Danfoss vacon nxc/p User guide

vacon® nxc/p
ac drives
user manual
vacon • 3
Document ID: DPD00890C
Revision release date: 21.3.2018
1. SAFETY .............................................................................................................6
1.1 Warnings .............................................................................................................................6
1.2 Safety instructions ..............................................................................................................7
1.3 grounding and earth fault protection .................................................................................7
1.4 Running the motor ..............................................................................................................8
2. INTRODUCTION .................................................................................................9
2.1 Manufacturer's declaration of conformity........................................................................10
3. RECEIPT OF DELIVERY.................................................................................... 11
3.1 Type designation code.......................................................................................................11
3.1.1 NX type designation..............................................................................................11
3.2 NXC additional option codes .............................................................................................12
3.2.1 Cabling (C-group) .................................................................................................12
3.2.2 External Terminals (T-group)...............................................................................12
3.2.3 Input Device (I-group)...........................................................................................12
3.2.4 Main Circuit (M-group) .........................................................................................12
3.2.5 Output Filters (O-group).......................................................................................12
3.2.6 Protection Devices (P-group) ...............................................................................12
3.2.7 General (G-group).................................................................................................13
3.2.8 Auxiliary Equipment (A-group).............................................................................13
3.2.9 Door Mounted (D-group) ......................................................................................13
3.3 Storage ..............................................................................................................................14
3.4 Maintenance......................................................................................................................15
4. TECHNICAL DATA ........................................................................................... 16
4.1 Power ratings....................................................................................................................16
4.1.1 VACON® NXC – Mains voltage 380-500 V ...........................................................16
4.1.2 VACON® NXC low harmonic drives – Mains voltage 380-500 V..........................17
4.1.3 VACON® NXP/C 6 – Mains voltage 500-690 V .....................................................18
4.1.4 VACON® NXC low harmonic drives – Mains voltage 525-690 V..........................19
4.2 Technical data ...................................................................................................................21
5. MOUNTING ......................................................................................................24
5.1 Dimensions .......................................................................................................................24
5.2 Lifting the unit out of the transport packaging ................................................................26
5.3 Fixing the unit to the floor or to the wall ..........................................................................27
5.3.1 Fixing to the floor and to the wall.........................................................................27
5.3.2 Fixing to the floor only..........................................................................................28
5.4 AC choke connections.......................................................................................................29
5.5 Auxiliary voltage transformer tappings............................................................................30
5.6 Cooling ..............................................................................................................................31
5.6.1 Free space around the cabinet.............................................................................31
5.7 Power losses .....................................................................................................................33
6. CABLING AND CONNECTIONS......................................................................... 34
6.1 Understanding the power unit topology ...........................................................................34
6.2 Power connections............................................................................................................36
6.2.1 LCL filter wiring diagram of NXC low-harmonic drive ........................................36
6.2.2 Mains and motor cables .......................................................................................38
6.2.3 Thermal supervision of option +ODC ...................................................................46
6.2.4 DC supply and brake resistor cables ...................................................................46
6.2.5 Control cable ........................................................................................................46
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
vacon • 4
6.2.6 Cable and fuse sizes, 380-500 V units..................................................................47
6.2.7 Cable and fuse sizes, 500/525-690 V units...........................................................50
7. LOW HARMONIC CABINET DRIVE....................................................................53
7.1 NXC Low-Harmonic Cabinet Pre-Charging and MCCB Operating Instructions..............53
7.1.1 Manual operation (MAN).......................................................................................54
7.1.2 Remote operation (REM) ......................................................................................55
7.1.3 Automatic operation (AUTO).................................................................................56
7.1.4 Circuit-Breaker TRIP due to overload or short-circuit........................................57
8. INSTALLATION INSTRUCTIONS.......................................................................58
8.1 Cable installation and the UL standards ..........................................................................60
8.1.1 Cable and motor insulation checks......................................................................61
8.2 Control unit .......................................................................................................................62
8.2.1 Control connections..............................................................................................63
8.2.2 Control terminal signals.......................................................................................65
8.3 Connecting power supply and internal control cables.....................................................69
8.4 Optic fibre cables, signal listing and connections............................................................70
9. CONTROL KEYPAD ..........................................................................................71
9.1 Indications on the Keypad display ....................................................................................71
9.1.1 Drive status indications ........................................................................................71
9.1.2 Control place indications......................................................................................72
9.1.3 Status LEDs (green – green – red).......................................................................72
9.1.4 Text lines...............................................................................................................72
9.2 Keypad push-buttons........................................................................................................73
9.2.1 Button descriptions ..............................................................................................73
9.3 Navigation on the control keypad .....................................................................................74
9.3.1 Monitoring menu (M1) ..........................................................................................76
9.3.2 Parameter menu (M2) ..........................................................................................77
9.3.3 Keypad control menu (M3) ...................................................................................78
9.3.4 Active faults menu (M4)........................................................................................80
9.3.5 Fault history menu (M5) .......................................................................................83
9.3.6 System menu (M6)................................................................................................84
9.3.7 Expander board menu (M7) ..................................................................................99
9.4 Further keypad functions................................................................................................100
10. COMMISSIONING........................................................................................... 101
10.1 Safety...............................................................................................................................101
10.2 Commissioning of the AC drive.......................................................................................102
11. FAULT TRACING............................................................................................104
11.1 Fault time data record ....................................................................................................104
11.2 Fault codes......................................................................................................................106
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
vacon • 5
AT LEAST THE FOLLOWING STEPS OF THE START-UP QUICK GUIDE MUST BE PERFORMED DURING THE INSTALLATION AND COMMISSIONING.
IF ANY PROBLEMS OCCUR, PLEASE CONTACT YOUR LOCAL DISTRIBUTOR.
Start-up Quick Guide
1. Check that the delivery corresponds to your order, see Chapter 3.
2. Before taking any commissioning actions read carefully the safety instructions in Chapter 1.
3. Before the mechanical installation, check the minimum clearances around the unit (Chapter 5.6) and check the ambient conditions in Chapter 4.2.
4. Check the size of the motor cable, mains cable, mains fuses and check the cable connections, read Chapters 6.2.2 to 6.2.7.
5. Follow the installation instructions, see Chapter 7.
6. Control connections are explained in Chapter 8.2.1.
7. If the Start-Up wizard is active, select the language of the keypad, the application you
want to use and set the basic parameters asked by the wizard. Always confirm by pressing the
Enter button
. If the Start-Up wizard is not active, follow the instructions 7a
and 7b.
7a. Select the language of the keypad from the Menu M6, page 6.1. Instructions on using the keypad are given in Chapter 9.
7b. Select the application you want to use from the Menu M6, page 6.2. Instructions on using the keypad are given in Chapter 9.
8. All parameters have factory default values. In order to ensure proper operation, check the rating plate data for the values below and the corresponding parameters of parameter group G2.1.
• nominal voltage of the motor
• nominal frequency of the motor
• nominal speed of the motor
• nominal current of the motor
• motor cos
ϕ
Some options may require special parameter settings.
All parameters are explained in the VACON
®
All in One Application Manual.
9. Follow the commissioning instructions, see Chapter 10.
®
10. The VACON
NX_ AC drive is now ready for use.
Vacon Ltd is not responsible for the use of the frequency converters against the instructions.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
vacon • 6 SAFETY
9000.emf
9000.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf

