Danfoss Vertical Bypass Operating guide

MAKING MODERN LIVING POSSIBLE

Instruction Manual

Vertical Bypass/Non Bypass Panel

Safety

Vertical Bypass/Non Bypass Panel

 

 

Safety

WARNING

EQUIPMENT HAZARD!

The vertical bypass/non bypass panel contains dangerous voltages when connected to mains voltage. It is strongly recommended that all electrical work conform to the National Electrical Code (NEC) and all national and local regulations. Installation, start-up and maintenance should be performed only by qualified personnel. Failure to follow the NEC or local regulations could result in death or serious injury.

Motor control equipment and electronic controls are connected to hazardous mains voltages. Extreme care should be taken to protect against shock. The user must be protected against supply voltage and the motor must be protected against overload in accordance with applicable national and local regulations. Be sure equipment is properly grounded. Wear safety glasses whenever working on electric control or rotating equipment.

WARNING

UNINTENDED START!

When the vertical bypass/non bypass panel is connected to AC input power, the motor may start at any time. The drive, panel, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness when panel and drive are connected to AC input power could result in death, serious injury, or equipment or property damage.

Warning against unintended start

When the vertical bypass/non bypass panel is connected to mains, the motor may be started by means of an external switch, a serial bus command, an input reference signal, or a cleared fault condition. Use appropriate cautions to guard against an unintended start.

WARNING

GROUNDING HAZARD!

For operator safety, it is important to ground drive, vertical bypass panel, and motor properly. Follow the grounding guidelines of local and national codes. Failure to follow grounding guidelines could result in death or serious injury.

Grounding

Correct protective grounding of the equipment must be established in accordance with national and local codes. Ground currents are higher than 3mA.

Safety Guidelines

1.Disconnect the drive and vertical bypass/non bypass panel from mains before commencing service work

2.DO NOT touch electrical parts of the vertical bypass/non bypass panel or drive when mains is connected. After mains has been disconnected, wait 15 minutes before touching any electrical components or read the label on vertical bypass/non bypass panel.

3.The user must be protected against supply voltage and the motor must be protected against overload in accordance with applicable national and local regulations.

4.While programming parameters, the motor may start without warning. Activate the [Off] key on the LCP when changing parameters.

5.The [Off] key on the LCP does not isolate the drive from mains voltage and is not to be used as a safety switch.

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Safety

Vertical Bypass/Non Bypass Panel

 

 

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Contents

Vertical Bypass/Non Bypass Panel

 

 

Contents

1 Introduction

2-1

1.1.1 Purpose of the Manual

2-1

1.1.2 Overview

2-1

1.1.3 Typical Bypass Operation

2-1

1.2 Bypass Circuits

2-1

1.2.1 Three-contactor Bypass

2-1

1.3 Bypass Options

2-2

1.3.1 Common Run/Stop with Bypass

2-2

1.3.2 Automatic Bypass

2-2

1.3.3 Run Permissive in Bypass

2-2

1.3.4 Basic Fire Mode in Bypass

2-2

1.3.5 Advanced Fire Mode in Bypass

2-2

1.3.6 Overload Protection

2-2

1.4 Bypass Platform Configurations

2-3

1.5 Switch Mode Power Supply

2-3

1.5.1 Control Transformer

2-3

1.6 Disconnects

2-3

1.6.1 Main Disconnect

2-3

1.6.2 Mode Selector Switch

2-4

1.6.3 Panel Configurations

2-5

1.6.4 Panel Voltage and Frame Ratings

2-6

1.7 Power Component Functions

2-6

1.7.1 Power Fusing

2-6

2 Pre-installation

3-1

2.1.1 Receiving Inspection

3-1

2.1.2 Pre-installation Check

3-1

2.1.3 Installation Site Check

3-1

2.2 Harsh Environments

3-2

2.2.1 Airborne Liquids

3-2

2.2.2 Airborne Solids

3-2

2.2.3 Corrosive Chemicals

3-2

3 Installation

4-1

3.1.1 Tools Required

4-1

3.1.2 Drive Fuses

4-1

3.1.3 Internal Main Panel Fuses

4-5

3.2 Mechanical Installation

4-5

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Contents

Vertical Bypass/Non Bypass Panel

 

 

3.2.1 Lifting

4-5

3.2.2 Hoist or Overhead Lift

4-5

3.2.3 Forklift

4-5

3.2.4 Shipping Weights

4-5

3.3 Cooling

4-6

3.4 Electrical Installation

4-7

3.4.1 Component Identification & Customer Connection

4-8

3.4.2 Wire and Cable Access

4-16

3.4.3 Wire Size

4-19

3.4.4 Wire Type Rating

4-21

3.4.5 Terminal Tightening Torques

4-21

3.4.6 Input Line Connection

4-25

3.4.7 Motor Wiring

4-25

3.4.8 Grounding (Earthing)

4-26

3.4.9 Control Wiring

4-26

3.4.10 Serial Communication Bus Connection

4-26

3.4.11 Drive Control Terminals

4-27

4 Start Up

5-1

4.1.1 Inspection Prior to Start Up

5-2

4.1.2 Start Up Procedure

5-2

5 Electromechanical Bypass (EMB2) Operation

6-1

5.1.1 Typical Control Connections for Common HVAC Applications

6-1

5.1.2 EMB2 Auto Bypass

6-3

5.1.3 EMB2 Common Run/Stop

6-3

5.1.4 EMB2 Run Permissive

6-4

5.1.5 EMB2 Overload

6-4

5.1.6 EMB2 Safety Interlock

6-5

5.1.7 EMB2 Fire Mode

6-5

5.1.8 EMB2 Fault Reporting

6-5

5.1.9 EMB2 Switches

6-6

6 Electronically Controlled Bypass (ECB) Operation

7-1

6.1 Electronically Controlled Bypass (ECB) Operation

7-1

6.1.1 Overview

7-1

6.1.2 ECB Control Card

7-2

6.1.3 ECB Drive or Bypass Selection

7-5

6.1.4 ECB Programming

7-7

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Contents

Vertical Bypass/Non Bypass Panel

 

 

6.1.5 ECB Hand/OFF/Auto

7-8

6.1.6 ECB Mode of Operation

7-8

6.1.7 Bypass Status Word Bit Examples

7-10

6.1.8 ECB Auto Bypass

7-10

6.1.9 ECB Run Permissive

7-11

6.1.10 ECB Overload

7-11

6.1.11 ECB Safety Interlock

7-12

6.1.12 ECB Common Run/Stop

7-12

6.1.13 ECB Advanced Fire Mode

7-13

6.1.14 ECB Fault Reporting

7-13

7 Start Up Troubleshooting

8-1

7.1.1 Option Panel Alarm and Warnings

8-1

8 Appendix

9-1

8.1.1 Dimensions

9-1

8.1.2 Mechanical Diagrams

9-2

8.1.3 Typical Wiring Diagrams

9-6

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Danfoss Vertical Bypass Operating guide

Contents

Vertical Bypass/Non Bypass Panel

 

 

Contents | Figure

Figure 1.1: Basic Non Bypass Circuit

1-2

Figure 1.2: Basic Bypass Circuit

1-3

Figure 2.1: Sample Panel Label

2-1

Figure 3.1: Proper Lifting Method

3-5

Figure 3.2: Side Cooling Clearance

3-6

Figure 3.3: Cooling Airflow

3-6

Figure 3.4: Power Connections

3-7

Figure 3.5: P2 Bypass Mechanical Layout Diagram

3-8

Figure 3.6: P2 Non Bypass Mechanical Layout Diagram.

