends out a Read/write request, it has to wait for the
response, before it sends a new request. The request
or response data value will be limited to max. 4 bytes,
which implies that text strings are not transferable.
0No response
1Transfer parameter value (word)
2Transfer parameter value (long word)
3Transfer description element
4Transfer parameter value (array word)
5
Transfer parameter value (array long word)
6Transfer number of array elements
7Request rejected (incl. fault #, see below)
8Not seviceable by PCV interface
9Spontaneous message (word)
If the slave rejects a request from the master, the RC word in
the PPO-read will indicate this by assuming the value 7.
The fault # will be carried by bytes 7 and 8 in the PVA element.
DP
Request/response handling
The RC portion of the PCA word defines the requests
that may be issued from the master to the slave as
well as what other portions of the PCV (IND and PVA)
are involved.
The PVA portion will transmit word-size parameter
values in bytes 7 and 8, while long word size values
require bytes 5 to 8 (32 bits).
If the Response / Request contains array elements,
the IND will carry the Array Subindex. If parameter
descriptions are involved, the IND will hold the Record
Subindex of the Parameter description.
RC content
RequestFunction
0No request
1Request parameter value
2Change parameter value (word)
3Change parameter value (long word)
4Request description element
5Change description element
6Request parameter value (array)
7Change parameter value (array word)
8
Change parameter value (array long word)
9Request number of array elements
10-15Not used
Fault #Interpretation
0Illegal PNU
1Parameter value cannot be changed
2Upper or lower limit exceeded
3Subindex corrupted
4No array
5Data type false
6Cannot be set by user (reset only)
7Description element cannot be changed
8IR required PPO-write not available
9Description data not available
10Access group
11No parameter write access
12Key word missing
13
14
Text in cyclical transmission not readable
Name in cyclical transmission not readable
15Text array not available
16PPO-write missing
17Request temporarily rejected
18Other fault
19
Date in cyclical transmission not readable
130There is no bus access to the parameter
called
131Data change is not possible because
factory Setup has been selected
MG.90.A2.02 – VL T is a registered Danfoss trademark
17
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ Parameter and data type structure description
DP
Parameter description:
PNU
Characteristics
Subindex 1
DP has a number of describing attributes (see rigth).
Size of elements
Read/write on parameter description is made by the
PCV part using the RC commands 4/5 and subindex
of the desired description element.
Size attribute
The size index and the conversion index for each
parameter can be taken from the parameter list on
page 36.
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ Object and data types supported by FC motor
and VLT 2800
Data types supported by FC motor and VLT 2800
DataObject ShortDescription
typeCodename
3512Integer 16
55Unsigned 8
65O2Unsigned 16
75O4Unsigned 32
105Byte string
135Time difference
1)
335N2Standardized value (16 bit)
355V2Bit sequence
1)
See elaboration below
1)
Time difference
The data type time difference is a time indication in
milliseconds.
Notation:Time difference
Value range: 0 ≤ i ≤ (2
32
-1) milliseconds
Coding:The time is presented as a binary
value of 32 bits (4 bytes). The first
four (MSB) bits are always zero.
Time difference is thus a byte string
of 4 bytes.
Data coding of the data type time difference
BitByte 1Byte 2Byte 3Byte 4
80ms223ms215ms27msMSB
70ms222ms214ms26msMSB
60ms221ms213ms25msMSB
50ms220ms212ms24msMSB
4227ms219ms211ms23ms
3226ms218ms210ms22ms
2225ms217ms29ms21ms
1224ms216ms28ms20ms
Standardized value
1)
A liniary value.
14
0% = 0 (0h), 100% is 2
(4000h)
Data typeN 2
Range-200% ... 200% – 2
Resolution2
–14
= 0.0061%
Length2 bytes
Notation: 2’s complement notation.
MSB is 1st bit after sign bit in 1st byte.
Sign bit = 0 = positive number
Sign bit = 1 = negative number
Bit 8 7 6 5 4 3 2 1
0
Byte 1SIGN 2
Byte 2 2–72
–12–22–32–42–52–6
2
–82–92–102–112–122–132–14
DP
–14
■ Spontaneous messages
The Spontaneous message is activated by the active
parameters i.e. 538, 540, or 953 and will be carried
with the PCV response, stating PNU and PVA of the
changed active parameter that triggered the
message.