1. SAFETY

ONLY A COMPETENT ELECTRICIAN MAY CARRY OUT THE ELECTRICAL INSTALLATION
= DANGEROUS VOLTAGE!
= WARNING or CAUTION

1.1 Warnings

®
The VACON
NX AC drive is meant for fixed installations only.
Do not perform any measurements when the AC drive is connected to the mains.
Do not perform any voltage withstand tests on any part of VACON
®
NX. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.
The AC drive has a large capacitive leakage current.
If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a main switch (EN 60204-1).
Only spare parts delivered by the manufacturer can be used.
The motor starts at power-up if the start command is 'ON'. Furthermore, the I/O functionalities (including start inputs) may change if parameters, applications or software are changed. Disconnect, therefore, the motor if an unexpected start can cause danger.
1
Prior to measurements on the motor or the motor cable, disconnect the motor cables from the AC drive.
Do not touch the components on the circuit boards. Static voltage discharge may damage the components.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
SAFETY vacon • 7
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf

1.2 Safety instructions

The components of the power unit of the AC drive and all cabinet mounted devices are potentially live when VACON
contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the DC-link/brake resistor terminals –/+ and all other mains devices are potentially live when VACON
even if the motor is not running. After disconnecting the AC drive from the mains, wait until the fan stops and the
indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes before doing any work on VACON
not even open the cabinet door before this time has expired. The control I/O-terminals are isolated from the mains potential. However, the relay
outputs and other I/O-terminals may have a dangerous control voltage present even
®
when VACON
NX is disconnected from mains.
Before connecting the AC drive to mains make sure that the VACON cable covers as well as the cabinet doors are closed.
®
NX is connected to mains potential. Coming into
®
NX is connected to mains,
®
NX connections. Do
®
NX front and
NOTE! If a fault protection relay is used , it must be of at least type B, preferably B+ ( according to EN 50178) , with a trip level of 300 mA. This is for fire protection, not for touch protection in grounded systems.

1.3 grounding and earth fault protection

The VACON® NX AC drive must always be earthed with an grounding conductor connected to the PE bar in the lower front side of the cabinet.
The earth fault protection inside the AC drive protects only the converter itself against earth faults in the motor or the motor cable. It is not intended for personal safety.
NOTE! Due to the high capacitive currents present in the AC drive, fault current protective switches may not function properly.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1
vacon • 8 SAFETY
9000.emf
13006.emf
9001.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf

1.4 Running the motor

Warning symbols
For your own safety, please pay special attention to the instructions marked with the following symbols:
= Dangerous voltage
= General warning
= Hot surface – Risk of burn
MOTOR RUN CHECK LIST
Before starting the motor, check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.
Set the maximum motor speed (frequency) according to the motor and the machine connected to it.
Before reversing the motor make sure that this can be done safely.
Make sure that no power correction capacitors are connected to the motor cable.
Make sure that the motor terminals are not connected to mains potential.
1
NOTE! You can download the English and French product manuals with applicable safety, warning and caution information from
http://drives.danfoss.com/knowledge-center/technical-documentation/.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit contenant l’ensemble des informations de sécurité, avertissements et mises en garde applicables sur le site http://drives.danfoss.com/knowledge-center/technical-documentation/ .
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
INTRODUCTION vacon • 9
13006.emf

