Danfoss VACON OPTE3, VACON OPTE5 User guide

User Guide
VACON® OPTE3/E5 PROFIBUS DP
VACON® OPTE3/E5 PROFIBUS DP
User Guide

Contents

1
1.1
Purpose of the Manual 8
Additional Resources 8
1.2
Manual and Software Version 8
1.3
1.4
Type Approvals and Certications 9
1.5
Product Overview 10
1.5.1
PROFIBUS 10
1.5.2
PROFIBUS DP 10
1.5.3
Features of PROFIBUS DP–VACON® Interface 10
Technical Data 10
1.5.4
VACON® PC Tools 11
1.5.5
Symbols and Abbreviations 11
1.6
Contents
Safety 13
2
2.1
Safety Symbols 13
2.2
Danger and Warnings 13
2.3
Cautions and Notices 14
2.4
Grounding 16
3
Commissioning 18
3.1
Before Commissioning 18
3.1.1
Installing VACON® PC Tools 18
3.1.2
Downloading Fieldbus Option Firmware 18
3.2
Commissioning with VACON® PC Tools 19
3.2.1
Updating Fieldbus Firmware with VACON® Loader 19
3.2.2
Adjusting Communication Settings 20
3.2.2.1
3.2.2.2
3.2.3
Setting Drive and PROFIBUS DP Parameters 21
3.2.3.1
Adjusting Serial Communication Settings in VACON® NCDrive 20
Adjusting Serial Communication Settings in VACON® Live 20
Setting Drive and PROFIBUS DP Parameters with VACON® NCDrive 21
3.2.3.2
3.3
Replacing VACON® NXS or NXL AC Drive with VACON® 100 Family AC Drive 23
4
Control Interface and Communication 25
4.1
PROFIBUS DP Communication Overview 25
4.1.1
Determining the PROFIBUS DP Cycle Time 25
4.2
Fieldbus Option Board Communication Modes 26
4.2.1
Requirements for Communication Modes 26
Setting Drive and PROFIBUS DP Parameters with VACON® Live 22
BC346130363093EN-US-000101/DPD00997 | 3Danfoss A/S © 2020.06
VACON® OPTE3/E5 PROFIBUS DP
User Guide
4.3
Contents
4.2.2
Fieldbus Communication Mode Features and Limitations 27
4.2.3
Normal Fieldbus Communication 28
4.2.4
Fast Fieldbus Communication 28
4.2.5
Fast Safety Fieldbus Communication 29
4.2.6
Normal Extended Mode 29
Drive Control 29
4.3.1
PROFIBUS DP Modules 29
4.3.2
Fieldbus Process Data 30
4.3.3
Bypass Operating Mode 33
4.3.3.1
4.3.3.2
4.3.3.3
4.3.4
Echo Operating Mode 41
4.3.5
PROFIdrive 4.1 Control Prole 41
Control Word Overview 33
Status Word Overview 37
Control and Status Word Monitoring Values 40
4.3.5.1
4.3.5.2
4.3.5.3
4.3.5.4
4.3.5.5
4.3.5.6
4.3.5.7
4.3.5.8
4.3.5.9
4.3.5.10
4.3.5.11
4.3.5.12
4.3.6
PROFIdrive 2.0 Control Prole 55
4.3.6.1
4.3.6.2
4.3.6.3
PROFIdrive 4.1 Prole Overview 41
PROFIdrive 4.1 State Machine 41
Standard Telegrams 43
Vendor-Specic Telegrams 45
PPO Types 48
PROFIdrive 4.1 Control Word (STW1) 50
PROFIdrive 4.1 Status Word (ZSW1) 51
Setpoint Value 52
Actual Speed Value 53
Normalization Reference Parameter 53
Shortlist of Commands to Start the Drive 53
Coding of Data Signals 54
PROFIdrive 2.0 Control Word 55
PROFIdrive 2.0 Status Word 56
State Machine for PROFIdrive 2.0 57
4.3.6.4
4.4
PROFIsafe 59
4.4.1
Introduction to PROFIsafe 59
4.4.2
PROFIdrive on PROFIsafe 60
5
Parameter Access 61
5.1
Parameter Access in PROFIdrive 4.1 61
5.1.1
Parameter Access Sequence 61
PPO Types 58
BC346130363093EN-US-000101/DPD009974 | Danfoss A/S © 2020.06
VACON® OPTE3/E5 PROFIBUS DP
User Guide
5.1.2
Parameter Requests 61
5.1.2.1
5.1.2.2
5.1.2.3
5.1.2.4
5.1.3
Parameter Responses 64
5.1.3.1
5.1.3.2
5.1.3.3
5.1.3.4
5.1.3.5
5.1.3.6
5.1.3.7
5.1.3.8
DP-V1 Header 62
Request Header 62
Parameter Address 63
Parameter Value 63
DP-V1 Header 64
Error Response 64
PROFIdrive 4.1 Error Classes and Codes 65
PROFIdrive Parameter Access Errors 66
Response Header 67
Parameter Values 68
Parameter Description Elements 68
Identier Field 68
Contents
5.1.3.9
5.1.3.10
5.1.3.11
5.1.3.12
5.1.3.13
5.1.3.14
5.1.3.15
5.1.3.16
5.1.4
Example Requests and Responses 71
5.1.4.1
5.1.4.2
5.1.4.3
5.1.4.4
5.1.4.5
5.1.4.6
5.1.4.7
Number of Array Elements Field 69
Standardization Factor Field 69
Variable Attribute Field 69
Name Field 70
Low/High Limit Fields 70
ID Extension Field 70
Normalization Reference Parameter Field 70
Normalization Field 71
Request Parameter PNU918 Value 71
Read Response to Request Parameter PNU918 Value 72
Request All Elements of Parameter PNU964 72
Read Response to Request Parameter PNU964 73
Request the Value of Unsupported Parameter PNU900 73
Read Response to Request of Unsupported Parameter PNU900 74
Request the Value of Drive Parameter ID 103 74
5.1.4.8
5.1.4.9
5.1.4.10
5.1.4.11
5.1.4.12
5.1.5
Supported Parameters 82
5.1.6
PROFIdrive Fault Buer 86
5.1.7
Drive System Time 87
Change the Value of Drive Parameter ID 103 (Successful) 75
Change the Value of Drive Parameter ID 103 (Unsuccessful) 75
Request Multiple Values from Drive 76
Change Values of Multiple Drive Parameters (Successful) 78
Change Values of Multiple Drive Parameters (Unsuccessful) 80
BC346130363093EN-US-000101/DPD00997 | 5Danfoss A/S © 2020.06
VACON® OPTE3/E5 PROFIBUS DP
User Guide
5.1.7.1
5.1.7.2
5.2
Parameter Access in PROFIdrive 2.0 88
5.2.1
DP-V1 with PROFIdrive 2.0 88
5.2.2
Parameter Field (PKW) in PPO Types 88
5.2.3
Example Requests and Responses 89
5.2.3.1
5.2.3.2
6
Parameters 91
6.1
PROFIBUS DP Board Parameters 91
6.1.1
Slave Address 91
6.1.2
Operate Mode 91
6.1.3
