Danfoss VACON NX Application guide

vacon
ac drives
®
nx
active front end ii (afe-ii)
arfiff05
application manual
Arfiff05 Standard AFE-II VACON® 3
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
Vacon Standard AFE-II application
INDEX
Document code: DPD01979A
Software code: ARFIFF05V070
Date: 3.6.2021
VACON STANDARD AFE-II APPLICATION ........................................................................................... 3
1. Introduction ........................................................................................................................................................... 6
1.1 Compatibility issues in parameters between versions ..................................................................................... 7
2. Operation ............................................................................................................................................................... 8
2.2 Charging of DC ................................................................................................................................................ 8
2.3 Main Circuit breaker control (MCB control) ..................................................................................................... 9
2.4 Quick Start instructions .................................................................................................................................. 9
2.5 Start Sequence ............................................................................................................................................. 10
2.6 Stop Sequence .............................................................................................................................................. 11
2.7 Start Stop timing diagram ............................................................................................................................. 12
3. CONTROL IO ......................................................................................................................................................... 13
4. AFE Application – Monitoring Values ................................................................................................................... 14
5.1 Monitoring values......................................................................................................................................... 15
5.1.1 Monitoring 1 ............................................................................................................................................ 15
5.1.2 FieldBus Monitoring values ....................................................................................................................... 15
5.1.3 Line Monitor OPT-D7 ................................................................................................................................ 15
5.1.4 Master Follower ....................................................................................................................................... 16
5.1.5 Monitoring values 2.................................................................................................................................. 16
4.7.1 PID Control ............................................................................................................................................... 16
5.2 Monitoring Values description ...................................................................................................................... 17
5.2.1 Monitoring 1 values.................................................................................................................................. 17
5.2.2 Fieldbus monitoring values ....................................................................................................................... 19
5.2.3 Line monitoring OPT-D7 ........................................................................................................................... 24
5.2.4 Master/Follower ...................................................................................................................................... 24
4.7.2 Statuses ................................................................................................................................................... 25
5.2.5 Monitoring values 2.................................................................................................................................. 25
4.7.3 PIC Controller ........................................................................................................................................... 25
5. Parameter List ...................................................................................................................................................... 26
6.1 Basic parameters .......................................................................................................................................... 26
6.2 Reference Handling ...................................................................................................................................... 26
5.8 PIC Function ................................................................................................................................................. 27
5.9 Input signals ................................................................................................................................................. 28
6.2.1 Digital inputs ............................................................................................................................................ 28
6.2.2 Analogue Input 1 ...................................................................................................................................... 29
6.2.3 Analogue Input 2 ...................................................................................................................................... 29
6.2.4 Cabin State DI ........................................................................................................................................... 29
6.2.5 Options .................................................................................................................................................... 29
6.3 Output signals .............................................................................................................................................. 30
6.3.1 Digital Outputs ......................................................................................................................................... 30
6.3.2 ANALOG OUTPUT 1 .................................................................................................................................. 30
6.3.3 Options .................................................................................................................................................... 31
6.5 Limit Settings ................................................................................................................................................ 32
5.9.1 Current Limit ............................................................................................................................................ 32
4 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
5.9.2 Power Limit .............................................................................................................................................. 32
5.9.3 Frequency Limit ........................................................................................................................................ 32
5.9.4 AC Voltage Limit ....................................................................................................................................... 32
5.9.5 DC Voltage Limit ....................................................................................................................................... 32
5.10 Drive Control parameters ............................................................................................................................. 33
5.10.1 Control ................................................................................................................................................. 33
5.11 Protections ................................................................................................................................................... 34
5.11.1 General ................................................................................................................................................ 34
5.11.2 Temperature sensor protections .......................................................................................................... 34
5.11.3 Fieldbus ............................................................................................................................................... 35
5.11.4 OPT-D7 protections .............................................................................................................................. 35
5.11.5 External Fault ....................................................................................................................................... 35
5.11.6 Cooling protection................................................................................................................................ 35
5.11.7 Cabin protection .................................................................................................................................. 35
5.11.8 Options ................................................................................................................................................ 36
5.12 Fieldbus parameters ..................................................................................................................................... 37
5.13 ID Control Functions ..................................................................................................................................... 38
5.13.1 Value control ....................................................................................................................................... 38
5.13.2 DIN ID Control 1 ................................................................................................................................... 38
5.14 Keypad control (Control keypad: Menu M3) .................................................................................................. 39
5.15 System menu (Control keypad: Menu M6) .................................................................................................... 39
5.16 Expander boards (Control keypad: Menu M7) ............................................................................................... 39
6. Description of parameters.................................................................................................................................... 40
6.1 Basic parameters .......................................................................................................................................... 40
6.2 Reference Handling ...................................................................................................................................... 41
6.2.1 PIC Function ............................................................................................................................................. 42
6.3 Input signals ................................................................................................................................................. 43
6.3.1 Digital inputs ............................................................................................................................................ 43
6.3.2 Analogue Inputs ....................................................................................................................................... 46
6.3.3 Cabin State DI ........................................................................................................................................... 49
6.3.4 Options .................................................................................................................................................... 49
6.4 Output signals .............................................................................................................................................. 50
6.4.1 Digital outputs .......................................................................................................................................... 50
6.4.2 Analogue outputs ..................................................................................................................................... 52
6.4.3 Options outputs ....................................................................................................................................... 54
6.5 Limit Settings ................................................................................................................................................ 55
6.5.1 Current limits ........................................................................................................................................... 55
6.5.2 Power Limits ............................................................................................................................................ 55
6.5.3 Frequency limits ....................................................................................................................................... 55
6.5.4 AC Voltage limits ...................................................................................................................................... 56
6.5.5 DC Voltage limit parameters ..................................................................................................................... 56
6.6 Drive control ................................................................................................................................................ 57
6.6.1 Control ..................................................................................................................................................... 59
6.7 Protections ................................................................................................................................................... 61
6.7.1 General .................................................................................................................................................... 61
6.7.2 Temperature sensor protections............................................................................................................... 62
6.7.3 Fieldbus ................................................................................................................................................... 64
6.7.4 OPT-D7 Protections .................................................................................................................................. 65
6.7.5 External Fault ........................................................................................................................................... 65
6.7.6 Cooling protection .................................................................................................................................... 65
6.7.7 Cabin Protection....................................................................................................................................... 66
6.7.8 Options .................................................................................................................................................... 66
6.8 Fieldbus parameters ..................................................................................................................................... 67
6.9 ID Functions ................................................................................................................................................. 68
6.9.1 Value Control ........................................................................................................................................... 68
6.9.2 DIN ID Control .......................................................................................................................................... 70
Arfiff05 Standard AFE-II VACON® 5
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
6.10 Keypad control ............................................................................................................................................. 71
7. Status and control words in detail ........................................................................................................................ 72
8.1 Basic In ByPass (0) ........................................................................................................................................ 72
8.2 FB Control Word ........................................................................................................................................... 73
8.2.1 Standard (1) ............................................................................................................................................. 73
8.2.2 Vacon AFE 1 profile (2) ............................................................................................................................. 74
8.2.3 Vacon AFE 2 Profile (3) ............................................................................................................................. 76
8.3 FB Status Word ............................................................................................................................................. 78
7.11 Fault Word 1 ................................................................................................................................................ 79
7.12 Fault Word 2 ................................................................................................................................................ 80
7.13 Warning Word 1 ........................................................................................................................................... 81
8.4 Auxiliary Control Word ................................................................................................................................. 82
8.5 Status Word (Application) ID 43 .................................................................................................................... 83
8. Problem Solving ................................................................................................................................................... 85
9. Fault codes ........................................................................................................................................................... 86
6 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