2. INTRODUCTION

The VACON® NXC is a product range of free standing enclosed AC drives for the high power range. The NXC is a modular product intended for use in all applications where reliability and high availability is appreciated.
This manual gives the basic information required to successfully perform installation and basic commissioning. Due to the high amount of options available, not all possible variations are described in this manual. For more information, refer to delivery-specific documentation. This manual assumes good competence in installation and commissioning skills.
In the All in One Application Manual you will find information about the different applications included in the All in One Application Package. Should these applications not meet the requirements of your process please contact the manufacturer for information on special applications.
Information on the installation of the drive in a cabinet can be found in manuals 'NXP AC drives, IP00 Module Installation, Frames FR10 to FR14 as well as Frequency Inverter and Active Front End manuals.
This manual is available in both paper and electronic editions. We recommend you to use the electronic version if possible. If you have the electronic version at your disposal you will be able to benefit from the following features:
The manual contains several links and cross-references to other locations in the manual which makes it easier for the reader to move around in the manual, to check and find things faster.
The manual also contains hyperlinks to web pages. To visit these web pages through the links you must have an internet browser installed on your computer.
In case you are in doubt about your ability to perform installation or commissioning, do not proceed. Contact your local distributor for advice.
For the NXC low-harmonic drive also see the AFE application manual.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
2
vacon • 10 INTRODUCTION

2.1 Manufacturer's declaration of conformity

Below you can find the Manufacturer's Declarations of Conformity assuring the compliance of VACON
®
NXP/C AC drives with the EMC-directives.
2
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
RECEIPT OF DELIVERY vacon • 11
NX C 0 0 00
A 2 L 0 SSG A1A20000C3
+
IFD
5
Product range: NXC = cabinet
Nominal current (lowoverload)
e.g. 0460 =460A etc.
Nominal mains voltage(3-phase):
5 = 380–500Vac, 6 = 525–690Vac
Enclosureclass:
2=IP21/Nema1(cabinet-mounted), 5 = IP54/Nema 12(cabinet-mounted)
Control keypad:
A = standard (alpha-numeric) B = no local control keypad F = dummy keypad G = graphic display
EMC emission level EN61800-3:
L = 2nd environment T=ForITnetworks
Brake chop per
0 =No brake chopper, 1= Integrated brake chopper
Control
F=standardFR9andNXC N = standard IP00 FR10 and NXC with IP54 control unit enclosure G = as Fbut varnished boards O = asN but varnished boards
Cooling
S = standard air-cooled
Supply
S=6-pulse T=12-pulse R = Regenerative low-harmonic (AFE)
Opti on bo ards; each slot is rep resen ted by two ch aracte rs w here :
Ax = basic I/ O board, Bx = expa nder I/O bo ard, Cx = fieldb us bo ard, Dx = sp ecial bo
ard
NXC options
7001.emf

3. RECEIPT OF DELIVERY

VACON® NX AC drives have undergone scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete (compare the type designation of the product to the code below).
Should the drive have been damaged during the shipping, please contact primarily the cargo insurance company or the carrier.
If the delivery does not correspond to your order, contact the supplier immediately. In the small plastic bag included in the delivery you will find a silver Drive modified sticker. The
purpose of the sticker is to notify the service personnel about the modifications made in the AC drive. Attach the sticker to the equipment to avoid losing it. Should the AC drive be later modified (option board added, IP or EMC protection level changed), mark the change in the sticker.

3.1 Type designation code

3.1.1 NX type designation

Figure 1. VACON® NXC type designation code
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3
vacon • 12 RECEIPT OF DELIVERY

3.2 NXC additional option codes

The NXC enclosure solution contains additional pre-engineered hardware options. These options are appended to the basic type code by using “+” codes. The most common NXC options are listed below:

3.2.1 Cabling (C-group)

+CIT Input (mains) cabling from TOP
+COT Output motor cabling from TOP

3.2.2 External Terminals (T-group)

+TIO I/O+ aux terminals (35 pcs) X2 +TID I/O+ double aux terminals (70 pcs) Double-decker terminals X2
+TUP Separate terminals for 230 VAC CV X1

3.2.3 Input Device (I-group)

+ILS Load switch +IFD Fused disconnecting switch With aR Fuses +ICO Contactor +IFU Fused With aR Fuses
+ICB Moulded-case or air circuit breaker

3.2.4 Main Circuit (M-group)

+MDC DC-bus bar connection Req. BSF converter hardware

3.2.5 Output Filters (O-group)

+OCM Common mode choke Ferrite
+OCH Common mode choke
+ODU dU/dt
+OSI Sine

3.2.6 Protection Devices (P-group)

Nanoperm
®
3
+PTR Thermistor relay PTB certified +PES Em. stop (cat 0) DI3
+PED Em. stop (cat 1) DI6 (sys.appl.)
+PAP Arc protection
+PIF Insulation fault sensor For IT-networks
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
RECEIPT OF DELIVERY vacon • 13

3.2.7 General (G-group)

+G40 400 empty cabinet +G60 600 empty cabinet
+G80 800 empty cabinet +GPL 100 mm base/plinth For 400 mm, 600 mm or 800 mm +GPH 200 mm base/plinth For 400 mm, 600 mm or 800 mm

3.2.8 Auxiliary Equipment (A-group)

+AMF Motor fan control +AMH Motor heater feeder +AMB Mechanical brake control
+ACH Cabinet heater
+ACL Cabinet light +ACR Control relay
+AAI Analogue signal isolator AI1, AO1, AI2
+AAC Aux. contact (input device) Wired to DI3
+AAA Aux. contact (control voltage devices) Chained to DI3
+ATx Aux. Transformer 400-690/230 VAC x = 1 (200 VA)
+ADC Power supply 24 VDC 10 A
+ACS 230 VAC customer socket With 30 mA leak current prot.