Spontaneous messages are generated when the
value is changed in one of the abovementioned
parameters. It means that a message will be sent
when a warning comes, and when a warning
disappears.
Simultaneously the VLT will toggle the SPM bit (11) of
PCA word (see “PCA handling” page 17).
Bit sequence
16 boolean values for control and presentation of user
functions. Notation is binary.
Bit 87654321
Byte 115141312111098
Byte 276543210
The Spontaneous messages will be transmitted until
the master has acknowledged reception of the
message by changing the SPM bit.
Spontaneous messages are only active when
parameter 917 is “ON”!
MG.90.A2.02 – VL T is a registered Danfoss trademark
19
Example of SPM execution
DP
In the VLT the SPMs are temporarily stored in a FIFO
buffer. This means that up to 16 consecutive SPMs
can be retained. If only one SPM has entered the
FIFO, the VLT will resume normal communication as
soon as the SPM has been acknowledged by the
master (and the condition causing the SPM been
rectified). If more SPMs are in the FIFO, these will be
transmitted consecutively upon acknowledgement. If
more SPMs are triggered when the FIFO is full, these
will be ignored.
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
PCA
MASTER
REQ 1
REQ 2
SPM 1 ACK.
SPM 2 NOT ACK.
REQ 2
SPM 2 ACK.
SPM BIT
0
0
0
1
1
0
1
0
0
0
SLAVE
RES. 1
SPM 1
SPM 2
SPM 2
RES. 2
■ Synchronize and freeze
The control commands SYNC/UNSYNC and
FREEZE/UNFREEZE are broadcast functions. SYNC/
UNSYNC is used to send syncronized control
commands and/or speed reference to all the
connected slaves (FC motor Series/VLT 2800 Series).
FREEZE/UNFREEZE is used to freeze the status
feedback in the slaves to get syncronized feedback
SYNC/UNSYNC
SYNC/UNSYNC can be used to obtain simultaneous
reactions in several slaves, for example synchronised
start, stop or speed change. A SYNC command will
freeze the actual control word and speed reference,
incoming Process Data will be stored but not used
until a new SYNC command or a UNSYNC command
is received.
from all connected slaves.
See the example below where the left column holds
The synchronize and freeze commands only affect
Process Data (the PCD part of the PPO).
the speed reference send out by the master and the
three right columns hold the actual speed reference
used in each of the three slaves.
Actual slave speed reference
VLTVLTVLT
From DP master to address:Address 3Address 4Address 5
12. UNSYNC command to all addresses⇒ 100 %⇒ 50 %⇒ 25 %
13. Speed reference = 0% to address 3⇒0%50%25%
14. Speed reference = 0% to address 40 %⇒0%25%
15. Speed reference = 0 % to address 50 %0 %⇒0%
20
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
FREEZE/UNFREEZE
FREEZE/UNFREEZE can be used to get simultaneous
reading of Process Data for example output current
from several slaves. A FREEZE command will freeze
the current actual values and on request the slave will
send back the value that was present when the
FREEZE command was received. The actual values
will be updated when a new FREEZE or UNFREEZE
command is received.
8. UNFREEZE command to all adresses⇒ 2A⇒ 3A⇒ 4A
Reading as by 1, 2 and 3
See the example below where the left column holds
the current values read by the master and the three
right columns hold the actual output current of the
three slaves.
Actual slave output current
VLTVLTVLT
DP
MG.90.A2.02 – VL T is a registered Danfoss trademark
21
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ Control word / status word
DP
The bits of the “Control word” tell the VLT how to
react, while the “Status word” bit status will tell the
master the condition of the VLT.
Control word
According to PROFIDRIVE control word (para. 512=0)According to VLT standard (para. 512=1)
BitBit = 0Bit = 1Bit = 0Bit = 1
00 (LSB)OFF 1ON 1Preset reference
01OFF 2ON 2
02OFF 3ON 3DC brakeRamp
03Motor coastingEnableCoastingEnable
04Quick-stopRampQuick-stopRamp
05Freeze output frequency Ramp enableFreeze outputRamp enable
06Ramp stopStartRamp stopStart
07No functionResetNo functionReset
08Jog 1 OFFONNo functionJog
09Jog 2 OFFON
10Data not validValidData not validValid
11No functionSlow downNo function
12No functionCatch-upNo function
13Setup selectSetup select
14
15 (MSB) No functionReversingNo functionReversing
Control word
The control words are used to send control
commands to the frequency converter when the
telegram is sent from the master.
