Pump and fan control with autochange can be
selected by setting the value of parameter 0.1
to 0.
The application can be used to control one
variable speed drive and 0-4 auxiliary drives.
Additionally the motor connected to the
frequency converter and the start order of the
auxiliary drives can be changed with the
autochange function and external relay
system. The PI-controller of the frequency
2 Control I/O
TerminalSignalDescription
PI-controller
actual value
READY
220
VAC
220
VAC
FAULT
1+10V
2Uin+Analog input, voltageProgrammable
3GNDI/O groundGround for reference and controls
+Analogue input,PI-controller actual value
4I
in
5Iin-current (programmable)range 4—20 mA
6+24VControl voltage outputVoltage for switches, etc. max. 0.1 A
7GNDControl voltage groundGround for reference and controls
8DIA1Start/StopContact open = stop
9DIA2Interlock input, autoch. 1Contact open = no interlock
10DIA3Interlock input, autoch. 2Contact open = no interlock
11CMACommon for DIA1—DIA3 Connect to GND or + 24V
12+24VControl voltage outputVoltage for switches, (same as #6)
13GNDI/O groundGround for reference and controls
14DIB4Start/StopContact open = stop
15DIB5Jogging speed selectContact open = no action
16DIB6Source A/B selectionContact open = source A is active
17CMBCommon for DIB4—DIB6Connect to GND or + 24V
18I
out
19I
out
20DO1 Digital outputProgrammable ( par. 3. 6)
21RO1Relay output 1Contact closed = control active
22RO1Autochange 1Programmable ( par. 3. 7)
23RO1control
24RO2Relay output 2Contact closed = control active
25RO2Autochange 2Programmable ( par. 3. 8 )
26RO2control
Reference outputVoltage for a potentiometer, etc.
ref
range 0—10 V DC(factory setting: not in use)
Source A (PI-controller)Contact closed = start
(programmable)Contact closed = interlock active
(programmable)Contact closed = interlock active
Source B (Direct freq. ref.) Contact closed = start
(programmable)Contact closed = jogging speed
+Analogue outputProgrammable (par. 3. 1)
-Output frequencyRange 0—20 mA/RL max. 500 Ω
FAULTOpen collector, I<50 mA, U<48 VDC
converter controls the speed of the variable
speed drive and gives control signals to Start
and Stop auxiliary drives to control the total
flow.
The application has two control sources on
I/O terminals. Source A is Pump and fan
control and source B is direct frequency
reference. The control source is selected with
DIB6 input.
Note! Remember to connect CMA and CMB inputs
Contact closed = source B is active
Figure 2-1Default I/O configuration and connection example of the Pump and fan
2 = Read up parameters to user's set
3 = Load down user's set parameters
4 = Read parameters up to the panel
(possible only with graphical panel)
5 = Load down parameters from panel
(possible only with graphical panel)
0.3 Language selection0—1100 = English
1 = Finnish
2= Spanish
0.1 Application selection
With this parameter the active application can be selected. If the device has been ordered
from the factory equipped with pump and fan control with autochange application this has
been loaded to the unit as application 0. The application has also been set active in the factory. Check anyway that the value of the parameter 0.1 is zero when you want to use the
pump and fan control with autochange application.
If the application is loaded to the device later it has to be set active always after loading
by setting the value of parameter 0.1 to zero.
0.2 Parameter loading
See User's manual chapter 11.
0.3 Language
With this parameter the language of the graphical panel can be selected.
1. 10Nominal voltage180—6901 V230 VVacon range CX/CXL28
of the motor400 VVacon range CX/CXL/CXS4
500 VVacon range CX/CXL/CXS5
690 VVacon range CX6
1. 11Nominal frequency30—500 Hz1 Hz50 Hzf
from the rating plate of8
n
of the motorthe motor
1. 12Nominal speed1—20000 rpm 1 rpm 1440 rpmn
from the rating plate of8
n
of the motor**)the motor
1. 13Nominal current2.5 x I
of the motor( I
n Mot)
n CX
0.1 AI
nCX
In from the rating plate of8
the motor
1. 14Supply voltage180—250230 VVacon range CX/CXL28
380—440400 VVacon range CX/CXL/CXS4
380—500500 VVacon range CX/CXL/CXS5
525—690690 VVacon range CX6
1. 15Parameter conceal0—110Visibility of the parameters:8
0 = All parameter groups visible
1 = Only group 1 is visible
1. 16Parameter value lock0—110Disables parameter changes:8
0 = Changes enabled
1 = Changes disabled
Note!=Parameter value can be changed
only when the frequency converter
is stopped.
*) If 1. 2 > motor synchr. speed, check suitability
for motor and drive system
Selecting 120 Hz/500 Hz range see page 6-5.
**) Default value for a four pole motor and a
nominal size frequency converter.
Table 5-1 Group 1 basic parameters.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 7
Pump control with autochange
5.2 Description of Group 1 parameters
1. 1, 1. 2 Minimum / maximum frequency
Defines frequency limits of the frequency converter.
The default maximum value for parameters 1. 1 and 1. 2 is 120 Hz. By setting 1. 2 =
120 Hz when the device is stopped (RUN indicator not lit) parameters 1. 1 and 1. 2
are changed to 500 Hz. At the same time the panel reference resolution is changed
from 0.01 Hz to 0.1 Hz.
Changing the max. value from 500 Hz to 120 Hz is done by setting parameter 1. 2 =
119 Hz when the device is stopped.
NOTICE! Start frequency of the auxiliary drive is not conditional on maximum
frequency because in the application start frequency and stop frequency of the
auxiliary drives are scaled by the endower of the system.
1. 3, 1. 4 Acceleration time 1, deceleration time 1:
These limits correspond to the time required for the output frequency to accelerate
from the set minimum frequency (par. 1. 1) to the set maximum frequency
(par. 1. 2).
1. 5PI-controller gain
This parameter defines the gain of the PI-controller.
If this parameter is set to 100%, a 10% change in error value causes the controller
output to change by 10.0 Hz.
If the parameter value is set to 0 the PI-controller operates as I-controller.
1. 6PI-controller I-time
Defines the integration time of the PI-controller.
1. 7Current limit
This parameter determines the maximum motor current from the frequency converter.
To avoid motor overloading set this parameter according to the rated current of the
motor.
1. 8U/f ratio selection
Linear:The voltage of the motor changes linearly with the frequency in
the constant flux area from 0 Hz to the field weakening point
0(par. 6. 3) where the nominal voltage is supplied to the motor. See
figure 6.4-1.
Linear U/f ratio should be used in constant torque applications.
This default setting should be used if there is no special demand for another
setting.
Squared:The voltage of the motor changes following a squared curve form
with the frequency in the area from 0 Hz to the field weakening
1point (par. 6. 3) where the nominal voltage is supplied to the motor.
See figure 6.4-1.
The motor runs undermagnetised below the field weakening point
and produces less torque and electromechanical noise. Squared U/f
ratio can be used in applications where torque demand of the load is
proportional to the square of the speed, e.g. in centrifugal fans and
Programm. The U/f curve can be programmed with three different points.
U/f curveThe parameters for programming are explained in the chapter 5.2.
2The programmable U/f curve can be used if the other settings do not
satisfy the needs of the application. See figure 4-2.
U[V]
Un
Par 6. 4
Par. 6. 6
(Olet. 10%)
Par. 6. 7
(Olet. 1.3%)
Default: nominal
voltage of the
motor
Par. 6. 5
(Olet. 5 Hz)
Field weakening
point
Default: nominal frequency
of the motor
Par. 6. 3
f[Hz]
UD009K08
Figure 6.4-2 Programmable U/f curve.
1. 9U/f optimization
AutomaticThe voltage to the motor changes automatically which makes the
torquemotor to produce torque enough to start and run at low frequencies.
boostThe voltage increase depends on the motor type and power.
Automatic torque boost can be used in applications where starting
torque is high due to starting friction, e.g. in conveyors.
NOTE!In high torque - low speed applications - it is likely the motor will
overheat. If the motor has to run a prolonged time under these
!
conditions, special attention must be paid to cooling the motor. Use
external cooling for the motor if the temperature tends to rise too high.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 9
Pump control with autochange
1. 10Nominal voltage of the motor
Find this value U
on the rating plate of the motor.
n
This parameter sets the Voltage at the field weakening point, parameter 6. 4, to
100% x U
n
motor
.
1. 11Nominal frequency of the motor
Find this value f
on the rating plate of the motor.
n
This parameter sets the field weakening point, parameter 6. 3, to the
same value.
1. 12Nominal speed of the motor
Find this value n
on the rating plate of the motor.
n
1. 13Nominal current of the motor
Find this value I
on the rating plate of the motor.
n
1. 14Supply voltage
Set parameter value according to the nominal voltage of the supply.
Values are pre-defined for CX/CXL2, CX/CXL/CXS4, CX/CXL/CXS5 and CX6
ranges, see table 6.4-1.
1. 15Parameter conceal
Defines which parameter groups are available:
0 = All parameter groups are visible
1 = Only group 1 is visible
1. 16Parameter value lock
Defines access to the changes of the parameter values:
0 = Parameter value changes enabled
1 = Parameter value changes disabled
2. 34 Option board Ain2 signal0 —10s0.01s0.1s0 = No filtering25
filter time
Pump and fan control with autochange
signal (control board) 24
in
2 = Set reference from the panel
(reference r1)
3 =
Signal from internal motor pot.
4 =
Signal from internal motor pot.
reset if Vacon unit is stopped
par.2. 281 Hz0 HzSelects the frequency that 24
max
corresponds to the max.
reference signal
0 = Scaling off
>0 = Scaled maximum value
signal (control board) 25
in
2 = Set reference from the panel
(reference r2)
3 =
Signal from internal motor pot.