3.2.9 Door Mounted (D-group)

+DLV Pilot light (Control voltage on) 230 VAC +DLD Pilot light (DO1) 24 VDC, DO1
+DLF Pilot light (FLT) 230 VAC, RO2 +DLR Pilot light (RUN) 230 VAC, RO1 +DAR Potentiometer for reference AI1 +DCO MC operation switch 0-1-START
x = 2 (750 VA) x = 3 (2500 VA) x = 4 (4000 VA)
+DRO Local / Remote op. switch Loc/Rem wired to DI6 +DEP Emergency stop push-button
+DRP Reset push-button DI6 +DAM Analogue meter (AO1) 48 mm, std scale 0-100% +DCM Analogue meter + current
transformer
+DVM Analogue vltg meter with sel.switch 0, L1-L2, L2-L3, L3-L1
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
48 mm, std scale 0-600 A
3
vacon • 14 RECEIPT OF DELIVERY

3.3 Storage

If the AC drive is to be kept in store before use make sure that the ambient conditions are acceptable:
Storing temperature –40…+70 Relative humidity <95%, no condensation
The environment should also be free from dust. If there is dust in the air the AC drive should be well protected to make sure dust does not get into the AC drive.
If the AC drive is to be stored during longer periods the power should be connected to the AC drive once in 24 months and kept on for at least 2 hours. If the storage time exceeds 24 months the electrolytic DC capacitors need to be charged with caution. Therefore, such a long storage time is not recommended.
If the storing time is much longer than 24 months, the recharging of the capacitors has to be carried out so that the possible high leakage current through the capacitors is limited. The best alternative is to use a DC-power supply with adjustable current limit. The current limit has to be set for example to 300…500mA and the DC-power supply has to be connected to the B+/B- terminals (DC supply terminals).
DC-voltage must be adjusted to nominal DC-voltage level of the unit (1.35*Un AC) and supplied at least for 1 hour.
If DC-voltage is not available and the unit has been stored de-energized much longer than 1 year consult factory before connecting power.
°C
3
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
RECEIPT OF DELIVERY vacon • 15

3.4 Maintenance

In normal conditions, VACON® NX AC drives are maintenance-free. However, we recommend to keep the AC drive clean, e.g. by cleaning the heatsink with compressed air whenever necessary.
In IP54 units, the air filters in the door and in the roof should be cleaned or replaced regularly. We also recommended to follow proactive maintenance schedule to ensure the highest possible
utilization rate of the cabinet drive.
Table 1. Proactive maintenance schedule
Maintenance interval Maintenance action
12 months (if unit stored) Reform capacitors (see separate instruction)
6-24 months
(depending on environment)
5-7 years Change cooling fans:
•Check I/O terminals
Check tightness of mains connection
Clean cooling tunnel
Check operation of cooling fan, check for corrosion on terminals, busbars and other surfaces
Check door and roof filters
-main fan
- fan of the LCL filter
5-10 years Change DC bus capacitors if DC voltage ripple is high
.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3
vacon • 16 TECHNICAL DATA