Compatib. Mode 93
6.2
Parameters Congured in PLC 94
Read Drive System Time 87
Write Drive System Time 87
Read Maximum Frequency (ID = 102) 89
Write Control Place (ID = 125) 90
Contents
6.2.1
Operate Mode 94
6.2.2
DP Mode 94
6.3
Safety Parameters 94
6.4
AC Drive Parameters 94
6.4.1
AC Drive Parameters for Fieldbus Control and Reference Selection 94
6.4.2
Fieldbus Parameters for VACON® 100 Family Standard Application 95
6.4.3
Fieldbus Parameters for VACON® 20 Standard Application 95
6.4.4
Fieldbus Parameters for VACON® 20 X Multipurpose Application 96
6.4.5
Fieldbus Parameters for VACON® NXP Multipurpose Application 96
6.5
Response to Fieldbus Fault Parameter 96
6.6
VACON® NXP System Software Parameters for Application Developers 97
6.6.1
System Software Variables for Selecting Communication Modes 97
6.6.2
System Software Variables for Monitoring Supported Communication Modes 97
6.6.3
System Software Variables for Selecting the Input Process Data Slot 98
7
Monitoring Values 99
7.1
PROFIBUS DP Board Monitoring Values 99
7.1.1
PROFIBUS DP Status 104
7.1.2
FB Protocol Status 104
7.1.3
Protocol 104
7.1.4
Baud Rate 104
7.1.5
PPO Type 104
7.1.6
Telegram Type 104
7.1.7
Safety Telegram 104
BC346130363093EN-US-000101/DPD009976 | Danfoss A/S © 2020.06
VACON® OPTE3/E5 PROFIBUS DP
User Guide
7.1.8
Protocol CW/Fieldbus CW 105
7.1.9
Protocol SW/Fieldbus SW 105
7.1.10
Drive CW 105
7.1.11
Drive SW 105
8
Fault Tracing 106
8.1
LED Indications on PROFIBUS Option Boards 106
8.2
PROFIBUS DP Diagnosis 107
8.2.1
Standard Diagnosis 107
8.2.2
Channel-Related Diagnosis 108
8.3
Fault Handling 109
8.4
Gathering Diagnostic Data 109
8.5
Typical Fault Conditions 109
8.5.1
Source3 Fault Codes 110
Contents
BC346130363093EN-US-000101/DPD00997 | 7Danfoss A/S © 2020.06
• NOTE! Download the English and French product manuals with applicable safety, warning and caution information from https://
www.danfoss.com/en/service-and-support/.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit contenant l'ensemble des informa­tions de sécurité, avertissements et mises en garde applicables sur le site https://www.danfoss.com/en/service-and-support/.
Manual ver­sion
New features
Firm­ware ver­sion
DPD00997B
Support for VACON® 100 INDUSTRIAL, VACON® 100 FLOW, VACON® 100 X, VACON® 20 X/CP, and VA­CON® 20 drives.
V004
DPD00997C
Support for new B version hardware. Firmware can also be used with older A version hardware.
Improved functionality of Control-By-PLC bit. This bit does not any more force control and refer­ence place to eldbus. This bit is still required so that control from the eldbus is possible.
V005
Support for VACON® NXP drive.
Support for PROFIsafe when OPTE3/E5 board is used together with Advanced safety option board. See details in 4.4 PROFIsafe.
Support for Fast Communication and 16 process data when installed to VACON® NXP drive. See details in 4.2 Fieldbus Option Board Communication Modes.
Support for "C3 C5 Mode" compatibility mode when OPTE3/E5 is installed to VACON® NXP drive. See details in 6.1 PROFIBUS DP Board Parameters.
Support for "NX Mode" compatibility mode when OPTE3/E5 is installed to VACON® 100 family and VACON® 20 drives. See details in 6.1 PROFIBUS DP Board Parameters.
V006
VACON® OPTE3/E5 PROFIBUS DP
User Guide

Introduction

1 Introduction
1.1 Purpose of the Manual
The PROFIBUS DP programming guide provides information about conguring the system, controlling the drive, accessing parame­ters, programming, troubleshooting, and some typical application examples.
The programming guide is intended for use by qualied personnel, who are familiar with the VACON® drives, PROFIBUS technology, and with the PC or PLC that is used as a master in the system.
Read the instructions before programming and follow the procedures in this manual.
1.2 Additional Resources
Resources available for the drive and optional equipment are:
VACON® RS485 CAN bus Installation Guide provides the necessary information to install the option board to the AC drive.
The Operating Guide of the AC drive provides the necessary information to get the drive up and running.
The Application Guide of the AC drive provides more details on working with parameters and many application examples.
VACON® OPTEA/OPTE9 Ethernet Board Programming Guide provides information on Ethernet settings.
Supplementary publications and manuals are available from drives.danfoss.com/knowledge-center/technical-documentation/. For US and Canadian markets:
1.3 Manual and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome. The original language of this manual is English.
Table 1: Manual and Software Version
BC346130363093EN-US-000101 / DPD009978 | Danfoss A/S © | 2020.06
Manual ver­sion
New features
Firm­ware ver­sion
DPD00997D
Support for PPO_PROFIdrive mode which enables usage of PROFIdrive 4.1 together with PPO types. See details in 6.1 PROFIBUS DP Board Parameters.
Support for drive fault history with time stamps. See details in 5.1.5 Supported Parameters.
