The location of the parameter in the menu, that is,
the parameter number.
B
The name of the parameter.
C
The minimum value of the parameter.
D
The maximum value of the parameter.
E
The unit of the value of the parameter. The unit
shows if it is available.
F
The value that was set in the factory.
G
The ID number of the parameter.
H
A short description of the values of the parameter
and/or its function.
VACON® 3000
Application Guide
Introduction
1 Introduction
1.1 Purpose of this Application Guide
This Application Guide provides information for configuring the system, controlling the AC drive, accessing parameters, programming, and troubleshooting of the AC drive. It is intended for use by qualified personnel. Read and follow the instructions to use the
drive safely and professionally. Pay particular attention to the safety instructions and general warnings that are provided in this
manual and other documentation delivered with the drive.
1.2 Manual and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome.
The original language of this manual is English.
Table 1: Manual and Software Version
1.3 Additional Resources
Other resources are available to understand advanced AC drive functions and operation.
•
The VACON® 3000 Design Guide provides technical information to understand the capabilities of the VACON® 3000 Drive Kit for
integration into motor control and monitoring systems.
•
The VACON® 3000 Operating Guides provide detailed information for the installation, commissioning, and start-up of the drive.
•
The operating and installation guides for VACON® options give detailed information about specific drive options.
Supplementary publications and manuals are available from Danfoss. See www.danfoss.com for listings.
1.4 Parameter Table Reading Guide
This manual includes a large quantity of parameter tables. These instructions tell you how to read the tables.
Illustration 1: Parameter Table Reading Guide
1.5 Start-up Quick Guide
The start-up wizard makes the commissioning of the drive easy and reduces the manual work with the parameters. It is also possible
to edit these parameters later.
1.5.1 Start-Up Wizard for INU
The start-up wizard tells you to give necessary data for the drive to control your procedure.
The [BACK/RESET] button. Use it to move back in the
menu, exit the Edit mode, reset a fault.
B
The arrow button UP. Use it to scroll up the menu
and to increase a value.
C
The [FUNCT] button. Use it to change the rotation
direction of the motor, access the control page, and
change the control place.
D
The arrow button RIGHT.
E
The START button.
F
The arrow button DOWN. Use it to scroll the menu
down and to decrease a value.
G
The STOP button.
H
The arrow button LEFT. Use it to move the cursor
left.
I
The [OK] button. Use it to go into an active level or
item, or to accept a selection.
VACON® 3000
Application Guide
User Interfaces
2 User Interfaces
2.1 Description of the Control Panel
2.1.1 Control Panel and the Keypad
The control panel is the interface between the AC drive and the user. With the control panel, you can control the speed of a motor
and monitor the status of the AC drive. You can also set the parameters of the AC drive.
Illustration 2: Buttons of the Keypad
2.1.2 Displays of the Control Panel
The display shows this data.
•
The status of the motor and the drive.
•
Faults in the motor and in the drive.
•
Your location in the menu structure.
If the text in the text display is too long for the display, the text scrolls to show the full text string. Some functions are only available
in the graphical display.
The location field: the ID number of the parameter
and the current location in the menu
G
An activated group or item
H
The number of items in the group in question
STOP
READYI/O
ID:25
FreqReference
Multimonitor
20.0 Hz
Motor Curre
0.00A
DC-link volt
0.0V
Output Freq
0.00 Hz
Motor Speed
0.0 rpm
Motor Voltage
0.0V
Motor Tempera
0.0%
Motor Torque
0.00 %
Unit Tempera
81.9°C
FreqReference
e30bg686.10
VACON® 3000
Application Guide
Illustration 3: Graphical Display of the Control Panel
User Interfaces
2.2 Graphical Display
2.2.1 Uses of the Monitor Menu
Monitor Menu allows monitoring the actual values of the parameters and signals. It also allows monitoring the statuses and measurements. Some of the values to be monitored can be customized.
2.2.2 Multimonitor Monitoring
2.2.2.1 Changing the Items to Monitor
On the Multimonitor page, 4–9 items can be monitored. Select the number of items with the parameter Multimonitor View (ID 1196)
in the Application Settings menu.
Procedure
1.
Go into the Monitor menu with the [OK] button.
2.
Go into Multimonitor.
To replace an old item, activate it. Use the arrow buttons.
Move from digit to digit with the arrow buttons Left and Right. Change the digits with the arrow buttons Up and Down.
4.
To accept the change, push the [OK] button. To ignore the change, use the [BACK/RESET] button.
2.2.5 Selecting More than 1 Value
With some parameters, more than 1 value can be selected. Select a checkbox at each necessary value.