3-9

Figure 3.7: P3 Bypass Mechanical Layout Diagram.

3-10

Figure 3.8: P3 Non Bypass Mechanical Layout Diagram.

3-11

Figure 3.9: P4 Bypass Mechanical Layout Diagram.

3-12

Figure 3.10: P4 Non Bypass Mechanical Layout Diagram.

3-13

Figure 3.11: P5 Bypass Mechanical Layout Diagram.

3-14

Figure 3.12: P5 Non Bypass Mechanical Layout Diagram.

3-15

Figure 3.13: Bypass Panel Conduit Entry Diagram

3-16

Figure 3.14: Non Bypass Panel Conduit Entry Diagram

3-16

Figure 3.15: P2 Panel

3-17

Figure 3.16: P3 Panel

3-17

Figure 3.17: P4 Panel

3-18

Figure 3.18: P5 Panel

3-19

Figure 3.19: Control Terminals Location

3-26

Figure 3.20: Removable Drive Connectors and Terminals

3-27

Figure 5.1: Customer Side EMB2 Control Card Terminal Connections

5-2

Figure 5.2: Sample Overload Device

5-5

Figure 6.1: Local Control Panel (LCP)

6-1

Figure 6.2: ECB Control Card Terminal Connections

6-3

Figure 6.3: Bypass Trip Time Delay

6-10

Figure 6.4: Drive Display with Bypass Start Time Delay Active

6-11

Figure 6.5: Sample Overload Device

6-12

Figure 8.1: P2 Bypass

8-2

Figure 8.2: P2 Non-bypass

8-3

Figure 8.3: P3 P4 P5 Bypass

8-4

Figure 8.4: P3 P4 P5 Non-bypass

8-5

Figure 8.5: EMB2 with Control Relay, Part 1

8-6

Figure 8.6: EMB2 with Control Relay, Part 2

8-7

Figure 8.7: EMB2, Part 1

8-8

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Contents

Vertical Bypass/Non Bypass Panel

 

 

Figure 8.8: EMB2, Part 2

8-9

Figure 8.9: ECB, Part 1

8-10

Figure 8.10: ECB, Part 2

8-11

Figure 8.11: ECB with Control Relays, Part 1

8-12

Figure 8.12: ECB with Control Relays, Part 2

8-13

Figure 8.13: Non-bypass

8-14

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Contents

Vertical Bypass/Non Bypass Panel

 

 

Contents | Table

Table 1.1: Contactor Operation

1-2

Table 1.2: Bypass Configurations

1-3

Table 1.3: Tier Definitions and Features

1-5

Table 1.4: Panel Voltage and Frame Ratings

1-6

Table 3.1: Tools Required

3-1

Table 3.2: Drive Fuses 208 V

3-1

Table 3.3: Drive Fuses 230 V

3-2

Table 3.4: Drive Fuses 460 V

3-3

Table 3.5: Drive Fuses 600 V

3-4

Table 3.6: Sample Fuse Rating Label

3-5

Table 3.7: Approximate Shipping Weights

3-5

Table 3.8: Reference Designator Definitions

3-8

Table 3.9: Wire Size Chart, 208 and 230 V

3-20

Table 3.10: Wire Size Chart 460 and 600 V

3-21

Table 3.11: Tightening Torques, 208 and 230 V

3-22

Table 3.12: Tightening Torques, 460 V

3-23

Table 3.13: Tightening Torques, 600 V

3-24

Table 3.14: Sample Tightening Torque and Wire Rating Label

3-25

Table 3.15: Drive Control Terminals Functions

3-27

Table 4.1: Inspection prior to Startup

4-2

Table 5.1: EMB2 Default Parameter Settings for Common HVAC Applications

5-1

Table 5.2: Common Functions for Controlling Motor using Bypass and Typical Terminal Connections.

5-1

Table 6.1: Parameter Group 5-** Factory Default Settings

6-2

Table 6.2: ECB Card Terminals

6-4

Table 6.3: LCP Control Keys Programming

6-8

Table 6.4: Bypass Parameter Functions

6-9

Table 6.5: Parameter 31-10 Bypass Status Word Bit Definitions

6-9

Table 7.1: Panel Alarms and Warnings (ECB only)

7-1

Table 7.2: Panel Status Display (ECB only)

7-1

Table 7.3: Fault Table

7-2

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Introduction

Vertical Bypass/Non Bypass Panel

 

 

1 Introduction

1.1.1 Purpose of the Manual

This manual is intended to provide detailed information for the installation and operation of the vertical panel used in conjunction with a Danfoss variable frequency drive (VFD). To enable efficient handling of the equipment, requirements are provided for installation of mechanical, electrical, control wiring, proper grounding, and environmental considerations. Pre-start and start up procedures are detailed. Also included is a detailed overview of the panel bypass function. In addition, identification of other optional components and their operation and start up troubleshooting instructions are included. For the electronically controlled bypass, additional programming and operation information is provided.

1.1.2 Overview

A variable frequency drive regulates the speed and operation of an electric motor. The drive is programmable and offers many features and savings compared to operating a motor from unregulated line voltage. The panel is a protective enclosure in which the drive and various optional components are assembled and mounted. The vertical non bypass panel is always configured with a disconnect switch and fuses to protect the drive. The vertical bypass panel allows switching between running the motor from the drive (variable speed) or across the line input power (constant speed).

The vertical bypass panel comes with one of two control options:

The electromechanical bypass (EMB2)

Electronically controlled bypass (ECB)

The EMB2 is operated by a selector switch on the front of the panel. The EMB2 controls a motor by switching between drive control, operation in bypass, or off. In addition, a test selection is available, which disengages the motor from the drive but keeps the drive operational while the motor runs in bypass. The switching function activates contactors to provide power to the motor through the drive or bypass circuitry, as required.

The ECB also uses contactors to provide power to the motor through the drive or bypass circuitry. However, the ECB contains a local processor that interacts with the drive’s control logic for programmable options, remote

1 1

inputs, and status reporting. The VFD’s logic circuitry is backed up by an independent panel-mounted power supply so that, even if the drive loses power, control and communication functions are maintained. Programming and display are provided by the LCP. An important feature of the ECB is the ability to accept commands from a building automation system (BAS) and to report operational status in return.