Support for Drive CW and Drive SW monitor values. See details in 7.1 PROFIBUS DP Board Monitor-
ing Values.
V007
DPD00997E
PROFIsafe over PROFIBUS for VACON® NXP extended for advanced safety option boards OPTBL, OPTBM and OPTBN in slots C and E in addition to slot D.
Maintance improvements and xes.
Conguration le updated.
The structure of the manual updated. Installation information removed (see VACON® RS485 CAN bus Installation Guide).
V008
Telegram 140
PNU 10129
V009
089
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Introduction
1.4 Type Approvals and Certications
The following list is a selection of possible type approvals and certications for Danfoss drives:
N O T I C E
The specic approvals and certication for the drive are on the nameplate of the drive. For more information, contact the local
Danfoss oce or partner.
BC346130363093EN-US-000101 / DPD00997 | 9Danfoss A/S © 2020.06
Technical item or function
Technical data
Connections
Interface
OPTE3: Pluggable connector (5.08 mm) OPTE5: 9-pin D-SUB connector (female)
Data transfer method
RS485, half duplex
Transfer cable
Shielded Twisted Pair
Electrical isolation
500 V DC
Communications
Drive prole
PROFIdrive
Standard Telegrams
1, 20
Vendor Telegrams
100, 101, 138, 139
Standard (Safety) Telegrams
30, 31
(1)
Vendor (Safety) Telegrams
58000
(1)
PPO types
1, 2, 3, 4, 5, 6
Baud rate
9.6 kBd to 12 MBd. Autobaud detect is always on.
Addresses
2–126
Environment
Ambient operating temperature
-10°C…50°C (For further information, see the installation manual of the AC drive)
Storing temperature
-40°C…60°C
Humidity
<95%, no condensation, or frost allowed, non-corrosive
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Introduction
1.5 Product Overview
1.5.1 PROFIBUS
PROFIBUS is an international standard for eldbus communication in automation technology (IEC 61158 and IEC 61784). The mem­ber companies of the PROFIBUS International User Community support the standard.
For information about PROFIBUS and downloads for PROFIBUS DP and the PROFIdrive prole, refer to www.probus.com.
1.5.2 PROFIBUS DP
The PROFIBUS DP protocol enables communication between PROFIBUS masters and slaves. The master devices control the communication. The master can send data without a separate command when a token is given to
the Master. The slave devices are peripheral devices. Typical slave devices include input/output devices, valves, drives, and measur­ing transmitters. They do not have bus access rights and they can only acknowledge received messages or send messages to the master when requested to do so.
VACON® AC drives can be connected to the PROFIBUS DP network using a eldbus board. The drive can then be controlled, moni­tored, and programmed from the Host system.
OPTE5/E3 option board also supports connection from DP Master (class 2) when DP-V1 is enabled. In this case, the master class 2 can initiate a connection, read and write parameters using the PROFIdrive Parameter Access service, and close the connection.
1.5.3 Features of PROFIBUS DP–VACON® Interface
Features of the PROFIBUS DP–VACON® interface:
Direct control of VACON® AC drives (for example, Run, Stop, Direction, Speed reference, Fault reset)
Full access to all VACON® AC drive parameters
Monitor VACON® AC drive status (for example, output frequency, output current, fault code)
1.5.4 Technical Data
Table 2: PROFIBUS DP Option Board Technical Data
BC346130363093EN-US-000101 / DPD0099710 | Danfoss A/S © | 2020.06
Technical item or function
Technical data
Altitude
Maximum 1000 m
Vibration
0.5 G at 9…200 Hz
Safety
Fullls EN 50178 standard
Tool
VACON® 100 family
VACON® NXS/NXP
VACON® 20 family
VACON® Loader
Serial
(1)
Serial
(1)
Serial
(1)
VACON® Live
Serial
(1)
, Ethernet
(2)
Serial
(1)
VACON® NCIPCong
Not used with OPTE3/E5 PROFIBUS DP
VACON® NCDrive
Serial
(1)
, Ethernet
(2)
VACON® NCLoad
Not used with OPTE3/E5 PROFIBUS DP
Abbreviation
Denition
CW
Control word
DP
Distributed periphery
DU
Data unit
EEPROM
Electrical erasable programmable read-only memory
EMC
Electromagnetic compatibility
FB
Fieldbus
FDT
Field device tool
GSD
Generic Station Description
HMI
Human machine interface
VACON® OPTE3/E5 PROFIBUS DP
User Guide
1
Select only when Advanced safety option board with PROFIsafe is connected.
Introduction
1.5.5 VACON® PC Tools
With VACON® PC tools, it is possible to do following operations for OPTE3/E5 PROFIBUS DP:
Update rmware into OPTE3/E5 PROFIBUS DP option board (with VACON® Loader), see 3.2.1 Updating Fieldbus Firmware with
VACON® Loader
Set parameters for OPTE3/E5 PROFIBUS DP (with VACON® NCDrive or VACON® Live), see 3.2.3.1 Setting Drive and PROFIBUS DP
Parameters with VACON® NCDrive and 3.2.3.2 Setting Drive and PROFIBUS DP Parameters with VACON® Live
Read monitor values of OPTE3/E5 PROFIBUS DP (with VACON® NCDrive or VACON® Live)
For instructions on downloading and installing the tools, see 3.1.1 Installing VACON® PC Tools. The following table describes what PC tools are supported in each AC drive type.
Table 3: The Supported PC Tools with Dierent AC Drives
1
The connection type "serial" is a direct serial connection to the AC drive.
2
The connection type "Ethernet" is an Ethernet connection, for example, VACON® 100 family built-in Ethernet interface, or a connection via OPTEA/
OPTE9 Dual Port Ethernet option board.
1.6 Symbols and Abbreviations
Table 4: Symbols and Abbreviations
BC346130363093EN-US-000101 / DPD00997 | 11Danfoss A/S © 2020.06
Abbreviation
Denition
IND
Sub index
LED
Light emitting diode
PC
Personal computer
PDI
Process Data In
PDO
Process Data Out
PLC
Programmable logic controller
PNU
Parameter number
PPO
Process parameter object
SW
Status word
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Introduction
BC346130363093EN-US-000101 / DPD0099712 | Danfoss A/S © | 2020.06
VACON® OPTE3/E5 PROFIBUS DP
User Guide
2 Safety
2.1 Safety Symbols
The following symbols are used in this manual:
D A N G E R
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
W A R N I N G
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
C A U T I O N
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
N O T I C E
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).