Procedure
1.
Find the parameter. There is a symbol on the display when a checkbox selection is possible.
User Interfaces
2.
To move in the list of values, use the arrow buttons Up and Down.
3.
To add a value into your selection, select the box that is next to it with the arrow button Right.
2.2.6 Faults
2.2.6.1 Uses of the Active Faults Submenu
When there is a fault or many faults, the display shows the name of the fault and blinks. Push [OK] to go back to the Diagnostics
menu. The submenu Active faults shows the number of faults. To see the fault-time data, select a fault and push [OK].
The Active faults submenu can keep storage of maximum 10 faults. The submenu shows the faults in the sequence in which they
occurred.
When the drive shows a fault and stops, examine the cause of fault, and reset the fault. The fault stays active until it is reset.
There are 2 procedures to reset a fault in the local control place: with the [BACK/RESET] button and with a parameter. It is also possi-
ble to reset faults by using I/O, a fieldbus, or a PC tool.
N O T I C E
Before resetting the fault, remove the external control signal to prevent restarting the drive accidentally.
2.2.6.2.1 Resetting Faults with the [BACK/RESET] Button
Procedure
1.
Push the [BACK/RESET] button on the keypad of the control panel for 2 seconds.
2.2.6.2.2 Resetting Faults with a Parameter on the Graphical Display
Faults can be reset with the parameter Reset Faults.
Procedure
1.
Go to the Diagnostics Menu.
2.
Go to the submenu Reset faults.
Select the parameter Reset Faults.
3.
2.2.6.3 Uses of the Fault History
The Fault history shows more data on the faults. There is a maximum number of 40 faults in the Fault history.
2.2.6.3.1 Examining the Fault History on the Graphical Display
Procedure
1.
To see more data on a fault, go to Fault history.
2.
To examine the data of a fault, push the Arrow button Right.
To change easily between the Local and Remote control places.
•
To change the rotation direction.
•
To edit quickly a parameter value.
User Interfaces
2.2.7.1 Different Control Places
The selection of the control place determines from where the AC drive takes the start and stop commands. All the control places
have a parameter for the selection of the frequency reference source. The Local control place is always Keypad. The Remote control
place is I/O or Fieldbus. The status bar of the display shows the current control place.
It is possible to use I/O A, I/O B, and Fieldbus as Remote control places. I/O A and Fieldbus have the lowest priority. Select them with
P3.2.1 (Remote Control Place). I/O B can bypass the Remote control places I/O A and Fieldbus with a digital input. Select the digital
input with parameter P3.5.1.7 (I/O B Control Force).
Keypad is always used as a control place when the control place is Local. Local control has higher priority than Remote control. For
example, if parameter P3.5.1.7 bypasses the control place with a digital input, and Local is selected in Remote control, Keypad becomes the control place. Use the [FUNCT] button or P3.2.2 Local/Remote to change between the Local and Remote control.
2.2.7.2 Changing the Control Place
This topic gives instructions on how to change the control place on the control panel.
Procedure
Anywhere in the menu structure, push the [FUNCT] button.
1.
To select Local/Remote, use the arrow buttons Up and Down. Push the [OK] button.
To select Local or Remote, use the arrow buttons Up and Down again. To accept the selection, push the [OK] button.
User Interfaces
4.
If Remote control place is changed to Local, that is, Keypad, give a keypad reference.
After the selection, the display goes back into the same location where it was when the [FUNCT] button was push-
ed.
2.2.7.3 Going into the Control Page
It is easy to monitor the most important values in the Control page.
If other control places or reference values are used, the display shows the frequency reference, which cannot be edited. The other
values on the page are Multimonitor values. These monitoring values can be selected.
Procedure
Anywhere in the menu structure, push the [FUNCT] button.
1.
2.
To select the Control page, push the arrow buttons Up and Down. Go in with the [OK] button.
The Control page opens.
With the Local control place and the keypad reference selected, P3.3.1.8 Keypad Reference can be set with the [OK] button.
3.
To change the digits in the value, push the arrow buttons Up and Down. Accept the change with the [OK] button.
4.
2.2.7.4 Changing the Rotation Direction
The rotation direction of the motor can be changed quickly with the [FUNCT] button.
N O T I C E
The command Change direction is available in the menu only if the current control place is Local.
Procedure
1.
Anywhere in the menu structure, push the [FUNCT] button.
2.
To select Change direction, push the arrow buttons Up and Down. Push the [OK] button.
The rotation direction changes immediately. The arrow indication in the status field of the display changes.