See more detailed descriptions of the EMB2 in 5 Electromechanical Bypass (EMB2) Operation and ECB in 6 Electronically Controlled Bypass (ECB) Operation of this manual.

1.1.3 Typical Bypass Operation

With contactors M1 and M2 closed and contactor M3 open, the motor is running in drive control. Opening contactor M2 removes power to the motor but allows the drive to remain under power. This is referred to as test mode. With contactors M1 and M2 open and contactor M3 closed, the motor is running in bypass from the line input power.

1.2 Bypass Circuits

1.2.1 Three-contactor Bypass

The bypass circuit consists of a bypass contactor (M3) interlocked with a drive output contactor (M2), a drive input contactor (M1), and an overload relay. For the EMB2, a door mounted Drive/OFF/Bypass/Test Selector switch is used to electrically select whether the motor is powered by the drive, connected to the full speed bypass, or disconnected from both. The test position applies power to the motor through the bypass (M3 closed) contactor but removes power from the drive (M2 open) while keeping the drive powered (M1 closed). A Pilot light indicates when in bypass. For the ECB, control selection is made through the drive keypad by pressing the DRIVE BYPASS key and selecting from the available options shown. Display data indicates when in bypass. The circuitry may be supplied with either an input disconnect switch or an input circuit breaker.

MG.13.A1.22 - VLT® is a registered Danfoss trademark

1-1

Introduction

Vertical Bypass/Non Bypass Panel

 

 

1

 

1

 

Contactor

Drive Mode

OFF

Bypass

Test Mode

 

 

 

 

 

Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

Closed

Open

Open

Closed

 

 

 

 

 

 

 

 

 

 

 

 

 

M2

Closed

Open

Open

Open

 

 

 

 

M3

Open

Open

Closed

Closed

Table 1.1 Contactor Operation

 

 

DRIVE

 

 

 

 

 

CUSTOMER SUPPLIED

 

 

DISCONNECT

 

 

 

 

 

AC MOTOR.

 

L1

1L1

Fuse

2L1

L1/91

VFD

U/96

T1

INPUT

L2

1L2

2L2

TYPE 1 ENCLOSURE

V/97

Fuse

L2/92

T2

POWER

L3

1L3

2L3

 

W/98

T3

Fuse

L3/93

 

 

 

 

DS1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EARTH

 

 

 

 

 

 

 

 

GROUND

 

Figure 1.1 Basic Non Bypass Circuit

<![if ! IE]>

<![endif]>130BX360.11

1.3 Bypass Options

1.3.1 Common Run/Stop with Bypass

Allows a remote signal to initiate operation in either drive control or bypass depending upon the position of the bypass selector switch.

1.3.2 Automatic Bypass

This feature automatically transfers the motor from drive to bypass without operator intervention when a fault condition trips the drive, after a programmable time-out period. The VFD’s internal fault circuitry controls this action. The time delay permits all automatically resettable faults to clear prior to transfer to bypass. Run permissive or safety circuit signals override the auto bypass function and may prevent or delay bypass operation.

1.3.3 Run Permissive in Bypass

With run permissive active, the drive sends a run request and waits for a remote response before commanding the motor to start. The response indicates the system is safe to operate.

1.3.4 Basic Fire Mode in Bypass

This option switches the panel to bypass whenever a remote fire mode signal is given to the VFD through the input terminals. In either drive or bypass, fire mode is intended to ignore common safety and overload inputs for emergency situations. The motor will continue to run in bypass until fire mode is removed or the drive, panel, or motor fails. External safety signals and motor overload are ignored when in fire mode.

1.3.5 Advanced Fire Mode in Bypass

The advanced fire mode allows for a variety of programmable responses to an external fire mode command signal. Bypass options are programmed through the drive’s fire mode parameters. See 6.1.13 ECB Advanced Fire Mode.

1.3.6 Overload Protection

This thermally activated device provides mechanical overload protection for the motor while in bypass operation. It measures motor current and is set to the full load amps (FLA) of the motor. A 1.2 x FLA service factor is built-in and maintained, meaning that should the motor current increase above that value, the overload will calculate the level of increase to activate timing for the trip function. The higher the current draw, the quicker the trip response. The overload provides Class 20 motor protection.

1-2

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Introduction

Vertical Bypass/Non Bypass Panel

 

 

1.4 Bypass Platform Configurations

The two bypass platform configurations are ECB and EMB2. The features available as options with each platform are listed in Table 1.2. The ECB, also listed below, has all option features available. See 5 Electromechanical Bypass (EMB2) Operation for additional details on the EMB2 and

6 Electronically Controlled Bypass (ECB) Operation for the ECB.

Control Features

EMB2

ECB

 

1

 

1

 

 

 

 

 

Safety Interlock

X

X

 

 

 

 

 

 

 

 

 

 

 

Common Start / Stop

X

X

 

 

 

 

 

 

 

 

 

 

 

Automatic Bypass

X

X

 

 

 

 

Run Permissive

X

X

 

 

 

 

Basic Fire Mode

X

X

 

 

 

 

Advanced Fire Mode

 

X

 

 

 

 

Serial Communication

 

X

 

 

 

 

Table 1.2 Bypass Configurations

MAIN DISCONNECT

 

 

 

 

EARTH

 

 

 

 

GROUND

 

L1

 

1L1

M1

 

 

 

INPUT

Fuse

2L1

Fuse

3L1

L1/91

L2

1L2

2L2

3L2

POWER

L3

Fuse

1L3

2L3

Fuse

3L3

L2/92

Fuse

Fuse

L3/93

 

 

DS1

 

 

 

 

 

VFD

Type 1 Enclosure

 

 

 

CUSTOMER

 

M2

OL1

SUPPLIED

 

AC MOTOR

U/96

2T1

1T1

 

2T2

1T2

T1

V/97

2T3

1T3

T2

W/98

T3

 

 

 

EARTH

M3

 

 

GROUND

 

 

<![if ! IE]>

<![endif]>130BX361.11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>Fuse

<![if ! IE]>

<![endif]>600V

<![if ! IE]>

<![endif]>Fuse

<![if ! IE]>

<![endif]>600V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MK903

MK902

MK904

CONTROL

TRANSFORMER

 

 

 

 

24 V DC SMPS

 

 

MK901

 

 

 

 

1

2

3

4

 

5 -

6

7

+ 8

 

Figure 1.2 Basic Bypass Circuit

1.5 Switch Mode Power Supply

The VFD’s logic circuitry is backed up by an independent panel-mounted switch mode power supply so if the drive loses power, control and communication functions are maintained. The SMPS converts three-phase AC input power to 24 V DC control power. Since the SMPS draws power from all three phases, it offers immunity protection from most phase-loss and brown-out conditions. The SMPS is internally protected from short circuit on its output and three board-mounted fuses provide additional protection. The SMPS is not designed for external use and may take up to 5 sec. to initialize at power-up. The SMPS will maintain a 24 V DC output with a low input line voltage. The 200 Volt SMPS will maintain the 24 V DC output with a line voltage as low as 150 V AC and the 600 V SMPS to 335 V AC. Refer to Figure 1.2.