1. INTRODUCTION

The AFE unit is a regenerative power converter for the front-end of a common DC bus product line. The AFE unit is utilized by using inverter hardware with special software. An external L(CL)-filter and
charging circuit is needed. This unit is selected when low harmonics are required. The principle connection of AFE drive has been described in Figure 1.
The Regenerative Application is easy and flexible to use due to its versatile fieldbus features. The parameters of the Regenerative Application are explained in Chapter 6 of this manual.
The basic I/O-configuration of the AFE drive consists of OPT-A1 and OPT-A2 option cards. The basic I/O configuration has been described in table 2-1. As a default the control place (P3.1) of the AFE drive is Keypad.
This application requires NXP3 control board VB00761.
Figure 1, AFE connection
Arfiff05 Standard AFE-II VACON® 7
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

1.1 Compatibility issues in parameters between versions

V025
Compatibility Issue: MCB Force Open inverted. This to follow NXC cabinet
default signals.
Update Note 1: This application parameters are not kept backwards compatible if new features or improvements would be difficult to implement by doing so. Read this change note and chapter Compatibility issues in parameters between versions” from manual before updating the application.
Update Note 2: It’s recommended to use compare function for parameter changes when updating
application, especially in cases when version number change is considerably high. Application is constantly developed; this includes changing parameter default values, and if parameters are directly downloaded to drive improved default values may be lost.
8 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

2. OPERATION

2.2 Charging of DC

This AFE application has own charging control, P2.4.1.9 DC Charge (24 Vdc required for control board) and charging protection in case external charging can’t get DC voltage to required level within set time P2.7.1.5 Charge Max Time (provided that DC Voltage reach at least drive under voltage fault level).
Charging function is activated when P2.4.1.9 DC Charge is A.1 or higher. When control place is IO, Keypad or NCDrive charging is started from start command. Charging is not started if:
- Drive is in fault state.
- P2.3.1.2 Enable MCB Close is FALSE
- P2.3.1.6 Run Enable is FALSE
- P2.3.1.7 Quick Stop is FALSE Charging is also stopped if above conditions happens during charging or start command is removed. For fieldbus control charging is started with B0 of FB Control Word on supporting FB profiles.
Charging is also stopped if B0 goes low as is MCB opened if already closed. DC Charge (F80) is given if 85 % of DC Nominal is not reached within P2.7.1.5 Charge Max Time
and charging is stopped. DC Charging is stopped when drive receives feedback from P2.3.1.5 MCB Status. Note! Use suitably sized DC Charging resistor by checking Pulse loadability for time duration set in
for Max Charge Time parameter
NOTE! The MCB feedback is necessary for the correct operation of the AFE application. NOTE! Only the drive controls its own MCB. If additional interlocks or opening commands are
needed, these commands must go through the drive. NOTE! Missing feedback signal prevent drive going to ready state. MCB Feedback can be monitored
from Status Word B10. NOTE! If feedback is not used there will be three second forced delay on internally generated MCB
feedback signal. MCB Feedback can be monitored from Status Word B10.
Arfiff05 Standard AFE-II VACON® 9
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