4 =
Signal from internal motor pot.
reset if Vacon unit is stopped
5 = Option board Ain1-signal
6 = Option board Ain2-signal
7 = Set reference from the panel
(reference r3)
2 = 0—10 V
Note! = Parameter value can be changed only when the frequency converter is stopped (Continues)
3. 1Analogue output function0—15110 = Not used
1 = O/P frequency
Scale 100%26
(0—f
)
max
2 = Motor speed(0—max. speed)
3 = O/P current(0—2.0 x I
4 = Motor torque(0—2 x T
5 = Motor power(0—2 x P
6 = Motor voltage (0—100% xU
nCX
nCX
nCX
)
)
)
)
nM
7 = DC-link volt.(0—1000 V)
8—10 = Not in use
11 = PI-controller reference value
12 = PI-controller actual value 1
13 = PI-controller actual value 2
14 = PI-controller error value
15 = PI-controller output
3. 2
Analogue output filter time
3. 3
Analogue output inversion
0.01—10 s0.011.00 26
0—1100 = Not inverted26
1 = Inverted
3. 4
Analogue output minimum
0—1100 = 0 mA 26
1 = 4 mA
3. 5Analogue output scale10—1000%1%100% 26
3. 6Digital output function0—30130 = Not used 27
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = Vacon overheat warning
6 = External fault or warning
7 = Reference fault or warning
8 = Warning
9 = Reversed
10 = Jogging speed selected
11 = At speed
12 = Motor regulator activated
13 = Output freq. limit superv. 1
14 = Output freq. limit superv. 2
15 = Torque limit supervision
16 = Reference limit supervision
17 = External brake control
18 = Control from I/O terminals
19 = Frequency converter
temperature limit supervision
20 =
Unrequested rotation direction
21 = External brake control inverted
22 = Analogue input supervision
22—26 = Not in use
27 =Autochange 3 control
28 = Auxiliary drive 1 start
29 = Auxiliary drive 2 start
30 = Auxiliary drive 3 start
3. 7Relay output 1 function
0—311260-25 = As parameter 3. 627
26 = Autochange 1 control
27 = Autochange 4 control
28-30 = As parameter 3. 6
31 = Aux. drive 4 start
3. 8Relay output 2 function0—301260-25 = As parameter 3. 628
26 = Autochange 2 control
27 = Autochange 5 control
28-30 = As parameter 3. 6
Note! = Parameter value can be changed only when the frequency converter is stopped. (Continues)
go before starting the sleep delay
counting ( 0.0 = not in use)
par. 9.16 before stopping Vacon
restarting Vacon
Level % from actual max. value
1 = Wake up exceeding the level
Level % from actual max. value
2 = Wake up falling below the level
Level % from current reference
3 = Wake up exceeding the level
Level % from current reference
Note! =Parameter value can be changed only when the frequency converter is stopped.(Continues)
1: External fault, closing contact = Fault is shown and motor is stopped when
the input is active
2: External fault, opening contact = Fault is shown and motor is stopped when
the input is not active
3: Run enablecontact open= Start of the motor disabled
contact closed= Start of the motor enabled
4: Acc. / Deccontact open= Acceleration/Deceleration time 1 selected
time select.contact closed= Acceleration/Deceleration time 2 selected
5: Reversecontact open= Forward
If two or more inputs are progr.
contact closed= Reverseto reverse then if one of them is
active the direction is reverse
6: Jogging freq.contact closed= Jogging frequency selected for freq. refer.
7: Fault resetcontact closed= Resets all faults
8: Acc./Dec.contact closed= Stops acceleration and deceleration until
operation the contact is opened
prohibited
9: DC-brakingcontact closed= In the stop mode, the DC-braking operates
command until the contact is opened, see figure 6-1.
Dc-brake current is set with parameter 4. 8.
10: Motor pot. contact closed = Reference increases until the contact is
UP opened
11: Interlock inp., contact closed = Interlock of autochange drive 1 is active
autochange 1
Output
frequency
DIA3
RUN
STOP
DIA3 as DC-brake command input and stop-mode = Ramp
DIA3 as DC-brake command input and stop-mode = Coasting
Param. 4. 10
t
UD009K32
t
UD009K32
Page 22 Vacon
Pump and fan control with autochange
2. 2DIA3 function
Selections are the same as in 2. 1 except :
10:Motor pot. contact closed = Reference decreases until the contact is
DOWN opened
2. 3U
signal range
in
0 =Signal range 0—10 V
1 =Custom setting range from custom minimum (par. 2. 4) to custom
maximum (par. 2. 5)
2 =Signal range 2—10 V
2. 4U
2. 5With these parameters you can set U
custom setting minimum/maximum
in
for any input signal span of 0—10 V.
in
Minimum setting:Set the Uin signal to its minimum level, select parameter 2. 4,
press the Enter button
Maximum setting: Set the Uin signal to its maximum level, select parameter 2. 5,
press the Enter button
Note!The parameter values can only be set with this procedure (not with arrow up/arrow
down buttons)
2. 6U
2. 7U
signal inversion
in
Parameter 2. 6 = 1, inversion of analogue U
signal filter time
in
Filters out disturbances from the
incoming analogue U
signal.
in
Long filtering time makes regulation
%
100%
signal.
in
Unfiltered signal
response slower.
See figure 6-2.
Filtered signal
63%
Figure 6-2 U
signal filtering
in
Par. 2. 7
2. 8Analogue inputIin signal range
0 = 0—20 mA
1 = 4—20 mA
2 = Custom signal span
2. 9Analogue input Iin custom setting
2. 10minimum/maximum
With these parameters you can scale the input current signal (Iin) signal range
between 0 and 20 mA. See par. 2. 4 and 2. 5.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
t [s]
UD009K15
Vacon Page 23
Pump control with autochange
2. 11Analogue input I
Parameter 2. 11 = 1, inversion of I
2. 12Analogue input I
Filters out disturbances from the
incoming analogue I
Long filtering time makes
regulation response slower.
See figure 6-3.
Figure 6-3 Analogue input Iin filter
time
2. 13DIA5 function
inversion
in
filter time
in
signal.
in
input.
in
100%
63%
%
Unfiltered signal
Filtered signal
t [s]
Par. 2. 12
UD009K30
1: External fault, closing contact = Fault is shown and motor is stopped when
the input is active
2: External fault, opening contact = Fault is shown and motor is stopped when
the input is not active
3: Run enablecontact open= Start of the motor disabled
contact closed= Start of the motor enabled
4: Acc. / Deccontact open= Acceleration/Deceleration time 1 selected
time select.contact closed= Acceleration/Deceleration time 2 selected
5: Reversecontact open= Forward
If two or more inputs are
contact closed= Reverseprogrammed to reverse then
if one of them is active the
direction is reverse
6: Jogging freq.contact closed= Jogging frequency selected for freq. refer.
7: Fault resetcontact closed= Resets all faults
8: Acc./Dec.contact closed= Stops acceleration and deceleration until
operation the contact is opened
prohibited
9: DC-brakingcontact closed= In the stop mode, the DC-braking operates
command until the contact is opened, see figure 6-1.
DC-brake current is set with parameter 4. 8.
10: PI-contr. ref.contact closed= reference 2 (selected with par. 2.29) is
selection active
11: Interlock inp. contact closed = Interlock of autochange drive 3 is active
autochange 3
2. 14Motor potentiometer ramp time
Defines how fast the electronic motor potentiometer value changes.
0Analogue voltage reference from terminals 2—3, e.g. a potentiometer
1Analogue current reference from terminals 4—5, e.g. a transducer.
2Panel reference is the reference set from the Reference Page (REF).
Reference r2 is the PI-controller reference, see chapter 6.
3Reference value is changed with digital input signals DIA2 and DIA3.
- switch in DIA2 closed = frequency reference increases
- switch in DIA3 closed = frequency reference decreases
Speed of the reference change can be set with the parameter 2. 3.
4Same as setting 3 but the reference value is set to the minimum frequency
(par. 1. 1) each time the frequency converter is stopped. When value of the
parameter 1. 5 is set to 3 or 4, value of the parameter 2.1 is automatically set
to 4 and value of the parameter 2. 2 is automatically set to 10.
5Analogue voltage signal from the terminals 202—203 of the I/O-expander
6Analogue signal from the terminals 204—205 of the I/O-expander
- current signal, Vacon CX 100 OPT
- voltage signal, Vacon CX 102 OPT
7Fieldbus signal
2. 16PI-controller actual value selection
0Actual value 1
1Sum of Actual value 1 and Actual value 2
2Difference of Actual value 1 and Actual value 2
3Multiplication of Actual value 1 and Actual value 2
4Minor of signals Actual value 1 and Actual value 2 is active actual value
5Major of signals Actual value 1 and Actual value 2 is active actual value
6Mean value of Actual value 1 and Actual value 2 signals
7Sum of square roots from Actual value 1 and Actual value 2
2. 17Actual value 1
2. 18Actual value 2
0No signal
1Analogue voltage reference from terminals 2—3
2Analogue current reference from terminals 4—5
3Analogue voltage signal from the terminals 202—203 of the I/O-expander
4Analogue signal from the terminals 204—205 of the I/O-expander
- current signal, Vacon CX 100 OPT
- voltage signal, Vacon CX 102 OPT
5Fieldbus signal
2. 19Actual value 1 minimum scale
Sets the minimum scaling point for Actual value 1. See figure 6-4.
2. 20Actual value 1 maximum scale
Sets the maximum scaling point for Actual value 1. See figure 6-4.
