Danfoss vacon nx liquid-cooled drives Application guide

VACON® NX

AC DRIVES

LIQUID-COOLED DRIVES

HEAT EXCHANGER

APPLICATION MANUAL

 

 

vacon • 1

INDEX

 

 

Document code: DPD01890A

 

 

Date edited: 5.8.2016

1.

General ..............................................................................................................................

2

2.

Control I/O .........................................................................................................................

3

3.

Parameter lists ..................................................................................................................

4

3.1

Monitoring values (Control keypad: menu M1)..........................................................................

4

3.2

Basic parameters (Control keypad: Menu M2 G2.1).............................................................

8

3.3

Input signals (Control keypad: Menu M2 G2.2) .....................................................................

9

3.4

Output signals (Control keypad: Menu M2 G2.3).................................................................

10

3.5

Drive control parameters (Control keypad: Menu M2 G2.4)...............................................

14

3.6

Prohibit frequency parameters (Control keypad: Menu M2 G2.5)......................................

14

3.7

Motor control parameters (Control keypad: Menu M2 G2.6)..............................................

15

3.8

Protections (Control keypad: Menu M2 G2.7)......................................................................

16

3.9

Autorestart parameters (Control keypad: Menu M2 G2.8) .................................................

17

3.10

PID control parameters (Control keypad: Menu M2 G2.9)..................................................

17

3.11

Flow control parameters (Control keypad: Menu M2 G2.10)..............................................

18

3.12

Fieldbus parameters (Control Keypad: Menu M2 G2.11).....................................................

19

3.13

Keypad control (Control keypad: Menu M3).............................................................................

20

3.14

System menu (Control keypad: M6).........................................................................................

20

3.15

Expander boards (Control keypad: Menu M7) .........................................................................

20

4.

Description of parameters ...............................................................................................

21

4.1

Keypad control parameters......................................................................................................

52

24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com

2 • vacon

General

heat exchanger application

1.GENERAL

This application is aimed to be used in the Vacon liquid-cooled AC drive inside the Heat exchanger unit.

The idea with the application is to maintain a constant flow of coolant through the heat exchanger and through the Vacon liquid-cooled drive.

The user sets a certain speed for the pump of the heat exchanger unit that produces a sufficient flow through the Vacon liquid-cooled drives to keep them cooled. This speed is NOT regulated but fixed by a parameter set value.

The Vacon AC drive also handles the temperature of the water in the heat exchanger unit by regulating the valve that handles the coolant intake to the heat exchanger element (from the customer's system). This regulation is based on the temperature of the water in the pipes between the outlet of the heat exchanger pump and the inlet of the cooling element of the Vacon liquid-cooled drive.

The actual value of the temperature for the regulation comes from a sensor called FSA11. This is a type of flow switch that measures both the temperature of the coolant and the flow in the pipes. If there is not enough flow in the pipe the sensor gives a signal that tells the drive to stop due to insufficient flow.

Vacon NX AC drives can be connected to the Profibus DP using a fieldbus board. The AC drive can then be controlled, monitored and programmed from the Host system. Profibus fieldbus board (OPT-C5) is normally included in the delivery of Vacon NX liquid-cooled drive Heat Exchanger Solution. The Profibus fieldbus board must be installed in slot E on the control board of the AC drive. For more information on the Profibus fieldbus board, see Vacon OPTC3/C5 Profibus Option Board User Manual.

The standard delivery also includes I/O boards OPT-A1 (placed in slot A), OPT-A2 (placed in slot B) and OPT-B5 (placed in slot C or D). The application, however, offers you more signals than the standard set of I/O boards allows you to connect. If you wish to use one additional analogue input signal and/or two additional analogue output signals, we recommend you to order Vacon I/O board OPT-B4 and place it in the last free board slot (C or D).

Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205

1

Danfoss vacon nx liquid-cooled drives Application guide

Control I/O

vacon • 3

 

 

 

2.CONTROL I/O

Reference potentiometer, 1…10 kΩ

2-wire

 

 

transmitter

 

 

Actual

 

value

I

(0)4…20 mA

+

mA

READY

RUN

220 VAC

OPT-A1

 

Terminal

 

 

 

Signal

 

Description

1

 

+10Vref

 

Reference output

 

Voltage for potentiometer, etc.