4. TECHNICAL DATA

4.1 Power ratings

4.1.1 VACON® NXC – Mains voltage 380-500 V

High overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IH)
Low overload = Max current I
Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IL)
, 2 sec/20 sec, Rated overload current, 1 min/10 min
S
Table 2. Power ratings and dimensions of VACON
®
NX 6- and 12-pulse drives supply voltage 380-500V
Mains voltage 380-500 V, 50/60 Hz, 3~
Loadability Motor shaft power
Low High 400V supply 500V supply
AC drive
type
NXC0261 5 261 287 205 308 349 132 110 160 132 FR9 606x2275x605/371 NXC0300 5 300 330 245 368 444 160 132 200 160 FR9 606x2275x605/371 NXC0385 5 385 424 300 450 540 200 160 250 200 FR10 606x2275x605/371 NXC0460 5 460 506 385 578 693 250 200 315 250 FR10 606x2275x605/403 NXC0520 5 520 572 460 690 828 250 250 355 315 FR10 606x2275x605/403 NXC0590 5 590 649 520 780 936 315 250 400 355 FR11 806x2275x605/577 NXC0650 5 650 715 590 885 1062 355 315 450 400 FR11 806x2275x605/577 NXC0730 5 730 803 650 975 1170 400 355 500 450 FR11 806x2275x605/577 NXC0820 5 820 902 730 1095 1314 450 400 560 500 FR12 1206x2275x605/810 NXC0920 5 920 1012 820 1230 1476 500 450 630 560 FR12 1206x2275x605/810 NXC1030 5 1030 1133 920 1380 1656 560 500 710 630 FR12 1206x2275x605/810 NXC1150 5 1150 1265 1030 1545 1620 630 560 800 710 FR13 1406X2275X605/1000
NXC1300 5 1300 1430 1150 1725 2079 710 630 900 800 FR13
NXC1450 5 1450 1595 1300 1950 2484 800 710 1000 900 FR13
NXC1770 5 1770 1947 1600 2400 2880 1000 900 1200 1100 FR14 2806X2275X605/2440 NXC2150 5 2150 2365 1940 2910 3492 1200 1100 1500 1300 FR14 2806X2275X605/2500
Rated
contin.
current
(A)
I
L
Rated
overload
current
(A)
Rated
contin.
current
I
H
(A)
Rated
over-
load
current
(A)
Max
current
I
S
Low
over-
load
P(kW)
High
over-
load
P(kW)
Low
over-
load
P(kW)
High
over-
load
P(kW)
Enclo-
sure
Dimensions and weight*
WxHxD/kg
6-p: 1606X2275X605/1150
12-p: 2006X2275X605/1150
6-p: 1606X2275X605/1150
12-p: 2006X2275X605/1150
4
NOTE! The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to or less than the factory default (automatic thermal management).
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
TECHNICAL DATA vacon • 17
*The dimensions indicated are for the basic 6-pulse IP21 version of the AC drive cabinet. Some options may increase the width, height or weight of the cabinet. See the delivery specific documentation for more details.
4.1.2 VACON
®
NXC low harmonic drives – Mains voltage 380-500 V
High overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IH)
Low overload = Max current I
, 2 sec/20 sec, Rated overload current, 1 min/10 min
S
Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IL)
Table 3. Power ratings and dimensions of VACON
®
low-harmonic drives, supply voltage 380-
500V
Mains voltage 380-500 V, 50/60 Hz, 3~
Loadability Motor shaft power
AC drive
type
current IL
NXC0261 5 261 287 205 308 349 132 110 AF9+AF9 1006x2275x605/680
NXC0300 5 300 330 245 368 444 160 132 AF9+AF9 1006x2275x605/680
NXC0385 5 385 424 300 450 540 200 160 AF10+AF10 1006x2275x605/700
NXC0460 5 460 506 385 578 693 250 200 AF10+AF10 1006x2275x605/700
NXC0520 5 520 572 460 690 828 250 250 AF10+AF10 1006x2275x605/700
NXC0650 5 650 715 590 885 1062 355 315 2xAF10+AF12 2006x2275x605/1400
NXC0730 5 730 803 650 975 1170 400 355 2xAF10+AF12 2006x2275x605/1400
NXC0820 5 820 902 730 1095 1314 450 400 2xAF10+AF12 2006x2275x605/1400
NXC0920 5 920 1012 820 1230 1476 500 450 2xAF10+AF12 2006x2275x605/1400
NXC1030 5 1030 1133 920 1380 1656 560 500 2xAF10+AF12 2006x2275x605/1400
NXC1150 5 1150 1265 1030 1545 1620 630 560 AF13+AF13 2206X2275X605/1950
NXC1300 5 1300 1430 1150 1725 2079 710 630 AF13+AF13 2206X2275X605/1950
NXC1450 5 1450 1595 1300 1950 2484 800 710 AF13+AF13 2206X2275X605/1950
NXC1770 5 1770 1947 1600 2400 2880 1000 900 2xAF13+AF14 4406X2275X605/3900
NXC2150 5 2150 2365 1940 2910 3492 1200 1100 2xAF13+AF14 4406X2275X605/3900
NXC2700 5 2700 2970 2300 3278 3933 1500 1200 2xAF13+AF14 4406X2275X605/3900
Low High 400V supply
Rated
contin.
(A)
Rated
overload
current
(A)
Rated
contin.
current
(A)
I
H
Rated
overload
current
(A)
Max
current
I
S
Low
over-
load
P(kW)
High
over-
load
P(kW)
Enclosure
Dimensions and
weight*
WxHxD/kg
NOTE! The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to or less than the factory default (automatic thermal management).
*The dimensions indicated are for the basic low-harmonic IP21 version of the AC drive cabinet. Some options increase the width, height or weight of the cabinet. Check the delivery specific documentation for more details.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
vacon • 18 TECHNICAL DATA