1.5.1 Control Transformer

A control transformer is included on larger horsepower units where the contactor coils are AC. The control transformer steps down the line input voltage to 120V AC. The coils of AC contactors are isolated from the Switch Mode Power Supply via relays.

1.6 Disconnects

1.6.1 Main Disconnect

The main disconnect removes line input power to the drive and bypass. A main disconnect is available in four options.

Fused disconnect. Two-position (ON/OFF) rotary switch, padlock compatible, with three fuses, one on each phase, built into the switch. For safety, the switch must be in the OFF position before

MG.13.A1.22 - VLT® is a registered Danfoss trademark

1-3

Introduction

Vertical Bypass/Non Bypass Panel

 

 

1 1

the option panel door can be opened. (Bypass panel only.)

Disconnect without fuses. For user-supplied fuses option. (Bypass panel only.)

Main circuit breaker. A thermal/ magnetic current interrupt device using an ON/TRIP/OFF/RESET switch. When in the ON position, a trip fault removes power from the drive/bypass circuit and the switch moves to the TRIP setting. The switch must be moved to the RESET position momentarily after the fault has been cleared to reset the circuit breaker. (Bypass panel only.)

Main Disconnect with drive fuses. Non-bypass panel two-position (ON/OFF) rotary switch that disconnects the main AC line power to the drive only.

1.6.2 Mode Selector Switch

The mode selector switch is used for 3-contactor bypass on EMB2 units. The selector switch allows the operator to select from four modes of operation.

Drive mode: When drive mode is selected, the M1 and M2 contactors are closed allowing power to flow in and out of the drive to the motor.

Off mode: This mode opens all contactors removing any power to the motor.

Bypass mode:When bypass mode is selected, the M3 contactor closes and allows the motor to run directly from the input line power.

Test mode:Test mode closes the M1 and M3 contactors and allows the motor to be powered by the input line power. This also allows the drive to power up without being connected to the motor. Refer to Figure 1.2.

1-4

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Introduction Vertical Bypass/Non Bypass Panel

1.6.3 Panel Configurations

 

 

1

1

The VLT FC Drive Series comes in two panel enclosure types. One is the non bypass and the other is the bypass. See

 

 

Table 1.3 for descriptions and available options.

 

 

 

 

Non bypass

 

Bypass

 

 

<![if ! IE]>

<![endif]>130BX363.10

<![if ! IE]>

<![endif]>130BX365.10

<![if ! IE]>

<![endif]>130BX362.10

<![if ! IE]>

<![endif]>130BX364.10

 

Drive plus both of the following:

Drive with bypass:

1.

Fuses

1. Fuses

2.

Disconnect

2.

Disconnect/Circuit Breaker

 

 

3.

Contactors

 

 

4.

Power Supply

 

 

5.

Control Module

Table 1.3 Tier Definitions and Features

MG.13.A1.22 - VLT® is a registered Danfoss trademark

1-5

Introduction Vertical Bypass/Non Bypass Panel

1

 

1

 

1.6.4 Panel Voltage and Frame Ratings

 

 

 

 

 

 

Table 1.4Table 1.5 defines the voltage and hp ratings of the frames sizes for the panel. See 8 Appendix for overall and

 

 

 

 

 

 

 

 

mounting dimensions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel P2

 

Bypass

 

 

Non Bypass

 

 

 

 

(B3 - Drive)

FC102/202/322

FC102/202/322

 

FC302

 

 

 

 

Volts VAC

 

 

 

HP (KW)

 

 

 

 

 

 

208

& 230

7.5

(5.5) - 15 (11)

7.5

(5.5) - 15 (11)

 

7.5 (5.5) - 10 (7.5)

 

 

 

 

460

& 600

15 (11) - 25 (18.5)

15 (11) -25 (18.5)

 

15 (11) - 20 (15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel P3

 

Bypass

 

 

Non Bypass

 

 

 

 

(B4 - Drive)

 

 

 

 

 

 

 

 

FC102/202/322

FC102/202/322

 

FC302

 

 

 

 

Volts VAC

 

 

 

HP (KW)

 

 

 

 

 

 

208

 

20(15)

20 (15) - 25 (18.5)

 

15 (11) - 20 (15)

 

 

 

 

230

20 (15) - 25 (18.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

460

& 600

30

(22) - 50 (37)

30

(22) - 50 (37)

 

25 (18.5) - 40 (30)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel P4

 

Bypass

 

 

Non Bypass

 

 

 

 

(C3 - Drive)

 

 

 

 

 

 

 

 

FC102/202/322

FC102/202/322

 

FC302

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Volts VAC

 

 

 

HP (KW)

 

 

 

 

 

 

208

25 (18.5) - 40 (30)

30

(22) - 40 (30)

 

25 (18.5) - 30 (22)

 

 

 

 

230

30

(22) - 40 (30)

 

 

 

 

 

 

 

 

 

 

 

 

 

460

& 600

60

(45) - 75 (55)

60

(45) - 75 (55)

 

50 (37) - 60 (45)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel P5)

 

Bypass

 

 

Non Bypass

 

 

 

 

(C4 - Drive)

 

 

 

 

 

 

 

 

FC102/202/322

FC102/202/322

 

FC302

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Volts VAC

 

 

 

HP (KW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208

& 230

50

(37) - 60 (45)

50

(37) - 60 (45)

 

40 (30) - 50 (37)

 

 

 

 

460

& 600

100

(75) - 125 (90)

100

(75) - 125 (90)

 

75 (55) - 100 (75)

Table 1.4 Panel Voltage and Frame Ratings

1.7 Power Component Functions

1.7.1 Power Fusing

For main panel power fuses, only use the specified fuse or an equivalent replacement. For drive fuses only use the specified fuse. See the fuse ratings label on the inside cover of the unit or Table 3.2Table 3.3, Table 3.3Table 3.4, Table 3.4Table 3.5 and Table 3.5Table 3.6.

Main fusing

Main fuses are located ahead of the drive and bypass. Main fuses are designed to protect the circuitry within the bypass panel but is not adequate to protect the drive. Main fuses are dual-element, time-delay types and mount inside the bypass enclosure.

Drive fusing

Drive fuses are located ahead of the drive and are a fastacting type. Drive fuses are standard in all bypass and nonbypass panels.

5,000 or 100,000 amp SCCR

The bypass panel supplied with a non fusible Main Disconnect Switch is 5,000 amps short-circuit current rating (SCCR). The bypass panel supplied with a Fusible disconnect or circuit breaker is 100,000 amp SCCR. The non bypass panel supplied with a non-fusible Main Disconnect is 100,000 amp SCCR. See the panel label for SCCR rating.