The FC motor Series Design Guide (MG.03.BX.02) and the VLT 2800 Series Design Guide (MG.28.EX.02) holds a
detailed description of the control word.
Status word
When the frequency converter returns the frame to
the master, the same two bytes operate as status
from the frequency converter with the following
functions:
Status word
According to PROFIDRIVE control word (para. 512=0)According to VLT standard (para. 512=1)
BitBit = 0Bit = 1Bit = 0Bit = 1
00 (LSB)Control not readyReady
01VLT not readyReadyVLT not readyReady
02Motor coastingEnableCoastingEnable
03No faultTripNo faultTri p
04ON 2OFF 2R e s e r v e d
05ON 3OFF 3R e s e r v e d
06Start enableStart disableR e s e r v e d
07No warningWarningNo warningWarning
08Speed ≠ ref.Speed = ref.Speed ≠ ref.Speed = ref.
09
10Out of rangeFrequency OKOut of rangeFrequency OK
11Not runningRunningNot runningRunning
12
13Voltage OKLimitVoltage OKAbove limit
14Torque OKLimitCurrent OKAbove limit
15 (MSB) No thermal warningThermal warningNo thermal warningThermal warning
The FC motor Series Design Guide (MG.03.BX.02) and the VLT 2800 Series Design Guide (MG.28.EX.02 ) holds a
detailed description of the status word.
22
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ Example
This example shows how PPO type 1 is used for
changing the ramp-up time (parameter 207) to
10 seconds and for commanding a start and speed
reference of 50%.
PPO. Parameter-Process Data Object
PCD:Process Data
PCV:Parameter-Characteristics-Value
PCA:Parameter-Characteristics (Bytes 1, 2)
PCA handling below
IND:Subindex (Byte 3), (Byte 4 is not used)
PVA:Parameter value (Bytes 5 to 8)
CTW:Control word
STW:Status word
The functions available appear from the table, page
17.
When a parameter is to be changed, choose value 2
or 3, in this example 3 is chosen, because parameter
207 covers a long word (32 bits).
SPM bit:
The function is explained on page 19, in the example
the function Spontaneous Messages is not applied
(parameter 917 = OFF), therefore SPM is set for 0.
PNU = Parameter number:
Parameter number is set for: 207 = CF Hex.
This means that the value of the PCA part is 30CF
Hex.
IND (bytes 3-4):
Used when reading/changing parameters with
subindex, for example parameter 915. In the example
bytes 3 and 4 are set for 00 Hex.
PVA (bytes 5-8):
The data value of parameter 207 must be changed to
10.00 seconds. The value transmitted must be 1000,
because the conversion index for parameter 207 is
-2, this means that the value received by VLT is
divided by 100, making VLT perceive 1000 as 10.00.
Bytes 5-8 = 1000 = 03E8 Hex.
MG.90.A2.02 – VL T is a registered Danfoss trademark
23
PCDPCD
PCD
PCDPCD
DP
CTW according to Profidrive profile:
Control words consisting of 16 bits, the meaning of
the various bits appears from the table, page 22.
The following bit pattern sets all necessary start
commands: 0000 0100 0111 1111 = 047F Hex.*
0000 0100 0111 1110 = 047E Hex.*
0000 0100 0111 1111 = 047F Hex.
Quickstop:0000 0100 0110 1111 = 046F Hex.
Stop:0000 0100 0011 1111 = 043F Hex.
* Only necessary at power up.
MRV:
Speed reference, the data format is "Standardized
value", see page 19. 0 Hex = 0% and 4000 Hex =
100%.
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
-A positive response of the above example may
look like this:
The PCD part responds according to the state and
parametration of the VLT.
The PCV part responds as:
PCA: As the request telegram, but here the RC part is
taken from the response table on page 16. In this
example RC is 2Hex, which is a confirmation that a
parameter value of the type long word (32 bit) has
been transferred.