2

 

AI1+

 

Analogue input, voltage range

 

Pressure, outlet (pump)

 

 

 

 

0—10V DC

 

 

3

 

AI1-

 

I/O Ground

 

Ground for reference and controls

4

 

AI2+

 

Analogue input, current range

 

Temperature

5

 

AI2-

 

0—20mA

 

 

6

 

+24V

 

Control voltage output

 

Voltage for switches, etc. max 0.1 A

7

 

GND

 

I/O ground

 

Ground for reference and controls

8

 

DIN1

 

Start/Stop

 

Contact closed = start

 

 

 

 

Control place A (PID

 

 

 

 

 

 

controller)

 

 

9

 

DIN2

 

Flow fault

 

NO/NC programmable

10

 

DIN3

 

External fault

 

Contact open = External fault

 

 

 

 

(programmable)

 

 

11

 

CMA

 

Common for DIN 1—DIN 3

Connect to GND or +24V

12

 

+24V

 

Control voltage output

 

Voltage for switches (see #6)

13

 

GND

 

I/O ground

 

Ground for reference and controls

14

 

DIN4

 

Pump 1

 

Forced or single run

 

 

 

 

 

 

 

 

Combined with DIN1

15

 

DIN5

 

Pump 2

 

Forced or single run

 

 

 

 

 

 

 

 

Combined with DIN1

16

 

DIN6

 

Sequence, 2-pump system

 

Combined with DIN1

17

 

CMB

 

Common for DIN4—DIN6

Connect to GND or +24V

18

 

AO1+

 

Output frequency

 

Programmable

19

 

AO1-

 

Analogue output

 

Range 0—20 mA/RL, max. 500Ω

20

 

DO1

 

Digital output

 

Programmable

 

 

 

 

READY

 

Open collector, I≤50mA, U≤48 VDC

OPT-A2

 

 

 

 

 

 

21

 

RO1

 

 

 

Relay output 1

 

Programmable

 

 

 

 

 

22

 

RO1

 

 

 

RUN

 

 

23

 

RO1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

 

RO2

 

 

 

Relay output 2

 

Programmable

 

 

 

 

 

 

 

 

 

 

25

 

RO2

 

 

 

FAULT

 

 

26

 

RO2

 

 

 

 

 

 

 

 

 

 

 

 

 

OPT-B5

 

 

 

 

 

 

22

 

RO1

 

 

 

Relay output 1

 

 

23

 

RO1

 

 

 

COOLING OK

 

 

 

 

 

 

 

 

25

 

RO2

 

 

 

Relay output 2

 

 

26

 

RO2

 

 

 

PUMP 1

 

 

 

 

 

 

 

 

28

 

RO3

 

 

 

Relay output 3

 

 

29

 

RO3

 

 

 

PUMP 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1. Heat exchanger application I/O configuration example (with 2-wire transmitter).

 

Jumper block X3:

 

 

Jumper block X4:

 

CAN grounding

 

 

CAN termination

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connected to shield Not connected to shield

Terminated

Not terminated

= Factory default

24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com

2

4 • vacon

Parameter lists

3.PARAMETER LISTS

On the next pages you will find the lists of parameters within the respective parameter groups. The parameter descriptions are given on pages 21 to 52.

Column explanations:

Code

= Location indication on the keypad; Shows the operator the present param. number

Parameter = Name of parameter

Min

= Minimum value of parameter

Max

= Maximum value of parameter

Unit

= Unit of parameter value; Given if available

Default

= Value preset by factory

Cust

= Customer’s own setting

ID

= ID number of the parameter

 

 

= In parameter row: Use TTF method to program these parameters.

= On parameter code: Parameter value can only be changed after the FC has been stopped.

3.1Monitoring values (Control keypad: menu M1)

The monitoring values are the actual values of parameters and signals as well as statuses and measurements. Monitoring values cannot be edited.

See the product’s user manual for more information.

Code

Parameter

Unit

ID

Description

V1.1

Output frequency

Hz

1

Output frequency to motor

V1.2

Frequency reference

Hz

25

Frequency reference to motor control

V1.3

Motor speed

rpm

2

Motor speed in rpm

V1.4

Motor current

A

3

 

V1.5

Motor torque

%

4

Calculated shaft torque

V1.6

Motor power

%

5

Motor shaft power

V1.7

Motor voltage

V

6

 

V1.8

DC link voltage

V

7

 

V1.9

Unit temperature

°C

8

Heatsink temperature

V1.10

Analogue input 1

V

13

AI1

V1.11

Analogue input 2

mA

14

AI2

V1.12

Analogue input 3

 

1543

AI3

V1.13

Analog Output1

 

26

 

V1.14

DIN1, DIN2, DIN3

 

15

Digital input statuses

V1.15

DIN4, DIN5, DIN6

 

16

Digital input statuses

V1.16

RO1, RO2, RO3

 

1516

Relay output statuses

V1.17

RO4, RO5, RO6

 

1574

Relay output statuses

V1.18

Temp reference

°C

1500

 

V1.19

Actual temperature

°C

1501

 

V1.20

Temp error value

°C

1502

 