2.3 Main Circuit breaker control (MCB control) The AFE application controls the MCB of the system with Relay Output RO2. When charging of the

DC bus is ready the MCB will be closed. The status of the MCB is monitored via digital input P2.3.1.5 MCB Status (Default is DigIn: A.4). MCB feedback is required for correct AFE functionality,
NOTE! MCB feedback is required for correct AFE functionality. Over Current (F1), Hardware IGBT (F31) and Software IGBT (F41) faults will open MCB
immediately. Some fault can be programmed to open MCB if needed.
NOTE! For correct operation of AFE system, AFE unit needs to be in control of charging circuit and Main Circuit Breaker (MCB).

2.4 Quick Start instructions

NOTE! Before taking any commissioning actions read carefully the safety instructions in Vacon NX
User's Manual, chapter 1.
1. Connect the unit according to the Figure 1.
2. Power up the control unit.
3. Set parameters in G2.1 Basic Parameters.
4. Check that digital input parameters (G2.3.1) have been set according to connections. Note that P2.3.1.5 MCB Status input is needed for correct operation of AFE unit.
5. Check the control place accordingly proves requirements (P3.1 Control Place).
6. Charge DC.
In case of parallel AFE:
1. Set Parallel AFE parameter (P2.1.5) = YES (in every AFE). (This will set also DC Drooping to 3,00 %
2. Set Start Up Delay in AFE units so that starting is in sequence with different intervals.
Time * 100 ms
Stop
AFE 1
Run
Stop
AFE 2
Run
Stop
AFE 3
Run
Stop
AFE 4
Run
10 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

2.5 Start Sequence

Init
Ready to
switch on
DC > 85 %
Close MCB
MCB close
enable
MCB Closed
Start
Command
Synchronized Trials >= 5
Modulating
F10: LineSynch
No
Yes
No
Yes
Yes
Yes
Yes
No
No
No
No
Yes
F64 A2
(Delayed)
Figure 0-2. AFE start sequence
Arfiff05 Standard AFE-II VACON® • 11
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

2.6 Stop Sequence

Modulating
MCB Closed
No
F64 A4
Open MCB
No
Yes
Yes
Stop Modulation
(If Run State)
Open MCB
Stop Request MCB Closed
No
F64 A2
(If DC > 75 %)
(Delayed)
Yes
MCB Closed
No
Yes
F64 A3
(Delayed)
End
Figure 0-3. AFE stop sequence
12 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

2.7 Start Stop timing diagram

DC Voltage
Charge Control
MCB Feedback
MCB Close Control
MCB Close level
Stable DC
Ready
IO Start
Run
FB CW.B00
Control in
FB Control
FB CW.B03
Contro in
IO Control
P. Start Delay
IO MCB Open
Command
Above example when “Standard” state machine is used. With “Basic” state machine operation
is like in IO Control.
Arfiff05 Standard AFE-II VACON® • 13
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

3. CONTROL IO

NXOPTA1
Terminal
Signal
Description
1
+10V
ref
Reference voltage output
Voltage for potentiometer, etc.
2
AI1+
Analogue input 1. Range 0-10V, Ri = 200 Range 0-20 mA Ri = 250
Analogue input 1 Input range selected by jumpers. Default range: Voltage 0 – 10 V
3
AI1-
I/O Ground
Ground for reference and controls
4
AI2+
Analogue input 2. Range 0-10V, Ri = 200 Range 0-20 mA Ri = 250
Analogue input 2 Input range selected by jumpers. Default range: Current 0 – 20 mA
5
AI2-
6
+24V
Control voltage output
Voltage for switches, etc. max 0.1 A
7
GND
I/O ground
Ground for reference and controls
8
DIN1
Start Request Programmable G2.3.1
Contact closed = Start Request
9
DIN2
Programmable G2.3.1
No function defined at default
10
DIN3
Fault Reset Programmable G2.3.1
Contact closed = Fault Reset
11
CMA
Common for DIN 1DIN 3
Connect to GND or +24V
12
+24V
Control voltage output
Voltage for switches (see #6)
13
GND
I/O ground
Ground for reference and controls
14
DIN4
MCB feedback
Contact open = MCB open Contact closed = MCB Closed
15
DIN5
Programmable G2.3.1
No function defined at default
16
DIN6
Programmable G2.2.1
17
CMB
Common for DIN4DIN6
Connect to GND or +24V
18
AOA1+
Analogue output 1 Programmable P2.3.1.2
Output range selected by jumpers. Range 020 mA. RL, max. 500 Range 010 V. RL > 1k
19
AOA1-
20
DOA1
Digital output Ready / Warning (Blinking)
Programmable Open collector, I50mA, U48 VDC
NXOPTA2
21
RO1
Relay output 1
Programmable G2.4.1
Switching capacity 24 VCD / 8 A 250 VAC / 8 A 125 VDC / 0.4 A
22
RO1
23
RO1
24
RO2
Relay output 2
MCB Contl
Cannot be reprogrammed
Fixed to MCB control. Closes when DC at 85 % of nominal DC. Opens when DC below 75 % of nominal DC
25
RO2
26
RO2
Table 4-2. Default I/O configuration.
220
VAC
mA
K1
Q1
14 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