IND is not used in this example.
PVA: 03E8Hex in the PVA part tells that the value of
the parameter in question (207) is 1000 which
corresponds to 10.00.
STW: 0F07 Hex means that the motor is running and
there are no warnings or faults (for details see Status
word table on page 22).
MAV: 2000 Hex tells that the output frequency is 50%
of max. frequency.
The PCV part is a “hand shake” procedure which
means that the VLT has to acknowledge the
command, before a new one can be written.
24
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
-A negative response may look like this:
ByteValue
PCA170
PCA200
IND300
PCV
PCD
RC is 7 Hex which means that the request has been
rejected, and the fault number can be found in the
PVA part. In this case the fault number is 2 which
means that the upper or lower limit of the parameter
is exceeded. See fault number table on page 17.
Auto_Baud_supp = 1;
Set_Slave_add_supp = 1;
Usr_Prm_Data_Len = 0;
Min_Slave_Intervall = 06;
Modular_Station = 1;
Max_Module = 2;
Max_Input_Len = 28;
Max_Output_Len = 28;
Max_Data_Len = 56;
Max_Diag_Data_Len = 6;
Module = "PPO Typ 1 Module consistent PCD" 0xF3,
0xF1;
EndModule;
Module = "PPO Typ 1 Word consistent PCD " 0xF3,
0x71;
EndModule;
Module = "PPO Typ 2 Module consistent PCD" 0xF3,
0xF5;
EndModule;
Module = "PPO Typ 2 Word consistent PCD " 0xF3,
0x75;
EndModule;
Module = "PPO Typ 3 Module consistent PCD" 0xF1;
EndModule;
Module = "PPO Typ 3 Word consistent PCD " 0x71;
EndModule;
Module = "PPO Typ 4 Module consistent PCD" 0xF5;
EndModule;
Module = "PPO Typ 4 Word consistent PCD " 0x75;
EndModule;
Module = "PPO Typ 5 Module consistent PCD" 0xF3,
0xF9;
EndModule;
Module = "PPO Typ 5 Word consistent PCD " 0xF3,
0x79;
EndModule;
The VLT can also accept word concistency in
the PCD modules, whereas the PCV portion
must be module consistent.
28
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
MG.90.A2.02 – VL T is a registered Danfoss trademark
29
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ FC motor and VLT 2800 parameters
Only the PROFIBUS specific parameters (800 - 805
and 904 . . ) are described in this manual. All other
parameters and their functions are unaffected by the
PROFIBUS option. We refer to the parameter
Parameters
description in the design guide on the FC motor
Series (MG.03.Bx.02) and the design guide on the
VLT 2800 Series (MG.28.Ex.02).
Special attention must be given to the following
parameters that are not described in this manual:
-502 - 508: Selection of how to gate PROFIBUS
control commands with control
commands on the digital inputs of the
FC motor / VLT2800.
-512:Control word profile, selects a control
word according to PROFIDRIVE or a
Danfoss specified control word.
-515 - 543:Data readout parameters that can be
used to read various actual data from
the VLT, as for example actual status
on the analog and digital inputs of the
FC motor / VLT 2800 thus using these
as inputs to the master.
■ PROFIBUS specific parameters
800 Protocol select (PROTOCOL SELECT)
✭ DP[1]
804 Bus time out function (TIME OUT FUNCT.)
Selection:
✭ Off (OFF)[0]
Freeze output frequency (FREEZE OUTPUT)[1]
Stop with auto restart (STOP)[2]
Output frequency = JOG freq. (JOGGING)[3]
Output freq. = Max. freq. (MAX SPEED)[4]
Stop with trip (STOP AND TRIP)[5]
Select Setup 2[8]
Function:
The time out counter is triggered at the first reception
of a valid control word i.e. bit 10 = ok, when DP is
used.
The time out function can be activated in two different
ways:
1. CTW is not updated within the time specified in
parameter 803.
2. Time out is triggered if the CTW is not valid, see
parameter 805.
The FC motor / VLT 2800 remains in time out state
until one of the following conditions is true:
1. Valid control word (Bit 10 = ok) is received. If Stopwith trip is selected, reset must also be activated.
If Select setup 2 is selected, the FC motor / VLT
2800 will remain in Setup 2 until parameter 4 is
changed.