User Interfaces
2.2.7.5 Using the Quick Edit Function
With the Quick Edit function, a parameter can be accessed quickly by typing the ID number of the parameter.
Procedure
1.
Anywhere in the menu structure, push the [FUNCT] button.
2.
Push the arrow buttons Up and Down to select Quick Edit and accept with the [OK] button.
Write the ID number of a parameter or monitoring value. Push [OK].
3.
The display shows the parameter value in the edit mode and the monitoring value in the monitoring mode.
2.2.8 Copying the Parameters of an AC Drive
Use this function to copy parameters from a drive to another. Before downloading parameters from the control panel to the drive,
stop the drive.
N O T I C E
This function is available only in the graphical display.
Use the arrow buttons Up and Down to select a function. Accept the selection with the [OK] button.
User Interfaces
The command Restore factory defaults brings back the parameter settings that were made at the factory. Use the command Save to keypad to copy all the parameters to the control panel. The command Restore from keypad copies all the
parameters from the control panel to the drive.
2.
Detach the control panel and connect it to another drive.
3.
Download the parameters to the new drive with the command Restore from keypad.
2.2.9 Comparing the Parameters
Use this function to compare the current parameter set with one of these 4 sets. See more about these parameters in 4.8.2 Parame-
ter Backup Parameters.
•
Set 1 (B6.5.4 Save to Set 1)
•
Set 2 (B6.5.6 Save to Set 2)
•
Defaults (B6.5.1 Restore Factory Defaults)
N O T I C E
If you have not saved the parameter set with which you want to compare the current set, the display shows the text Comparing
failed.
Select the pair of sets. Push [OK] to accept the selection.
User Interfaces
4.
5.
2.2.10 Reading Help Texts
The graphical display can show help texts on many topics. All the parameters have a help text. The help texts are also available for
the faults, alarms, and the start-up wizard.
The help texts are always in English.
Procedure
1.
Select Active and push [OK].
Examine the comparing between the current values and the values of the other set.
This menu is not available in the VACON® Live tool.
If the same items are used frequently, they can be added into Favourites. You can collect a set of parameters or monitoring signals
from all the control panel menus. It is not necessary to find them in the menu structure one by one. As an alternative, add them into
the Favourites folder where it is easy to find them.
2.2.11.1 Adding an Item to the Favourites
It is possible to add frequently used items into Favourites where they are easily accessible.
Procedure
1.
Find the item to be added to Favourites. Push the [OK] button.
2.
Select Add to favourites and push the [OK] button.
The steps are now completed.
3.
To continue, read the instructions on the display.
2.2.11.2 Removing an Item from the Favourites
Procedure
1.
Go to the Favourites.
2.
Find the item to be removed. Push the [OK] button.
Make the connection between the AC drive and the PC tool with the VACON® serial communication cable. The serial communication drivers are installed automatically during the installation of VACON® Live. After the cable is installed, VACON® Live finds the
connected drive automatically.
See more on how to use VACON® Live in the help menu of the program.
The programming of inputs of the AC drive is flexible. It is possible to use freely the available inputs of the standard and optional I/O
for different functions.
It is possible to expand the available capacity of I/O with option boards. It is possible to install the option boards in the slots C, D,
and E. For more data on the installation of option boards, see the Installation Guide.
Illustration 5: The Option Board Slots and Programmable Inputs
3.2 DIP Switches on the Control Unit
3.2.1 Selection of Terminal Functions with DIP Switches
Two selections for specified terminals can be done with the DIP switches. The switches have two positions: up and down. See the
location of the DIP switches and the possible selections in Illustration 6.
Illustration 6: The Selections of the DIP Switches
Table 2: The Default Positions of the DIP Switches
3.2.2 Isolation of the Digital Inputs from Ground
It is possible to isolate from ground the digital inputs (terminals 8–10 and 14–16) on the standard I/O board. To do this, change the
position of a DIP switch on the control board.
The value of the parameter, that is, the set digital input
Input type (graphical
display)
Input type
(text display)
Slot
Input #
Explanation
DigIN
dIA1
Digital input #1 (terminal 8) on a board in Slot A (standard I/O board).
DigIN
dIA2
Digital input #2 (terminal 9) on a board in Slot A (standard I/O board).
VACON® 3000
Application Guide
Illustration 7: Change the Position of This Switch to Isolate the Digital Inputs from Ground
Programming of Digital and
Analog Inputs
3.3 Programming of Digital Inputs
The digital input parameters are functions that you can connect to a digital input terminal. The text DigIn Slot A.2 means the second
input on the slot A. It is also possible to connect the functions to time channels. The time channels work as terminals.