4. AFE APPLICATION – MONITORING VALUES

On the next pages you will find the lists of parameters within the respective parameter groups. Column explanations:
Code = Location indication on the keypad; Shows the operator the present parameter
number Parameter = Name of parameter Min = Minimum value of parameter Max = Maximum value of parameter Unit = Unit of parameter value; Given if available Default = Value preset by factory Cust = Customer’s own setting ID = ID number of the parameter _____ = On parameter code: Parameter value can only be changed after the Drive has
been stopped. _____ = Monitoring value is possible to control from fieldbus by ID number
The manual presents signals that are not normally visible for monitoring. i.e. is not a parameter or standard monitoring signal. These signals are presented with [Letter]. e.g. [FW]MotorRegulatorStatus
[V] Normal monitoring signal [P] Normal parameter in application. [FW] Firmware signal, Can be monitored with NCDrive when signal type is selected Firmware [A] Application signal, can be monitored with NCDrive when signal type is selected Application. [R] Reference type parameter on keypad. [F] Function. Signal is received as a output of function. [DI] Digital input signal. CB Circuit Breaker MCB Main Circuit Breaker = AFE controller Circuit Breaker
Arfiff05 Standard AFE-II VACON® • 15
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

5.1 Monitoring values The monitoring values are the actual values of parameters and signals as well as statuses and

measurements. Monitoring values cannot be edited.

5.1.1 Monitoring 1

Code
Signal
Unit
ID
Description
V1.1.1
DC-Link Voltage
Vdc
1108
Measured DC Link voltage in Volts, filtered.
V1.1.2
DC-Link Ref.
Vdc
25
DC Voltage Reference in Vdc
V1.1.3
DC Voltage Ref.
%
1200
Used DC Voltage Reference
V1.1.4
DC Voltage Act.
%
7
Actual DC Voltage
V1.1.5
Total Current
A
3
Total current of the regenerative unit in Amperes.
V1.1.6
Active Current
%
1125
Avtive current of the regenerative drive in % of Rated Line Current. > 0 power from AC side to DC side < 0 power from DC side to AC side
V1.1.7
Reactive Current
%
1157
Reactive current of the regenerative drive in % of Rated Line Current. > 0 Inductive current < 0 Capacitive current
V1.1.8
Supply Frequency
Hz
1
Supply frequency in ##.## Hz .The sign indicates the phase order.
V1.1.9
Supply Voltage
V
6
Input AC voltage, RMS line to line Volts.
V1.1.10
Unit Temperature
°C
8
Heat sing temperature
V1.1.11
Status Word
43 V1.1.12
DIN 645. 321
15
V1.1.13
Analogue Input 1
%
13
V1.1.14
Analogue Input 2
%
14 V1.1.15
Analogue Out 1
%
26 V1.1.16
Operation Hours
h
1856 V1.1.17
DC-Link Current
A
72 V1.1.18
DC-Link ActCurr
%
1158

5.1.2 FieldBus Monitoring values

Code
Signal
Unit
ID
Description
V1.2.1
FB Control Word
1160
Control word from fieldbus
V1.2.2
FB Status Word
68
Status word to fieldbus
V1.2.3
Fault Word 1
1172
V1.2.4
Fault Word 2
1173
V1.2.5
DIN Status Word 1
56 V1.2.6
DIN Status Word 2
57
V1.2.7
Warning Word 1
1174
V1.2.8
DC Voltage
44
Unfiltered DC-Link voltage
V1.2.9
Current
1113
Unfiltered total current
V1.2.10
Drive Power
kW
1508
Electrical AFE terminal power
V1.2.11
Fault History
37
V1.2.12
Final DC Ref
%
1131
V1.2.13
Cabin State Word
1884
V1.2.14
Warning
74

5.1.3 Line Monitor OPT-D7

Code
Signal
Unit
ID
Description
V1.3.1
Line Voltage
V
1650
V1.3.2
Line Frequency
Hz
1654
V1.3.3
Synch Error D7
1659
V1.3.4
Line Voltage THD
1670
V1.3.5
Line Voltage HF rms
1671
16 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

5.1.4 Master Follower

Code
Parameter
Unit
Form.
ID
Description
V1.4.1
SB SystemStatus
1601 V1.4.2
Master CW
93 Code
Parameter
Unit ID
Description
V1.4.3.1
Current D1
A
Varies
1820
V1.4.3.2
Current D2
A
Varies
1821
V1.4.3.3
Current D3
A
Varies
1822
V1.4.3.4
Current D4
A
Varies
1823 Code
Parameter
Unit ID
Description
V1.4.4.1
Status Word D1
# 1828
V1.4.4.2
Status Word D2
# 1829
V1.4.4.3
Status Word D3
# 1830
V1.4.4.4
Status Word D4
# 1831

5.1.5 Monitoring values 2

Code
Signal
Unit
ID
Description
V1.5.1
Measured temperature 1
50
4 s filtering.
V1.5.2
Measured temperature 2
51
4 s filtering.
V1.5.3
Measured temperature 3
52
4 s filtering.
V1.5.4
Measured temperature 4
69
4 s filtering.
V1.5.5
Measured temperature 5
70
4 s filtering.
V1.5.6
Measured temperature 6
71
4 s filtering.
V.1.5.7
PT-100 Temperature
42
Highest temperature of OPTB8/OPTBH board. 4 s filtering.