V1.21

PID output

%

23

In % of the max. output value

V1.22

Inlet pressure

bar

1511

PT11

Table 2. Monitoring values

Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205

3

Parameter lists

vacon • 5

 

 

 

3.1.1FB Monitor

Code

Parameter

Unit

ID

Description

V1.23.1

Motor Current

A

45

Motor current with one decimal

V1.23.2

Fault History

 

37

Last active fault code

V1.23.3

Status Word

 

43

Application status word

V1.23.4

Status Word 2

 

1800

Application status word 2

V1.23.5

Fault Word 1

 

1172

General fault word 1

V1.23.6

Fault Word 2

 

1173

General fault word

V1.23.7

Warning Word 1

 

1174

General warning word

V1.23.8

Fault Word 10

 

1202

Heat exchanger specific faults

V1.23.9

Warning Word 10

 

1269

Heat exchanger specific warnings

Table 3. Monitoring values (G1.24 FB Monitor)

3.1.1.1Status Word, ID43

 

Description

Comment

b0

 

 

b1

Ready

 

b2

Run

 

b3

Fault

 

b4

 

 

b5

 

 

b6

Run enable

 

b7

Warning

 

b8

 

 

b9

 

 

b10

RO4 status

 

b11

RO5 status

 

b12

Run request

 

b13

Motor regulator

 

active

 

 

 

b14

 

 

b15

Cooling OK

 

Table 4. Status Word

3.1.1.2Status Word 2, ID1800

Give this status word to Vacon personnel in case of problems with running the application.

24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com

3

6 • vacon

Parameter lists

3.1.1.3Fault Word 1, ID1172

 

Description

Comment

b0

Over current

F1

b1

Over voltage

F2

b2

Under voltage

F9

b3

Motor stalled

F15

b4

 

 

b5

Motor underload

F17

b6

Unit over

 

temperature

 

 

 

b7

Motor over

F16

temperature

 

 

 

b8

Input phase

F10

b9

 

 

b10

 

 

b11

Keypad or PC

F52

communication

 

 

 

b12

Fieldbus

F53

communication

 

 

 

b13

 

 

b14

Slot communication

F54

b15

4 mA

F50

Table 5. Fault Word 1

3.1.1.4Fault Word 2, ID1173

 

Description

Comment

b0

Output phase

F11

b6

External fault

F51

(fault or warning)

 

 

b9

IGBT

F41

Table 6. Fault Word 2

3.1.1.5Warning Word 1, ID1174

 

 

Description

Comment

b0

 

Motor stalled

F15

b1

 

Motor over

F16,

 

temperature

F29 (fault or warn)

 

 

b2

 

Motor underload

F17

b3

 

Input phase

F10

b4

 

Output phase

F11

b8

 

Unit temperature

 

b9

 

4 mA

F50

b15

 

Keypad

F52

 

communication

 

 

 

 

 

Table

7. Warning Word 1

 

Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205

3

Parameter lists

vacon • 7

 

 

 

3.1.1.6Fault Word 10, ID1202

 

Description

Comment

b0

 

 

b1

 

 

b2

 

 

b3

 

 

b4

 

 

b5

Over temperature

F85 (warning)

b6

 

 

b7

Inlet pressure low

F88

b8

Flow

F87

Table 8. Fault Word 10

3.1.1.7Warning Word 10, ID1269

 

 

Description

Comment

b0

 

 

 

b1

 

 

 

b2

 

 

 

b3

 

Inlet pressure low

F82

b4

 

Over temperature

F83

b5

 

Low temperature

F86

b6

 

 

 

 

Table

9. Warning Word 10

 

24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com

3

8 • vacon

Parameter lists

3.2Basic parameters (Control keypad: Menu M2 G2.1)

 

 

 

Code

Parameter

Min

Max

Unit

Default

Cust

ID

Note

 

 

 

 

 

 

P2.1.1

Min Frequency

0.00

Par. 2.1.2

Hz

25.00

 

101

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: If fmax > than the

 

 

 

P2.1.2

Max Frequency

Par. 2.1.1

320.00

Hz

50.00

 

102

motor synchronous speed,

 

 

 

 

check suitability for motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and drive system

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: If PID-controller is

 

 

 

P2.1.3

Acceleration time 1

0.1

3000.0

s

1.0

 

103

used, Acceleration time 2

 

 

 

 

(par. 2.4.3) is automatically

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

applied

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: If PID-controller is

 

 

 

P2.1.4

Deceleration time 1

0.1

3000.0

s

1.0

 

104

used, Deceleration time 2

 

 

 

 

(par. 2.4.4) is automatically

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

applied

 

 

 

P2.1.5

Current limit

0

2 x IH

A

IL

 

107

 