2. 21Actual value 2 minimum scale
Sets the minimum scaling point for Actual value 2. See figure 6-4
2. 22Actual value 2 maximum scale
Sets the maximum scaling point for Actual value 2. See figure 6-4
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 25
Pump control with autochange
Scaled
input signal [%]
100
Par. 2. 19 = 30%
Par. 2. 20 = 80%
0
0
0
4
1008030
10.0 V
8.03.0
20.0 mA
16.06.0
16.88.820.0 mA
2. 23Error value inversion
This parameter allows you to invert the error value of the PI-controller (and thus the
operation of the PI-controller).
Figure 6-4 Examples about the scaling of actual value signal.
2. 24PI-controller minimum limit
2. 25PI-controller maximum limit
These parameters set the minimum and maximum values of the PI-controller output.
Parameter value limits: par 1.1 <par. 2. 24 <par. 2. 25.
Analogue
input [%]
(15.3 mA)
-30
100
76.5
17.7
(3.5 mA)
Scaled
input signal [%]
Par. 2. 19 = -30%
Par. 2. 20 = 140%
0
0
0
4
100140
10.0 V
20.0 mA
20.0 mA
Analogue
input [%]
UD012K34
2. 26Direct frequency reference, Place B
0Analogue voltage reference from terminals 2—3, e.g. a potentiometer
1Analogue current reference from terminals 4—5, e.g. a transducer.
2Panel reference is the reference set from the Reference Page(REF),
Reference r1 is the Place B reference, see chapter 6.
3Reference value is changed with digital input signals DIA2 and DIA3.
- switch in DIA2 closed = frequency reference increases
- switch in DIA3 closed = frequency reference decreases
Speed of the reference change can be set with the parameter 2. 3.
4Same as setting 3 but the reference value is set to the minimum frequency
(par. 1. 1) each time the frequency converter is stopped. When value of the
parameter 1. 5 is set to 3 or 4, value of the parameter 2. 1 is automatically set
to 4 and value of the parameter 2. 2 is automatically set to 10.
2. 27Place B reference scaling, minimum value/maximum value
0Analogue voltage reference from terminals 2—3, e.g. a potentiometer
1Analogue current reference from terminals 4—5, e.g. a transducer.
2Panel reference is the reference set from the Reference Page (REF).
Reference r2 is the PI-controller reference, see chapter 6.
3Reference value is changed with digital input signals DIA2 and DIA3.
- switch in DIA2 closed = frequency reference increases
- switch in DIA3 closed = frequency reference decreases
Speed of the reference change can be set with the parameter 2. 3.
4Same as setting 3 but the reference value is set to the minimum frequency
(par. 1. 1) each time the frequency converter is stopped. When value of the
parameter 1. 5 is set to 3 or 4, value of the parameter 2.1 is automatically set
to 4 and value of the parameter 2. 2 is automatically set to 10.
5Analogue voltage signal from the terminals 202—203 of the I/O-expander
6Analogue signal from the terminals 204—205 of the I/O-expander
- current signal, Vacon CX 100 OPT
- voltage signal, Vacon CX 102 OPT
7Panel reference r3, can be set on the Reference Page (REF) of the panel.
100
UD012K35
Analogue
input [V]
2. 30Ain1
signal inversion (I/O-expander)
Parameter 2. 30 = 0, no inversion
2. 31Ain1
signal filter time
Filters out disturbances from the incoming analogue Ain1 signal. Long filtering time
makes regulation response slower.
2. 32Ain2 input (I/O-expander) signal range
0 = 0—20 mA
1 = 4—20 mA
2 = 0-10 V (must be used with 102 OPT)
2. 33Ain2
signal inversion (I/O-expander)
Parameter 2. 33 = 0, no inversion
2. 34Ain2
signal filter time
Filters out disturbances from the incoming analogue Ain2 signal. Long filtering time
makes regulation response slower.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 27
Pump control with autochange
3. 1Analogue output function
See table on page 13.
3. 2Analogue output filter time
Filters the analogue output signal.
See figure 6-7.
Figure 6-7 Analogue output filtering.
3.3Analogue output invert
Inverts analogue output signal:
max. output signal = minimum set
value
min. output signal = maximum set
value
%
100%
63%
Analogue
output
current
20 mA
12 mA
10 mA
Unfiltered signal
Par. 3. 2
Filtered signal
t [s]
UD009K16
Param. 3. 5
= 50%
Figure 6-8 Analogue output invert.
3. 4Analogue output minimum
Defines the signal minimum to
be either 0 mA or 4 mA (living
zero). See figure 6-9.
3. 5Analogue output scale
Scaling factor for analogue output.
See figure 6-9.
SignalMax. value of the signal
Output freq.Max. frequency (p. 1. 2)
Motor speedMax. speed (n
Output2 x I
current
Motor torque2 x T
Motor power2 x P
Motor voltage 100% x U
nCX
nCX
nCX
DC-link volt.1000 V
PI-ref. value100% x ref. value max.
PI-act. value1 100% x act. value max.
PI-act. value2 100% x act. value max.
PI-error value 100%x error value max.
PI-output100% x output max.
Digital output DO1 sinks current and programmable
relay (RO1, RO2) is activated when:
1 = ReadyThe frequency converter is ready to operate
2 = RunThe frequency converter operates (motor is running)
3 = FaultA fault trip has occurred
4 = Fault invertedA fault trip
5 = Vacon overheat warningThe heat-sink temperature exceeds +70°C
6 = External fault or warningFault or warning depending on parameter 7. 2
7 = Reference fault or warningFault or warning depending on parameter 7. 1
- if analogue reference is 4—20 mA and signal is <4mA
8 = WarningAlways if a warning exists
9 = ReversedThe reverse command has been selected
10= Multi-step or jogging speedMulti-step or jog. speed has been selected with digital
input
11 = At speedThe output frequency has reached the set reference
12 = Motor regulator activatedOvervoltage or overcurrent regulator was activated
13 = Output frequency supervision 1The output frequency goes beyond the set supervision
Low limit/ High limit (par. 3. 9 and par. 3. 10)
14= Output frequency supervision 2The output frequency goes beyond the set supervision
Low limit/ High limit (par. 3. 11 and par. 3. 12)
15= Torque limit supervisionThe motor torque goes beyond the set supervision
Low limit/ High limit (par. 3. 13 and par. 3. 14)
16= Active referenceActive reference goes beyond the set supervision
limit supervisionLow limit/ High limit (par. 3. 15 and par. 3. 16)
17 = External brake controlExternal brake ON/OFF control with programmable de
lay (par 3. 17 and 3. 18)
18 = Control from I/O terminalsExternal control mode selected with pr. push-button #2
19 = Frequency converterTemperature on frequency converter goes beyond
temperature limit supervisionset supervision limits (par. 3. 19 and 3. 20)
20 = Unrequested rotation directionRotation direction of the motor shaft is different from the
requested one
21 = External brake control invertedExternal brake ON/OFF control (par. 3.17 and 3.18),
output active when brake control is ON
22= Analog input limit supervisionThe level of selected analog input goes beyond the
set supervision low / high limit (par. 3. 29 and par. 3. 30)
23—26 = Not in use
27 = Autochange 3 controlControl signal for drive 3 in autochange system
28 = Auxiliary drive 1 startStarts and stops auxiliary drive 1
29 = Auxiliary drive 2 startStarts and stops auxiliary drive 2
30 = Auxiliary drive 3 startStarts and stops auxiliary drive 3
has not occurred
Table 6-3a Output signals via DO1
3. 7Relay output 1 content
Setting valueSignal content
0-22 = Same as parameter 3.6
23—25 = Not in use
26 = Autochange 1 controlControl signal for drive 1 in autochange system
27 = Autochange 4 controlControl signal for drive 1 in autochange system with
0-22 = Same as parameter 3.6
23—25 = Not in use
26 = Autochange 2 controlControl signal for drive 2 in autochange system
27 = Autochange 5 controlControl signal for drive 5 in autochange system with
3. 9Output frequency limit 1,
supervision function
3. 11Output frequency limit 2,
f[Hz]
supervision function
0 = No supervision
Par 3. 10
1 = Low limit supervision
2 = High limit supervision
Par. 3.9 = 2
If the output frequency goes under/
over the set limit (3. 10, 3. 12) this
function generates a warning
message via the digital output DO1
Example:
21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
UD009K19
21 RO1
22 RO1
23 RO1
or via the relay output RO1 or RO2
depending on the settings of the
Figure 6-10 Output frequency supervision.
parameters 3. 6—3. 8.
t
3. 10Output frequency limit 1, supervision value
3. 12Output frequency limit 2, supervision value
The frequency value to be supervised by the parameter 3. 9 (3. 11).
See figure 6-10.
3. 13Torque limit, supervision
function
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the calculated torque value goes under/over the set limit (3. 14) this function
generates a warning message via the digital output DO1 or via a relay output RO1
or RO2 depending on the settings of the parameters 3. 6—3. 8.
3. 14Torque limit, supervision value
The calculated torque value to be supervised by the parameter 3. 13.
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the reference value goes under/over the set limit (3. 16) this function generates a
warning message via the digital output DO1 or via a relay output RO1 or
RO2 depending on the settings of the parameters 3. 6—3. 8. The supervised
reference is the current active reference. It can be source A or B reference depending
on DIB6 input or panel reference if the panel is the active control source.
3. 16Active reference limit, supervision value
The frequency value to be supervised by the parameter 3. 15.
3. 17External brake-off delay
3. 18External brake-on delay
With these parameters the timing of external brake can be linked to the Start
and Stop control signals, see figure 6-11.
The brake control signal can be programmed via the digital output DO1 or via one
of relay outputs RO1 and RO2, see parameters 3. 6—3. 8.
The temperature value to be supervised by the parameter 3. 20.