2. Parameter 804 = Off ⇒ control via PROFIBUS is
resumed and the most recent control word is
used.
Function:
Selection of the PROFIBUS protocol supported by the
master.
Description of selections:
-DP: Communication according to DIN 19245 part
3.
Updating parameter 800, even with an
unchanged data value, will initialise the
PROFIBUS option, meaning that all
communication parameters such as slave addresses,
PPO type etc. will be updated.
803 Bus time out (BUS TIME OUT)
Selection:
✭ 1 - 99sec1 sec
✭ Factory setting
Description of selections:
-Freeze output frequency: Freeze output frequency
until communication is resumed.
-Stop with auto restart: Stop with auto restart
when communication is resumed.
-Output frequency = JOG freq.: Motor will run at
JOG frequency until communication is
resumed.
-Output frequency = Max. freq.: Motor will run at
max. frequency until communication is resumed.
-Stop with trip: Motor is stopped, reset needed for
restart, see explanation above.
-Select setup 2.
30
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
805 Function of control word bit 10
(Bit 10 function)
Selection:
No function (NO FUNCTION)[0]
✭ Bit 10 = 1 ⇒ CTW active
(BIT 10 = 1 ⇒ CTW ACTIVE)[1]
Bit 10 = 0 ⇒ CTW active
(BIT 10 = 0 ⇒ CTW ACTIVE)[2]
Bit 10 = 0 ⇒ time out
(BIT 10 = 0 ⇒ TIME OUT)[3]
Function:
According to the PROFIDRIVE profile, control word
and speed reference will be ignored if bit 10 of the
control word is 0, but parameter 805 lets the user
change the function of bit 10. This is some times
necessary as some masters are setting all bits to 0 in
various fault situations. In these cases it makes sense
to change the function of bit 10 so that the FC motor/
VLT 2800 is commanded to stop (coast) when all bits
are 0.
Description of selections:
-Bit 10 = 1 ⇒ CTW active: Control word and speed
reference is ignored if bit 10 = 0.
-Bit 10 = 0
reference is ignored if bit 10 = 1. If all bits of the
control word are 0 the FC motor / VLT 2800
reaction will be coasting.
-Bit 10 = 0
selected in parameter 804 is activated when bit 10
is 0.
-No function: Bit 10 is ignored, i.e. control word
and speed reference is always valid.
⇒
CTW active: Control word and speed
⇒
time out: The time out function
904 PPO type select for DP (PPO TYPE SELECT)
Parameters
Selections:
✭ PPO type 1 (PPO TYPE 1)[900]
PPO type 2 (PPO TYPE 2)[901]
PPO type 3 (PPO TYPE 3)[902]
PPO type 4 (PPO TYPE 4)[903]
PPO type 5 (PPO TYPE 5)[905]
Function:
The selection is valid for read and write, i.e. the same
PPO type must be used for read and write.
Description of selections:
-PPO type 1: 12 byte PPO with parameter channel
for read and write of parameters and 4 bytes of
process data (control/status word and reference/
actual output frequency).
-PPO type 2: 20 byte PPO as PPO type 1 with 8
additional bytes of selectable process data.
-PPO type 3: 4 byte process data (control/status
word and reference/actual output frequency).
-PPO type 4: 12 byte process data, as process
data part of PPO type 2.
-PPO type 5: 28 byte as PPO type 2 with 8
additional bytes of selectable process data.
A detailed description of the PPO types can be found
on page 23.
Change of parameter 904 is executed when
parameter 800 is updated or at next power up.
✭ Factory setting
MG.90.A2.02 – VL T is a registered Danfoss trademark
31
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
915 PCD config. write (PCD IN WR-)
Selections:
Sub index 1 (PCD1)Parameter #
Sub index 2Parameter #
Parameters
Sub index 3Parameter #
Sub index 4Parameter #
Sub index 5Parameter #
Sub index 6Parameter #
Sub index 7Parameter #
Sub index 8Parameter #
Function:
Different parameters can be assigned to PCD 1-8 of
the PPO’s (the number of PCD’s depends on the PPO
type). The values in PCD 1-8 will be written to the
selected parameters as data values.