 

 

 

 

 

 

Nominal voltage of

180

690

V

400V

 

110

 

 

 

 

P2.1.6

 

 

 

 

 

 

 

 

 

the motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal frequency

30.00

320.00

Hz

50.00

 

111

Check the rating plate of the

 

 

 

P2.1.7

 

 

 

 

 

 

 

of the motor

 

 

 

 

 

 

motor

 

 

 

 

 

 

Nominal speed of

 

 

 

 

 

 

The default applies for a 4-

 

 

 

P2.1.8

 

 

300

20 000

rpm

1440

 

112

pole motor and a nominal

 

 

 

 

 

the motor

 

 

 

 

 

 

 

 

 

 

 

 

 

size AC drive.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal current of

0.4 x I

2 x I

A

I

 

113

Check the rating plate of the

 

 

 

P2.1.9

 

 

 

 

 

 

 

the motor

H

H

 

H

 

 

motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor cosϕ

 

 

 

 

 

 

Check the rating plate of the

 

 

P2.1.10

 

0.30

1.00

 

0.85

 

120

 

 

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.1.11

Start function

0

1

 

0

 

505

0=Ramp

 

 

 

 

1=Flying start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Coasting

 

 

P2.1.12

Stop function

0

3

 

0

 

506

1=Ramp

 

 

 

 

2=Ramp+Run enable coast

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3=Coast+Run enable ramp

 

 

P2.1.13

U/f optimization

0

1

 

0

 

109

0=Not used

 

 

 

 

1=Automatic torque boost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.1.14

I/O reference

0

1

 

0

 

117

0=Keypad reference

 

 

 

 

1=Fieldbus reference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.1.15

Preset speed1

0.00

Par. 2.1.2

Hz

10.00

 

105

 

 

 

P2.1.16

Automatic restart

0

1

 

0

 

731

0=Not used

 

 

 

 

1=Automatic restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.1.17

Parameter conceal

0

1

 

1

 

115

0=All parameters visible

 

 

 

 

1=Basic group (G2.1) visible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 10. Basic parameters G2.1

Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205

3

Parameter lists

vacon • 9

 

 

 

3.3Input signals (Control keypad: Menu M2 G2.2)

 

 

 

Code

Parameter

Min

Max

Unit

Default

Cust

ID

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Normally open

 

 

 

P2.2.1

 

 

DIN2 input

0

1

 

1

 

1590

 

 

 

 

 

 

 

1=Normally closed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Motor pot. UP(cc)

 

 

 

 

 

 

 

 

 

 

 

 

 

1=Reverse

 

 

 

 

 

 

 

 

 

 

 

 

 

2=External fault CC

 

 

 

 

 

 

 

 

 

 

 

 

 

3=External fault OC

 

 

 

 

 

 

 

 

 

 

 

 

 

4=Fault reset

 

 

 

 

 

 

 

 

 

 

 

 

 

5=Run enable

 

 

 

P2.2.2

 

 

DIN3 function

0

10

 

3

 

301

 

 

 

 

 

 

 

6=Preset speed 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7=DC brake cmnd

 

 

 

 

 

 

 

 

 

 

 

 

 

8=PID disable

 

 

 

 

 

 

 

 

 

 

 

 

 

9=PID disable, go to preset

 

 

 

 

 

 

 

 

 

 

 

 

 

speed

 

 

 

 

 

 

 

 

 

 

 

 

 

10=PID keypad ref 2

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Preset Speed 1

 

 

 

P2.2.3

 

 

DIN6 Function

0

1

 

0

 

1572

 

 

 

 

 

 

 

1=Fault Reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Signal range 0-20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

1=Signal range 4-20mA

 

 

 

P2.2.4

 

 

AI1 signal range

0

3

 

1

 

379

 

 

 

 

 

 

 

2=0-10V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3=2-10V

 

 

 

P2.2.5

 

 

AI1 supervision

0

1

 

0

 

1544

 

 

 

 

 

 

 

AI1 custom

0.00

P2.2.6

%

0.00

 

380

 

 

 

 

P2.2.6

 

 

 

 

 

 

 

 

 

minimum setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AI1 custom

 

 

 

 

 

 

 

 

 

 

P2.2.7

 

 

0.00

100.00

%

100.00

 

381

 

 

 

 

 

 

maximum setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Not inverted

 

 

 

P2.2.8

 

 

AI1 inversion

0

1

 

0

 

387

 

 

 

 

 

 

 

1=Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.2.9

 

 

AI1 filter time

0.00

10.00

s

1.00

 

378

0=No filtering

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Signal range 0-20mA

 

 

P2.2.10

 

AI2 signal range

0

1

 

1

 

390

 

 

 

 

 