Safety

2.2 Danger and Warnings
D A N G E R
SHOCK HAZARD FROM POWER UNIT COMPONENTS
The power unit components are live when the drive is connected to mains. A contact with this voltage can lead to death or seri-
ous injury.
Do not touch the components of the power unit when the drive is connected to mains. Before connecting the drive to mains,
-
make sure that the covers of the drive are closed.
D A N G E R
SHOCK HAZARD FROM TERMINALS
The motor terminals U, V, W, the brake resistor terminals, or the DC terminals are live when the drive is connected to mains, also
when the motor does not operate. A contact with this voltage can lead to death or serious injury.
Do not touch the motor terminals U, V, W, the brake resistor terminals, or the DC terminals when the drive is connected to
-
mains. Before connecting the drive to mains, make sure that the covers of the drive are closed.
D A N G E R
SHOCK HAZARD FROM DC LINK OR EXTERNAL SOURCE
The terminal connections and the components of the drive can be live 5 minutes after the drive is disconnected from the mains
and the motor has stopped. Also the load side of the drive can generate voltage. A contact with this voltage can lead to death or
serious injury.
Before doing electrical work on the drive:
-
Disconnect the drive from the mains and make sure that the motor has stopped. Lock out and tag out the power source to the drive. Make sure that no external source generates unintended voltage during work. Wait 5 minutes before opening the cabinet door or the cover of the AC drive. Use a measuring device to make sure that there is no voltage.
BC346130363093EN-US-000101 / DPD00997 | 13Danfoss A/S © 2020.06
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Safety
W A R N I N G
SHOCK HAZARD FROM CONTROL TERMINALS
The control terminals can have a dangerous voltage also when the drive is disconnected from mains. A contact with this voltage
can lead to injury.
Make sure that there is no voltage in the control terminals before touching the control terminals.
-
W A R N I N G
ACCIDENTAL MOTOR START
When there is a power-up, a power break, or a fault reset, the motor starts immediately if the start signal is active, unless the pulse
control for Start/Stop logic is selected. If the parameters, the applications or the software change, the I/O functions (including the
start inputs) can change. If you activate the auto reset function, the motor starts automatically after an automatic fault reset. See
the Application Guide. Failure to ensure that the motor, system, and any attached equipment are ready for start can result in
personal injury or equipment damage.
Disconnect the motor from the drive if an accidental start can be dangerous. Make sure that the equipment is safe to operate
-
under any condition.
W A R N I N G
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
Ensure the correct grounding of the equipment by a certied electrical installer.
-
W A R N I N G
SHOCK HAZARD FROM PE CONDUCTOR
The drive can cause a DC current in the PE conductor. Failure to use a residual current-operated protective (RCD) device Type B or
a residual current-operated monitoring (RCM) device can lead to the RCD not providing the intended protection and therefore
can result in death or serious injury.
Use a type B RCD or RCM device on the mains side of the drive.
-
2.3 Cautions and Notices
C A U T I O N
DAMAGE TO THE AC DRIVE FROM INCORRECT MEASUREMENTS
Doing measurements on the AC drive when it is connected to mains can damage the drive.
Do not do measurements when the AC drive is connected to mains.
-
C A U T I O N
DAMAGE TO THE AC DRIVE FROM INCORRECT SPARE PARTS
Using spare parts that are not from the manufacturer can damage the drive.
Do not use spare parts that are not from the manufacturer.
-
C A U T I O N
DAMAGE TO THE AC DRIVE FROM INSUFFICIENT GROUNDING
Not using a grounding conductor can damage the drive.
Make sure that the AC drive is always grounded with a grounding conductor that is connected to the grounding terminal
-
that is identied with the PE symbol.
BC346130363093EN-US-000101 / DPD0099714 | Danfoss A/S © | 2020.06
VACON® OPTE3/E5 PROFIBUS DP
User Guide
C A U T I O N
CUT HAZARD FROM SHARP EDGES
There can be sharp edges in the AC drive that can cause cuts.
Wear protective gloves when mounting, cabling, or doing maintenance operations.
-
C A U T I O N
BURN HAZARD FROM HOT SURFACES
Touching surfaces, which are marked with the 'hot surface' sticker, can result in injury.
Do not touch surfaces which are marked with the 'hot surface' sticker.
-
N O T I C E
DAMAGE TO THE AC DRIVE FROM STATIC VOLTAGE
Some of the electronic components inside the AC drive are sensitive to ESD. Static voltage can damage the components.
Remember to use ESD protection always when working with electronic components of the AC drive. Do not touch the com-
-
ponents on the circuit boards without proper ESD protection.
Safety
N O T I C E
DAMAGE TO THE AC DRIVE FROM MOVEMENT
Movement after installation can damage the drive.
Do not move the AC drive during operation. Use a xed installation to prevent damage to the drive.
-
N O T I C E
DAMAGE TO THE AC DRIVE FROM INCORRECT EMC LEVEL
The EMC level requirements for the AC drive depend on the installation environment. An incorrect EMC level can damage the
drive.
Before connecting the AC drive to the mains, make sure that the EMC level of the AC drive is correct for the mains.
-
N O T I C E
RADIO INTERFERENCE
In a residential environment, this product can cause radio interference.
Take supplementary mitigation measures.
-
N O T I C E
MAINS DISCONNECTION DEVICE
If the AC drive is used as a part of a machine, the machine manufacturer must supply a mains disconnection device (refer to EN
60204-1).
N O T I C E
MALFUNCTION OF FAULT CURRENT PROTECTIVE SWITCHES
Because there are high capacitive currents in the AC drive, it is possible that the fault current protective switches do not operate
correctly.
BC346130363093EN-US-000101 / DPD00997 | 15Danfoss A/S © 2020.06
Cross-sectional area of the phase conductors (S) [mm2]
The minimum cross-sectional area of the protective earthing con­ductor in question [mm2]
S ≤ 16
S
16 < S ≤ 35
16
35 < S
S/2
VACON® OPTE3/E5 PROFIBUS DP
User Guide
N O T I C E
VOLTAGE WITHSTAND TESTS
Doing voltage withstand tests can damage the drive.