4.7.1 PID Control

Code
Parameter
Unit
Form.
ID
Description
V1.6.1
PID Reference
#,#
20
V1.6.2
PID Actual Value
#,#
21
V1.6.3
PID Output
#,##
23
Arfiff05 Standard AFE-II VACON® • 17
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
5.2

Monitoring Values description

5.2.1 Monitoring 1 values

V1.1.1 DC-Link Voltage Vdc ID44
Measured DC voltage, filtered.
V1.1.2 DC-Link Ref. Vdc ID25
DC-Link voltage reference in Vdc.
V1.1.3 DC Voltage Ref. % ID1200
Used DC Voltage reference in %
V1.1.4 DC Voltage Act. % ID7
Actual DC Voltage in %
V1.1.5 Total Current A ID3
Total current of the regenerative unit in Amperes, filtered
V1.1.6 Active Current % ID1125
Active current in % of System Rated Current. Negative value means that current is flowing to AC side from DC side i.e. regenerating.
V1.1.7 Reactive Current % ID1157
Reactive current of the regenerative drive in % of System Rated Current. Positive is Inductive current. Negative is capacitive current.
V1.1.8 Supply Frequency Hz ID1
Supply frequency in ##.## Hz .The sign indicates the phase order. Updated when drive in run state. Updated also in stop state when OPT-D7 is used or Regen Options B9 is activated.
V1.1.9 Supply Voltage V ID6
Input AC voltage, RMS line to line Volts. Updated when drive in run state. Updates also when OPT-D7 is used.
V1.1.10 Unit Temperature °C ID8
Temperature of the unit in degrees Celsius
18 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
V1.1.11 Status Word ID43
Application Status Word combines different drive statuses to one data word.
Application Status Word ID43
FALSE
TRUE
b0
b1
Not in Ready state
Ready
b2
Not Running
Running
b3
No Fault
Fault
b4
b5
Quick Stop Active
Quick Stop Not Active
b6
Run Disabled
Run Enable
b7
No Warning
Warning
b8 Charging Switch closed (internal)
b9 MCB Control (DO Final)
b10 MCB Feedback
b11 DO Charging Active
b12
No Run Request
Run Request
b13
b14
b15
V1.1.12 DIN 645. 321 ID15
DIN1/DIN2/DIN3 status
B0
DIN1
B1
DIN2
B2
DIN3
B3
DIN4
B4
DIN5
B5
DIN6
V1.1.13 Analogue Input 1 % ID13 V1.1.14 Analogue Input 2 % ID14
Unfiltered analogue input level. 0 % = 0 mA / 0 V, -100 % = -10 V, 100 % = 20 mA / 10 V. Monitoring scaling is determined by the option board parameter.
V1.1.15 Analogue Out 1 % ID26
Analogue Output value 0 % = 0 mA / 0 V, 100 % = 20 mA / 10 V
V1.1.16 Operation Hours ID1856
Run state hours
V1.1.17 DC-Link Current [A] ID72
Calculated DC-Link Current in Amps.
V1.1.18 DC-Link ActCurr [%] #,# ID1158
Calculated DC-Link Current in %.
Arfiff05 Standard AFE-II VACON® • 19
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