1=Signal range 4-20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.2.11

AI2 supervision

0

1

 

1

 

1545

 

 

 

P2.2.12

AI2 custom

0.00

P2.2.6

%

0.00

 

391

 

 

 

minimum setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.2.13

AI2 custom

0.00

100.00

%

100.00

 

392

 

 

 

maximum setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.2.14

AI2 inversion

0

1

 

0

 

398

0=Not inverted

 

 

 

 

1=Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.2.15

AI2 filter time

0.00

10.00

s

1.00

 

389

0=No filtering

 

 

 

 

 

P2.2.16

AI3 signal selection

0

59

 

 

 

1558

TTF programming method

 

 

P2.2.17

AI3 signal range

0

1

 

1

 

1520

0=Signal range 0-20mA

 

 

 

 

1=Signal range 4-20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.2.18

AI3 supervision

0

1

 

0

 

1546

 

 

 

P2.2.19

AI3 custom

0.00

P2.2.18

%

0.00

 

1517

 

 

 

minimum setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.2.20

AI3 custom

P2.2.17

100.00

%

100.00

 

1518

 

 

 

maximum setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.2.21

AI3 inversion

0

1

 

0

 

1529

0=Not inverted

 

 

 

 

1=Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.2.22

AI3 filter time

0.00

10.00

s

1.00

 

1526

0=No filtering

 

 

 

 

 

 

Keypad control

 

 

 

 

 

 

Keypad freq ref selection:

 

 

P2.2.23

0

1

 

0

 

121

0=Reference from Keypad

 

 

reference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=FB reference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fieldbus frequency

 

 

P2.2.24

Fieldbus control

0

1

 

1

 

122

reference selection:

 

 

reference

 

 

0=Reference from Keypad

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=FB reference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 11. Input signals, G2.2

*Remember to place jumpers of block X2 accordingly. See the product's user manual.

24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com

3

10 • vacon

Parameter lists

3.4Output signals (Control keypad: Menu M2 G2.3)

3.4.1Analogue output 1

 

Code

Parameter

Min

Max

Unit

Default

Cust

ID

Note

 

 

 

 

 

 

 

 

 

 

0=Not used

 

 

 

 

 

 

 

 

 

1=Output freq. (0—fmax)

 

 

 

 

 

 

 

 

 

2=Freq. reference (0—fmax)

 

 

 

 

 

 

 

 

 

3=Motor speed (0—Motor

 

 

 

 

 

 

 

 

 

nominal speed)

 

 

 

 

 

 

 

 

 

4=Motor current (0—InMotor)

 

 

 

 

 

 

 

 

 

5=Motor torque (0—TnMotor)

 

 

Analogue output 1

0

13

 

13

 

307

6=Motor power (0—PnMotor)

 

P2.3.1.1

 

 

7=Motor voltage (0-UnMotor)

 

function

 

 

 

 

 

 

 

 

 

 

8=DC-link volt (0—1000V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9=PI controller temp ref

 

 

 

 

 

 

 

 

 

10=PI contr. act. temp.

 

 

 

 

 

 

 

 

 

11=PI contr. temperature

 

 

 

 

 

 

 

 

 

error value

 

 

 

 

 

 

 

 

 

12=PI controller output

 

 

 

 

 

 

 

 

 

13=Pressure from PT11,

 

 

 

 

 

 

 

 

 

pump inlet

 

P2.3.1.2

Analogue output 1

0.00

10.00

s

1.00

 

308

0=No filtering

 

 

filter time

 

 

 

 

 

 

 

 

P2.3.1.3

Analogue output 1

0

1

 

0

 

309

0=Not inverted

 

 

inversion

 

 

 

 

 

 

1=Inverted

 

P2.3.1.4

Analogue output 1

0

1

 

1

 

310

0=0 mA

 

 

minimum

 

 

 

 

 

 

1=4 mA

 

P2.3.1.5

Analogue output 1

10

1000

%

100

 

311

 

 

 

scale

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 12. Analogue output 1 signals

3.4.2Analogue output 2

 

Code

Parameter

Min

Max

Unit

Default

Cust

ID

 

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Not used

 

 

 

 

 

 

 

 

 

 

 

1=Output freq. (0—fmax)

 

 

 

 

 

 

 

 

 

 

 

2=Freq. reference (0—fmax)

 

 

 

 

 

 

 

 

 

 

 

3=Motor speed (0—Motor

 

 

 

 

 

 

 

 

 

 

 

nominal speed)

 

 

 

 

 

 

 

 

 

 

 

4=Motor current (0—InMotor)

 

 

 

 

 

 

 

 

 

 

 

5=Motor torque (0—TnMotor)

 

 

 

Analogue output 2

0

13

 