Do not do voltage withstand tests on the AC drive. The manufacturer has already done the tests.
-
2.4 Grounding
Ground the AC drive in accordance with applicable standards and directives.
C A U T I O N
DAMAGE TO THE AC DRIVE FROM INSUFFICIENT GROUNDING
Not using a grounding conductor can damage the drive.
Make sure that the AC drive is always grounded with a grounding conductor that is connected to the grounding terminal
-
that is identied with the PE symbol.
W A R N I N G
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
Ensure the correct grounding of the equipment by a certied electrical installer.
-
Safety
The standard EN 61800-5-1 tells that 1 or more of these conditions for the protective circuit must be true.
The connection must be xed.
The protective earthing conductor must have a cross-sectional area of minimum 10 mm2 Cu or 16 mm2 Al. OR
There must be an automatic disconnection of the mains, if the protective earthing conductor breaks. OR
There must be a terminal for a second protective earthing conductor in the same cross-sectional area as the rst protective earthing conductor.
The values of the table are valid only if the protective earthing conductor is made of the same metal as the phase conductors. If this is not so, the cross-sectional area of the protective earthing conductor must be determined in a manner that produces a conduc­tance equivalent to that which results from the application of this table.
The cross-sectional area of each protective earthing conductor that is not a part of the mains cable or the cable enclosure, must be a minimum of:
2.5 mm2 if there is mechanical protection, and
4 mm2 if there is not mechanical protection. With cord-connected equipment, make sure that the protective earthing conductor in the cord is the last conductor to be interrupted, if the strain-relief mechanism breaks.
Obey the local regulations on the minimum size of the protective earthing conductor.
N O T I C E
MALFUNCTION OF FAULT CURRENT PROTECTIVE SWITCHES
Because there are high capacitive currents in the AC drive, it is possible that the fault current protective switches do not operate
correctly.
BC346130363093EN-US-000101 / DPD0099716 | Danfoss A/S © | 2020.06
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Safety
N O T I C E
VOLTAGE WITHSTAND TESTS
Doing voltage withstand tests can damage the drive.
Do not do voltage withstand tests on the AC drive. The manufacturer has already done the tests.
-
W A R N I N G
SHOCK HAZARD FROM PE CONDUCTOR
The drive can cause a DC current in the PE conductor. Failure to use a residual current-operated protective (RCD) device Type B or
a residual current-operated monitoring (RCM) device can lead to the RCD not providing the intended protection and therefore
can result in death or serious injury.
Use a type B RCD or RCM device on the mains side of the drive.
-
BC346130363093EN-US-000101 / DPD00997 | 17Danfoss A/S © 2020.06
VACON® OPTE3/E5 PROFIBUS DP
User Guide

Commissioning

3 Commissioning
3.1 Before Commissioning
VACON® OPTE3/E5 PROFIBUS DP can be commissioned through the control panel of the AC drive or by using the VACON® PC tools.
Before starting the commissioning, check the following:
When using the control panel of the AC drive for commissioning: for instructions on how to use the control panel, see the Oper­ating Guide for VACON® NXP products or the Application Guide for the VACON® 100 family.
When using VACON® PC tool for commissioning: the correct tool installed.
-
For a list of supported PC tools, see 1.5.5 VACON® PC Tools.
-
For instructions on installing the tools, see 3.1.1 Installing VACON® PC Tools.
VACON® AC drive in which OPTE3/E5 PROFIBUS DP option board installed. See VACON® RS485 CAN bus Installation Guide for instructions.
When using serial connection:
-
VACON® NXP is connected to PC with RS232 serial cable. The cable is connected from PC to the 9-pin D-SUB connector (female) of the VACON® NXP control unit. If PC does not contain RS232 serial port, then USB - RS232 converter device is needed between PC and VACON® NXP control unit.
-
VACON® 100 family and VACON® 20 are connected to PC with VACON® Serial Cable.
When using Ethernet connection:
-
Ethernet cable which is connected to the Ethernet interface of the option board, or, in VACON® 100 family drives, of the control board.
-
VACON® NXP requires option board supporting Ethernet communication. For example, OPTEA/OPTE9 Dual Port Ethernet option board.
3.1.1 Installing VACON® PC Tools
Prepare for commissioning by installing the needed VACON® PC Tools.
Procedure
1.
Go to www.danfoss.com/.
2.
Select Downloads from Service and Support drop-down menu.
3.
Select Drives as business unit.
4.
Download the VACON® PC tool depending on the used AC drive.
VACON® 100 family AC drive: VACON® Loader and VACON® Live
VACON® 20 AC drive: VACON® Loader and VACON® Live
VACON® NXP AC drive: VACON® NCDrive and VACON® Loader
5.
Start the installation program and follow the on-screen instructions.
6.
After installation, launch VACON® PC tool from Windows Start menu.
7.
For more information about software features, go to Help drop-down menu and select Contents.
3.1.2 Downloading Fieldbus Option Firmware
Prepare for commissioning by downloading the Fieldbus Option Firmware.
Procedure
Go to
1.
2.
3.
4.
www.danfoss.com/.
Select Downloads from Service and Support drop-down menu. Select Drives as business unit. Download le Fieldbus rmware.
BC346130363093EN-US-000101 / DPD0099718 | Danfoss A/S © | 2020.06
e30bh634.10
e30bh635.10
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Commissioning
3.2 Commissioning with VACON® PC Tools
3.2.1 Updating Fieldbus Firmware with VACON® Loader
Use these instructions to upload the eldbus rmware with VACON® Loader.
NOTE! Screenshots in these instructions are examples only. The product information shown in them is dierent depending on which option board is used.
Check the list in Before commissioning. Adjust the baud rate if needed:
With VACON® 20, use the baud rate 9600.
With VACON® 20 X and VACON® 20 CP, the following baud rates are supported: 9600, 19200, 38400 or 57600.
With VACON® 100 family and VACON® NXP drives, VACON® Loader selects a correct baud rate automatically.
Procedure
1.
Connect your PC to the controller by using the serial cable.
2.
Open the File Explorer and select the rmware le to be updated to the option board and double-click it.
VACON® Loader software opens.
3.
Press Next and wait for the loader to nd the network drives.
4.