5.2.2 Fieldbus monitoring values

V1.2.1 FB Control Word ID 1160
Control word from fieldbus. Below table is for bypass operation for such fieldbus board that natively supports this or can be parameterized to bypass mode.
FB Control Word ID1160
Signal
Comment
SM
B00
DC Charge
0= Open MCB. 1= Close DC charge contactor, MCB closed automatically, see
B01.
1,2,3
B01
MCB Close Enable
0= Disable Closing of MCB (Also opens if Control Options.B0=TRUE) 1= Enable Closing of MCB (Works also for reclosing)
3
B02
Quick Stop
0= Quick Stop 1= No Quick Stop
3
B03
Run
0= AFE is stopped 1= AFE is started
1,2,3
B04
Output Power Limit to
Zero
0= Output Power Limit to Zero (7%) 1= Output Power Limit = P2.5.2.1
3
B05
Disable Power
Increase.
Input or Output
0= Disable increase of power. 1= Power limits defined by G2.5.2
3
B06
Input Power Limit to
Zero
0= Input Power Limit to Zero (7%) 1= Output Power Limit = P2.5.2.2
3
B07
Reset
0>1 Reset fault.
1,2,3
B08
DC Voltage Ref B00
B00 | B01 0 | 0 = FB Reference. P2.2.1, if not FB Control & FB Ref > 50,00 %
0 | 1 = 110 % 1 | 0 = 115 % 1 | 1 = 120 %
2,3
B09
DC Voltage Ref B01
2,3
B10
Fieldbus Control
0= No control from fieldbus 1=Control from fieldbus
2,3
B11
Watchdog
0>1>0>1…0,5 sec square wave clock. This is used to check data
communication between fieldbus master and the drive.
2,3
B12
FB DIN2
Can be used to control RO or directly parameter by ID number. G2.4.1
1,2,3
B13
FB DIN3
Can be used to control RO or directly parameter by ID number. G2.4.1
1,2,3
B14
FB DIN4
Can be used to control RO or directly parameter by ID number. G2.4.1
1,2,3
B15
Reserved for future use.
20 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
V1.2.2 FB Status Word ID 68
FB Status word to fieldbus. Below table is for bypass operation for such fieldbus board that natively supports this or can be parameterized to bypass mode.
FB Status Word ID68
Signal
Comment
b0
Ready On
0=Drive not ready to switch on 1=Drive ready to start charging
b1
Ready Run
0=Drive not ready to run 1=Drive ready and MCB is ON
b2
Running
0=Drive not running 1=Drive in Run state (Modulating)
b3
Fault
0=No active fault 1=Fault is active
b4
Run Enable Status
0= Run Disabled. Drive in stop state 1= Run Enabled. Drive can be started.
b5
Quick Stop Active
0=Quick Stop Active 1=Quick Stop not Active
b6
MCB Control NOT OK
0= MCB Control OK 1= MCB Requested open but DC stays high
b7
Warning
0= No active warnings 1= Warning active
b8
At Reference
0= DC Voltage Ref and Act DC Voltage are not same.
b9
Fieldbus Control Active
0=Fieldbus control not active 1=Fieldbus control active
b10
Above Limit
0= DC Voltage is below P2.5.5.1 level 1=The DC Voltage is above the P2.5.5.1 level
b11
MCB Control (DO Final)
0= Drive is controlling MCB to be Open. 1= Drive is controlling MCB to be Closed
b12
MCB Feedback
0= Feedback indicates MCB to be Open 1= Feedback indicates MCB to be Closed
b13
Reserved for future use.
b14
DC Charge DO Control
0= DC not charged 1= DC Charging Active
b15
Watchdog
Same as received on bit 11 of the FB Control Word.
Arfiff05 Standard AFE-II VACON® • 21
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
V1.2.3 Fault Word 1 ID 1172
Fault Word 1 ID1172
Bit
Fault(s)
B0
F1 Over current, F31 IGBT, F41 IGBT
B1
F2 Over Voltage
B2
F9 Under Voltage
B3
F91 Short Circuit
B4
F3 Earth Fault
B5 B6
F14 Unit Over Temperature
B7
F29 Thermistor, F56 Measured Temperature 1, F65 Measured Temperature 2 F71 LCL Over Temperature
B8
F10 Line Synch fault F11 Supply Phase
B9 B10
Device faults: F37, F38, F39, F40
B11
B12
B13 B14
B15
V1.2.4 Fault Word 2 ID 1173
Fault Word 2 ID1173
Bit
Fault(s)
B0
B1
F5 Charging Fault, F80 Charge Fault
B2
B3
Hardware faults: F7
B4
F13 Under Temperature
B5
F22 EPROM, F49 Zero Division
B6 B7 B8
B9
F31 IGBT, F41 IGBT
B10
B11
F32 Fan Fault, F70 LCL Fan Fault, F60 LC Cooling Warning/Fault
B12
B13
F8 System, F26 Start Up Prevented, F36 Control Unit
B14
F64 MCB State Fault
B15
22 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
V1.2.5 DIN Status 1 ID 56 V1.2.6 DIN Status 2 ID 57
DIN Status Word 1
DIN Status Word 2
b0
DIN: A.1
DIN: C.5
b1
DIN: A.2
DIN: C.6
b2
DIN: A.3
DIN: D.1
b3
DIN: A.4
DIN: D.2
b4
DIN: A.5
DIN: D.3
b5
DIN: A.6
DIN: D.4
b6
DIN: B.1
DIN: D.5
b7
DIN: B.2
DIN: D.6
b8
DIN: B.3
DIN: E.1
b9
DIN: B.4
DIN: E.2
b10
DIN: B.5
DIN: E.3
b11
DIN: B.6
DIN: E.4
b12
DIN: C.1
DIN: E.5
b13
DIN: C.2
DIN: E.6
b14
DIN: C.3
b15
DIN: C.4
V1.2.7 Warning Word 1 ID 1174
Warning Word 1 ID1174
Bit
Warning(s)
B0
B1
W29 Thermistor F56 Measured Temperature 1, F65 Measured Temperature 2 F71 LCL Over Temperature
B2
B3
W11 Supply Phase
B4
B5 B6 B7 B8
W14 Unit Over Temperature
B9 B10
F32 Fan Fault, F70 LCL Fan Fault
B11
B12
B13
B14
B15
Arfiff05 Standard AFE-II VACON® • 23
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
V1.2.8 DC Voltage [Vdc] ID44
Unfiltered DC-Link Voltage
V1.2.9 Current [A] ID1113
Total unfiltered current
V1.2.10 Drive Power [kW] ID 1508
Drive input terminal electrical power.
V1.2.11 Fault History ID37
Last active fault. If drive has several fault at the same time see from fault history what was the first fault.
V1.2.12 Final DC Ref [%] ID1131
Final DC Reference, including offset control.
V1.2.13 Cabin State Word ID1884
Cabin State Word ID1884
Fault
Fault Codes
b0
Main Fuse
W81
b1
Aux voltage
W82
b2
STO Fuse
W83
b3
Insulation Fault
W84
b4
Earthswitch Fault
W85
b5
Arc Relay
W86
b6
high Amb Temp.
W88
b7
Leakage
W89
b8
Not used
b9
Not used
b10
Not used
b11
Not used
b12
Not used
b13
Not used
b14
Not used
b15
Not used
V1.2.14 Warning ID74
Last active warning. If drive has several warning at the same time see from fault history what was the first warning.
24 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