10

 

1530

 

6=Motor power (0—PnMotor)

 

 

P2.3.2.1

 

 

 

7=Motor voltage (0-UnMotor)

 

 

function

 

 

 

 

 

 

 

 

 

 

 

 

 

8=DC-link volt (0—1000V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9=PID controller ref. value

 

 

 

 

 

 

 

 

 

 

 

10=PI contr. act. temp

 

 

 

 

 

 

 

 

 

 

 

11=PI contr. temperature

 

 

 

 

 

 

 

 

 

 

 

error value

 

 

 

 

 

 

 

 

 

 

 

12=PI controller output

 

 

 

 

 

 

 

 

 

 

 

13=Pressure from PT11,

 

 

 

 

 

 

 

 

 

 

 

pump inlet

 

 

P2.3.2.2

Analogue output 2

0.00

10.00

s

1.00

 

1531

 

0=No filtering

 

 

 

filter time

 

 

 

 

 

 

 

 

 

 

P2.3.2.3

Analogue output 2

0

1

 

0

 

1532

 

0=Not inverted

 

 

inversion

 

 

 

1=Inverted

 

 

P2.3.2.4

Analogue output 2

0

1

 

0

 

1533

 

0=0 mA

 

 

minimum

 

 

 

1=4 mA

 

 

P2.3.2.5

Analogue output 2

10

1000

%

100

 

1534

 

 

 

 

 

scale

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 13. Analogue output 2 signals

Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205

3

Parameter lists

vacon • 11

 

 

 

3.4.3Analogue output 3

 

Code

Parameter

Min

Max

Unit

Default

Cust

ID

 

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Not used

 

 

 

 

 

 

 

 

 

 

 

1=Output freq. (0—fmax)

 

 

 

 

 

 

 

 

 

 

 

2=Freq. reference (0—fmax)

 

 

 

 

 

 

 

 

 

 

 

3=Motor speed (0—Motor

 

 

 

 

 

 

 

 

 

 

 

nominal speed)

 

 

 

 

 

 

 

 

 

 

 

4=Motor current (0—InMotor)

 

 

 

 

 

 

 

 

 

 

 

5=Motor torque (0—TnMotor)

 

 

 

Analogue output 3

0

13

 

4

 

1535

 

6=Motor power (0—PnMotor)

 

 

P2.3.3.1

 

 

 

7=Motor voltage (0-UnMotor)

 

 

function

 

 

 

 

 

 

 

 

 

 

 

 

 

8=DC-link volt (0—1000V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9=PID controller ref. value

 

 

 

 

 

 

 

 

 

 

 

10=PI contr. act. temp

 

 

 

 

 

 

 

 

 

 

 

11=PI contr. temperature

 

 

 

 

 

 

 

 

 

 

 

error value

 

 

 

 

 

 

 

 

 

 

 

12=PID controller output

 

 

 

 

 

 

 

 

 

 

 

13=Pressure from PT11,

 

 

 

 

 

 

 

 

 

 

 

pump inlet

 

 

P2.3.3.2

Analogue output 3

0.00

10.00

s

1.00

 

1536

 

0=No filtering

 

 

 

filter time

 

 

 

 

 

 

 

 

 

 

P2.3.3.3

Analogue output 3

0

1

 

0

 

1537

 

0=Not inverted

 

 

inversion

 

 

 

1=Inverted

 

 

P2.3.3.4

Analogue output 3

0

1

 

0

 

1538

 

0=0 mA

 

 

minimum

 

 

 

1=4 mA

 

 

P2.3.3.5

Analogue output 3

10

1000

%

100

 

1539

 

 

 

 

 

scale

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 14. Analogue output 3 signals

3.4.4Relay output 1

 

 

Code

Parameter

 

Min

 

Max

 

Unit

 

Default

 

Cust

 

ID

 

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.3.4.1

 

Relay output 1

 

 

 

 

 

 

 

 

 

B.1

 

 

 

 

1549

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2=Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3=Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4=Fault inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5=FC overheat warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6=Ext. fault or warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7=Ref. fault or warning

 

 

 

 

 

Relay output 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8=Warning

 

 

 

P2.3.4.2

0

 

18

 

 

 

2

 

 

 

313

 

 

9=Reversed

 

 

 

function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10=Preset speed 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11=At speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12=Mot. regulator active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13=OP freq. limit superv.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14=Control place: IO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15=Thermistor fault/warn.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16=Actual value supervision

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17=Cooling OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18=Alarm latched

 

 

 

P2.3.4.3

Relay output 1

0

 

1

 

 

 

0

 

 

 

1540

 

 

0=Not inverted

 

 

 

inversion

 

 

 

 

 

 

 

 

 

