Danfoss VACON NX All-in-One Application guide

Application Guide
VACON® NX All-in-One
drives.danfoss.com
VACON® NX All-in-One
Application Guide

Contents

1
1.1
Purpose of this Application Guide 8
Manual and Software Version 8
1.2
Additional Resources 8
1.3
1.4
Parameter Table Reading Guide 8
2
Basic Application 10
2.1
Introduction to Basic Application 10
2.1.1
Motor Protection Functions in the Basic Application 10
2.2
Control I/O in Basic Application 11
2.3
Control Signal Logic in Basic Application 12
2.4
Parameter Lists for Basic Application 12
2.4.1
Monitoring Values (Control Panel: Menu M1) 12
Contents
2.4.2
Basic Parameters (Control Panel: Menu M2 -> G2.1) 13
2.4.3
Keypad Control (Control Panel: Menu M3) 15
2.4.4
System Menu (Control Panel: Menu M6) 15
2.4.5
Expander Boards (Control Panel: Menu M7) 15
3
Standard Application 16
3.1
Introduction to Standard Application 16
3.2
Control I/O in Standard Application 17
3.3
Control Signal Logic in Standard Application 18
3.4
Parameter Lists for Standard Application 18
3.4.1
Monitoring Values (Control Panel: Menu M1) 12
3.4.2
Basic Parameters (Control Panel: Menu M2 -> G2.1) 19
3.4.3
Input Signals (Control Panel: Menu M2 -> G2.2) 20
3.4.4
Output Signals (Control Panel: Menu M2 ->G2.3) 21
3.4.5
Drive Control Parameters (Control Panel: Menu M2->G2.4) 23
3.4.6
Prohibit Frequency Parameters (Control Panel: Menu M2 -> G2.5) 23
3.4.7
Motor Control Parameters (Control Panel: Menu M2 -> G2.6) 24
3.4.8
Protections (Control Panel: Menu M2 -> G2.7) 25
3.4.9
Autorestart Parameters (Control Panel: Menu M2 -> G2.8) 27
3.4.10
Keypad Control (Control Panel: Menu M3) 27
3.4.11
System Menu (Control Panel: Menu M6) 15
3.4.12
Expander Boards (Control Panel: Menu M7) 15
4
Local/Remote Control Application 28
4.1
Introduction to Local/Remote Control Application 28
AB296635287482en-000201/DPD00903 | 3Danfoss A/S © 2020.12
VACON® NX All-in-One
Application Guide
4.2
Control I/O in Local/Remote Control Application 29
4.3
Control Signal Logic in Local/Remote Control Application 31
4.4
Parameter Lists for Local/Remote Control Application 31
4.4.1
Monitoring Values (Control Panel: Menu M1) 12
4.4.2
Basic Parameters (Control Panel: Menu M2 -> G2.1 32
4.4.3
Input Signals (Control Panel: Menu M2 -> G2.2) 33
4.4.4
Output Signals (Control Panel: Menu M2 -> G2.3) 36
4.4.5
Drive Control Parameters (Control Panel: Menu M2->G2.4) 23
4.4.6
Prohibit Frequency Parameters (Control Panel: Menu M2 -> G2.5) 39
4.4.7
Motor Control Parameters (Control Panel: Menu M2 -> G2.6) 24
4.4.8
Protections (Control Panel: Menu M2 -> G2.7) 25
4.4.9
Autorestart Parameters (Control Panel: Menu M2 -> G2.8) 27
4.4.10
Keypad Control (Control Panel: Menu M3) 27
4.4.11
System Menu (Control Panel: Menu M6) 15
Contents
4.4.12
Expander Boards (Control Panel: Menu M7) 15
5
Multi-step Speed Control Application 44
5.1
Introduction to Multi-step Speed Control Application 44
5.2
Control I/O in Multi-step Speed Control 45
5.3
Control Signal Logic in Multi-step Speed Control Application 46
5.4
Parameter Lists for Multi-step Speed Control Application 47
5.4.1
Monitoring Values (Control Panel: Menu M1) 12
5.4.2
Basic Parameters (Control Panel: Menu M2 -> G2.1) 47
5.4.3
Input Signals (Control Panel: Menu M2 -> G2.2) 49
5.4.4
Output Signals (Control Panel: Menu M2 -> G2.3) 51
5.4.5
Drive Control Parameters (Control Panel: Menu M2->G2.4) 23
5.4.6
Prohibit Frequency Parameters (Control Panel: Menu M2 -> G2.5) 39
5.4.7
Motor Control Parameters (Control Panel: Menu M2 -> G2.6) 24
5.4.8
Protections (Control Panel: Menu M2 -> G2.7) 56
5.4.9
Autorestart Parameters (Control Panel: Menu M2 -> G2.8) 27
5.4.10
Keypad Control (Control Panel: Menu M3) 27
5.4.11
System Menu (Control Panel: Menu M6) 15
5.4.12
Expander Boards (Control Panel: Menu M7) 15
6
PID Control Application 59
6.1
Introduction to PID Control Application 59
6.2
Control I/O in PID Control Application 60
6.3
Control Signal Logic in PID Control Application 62
6.4
Parameter Lists for PID Control Application 62
AB296635287482en-000201/DPD009034 | Danfoss A/S © 2020.12
VACON® NX All-in-One
Application Guide
6.4.1
Monitoring Values (Control Panel: Menu M1) 62
6.4.2
Basic Parameters (Keypad Panel: Menu M2 -> G2.1) 63
6.4.3
Input Signals (Control Panel: Menu M2 -> G2.2) 65
6.4.4
Output Signals (Control Panel: Menu M2 -> G2.3) 68
6.4.5
Drive Control Parameters (Control Panel: Menu M2 -> G2.4) 70
6.4.6
Prohibit Frequency Parameters (Control Panel: Menu M2 -> G2.5) 71
6.4.7
Motor Control Parameters (Control Panel: Menu M2 -> G2.6) 72
6.4.8
Protections (Control Panel: Menu M2 -> G2.7) 73
6.4.9
Autorestart Parameters (Control Panel: Menu M2 -> G2.8) 27
6.4.10
Keypad Control (Control Panel: Menu M3) 75
6.4.11
System Menu (Control Panel: Menu M6) 15
6.4.12
Expander Boards (Control Panel: Menu M7) 15
7
Multi-purpose Control Application 77
7.1
Introduction to Multi-purpose Control Application 77
Contents
7.2
Control I/O in Multi-purpose Control Application 78
7.3
Control Signal Logic in Multi-purpose Control Application 79
7.4
Parameter Lists for Multi-purpose Control Application 79
7.4.1