Write access via PROFIBUS or standard RS 485.
Description of selections:
The order of the subindexes corresponds to the order
of the PCD’s in the PPO, i.e. subindex 1 ≈ PCD 1,
subindex 2 ≈ PCD 2 and so on. Each subindex can
hold the number of the FC motor / VLT 2800
parameters with write access, but it is only possible
to write 2 byte values (least significant bytes) to
parameters with 4 byte data values because 1 PCD
consists of only 2 bytes.
916 PCD config. read (PCD IN RD-)
Selections:
Sub index 1 (PCD 1)Parameter #
Sub index 2Parameter #
Sub index 3Parameter #
Sub index 4Parameter #
Sub index 5Parameter #
Sub index 6Parameter #
Sub index 7Parameter #
Sub index 8Parameter #
Function:
Different parameters can be assigned to PCD 1-8 of
the PPO’s (the number of PCD’s depends on the PPO
type). PCD 1-8 will hold the actual data value of the
selected parameters.
Description of selections:
The order of the subindexes corresponds to the order
of the PCD’s in the PPO, i.e. subindex 1 ≈ PCD 1,
subindex 2 ≈ PCD 2 and so on. Each subindex can
hold the number of any of the FC motor / VLT 2800
parameters, but it is only possible to read 2 byte
values (least significant bytes) from parameters with 4
byte data values as 1 PCD consists of only 2 bytes.
917 Activate spontaneous messages
(SPONT. MES)
Selections:
✭ Off (OFF)[0]
On (ON)[1]
Function:
The spontaneous messages function can be switched
on if it is desired to make the FC motor / VLT 2800 issue
a message when a warning or an alarm comes up.
Unread spontaneous messages will be stored
in a 16 elements FIFO buffer.
Description of selections:
-OFF: The FC motor / VLT 2800 will not issue
spontaneous messages or event notification in
case of a warning or an alarm.
-ON: The FC motor / VLT 2800 will issue a
spontaneous message when warnings or alarms
are coming up.
918 Station address (STATION ADDR)
Selections:
1-126
✭ 0
Function:
All stations connected to the same bus must have a
unique address. The station address can be set in
parameter 918.
Change parameter 918 is executed at next
power up and if parameter 800 is updated.
Write access via Profibus or standard RS 485.
✭ Factory setting
32
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
953 Warning parameter 1 (WARN. PARA)
Selections:
Read only
Function:
A 16 bit bitstring where each bit is associated with a
specific warning according to the list below.
BitBit = “1” when:
0LSBConnection with DP-master is not ok
1Not used
2FDL (Field-bus Data link Layer) is not ok
3Clear data command received
4Actual value is not updated
5Spontaneous message FIFO overflow
6PROFIBUS ASIC is not transmitting
7Initialising of PROFIBUS option is not ok
8Not used
9Not used
10Not used
11Not used
12Fatal DPR-handling error/Error code
during init.: Bit 0
13Fatal DPR-handling error/Error code
during init.: Bit 1
14Fatal DPR-handling error/Error code
during init.: Bit 2
15MSBFatal DPR-handling error/Error code
during init.: Bit 3
If errors occur during DPR-handling (bit 7 not
asserted)
Code
0OK
1 Fatal error in warning channel
2 Fatal error in spontaneous channel
3 Fatal error in channel for input of process data
4 Fatal error in channel for output of process data
5 Fatal error in parameter channel 1
6 Fatal error in parameter channel 2
7 Fatal error in parameter channel 3
15 Fatal error in DPR form SPC3
967 Control word
Selections:
16 bits binary code
See page 22.
968 Status word
Selections:
Read only
See page 22.
Parameters
Explanation of errExplanation of err
Explanation of err
Explanation of errExplanation of err
If init. went wrong (bit 7 asserted) following codes are
defined:
Code
0OK
1Init. channel not empty
2No resp. on command „Init SPC3 controller“
3No resp. on command „No action“
4No resp. on writing init.-data
5No valid resp. on writing init.-data
6No positive resp. on writing init.-data
MG.90.A2.02 – VL T is a registered Danfoss trademark
As parameter 005, described in the FCM 300 design
guide (MG.03.Bx.02) and the VLT 2800 design guide
(MG.28.Ex.02).