You can monitor the statuses of the digital inputs and the digital outputs in the Multimonitoring view.
To give a digital input to a function, set a value to the correct parameter.
Illustration 8: The Digital inputs menu in the graphical display
Example
In the standard I/O board compilation, there are 6 digital inputs available: the slot A terminals 8, 9, 10, 14, 15 and 16.
Digital input #3 (terminal 10) on a board in Slot A (standard I/O board).
DigIN
dIA4
Digital input #4 (terminal 14) on a board in Slot A (standard I/O board).
DigIN
dIA5
Digital input #5 (terminal 15) on a board in Slot A (standard I/O board).
DigIN
dIA6
Digital input #6 (terminal 16) on a board in Slot A (standard I/O board).
Parameter
Default
ID
Description
External fault close
DigIN SlotA.3
405
OPEN = OK
CLOSED = External fault
STOP
READYI/O
Ext Fault Close
P3.5.1.11
ID:405
Min:
Max:
DigIN SlotA.3
e30bg705.10
STOP
READYI/O
Ext Fault Close
P3.5.1.11
ID:405
Min:
Max:
DigIN SlotA.6
e30bg706.10
VACON® 3000
Programming of Digital and
Application Guide
The function External Fault Close (ID 405) gets the default value DigIN SlotA.3 in the graphical display, and dI A.3 in the text display.
After this selection, a digital signal to the digital input DI3 (terminal 10) controls External Fault Close.
To change the input from DI3 to, for example, DI6 (terminal 16) on the standard I/O, obey these instructions.
Analog Inputs
3.3.1 Programming of Digital Inputs in the Graphical Display
Procedure
1.
Select a parameter. To go into the Edit mode, push the arrow button Right.
2.
In the Edit mode, the slot value DigIN SlotA is underlined and blinks. If there are more digital inputs available in the I/O, for
example, because of option boards in slots C, D, or E, select them.
3.
To activate the terminal 3, push the arrow button Right again.
4.
To change the terminal to 6, push the arrow button Up 3 times. Accept the change with the [OK] button.
5.
3.4 Programming of Analog Inputs
You can select the target input for the signal of the analog frequency reference from the available analog inputs.
If the digital input DI6 was already used for some other function, a message shows on the display. Change one of these
selections.
The value of the parameter, that is, the set analog input
Input type (graphical display)
Input type (text
display)
Slot
Input #
Explanation
AnINAIA1Analog input #1 (terminals 2/3) on a board in Slot A (standard I/O
board).
AnINAIA2Analog input #2 (terminals 4/5) on a board in Slot A (standard I/O
board).
Parameter
Default
ID
Description
AI1 Signal Selection
AnIN SlotA.1
377
STOP
READYI/O
AI1 Signal Sel
AnIN SlotA.1
P3.5.2.1.1
ID:377
Min:
Max:
e30bg711.10
VACON® 3000
Application Guide
Illustration 9: The Analog inputs menu in the graphical display
Programming of Digital and
Analog Inputs
Example
In the standard I/O board compilation, there are 2 analog inputs available: the slot A terminals 2/3 and 4/5.
AI1 Signal Selection (ID 377) gets the default value AnIN SlotA.1 in the graphical display or AI A.1 in the text display. The target input
for the signal of the analog frequency reference AI1 is then the analog input in the terminals 2/3. Use the dip switches to set the
signal to be voltage or current. See the Installation manual for more data.
To change the input from AI1 to, for example, the analog input on your option board in slot C, obey these instructions.
3.4.1 Programming of Analog Inputs in the Graphical Display
Procedure
1.
To select the parameter, push the arrow button Right.
2.
In the Edit mode, the value AnIN SlotA is underlined and blinks.
Digital inputs:
You can use this function to set a digital signal to be in a constant OPEN or CLOSED state. The manufacturer set
some signals so that they are always in the CLOSED state, for example parameter ID 407 (Run Enable). The Run
Enable signal is always on if you do not change it.
# = 1: Always OPEN
# = 2-10: Always CLOSED
Analog inputs (used for testing purposes):
# = 1: Analog input = 0% of the signal strength
# = 2: Analog input = 20% of the signal strength
# = 3: Analog input = 30% of the signal strength etc.
# = 10: Analog input = 100% of the signal strength
SlotA.#
Number (#) agrees to a digital input in slot A.
SlotB.#
Number (#) agrees to a digital input in slot B.
SlotC.#
Number (#) agrees to a digital input in slot C.
SlotD.#
Number (#) agrees to a digital input in slot D.