Monitoring Values (Control Panel: Menu M1) 79
7.4.2
Basic Parameters (Control Panel: Menu M2 -> G2.1) 90
7.4.3
Input Signals 92
7.4.4
Output Signals 97
7.4.5
Drive Control Parameters (Control Panel: Menu M2 -> G2.4) 102
7.4.6
Prohibit Frequency Parameters (Control Panel: Menu M2 -> G2.5) 71
7.4.7
Motor Control Parameters, VACON® NXS (Control Panel: Menu M2 -> G2.6) 104
7.4.8
Motor Control Parameters, VACON® NXP (Control Panel: Menu M2 -> G2.6) 107
7.4.9
Protections (Control Panel: Menu M2 -> G2.7) 111
7.4.10
Autorestart Parameters (Control Panel: Menu M2 -> G2.8) 27
7.4.11
Fieldbus Parameters (Control Panel: Menu M2 -> G2.9) 117
7.4.12
Torque Control Parameters (Control Panel: Menu M2 -> G2.10) 118
7.4.13
Master Follower Parameters, VACON® NXP (Control Panel: Menu M2 -> G2.11 119
7.4.14
Functional Safety (Control Panel: Menu M2 -> G.12) 120
7.4.15
Condition-based Monitoring (Control Panel: Menu M2 -> G.13) 121
7.4.16
Keypad Control (Control Panel: Menu M3) 125
7.4.17
System Menu (Control Panel: Menu M6) 15
7.4.18
Expander Boards (Control Panel: Menu M7) 15
8
Pump and Fan Control Application 127
8.1
Introduction to Pump and Fan Control Application 127
AB296635287482en-000201/DPD00903 | 5Danfoss A/S © 2020.12
VACON® NX All-in-One
Application Guide
8.2
Control I/O in Pump and Fan Control Application 128
8.3
Control Signal Logic in Pump and Fan Control Application 131
8.4
Parameter Lists for Pump and Fan Control Application 131
8.4.1
Monitoring Values (Control Panel: Menu M1) 131
8.4.2
Basic Parameters (Control Panel: Menu M2 -> G2.1) 132
8.4.3
Input Signals 134
8.4.4
Output Signals 138
8.4.5
Drive Control Parameters (Control Panel: Menu M2 -> G2.4) 142
8.4.6
Prohibit Frequency Parameters (Control Panel: Menu M2 -> G2.5) 71
8.4.7
Motor Control Parameters (Control Panel: Menu M2 ->G2.6) 143
8.4.8
Protections (Control Panel: Menu M2 -> G2.7) 144
8.4.9
Auto Restart Parameters (Control Panel: Menu M2 -> G2.8) 146
8.4.10
Pump and Fan Control Parameters (Control Panel: Menu M2 -> G2.9) 146
8.4.11
Keypad Control (Control Panel: Menu M3) 148
Contents
8.4.12
System Menu (Control Panel: Menu M6) 15
8.4.13
Expander Boards (Control Panel: Menu M7) 15
9
Monitoring Value Descriptions 149
10
Parameter Descriptions 165
10.611
Keypad Control Parameters 298
10.612
Master/Follower Function 299
10.613
External Brake Control with Additional Limits (IDs 315, 316, 346–349, 352, 353) 300
10.614
Parameters of Motor Thermal Protection (IDs 704–708) 302
10.615
Parameters of Stall Protection (IDs 709–712) 303
10.616
Parameters of Underload Protection (IDs 713–716) 303
10.617
Fieldbus Control Parameters (IDs 850–859) 303
10.617.1
Process Data Out (Slave -> Master) 303
10.617.2
Current Scaling in Different Size of Units 303
10.617.3
Process Data in (Master -> Slave) 304
10.618
Closed Loop Parameters (IDs 612–621) 305
10.619
"Terminal to Function" (TTF) Programming Principle 305
10.619.1
Defining an Input/Output for a Certain Function on Keypad 305
10.619.2
Defining a Terminal for a Certain Function with VACON® NCDrive 306
10.619.3
Defining Unused Inputs/Outputs 307
10.620
Speed Control Parameters (Multi-Purpose Control Application Only) 307
10.621
Functional Safety Parameters (Multi-Purpose Control Application Only) 309
10.622
Automatic Changing Between Drives (Pump and Fan Control Application Only) 310
10.623
Interlock Selection (Pump and Fan Control Application Only) 310
AB296635287482en-000201/DPD009036 | Danfoss A/S © 2020.12
VACON® NX All-in-One
Application Guide
10.624
Examples of Autochange and Interlock Selection 310
10.624.1
Pump and Fan Automatics with Interlocks and No Autochange 310
10.624.2
Pump and Fan Automatics with Interlocks and Autochange 311
10.625
Fieldbus Control in Detail 314
10.625.1
Combination 2: Bypass - ProfiDrive 314
10.625.2
Combination 3: Bypass - Standard 316
10.626
Condition-based Monitoring 317
10.626.1
Stages of Condition-based Monitoring 318
11
Fault Tracing 320
11.1
Faults and Alarms 320
Contents
AB296635287482en-000201/DPD00903 | 7Danfoss A/S © 2020.12
-
-
Manual Edi­tion
Remarks
Software code
DPD00903H
New and updated monitoring values and parameters in Multi-purpose Con­trol Application, for example, related to Condition-based Monitoring.
New faults related to Condition-based Monitoring
Other minor changes and corrections throughout the manual.
Basic Application = ASFIFF01, Version 4.08
Standard Application = ASFIFF02, Version 4.08
Local/Remote Control Application = ASFIFF03, Version 4.08
Multi-step Speed Control Application = ASFIFF04, Version 4.08
PID Control Application = ASFIFF05, Version 4.11
Multi-purpose Control Application
VACON® NXS = ASFIFF06, Version 4.14
VACON® NXP = APFIFF06, Version 2.64
Pump and Fan Control Application = ASFIFF07, Version 4.09
NOTE! Download the English and French product manuals with applicable safety, warning and caution information from https://
www.danfoss.com/en/service-and-support/.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit contenant l'ensemble des informa­tions de sécurité, avertissements et mises en garde applicables sur le site https://www.danfoss.com/en/service-and-support/.