1=Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 15. Relay output 1 signals

24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com

3

12 • vacon

3.4.5Relay output 2

Parameter lists

 

 

Code

Parameter

 

Min

 

Max

 

Unit

 

Default

 

Cust

 

ID

 

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.3.5.1

 

Relay output 2

 

 

 

 

 

 

 

 

 

B.2

 

 

 

 

1550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1=Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2=Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3=Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4=Fault inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5=FC overheat warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6=Ext. fault or warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7=Ref. fault or warning

 

 

 

 

 

Relay output 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8=Warning

 

 

 

P2.3.5.2

0

 

18

 

 

 

3

 

 

 

1513

 

 

9=Reversed

 

 

 

function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10=Preset speed 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11=At speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12=Mot. regulator active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13=OP freq. limit superv.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14=Control place: IO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15=Thermistor fault/warn.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16=Actual value supervision

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17=Cooling OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18=Alarm latched

 

 

 

P2.3.5.3

Relay output 2

0

 

1

 

 

 

0

 

 

 

1541

 

 

0=Not inverted

 

 

 

inversion

 

 

 

 

 

 

 

 

 

1=Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 16. Relay output 2 signals

3.4.6Relay output 3

 

 

Code

Parameter

 

Min

 

Max

 

Unit

 

Default

 

Cust

 

ID

 

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.3.6.1

 

Relay output 3

 

 

 

 

 

 

 

 

 

D.1

 

 

 

 

1551

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.3.6.2

Relay output 3

0

 

3

 

 

 

1

 

 

 

1515

 

 

1=Cooling OK

 

 

 

function

 

 

 

 

 

 

 

 

 

2=Pump 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3=Pump 2

 

 

 

P2.3.6.3

Relay output 3

0

 

1

 

 

 

0

 

 

 

1542

 

 

0=Not inverted

 

 

 

inversion

 

 

 

 

 

 

 

 

 

1=Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 17. Relay output 3 signals

3.4.7Relay output 4

 

 

Code

Parameter

 

Min

 

Max

 

Unit

 

Default

 

Cust

 

ID

 

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.3.7.1

 

Relay output 4

 

 

 

 

 

 

 

 

 

D.2

 

 

 

 

1552

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.3.7.2

Relay output 4

0

 

3

 

 

 

2

 

 

 

1553

 

 

1=Cooling OK

 

 

 

function

 

 

 

 

 

 

 

 

 

2=Pump 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3=Pump 2

 

 

 

P2.3.7.3

Relay output 4

0

 

1

 

 

 

0

 

 

 

1554

 

 

0=Not inverted

 

 

 

inversion

 

 

 

 

 

 

 

 

 

1=Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 18. Relay output 4 signals

Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205

3

Parameter lists

vacon • 13

 

 

 

3.4.8Relay output 5

 

 

Code

Parameter

 

Min

 

Max

 

Unit

 

Default

 

Cust

 

ID

 

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.3.8.1

 

Relay output 5

 

 

 

 

 

 

 

 

 

D.3

 

 

 

 

1555

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.3.8.2

Relay output 5

0

 

3

 

 

 

3

 

 

 

1556

 

 

1=Cooling OK

 

 

 

function

 

 

 

 

 

 

 

 

 

2=Pump 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3=Pump 2

 

 

 

P2.3.8.3

Relay output 5

0

 

1

 

 

 

0

 

 

 

1557

 

 

0=Not inverted

 

 

 

inversion

 

 

 

 

 

 

 

 

 

1=Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 19. Relay output 5 signals

3.4.9Relay output 6

Code

Parameter

Min

Max

Unit

Default

Cust

ID

P2.3.9.1

Relay output 6

 

 

 

A.1

 

1573

signal selection

 

 

 

 

 

 

 

 

 

 

 

P2.3.9.2

Relay output 6

0

18

3

1567

function

 

 

 

 

 

P2.3.9.3

Relay output 6

0

1

0

1568

inversion

 

 

 

 

 

Table 20. Relay output 6 signals

Note

0=Not used 1=Ready 2=Run 3=Fault

4=Fault inverted

5=FC overheat warning 6=Ext. fault or warning 7=Ref. fault or warning 8=Warning 9=Reversed 10=Preset speed 1 11=At speed

12=Mot. regulator active 13=OP freq. limit superv.1 14=Control place: IO 15=Thermistor fault/warn. 16=Actual value supervision 17=Cooling OK

18=Alarm latched 0=Not inverted 1=Inverted

24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com

3

14 • vacon

Parameter lists

3.5Drive control parameters (Control keypad: Menu M2 G2.4)

 

 

Code

Parameter

Min

Max

Unit

Default

Cust

ID

Note

 

 

 

 