Select a drive from the list and press Connect to Selected.
5.
Select the modules to be updated, and press Next.
Firmware starts to load:
BC346130363093EN-US-000101 / DPD00997 | 19Danfoss A/S © 2020.06
e30bh636.10
e30bh637.10
e30bh638.10
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Commissioning
Loading is nished:
3.2.2 Adjusting Communication Settings
3.2.2.1 Adjusting Serial Communication Settings in VACON® NCDrive
Use these instructions to adjust the serial communication settings in VACON® NCDrive.
Procedure
1.
Connect your PC to the control unit by using the USB/RS232 cable.
2.
Select Tools.
3.
Select Options….
4.
Select Communication tab.
5.
Dene settings for the USB - RS232 adapter and press OK.
3.2.2.2 Adjusting Serial Communication Settings in VACON® Live
Use these instructions to adjust the serial communication settings in VACON® Live.
BC346130363093EN-US-000101 / DPD0099720 | Danfoss A/S © | 2020.06
e30bh642.10
e30bh643.10
e30bh644.10
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Procedure
1.
Connect the PC to VACON® AC drive with VACON® Serial Cable.
2.
Start VACON® Live.
3.
When the program starts, select Online for start-up mode.
4.
If VACON® Live cannot nd your AC drive, ensure that Serial / Ethernet or Serial is selected.
Commissioning
The program scans compatible drives. After successful scanning, VACON® Live shows the drive in connected drives window.
5.
Press Scan.
6.
Select the drive and press Connected to Selected.
VACON® Live reads parameter and monitor value tree from the drive.
3.2.3 Setting Drive and PROFIBUS DP Parameters
3.2.3.1 Setting Drive and PROFIBUS DP Parameters with VACON® NCDrive
Use these instructions to set the Drive and PROFIBUS DP Parameters with VACON® NCDrive.
Make sure that the communications have been adjusted. More information:
Serial communication:
-
VACON® NCDrive, see 3.2.2.1 Adjusting Serial Communication Settings in VACON® NCDrive
When using Ethernet communication, see VACON OPTEA/OPTE9 Programming Guide for instructions.
BC346130363093EN-US-000101 / DPD00997 | 21Danfoss A/S © 2020.06
e30bh639.10
e30bh640.10
e30bh641.10
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Procedure
1.
Press the ON-LINE button.
2.
To change the option board settings, navigate to the M7 Expander boards menu, and select the slot to which OPTE3/E5 PROFIBUS DP is connected.
Commissioning
The NCDrive connects to the drive and starts loading parameter information.
It is possible to change parameters dened in 6.1 PROFIBUS DP Board Parameters. Add at least the PROFIBUS slave ad­dress.
3.2.3.2 Setting Drive and PROFIBUS DP Parameters with VACON® Live
Use these instructions to nd the Drive and PROFIBUS DP Parameters with VACON® Live.
With VACON® Live, it is possible to modify OPTE3/E5 PROFIBUS DP parameters and view monitor values.
Make sure that the communications have been adjusted. More information:
Serial communication:
-
VACON® Live, see 3.2.2.2 Adjusting Serial Communication Settings in VACON® Live
When using Ethernet communication, see VACON OPTEA/OPTE9 Programming Guide for instructions.
Procedure
1.
Open VACON® Live.
2.
Navigate to 5. I/O and Hardware menu. Add at least the PROFIBUS slave address.
BC346130363093EN-US-000101 / DPD0099722 | Danfoss A/S © | 2020.06
e30bh645.10
e30bh646.10
VACON® OPTE3/E5 PROFIBUS DP
User Guide
3.3 Replacing VACON® NXS or NXL AC Drive with VACON® 100 Family AC Drive
Make these adjustments when replacing VACON® NXS or VACON® NXL AC Drive with VACON® 100 Family AC Drive.
Commissioning
With VACON® 100 Family AC drive and OPTE3/E5, the baud rate is always automatically selected.
Procedure
1.
Take the newer GSD le into use in the PLC.
a.
Download the GSD les from http://drives.danfoss.com.
b.
If the Mode parameter is set to NX mode or C3/C5 mode (see 6.1 PROFIBUS DP Board Parameters), use the GSD le for OPTC3/C5. This option can be used to support old installations.
By default, the OPTE3/E5 uses a dierent GSD le containing more modules than OPTC3/C5. The PPO types supported in OPTC3/C5 (1–5) are still supported and are compatible with OPTE3/E5.
2.
To select operate mode with panel parameter, use Local.
In OPTC3/C5, the PPO type and operate mode are selected using panel parameters. In OPTE3/E5, when Local is not selec­ted, it is possible to do it with the PLC. See 6.1.2 Operate Mode for more information.
BC346130363093EN-US-000101 / DPD00997 | 23Danfoss A/S © 2020.06
e30bh625.10
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Commissioning
3.
If needed, remove FBDIN bits used in PROFIdrive 2.0. VACON® 100 family AC drives do not support them.
BC346130363093EN-US-000101 / DPD0099724 | Danfoss A/S © | 2020.06
PROFIBUS DP MASTER
Application
Control Word
Option Board Control Board
PDI[0]
PDI[2]
PDI[4]
PDI[10]
PDO[0]
PDO[2]
PDO[4]
PDO[10]
Speed Reference
ProcessData 1
ProcessData 2
ProcessData 1
ProcessData 2
ProcessData
Service Data
Parameter Field (4 word) Parameter Definit ons and values
Parameter Field (4 word) Variable Definit ons and values
Request
Response
Status Word
Actual Speed
..
.
...
.
...
...
e30bh618.10
VACON® OPTE3/E5 PROFIBUS DP
Control Interface and
User Guide
Communication
4 Control Interface and Communication
4.1 PROFIBUS DP Communication Overview
The data transfer between the PROFIBUS DP master and the slave takes place via the input/output data eld. The Master writes to the output data of the Slave and the Slave answers by sending the contents of its input data to the Master. The contents of the input/output data is dened in the device prole. The device prole for AC drives is PROFIdrive.
When eldbus has been selected as the active control place on the AC drive, the operation of the AC drive can be controlled from the PROFIBUS DP Master. Regardless if the active control place is eldbus, the AC drive can be monitored and its parameters set by the PROFIBUS DP Master.