SlotE.#
Number (#) agrees to a digital input in slot E.
FieldbusCW.#
Number (#) refers to a control word bit number.
FieldbusPD.#
Number (#) refers to the process data 1 bit number.
Aux 14–Aux 17
Auxiliary I/O signals
MV-star
MV-star signals
Input
Terminal(s)
Reference
Function
Parameter ID
DI18A.1
Control Signal 1 A
403
DI29A.2
Control Signal 2 A
404
DI310A.3
External Fault Close
405
DI414A.4
Preset Frequency Selection 1
419
DI515A.5
Preset Frequency Selection 2
420
DI616A.6
Fault Reset Close
414
AI1
2/3
A.1
AI1 Signal Selection
377
AI2
4/5
A.2
AI2 Signal Selection
388
VACON® 3000
Programming of Digital and
Application Guide
3.To change the value to AnIN SlotC, push the arrow button Up. Accept the change with the [OK] button.
3.5 Descriptions of Signal Sources
Table 3: Descriptions of Signal Sources
Analog Inputs
3.6 Default Functions of Programmable Inputs
Table 4: Default functions of the programmable digital and analog inputs
The INU application is used to control the INU phase modules of the VACON® 3000.
It is possible to control the drive from the control panel (keypad), Fieldbus, or I/O terminal.
When controlling the drive with the I/O terminal, the frequency reference signal is connected to AI1 (0…10 V) or AI2 (4…20 mA).
The connection depends the type of the signal. There are also 3 preset frequency references available. The preset frequency references can be activated with DI4 and DI5. The start/stop signals of the drive are connected to DI1 (start forward) and DI2 (start reverse).
It is possible to configure all the drive outputs freely. There is 1 analog output (Output Frequency) and 3 relay outputs (Run, Fault,
Ready) available on the Basic I/O board.
Illustration 10: The Default Control Connections of the INU Application
4.2 Menu Structure
The data of the AC drive is in menus and submenus. To move between the menus, use the arrow buttons Up and Down in the
keypad. To go into a group or an item, push the [OK] button. To go back to the previous level, push the [BACK/RESET] button.
The display shows the current location in the menu, for example M3.2.1, and the name of the group or item.
Only the standard I/O board statuses are available in the Monitor menu. For the statuses of all the I/O board signals as raw data, see
the I/O and Hardware menu.
Check the statuses of the expander I/O board in the I/O and Hardware menu when the system asks.
B1 = Ready
B2 = Run
B3 = Fault
B6 = Run Enable
B7 = Alarm Active
B10 = DC current in stop
B11 = DC brake active
B12 = Run Request
B13 = Motor Regulator Active
V2.6.2
Ready status
1
78
B0 = Run Enable high
B1 = No fault active
B2 = Charge switch closed
B3 = DC voltage within limits
B4 = Power manager initialized
B5 = Power unit is not blocking start
B6 = System software is not blocking start
B2 = Reserved
B3 = Ramp 2 active
B4 = Mechanical brake control
B5 = I/O A control active
B6 = I/O B control active
B7 = Fieldbus Control Active
B8 = Local control active
B9 = PC control active
B10 = Preset frequencies active
B11 = Jogging active
B13 = Motor Preheat active
B14 = Quick stop active
B15 = Drive stopped from keypad
V2.6.4
Application Status Word2
1
90
B0 = Acc/Dec prohibited
B1 = Motor switch open
B5 = Precharge ready
B6 = Precharge inhibit
B7 = Precharge started
B8 = Supervision 1
B9 = Supervision 2
b0 = Software
b1 = Main Pilot Open TO
b2 = Mx Open TO
b3 = PC Contactor Open TO
b4 = DC-link Discharge TO
b5 = Front End Fault Clear TO
b6 = DC-link Overvoltage
b7 = Front End Lost Phase Lock
b8 = Front End Faulted
b9 = Mx Premature Close
b10 = Main Pilot Premature Close
b11 = Precharge Premature Termination
b12 = Max Charge Rate Exceeded
b13 = Min Charge Rate Deficient
b14 = Precharge TO
b15 = DC-link Voltage Deficient
b16 = Synchronization TO
b17 = Main Pilot Close TO
b18 = Front End Lost Synchronization
b19 = Mx Close TO
b20 = Mx Premature Open
b21 = Stabilization TO
b22 = Front End Deactivated
b23 = Front End Lost Stabilization
b24 = Unexpected Parameterization
b25 = Invalid Parameterization
b26 = Test Mode Activated While Hot
b27 = INU Became Faulted
0 = Not used
1 = Test (always closed)
2 = Ready
3 = Run
4 = Fault
5 = Fault inverted
6 = Alarm
7 = Reverse
8 = At speed
9 = Thermistor fault
10 = Motor regulator active
11 = Start signal active
12 = Keypad control active
13 = I/O B control activated
14 = Limit supervision1
15 = Limit supervision2
16 = Jogging activated
17 = Preset frequency active
18 = Quick stop active
19 = PID in Sleep mode
20 = Fieldbus Control- Word B13
21 = Fieldbus Control- Word B14
22 = Fieldbus Control- Word B15
23 = Fieldbus Process- Data1.B0
24 = Fieldbus Process- Data1.B1
25 = Fieldbus Process- Data1.B2
26 = Mechanical brake (Open brake command)
27 = Mechanical brake inverted
28 = Motor Switch Open
29 = Mains contactor permissive
30 = Mains contactor close
31 = Precharge permissive
32 = INU run enable
VACON® 3000
Application Guide
INU Application
N O T I C E
Shows only the parameters for the outputs on option boards in slots C, D, and E. Make the selections as in RO1 Function
(P3.5.3.2.1). This group or these parameters are not visible if there are no digital outputs in slots C, D, or E.