5.2.3 Line monitoring OPT-D7

V1.3.1 Line Voltage V ID1650
The measured line voltage rms value when using the OPT-D7 option board in slot C.
V1.3.2 Line Frequency Hz ID1654
The measured line voltage frequency when using the OPT-D7 option board in slot C.
V1.3.3 Synch Error D7 ID1659
An error on voltage angles between the drive and the measurement taken by OPT-D7.
-3072...+3071 = -180...180 degrees. If the value is not near to zero when running in AFE mode, the phase order may be wrong even if the OPT-D7 frequency is correct (Error about 2047 = 120 degree). If measurement is after Dyn11 transformer error is usually about 512 (30,0 Degree).
V1.3.4 Line Voltage THD ID1670
V1.3.5 LineVoltageHFrms ID1671

5.2.4 Master/Follower

Here are gathered relevant signals in Master follower system.
V1.4.1 SB SystemStatus ID 1601
System Bus Status Word ID1601
FALSE
TRUE
b0 Not used
b1 Drive 1 Ready
b2 Drive 1 Running
b3 Drive 1 Fault
b4 Not used
b5 Drive 2 Ready
b6 Drive 2 Running
b7 Drive 2 Fault
b8 Not used
b9 Drive 3 Ready
b10 Drive 3 Running
b11 Drive 3 Fault
b12 Not used
b13 Drive 4 Ready
b14 Drive 4 Running
b15 Drive 4 Fault
Arfiff05 Standard AFE-II VACON® • 25
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
V1.4. 2 Master CW ID93
Master Drive Control Word. Master Sending, Follower receiving.
.4.7.1.1 Currents
V1.4.3.1 Current D1 A Varies 1820 V1.4.3.2 Current D2 A Varies 1821 V1.4.3.3 Current D3 A Varies 1822 V1.4.3.4 Current D4 A Varies 1823

4.7.2 Statuses

V1.4.4.1 Status Word D1 # 1828 V1.4.4.2 Status Word D2 # 1829 V1.4.4.3 Status Word D3 # 1830 V1.4.4.4 Status Word D4 # 1831

5.2.5 Monitoring values 2

V1.5.1 Measured temperature 1 ID 50 V1.5.2 Measured temperature 2 ID 51 V1.5.3 Measured temperature 3 ID 52 V1.5.4 Measured temperature 4 ID 69 V1.5.5 Measured temperature 5 ID 70 V1.5.6 Measured temperature 6 ID 71 V1.5.7 PT-100 Temperature ID 42
Highest temperature of OPTB8/OPTBH board. 4 s filtering.

4.7.3 PIC Controller

Monitoring values for power controller in AFE mode
V1.6.1 PID Reference 20
Active Current reference
V1.6.2 PID Actual Value 21
Active current
V1.6.3 PID Output 23
PID controller output for DC Voltage reference, gives an offset for DC Voltage Reference.
26 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

5. PARAMETER LIST

6.1 Basic parameters

Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.1.1
Grid Nominal Voltage
500V:
380V
690V: 525V
500V:
500V
690V:
690V
V
400
110
Set here the nominal voltage of the grid.
P2.1.2
Grid Nominal
Frequency
48
63
Hz
50
1532
Set here the nominal frequency of the grid.
P2.1.3
System Rated Current
0,0
Ih A Ih
113
Capacity of supply, used if oversized AFE.
P2.1.4
System Rated Power
0
32000
kW 0 116
P2.1.5
Parallel AFE
0 3 0 1501
0 = Single AFE 1 = Parallel AFE 1 = Master 1 = Follower
Table 4-2. Basic parameters

6.2 Reference Handling

Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.2.1
DC Voltage Ref.
105
Varies
%
110,00
1462
DC Voltage reference as % of Nominal DC Voltage
Nominal DC voltage = 1,35 * Supply voltage
P 2.2.2
DC Voltage Drooping
0,00
100,00
0,00
620
AFE drooping DC-voltage. Set to 3,00 % when parallel AFE operation is selected
P2.2.3
Reactive Current
Reference
-100,0
100,0 % 0,0
1459
Regenerative reactive current reference 100,0 = nominal current. Positive =Inductive Negative = Capacitive
P2.2.4
DC Reference Offset
-5,00
5,00 % 0,00
1777
Table 1- 1, Reference Handling
Arfiff05 Standard AFE-II VACON® • 27
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