4.1.3 VACON® NXP/C 6 – Mains voltage 500-690 V

High overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IH)
Low overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IL)
Table 4. Power ratings and dimensions of VACON
®
NX 6- and 12-pulse drives, supply voltage 500—
690V
Mains voltage 500-690 V, 50/60 Hz, 3~
Loadability Motor shaft power
Low High 690V supply 575V supply
50%
over-
load
current
(A)
Max
current
I
S
Low
over-
load
P(kW)
High
over-
load
P(kW)
Low
over-
load
P(hp)
AC drive type
NXC0125 6 125 138 100 150 200 110 90 125 100 FR9 606x2275x605/371 NXC0144 6 144 158 125 188 213 132 110 150 125 FR9 606x2275x605/371 NXC0170 6 170 187 144 216 245 160 132 150 150 FR9 606x2275x605/371 NXC0208 6 208 229 170 255 289 200 160 200 150 FR9 606x2275x605/371 NXC0261 6 261 287 208 312 375 250 200 250 200 FR10 606x2275x605/341 NXC0325 6 325 358 261 392 470 315 250 300 250 FR10 606x2275x605/371 NXC0385 6 385 424 325 488 585 355 315 400 300 FR10 606x2275x605/371
NXC0416 6** 416 416 325 488 585 400 315 450 300 FR10 606x2275x605/371
NXC0460 6 460 506 385 578 693 450 355 450 400 FR11 806x2275x605/524 NXC0502 6 502 552 460 690 828 500 450 500 450 FR11 806x2275x605/524
NXC0590 6** 590 649 502 753 904 560 500 600 500 FR11 806x2275x605/577
NXC0650 6 650 715 590 885 1062 630 560 650 600 FR12 1206x2275x605/745 NXC0750 6 750 825 650 975 1170 710 630 800 650 FR12 1206x2275x605/745
NXC0820 6** 820 902 650 975 1170 800 630 750 650 FR12 1206x2275x605/745
NXC0920 6 920 1012 820 1230 1410 900 800 900 800 FR13 1406x2275x605/1000 NXC1030 6 1030 1130 920 1380 1755 1000 900 1000 900 FR13 1406x2275x605/1000
NXC1180 6** 1180 1298 1030 1463 1755 1150 1000 1100 1000 FR13 1406x2275x605/1000
NXC1500 6 1500 1650 1300 1950 2340 1500 1300 1500 1350 FR14 2406X2275X605/2350 NXC1900 6 1900 2090 1500 2250 2700 1800 1500 2000 1500 FR14 2806X2275X605/2440
NXC2250 6** 2250 2475 1900 2782 3335 2000 1800 2300 2000 FR14 2806X2275X605/2500
Rated
contin.
current I
(A)
overloa
L
current
Rated
d
(A)
Rated
contin.
current
(A)
I
H
High
over-
load
P(hp)
Enclo-
sure
Dimensions and
weight*
WxHxD/kg
4
NOTE! The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to or less than the factory default (automatic thermal management).
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
TECHNICAL DATA vacon • 19
*The dimensions indicated are for the basic 6-pulse IP21 version of the AC drive cabinet. Some options increase the width, height or weight of the cabinet. Check the delivery specific documentation for more details.
** Maximum ambient temperature +35 °C.
4.1.4 VACON
®
NXC low harmonic drives – Mains voltage 525-690 V
High overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IH)
Low overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output current (IL)
Table 5. Power ratings and dimensions of VACON
®
low-harmonic drives, supply voltage 525-690V
Mains voltage 525-690 V, 50/60 Hz, 3~
Loadability Motor shaft power
Low High 690V supply
AC drive type
NXC0125 6 125 138 100 150 200 110 90 AF9+AF9 1006x2275x605/680 NXC0144 6 144 158 125 188 213 132 110 AF9+AF9 1006x2275x605/680 NXC0170 6 170 187 144 216 245 160 132 AF9+AF9 1006x2275x605/680 NXC0208 6 208 229 170 255 289 200 160 AF9+AF9 1006x2275x605/680 NXC0261 6 261 287 208 312 375 250 200 AF10+AF10 1006x2275x605/700 NXC0325 6 325 358 261 392 470 315 250 AF10+AF10 1006x2275x605/700 NXC0385 6 385 424 325 488 585 355 315 AF10+AF10 1006x2275x605/700
NXC0416 6** 416 416 325 488 585 400 315 AF10+AF10 1006x2275x605/700
NXC0460 6 460 506 385 578 693 450 355 2xAF10+AF12 2006x2275x605/1400 NXC0502 6 502 552 460 690 828 500 450 2xAF10+AF12 2006x2275x605/1400
NXC0590 6** 590 649 502 753 904 560 500 2xAF10+AF12 2006x2275x605/1400
NXC0650 6 650 715 590 885 1062 630 560 2xAF10+AF12 2006x2275x605/1400 NXC0750 6 750 825 650 975 1170 710 630 2xAF10+AF12 2006x2275x605/1400
NXC0820 6** 820 902 650 975 1170 750 650 2xAF10+AF12 2006x2275x605/1400
NXC0920 6 920 1012 820 1230 1476 900 800 AF13+AF13 2206x2275x605/1950 NXC1030 6 1030 1133 920 1380 1656 1000 900 AF13+AF13 2206x2275x605/1950
NXC1180 6** 1180 1298 1030 1463 1755 1150 1000 AF13+AF13 2206x2275x605/1950
NXC1500 6 1500 1650 1300 1950 2340 1500 1300 2xAF13+AF14 4406X2275X605/3900 NXC1900 6 1900 2090 1500 2250 2700 1800 1500 2xAF13+AF14 4406X2275X605/3900
NXC2250 6** 2250 2475 1900 2782 3335 2000 1800 2xAF13+AF14 4406X2275X605/3900
Rated
contin.
current I
(A)
Rated
overload
L
current (A)
Rated
contin.
current
(A)
I
H
50%
overload
current (A)
Max
current
I
S
Low
overload
P(kW)
High
overload
P(kW)
Enclosure
Dimensions and
weight*
WxHxD/kg
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
vacon • 20 TECHNICAL DATA
NOTE! The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to or less than the factory default (automatic thermal management).
*The dimensions indicated are for the basic low-harmonic IP21 version of the AC drive cabinet. Some options increase the width, height or weight of the cabinet. Check the delivery specific documentation for more details.
** Maximum ambient temperature +35 °C.
4
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
TECHNICAL DATA vacon • 21