Table 56: Digital Output Settings on Standard I/O Board
Shows only the parameters for the outputs on option boards in slots C, D, and E. Make the selections as in Basic AO1 Function
(P3.5.4.1.1). This group or these parameters are not visible if there are no digital outputs in slots C, D, or E.
Table 58: Analog Output Settings on Standard I/O board
Table 60: The default values for Process Data Out in fieldbus
INU Application
Example
The value 2500 for Output frequency equals 25.00 Hz, because the scale is 0.01. All the monitoring values that you can find in the
Monitor menu are given the scale value.
Shows the mode that is set for the analog input signal.
The selection is made with a DIP switch on the control
board.
1 = 0...20mA
3 = 0...10V
V5.1.8
Analog Input 1
0
100%0.00
2509
Status of the analog input signal
V5.1.9
Analog Input 2 Mode
133
2510
Shows the mode that is set for the analog input signal.
The selection is made with a DIP switch on the control
board.
1 = 0...20mA
3 = 0...10V
V5.1.10
Analog Input 2
0
100%0.00
2511
Status of the analog input signal
V5.1.11
Analog Output 1
Mode
131
2512
Shows the mode that is set for the analog input signal.
The selection is made with a DIP switch on the control
board.
1 = 0...20mA
3 = 0...10V
V5.1.12
Analog Output 1
0
100%0.00
2513
Status of the analog output signal
V5.1.13
Relay Output 1
010
2514
Status of the relay output signal
V5.1.14
Relay Output 2
010
2515
Status of the relay output signal
V5.1.15
Relay Output 3
010
2516
Status of the relay output signal
VACON® 3000
Application Guide
4.7 I/O and Hardware Menu
4.7.1 Basic I/O
Table 97: The Basic I/O Parameters in the I/O and Hardware Menu
INU Application
4.7.2 Option Board Slots
The parameters in this menu are different for all the option boards. The parameters of the installed option board is shown. If there is
no option board in the slots C, D or E, no parameters are shown. See more about the location of the slots in chapter 3.1 General
Information on the Programming.
When an option board is removed, the fault code 39 and the fault name Device removed show on the display.
The settings that are related to the option board.
Monitoring
Monitor the data that is related to the option board.
Slot D
Settings
The settings that are related to the option board.
Monitoring
Monitor the data that is related to the option board.
Slot E
Settings
The settings that are related to the option board.
Monitoring
Monitor the data that is related to the option board.
Index
Parameter
Min
Max
Unit
Default
ID
Description
V5.5.1
Battery State
132205
Status of the battery.
1 = Not installed
2 = Installed
3 = Replace the battery
P5.5.2
Time
hh:mm:ss
2201
The current time of the day
P5.5.3
Date
dd.mm.
2202
The current date
P5.5.4
Year
yyyy
2203
The current year
P5.5.5
Daylight Saving
142204
The daylight saving rule
1 = Off
2 = EU: starts on the last Sunday in March, ends on the last
Sunday in October
3 = US: starts on the 2nd Sunday in March, ends on the 1st
Sunday in November
4 = Russia (permanent)
P5.5.6
Time Offset
2614
Index
Parameter
Min
Max
Unit
Default
ID
Description
V5.5.7.1.1
SNTP Mode
3162
V5.5.7.1.2
Server 1 IP
3163
V5.5.7.1.3
Server 2 IP
3164
V5.5.7.1.4
SNTP Port
3165
V5.5.7.1.5
Time Interval
3166
VACON® 3000
Application Guide
Table 98: Option Board Related Parameters
4.7.3 Real-time Clock
Table 99: The Real-time Clock Parameters in the I/O and Hardware Menu
INU Application
4.7.4 Simple Network Time Protocol (SNTP)
The simple network time protocol (SNTP) allows devices connected to a TCP/IP network receive precise time information from designated time servers. The time information can be received either by the client device polling the time servers or the time servers
broadcasting the time.