971 Store data values (STORE DATA VALUE)
Selections:
✭ No action(NO ACTION)[0]
Store active setup (STORE ACTIVE SETUP)[1]
Store edit setup(STORE EDIT SETUP)[2]
Store all setups(STORE ALL SETUPS)[3]
Function:
Parameter values changed via PROFIBUS is only
stored in RAM meaning that the changes are lost at
power down. This parameter is used to activate a
function that stores all parameter values in the
EEPROM thus retaining changed parameter values at
power down.
Description of selections:
No action: The store function is inactive.
Store active setup: All parameter values in the active
setup will be stored in the EEPROM. The value
returns to No action when all parameter values have
been stored.
Store edit setup: All parameter values in the setup
you are editing will be stored in the EEPROM. The
value returns to No action when all parameter values
have been stored.
Store all setups: All parameter values in both setups
will be stored in the EEPROM. The value returns to
No action when all parameter values have been
stored.
980-982 Defined parameters (DEFINED PNU'S)
Selections:
Read only
Function:
The three parameters hold a list of all the parameters
that are defined in the FC motor / VLT 2800. It is
possible to read single elements of the list by DP by
using the corresponding subindex. The subindexes
start at 1 and follow the order of the parameter
numbers.
Each parameter holds up to 116 elements (parameter
numbers).
When a 0 is returned as parameter number the list
ends.
990-992 Modified parameters
(MODIFIED PNU'S)
Selections:
Read only
Function:
The three parameters hold a list of all the FC motor /
VLT 2800 parameters that have been changed from
factory setting. It is possible to read single elements
of the list by DP by using the corresponding subindex.
The subindexes start at 1 and follow the order of the
parameter numbers. Each parameter holds up to 116
elements (parameter numbers). The number of
parameters (990, 991 and 992) in use depends on
how many parameters have been changed from
factory setting.
Read only parameters, as for example data read out
parameters, will not be registered as modified
eventhough they are changing.
When a 0 is returned as parameter number the list
ends.
✭ Factory setting
34
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
■ Warning and alarm messages
There is a clear distinction between alarms and
warnings. In the case of an alarm, the FC motor / VLT
2800 will enter a fault condition. After the cause for
the alarm has been cleared, the master will have to
acknowledge the alarm message for the FC motor /
VLT 2800 to start operating again. A warning, on the
other hand may come when a warning condition
appears, and disappear when conditions return to
normal without interfering with the process.
Warnings
Any warning within the FC motor / VLT 2800 is
represented by a single bit within a warning word. A
warning word is always an active parameter. Bit
status FALSE [0] means no warning, while bit status
TRUE [1] means warning.
Any bit change in the warning word will result in a
Spontaneous message being issued.
In addition to the warning word message the master
will also be notified through a change of bit 7 in the
Status Word.
■ Spontaneous messages
If a fault or warning condition should occur, the FC
motor / VLT 2800 will, if the proper communicative
relationship has been established, issue a
Spontaneous message to communication partners.
Instead of responding to the master’s request, the FC
motor / VLT 2800 will exchange the requested
response with the alarm or the warning message.
Warnings and alarms will trigger a Spontaneous
message. The same is true with any change to an
active parameter.
Warning and alarm messages
Alarms
Following an Alarm message the FC motor / VLT
2800 will enter Fault condition. Only after the fault has
been alleviated and the master has acknowledged the
alarm message by setting bit 7 in the Control word,
can the FC motor /VLT 2800 resume operation.
Any alarm within the FC motor / VLT 2800 is
represented by a single bit within an alarm word. An
alarm word is always an action parameter. Bit status
FALSE [0] means no fault, while bit status TRUE [1]
means fault.
Any bit change in the alarm word will result in a
Spontaneous message being issued.