The communication between the PROFIBUS DP board and the AC drive can be split into two types:
Process Data
-
Process Data In (PDI): For controlling AC drive, maximum of 18 words
-
Process Data Out (PDO): Is used for fast monitoring of the AC drive, maximum of 18 words
Service Data: Used for Write/Read parameters and variables. Available only when the device is congured to use PPO1, PPO2, or PPO5. In this case, PROFIdrive 2.0 is used by the default. PROFIdrive 4.1 can be used together with PPO types by enabling "PPO_PROFIdrive Mode" setting. See details in chapter 5.1 PROFIBUS DP board parameters.
NOTE! If Standard Telegrams are used in data exchange, Service Data is communicated using the acyclic data exchange as specied in DP-V1 and the PROFIdrive 4.1 specication.
Illustration 1: Data Transfer between PROFIBUS DP Master and VACON® AC drive
4.1.1 Determining the PROFIBUS DP Cycle Time
The PROFIBUS DP cycle time must be determined, for example, when using PROFIsafe over PROFIBUS DP, as it must be considered for the safety watchdog time.
The PROFIBUS DP master calculates the cycle time based on these variables:
BC346130363093EN-US-000101 / DPD00997 | 25Danfoss A/S © 2020.06
Software or hardware
Fast/Normal Extended
Fast safe
Control Board
NXP (serial number 761 or later)
NXP (serial number 761 or later)
System Software
NXP00002V196.vcn
NXP00002V196.vcn
Applications
(1)
Multipurpose V236 or later (Normal Extended Mode)
Any
(2)
Fieldbus option rmware version
OPTE3/E5 V006 or later
OPTE3-E5_FW0083V006.vcx or later
OPTE9 V007 or later
-
OPTEA V001 or later
OPTEA V001 or later
(3)
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Number of slaves
Transmission rate
Data volume (input and output data)
Use the PLC program to check the value. Instructions use this setup:
PLC with 4 VACON® AC drives
congured with 16 bytes of Process Data
on a transmission rate of 1.5 Mbps.
NOTE! These examples do not include the eect of acyclic data exchange, alarms, or retransmissions.
Using Siemens TIA Portal V13
1.
Open Network view.
2.
Select the PROFIBUS network.
3.
Select General.
4.
Select PROFIBUS.
5.
Select Bus parameters.
6.
Select Ttr typical.
Control Interface and
Communication
The following value is shown: 3.3 ms.
Using Beckho TwinCAT System Manager V2
1.
Open I/O - Conguration.
2.
Select PROFIBUS master.
3.
Select EL6731 (in this example).
4.
Select Estimated DPCycle.
The following value is shown: 3.1 ms.
4.2 Fieldbus Option Board Communication Modes
The VACON® eldbus option boards support the following eldbus board communication modes:
Normal mode, for most commonly used setups (see
Normal extended mode, for setups that requires 16 process data items
Fast mode, with low latency process data (see 4.2.4 Fast Fieldbus Communication)
Fast safety mode with safety "black channel" (see 4.2.5 Fast Safety Fieldbus Communication)
Fast PROFIBUS mode. Use other modes with new installations.
NOTE! Not all boards support all modes. For details, see 4.2.1 Requirements for Communication Modes. The fast communication modes can be enabled to get minimum communication delay between the eldbus and application.
4.2.3 Normal Fieldbus Communication)
4.2.1 Requirements for Communication Modes
Table 5: Requirements for Dierent Fieldbus Communication Modes for VACON® NXP
BC346130363093EN-US-000101 / DPD0099726 | Danfoss A/S © | 2020.06
Software or hardware
Fast/Normal Extended
Fast safe
OPTEC V003 or later
-
OPTE6 V010 or later
-
OPTE7 V006 or later
-
Advanced safety option
-
OPTBL_FW0227V001 or later
Software
Normal Extended
System Software
INDUSTRIAL FW0072V030
FLOW FW0159V022
Fieldbus option rmware version
OPTE9: V010
OPTEA: V003
OPTE7: V006
OPTE3/OPTE5: V008
VACON® OPTE3/E5 PROFIBUS DP
Control Interface and
User Guide
1
For latest information about application support for eldbus communication modes, refer to application-specic manuals.
2
If safety option is congured to use a safety eldbus, the fast safe mode is automatically enabled regardless of used application. However, the availability of 16 process items is limited by the application in use. Also the process data application cycle is normally set to 10 ms, instead of 1 ms for fast application.
3
Only with Advanced Safety Option
Table 6: Requirements for Normal Extended Communication Mode for VACON® 100 Family
Communication
4.2.2 Fieldbus Communication Mode Features and Limitations
Fast mode
1 ms process data interval
Available in VACON® NXP slots D and E
-
Possible to run both slots simultaneously
-
Have similar process data latency in both slots
Service data latency is also reduced
-
Running multiple service data queries at high interval can cause high CPU load in VACON® NXP AC drive.
Fast safe mode
1 ms process data interval
Includes safety "black channel"
Activated/deactivated automatically, not available for setting
Safety eldbus must be activated in safety conguration
-
Advanced safety option board must be installed into slot D
-
Safety eldbus must be activated in safety conguration
16 process data items
16 process data items always require support from application
Available in Fast, Fast safe, and Normal extended mode
If no support is available in the application, the process data out is always '0', while incoming process data items 9–16 are discar­ded
BC346130363093EN-US-000101 / DPD00997 | 27Danfoss A/S © 2020.06
Communication cycle
Update interval
IO Data
Cyclic
x ms
Acyclic
Parameters, etc.
Low
Priority
High
Priority
Software
10ms
10ms
Update interval
5ms
Application
task
10-50ms
Process
Data
Application
task
50-500ms
Service
Data
Option Board Drive Control Board
e30bh626.10
VACON® OPTE3/E5 PROFIBUS DP
Control Interface and
User Guide
Communication
4.2.3 Normal Fieldbus Communication
The normal eldbus communication between option board and the AC drive application is shown in Illustration 2. In normal com­munication, both process data, and service data are transferred in succession at 5 ms interval.
Communication delay for process data can be calculated by summing all delays together:
t = t
IOdatacycle
+ t
updateinterval
+ 2 ⋅ t
communicationdelay
+ t
applicationcycle
Example: With eldbus cycle time of 4 ms and application cycle of 10 ms, the delay is:
t = 4ms + 10ms + 2 5 ms + 10ms = 34ms
NOTE!: This value does not include delays of the eldbus master, jitter in the process data cycle of the communication protocol or resending due to electronic interference.