3. 19Frequency converter temperature limit supervision function
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the temperature of the frequency converter goes under/over the set limit (3. 20)
this function generates a warning message via the digital output DO1 or via a relay
output RO1 or RO2 depending on the settings of the parameters 3. 6—3. 8.
3. 20Frequency converter temperature limit value
The temperature value to be supervised by the parameter 3. 19.
3. 26Analogue output offset
3. 27I/O-expander analogue output offset
With these parameters can be set the offsets of the basic control board and I/Oexpander analogue outputs. See figure 6-12.
Analogue
output
current
20 mA
Param. 3. 5
= 100%
Param. 3. 26
= -30%(-6mA)
Param. 3. 26
= 25% (+5 mA)
Maximum value of
0 mA
0
0.5
selected signal
1.0
Figure 6-12 Analogue output offset
3. 28Analogue input supervision, input signal selection
0Analogue voltage signal from terminals 2—3
1Analogue current signal from terminals 4—5
2Analogue voltage signal from terminals 202—203 of the I/O-expander
3Analogue signal from the terminals 204—205 of the I/O-expander
- current signal, Vacon CX 100 OPT
- voltage signal, Vacon CX 102 OPT
3. 29Analoque input supervision function
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
ao-offse.fh3
If the value of the selected analogue input (par. 3.28) goes under/over the set limit
(3. 30) this function generates a warning message via the digital output DO1 or via
a relay output RO1 or RO2 depending on the settings of the parameters 3. 6—3. 8.
3. 30Analoque input supervision limit value
The value of the analogue input to be supervised by the parameter 3. 29.
The start and end of the acceleration and deceleration ramps can be smoothed with
these parameters. Setting value 0 gives a linear ramp shape which causes
acceleration and deceleration to react immediately to the changes in the reference
signal with the time constant set by the parameter 1. 3 and 1. 4 (4. 3 and 4. 4).
Setting value 0.1—10 seconds for 4.1 (4.2) causes linear acceleration/deceleration
to adopt an S-shape. Parameters 1. 3 and 1. 4 (4. 3 and 4. 4) determine the time
constant of acceleration/deceleration in the middle of the curve.
See figure 6-13.
4. 3Acceleration time 2
4. 4Deceleration time 2
These values correspond to the time required for the output frequency to accelerate
from the set minimum frequency (par. 1. 1) to the set maximum frequency
(par. 1. 2). These times give the possibility to set two different acceleration/
deceleration time sets for one application. The active set can be selected with the
programmable signal DIA3 of this application, see parameter 2. 2. Acceleration/
deceleration times can be reduced with an external free analogue input signal, see
parameters 2. 18 and 2. 19.
4. 5Brake chopper
0 = No brake chopper
1 = Brake chopper and brake resistor installed
2 = External brake chopper
When the frequency converter is decelerating the motor, the inertia from the motor
and the load is fed into the external brake resistor. This enables the frequency
converter to decelerate the load with the torque equal to that of acceleration, if the
brake resistor is selected correctly. See separate Brake resistor installation manual.
[Hz]
1. 3, 1. 4
(4. 3, 4. 4)
4. 1 (4. 2)
4. 1 (4. 2)
Figure 6-13 S-shaped acceleration / deceleration.
[t]
UD009K20
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 33
Pump control with autochange
4. 6Start function
Ramp:
0The frequency converter starts from 0 Hz and accelerates to the set reference
frequency within the set acceleration time. (Load inertia or starting friction may
cause prolonged acceleration times).
Flying start:
1The frequency converter is able to start into running motor by applying a small
torque to motor and searching for frequency corresponding to the speed the
motor is running at. Searching starts from the maximum frequency towards
the actual frequency until the correct value is detected. Thereafter the output
frequency will be accelerated/decelerated to the set reference value according
to the set acceleration/deceleration parameters.
Use this mode if the motor may be coasting when the start command is given.
With the flying start it is possible to ride through short mains voltage
interruptions.
4. 7Stop function
Coasting:
0The motor coasts to a halt without any control from the frequency converter,
after the Stop command.
Ramp:
1After the Stop command, the speed of the motor is decelerated according to
the set deceleration parameters. If the regenerated energy is high it may be
necessary to use an external braking resistor for faster deceleration.
4. 8DC braking current
Defines the current injected into the motor during the DC braking.
Defines if braking is ON or OFF and braking time of the DC-brake when the motor is
stopping. The function of the DC-brake depends on the stop function, parameter 4.
7. See figure 6-14.
0DC-brake is not used
>0DC-brake is in use and its function depends on the Stop function,
(param. 4. 7), and the time depends on the value of parameter 4. 9:
Stop-function = 0 (coasting):
After the stop command, the motor coasts to a stop without any control from
the frequency converter.
With DC-injection, the motor can be electrically stopped in the shortest possible
time, without using an optional external braking resistor.
The braking time is scaled according to the frequency when the DC-
braking starts. If the frequency is >nominal frequency of the motor (par. 1.11),
the setting value of parameter 4.9 determines the braking time. When the
frequency is <10% of the nominal, the braking time is 10% of the set
value of parameter 4.9.
f
f
n
RUN
STOP
out
Output frequency
Motor speed
DC-braking ON
t
t = 1 x par. 4. 9
f
n
0,1x f
RUN
STOP
f
Figure 6-14 DC-braking time when par. 4. 7 = 0.
Stop-function = 1 (ramp):
After the Stop command,
the speed of the motor is
reduced according to the
set deceleration parameters, as fast as
possible, to a speed
defined with the parameter
4. 10, where the DC-
Param. 4. 10
braking starts. The braking
time is defined with parameter 4. 9. If high inertia
exists, it is recommended
RUN
STOP
to use an external braking
resistor for faster
Figure 6-15 DC-braking time when par. 4. 7 = 1.
deceleration. See figure
6-15.
out
f
out
Output frequency
Motor speed
n
DC-braking ON
t = 0.1 x par. 4. 9
Motor speed
Output frequency
DC-braking
t = param. 4. 9
t
UD009K21
t
UD009K23
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 35
Pump control with autochange
4. 10Execute frequency of DC-brake during ramp Stop
See figure 6-15.
4. 11DC-brake time at start
0DC-brake is not used
>0DC-brake is activated when
the start command is given
and this parameter defines
the time before the brake is
released. After the brake is
released, the output frequency increases according to the set start function
parameter
4.6 and accelera-
tion parameters (1. 3, 4. 1 or
4.2, 4.3), see figure 6-16.
Figure 6-16 DC-braking time at start
4. 12Jogging speed reference
Parameter value defines the jogging speed selected with the digital input.
5. 1Prohibit frequency area,
5. 2Low limit/High limit
5. 3
5. 4
5. 5
5. 6
Output
frequency
RUN
STOP
f
out
[Hz]
t
Par 4. 11
UD009K22
In some systems it may be
necessary to avoid certain
frequencies because of
mechanical resonance problems.
With these parameters it is
possible to set limits for three "skip
frequency" regions.
Figure 6-17 Example of prohibit
frequency area setting.
6. 1Motor control mode
0 = Frequency control:The I/O terminal and panel references are frequency
1 = Speed control:The I/O terminal and panel references are speed
frequency
reference
5. 1 5. 2
5. 3 5. 4
5. 5 5. 6
[Hz]
UD009K33
references and the frequency converter controls the
output frequency (output freq. resolution 0,01 Hz)
references and the frequency converter controls the
motor speed (regulation accuracity ± 0,5%).
Motor noise can be minimized by using high switching frequency. Increasing the
frequency reduces the capacity of the frequency converter. Before changing the
frequency from the factory default 10 kHz (3.6 kHz from 30 kW upwards), check the
allowed capacity from the curves in the figure 5.2-3 of the User's Manual.
6. 3Field weakening point
6. 4Voltage at the field weakening point
Field weakening point is the output frequency where the output voltage reaches the
set maximum value (par. 6. 4). Above that frequency the output voltage remains at
the set maximum value.
Below that frequency output voltage depends on the setting of the U/f curve
parameters 1. 8, 1. 9, 6. 5, 6. 6 and 6. 7. See figure 6-18.
When the parameters 1. 10 and 1. 11, nominal voltage and nominal frequency of
the motor, are set, also parameters 6. 3 and 6. 4 are set automatically to the
corresponding values. If different values for the field weakening point and
the maximum output voltage are required, change these parameters
after setting
the parameters 1. 10 and 1. 11.
6. 5U/f curve, middle point frequency
If the programmable U/f curve has been selected with the parameter 1. 8 this
parameter defines the middle point frequency of the curve. See figure 6-18.
6. 6U/f curve, middle point voltage
If the programmable U/f curve has been selected with the parameter 1. 8 this
parameter defines the middle point voltage (% from motor nom. voltage) of the
curve. See figure 6-18.
6. 7Output voltage at zero frequency
If the programmable U/f curve has been selected with the parameter 1. 8 this
parameter defines the zero frequency voltage of the curve. See figure 6-18.
U[V]
Un
Par 6. 4
Par. 6. 6
(Olet. 10%)
Par. 6. 7
(Olet. 1.3%)
Par. 6. 5
(Olet. 5 Hz)
Par. 6. 3
f[Hz]
UD009K08
Figure 6-18 Programmable U/f curve.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 37
Pump control with autochange
6. 8Overvoltage controller
6. 9Undervoltage controller
These parameters allow the over/undervoltage controllers to be switched out of
operation. This may be useful, for example, if the mains supply voltage varies more
than -15%—+10% and the application will not tolerate this over-/undervoltage, the
regulator controls output frequency according to the supply fluctuations.
Over/undervoltage trips may occur when controllers are switched out of operation.
7. 1Response to the reference fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated if 4—20 mA reference signal
is used and the signal falls below 4 mA. The information can also be programmed
via digital output DO1 and via relay outputs RO1 and RO2.