Index
Min Max Unit Default
ID Description
Parameter
e30bg858.10
A
B
C
D E F G H
VACON® NX All-in-One
Application Guide

Introduction

1 Introduction
1.1 Purpose of this Application Guide
This Application Guide provides information on functions of different applications, available parameters, and alarms to help in con­figuring the system, programming, and troubleshooting the AC drive. It is intended for use by qualified personnel. Read and follow the instructions to use the drive safely and professionally. Pay particular attention to the safety instructions and general warnings that are provided in this manual and other documentation delivered with the drive.
1.2 Manual and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome. The original language of this manual is English.
Table 1: Manual and Software Version
1.3 Additional Resources
Other resources are available to understand advanced AC drive functions and operation.
VACON® NXS/NXP Air-cooled Wall-mounted and Standalone Operating Guide
VACON® NXP NXC User Manual
VACON® NXP IP00 User Manual
VACON® NXP Liquid Cooled User Manual
Instructions for operation with option boards and other optional equipment.
Supplementary publications and manuals are available from Danfoss. For US and Canada market:
1.4 Parameter Table Reading Guide
This manual includes a large quantity of parameter tables. These instructions tell you how to read the tables.
Illustration 1: Parameter Table Reading Guide
AB296635287482en-000201 / DPD009038 | Danfoss A/S © 2020.12
A
The location of the parameter in the menu, that is, the parameter number.
B
The name of the parameter.
C
The minimum value of the parameter.
D
The maximum value of the parameter.
E
The unit of the value of the parameter. The unit shows if it is available.
F
The value that was set in the factory.
G
The ID number of the parameter.
H
A short description of the values of the parameter and/or its function.
VACON® NX All-in-One
Application Guide
Introduction
AB296635287482en-000201 / DPD00903 | 9Danfoss A/S © 2020.12
VACON® NX All-in-One
Application Guide

Basic Application

2 Basic Application
2.1 Introduction to Basic Application
The Basic Application is a simple and easy-to-use application. It is the default setting on delivery from the factory. Otherwise select the Basic Application in menu M6 on page S6.2. See the User Manual of the product.
Digital input DIN 3 is programmable. The parameters of the Basic Application are explained in Chapter Parameter descriptions of this manual. The explanations are ar-
ranged according to the individual ID number of the parameter.
2.1.1 Motor Protection Functions in the Basic Application
The Basic Application provides almost all the same protection functions as the other applications:
External fault protection
Input phase supervision
Undervoltage protection
Output phase supervision
Earth fault protection
Motor thermal protection
Thermistor fault protection
Fieldbus fault protection
Slot fault protection
Unlike the other applications, the Basic Application does not provide any parameters for choosing the response function or limit values for the faults. For more information on the motor thermal protection, see 10.336 (ID 704) Motor Thermal Protection and
10.614 Parameters of Motor Thermal Protection (IDs 704–708).
AB296635287482en-000201 / DPD0090310 | Danfoss A/S © 2020.12
1
6
2
3
4
5
18
19
20
12
7
13
8
9
10
14
15
16
21
OPTA 2 / OPTA 3
22
23
11
17
24
25
26
DIN4
DIN5
Voltage for potentiometer, etc.
Ground for reference and controls
Ground for reference and controls
Ground for reference and controls
Analogue input 2 frequency reference
Voltage for switches (see #6)
Connect to GND or +24 V
FAULT
External fault input Programmable (P2.17)
Connect to GND or +24 V
Contact open = no action Contact closed = fault reset
Contact open = no fault Contact closed = fault
Contact closed = start forward
Contact closed = start reverse
Analogue output 1 Output frequency Programmable (P2.16)
Range 0—20 mA/RL, max. 500 Ω
Open collector, I≤50 mA, U≤48 VDC
Digital output 1 READY
RUN
mA
READY
AO1-
DO1
+24V
GND
GND
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
R O1
R O1
R O1
CMA
CMB
R O2
R O2
R O2
Standard I/O board
Terminal Signal Description
+10V
ref
AI1+
AI1-
AI2+
AI2-
+24V
Reference output
Analogue input 1 Voltage range 0—10 V DC Programmable (P2.14)
Analogue input 2
Current range 0-20mA
Control voltage output
I/O ground
I/O ground
Preset speed select 1
Preset speed select 2
Fault reset
Common for DIN 1—DIN 3
Common for DIN4-DIN6
Control voltge output
I/O ground
Relay output 1
Relay output 2
AO1+
Analogue input 1 frequency reference
Voltage for switches, etc. max 0.1 A
Start forward
Start reverse
Freq. ref.
Open Closed Open Closed
Open Open Closed Closed
I/O ref (P2.14) Preset Speed 1 Preset Speed 2 Max frequency
RUN
Reference potentiometer,
1-10kΩ
e30bh055.20
VACON® NX All-in-One
Application Guide
2.2 Control I/O in Basic Application
Illustration 2: Default I/O Configuration in Basic Application
The option board OPTA3 has no terminal for open contact on its second relay output (terminal 24 is missing). See jumper selections in Illustration 3. More information in the User Manual of the product.
AB296635287482en-000201 / DPD00903 | 11Danfoss A/S © 2020.12
Basic Application
Jumper block X3:
CMA and CMB grounding
CMB connected to GND CMA connected to GND
CMB isolated from GND CMA isolated from GND
CMB and CMA internally connected together,isolated from GND
= Factory default
e30bh013.10
e30bh049.10
DIN4 DIN5 AI1 AI2
DIN1 DIN2
DIN6 DIN3
≥ 1
3.2 Keypad reference
3.1 Control place
Start forward
Start reverse
Start/Stop
Reverse
Internal Start/Stop
Internal reverse
Internal fault reset
Fault reset input
External fault input (programmable)
Reset button
Start/Stop buttons
Reference from fieldbus
Start/Stop from fieldbus
Direction from fieldbus
3.3 Keypad direction
2.14 I/O Reference
2.19 Preset Speed 2
2.18 Preset Speed 1
2.2 Max Frequency
Start/Stop and reverse logic
Internal frequency reference
VACON® NX All-in-One
Application Guide
Illustration 3: Jumper Selections
2.3 Control Signal Logic in Basic Application
Basic Application
Illustration 4: Control Signal Logic of the Basic Application
2.4 Parameter Lists for Basic Application
2.4.1 Monitoring Values (Control Panel: Menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and measurements. Monitoring values cannot be edited.