Illustration 2: Normal Fieldbus Communication
4.2.4 Fast Fieldbus Communication
The fast mode decreases the communication delay between the PLC and the AC drive application signicantly by using two com­munication channels separately for process and service data. The process data interval is set to 1 ms, while other data is sent acycli­cally. When the fast mode is activated, the application can be synchronized to run with the communication cycle. The Fast commu­nication mode is shown in Illustration 3. This mode also includes the ability to transfer 16 process data items.
The communication delay for process data in fast communication mode is (when application task is synchronized with communica­tion):
t = t
IOdatacycle
Example: With eldbus cycle time of 1 ms, an application cycle of 1 ms the delay is:
t = 1ms + 1+1ms = 3ms
NOTE: This value does not include delays of the eldbus master, jitter in the process data cycle of the communication protocol or resending due to electronic interference.
+ t
updateinterval
+ t
applicationcycle
BC346130363093EN-US-000101 / DPD0099728 | Danfoss A/S © | 2020.06
Low priority
IO Data
Cyclic
x ms
Acyclic
Parameters, etc.
Low
Priority
High
Priority
Software
Option Board Drive Control Board
1ms
1ms
Application
task
1-50ms
Process
Data
Application
task
50-500ms
Service
Data
Acyclic
Update interval
Communi­cation cycle
e30bh627.10
Module name
Number
Abbreviation
Type
Description
Standard Telegram 1
7
ST1
Drive
(1)
See 4.3.5.3 Standard Telegrams.
VACON® Telegram 100
8
ST1+4PD
See 4.3.5.4 Vendor-Specic Telegrams.
VACON® Telegram 101
9
ST1+8PD
VACON® Telegram 138
11
ST1+12PD
VACON® Telegram 139
12
ST1+16PD
VACON® Telegram 140
16
GCW+16PD
Standard Telegram 20
10
ST20
See 4.3.5.3 Standard Telegrams.
Parameter-Process Data Type 1…6
1...6
PPO1…PPO6
See 4.3.6.4 PPO Types.
Standard Telegram 30
13
ST30
Safety
(2)
See 4.4.2 PROFIdrive on PROFIsafe.
VACON® OPTE3/E5 PROFIBUS DP
User Guide
Illustration 3: Fast Fieldbus Communication
Control Interface and
Communication
4.2.5 Fast Safety Fieldbus Communication
The fast safety mode uses the same communication methods as in "Fast mode" (Illustration 3), but also transfers safety "black chan­nel" data used to the advanced safety option board.
NOTE: This mode is automatically enabled, if an advanced safety option board is connected to slot D and the safety eldbus is acti- vated and is not available for setting. This mode is also automatically turned o when the advanced safety option board is removed.
4.2.6 Normal Extended Mode
The normal extended mode uses the same communication method as in "Fast mode", but reduces the communication cycle to 10 ms. This mode can be used in applications where 16 process data items are required but the lowest possible communication delay is not needed. It can also be used in these applications when the increased CPU load of Fast mode to VACON® NXP drives is undesira­ble.
NOTE! This mode can be automatically enabled in VACON® applications supporting 16 process data items.
4.3 Drive Control
4.3.1 PROFIBUS DP Modules
The OPTE3/E5 option board implements the following PROFIBUS DP modules:
Table 7: OPTE3/E5 Modules
BC346130363093EN-US-000101 / DPD00997 | 29Danfoss A/S © 2020.06
Module name
Number
Abbreviation
Type
Description
Standard Telegram 31
14
ST31
VACON® Telegram 58000
15
ST58000
Slot 1
Slot 2: Empty
Slot 2: ST1(+PD)
Slot 2: ST20
Slot 2:PPO1...6
Empty
-
allowed
allowed
allowed
ST1(+PD)
allowed
---
ST20
allowed
---
ST30, 31
-
allowed
--ST58000
-
allowed
--PPO1...6
allowed
---
VACON® OPTE3/E5 PROFIBUS DP
User Guide
1
Drive module rules:
Only 1 drive module is allowed.
Always congure 1 drive module.
2
Safety module rules:
If a safety module is congured, it must always be in slot 1.
Only 1 safety module is allowed.
ST20 and PPO1...6 is not allowed with safety modules.
In the Advanced Safety option board, select the same safety module as congured.
The supported module combinations are described in
Table 8: Supported Module Combinations
Table 8.
Control Interface and
Communication
An invalid module conguration causes a diagnostic conguration fault. As a result, the device returns to parameterization state and does not start the data exchange with PROFIBUS DP master.
If there is a safety module fault, a channel-related diagnosis (see 8.2.2 Channel-Related Diagnosis) is activated to notify the master of a problem with the safety module. The data exchange is started with PROFIBUS DP master.
4.3.2 Fieldbus Process Data
The process data items are directly sent unmodied from eldbus to the application. Therefore the process data mapping and usage must be congured in application. For the latest information, see the application-specic manual.
Fieldbus process data items can be used to write and read variables quickly and periodically to/from VACON® AC drives. Incoming process data can be used for multiple dierent purposes (for example, torque reference), and outgoing process data can be used for information about the state of the AC drive.
For fast access to any VACON® AC drive application ID over any eldbus, generic Process Data Out parameters are dened. The con­tent of the process data items is selected with the FB DataOut Selection parameters. Writing any application ID number to these parameters then maps the data value of that application ID to be sent in the corresponding Process Data Out variable.
The eldbus data-mapping (FB DataOut x Sel) aects the data of the corresponding Process Data Out variable (see Illustration 4). By writing ID value 1 to FB DataOut1 Selection (ID 852), the value of ID 1 (Output Frequency) is sent in Process Data Out 1. The value is always raw value in process data out, so for example, 16.43 Hz has value 1643. The scaling of the parameters can be checked from application manuals.
The status word and actual speed values cannot be changed. However, if a prole is used, the values sent by the eldbus protocol can dier. In Bypass mode, these values are given as is.
BC346130363093EN-US-000101 / DPD0099730 | Danfoss A/S © | 2020.06
Loading...
+ 84 hidden pages