7. 2Response to external fault
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to parameter 4.7
3 = Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated from the external fault signal
in the digital input DIA3. The information can also be programmed into digital output
DO1 and into relay outputs RO1 and RO2.
7. 3Phase supervision of the motor
0 = No action
2 = Fault
Phase supervision of the motor ensures that the motor phases have approximately
equal current.
7. 4Earth fault protection
0 = No action
2 = Fault message
Earth fault protection ensures that the sum of the motor phase currents is zero.
The overcurrent protection is always working and protects the frequency converter
from earth faults with high currents.
Parameters 7. 5—7. 9 Motor thermal protection
General
Motor thermal protection is to protect the motor from overheating. Vacon CX/CXL/CXS drive is
capable of supplying higher than nominal current to the motor. If the load requires this high current
there is a risk that motor will be thermally overloaded. This is true especially at low frequencies.
With low frequencies the cooling effect of the motor is reduced and the capacity of the motor is
reduced. If the motor is equipped with an external fan the load reduction on low speeds is small.
Motor thermal protection is based on a calculated
model and it uses the output current of the drive to
determine the load on the motor. When the power
is turned on to the drive, the calculated model uses
the heatsink temperature to determine the initial
thermal stage for the motor. The calculated model
assumes that the ambient temperature of the motor
is 40°C.
Motor thermal protection can be adjusted by setting
the parameters. The thermal current IT specifies
the load current above which the motor is overloaded.
This current limit is a function of the output
frequency. The curve for IT is set with parameters 7.
6, 7. 7 and 7. 9 (refer to the figure 5-18). The
parameters have their default values set from the
motor name plate data.
!
CAUTION!
The calculated model does not protect the motor if the airflow to the
motor is reduced by blocked air intake grill.
7. 5Motor thermal protection
With the output current at IT the thermal stage will
reach the nominal value (100%). The thermal stage
changes by the square of the current. With output
current at 75% of IT the thermal stage will reach
56% level and with output current at 120% from I
the thermal stage would reach 144% level. The
function will trip the device (refer par. 7. 5) if the
thermal stage will reach a value of 105%. The speed
of change in thermal stage is determined with the
time constant parameter 7. 8. The bigger the motor
the longer it takes to reach the final temperature.
The thermal stage of the motor can be monitored
through the display. Refer to the table for monitoring
items. (User's Manual, table 7.3-1).
T
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will display the same message code. If the tripping is selected
the drive will stop and activate the fault stage.
Deactivating the protection, setting parameter to 0, will reset the thermal stage of
the motor to 0%.
7. 6Motor thermal protection, break point current
The current can be set between 50.0—150.0% x I
This parameter sets the value for thermal current at frequencies above the
break point on the thermal current curve. Refer to the figure 6.5-18.
The value is set in percentage which refers to the name plate data of the
motor, parameter 1. 13, nominal current of the motor, not the drive's nominal output
current.
The motor's nominal current is the current which the motor can withstand in direct
on-line use without being overheated.
If parameter 1. 13 is adjusted, this parameter is automatically restored to the default
value.
nMotor
.
Setting this parameter (or parameter 1. 13) does not affect the maximum output
current of the drive. Parameter 1. 7 alone determines the maximum output
current of the drive.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 39
Pump control with autochange
I
Current
limit
par. 1. 7
Par. 7. 6
Par. 7. 7
Figure 6-19 Motor thermal current
IT curve.
7. 7Motor thermal protection, zero frequency current
The current can be set between 10.0—150.0% x I
nMotor
value for thermal current at zero frequency. Refer to the figure 5-18.
The default value is set assuming that there is no external fan cooling the motor. If
an external fan is used this parameter can be set to 90% (or even higher).
The value is set as a percentage of the motor
name plate data, parameter 1. 13, motor's
nominal current, not the drive's nominal
output current. Motor's nominal current is the
current which the motor can stand in direct
on-line use without being overheated.
If you change the parameter 1. 13 this
parameter is automatically restored to the
default value.
Setting this parameter (or parameter 1. 13)
does not affect to the maximum output
current of the drive. Parameter 1. 7 alone
determines the maximum output current of
the drive.
Overload area
Par. 7. 9
. This parameter sets the
f
UMCH7_91
I
T
7. 8Motor thermal protection, time constant
The time can be set between 0.5—300 minutes.This
is the thermal time constant of the motor. The bigger the motor the bigger the time
constant. The time constant is the time when the calculated thermal stage has
reached 63% of its final value.
The motor thermal time is specific for the
motor design and it varies between different
motor manufacturers.
The default value for the time constant is
calculated on the basis of the motor name
plate data given with parameters 1. 12 and
1. 13. If either of these parameters is set,
then this parameter is set to default value.
If the motor's t6 -time is known (given by the
motor manufacturer) the time constant
parameter could be set based on t6 -time.
As a rule of thumb, the motor thermal time
constant in minutes equals to 2xt6 (t6 in
seconds is the time a motor can safely
operate at six times the rated current). If the
drive is in stop stage the time constant is
internally increased to three times the set
parameter value. The cooling in the stop stage
is based on convection and the time constant
is increased.
Page 40 Vacon
Pump and fan control with autochange
7. 9Motor thermal protection, break point frequency
The frequency can be set between 10—500 Hz.This
is the break point of thermal current curve. With frequencies above this point the
thermal capacity of the motor is assumed to be constant. Refer to the figure 6-19.
The default value is based on the motor's name plate data, parameter 1. 11. It is 35
Hz for a 50 Hz motor and 42 Hz for a 60 Hz motor. More generally, it is 70% of the
frequency at field weakening point (parameter 6. 3). Changing either parameter 1.
11 or 6. 3 will restore this parameter to its default value.
Motor temperature
Figure 6-20 Calculating motor temperature
Trip area
105%
Motor
current
I/I
T
Time constant T
Motor temperature
*)
adjusted with parameter 7. 8
*)
Θ = (I/IT)2 x (1-e
Changed with motor size and
Trip/warning
par. 7. 5
-t/T
)
Time
UMCH7_92
Parameters 7. 10— 7. 13, Stall protection
General
Motor stall protection protects the motor from short time overload situations caused by e.g. a
stalled shaft. The reaction time of stall protection can be set shorter than that of motor thermal
protection. The stall state is defined with two parameters, 7.11. Stall Current and 7.13. Stall
Frequency. If the current is higher than the set limit and output frequency is lower than the set
limit the stall state is true. There is actually no real indication of the shaft rotation. Stall protection
is a type of overcurrent protection.
7. 10Stall protection
Operation:
0 = Not in use
1 = Warning
2 = Trip function
Tripping and warning will display the same message code. If the tripping is set on,
the drive will stop and activate the fault stage.
Setting the parameter to 0 will deactivate the protection and will reset the stall time
counter to zero.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 41
Pump control with autochange
7. 11Stall current limit
The current can be set between
0.0—200% x I
nMotor
In the stall stage the current has to
beabove this limit. Refer to the
figure6-21. The value is set as a
percentage of the motor's name
plate data, parameter 1. 13,
motor's nominal current. If
parameter 1. 13 is adjusted, this
parameter is automatically
restored to the default value.
Figure 6-21 Setting the stall
characteristics.
7. 12Stall time
The time can be set between 2.0—120 s.
This is the maximum allowed time for a stall stage. There is an internal up/down
counter to count the stall time. Refer to the figure 6-22.
If the stall time counter value goes above this limit the protection will cause a trip
(refer to the parameter 7. 10).
I
.
Stall area
Par. 7. 11
f
Par. 7. 13
UMCH7_11
7. 13Maximum stall frequency
Stall time counter
The frequency can be set between
1—f
In the stall state, the ouput
frequency has to be smaller than
this limit. Refer to the figure 6-21.
Figure 6-22 Counting the stall time.
(par. 1. 2).
max
Par. 7. 12
Stall
No stall
Trip area
Trip/warning
par. 7. 10
UMCH7_12
Time
Parameters 7. 14— 7. 17, Underload protection
General
The purpose of motor underload protection is to ensure that there is load on the motor whilst
the drive is running. If the motor looses its load there might be a problem in the process, e.g. a
broken belt or dry pump.
Motor underload protection can be adjusted by setting the underload curve with parameters
5Hz (the underload counter value is stopped). Refer
to the figure 6-23.
7. 15 and 7. 16. The underload curve is a squared
curve set between zero frequency and the field
weakening point. The protection is not active below
The torque values for setting the underload curve
are set in percentage which refer to the nominal
Page 42 Vacon
Pump and fan control with autochange
torque of the motor. The motor's name plate data,
parameter 1. 13, the motor's nominal current and
the drive's nominal current ICT are used to find the
scaling ratio for the internal torque value. If other
than nominal motor is used with the drive the
accuracy of the torque calculation is decreased.
7. 14Underload protection
Operation:
0 = Not in use
1 = Warning
2 = Fault
Tripping and warning will display the same message code. If tripping is set active
the drive will stop and activate the fault stage.
Deactivating the protection, by setting parameter to 0, will reset the underload time
counter to zero.
7. 15Underload protection, field weakening area load
The torque limit can be set
between 20.0—150 % x T
nMotor
.
This parameter gives the value for
the minimum allowed torque when
the output frequency is above the
Par. 7. 15
field weakening point.
Refer to the figure 6-23.
If parameter 1. 13 is adjusted, this
parameter is automatically
restored to the default value.
Par. 7. 16
Torque
Underload area
Figure 6-23
Setting of minimum load.
7. 16Underload protection, zero frequency load
The torque limit can be set between 10.0—150 % x T
This parameter gives value for the minimum allowed torque with zero frequency.
Refer to the figure 6-23. If parameter 1. 13 is adjusted, this parameter is automatically
restored to the default value.