AB296635287482en-000201 / DPD0090312 | Danfoss A/S © 2020.12
Index
Monitoring value
Unit
Form
ID
Description
V1.1
Output frequency
Hz
#.##1-
V1.2
Frequency reference
Hz
#.##25-
V1.3
Motor speed
RPM#2-V1.4
Motor current
A
Varies
3-V1.5
Motor torque
%
#.#4-
V1.6
Motor shaft power
%
#.#5-
V1.7
Motor voltage
V
#.#6-
V1.8
DC-link voltage
V#7-V1.9
Unit temperature
°C#8-V1.10
Motor temperature
%
#.#9-
V1.11
Analog input 1
V/mA
#.##13-
V1.12
Analog input 2
V/mA
#.##14-
V1.13
DIN 1, 2, 3
--15-V1.14
DIN 4, 5, 6
--16-V1.15
DO1, RO1, RO2
--17
-
V1.16
Analog I
out
mA
#.##26-
V1.17
Multimonitoring items
---
-
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.1
Min frequency
0.00
P2.2Hz0.00
101-P2.2
Max frequency
P2.1
320.00
Hz
50.00
102-P2.3
Acceleration time 1
0.1
3000.0
s
3.0
103-P2.4
Deceleration time 1
0.1
3000.0
s
3.0
104
-
P2.5
Current limit
0.1 x I
H
2 x IHA
IL107
-
P2.6
Nominal voltage of the motor
180
690VNX2: 230 V NX5: 400 V NX6: 690 V
110
-
P2.7
Nominal frequency of the mo­tor
8.00
320.00
Hz
50.00
111
­P2.8
Nominal speed of the motor
24
20 000
RPM
1440
112
-
VACON® NX All-in-One
Application Guide
Table 2: Monitoring Values
Basic Application
2.4.2 Basic Parameters (Control Panel: Menu M2 -> G2.1)
Table 3: Basic Parameters G2.1
AB296635287482en-000201 / DPD00903 | 13Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.9
Nominal current of the motor
0.1 x I
H
2 X IHA
IH113
-
P2.10
Motor cos phi
0.30
1.00-0.85
120
-
P2.11
Start function
0
2-0
505
0 = Ramp 1 = Flying start 2 = Conditional flying start
P2.12
Stop function
0
3-0
506
0 = Coasting 1 = Ramp 2 = Ramp + Run enable coast Ramp 3 = Coast + Run enable ramp
P2.13
U/f optimization
0
1-0
109
0 = Not used 1 = Automatic torque boost
P2.14
I/O reference
0
3-0
117
0 = AI1 1 = AI2 2 = Keypad 3 = Fieldbus
P2.15
Analog input 2, reference off­set
0
1-1
302
0 = 0–20 mA 1 = 4–20 mA
P2.16
Analog output function
0
8-1
307
0 = Not used 1 = Output freq. (0- f
max
)
2 = Freq. reference (0-f
max
)
3 = Motor speed (0-Motor nominal speed) 4 = Output current (0-InMotor) 5 = Motor torque (0-TnMotor) 6 = Motor power (0-PnMotor) 7 = Motor voltage (0-UnMotor) 8 = DC-link volt (0-1000V)
P2.17
DIN 3 function
0
7-1
301
0 = Not used 1 = Ext. fault, closing cont. 2 = Ext. fault, opening cont. 3 = Run enable, cc 4 = Run enable, oc 5 = Force cp. to I/O 6 = Force cp. to keypad 7 = Force cp. to fieldbus
P2.18
Preset speed 1
0.00
P2.2Hz0.00
105-P2.19
Preset speed 2
0.00
P2.2Hz50.00
106
-
P2.20
Automatic restart
0
1-0
731
0 = Disabled 2 = Enabled
VACON® NX All-in-One
Application Guide
Basic Application
AB296635287482en-000201 / DPD0090314 | Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.1
Control place
1
3-1
125
1 = I/0 terminal 2 = Keypad 3 = Fieldbus
P3.2
Keypad reference
P2.1
P2.2Hz0.00
-
-
P3.3
Direction (on keypad)
0
1-0
123
0 = Forward 1 = Reverse
R3.4
Stop button
0
1-1
114
0 = Limited function of Stop button 1 = Stop button always enabled
VACON® NX All-in-One
Application Guide
Basic Application
2.4.3 Keypad Control (Control Panel: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed in Table 4. See the Keypad control menu in the User Manual of the product.
Table 4: Keypad Control Parameters, M3
2.4.4 System Menu (Control Panel: Menu M6)
For more information related to the general use of the AC drive, such as selecting application and language, customized parameter sets, or hardware and software, see the User Manual of the product.
2.4.5 Expander Boards (Control Panel: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and board-related information. For more infor­mation, see the User Manual of the product.
AB296635287482en-000201 / DPD00903 | 15Danfoss A/S © 2020.12
VACON® NX All-in-One
Application Guide

Standard Application

3 Standard Application
3.1 Introduction to Standard Application
Select the Standard Application in menu M6 on page S6.2. The Standard Application is typically used in pump and fan applications and conveyors for which the Basic Application is too limited
but where no special features are needed.
The Standard Application has the same I/O signals and the same control logic as the Basic Application.
Digital input DIN 3 and all the outputs are freely programmable.
Extra functions:
Programmable Start/Stop and Reverse signal logic
Reference scaling
One frequency limit supervision
Second ramps and S-shape ramp programming
Programmable start and stop functions
DC brake at stop
One prohibit frequency area
Programmable U/f curve and switching frequency
Auto restart
Motor thermal and stall protection: Programmable action; off, warning, fault
The parameters of the Standard Application are explained in Chapter Parameter descriptions of this manual. The explanations are arranged according to the individual ID number of the parameter.