4.2 Technical data

Table 6. Technical data
Mains connection
Motor connection
Input voltage U
Input frequency 45…66 Hz Connection to mains Once per minute or less (normal case); Supply grounding system TN-S, TN-C, TN-CS, TT or IT Short circuit ratings Defined by ratings of installed fuses or circuit
Output voltage 0—U Continuous output cur-
rent
Overloadability High: 1.5 x IH (1 min/10 min), Low: 1.1 x IL (1 min/10 min) Starting current IS for 2 s every 20 s
Output frequency 0…320 Hz; (higher with special SW) Control performance Open Loop Vector Control (5-150% of base
in
380…500 V; 500…690 V; –10%…+10%
380...500 V;525...690 V; –10%…+10% (low harmonic drives)
breaker(s). Max permitted values 50 kA at 380...500 VAC, 40 kA at 525...690 VAC. Refer to cabinet specific documentation for more details
in
Ambient temperature max. +40 °C (up to +50 °C with current derating 1,5% per 1°). See Table 2 and Table 4.
speed): speed control 0.5%, dynamic 0.3%sec, torque lin. <2%, torque rise time ~5 ms
Closed Loop Vector Control (entire speed range): speed control 0.01%, dynamic 0.2%sec, torque lin. <2%, torque rise time ~2 ms
Control
characteristics
Switching frequency NX_5:
NX_6:
Frequency reference Analogue input Panel reference
Field weakening point 8…320 Hz Acceleration time 0.1…3000 sec Deceleration time 0.1…3000 sec Braking DC brake: 30% * TN (without brake option); flux
Resolution 0.1% (10-bit), accuracy ±1% Resolution 0.01 Hz
braking
1…6 kHz; Factory default 3.6 kHz * 1…6 kHz; Factory default 1.5 kHz *
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
vacon • 22 TECHNICAL DATA
Table 6. Technical data
Ambient conditions
EMC (at default
settings)
Ambient operating tem­perature
Storage temperature –40 °C…+70 °C Relative humidity 0 to 95% RH, non-condensing, non-corrosive,
Air quality:
- chemical vapours
- mechanical particles
Cabinet surface treat­ment
Altitude 100% load capacity (no derating) up to 1,000 m
Vibration EN50178/EN60068-2-6
Shock EN50178, EN60068-2-27
Enclosure class IP21/NEMA1 standard in entire kW/HP range
Immunity Fulfils all EMC immunity requirements Emissions EMC level L: EN 61800-3 (2004), Category C3
–10 °C (no frost)…+40 ºC
no dripping water
IEC 721-3-3, unit in operation, class 3C2 IEC 721-3-3, unit in operation, class 3S2
Nanoceramic pretreatment. Anodic dipcoat-priming and textured powder-coating.
1-% derating for each 100m above 1000; max. 3000 m (690 V max 2000 m).
Displacement amplitude 0.25 mm (peak) at 5…31 Hz Max acceleration 1 G at 31…150 Hz Use anti-vibration mountings under the drive if extra vibration resistance is required.
UPS Drop Test (for applicable UPS weights) Storage and shipping: max 15 G, 11 ms (in package)
IP54/NEMA12 option in entire kW/HP range Pollution degree PD2
EMC level T: Low earth-current solution for IT­networks, EN 61800-3 (2004), Category C4 (can be modified from level L units.
Safety
EN 50178 (1997), EN 60204-1 (1996), EN 60950 (2000, 3rd edition) (as relevant), CE, UL, CUL, EN 61800-5; (see unit nameplate for more detailed approvals). IEC 60664-1 and UL840 in overvoltage category III.
4
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
TECHNICAL DATA vacon • 23
Table 6. Technical data
Analogue input voltage 0…+10 V, Ri = 200 kW, (–10 V…+10 V joystick control)
Resolution 0.1%, accuracy ±1%
Analogue input current 0(4)…20 mA, Ri = 250 W differential; Resolution
0.1%, accuracy ±1% Digital inputs (6) Positive or negative logic; 18…30 VDC Auxiliary voltage +24 V, ±15%, max volt. ripple < 100 mVrms; max. 250
mA Dimensioning: max. 1000 mA/control box
Control connections (factory default I/O)
Output reference voltage +10 V, ±3%, max. load 10 mA Analogue output 0(4)…20 mA; RL max. 500 W; Resolution 10 bit;
Accuracy ±2% Digital outputs Open collector output, 50 mA/48 V Relay outputs 2 programmable change-over relay outputs
Switching capacity: 24 VDC/8 A, 250 VAC/8 A,
125 VDC/0.4 A
Min. switching load: 5 V/10 mA
Protections
Thermistor input (OPT­A3)
Overvoltage trip limit Undervoltage trip limit
Earth fault protection In case of earth fault in motor or motor cable, only
Mains supervision Trips if any of the input phases is missing Motor phase supervision Trips if any of the output phases is missing Overcurrent protection Yes Unit overtemperature
protection Motor overload
protection
Motor stall protection Yes Motor underload
protection Short-circuit protection
of +24V and +10V reference voltages
Galvanically isolated, Rtrip = 4.7 kΩ
NX_5: 911 VDC; NX_6: 1200 VDC
NX_5: 333 VDC; NX_6: 460 VDC
the AC drive is protected
Yes
Yes **
Motor overload protection provided at 110% of full
load current
Yes
Yes
* The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to or less than the factory default. Thermal management might reduce the switching frequency.
** System software version NXP00002V186 (or newer) must be used for the motor thermal memory and memory retention functionality to conform to UL 508C requirements. If an older system software version is used, motor overtemperature protection is required at installation to comply with UL requirements.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
vacon • 24 MOUNTING
H1
W1
D1
11483_00

5. MOUNTING

5.1 Dimensions

The table below shows the dimensional drawing of the basic cabinet. It is allowed to install NXC drives side by side. Please note that certain NXC options will further affect the total width or height of the cabinet. Always refer to the delivery specific information for the exact dimensions.
Figure 2. Basic cabinet dimensions
Table 7. NXC 6-pulse drives cabinet dimensions
Dimensions [mm] IP21 Dimensions [mm] IP54
Type
W1 H1 D1 W1 H1 D1
0261—0520 5 0125—0416 6
0650—0730 5 0460—0590 6
0820—1030 5 0650—0820 6
1150 5 1406** 2275* 605 1206** 2400* 605 1300—1450 5 1606** 2275* 605 1606 2400 605 0920—1180 6 1406** 2275* 605 1406 2400 605
1500 6 2406 2275* 605 2406** 2400* 605 1770—2150 5
1900—2250 6
606** 2275* 605 606** 2400* 605
806** 2275* 605 806** 2400* 605
1206** 2275* 605 1206** 2400* 605
2806 2275* 605 2806** 2400* 605
5
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
MOUNTING vacon • 25
Table 8. NXC 12-pulse drives cabinet dimensions
Dimensions [mm] IP21 Dimensions [mm] IP54
Type
W1 H1 D1 W1 H1 D1
0385—0520 5 0261—0416 6
0590—0730 5 0460—0590 6
0820—1030 5 0650—0820 6
1150 5 0920—1180 6
1300—1450 5 2006** 2275* 605 2006** 2400* 605 1770—2150 5
1500—2250 6
Table 9. NXC drive low-harmonic cabinet dimensions
Type
0261—0520 5 0125—0416 6
0590—1030 5 0460—0820 6
1150—1450 5 0920—1180 6
1770—2700 5 1500—2250 6
606** 2275* 605 606** 2400* 605
806** 2275* 605 806** 2400* 605
1206** 2275* 605 1206** 2400* 605
1406** 2275* 605 1406** 2400* 605
2806** 2275* 605 2806** 2400* 605
Dimensions [mm] IP21 Dimensions [mm] IP54
W1 H1 D1 W1 H1 D1
1006** 2275* 605 1006** 2405* 605
2006** 2275* 605 2006** 2405* 605
2206** 2275* 605 2206** 2445* 605
4406** 2275* 605 4406** 2445* 605
* the options +GPL or +GPH (Plinth) increase the height by 100mm or 200mm respectively ** some options, e.g. +CIT (Top input cabling +400mm), +COT (Top output cabling +400mm) and +ODU
(output du/dt filter +400mm) affect the width of the cabinet
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5
vacon • 26 MOUNTING
Min 60°
Min 60°
Min 60°
11484_00