NOTE!

The 600 V circuit breaker option is 5,000 amp (SCCR).

1-6

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Pre-installation

Vertical Bypass/Non Bypass Panel

 

 

2 Pre-installation

2.1.1 Receiving Inspection

Inspect the packaging and equipment closely when received. Any indication of careless handling by the carrier should be noted on the delivery receipt, especially if the equipment will not be immediately uncrated. Obtain the delivery person’s signed agreement to any noted damages for any future insurance claims. Ensure that the model number and power match the order and intended use for the drive.

IMPORTANT!

LOST OR DAMAGED GOODS

INSPECT THIS SHIPMENT IMMEDIATELY UPON ARRIVAL

If goods are received short or in damaged condition, insist on a notation of the loss or damage across the face of the freight bill. Otherwise no claim can be enforced against the transportation company. If concealed loss or damage is discovered, notify your carrier at once and request an inspection. This is absolutely necessary. Unless you do this the carrier will not entertain any claim for loss or damage. The agent will make an inspection and can grant a concealed damage notation. If you give the transportation company a clear receipt for equipment that has been damaged or lost in transit, you do so at your own risk and expense.

Danfoss is willing to assist you to collect claims for loss or damage, but willingness on our part does not make us responsible for collection of claims or replacement of material. The actual filing and processing of the claim is your responsibility.

<![if ! IE]>

<![endif]>130BX366.10

Figure 2.1 Sample Panel Label

Ensure that the model number and power match the order and intended use for the drive.

2.1.2 Pre-installation Check

2

2

 

 

1.Compare panel model number to what was ordered.

2.Ensure each of the following are rated for the same voltage:

Drive

Panel

Power line

Motor

3.Ensure that the panel output rating is equal to or greater than motor total full load current for full motor performance.

Motor power size and panel must match for proper overload protection.

If panel rating is less than motor; full motor output cannot be achieved.

4.Check motor wiring:

Any disconnect between drive and motor should be interlocked to drive safety interlock circuit to avoid unwanted drive trips.

Do not connect power factor correction capacitors between the drive and motor.

Two speed motors must be wired permanently for full speed.

Y-start, -run motors must be wired

 

permanently for run.

2.1.3 Installation Site Check

Because the panel relies on the ambient air for cooling, it is important to observe the limitations on ambient air temperature. Derating concerns start above 104°F (40°C) and 3300 feet (1000m) elevation above sea level.

It is important with multiple panels to check wall strength. Make sure that the proper mounting screws or bolts are used.

Ensure that the wall or floor area for installation will support the weight of the unit.

If construction work continues after the equipment is mounted, it is important to keep the interior free from concrete dust and similar

MG.13.A1.22 - VLT® is a registered Danfoss trademark

2-1

 

 

Pre-installation

Vertical Bypass/Non Bypass Panel

 

 

 

 

 

dirt. If the unit does not have power applied to it,

 

 

supply a protective covering. It is important to

 

 

ensure that the components stay as clean as

2

2

possible. It may be necessary to clean the interior

once construction is completed.

 

 

 

 

Keep drawings and manuals accessible for detailed installation and operation instructions. It is important that the manuals be available for equipment operators.

2.2Harsh Environments

The mechanical and electrical components within the panel can be adversely affected by the environment. The effects of contaminants in the air, either solid, liquid, or gas, are difficult to quantify and control.

2.2.1 Airborne Liquids

Liquids in the air can condense in components. Water carried in the air is easily measured as relative humidity, but other vapors are often more difficult to measure or control. Steam, oil and salt water vapor may cause corrosion of components. In such environments, use TYPE 12 enclosures to limit the exchange of outside air into the option enclosure. Extremely harsh environments may require a higher level of protection.

2.2.2 Airborne Solids

Particles in the air may cause mechanical, electrical or thermal failure in components. A TYPE 1 enclosure provides a reasonable degree of protection against falling particles, but it will not prevent the fan from pulling dirty air into the enclosure.

2.2.3 Corrosive Chemicals

In environments with high temperatures and humidity, corrosive gases such as sulfur, nitrogen and chlorine compounds cause corrosion to occur in components. Indications of corrosion are blackened copper or rust on steel or oxidized aluminum. In such environments, it is recommended that the equipment be mounted in a cabinet with fresh air ventilation and that corrosive compounds be kept away. A non-ventilated cabinet fitted with an air conditioner as a heat exchanger may be used. Conformal coated circuit boards may be specified to reduce the corrosive effects of a harsh environment.

2-2

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Installation

Vertical Bypass/Non Bypass Panel

 

 

3 Installation

3.1.1 Tools Required

In addition to the standard tool kit, the tools in Table 3.1 are recommended for installation of the panel.

3.1.2 Drive Fuses

TOOLS

 

 

 

 

Spreader bar capable of lifting up to 750 lbs.

 

 

 

 

Max diameter 0.5 in.

 

 

 

 

 

3

 

3

Forklift, crane, hoist or other lifting device capable of handling

 

 

 

 

 

 

up to 750 lbs. (Qualified device operator available for operating

 

 

 

 

the equipment.)

 

 

 

 

 

 

 

 

Metric Socket Set: 7 - 19mm

 

 

 

 

 

 

 

 

 

Socket Extensions: 4, 6, and 12 inch

 

 

 

 

 

 

 

 

 

Torx driver set: T10 - T40

 

 

 

 

 

 

 

 

 

Torque wrench: 6 - 375 lbs-in

 

 

 

 

 

 

 

 

 

Allen Wrenches:1/8, 3/16, 1/4, & 5/16 inches

 

 

 

 

 

 

 

 

 

Metric or English wrenches: 7 - 19mm

 

 

 

 

 

 

 

 

 

Table 3.1 Tools Required

 

 

 

 

To maintain UL, the drive fuses should be replaced only with the fuses specified in , , , and . If an alternate drive fuse is desired please consult the factory. See the specifications label inside the cover of the unit for acceptable replacement drive fuses. A sample of this data can be seen in Table 3.6

208 V AC

 

 

Panel

Main Fuse

Drive Fuse

Transformer Fuse

Panel

Drive Fuse

 

UL Motor

(FC102/202/322)

(FC302)

HP (KW)

(FC102/202/322)

(FC102/202/322)

(FC102/202/322)

(FC302) Danfoss

Current

Non Bypass &

Non

 

Danfoss (Bussman)

Danfoss (Bussman)

Danfoss (Bussman)

(Bussman)

 

 

Bypass

Bypass

 

 

 

 

 

 

7.5 (5.5)

24.2

 

34035600 (LPJ-40-

176F8953 (JJN-50)

 

 

176F8953

 

SP)

 

 

(JJN-50)

 

 

 

 

 

P2

10 (7.5)

30.8

P2

34035700 (LPJ-50-

176F8953 (JJN-50)

 

176F8955

 

 

SP)

 