P2.4.1

Ramp 1 shape

0.0

10.0

s

0.0

 

500

0=Linear

 

 

 

>0=S-curve ramp time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Disabled

 

 

 

 

 

 

 

 

 

 

 

1=Used when running

 

 

P2.4.2

Brake chopper

0

3

 

0

 

504

2=External brake chopper

 

 

 

 

 

 

 

 

 

 

 

3=Used when stopped/

 

 

 

 

 

 

 

 

 

 

 

running

 

 

P2.4.3

DC braking current

0.4 x IH

2 x IH

A

IH

 

507

 

 

 

P2.4.4

DC braking time

0.00

600.00

s

0.00

 

508

0=DC brake is off at stop

 

 

at stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency to start

 

 

 

 

 

 

 

 

 

P2.4.5

 

DC braking during

0.10

10.00

Hz

1.50

 

515

 

 

 

 

 

ramp stop

 

 

 

 

 

 

 

 

 

P2.4.6

DC braking time

0.00

600.00

s

0.00

 

516

0=DC brake is off at start

 

 

at start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.4.7

Flux brake

0

1

 

0

 

520

0=Off

 

 

 

 

1=On

 

 

 

 

 

 

 

 

 

 

 

 

 

P2.4.8

Flux braking current

0.4 x IH

2 x IH

A

IH

 

519

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 21. Drive control parameters, G2.4

3.6Prohibit frequency parameters (Control keypad: Menu M2 G2.5)

 

Code

Parameter

Min

Max

Unit

Default

Cust

ID

Note

 

P2.5.1

Prohibit frequency

0.00

Par. 2.5.2

Hz

0.00

 

509

0=Not used

 

range 1 low limit

 

 

 

 

 

 

 

 

 

 

 

P2.5.2

Prohibit frequency

0.00

Par. 2.1.2

Hz

0.00

 

510

0=Not used

 

range 1 high limit

 

 

 

 

 

 

 

 

 

 

 

P2.5.3

Prohibit acc./dec.

0.1

10.0

Times

1.0

 

518

 

 

ramp

 

 

 

 

 

 

 

 

 

 

 

 

 

Output frequency

 

 

 

 

 

 

0=No limit

 

P2.5.4

0

2

 

0

 

315

1=Low limit supervision

 

limit 1 supervision

 

 

 

 

 

 

 

 

 

 

2=High limit supervision

 

 

 

 

 

 

 

 

 

 

 

Output frequency

 

 

 

 

 

 

 

 

P2.5.5

limit 1;

0.00

Par. 2.1.2

Hz

0.00

 

316

 

 

 

Supervised value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 22. Prohibit frequency parameters, G2.5

Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205

3

Parameter lists

vacon • 15

 

 

 

3.7Motor control parameters (Control keypad: Menu M2 G2.6)

 

 

 

Code

Parameter

Min

Max

Unit

Default

Cust

ID

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Frequency control

 

 

 

P2.6.1

 

 

Motor control mode

0

1

 

0

 

600

 

 

 

 

 

 

 

1=Speed control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0=Linear

 

 

 

 

 

 

 

 

 

 

 

 

 

1=Squared

 

 

 

P2.6.2

 

 

U/f ratio selection

0

3

 

0

 

108

 

 

 

 

 

 

 

2=Programmable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3=Linear with flux optim.

 

 

 

P2.6.3

 

 

Field weakening point

8.00

320.00

Hz

50.00

 

602

 

 

 

 

 

 

 

Voltage at field

 

 

 

 

 

 

 

 

 

 

P2.6.4

 

 

10.00

200.00

%

100.00

 

603

n% x Unmot

 

 

 

 

 

weakening point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U/f curve midpoint

 

par.

 

 

 

 

 

 

 

 

P2.6.5

 

 

0.00

Hz

50.00

 

604

 

 

 

 

 

 

frequency

P2.6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U/f curve midpoint

0.00

100.00

%

100.00

 

605

n% x Unmot

 

 

 

P2.6.6

 

 

 

Parameter max. value =

 

 

 

 

 

voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

par. 2.6.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output voltage at zero

0.00

40.00

%

Varies

 

606

n% x Unmot

 

 

 

P2.6.7

 

 

 

 

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switching frequency

1.0

Varies

kHz

Varies

 

601

See Table 31 for exact

 

 

 

P2.6.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

values

 

 

 

P2.6.9

Overvoltage controller

0

1

 

1

 

607

0=Not used

 

 

 

 

 

1=Used (no ramping)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Undervoltage

0

1

 

1

 

608

0=Not used

 

 

P2.6.10

 

 

 

 

 

 

controller

 

 

1=Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 23. Motor control parameters, G2.6

24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com

3

Loading...
+ 38 hidden pages