Number of phase module belts connected to the
control unit.
P5.6.4.9
AUX Chain Unit Count
0
6001
Number of auxiliary connections to the control unit,
for example, auxiliary I/O boards, DFE, or CCA board.
P5.6.5.1
Sine Filter
010
2527
0 = Disabled
1 = Enabled
P5.6.6.1
Harmonic Filter
010
2497
0 = Disabled
1 = Enabled
Index
Parameter
Min
Max
Unit
Default
ID
Description
P5.7.1
Timeout
Time
060min0804
The time after which the display goes back to the page that is set
with parameter P5.7.2.
0 = Not used
P5.7.2
Default
Page
040
2318
The page that the display shows when the drive is powered up, or
when the time that is set with P5.7.1 is expired. If the value is set to
0, the display shows the last page that it showed.
0 = None
1 = A menu index
VACON® 3000
Application Guide
Table 101: SNTP Monitoring
INU Application
4.7.5 Power Unit Settings
This menu contains the settings of the fan, the sine-wave filter, and the harmonic filter.
The fan operates in the optimized or the always on mode. In the optimized mode, the internal logic of the drive receives data about
the temperature and controls the fan speed. After the drive goes in the Ready state, the fan stops in 5 minutes. In the always on
mode, the fan operates in full speed, and does not stop.
The sine-wave filter keeps the overmodulation depth in limits and does not let the thermal management functions decrease the
switching frequency.
The harmonic filter can be enabled to avoid possible resonances in the DC link of the AC drive.
Table 102: Power Unit Settings
4.7.6 Keypad
Table 103: The Keypad Parameters in the I/O and Hardware Menu
Set a page to be the menu index. (The selection 1 in P5.7.2.)
P5.7.4
Contrast
3070%50830
Set the contrast of the display.
P5.7.5
Backlight
Time
060min5818
Set the time after which the backlight of the display turns off. If the
value is set to 0, the backlight is always on.
Submenu level 1
Submenu level 2
Submenu level 3
Submenu level 4
RS-485
Common settings
Protocol
Ethernet
Common settings
IP address mode
Duplicate IP detect
Speed/Duplex
Ethernet Fieldbus 1
Ethernet Fieldbus 2
Fixed IP
IP address
Subnet mask
Default gateway
Speed/Duplex
IP address
Subnet mask
Default gateway
MAC address
Packet rate
Peak packet rate
Modbus TCP
Common settings
Connection limit
Slave address
Communication timeout
IDMap
Monitoring
Control word
VACON® 3000
Application Guide
INU Application
4.7.7 Fieldbus
In the I/O and Hardware menu, there are the parameters that are related to fieldbus boards. You can find the instructions on how to
use these parameters in the related fieldbus manual.
Needed internal Ethernet based fieldbus protocols can be enabled with parameters Ethernet Fieldbus 1 (ID 2622) and Ethernet Field-bus 2 (ID 2623).
Both parameters contain the same list with “PROFINET I/O, EtherNet/IP, BACnet/IP and Modbus TCP” protocols. PROFINET I/O and
EtherNet/IP are visible only if included in the drive configuration. By default Modbus TCP is enabled, but if not used, it is recommended to turn it off.
If the same fieldbus is selected to both parameters, the fieldbus protocol is still activated only once. Protocol specific menu tree
becomes visible only after enabling it from these parameters. When using VACON® Live, to see protocol specific menus, the M5.9
Ethernet menu tree must be reloaded after enabling the protocols.
When restoring parameters from older firmware version, drive checks on start-up which protocols were enabled in old firmware and
sets up these new parameters accordingly. After having restored parameters, restart the drive. If more than two Ethernet fieldbuses
were activated in old firmware, new firmware allows it. In this case, these two new parameters show “None”, but when the values
are changed, all Ethernet fieldbuses are stopped, and only the enabled ones are started.