7. 17Underload time
This time can be set between 2.0—600.0 s.
This is the maximum allowed time for an underload state. There is an internal up/
down counter to accumulate the underload time. Refer to the figure 6-24.
If the underload counter value goes above this limit the protection will cause a trip
(refer to the parameter 7. 14). If the drive is stopped the underload counter is reseted
to zero.
5 Hz
Fieldweakening
point par. 6. 3
.
nMotor
f
UMCH7_15
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 43
Figure 6-24 Counting the under-
Pump control with autochange
Par. 7. 17
Underl.
No underl.
Underload time counter
Trip area
Trip/warning
par. 7. 14
UMCH7_17
Time
load time.
7. 18Phase supervision of the supply voltage
0 = No action
2 = Fault
By setting the parameter value to zero the phase supervision of the supply voltage
will not cause tripping.
7. 19Termistor input of IO-Expander
0 = No action
1 = Warning
2 = Fault
The termistors connected to the termistor input of the I/O-expander board supervise
the temperature of the motor. With parameter 7.19 the response of the frequency
converter when the termistors indicate about overtemperature can be programmed.
7.20Fieldbus fault
0 = No action
1 = Warning
2 = Fault
8. 1Automatic restart: number of tries
8. 2Automatic restart: trial time
The Automatic restart function restarts the frequency converter after the faults
selected with parameters 8. 4—8. 8. The Start function for Automatic restart is
selected with parameter 8. 3.
Parameter 8. 1 determines how many automatic restarts can be made during the
trial time set by the parameter 8. 2.
The time counting starts from the first autorestart. If the number of restarts does
not exceed the value of the parameter 8.1 during the trial time, the counting is cleared
after the time is elapsed and next fault starts the counting again. See figure 6-25.
If the automatic restart trial time is 0s, the automatic restart is not used.
0 = Start with ramp
1 = Flying start, see parameter 4. 6.
8. 4Automatic restart after undervoltage trip
0 = No automatic restart after undervoltage trip
1 = Automatic restart after undervoltage fault condition returns to the normal
condition (DC-link voltage returns to the normal level)
Par. 8. 2 = 3
t
trial
Four faults
= par. 8. 1
t
UD009K25
8. 5Automatic restart after overvoltage trip
0 = No automatic restart after overvoltage trip
1 = Automatic restart after overvoltage fault condition returns to the normal
condition (DC-link voltage returns to the normal level)
8. 6Automatic restart after overcurrent trip
0 = No automatic restart after overcurrent trip
1 = Automatic restart after overcurrent faults
8. 7Automatic restart after reference fault trip
0 = No automatic restart after reference fault trip
1 = Automatic restart after analog current reference signal (4—20 mA)
returns to the normal level (
>4 mA)
8. 8Automatic restart after over-/undertemperature fault trip
0 = No automatic restart after temperature fault trip
1 = Automatic restart after heatsink temperature has returned to its normal
level between -10°C—+75°C.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 45
Pump control with autochange
9. 1Number of auxiliary drives
With this parameter the number of auxiliary drives in use will be defined. The signals
controlling the auxiliary drives on and off can be programmed to relay outputs or to
digital output with parameters 3. 6 - 3. 8. The default setting is one auxiliary drive in
use and it is pre-programmed to relay output RO1.
9. 2Start frequency of auxiliary drive 1
9. 4Start frequency of auxiliary drive 2
9. 6Start frequency of auxiliary drive 3
The frequency of the drive controlled by the frequency converter must exceed the
limit defined with these parameters with 1 Hz before the auxiliary drive is started.
The 1 Hz overdraft makes a hysteresis to avoid unnecessary starts and stops. See
figure 6-26. Notice! See the parameter description par.1.1 and 1.2, page 6.
9. 3Stop frequency of auxiliary drive 1
9. 5Stop frequency of auxiliary drive 2
9. 7Stop frequency of auxiliary drive 3
The frequency of the drive controlled by the frequency converter must fall with 1Hz
below the limit defined with these parameters before the auxiliary drive is stopped.
The stop frequency limit also defines the frequency to which the frequency of the
drive controlled by the frequency converter is dropped after starting the auxiliary
drive. See figure 6-26.
9. 10Start delay of auxiliary drives
The frequency of the drive controlled by the frequency converter must exceed the
start frequency of the auxiliary drive with the time defined with parameter 9. 10 before
the drive is started. The delay is the same for all auxiliary drives. This prevents the
unnecessary starts caused by momentary start limit exceedings. See figure 6-26.
9. 11Stop delay of auxiliary drives
The frequency of the drive controlled by the frequency converter must fall below the
stop limit of the auxiliary drive with the time defined with parameter 9. 11 before the
drive is stopped. The delay is the same for all auxiliary drives. This prevents
unnecessary stops caused by momentary falls below the stop limit. See figure 6-
26.
Output frequency
Start freq. of aux. drive 1 (par. 9.2 + 1 Hz)
Frequency after
starting the aux. drive1
is par. 9.3 - 1 Hz
Fmin
par. 1.1
Stop freq. of aux. drive 1
(par. 9.3 - 1 Hz)
Frequency after
starting the aux. drive1
is par. 9.3 + 1 Hz
Flow
Output frequency
Output frequency
Start freq. of aux. drive 1 (par. 9.2 + 1 Hz)
Stop freq. of aux.
drive 1
(par. 9.3 - 1 Hz)
Frequency decrease
during the stop delay
Fmin
par. 1.1
Start delay of the aux.
drives (par 9.10)
Stop delay of the aux.
drives (par 9.11)
Flow
Frequency
increase
during the
start delay
Figure 6-26 Example of effect of parameters in variable speed and one auxiliary
9. 12Reference step after start of the auxiliary drive 1
9. 13Reference step after start of the auxiliary drive 2
9. 14Reference step after start of the auxiliary drive 3
9. 15Reference step after start of the auxiliary drive 4
The reference step will be automatically added to the reference value always when
the corresponding auxiliary drive is started. With the reference steps e.g. the pressure
loss in the piping caused by the increased flow can be compensated. See figure 6-
27.
Reference for PI-controller
Reference step 3
par. 9.14
Reference step 2
par. 9.13
Reference step 1
par. 9.12
Reference
(analoginput)
start
Aux. drive 1
Aux. drive 2
Aux. drive 3
stop
start
stop
start
stop
Figure 6-27 Reference steps after starting auxiliary drives.
Time
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 47
Pump control with autochange
9. 16Sleep level
9. 17Sleep delay
The change of this parameter from value 0.0 Hz activates the sleep function where
the frequency converter is stopped automatically when the frequency of the drive
controlled by the frequency converter is below the sleep level (par. 9.16) continuously
for the duration of the sleep delay (9. 17). During the stop state the Pump and fan
control is operating and it turns frequency converter to Run state when the wake up
level defined with parameters 9. 18 and 9. 19 is reached. See figure 6-28.
9. 18Wake up level
The wake up level defines the level below which the actual value must fall or which
has to be exceeded before starting the frequency converter from the sleep function.
See figure 6-28.
Actual value
Wake up level (param. 9.18 )
Output frequency
Sleep level
param. 9.16
Start/Stop status of
the var. speed drive
Figure 6-28 Example of the sleep function.
9. 19Wake up function
t < t
sleep
(param. 9.17)
running
t
sleep
Time
Time
stop
This parameter defines if the wake up occurs when the actual value signal falls below or exceeds the wake up level. Furthermore, it shall be selected if the level (Par.
9.18) is percents of maximum value of the actual value or percents of the current
reference signal value.
Wake up happens
when actual value
goes below the
limit
Wake up happens
when actual value
exceeds the
limit
Limit
The limit defined
with parameter
9.18 is procents
from the maximum
value of the actual
value
The limit defined
with parameter
9.18 is procents
from the maximum
value of the actual
value
Description
Actual value signal
100%
Start
Stop
Actual value signal
100%
Par. 9.18=60%
Par. 9.18=30%
time
time
Wake up happens
2
when actual value
goes below the
limit
3
Wake up happens
when actual value
exceeds the
limit
The limit defined
with parameter
9.18 is procents
from the current
value of the
reference signal
The limit defined
with parameter
9.18 is procents
from the current
value of the
reference signal
Actual value signal
100%
refrence=50%
Start
Stop
Actual value signal
100%
Par.9.18=140%
limit=140%*refrence=70%
refrence=50%
Start
Stop
Par.9.18=60%
limit=60%*refrence=30%
time
time
Table 6-3Wake up function parameter selections
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Start
Stop
Vacon Page 49
Pump control with autochange
9. 20PI-regulator bypass
With this parameter the PI-regulator can be programmed to be bypassed. Then the
frequency of the drive controlled by the frequency converter and the starting points
of the auxiliary drives are defined according to the actual value signal.
Output freq.
Max. freq.
(par. 1.2)
Minimum freq.
(par. 1.1)
Start freq. of the aux. drive 1
(par.9.2)
Stop freq. of the aux.
drive 1 (par.9.3)
Minimum of the
actual value
Start freq. of the aux. drive 2
(par.9.4)
Stop freq. of the aux.
drive 2 (par.9.5)
Maximum of the
actual value
Actual value
Start/stop control of
the freq. converter
Auxiliary drive 1
Auxiliary drive 2
stop
start
stop
start
start
stop
Figure 6-29 Example of the function of variable speed drive and two auxiliary
drives when PI-regulator is bypassed with parameter 9. 20.
9. 21Input pressure measurement analog input selection
9. 22Input pressure high limit
9. 23Input pressure low limit
9. 24Output pressure drop value
In the pressure increase stations there may be need for decreasing the output
pressure if the input pressure decreases below a certain limit. The function needs
input pressure measurement that is connected to the analogue input selected with
parameter 9.21. See figure 6-30.