AB296635287482en-000201 / DPD0090316 | Danfoss A/S © 2020.12
1
6
2
3
4
5
18
19
20
12
7
13
8
9
10
14
15
16
21
22
23
11
17
24
25
26
DIN4
DIN5
mA
READY
RUN
AO1-
DO1
+24 V
GND
GND
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
R O1
R O1
R O1
CMA
CMB
R O2
R O2
R O2
OPTA1
OPTA2 / OPTA3
Terminal Signal Description
+10 V
ref
AI1+
AI1-
AI2+
AI2-
+24V
Reference output
I/O Ground
Analogue input 2 Current range 0—20mA
Control voltage output
I/O ground
Start forward Programmable logic (P2.2.1)
Start reverse Ri min = 5
External fault input Programmable (P2.2.2)
Preset speed select 1
Preset speed select 2
Fault reset
Common for DIN 1—DIN 3
Common for DIN4—DIN6
Control voltage output
I/O ground
Analogue output 1 Output frequency Programmable (P2.3.2)
Digital output 1 READY Programmable (P2.3.7)
Open collector, I≤50 mA, U≤48 VDC
Relay output 1
RUN
Programmable
(P2.3.8)
Relay output 2
FAULT
Programmable
(P2.3.9)
Range 0—20 mA/RL, max. 500 Ω
Connect to GND or +24 V
Contact open = no action Contact closed = fault reset
AO1+
Analogue input 1 frequency reference
Ground for reference and controls
Analogue input 2 frequency reference
Contact closed = start forward
Contact closed = start reverse
Contact open = no fault Contact closed = fault
Freq. ref.
Open Closed Open Closed
Open Open Closed Closed
I/O Reference Preset Speed 1 Preset Speed 2 Analog input 2
Voltage for potentiometer, etc.
Analogue input 1 Voltage range 0—10V DC Programmable (P2.1.11)
Voltage for switches, etc. max 0.1 A
Voltage for switches (see #6)
Connect to GND or +24 V
Ground for reference and controls
Ground for reference and controls
Reference potentiometer,
1-10kΩ
e30bh091.20
VACON® NX All-in-One
Application Guide
3.2 Control I/O in Standard Application
Standard Application
Illustration 5: Default I/O Configuration in Standard Application
The option board OPTA3 has no terminal for open contact on its second relay output (terminal 24 is missing). See jumper selections in Illustration 6. More information in the User Manual of the product.
AB296635287482en-000201 / DPD00903 | 17Danfoss A/S © 2020.12
Jumper block X3:
CMA and CMB grounding
CMB connected to GND CMA connected to GND
CMB isolated from GND CMA isolated from GND
CMB and CMA internally connected together,isolated from GND
= Factory default
e30bh013.10
e30bh050.10
DIN4 DIN5 AI1 AI2
DIN1 DIN2
DIN6 DIN3
≥ 1
3.2 Keypad reference
3.1 Control place
Start forward
Start reverse
Start/Stop
Reverse
Internal Start/Stop
Internal reverse
Internal fault reset
Fault reset input
External fault input (programmable)
Reset button
Start/Stop buttons
Reference from fieldbus
Start/Stop from fieldbus
Direction from fieldbus
3.3 Keypad direction
2.1.13 Fieldbus Ctrl Reference
2.1.15 Preset Speed 2
2.1.14 Preset Speed 1
2.1.11 I/O Reference
2..1.12 Keypad Ctrl Speed 1
Programmable Start/Stop and
reverse logic
Internal frequency reference
(programmable)
(programmable)
VACON® NX All-in-One
Application Guide
Illustration 6: Jumper Selections
3.3 Control Signal Logic in Standard Application
Standard Application
Illustration 7: Control Signal Logic of the Standard Application
3.4 Parameter Lists for Standard Application
3.4.1 Monitoring Values (Control Panel: Menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and measurements. Monitoring values cannot be edited.
AB296635287482en-000201 / DPD0090318 | Danfoss A/S © 2020.12
Index
Monitoring value
Unit
Form
ID
Description
V1.1
Output frequency
Hz
#.##1-
V1.2
Frequency reference
Hz
#.##25-
V1.3
Motor speed
RPM#2-V1.4
Motor current
A
Varies
3-V1.5
Motor torque
%
#.#4-
V1.6
Motor shaft power
%
#.#5-
V1.7
Motor voltage
V
#.#6-
V1.8
DC-link voltage
V#7-V1.9
Unit temperature
°C#8-V1.10
Motor temperature
%
#.#9-
V1.11
Analog input 1
V/mA
#.##13-
V1.12
Analog input 2
V/mA
#.##14-
V1.13
DIN 1, 2, 3
--15-V1.14
DIN 4, 5, 6
--16-V1.15
DO1, RO1, RO2
--17
-
V1.16
Analog I
out
mA
#.##26-
V1.17
Multimonitoring items
---
-
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.1.1
Min frequency
0.00
P2.1.2
Hz
0.00
101-P2.1.2
Max frequency
P2.1.1
320.00
Hz
50.00
102-P2.1.3
Acceleration time 1
0.1
3000.0
s
0.0
103-P2.1.4
Deceleration time 1
0.1
3000.0
s
0.0
104
-
P2.1.5
Current limit
0.1 x I
H
2 x IHA
IL107
-
P2.1.6
Nominal voltage of the motor
180
690VNX2: 230 V NX5: 400 V NX6: 690 V
110
-
P2.1.7
Nominal frequency of the motor
8.00
320.00
Hz
50.00
111-P2.1.8
Nominal speed of the motor
24
20 000
RPM
1440
112
-
VACON® NX All-in-One
Application Guide
Table 5: Monitoring Values
Standard Application
3.4.2 Basic Parameters (Control Panel: Menu M2 -> G2.1)
Table 6: Basic Parameters G2.1
AB296635287482en-000201 / DPD00903 | 19Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.1.9
Nominal current of the motor
0.1 x I
H
2 X IHA
IH113
-
P2.1.10
Motor cos phi
0.30
1.00-0.85
120
-
P2.1.11
I/O reference
0
3-0
117
0 = AI1 1 = AI2 2 = Keypad 3 = Fieldbus
P2.1.12
Keypad control reference
0
3-2
121
0 = AI1 1 = AI2 2 = Keypad 3 = Fieldbus
P2.1.13
Fieldbus control reference
0
3-3
122
0 = AI1 1 = AI2 2 = Keypad 3 = Fieldbus
P2.1.14
Preset speed 1
0.00
P2.1.2
Hz
10.00
105-P2.1.15
Preset speed 2
0.00
P2.1.2
Hz
50.00
106
-
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.2.1
Start/Stop logic
0
6-0
300
Logic = 0
Ctrl sgn 1 = Start forward Ctrl sgn 2 = Start reverse
Logic = 1
Ctrl sgn1 = Start/ Stop Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/ Stop Ctrl sgn 2 = Run enable
Logic = 3
Ctrl sgn 1 = Start pulse (edge) Ctrl sgn 2 = Stop pulse
Logic = 4
Ctrl sgn 1 = Forward pulse (edge) Ctrl sgn 2 = Reverse pulse (edge)
Logic = 5
Ctrl sgn 1 = Start pulse (edge) Ctrl sgn 2 = Reverse pulse