 

(JJN-60)

 

 

 

 

 

 

15 (11)

46.2

 

34042800 (LPJ-70-

176F8955 (JJN-60)

 

 

176F8957

 

SP)

 

 

(JJN-80)

 

 

 

 

 

P3

20 (15)

59.4

P3

34042900 (LPJ-90-

176F8957 (JJN-80)

 

176F8960

 

 

SP)

 

 

(JJN-125)

 

 

 

 

 

 

25 (18.5)

74.8

P3 - Non Bypass P4

34043100 (LPJ-125-

176F8960 (JJN-125)

 

 

176F8960

 

 

- Bypass

SP)

 

 

P4

(JJN-125)

30 (22)

88

 

34043200 (LPJ-150-

176F8960 (JJN-125)

 

174N6538

 

 

 

 

 

P4

SP)

 

 

 

(JJN-150)

40 (30)

114

34043300 (LPJ-175-

174N6538 (JJN-150)

 

 

174N6839

 

 

 

 

 

 

SP)

 

 

P5

(JJN-200)

50 (37)

143

 

34042300 (LPJ-250-

174N6839 (JJN-200)

34046200 (FNQ-

174N6840

 

 

 

 

 

SP)

 

R-1.25)

 

(JJN-250)

 

 

P5

34042300 (LPJ-250-

 

34046200 (FNQ-

 

 

60 (45)

169

 

174N6840 (JJN-250)

 

 

 

 

 

SP)

 

R-1.25)

 

 

 

 

 

 

 

 

 

 

Table 3.2 Drive Fuses 208 V

MG.13.A1.22 - VLT® is a registered Danfoss trademark

3-1

 

 

 

 

Installation

 

 

 

Vertical Bypass/Non Bypass Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230 V AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel

Main Fuse

Drive Fuse

Transformer Fuse

Panel

Drive Fuse

 

 

 

 

 

UL Motor

(FC102/202/322)

(FC302)

 

 

 

 

HP (KW)

(FC102/202/322)

(FC102/202/322)

(FC102/202/322)

(FC302) Danfoss

 

 

 

 

Current

Non Bypass &

Non

 

 

 

 

 

Danfoss (Bussman)

Danfoss (Bussman)

Danfoss (Bussman)

(Bussman)

 

 

 

 

 

 

Bypass

Bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5 (5.5)

22

 

 

34042600 (LPJ-35-

176F8953 (JJN-50)

 

 

176F8953

3

 

3

 

 

 

SP)

 

P2

(JJN-50)

 

 

 

 

 

 

 

 

 

 

10 (7.5)

28

P2

34042700 LPJ-45-

176F8953 (JJN-50)

 

176F8955

 

 

 

 

 

 

SP

 

 

(JJN-60)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 (11)

42

 

 

34042800 (LPJ-70-

176F8955 (JJN-60)

 

 

176F8957 JJN-80

 

 

 

 

 

 

SP)

 

 

 

 

 

 

 

 

 

 

 

 

P3

 

 

 

 

 

20 (15)

54

 

 

34042900 (LPJ-90-

176F8957 (JJN-80)

 

176F8960

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP)

 

 

(JJN-125)

 

 

 

 

 

 

P3

 

 

 

 

 

 

 

25 (18.5)

68

34043000 (LPJ-100-

176F8960 (JJN-125)

 

 

176F8960

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP)

 

 

P4

(JJN-125)

 

 

 

 

30 (22)

80

 

 

34043100 (LPJ-125-

176F8960 (JJN-125)

 

174N6538

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P4

SP)

 

 

 

(JJN-150)

 

 

 

 

40 (30)

104

34043200 (LPJ-150-

174N6538

 

 

174N6839

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP)

(JJN-150)

 

 

(JJN-200)

 

 

 

 

 

 

 

 

 

P5

 

 

 

 

50 (37)

130

 

 

34043400 (LPJ-200-

174N6839

34046200 (FNQ-

174N6840

 

 

 

 

 

 

 

 

 

 

 

 

 

SP)

(JJN-200)

R-1.25)

 

(JJN-250)

 

 

 

 

 

 

P5

 

 

 

 

 

60 (45)

154

34042300 (LPJ-250-

174N6840

34046200 (FNQ-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP)

(JJN-250)

R-1.25)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3.3 Drive Fuses 230 V

3-2

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Installation

 

 

Vertical Bypass/Non Bypass Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460 V AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel

 

 

Transformer

 

 

 

 

 

 

 

 

 

Main Fuse

Drive Fuse

Fuse

Panel

Drive Fuse

 

 

 

 

 

 

UL Motor

(FC102/202/322)

 

 

 

 

 

HP (KW)

(FC102/202/322)

(FC102/202/322)

(FC102/202/322

(FC302) Non

(FC302) Danfoss

 

 

 

 

 

Current

Non Bypass &

 

 

 

 

 

 

Danfoss (Bussman)

Danfoss (Bussman)

) Danfoss

Bypass

(Bussman)

 

 

 

 

 

 

 

Bypass

 

 

 

 

 

 

 

 

 

(Bussman)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 (11)

21

 

34042600 (LPJ-35-

176F8952 (JJS-40)

 

P2

176F8952

 

 

3

 

3

 

SP)

 

(JJS-40)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 (15)

27

P2

34035600 (LPJ-40-

176F8952 (JJS-40)

 

 

176F8954

 

 

 

 

 

SP)

 

 

(JJS-50)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 (18.5)

34

 

34035700 (LPJ-50-

176F8954 (JJS-50)

 

 

176F8956

 

 

 

 

 

 

SP)

 

 

(JJS-60)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30 (22)

40

 

34035800 (LPJ-60-

176F8956 (JJS-60)

 

P3

176F8958

 

 

 

 

 

 

SP)

 

(JJS-80)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40 (30)

52

P3

176U5037 (LPJ-80-

176F8958 (JJS-80)

 

 

176F8959

 

 

 

 

 

SP)

 

 

(JJS-100)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 (37)

65

 

34043000 (LPJ-100-

176F8959 (JJS-100)

 

 

176F8961

 

 

 

 

 

 

SP)

 

 

(JJS-125)

 

 

 

 

 

 

 

 

 

 

P4

 

 

 

 

 

60 (45)

77

 

34043100 (LPJ-125-

176F8961 (JJS-125)

 

176F9078

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP)

 

 

(JJS-150)

 

 

 

 

 

 

 

P4

 

 

 

 

 

 

 

 

75 (55)

96

34043200 (LPJ-150-

176F9078 (JJS-150)

 

 

34051200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP)

 

 

(JJS-200)

 

 

 

 

 

 

 

 

 

 

P5

 

 

 

 

 

100 (75)

124

 

34043400 (LPJ-200-

34051200 (JJS-200)

34046000 (FNQ-

00002051

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P5

SP)

 

R-0.60)

 

(JJS-250)

 

 

 

 

 

125 (90)