Vacon
CX/CXL/CXS
Input pressure
measurement
input, par 9.21
PI-controller
actual value
input par. 2.16
M
Figure 6-30 Ouput pressure decrease inputs
With parameters 9.22 and 9.23 the limits for the area of the input pressure,
where the output pressure is decreased, can be selected. Values are in
percentage of the input pressure measurement maximum value. With parameter
9.24 the value for output pressure decrease in this area can be set. The value is
percents of the reference value maximum. See Figure 6-31.
OUTPUT PRESSURE
Par. 9.24
Output
pressure
drop value
INPUT PRESSURE
TIME
Par. 9.22
Input pressure
high limit
Par. 9.23
Input pressure
low limit
Figure 6-31 Output pressure function
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
PUMP631.DS4
TIME
Vacon Page 51
Pump control with autochange
9. 25Frequency drop delay after starting an auxiliary drive
9. 26Frequency increase delay after stopping an auxiliary drive
If the speed of auxiliary drive increases slowly (e.g. soft starter control) then a
delay (par. 9.25) between auxiliary drive start and the frequency drop of the variable speed drive will make the control smoother.
Also if the speed of the auxiliary drives decreases slowly (soft starter control)
then with parameter 9.26 a delay between auxiliary drive stop and the frequency
increase of the variable speed drive can be programmed. See figure 6-32.
If either value of parameters 9.25 and 9.26 is maximum (300,0 s) then there is
no frequency drop nor increase.
The autochange changes the start and stop order of the drives controlled by the pump- and
fan control. Also the frequency converter controlled drive can be included in the autochange
system. By using the autochange the running periods of the motors can be equal and e.g.
the stalling of the pumps because of being unused for a long period can be prevented.
The autochange can be activated by selecting the autochange mode with parameter 9.27.
The autochange happens when the time period set by parameter 9.28 is elapsed and the
level of used capacity is below the limit defined with parameters 9.29 and 9.30. During the
autochange moment all drives are stopped and then started with new order.
External contactors controlled by the relay outputs of the frequency converter connect the
drives to the mains or to the frequency converter
9. 27Autochange mode
0autochange not in use
1Autochange is done by changing the starting order of the auxiliary
drives. See figure 6-33.
The frequency converter controlled drive stays same. Only the mains
contactor is needed for each drive.
Vacon
M
Aux. drive 1
M
Aux. drive 2
M
Figure 6-33 Autochange only with auxiliary drives
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 53
Pump control with autochange
2Autochange with all drives
Frequency converter drive is included in the autochange. For each drive
a contactor for mains and another for frequency converter is needed. See
figure 6-34.
Vacon
auxiliary
contact
connection
Drive 1Drive 2
M
Figure 6-34 Autochange with all drives
9. 28Autochange interval
The parameter defines the time period after which the autochange will be done if
the used capacity is below the limit defined with parameters 9.29 and 9.30. If the
level is over the limit, wait the level to decrease below the limit before
autochange execution. The next time period counting starts from the
autochange execution. See figure 6-35.
9. 30Autochange level, variable speed drive frequency
These parameters define the level below which the used capacity must be when
the autochange happens.
* If the number of running auxiliary drives is less than the value of the parameter
9.29 the autochange can happen.
* If the number of running auxiliary drives is equal to par. 9.29 and the frequency
of the variable speed drive is less than the value of parameter 9.30 the
autochange can happen.
* If the parameter 9.30 = 0,0 Hz then the autochange can happen only in sleep
or stop state in spite of the value of parameter 9.29.
Output
frequency
Par. 9.29 = 1
Autochange level,
auxiliary drives
Autochange moment
Par. 9.30
Autochange
level, frequency
Par. 9.28
Autochange interval
Aux. drive 1
control
Aux. drive 2
control
Kuva 6-35 Autochange interval and level
Time
Par. 9.28
Autochange interval
vuorot3.fh3
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 55
Pump control with autochange
9. 31Autochange interlocks
With this parameter the use of interlocks can be activated. The interlocks come
from the switches that contact motors to the automatic control (frequency converter), off-state or directly to the mains. The interlock signals are connected to
the digital inputs of the frequency converter. These inputs must be programmed
to interlock inputs. Each drive must have own interlock input.
Pump- and fan control controls only those motors whose interlock input is active.
If the interlock input changes to inactive or comes active again in Run state then
pump and fan control stops all motors and then starts control with new composition.
If the intelock of auxiliary drives comes true via RUN mode, operation depends
on par.9.35 setting. Default value is to restart the frequency converter and auxiliary
drives after STOP taking with the drives in the regulator system (dig. input =
ON). See par.9.35.
PE
L1
L2
L3
Q1
F3
F1
F2
VACON
K1
ac2maint.ds4
L1 L2 L3
UVW
M1
K1.1
PE
UVW
M
3
K2.1
K2
PE
UVW
M2
M
3
Figure 6-36 Example of two pump autochange, main diagram
9. 34Actual value special display, number of decimals
DIA3
10
With these parameters the minimum and maximum values and also the number
of decimals of the actual value special display can be set. The actual value can be
found on the monitoring page with signal number n26.
Minimum value (par. 9.32)
Maximum value (par. 9.33)
Figure 6-38 Actual value special display
Number of decimals (par. 9.34)
3 0. 0 0
.
.
1 0 0. 0 0
(4 mA)
(20 mA)
actspedi.fh3
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 57
Pump control with autochange
9.35 Interlock update
Interlock update moment is selected when the dig. input comes true during RUN mode.
0: Update after autochange interval or in STOP state (f.eg. sleep function). During START
state used drives (interlock TRUE) are taken with in the regulator system .
1: Update immediately. When the interlock comes TRUE the frequency converter and auxil-
iary drives are stopped. After this the frequency converter RERUN automatically taking with
drives of regulator system when dig. input is ON.
When dig. input is OFF interlocked drive is stopped if it is in RUN state and it is removed
from the regulator system. Frequency converter and other auxiliary drives are in RUN state.
10Fieldbus control
Fieldbus control can be activated with parameter 10.1. Then the frequency or speed reference comes from the fieldbus as well as the Start/Stop and Reverse control.
First two parameters in group 10 concern all fieldbuses. Parameters 10.3 - 10.6 are only for
Modbus, parameters 10.7 - 10.13 only for Profibus and 10.14 only for LONWorks.
10.1Fieldbus control
Defines the active control source:
0: control via I/O terminals
1: control via Fieldbus board
Parameters 10.2 - 10.5 only for Modbus protocol
10.2Slave address
Defines slave device address. Maximum value for this parameter is 247 and minimum is 1.
The Modbus time-out determines how long the Fieldbus board waits for a message from a
master device and is specific in seconds. Time can be set between 0 - 3600 s. Time 0 s =
No time-out.
Selection of profibus PPO type.
1: PPO 1 (Parameter data 8 bytes, Control data 4 bytes)
2: PPO 2 (Parameter data 8 bytes, Control data 4 bytes)
3: PPO 3 (Control data 4 bytes)
4: PPO 4 (Control data 12 bytes)
10.9Profibus process Data 1
10.10Profibus process Data 2
10.11Profibus process Data 3
10.12Profibus process Data 4
Selection of profibus process data source.
Value 1 . . . 22 Number of actual value (=n1 . . . n22 in monitoring page).
Value 99 Active fault code.
Parameter 10.13 only for LONWorks protocol
10.14LONWorks service button
Changing the value of tjhis parameter from 0 to 1 or vice versa and pressing the Enter
button cause the unique LONWorks ID number to be sent to the network.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 59
Pump control with autochange
7I/O-expander with pump and fan control application
The digital inputs and relay outputs of the I/O-expander board has fixed signals according to
figure 6-1 when the pump and fan control application is selected.
Digital inputs are used for interlock inputs and they all or part of them are active if the use of
interlocks is set active with parameter 9.31. Number of auxiliary drives (par, 9.1) defines
how many inputs are active. The controls of auxiliary drives are connected to relay outputs.
If four- or five-pump autochange is in use then the relay outputs of the basic control board
can be used additionally.
203GNDI/O groundGround for reference and controls
204 I
205 Iin-range 0—20 mA(Default: Not in use)
206 +24VControl voltage outputVoltage for switches, etc. max. 0.1 A
207GNDI/O groundGround for reference and controls
208 CMCCommon for DIC1-DIC7Connect to GND or + 24 V
209 DIC1Interlock input,Contact closed = interlock is active
210 DIC2Interlock inputContact closed = interlock is active
211 DIC3Interlock input,Contact closed = interlock is active
212 DIC4Interlock inputContact closed = interlock is active
213 DIC5Interlock input,Contact closed = interlock is active
206 +24VControl voltage outputVoltage for switches, etc. max. 0.1 A
207GNDI/O groundGround for reference and controls
208 CMCCommon for DIC1-DIC7Connect to GND or + 24 V
209 DIC1Interlock input,Contact closed = interlock is active
autochange 1
210 DIC2Interlock inputContact closed = interlock is active
autochange 2
211 DIC3Interlock input,Contact closed = interlock is active
autochange 3
212 DIC4Interlock inputContact closed = interlock is active
autochange 4
213 DIC5Interlock input,Contact closed = interlock is active
autochange 5
214GNDI/O groundGround for reference and controls
215 I
Figure 7-2 I/O-Expander 103 OPT with pump and fan control
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 61
Signal from
motor termistor
Pump control with autochange
TerminalSignalDescription
206 +24VControl voltage outputVoltage for switches, etc. max. 0.1 A
207GNDI/O groundGround for reference and controls
208 COMECommon for DIC1-DIC7Connect to GND or + 24 V
209DIE1Interlock input,Contact closed = interlock is active
autochange 1
210DIE2Interlock inputContact closed = interlock is active
autochange 2
211DIE3Interlock input,Contact closed = interlock is active
autochange 3
212DIE4Interlock inputContact closed = interlock is active
autochange 4
213Not used
214 DIE6A+ Interlock inputContact closed = interlock is active
215 DIE6A-autochange 5
216DIE7B+
217DIE7B218DOE1
219DOE2
220Not used
221 TI+Termistor input
222 TI225RO4/1Aux. drive 3 / autochange 3 control
226RO4/2
231DOE3Open collector output 3Aux. drive 1 / autochange 1 control
232GNDI/O ground
233DOE4Open collector output 4Aux. drive 2 / autochange 2 control
234GNDI/O ground
Figure 7-2 I/O-Expander 202OPT with pump and fan control (Profibus)
NOTE! Termistor input (terminals 327 and 328) must be shorted if not used.