5.2 Lifting the unit out of the transport packaging

The unit is delivered either in a wooden box or a wooden cage. The box may be transported either horizontally or vertically, while transportation of the cage in a horizontal position is not allowed. Always refer to shipping marks for more detailed information. To lift the unit out of the box, use lifting equipment capable of handling the weight of the cabinet.
There are lifting lugs on the top of the cabinet and these lugs can be used to lift the cabinet into an upright position and to move it to the place needed.
Figure 3. Lifting the unit
NOTE! Location of lifting lugs varies between different enclosures. Recycle the packaging material according to local regulations.
5
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
MOUNTING vacon • 27
13006.emf
11485_00

5.3 Fixing the unit to the floor or to the wall

Before starting the installation work make sure that the level of the floor is within acceptable limits. The maximum deviation from the basic level can be no more than 5 mm over 3 m distance. The maximum acceptable height difference between cabinet front and rear edges should be within +2/­0mm limit.
The cabinet should always be fixed to the floor or to the wall. Depending on installation conditions, the cabinet sections can be fixed in different ways. There are holes in the front corners which can be used for fixing. Additionally, the rails on the top of the cabinet have fixing lugs for fixing the cabinet to the wall.
Welding of the cabinet might risk sensitive components in the AC drive. Ensure that no grounding currents can flow through any part of the AC drive.

5.3.1 Fixing to the floor and to the wall

In installations where the cabinet is mounted against the wall, it is more convenient to fix the top of the cabinet to the wall. Fix the cabinet in the two front corners to the floor with bolts. Fix the top part to the wall with bolts. Note that the rails and the fixing lugs can be moved horizontally to make sure the cabinet stands in a horizontal position. In AC drives consisting of more than one cabinet section, fix all sections in the same way.
Figure 4. Fixing the cabinet to the floor and to the wall
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5
vacon • 28 MOUNTING
11486_00

5.3.2 Fixing to the floor only

NOTE! This option is not available for FR13 and bigger units. For fixing FR13 and bigger units see delivery specific documentation.
If bottom-only fixing is used, additional fixing brackets (Rittal part.nr. 8800.210) or equivalent are necessary. Fix the cabinet to the floor in the front with bolts and use the fixing brackets in the middle. Fix all cabinet sections in the same way.
Figure 5. Fixing all for corners to the floor
5
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
MOUNTING vacon • 29
13006.emf
111
333
222
Terminal numbers
11487_uk
Move the bridge plate to change tapping
11488 uk

5.4 AC choke connections

NOTE! The NXC low-harmonic drive incorporates an LCL filter instead of AC chokes and this instruction can be ignored.
The AC input choke carries out several functions in the VACON input choke is needed as an essential component for motor control, to protect the input and DC-link components against abrupt changes of current and voltage as well as to function as a protection against harmonics.
The NXC 6- and 12-pulse AC drive is equipped with one or more input AC chokes. The chokes have two inductance levels to optimise the functionality at different supply voltages. In the installation phase, the wiring of the chokes should be checked and changed if needed (not for FR9).
The input is always connected to terminal #1 (see picture below) and should not be changed. The output of the choke should be connected to terminal #2 or #3 (see picture below) according to the table below. The terminals are marked with inductance values and applicable voltage.
In units FR10 to FR12, the connection is changed by moving the cable to the appropriate terminals. In FR13/14, the bridges of the busbar connection should be moved according to the settings shown in the table.
In units with two or more parallel chokes (some FR11 as well as all FR12 and FR13) all chokes have to be wired in the same way. If chokes are wired differently the AC drive may be damaged.
®
NX 6- and 12-pulse AC drive. The
Figure 6. Input chokes
Supply voltage
400-480 Vac/50-60 Hz
(500 V unit)
500 Vac/50 Hz
(500 V unit)
500 Vac/50 Hz
(690 V unit)
575-690 Vac/50-60 Hz
(690 V unit)
AC drive
connection
(terminals)
2
3
3
3
Figure 7. Input chokes tapping in FR13/14 units
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5
vacon • 30 MOUNTING

5.5 Auxiliary voltage transformer tappings

NOTE! An auxiliary voltage transformer is always included as standard in NXC low-harmonic drives. If the drive is ordered with an auxiliary voltage transformer for 230V auxiliary voltage supply (+ATx
option) the tappings of the transformer have to be set according to the mains voltage. The tappings of the transformer in 500V drives is by default set to 400V or 500V and in 690V drives
to 690V unless otherwise ordered. Locate the transformer in the lower part of the cabinet. The primary side of the transformer has
tappings that correspond to standard main voltages. Change to tapping to correspond to the mains voltage in use.
5
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Loading...
+ 80 hidden pages