156

34042300 (LPJ-250-

00002051 (JJS-250)

34046000 (FNQ-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP)

 

R-0.60)

 

 

 

 

 

 

 

Table 3.4 Drive Fuses 460 V

MG.13.A1.22 - VLT® is a registered Danfoss trademark

3-3

 

 

 

 

Installation

 

 

Vertical Bypass/Non Bypass Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600 V AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel

 

 

Transformer

 

 

 

 

 

 

 

 

Main Fuse

Drive Fuse

Fuse

Panel

Drive Fuse

 

 

 

 

 

UL Motor

(FC102/202/322)

 

 

 

 

HP (KW)

(FC102/202/322)

(FC102/202/322)

(FC102/202/322)

(FC302) Non

(FC302) Danfoss

 

 

 

 

Current

Non Bypass &

 

 

 

 

 

Danfoss (Bussman)

Danfoss (Bussman)

Danfoss

Bypass

(Bussman)

 

 

 

 

 

 

Bypass

 

 

 

 

 

 

 

 

(Bussman)

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

3

 

15 (11)

17

 

34035500 (LPJ-30-

176F9076 (JJS-35)

 

P2

176F9076

 

 

 

SP)

 

(JJS-35)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 (15)

22

P2

34042600 (LPJ-35-

176F9076 (JJS-35)

 

 

176F9077

 

 

 

 

SP)

 

 

(JJS-45)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 (18.5)

27

 

34042700 (LPJ-45-

176F9077 (JJS-45)

 

 

176F8954

 

 

 

 

 

SP)

 

 

(JJS-50)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30 (22)

32

 

34035700 (LPJ-50-

176F8954 (JJS-50)

 

P3

176F8956

 

 

 

 

 

SP)

 

(JJS-60)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40 (30)

41

P3

34035800 (LPJ-60-

176F8956 (JJS-60)

 

 

176F8958

 

 

 

 

SP)

 

 

(JJS-80)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 (37)

52

 

176U5037 (LPJ-80-

176F8958 (JJS-80)

 

 

176F8959

 

 

 

 

 

SP)

 

 

(JJS-100)

 

 

 

 

 

 

 

 

 

P4

 

 

 

 

60 (45)

62

 

34043000 (LPJ-100-

176F8959 (JJS-100)

 

176F8961

 

 

 

 

 

 

 

 

 

 

 

 

SP)

 

 

(JJS-125)

 

 

 

 

 

 

P4

 

 

 

 

 

 

 

75 (55)

77

34043100 (LPJ-125-

176F8961 (JJS-125)

 

 

176F9078

 

 

 

 

 

 

 

 

 

 

 

 

SP)

 

 

(JJS-150)

 

 

 

 

 

 

 

 

 

P5

 

 

 

 

100 (75)

99

 

34043200 (LPJ-150-

176F9078 (JJS-150)

34053600 (FNQ-

130G0488

 

 

 

 

 

 

 

 

 

 

 

SP)

R-0.50)

 

(JJS-175)

 

 

 

 

 

 

P5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

125 (90)

125

34043400 (LPJ-200-

130G0488 (JJS-175)

34053600 (FNQ-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP)

R-0.50)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3.5 Drive Fuses 600 V

3-4

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Installation

Vertical Bypass/Non Bypass Panel

 

 

3.1.3 Internal Main Panel Fuses

Use only the specified fuse or an equivalent replacement for the internal main fuses. See the specifications label inside the cover of the unit for acceptable replacement main fuses. A sample of this can be seen in Table 3.6.

Fuse

Description

Manufacturer

Part Number/Size

 

 

 

 

 

3

 

3

F13A & C

Primary Transformer

Bussmann

FNQ-R-0.50

 

 

F15A, B, & C

Main Fuses

Bussmann

LPJ-30-SP

 

 

F16A, B, & C

Drive Fuses

Bussmann

JJS-35

 

 

 

 

 

 

 

 

F900, F901,F902

SMPS - Power Supply

Bussmann

FWH-020A6F, 500V

 

 

 

 

Table 3.6 Sample Fuse Rating Label

3.2 Mechanical Installation

3.2.1 Lifting

Check the weight of the unit before attempting to lift. Ensure that the lifting device is suitable for safely lifting the panel. If necessary, plan for a hoist, crane or forklift with appropriate rating to move the units.

3.2.2 Hoist or Overhead Lift

Use a solid steel spreader bar for lifting. Slide the spreader bar through the two (2) lifting holes on the panel. Lifting rings are 0.59in (15mm) in diameter (see Figure 3.1). If VFD mounting screws interfere with the spreader bar, lifting hooks can be used instead of the lifting bar.

Connect the spreader bar to a hoist or other lifting device.

Carefully lift the unit and secure it to the wall. Refer to 8 Appendix for dimensional drawings to determine fasteners size and location.

3.2.3 Forklift

Only a competent lift operator with additional support personnel should attempt moving the unit.

Carefully position forklift and ensure stability prior to lift.

3.2.4 Shipping Weights

Weights listed in Table 3.7 are approximate for base units. Options can add or reduce weight of unit. Weights listed are in lbs.

Frame

Non Bypass Panel

Bypass Panel

P2

36

84

P3

66

106

P4

106

167

P5

155

248

Table 3.7 Approximate Shipping Weights

 

 

 

<![if ! IE]>

<![endif]>130BX367.10

Figure 3.1 Proper Lifting Method

MG.13.A1.22 - VLT® is a registered Danfoss trademark

3-5

Installation

Vertical Bypass/Non Bypass Panel

3.3

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

Only mount the drive and panel vertically.

50.8 [2.0] min

 

 

 

 

 

 

 

 

 

Panels rely on the ambient air for cooling. It is

 

 

 

 

 

 

 

important to observe the limitations on ambient

 

 

 

3

 

3

 

 

 

 

 

 

 

 

 

 

 

air temperature. The maximum ambient

 

 

 

 

 

temperature for all bypass panels is 40°C and

 

 

 

 

 

 

 

45°C for non bypass panels. Derating concerns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

start above 3300 feet elevation above sea level.

 

 

 

 

 

 

Most panels may be mounted side-by-side

 

 

 

 

 

 

 

without additional side clearance. However, the

 

 

 

P2 (B3 frame size) units require 1.5 in. minimum clearance between units (see Figure 3.2).

CEILING

AIRFLOW

Top and bottom clearance is required for cooling (see Figure 3.3). Generally, 2 to 10 inches (50 to

250mm) minimum clearance is required, depending upon the hp (kW) of the unit. See the dimensional drawings in 8 Appendix for specific requirements.

No additional back plate is required for drives

with the bypass and non bypass panels.

38.1 [1.5]

<![if ! IE]>

<![endif]>130BX368.10

 

101.6 [4.0] min

AIRFLOW

FLOOR

Figure 3.3 Cooling Airflow

Figure 3.2 Side Cooling Clearance

<![if ! IE]>

<![endif]>130BX369.12

3-6

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Installation

Vertical Bypass/Non Bypass Panel

 

 

3.4 Electrical Installation

WARNING

EQUIPMENT HAZARD!