Logic = 6
Ctrl sgn 1 = Start pulse (edge) Ctrl sgn 2 = Enable pulse
P2.2.2
DIN 3 function
0
8-1
301
0 = Not used
VACON® NX All-in-One
Application Guide
Standard Application
3.4.3 Input Signals (Control Panel: Menu M2 -> G2.2)
Table 7: Input Signals, G2.2
AB296635287482en-000201 / DPD0090320 | Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description
1 = Ext. fault, closing cont. 2 = Ext. fault, opening cont. 3 = Run enable 4 = Acc./Dec. time select. 5 = Force cp. to I/O 6 = Force cp. to keypad 7 = Force cp. to fieldbus 8 = Reverse
P2.2.3
(1)
Analog input 2 reference offset
0
1-1
302
0 = 0–20 mA (0–10 V) 1 = 4–20 mA (2–10 V)
P2.2.4
Reference scaling minimum value
0.00
320.00
Hz
0.00
303-P2.2.5
Reference scaling maximum value
0.00
320.00
Hz
0.00
304
-
P2.2.6
Reference inversion
0
1-0
305
0 = Not inverted 1 = Inverted
P2.2.7
Reference filter time
0.00
10.00
s
0.10
306
0 = No filtering
P2.2.8
(2)
AI1 signal selection
---
A1
377
-
P2.2.9
(2)
AI2 signal selection
---
A2
388
-
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.3.1
(1)
Analog output 1 signal selection
0
-
-
A.1
464
-
P2.3.2
Analog output function
0
8-1
307
0 = Not used (20 mA/10 V) 1 = Output freq. (0–f
max
)
2 = Freq. reference (0–f
max
)
3 = Motor speed (0–Motor nominal speed) 4 = Motor current (0-I
nMotor
)
5 = Motor torque (0-T
nMotor
)
6 = Motor power (0-P
nMotor
)
7 = Motor voltage (0-U
nMotor
)
8 = DC-link volt (0–1000 V)
P2.3.3
Analog output filter time
0.00
10.00
s
1.00
308
0 = No filtering
P2.3.4
Analog output inversion
0
1-0
309
0 = Not inverted 1 = Inverted
P2.3.5
Analog output minimum
0
1-0
310
0 = 0 mA (0 V)
VACON® NX All-in-One
Application Guide
Standard Application
1
Remember to place jumpers of block X2 according to the selection (0 or 1). See the User Manual of the product.
2
Use the Terminal to Function method (TTF) with these parameters, see
3.4.4 Output Signals (Control Panel: Menu M2 ->G2.3)
Table 8: Output Signals, G2.3
10.619 "Terminal to Function" (TTF) Programming Principle.
AB296635287482en-000201 / DPD00903 | 21Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description
1 = 4 mA (2 V)
P2.3.6
Analog output scale
10
1000%100
311
-
P2.3.7
Digital output 1 function
0
16-1
312
0 = Not used 1 = Ready 2 = Run 3 = Fault 4 = Fault inverted 5 = AC drive overheat warning 6 = Ext. fault or warning 7 = Ref. fault or warning 8 = Warning 9 = Reversed 10 = Preset speed 1 11 = At speed 12 = Motor regulator active 13 = OP freq. limit 1 superv. 14 = Control place: I/O 15 = Thermistor fault/warning 16 = Fieldbus DIN 1
P2.3.8
RO1 function
0
16-2
313
As parameter 2.3.7
P2.3.9
RO2 function
0
16-3
314
As parameter 2.3.7
P2.3.10
Output frequency limit 1 super­vision
0
2-0
315
0 = No limit 1 = Low limit supervision 2 = High limit supervision
P2.3.11
Output frequency limit 1; Super­vised value
0.00
320.00
Hz
0.00
316
­P2.3.12
(1)
Analog output 2 signal selection
0.1
E.10-0.1
471-P2.3.13
Analog output 2 function
0
8-4
472
As parameter 2.3.2
P2.3.14
Analog output 2 filter time
0.00
10.00
s
1.00
473
0 = No filtering
P2.3.15
Analog output 2 inversion
0
1-0
474
0 = Not inverted 1 = Inverted
P2.3.16
Analog output 2 minimum
0
1-0
475
0 = 0 mA (0 V) 1 = 4 mA (2 V)
P2.3.17
Analog output 2 scaling
10
1000%1.00
476
-
VACON® NX All-in-One
Application Guide
Standard Application
1
Use the Terminal to Function method (TTF) with these parameters, see
10.619 "Terminal to Function" (TTF) Programming Principle.
AB296635287482en-000201 / DPD0090322 | Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.4.1
Ramp 1 shape
0.0
10.0s0.1
500
0 = Linear 100 = full acc/dec inc/dec tmes
P2.4.2
Ramp 2 shape
0.0
10.0s0.0
501
0 = Linear 100 = full acc/dec inc/dec tmes
P2.4.3
Acceleration time 2
0.1
3000.0
s
1.0
502-P2.4.4
Deceleration time 2
0.1
3000.0
s
1.0
503
-
P2.4.5
Brake chopper
0
4-0
504
0 = Disabled 1 = Used when running 2 = External brake chopper 3 = Used when stopped/running 4 = Used when running (no testing)
P2.4.6
Start function
0
2-0
505
0 = Ramp 1 = Flying start 2 = Conditional flying start
P2.4.7
Stop function
0
3-0
506
0 = Coasting 1 = Ramp 2 = Ramp+Run enable coast 3 = Coast+Run enable ramp
P2.4.8
DC braking current
0.00
ILA
0.7 x I
H
507
-
P2.4.9
DC braking time at stop
0.00
600.00
s
0.00
508
0 = DC brake is off at stop
P2.4.10
Frequency to start DC braking during ramp stop
0.10
10.00
Hz
1.50
515
­P2.4.11
DC braking time at start
0.00
600.00
s
0.00
516
0 = DC brake is off at start
P2.4.12
Flux brake
0
1-0
520
0 = Off 1 = On
P2.4.13
Flux braking current
0.00
ILA
IH519
-
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.5.1
Prohibit frequency range 1 low limit
0.00
320.00
Hz
0.00
509-P2.5.2
Prohibit frequency range 1 high limit
0.00
320.00
Hz
0.00
510
-
VACON® NX All-in-One
Application Guide
3.4.5 Drive Control Parameters (Control Panel: Menu M2->G2.4)
Table 9: Drive Control Parameters, G2.4
Standard Application
3.4.6 Prohibit Frequency Parameters (Control Panel: Menu M2 -> G2.5)
Table 10: Prohibit Frequency Parameters, G2.5
AB296635287482en-000201 / DPD00903 | 23Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.5.3
Prohibit acc./dec. ramp
0.1
10.0x0.1
518
-
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.1
(1)
Motor control mode
0
1/4-0
600
0 = Frequency control 1 = Speed control
VACON® NXP:
2 = Open loop torque control 3 = Closed loop speed ctrl 4 = Closed loop torque control
P2.6.2
(1)
U/f optimisation
0
1-0
109
0 = Not used 1 = Automatic torque boost
P2.6.3
(1)
U/f ratio selection
0
3-0
108
0 = Linear 1 = Squared 2 = Programmable 3 = Linear with flux optim.