READY = ON, when mains voltage has been applied and Vacon CX is ready to operate.
RUN = ON, when motor is running.
FAULT = ON, if a fault occurs.
FIELDBUS CONTROL = ON, when the fieldbus board is the Active Control Source.
301 DID1Interlock input,Contact closed = interlock is active
autochange 1
302DID2Interlock inputContact closed = interlock is active
autochange 2
303DIE3Interlock input,Contact closed = interlock is active
autochange 3
304DIE4Interlock inputContact closed = interlock is active
autochange 4
305 COMDCommon for DID1-DID2Connect to GND or +24 V
306+24 VControl voltage outputVoltage for switches, etc. max. 0.1 A
307 COMECommon for DIE3-DIE4Connect to GND or +24 V
308GNDI/O groundGround for reference and controls
309 DID5A+ Interlock inputContact closed = interlock is active
310 DID5A-autochange 5
311DID6B+
312DID6B313DID7Z+
314DID7Z315GNDI/O groundGround for reference and controls
316DOD1Open collector output 1Aux. drive 1 / autochange 1 control
317DOD2Open collector output 2Aux. drive 2 / autochange 2 control
318DOD3Open collector output 3Aux. drive 3 / autochange 3 control
319DOD4Open collector output 4Fieldbus control
320GNDI/O groundGround for reference and controls
327 TI+Termistor input
328 TI-
Figure 7-3 I/O-Expander 201OPT with pump and fan control (Modbus)
NOTE! Termistor input (terminals 327 and 328) must be shorted if not used.
READY = ON, when mains voltage has been applied and Vacon CX is ready to operate.
RUN = ON, when motor is running.
FAULT = ON, if a fault occurs.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 63
Signal from
motor termistor
Pump control with autochange
TerminalSignalDescription
301 DID1Interlock input,Contact closed = interlock is active
autochange 1
302 DID2Interlock inputContact closed = interlock is active
autochange 2
303DIE3Interlock input,Contact closed = interlock is active
autochange 3
304DIE4Interlock inputContact closed = interlock is active
autochange 4
305 COMDCommon for DID1-DID2Connect to GND or +24 V
306+24 VControl voltage outputVoltage for switches, etc. max. 0.1 A
307 COMECommon for DIE3-DIE4Connect to GND or +24 V
308GNDI/O groundGround for reference and controls
309 DID5A+ Interlock inputContact closed = interlock is active
310 DID5A-autochange 5
311 DID6B+
312DID6B313DID7Z+
314DID7Z315GNDI/O groundGround for reference and controls
316DOD1Open collector output 1Aux. drive 1 / autochange 1 control
317DOD2Open collector output 2Aux. drive 2 / autochange 2 control
318DOD3Open collector output 3Aux. drive 3 / autochange 3 control
319DOD4Open collector output 4Fieldbus control
320GNDI/O groundGround for reference and controls
327 TI+Termistor input
328 TI329LONWorks network
330
Figure 7-4 I/O-Expander 203OPT with pump and fan control (LONWorks)
NOTE! Termistor input (terminals 327 and 328) must be shorted if not used.
READY = ON, when mains voltage has been applied and Vacon CX is ready to operate.
RUN = ON, when motor is running.
FAULT = ON, if a fault occurs.
302 DID2RUN disableContact open=start of motor enable
Contact closed=start of motor
303 DID3Acceler. / Decel. timeContact open = time 1 selected
selectionContact closed = time 2 selected
304 DID4Jogging speed selectionContact open = no action
Contact closed = jogging speed
305 COMDCommon for DID1-DID2Connect to GND or +24 V
306+24 VControl voltage outputVoltage for switches, etc. max. 0.1 A
307 COMECommon for DIE3-DIE4Connect to GND or +24 V
308GNDI/O groundGround for reference and controls
309 DID5A+ Pulse input A
310 DID5A-(differential input)
311 DID6B+ Pulse input B90 degrees phase shift compared
312 DID6B- (differential input)to pulse input A
313DID7Z+ Pulse input Zone pulse per one revolution
314DID7Z-(differential input)
315GNDI/O groundGround for reference and controls
316DOD1Open collector output 1Aux. drive 1 / autochange 1 control
317DOD2Open collector output 2Aux. drive 2 / autochange 2 control
318DOD3Open collector output 3Aux. drive 3 / autochange 3 control
319DOD4Open collector output 4Fieldbus control
320GNDI/O groundGround for reference and controls
327 TI+Termistor input
328 TI-
disabled
Figure 7-5 I/O-Expander 200OPT with pump and fan control (Interbus-S)
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 65
Pump control with autochange
PE
L1
L2
L3
Q1
F3
F1
F2
F2
VACON
ac3maint.ds4
K1
L1 L2 L3
UVW
M1
K1.1
K2
PE
UVW
M
3
M2
K2.1
UVW
M
3
K3
PE
M2
Figure 7-6Example of 3-pump autochange system, main diagram
230 VAC
K3.1
PE
UVW
M
3
K1
K3
K2
K1.1
M1/Vacon
S1
AOV
K1.1
K2
K1
M1/mains
223
224
K3
24 VDC
206
209
AOV
S2
K3
K1
K2.1
K2
Vacon
M2/
K2.1
K1
K2
M2/mains
225
226
K3
VACON I/O-expander
210
K3
K2
K3.1
K3
M3/Vacon
Figure 7-7Principal control diagram of 3-pump autochange system
8 Commissioning of pump- and fan control application
General
1.Set motor name plate data, supply voltage and other parameters if necessary.
2.Set the number of auxiliary drives
3.If needed change the start and stop limits of the auxiliary drives as well as start
and stop delays of auxiliary drives
Autochange not in use
4A.Program the relay outputs and digital output according to the number of auxiliary
drives. Set own output for each drive with parameters 3.6 - 3.8.
The value of the parameter will be Aux. drive 1, Aux. drive 2 or Aux. drive 3
Autochange in use
4B.Program the relay outputs and digital output according to the number of auxiliary
drives by setting values of parameters 3.6 - 3.8 to:
3.6 = Autochange 3 control (27) , Digital output
3.7 = Autochange 1 control (26) , Relay output 1
3.8 = Autochange 2 control (26) , Relay output 2
If the Autochange is only with auxiliary drives (par. 9.27 =1) then the outputs are
auxiliary drive control signals. In the beginning the Autochange 1 control is the
control signal of the first auxiliary drive.
If all drives are included to the autochange (par. 9.27 = 2) then the outputs are
control signals of the frequency converter controlled drive and auxiliary drives. In
the beginning the Autochange 1 control is the control signal of the frequency
converter controlled drive
5B.Program the autochange interval (par. 9.28) and proper capacity level (par. 9.29
and par 9.30) that can be in use when the Autochange happens.
6B.If interlocks are used then set the function active with parameter 9.31. Program
own interlock input for each drive. If I/O-expander is in use it has interlock inputs
as constant and the inputs of basic control board are not needed.
Vacon PlcPhone: +358-201 2121Fax:+358-201 212 205
Service: +358-40-8371 150E-mail: vacon@vacon.com
Vacon Page 67
Pump control with autochange
9 MONITORING DATA
The PI-control application has extra items for monitoring (V20 - V26). See table 9-1
DataDataUnitDescription
numbername
V1Output frequencyHzFrequency to the motor
V2Motor speedrpmCalculated motor speed
V3Motor currentAMeasured motor current
V4Motor torque%Calculated actual torque/nominal torque of the unit
V5Motor power%Calculated actual power/nominal power of the unit
V6Motor voltageVCalculated motor voltage
V7DC-link voltageVMeasured DC-link voltage
V8Temperature°CTemperature of the heat sink
V9Operating day counterDD.ddOperating days 1), not resettable
V10Operating hours,HH.hhOperating hours 2), can be reset with
"trip counter" programmable button #3
V11MW-hoursMWhTotal MW-hours, not resettable
V12MW-hours,MWhMW-hours, can be reset with programmable
"trip counter"button #4
V13Voltage/analogue inputVVoltage of the terminal Uin+ (term. #2)
V14Current/analogue inputmACurrent of terminals Iin+ and Iin- (term. #4, #5)
V15Digital input status, gr. A
V16Digital input status, gr. B
V17Digital and relay output
status
V18Control programVersion number of the control software
V19Unit nominal powerkWShows the power size of the unit
V20PI-controller reference%Percents of the maximum reference
V21PI-controller actual value%Percents of the maximum actual value
V22PI-controller error value%Percents of the maximum error value
V23PI-controller outputHz
V24Number of running
auxiliary drives
V25Motor temperature rise %100%= temperature of motor has risen to nominal
V26Actual value specialMinimum and maximum values and number of
displaydecimals is defined with parameters 9.32 - 9.34
V27Digital input OPT 1 - 3 See V15, V16, V17
V28Digital input OPT 4 - 5 See V15, V16, V17
V29Digital and relay output OPT See V15, V16, V17