Rotating shafts and electrical equipment can be hazardous. It is strongly recommended that all electrical work conform to all national and local regulations. Installation, start-up and maintenance should be performed only by qualified personnel. Failure to follow local regulations could result in death or serious injury.

Motor control equipment and electronic controls are connected to hazardous line voltages. Extreme care should be taken to protect against electrical hazard.

Correct protective grounding of the equipment must be established. Ground currents are higher than 3mA.

A dedicated ground wire is required.

Wear safety glasses whenever working on electric control or rotating equipment.

NOTE!

Make all power connections with a minimum of 60°C/ 140°F rated copper wire.

WARNING

INDUCED VOLTAGE!

Run output motor cables from multiple drives separately. Induced voltage from output motor cables run together can charge equipment capacitors even with the equipment turned off and locked out. Failure to run output motor cables separately could result in death or serious injury.

NOTE!

Run input power, motor wiring and control wiring in three separate metallic conduits or raceways for high frequency noise isolation. Failure to isolate power, motor and control wiring could result in less than optimum drive and associated equipment performance.

Because the motor wiring carries high frequency electrical pulses, it is important that no other wires are run together. If the incoming power wiring is run in the same conduit as the motor wiring, these pulses can couple electrical noise back onto the building power grid.

At least three separate conduits must be connected to the panel (Figure 3.4).

Power into the panel (and ground back to the distribution panel)

Power from the panel to the motor and earth insulated motor ground

Control wiring

Control wiring should always be isolated from the high

voltage power wiring. 3 3

Avoid getting metal chips into electronics.

Follow the connection procedures as illustrated in the drawing provided with the unit.

<![if ! IE]>

<![endif]>130BX370.10

Stop

Start

Speed

Line Power

Motor

 

 

Control

Figure 3.4 Power Connections

MG.13.A1.22 - VLT® is a registered Danfoss trademark

3-7

Installation

Vertical Bypass/Non Bypass Panel

 

 

3.4.1 Component Identification & Customer Connection

Mechanical layout drawings are intended to provide the installer or equipment user with component identification and location for that specific unit. Figure 3.5 represents a typical layout drawing. Table 3.8 provides definitions for drawing reference designators. (Not all reference designators are shown.)

3

3

26

 

 

17

 

 

19 (ECB OPTION ONLY)

 

 

CUST. CONNECTION

 

 

ECB CONTROL WIRES

 

 

CUST. CONNECTION

 

 

DRIVE CONTROL

 

 

TERMINALS

 

 

18 (EMB2 OPTION ONLY)

 

 

CUST. CONNECTION

 

CUSTOMER CONNECTION

EMB2 CONTROL WIRES

 

TERMINAL BLOCK 1

 

14

(EMB2 OPTION ONLY)

1

 

7

 

15 (EMB2 OPTION ONLY)

 

 

10

2

 

 

 

4,5,6

 

27

 

 

 

12

11

 

 

 

8

13

 

 

 

CUST. CONNECTION

 

 

INPUT & OUTPUT

 

 

GROUND

 

 

CUST. CONNECTION

CUST. CONNECTION

 

INPUT POWER

POWER TO MOTOR

 

L1 L2 L3

T1 T2 T3

Figure 3.5 P2 Bypass Mechanical Layout Diagram

<![if ! IE]>

<![endif]>130BX372.12

ID

Device

Definition

ID

Device

Definition

1

24 V DC

Panel 24 V DC SMPS

15

S1

Auto Bypass Selector Switch

2

HPC

High Pot Connector

16

TF

120 V AC control transformer

3

F13

T1 primary fuse

17

VFD

Variable frequency drive

4

CB1

Main Circuit Breaker

18

EMB2

Control Module

5

DS1

Main or Drive Disconnect

19

ECB

Control Module

6

F15

Main fuse

20

TB1-C

Terminal block 1 - Control

7

F16

Drive fuse

21

TB1-P

Terminal block 1 - Power

8

GND

Ground terminal

22

PR1

Control Relay for M1 Contactor

 

 

 

 

 

 

9

LCP

LCP

23

PR2

Control Relay for M2 Contactor

 

 

 

 

 

 

10

M1

Drive Input contactor

24

PR3

Control Relay for M3 Contactor

 

 

 

 

 

 

11

M2

Drive Output contactor

25

UVM

Under voltage module

 

 

 

 

 

 

12

M3

Bypass contactor

26

TC

Top Cover

 

 

 

 

 

 

13

OL1

Overload for Motor

27

DH

Disconnect Handle

 

 

 

 

 

 

14

PL1

Bypass indicator light

 

 

 

 

 

 

 

 

 

Table 3.8 Reference Designator Definitions

3-8

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Installation

Vertical Bypass/Non Bypass Panel

 

 

27

Figure 3.6 P2 Non Bypass Mechanical Layout Diagram.

26

<![if ! IE]>

<![endif]>130BX374.11

 

3 3

17

CUST. CONNECTION

DRIVE CONTROL

TERMINALS

CUSTOMER CONNECTION

TERMINAL BLOCK 1

7

21 5

CUST. CONNECTION

POWER TO MOTOR

T1 T2 T3

8

CUST. CONNECTION

INPUT AND OUTPUT GROUND

CUST. CONNECTION

INPUT POWER

L1 L2 L3

See Table 3.8 for reference designator definitions.

MG.13.A1.22 - VLT® is a registered Danfoss trademark

3-9

Installation

Vertical Bypass/Non Bypass Panel

 

 

 

 

 

 

26

 

 

 

 

<![if ! IE]>

<![endif]>130BX375.12

3

3

 

CUST. CONNECTION

CUST. CONNECTION

EMB2 / ECB CONTROL WIRES

 

 

 

 

DRIVE CONTROL

 

 

 

 

TERMINALS

18 OR 19

 

 

17

 

 

 

 

 

2

 

 

(EMB2 OPTION ONLY) 14

 

 

 

 

(EMB2 OPTION ONLY) 15

7

1

 

 

 

 

 

 

 

10

11

 

 

 

 

 

 

27

 

 

 

 

 

4,5,6

 

 

 

 

 

13

CUST. CONNECTION

 

 

 

 

 

 

 

 

OUTPUT GROUND

 

 

12

8

 

 

 

 

 

CUST. CONNECTION

CUST. CONNECTION

CUST. CONNECTION

INPUT POWER

INPUT GROUND

POWER TO MOTOR

L1 L2 L3

 

T1 T2 T3

Figure 3.7 P3 Bypass Mechanical Layout Diagram.

See Table 3.8 for reference designator definitions.

3-10

MG.13.A1.22 - VLT® is a registered Danfoss trademark

Loading...
+ 62 hidden pages