P2.6.4
(1)
Field weakening point
8.00
320.00
Hz
50.00
602
-
P2.6.5
(1)
Voltage at field weakening point
10.00
200.00
%
100.00
603
-
P2.6.6
(1)
U/f curve midpoint frequency
0.00
P2.6.4
Hz
50.00
604
-
P2.6.7
(1)
U/f curve midpoint voltage
0.00
100.00
%
100.00
605
-
P2.6.8
(1)
Output voltage at zero frequency
0.00
40.00
%
Varies
606-P2.6.9
Switching frequency
1.0
Varies
kHz
Varies
601
-
P2.6.10
Overvoltage controller
0
2-1
607
0 = Not used 1 = Used (no ramping) 2 = Used (ramping)
P2.6.11
Undervoltage controller
0
2-2
608
0 = Not used 1 = Used 2 = Used (ramping to zero)
P2.6.12
Load drooping
0.00
100.00
%
0.00
620
-
P2.6.13
Identification
0
2/5-0
631
0 = No action 1 = Identification w/o run 2 = Identification with run
Only VACON® NXP:
3 = Encoder ID run 4 = No action 5 = ID Run Failed
VACON® NX All-in-One
Application Guide
3.4.7 Motor Control Parameters (Control Panel: Menu M2 -> G2.6)
Table 11: Motor Control Parameters, G2.6
Standard Application
AB296635287482en-000201 / DPD0090324 | Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description Closed Loop parameter group 2.6.14
P2.6.14.1
Magnetizing current
0.00
2 x IHA
0.00
612
-
P2.6.14.2
Speed control P gain
1
1000-30
613-P2.6.14.3
Speed control I time
0.0
3200.0
ms
30.0
614-P2.6.14.5
Acceleration compensation
0.00
300.00
s
0.00
626-P2.6.14.6
Slip adjust
0
500%100
619
-
P2.6.14.7
Magnetizing current at start
0.00
ILA
0.00
627
-
P2.6.14.8
Magnetizing time at start
0
60000
ms0628-P2.6.14.9
0-speed time at start
0
32000
ms
100
615-P2.6.14.10
0-speed time at stop
0
32000
ms
100
616
-
P2.6.14.11
Start-up torque
0
3-0
621
0 = Not used 1 = Torque memory 2 = Torque reference 3 = Start-up torque fwd/rev
P2.6.14.12
Start-up torque FWD
-300.0
300.0
%
0.0
633-P2.6.14.13
Start-up torque REV
-300.0
300.0
%
0.0
634-P2.6.14.15
Encoder filter time
0.0
100ms0.0
618-P2.6.14.17
Current control P gain
0.00
100.00
%
40.00
617
-
Identification parameter group 2.6.15
P2.6.15.1
Speed step
-50.0
50.0-0.0
1252
-
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.7.1
Response to 4 mA reference fault
0
5-0
700
0 = No response 1 = Warning 2 = Warning+Previous Freq. 3 = Wrng+Preset- Freq 2.7.2 4 = Fault, stop acc. to 2.4.7 5 = Fault, stop by coasting
P2.7.2
4 mA reference fault frequency
0.00
P2.1.2
Hz
0.00
728
-
VACON® NX All-in-One
Application Guide
Standard Application
1
Parameter value can only be changed after the AC drive has been stopped.
3.4.8 Protections (Control Panel: Menu M2 -> G2.7)
Table 12: Protections, G2.7
AB296635287482en-000201 / DPD00903 | 25Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.7.3
Response to external fault
0
3-2
701
0 = No response 1 = Warning 2 = Fault, stop acc. to 2.4.7 3 = Fault, stop by coasting
P2.7.4
Input phase supervision
0
3-0
730
P2.7.5
Response to undervoltage fault
0
1-0
727
0 = Fault stored in history 1 = Fault not stored
P2.7.6
Output phase supervision
0
3-2
702
0 = No response 1 = Warning 2 = Fault, stop acc. to 2.4.7 3 = Fault, stop by coasting
P2.7.7
Earth fault protection
0
3-2
703
P2.7.8
Thermal protection of the motor
0
3-2
704
P2.7.9
Motor ambient temperature factor
-100.0
100.0
%
0.0
705-P2.7.10
Motor cooling factor at zero speed
0.0
150.0
%
40.0
706-P2.7.11
Motor thermal time constant
1
200
min
Varies
707-P2.7.12
Motor duty cycle
0
150%100
708
-
P2.7.13
Stall protection
0
3-0
709
0 = No response 1 = Warning 2 = Fault, stop acc. to 2.4.7 3 = Fault, stop by coasting
P2.7.14
Stall current
0.00
2 x IHA
IH710
-
P2.7.15
Stall time limit
1.00
120.00
s
15.00
711-P2.7.16
Stall frequency limit
1.0
P2.1.2
Hz
25.00
712
-
P2.7.17
Underload protection
0
3-0
713
0 = No response 1 = Warning 2 = Fault, stop acc. to 2.4.7 3 = Fault, stop by coasting
P2.7.18
UP From Torque
10.0
150.0
%
50.0
714-P2.7.19
UP Zero frequency load
5.0
150.0
%
10.0
715-P2.7.20
Underload protection time limit
2.00
600.00
s
20.00
716-P2.7.21
Response to thermistor fault
0
3-2
732
0 = No response 1 = Warning 2 = Fault, stop acc. to 2.4.7 3 = Fault, stop by coasting
P2.7.22
Response to fieldbus fault
0
3-2
733
P2.7.23
Response to slot fault
0
3-2
734
VACON® NX All-in-One
Application Guide
Standard Application
AB296635287482en-000201 / DPD0090326 | Danfoss A/S © 2020.12
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.8.1
Wait time
0.10
10.00
s
0.50
717-P2.8.2
Trial time
0.00
60.00
s
30.00
718
-
P2.8.3
Start function
0
2-0
719
0 = Ramp 1 = Flying start 2 = According to P2.4.6
P2.8.4
Number of tries after undervoltage trip
0
10-0
720-P2.8.5
Number of tries after overvoltage trip
0
10-0
721-P2.8.6
Number of tries after overcurrent trip
0
3-0
722-P2.8.7
Number of tries after 4 mA reference trip
0
10-0
723-P2.8.8
Number of tries after motor temperature fault trip
0
10-0
726-P2.8.9
Number of tries after external fault trip
0
10-0
725-P2.8.10
Number of tries after underload fault trip
0
10-0
738
-
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.1