0 = Disabled
1 = Switch on failing
2 = Switch on faulted
P5.13.3.2
Primary Fieldbus Connection
0
2607
VACON® 3000
Application Guide
1
Depends on fieldbuses included in drive configuration
Table 106: Fixed IP
INU Application
Table 107: Fieldbus General
4.7.9 Fieldbus Redundancy
VACON® 3000 supports the usage of two fieldbus connections. The drive accepts control data only from the primary fieldbus. If the
primary fieldbus connection fails, the control can be automatically switched to a secondary fieldbus using the fieldbus redundancy
control. VACON® 3000 built-in fieldbus protocols support fieldbus redundancy control. The only exception is RS485 N2, which does
not support fieldbus redundancy. Recent firmware versions of fieldbus option boards also support fieldbus redundancy.
When switch on failing mode is selected, and the current fieldbus connection detects missing communication from the controller,
the switchover command is given to change to the other fieldbus connection. When switch on faulted mode is selected, and the
current fieldbus connection gets a timeout, the switchover command is given to change to the other fieldbus connection.
The switchback functionality forces a change back to the primary fieldbus connection when it is in operational state and when the
given time delay has elapsed. If the switchback functionality is deactivated, the switchover between the fieldbus connections is only
performed when the currently controlling fieldbus begins to fail or becomes faulted.
The currently controlling fieldbus protocol can be checked from the monitoring value V5.13.2 Controlling Fieldbus (ID 2610).
Shows the mode that is set for the analog
input signal. The selection is made with a
DIP switch on the board.
1 = 0...20 mA
3 = 0...10 V
V5.14.1.10
Analog input 2
0.00
100.00
%
0.00
29009
Status of the analog input signal
V5.14.1.11
Analog input 2 mode
29010
Shows the mode that is set for the analog
input signal. The selection is made with a
DIP switch on the board.
1 = 0...20 mA
3 = 0...10 V
V5.14.1.12
Analog input 3
0.00
100.00
%
0.00
29011
Status of the analog input signal
V5.14.1.13
Analog input 3 mode
29012
Shows the mode that is set for the analog
input signal. The selection is made with a
DIP switch on the board.
1 = 0...20 mA
3 = 0...10 V
V5.14.1.14
Analog input 4
0.00
100.00
%
0.00
29013
Status of the analog input signal
VACON® 3000
Application Guide
INU Application
4.7.10 Aux Chain
The contents of the menu depend on the units connected to the aux chain. The number of units is configured with parameter AUXChain Unit Count (ID 6001). The parameters in
unit has a similar menu and set of parameters (Aux 15, Aux 16, Aux 17).
Table 109: Aux 14 Parameters in the I/O and Hardware Menu
Table 97 are for the first unit connected to the Aux chain (Aux 14). Each connected
The AFE application is used to control the AFE phase modules of the VACON® 3000.
It is possible to control the drive from the control panel (keypad), Fieldbus, or I/O terminal.
It is possible to configure all the drive outputs freely. There is 1 analog output and 3 relay outputs (Run, Fault, Ready) available on
the basic I/O board.
5.2 Menu Structure
The data of the AC drive is in menus and submenus. To move between the menus, use the arrow buttons Up and Down in the
keypad. To go into a group or an item, push the [OK] button. To go back to the level where you were before, push the [BACK/RESET]
button.
On the display, you see your current location in the menu, for example M3.2.1. You also see the name of the group or item in your
current location.
0 = Source Voltage (pre-LCL)
1 = Shunt Capacitor Voltage
2 = PCC Voltage
1.3
Grid Voltage Feedback Channel A
0127
5021
0 = Ground/Reference
1 = AN Phase Voltage
2 = NA Phase Voltage
3 = BN Phase Voltage
4 = NB Phase Voltage
5 = CN Phase Voltage
6 = NC Phase Voltage
7 = AB Line Voltage
B1 = Ready
B2 = Run
B3 = Fault
B6 = Run Enable
B7 = Alarm Active
B10 = DC current in stop
B11 = DC brake active
B12 = Run Request
B13 = Regulator Active
V2.6.2
Ready status
1
78
B0 = Run Enable high
B1 = No fault active
B2 = Charge switch closed
B3 = DC voltage within limits
B4 = Power manager initialized
B5 = Power unit is not blocking start
B6 = System software is not blocking start
V2.6.3
Application Status Word1
1
89
B0 = Run Interlock 1
B1 = Run Interlock 2
B5 = I/O A control active
B7 = Fieldbus Control Active
B8 = Local control active
B9 = PC control active
B15 = Drive stopped from keypad
b0 = Software
b1 = Main Pilot Open TO
b2 = Mx Open TO
b3 = PC Contactor Open TO
b4 = DC-link Discharge TO
b5 = Front End Fault Clear TO
b6 = DC-link Overvoltage