MG.90.A2.02 – VL T is a registered Danfoss trademark
35
■ Abbreviations
EnglishGermanElaboration
Glossary
ACI-Acyclical Control Interval
ALI-Aplication Layer Interface
ATTR-Attribute
BRCT-Broadcast
CCI-Cyclical Control Interval
CRKRCommunication Reference
CRLKBLCommunication Reference List
CSRD-Cyclical Send and Request Data
CTTypConnection Type
CTWSTWControl Word
DA-Destination Address
DP-Distributed Periphery
EIA-Electronic Industries Association: Specifiers of the EIA Standard RS 485-A
EMCEMVElectromagnetic Compatibility
EN-Event Notification
FIFO-First In First Out
HSA-Highest Station Address
Hd-Hamming distance
HPFB-High Performance Field Bus
IND-Subindex
I/OE/AInput/Output
ISO-International Standards Organization
IR-Information Report
LSAP-Local Service Access Point
LSB-Least Significant Bit
MSB-Most Significant Bit
MAP-Manufacturing Automation Protocol
MAVHIWMain Actual Value
MMS-Manufacturing Message Specification
MRVHSWMain Reference Value
MSACMZACMaster-Slave connection for acyclical transmission
MSAC_SIMZAC_SIMaster-Slave connection for acyclical transmission with slave initiative
MSCYMSZYMaster-Slave connection for cyclical transmission
MSCY_SIMSZY_SIMaster-Slave connection for cyclical transmission with slave initiative
MULT-Multicast
ODOVObject Directory
PC-Personal Computer
PCAPKEParameter Characteristics
PCDPZDProcess Data
PCVPKWParameter-Characteristics-Value
PDU-Protocol Data Unit
PLCSPSProgrammable Logic Control
PNU-Parameter Number
PPO-Parameter-Process Data Object
PVAPWEParameter Value
RAC-Receive Acknowledged request Counter
RADR-Remote Address
RCAKRequest/Response Characteristics
RCC-Receive Confirmed request Counter
RSAP-Remote Service Access Point
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
36
MG.90.A2.02 – VL T is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
EnglishGermanElaboration
SAC-Send Acknowledged request Counter
SAP-Service Access Point
SCC-Send Confirmed request Counter
SPM-Spontaneous Notification
STWZSWStatus Word
TRT-Target Rotation Time
VDE-Association of German Electrical Technicians
VDI-Association of German Electrical Engineers
VSDFUVariable Speed Drive
Glossary
MG.90.A2.02 – VL T is a registered Danfoss trademark
37
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
PNU
#
800
803
804
Parameter list
805
904
915
916
4
917
918
967
968
970
S
971
980
981
982
990
991
992
*Automatic reset to (0).
4
) Available in all 4 setups.
S
) Only in stop mode
ParameterParameter
ParameterDefault valueRange
ParameterParameter
DesignationDesignation
Designation
DesignationDesignation
PrPr
otocol selectotocol select
Pr
otocol select1005
PrPr
otocol selectotocol select
Bus time outBus time out
Bus time out1405
Bus time outBus time out
Bus time out functionBus time out function
Bus time out function0005
Bus time out functionBus time out function
Bit 10 functionBit 10 function
Bit 10 function1005
Bit 10 functionBit 10 function
PPO type selectPPO type select
PPO type select900900-903006
PPO type selectPPO type select
PCD config. writePCD config. write
PCD config. write0006
PCD config. writePCD config. write
PCD config. rPCD config. r
PCD config. r
PCD config. rPCD config. r
Spontaneous messagesSpontaneous messages
Spontaneous messagesOFF (0)ON/OFF0035
Spontaneous messagesSpontaneous messages
Station addrStation addr
Station addr
Station addrStation addr
ContrContr
ol worol wor
Contr
ol wor
ContrContr
ol worol wor
Status worStatus wor
Status wor
Status worStatus wor
Edit setupEdit setup
Edit setup50 - 6006
Edit setupEdit setup
StorStor
e data valuese data values
Stor
e data valuesOFF (0)ON/OFF006*
StorStor
e data valuese data values
Defined parametersDefined parameters
Defined parameters006
Defined parametersDefined parameters
Modified parametersModified parameters
Modified parameters006
Modified parametersModified parameters
eadead
ead0006
eadead
essess
ess01-126006
essess
dd
d016 bits0035
dd
dd
d16 bits0035
dd
1
) See table on page 18
Size
index
Conversion
1)
index
Data
1)
type
Conversion index:
This number refers to a conversion
figure to be used when writing or
reading by means of a VLT frequency
converter.
2)
2
) See table on page 19
38
MG.90.A2.02 – VL T is a registered Danfoss trademark