Control place
1
3-1
125
1 = I/0 terminal 2 = Keypad 3 = Fieldbus
P3.2
Keypad reference
P2.1.1
P2.1.2
Hz
0.00
-
-
P3.3
Direction (on keypad)
0
1-0
123
0 = Forward 1 = Reverse
R3.4
Stop button
0
1-1
114
0 = Limited function of Stop button 1 = Stop button always enabled
VACON® NX All-in-One
Application Guide
3.4.9 Autorestart Parameters (Control Panel: Menu M2 -> G2.8)
Table 13: Autorestart Parameters, G2.8
Standard Application
3.4.10 Keypad Control (Control Panel: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed in this table. See the Keypad control menu in the User Manual of the product.
Table 14: Keypad Control Parameters, M3
3.4.11 System Menu (Control Panel: Menu M6)
For more information related to the general use of the AC drive, such as selecting application and language, customized parameter sets, or hardware and software, see the User Manual of the product.
3.4.12 Expander Boards (Control Panel: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and board-related information. For more infor­mation, see the User Manual of the product.
AB296635287482en-000201 / DPD00903 | 27Danfoss A/S © 2020.12
VACON® NX All-in-One
Application Guide

Local/Remote Control Application

4 Local/Remote Control Application
4.1 Introduction to Local/Remote Control Application
Select the Local/Remote Control Application in menu M6 on page S6.2. With the Local/Remote Control Application, it is possible to have two different control places. For each control place the frequency
reference can be selected from either the control panel, I/O terminal, or fieldbus. The active control place is selected with the digital input DIN 6.
All outputs are freely programmable.
Extra functions:
Programmable Start/Stop and Reverse signal logic
Reference scaling
One frequency limit supervision
Second ramps and S-shape ramp programming
Programmable start and stop functions
DC brake at stop
One prohibit frequency area
Programmable U/f curve and switching frequency
Auto restart
Motor thermal and stall protection: Programmable action; off, warning, fault
The parameters of the Local/Remote Control Application are explained in Chapter Parameter descriptions of this manual. The ex­planations are arranged according to the individual ID number of the parameter.
AB296635287482en-000201 / DPD0090328 | Danfoss A/S © 2020.12
Reference potentiometer,
1-10kΩ
1
6
2
3
4
5
18
19
20
12
7
13
8
9
10
14
15
16
21
22
23
11
17
24
25
26
mA
Remote Reference
0(4) - 20 mA
RUN
READY
AO1-
DO1
+24 V
GND
GND
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
R
O1
R
O1
R
O1
CMA
CMB
R
O2
R
O2
R
O2
OPTA1
OPTA2 / OPTA3
Terminal
Signal Description
+10 V
ref
AI1+
AI1-
AI2+
AI2-
+24V
Reference output
I/O Ground
Analogue input 2 Current range 0—20mA Programmable (P2.1.11)
Control voltage output
I/O ground
Place A: Start forward Programmable logic (P2.2.1)
Place A: Start reverse Ri min = 5 kohm
External fault input Programmable (P2.2.2)
Place B: Start forward Programmable logic (P2.2.15)
Place B: Start reverse Ri min = 5 kΩ
Place A/B selection
Common for DIN 1—DIN 3
Common for DIN4—DIN6
Control voltage output
I/O ground
Analogue output 1 Output frequency Programmable (P2.3.2)
Digital output READY Programmable (P2.3.7)
Open collector, I≤50 mA, U≤48 VDC
Relay output 1
RUN
Programmable
(P2.3.8)
Relay output 2
FAULT
Programmable
(P2.3.9)
Range 0—20 mA/RL, max. 500 Ω
Contact open = place A is active Contact closed = Place B is active
Contact closed = start forward Contact closed = start reverse
AO1+
Analogue input 1 reference for place B
Ground for reference and controls
Analogue input 2 reference for place A
Contact closed = start forward
Contact closed = start reverse
Contact open = no fault Contact closed = fault
Voltage for potentiometer, etc.
Analogue input 1 Voltage range 0—10V DC Programmable (P2.1.12)
Voltage for switches, etc. max 0.1 A
Voltage for switches (see #6)
Connect to GND or +24 V
Connect to GND or +24 V
Ground for reference and controls
Ground for reference and controls
e30bh092.20
VACON® NX All-in-One
Application Guide
4.2 Control I/O in Local/Remote Control Application
Local/Remote Control Application
Illustration 8: Default I/O Configuration in Local/Remote Control Application
The option board OPTA3 has no terminal for open contact on its second relay output (terminal 24 is missing). See jumper selections in Illustration 12. More information in the User Manual of the product.
AB296635287482en-000201 / DPD00903 | 29Danfoss A/S © 2020.12
Jumper block X3:
CMA and CMB grounding
CMB connected to GND CMA connected to GND
CMB isolated from GND CMA isolated from GND
CMB and CMA internally connected together,isolated from GND
= Factory default
e30bh013.10
VACON® NX All-in-One
Application Guide
Illustration 9: Jumper Selections
Local/Remote Control Application
AB296635287482en-000201 / DPD0090330 | Danfoss A/S © 2020.12
Loading...
+ 324 hidden pages