5.8 PIC Function

Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.2.5.1
PIC Enable
0.1
E.10
1905 P2.2.5.2
PIC Control Mode
0 2 1914 P2.2.5.3
PIC Reference
-320
320 %
167 P2.2.5.4
PIC Kp
1
3200 %
19111 P2.2.5.5
PIC Ti
0
3200
ms 1906 P2.2.5.6
PID DC Low
-50
50 %
1903 P2.2.5.7
PIC DC High
-50
50 %
1906
28 • VACON® arfiff05 Standard AFE-II
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

5.9 Input signals

6.2.1 Digital inputs

Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.3.1.1
Start Signal 1
0.1
E.10
DigIn:
A.1
403
P2.3.1.2
Enable MCB Close
0.1
E.10
DigIn:
0.2
1619
With CO.B00; Opens MCB also
P2.3.1.3
Open MCB Power
Dawn
0.1
E.10
DigIn:
0.2
1600
Power down command
P2.3.1.4
LCL Temp. X51
0.1
E.10
DigIn:
0.2
1179 P2.3.1.5
LCL Temp. X52
0.1
E.10
DigIn:
0.2
1125
P2.3.1.6
MCB Status
0.1
E.10
DigIn:
A.4
1453
P2.3.1.7
Run Enable
0.1
E.10
DigIn:
0.2
407
P2.3.1.8
Quick Stop
0.1
E.10
DigIn:
0.2
1213
Power down with a warning
P2.3.1.9
Ext. Fault 1
0.1
E.10
DigIn:
0.1
405 P2.3.1.10
Ext. Fault 2
0.1
E.10
DigIn:
0.1
406 P2.3.1.11
Fault Reset
0.1
E.10
DigIn:
0.1
414 P2.3.1.12
LC Cooling
0.1
E.10
DigIn:
0.2
750 P2.3.1.13
MCB Trip State
0.1
E.10
DigIn
0.1
1706
P2.3.1.14
Control from I/O
terminal
0.1
0.1
DigIn
0.1
409
Force control place to I/O terminal (cc)
P2.3.1.15
Control from
keypad
0.1
0.1
DigIn
0.1
410
Force control place to keypad (cc)
P2.3.1.16
Control from
fieldbus
0.1
0.1
DigIn
0.1
411
Force control place to fieldbus (cc)
Table 4-3. Digital inputs parameters
Arfiff05 Standard AFE-II VACON® • 29
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

6.2.2 Analogue Input 1

Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.3.2.1
AI1 signal selection
0.1
E.10
AnIN:
0.1
377
P2.3.2.2
AI1 filter time
0,000
32,000 s 0,000
324
P2.3.2.3
AI1 custom
minimum setting
-160,00
160,00 % 0,00
321
P2.3.2.4
AI1 custom
maximum setting
-160,00
160,00
%
100,00
322
P2.3.2.5
AI1 signal inversion
0 1 0 387
P2.3.2.6
AI1 reference
scaling, minimum
value
-32000
32000 0
303
P2.3.2.7
AI1 reference
scaling, maximum
value
-32000
32000 0
304
P2.3.2.8
AI1 Controlled ID
0
10000 0
1507
Table 1- 2, ANALOG INPUT1,

6.2.3 Analogue Input 2

Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.3.3.1
AI2 signal selection
0.1
E.10
AnIN:
0.1
388
P2.3.3.2
AI2 filter time
0,000
32,000 s 0,000
329
P2.3.3.3
AI2 custom
minimum setting
-160,00
160,00 % 0,00
326
P2.3.3.4
AI2 custom
maximum setting
-160,00
160,00
%
100,00
327
P2.3.3.5
AI2 signal inversion
0 1 0 398
P2.3.3.6
AI2 reference
scaling, minimum
value
-32000
32000 0
393
P2.2.3.7
AI2 reference
scaling, maximum
value
-32000
32000 0
394
P2.3.3.8
AI2 Controlled ID
0
10000 0
1511
Table 1- 3, ANALOG INPUT2

6.2.4 Cabin State DI

Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.3.4.1
Main Fuse
0.1
E.10
DigIn:
0.2
1700
P2.3.4.2
Aux Voltage
0.1
E.10
DigIn:
0.2
1703
P2.3.4.3
STO Fuse
0.1
E.10
DigIn:
0.2
1702
P2.3.4.4
Insulation Fault
0.1
E.10
DigIn:
0.2
1704
P2.3.4.5
Earthswitch Fault
0.1
E.10
DigIn:
0.2
1732
P2.3.4.6
Arc Relay
0.1
E.10
DigIn:
0.2
1733
P2.3.4.7
High Amb Temp.
0.1
E.10
DigIn:
0.2
1734
P2.3.4.8
Leakage
0.1
E.10
DigIn:
0.2
1735
P2.3.4.9
Klixon In 1
0.1
E.10
DigIn
0.2
780
P2.3.4.10
Klixon In 2
0.1
E.10
DigIn
0.2
781
P2.3.4.11
Input Switch
0.1
E.10
DigIn
0.2
1209

6.2.5 Options

Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.3.5.1
Start/Stop Logic
0 2 0 300
0/Static 1/ Rising edge 2/ Pulse
P2.3.5.2
Input Inversion
0
65535 0
1091
Table 1- 4, Digital input options
Loading...
+ 67 hidden pages