This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
= DANGER! Dangerous voltage
= WARNING or CAUTION
= Caution! Hot surface
Table 1. Warning signs
1.1Danger
The components of the power unit of Vacon 100 are live when the AC drive is
connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when
Vacon 100 is connected to mains, even if the motor is not running.
After disconnecting the AC drive from the mains, wait until the indicators on the
keypad go out (if no keypad is attached see the indicators on the cover). Wait 5
more minutes before doing any work on the connections of Vacon100. Do not
open the cover before this time has expired. After expiration of this time, use a
measuring equipment to absolutely ensure that no
ensure absence of voltage before starting any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the
relay outputs and other I/O-terminals may have a dangerous control voltage
present even when Vacon 100 is disconnected from mains.
Before connecting the AC drive to mains make sure that the front and cable covers of Vacon 100 are closed.
voltage is present.
Always
During a ramp stop (see the Application Manual), the motor is still generating
voltage to the drive. Therefore, do not touch the components of the AC drive
before the motor has completely stopped. Wait until the indicators on the keypad
go out (if no keypad is attached see the indicators on the cover). Wait additional 5
minutes before starting any work on the drive.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
1
vacon • 4Safety
1.2Warnings
Vacon 100 AC drive is meant for fixed installations only.
Do not perform any measurements when the AC drive is connected to the mains.
The earth leakage current of Vacon 100 AC drives exceeds 3.5mA AC. According
to standard EN61800-5-1, a reinforced protective ground connection must be
ensured. See chapter 1.3.
If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN
60204-1).
Only spare parts delivered by Vacon can be used.
At power-up, power brake or fault reset the motor will start immediately if the
start signal is active, unless the pulse control for
Futhermore, the I/O functionalities (including start inputs) may change if parameters, applications or software are changed.Disconnect, therefore, the motor if
an unexpected start can cause danger.
Start/Stop logic has been selected
.
The motor starts automatically after automatic fault reset if the auto restart
function is activated. See the Application Manual for more detailed information.
Prior to measurements on the motor or the motor cable, disconnect the motor
cable from the AC drive.
Do not touch the components on the circuit boards. Static voltage discharge may
damage the components.
Check that the EMC level of the AC drive corresponds to the requirements of
your supply network.
1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Safetyvacon • 5
1.3Earthing and earth fault protection
CAUTION!
The Vacon 100 AC drive must always be earthed with an earthing conductor connected to the
earthing terminal marked with .
The earth leakage current of Vacon 100 exceeds 3.5mA AC. According to EN61800-5-1, one or
more of the following conditions for the associated protective circuit shall be satisfied:
a)The protective conductor shall have a cross-sectional area of at least 10 mm2 Cu or 16
mm2 Al, through its total run.
b)Where the protective conductor has a cross-sectional area of less than 10 mm2 Cu or
16 mm2 Al, a second protective conductor of at least the same cross-sectional area
shall be provided up to a point where the protective conductor has a cross-sectional
area not less than 10 mm2 Cu or 16 mm2 Al.
c)Automatic disconnection of the supply in case of loss of continuity of the protective
conductor.
The cross-sectional area of every protective earthing conductor which does not form part of
the supply cable or cable enclosure shall, in any case, be not less than:
-2.5mm
-4mm
The earth fault protection inside the AC drive protects only the drive itself against earth faults
in the motor or the motor cable. It is not intended for personal safety.
Due to the high capacitive currents present in the AC drive, fault current protective switches
may not function properly.
2
if mechanical protection is provided or
2
if mechanical protection is not provided.
Do not perform any voltage withstand tests on any part of Vacon 100. There is a
certain procedure according to which the tests shall be performed. Ignoring this
procedure may result in damaged product.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
1
vacon • 6LonWorks - general info
2.LONWORKS - GENERALINFO
Vacon 100 frequency converters can be connected to the LonWorks® network using a fieldbus
board. The converter can then be controlled, monitored and programmed from the Host system.
LONWORKS technology has been developed by Echelon Corporation. LONWORKS network is
used in applications like industry and building automation, controlling household electronics,
medical instrumentation and many others. The target of the LONWORKS network is to provide
a common vendor independent communication network for intelligent devices.
In a LONWORKS network, no central control or master-slave architecture is needed. Nodes on
a network communicate with each other using LonTalk® protocol. Interoperable nodes use
Standard Network Variable Types (SNVT) for communicating over the network. The definition
of an SNVT includes units, a range, and an increment. Vacon option board uses only Standard
Network Variable Types for the data types.
All network variables are either input (data is coming from the network to the device) or output
(data is sent to the network by the device) network variables. When network variables on different nodes on the network have been bound together by an installation tool, passing of data
is automatic between the right nodes. Only the same type of network variables can be bound
together, so it is very important to have compatible interfaces.
2
If you need further information related to LonWorks, please contact fieldbus@vacon.com
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks technical datavacon • 7
3.LONWORKSTECHNICALDATA
3.1General
InterfacePluggable connector (5 mm)
Connections and
communications
Environment
SafetyFulfils EN50178 standard
Channel typeTP/FT-10
Transfer cableShielded Twisted Pair
Baud rate78 Kbit/s
Ambient operating
temperature
Storing temperature-40°C…70°C
Humidity<95%, no condensation allowed
AltitudeMax. 1000 m
Vibration0.5 G at 9…200 Hz
-10°C…50°C
Table 2.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
3
vacon • 8LonWorks technical data
3.2Physical media and wiring
LONWORKS networks can be implemented on many different physical media. Vacon OPT-C4 option
board is equipped with an FT-X1 transceiver supporting the Free Topology transformer coupled network, which allows the network wire to be connected as bus, star, loop or combination of these. This
media reaches a communication speed of 78kBits/s. The FT-X1 transceiver is compatible with Echelon's LPT-10 Link Power Transceiver, and these transceivers can communicate with each other on a
single twisted pair cable.
TerminationTermin ation
Figure 1. Doubly terminated bus topology
The doubly terminated bus topology is recommended to be used. However, also singly termiated, star or loop topologies can be used with OPT-C4 option board.
Up to 64 FTT-10 transceiver nodes are allowed per network segment, the individual segments
can be connected together by a router. See Table 3for possible cable types and cable lengths
for FTT-10. Even if unshielded cable types are possible to be used with this type of transceiver,
it is still highly recommended to use only shielded cables with frequency converters. Attention should be paid to proper grounding of the shield to ensure bus operation. Grounding of the
shield should be done at both ends of the cable.
Cable type
JY (St) Y 2x2x0.8mm
LONAK 2x2x0,8 (shielded)
Max. doubly
terminated bus
length
900 m500 m320 m
Table 3.
Max. free
topology wire
length
Max. node-to-
node
distance
3.3Profiles
LonMark Functional Profiles describe in detail the application layer interface, including the
network variables, configuration properties, and default and power-up behaviors required on
LonMark devices for specific, commonly used control functions.
3.3.1Variable speed profile
Leading manufacturers of drive technology have jointly defined the LonMark profile. The profile specifies how the drives are to be parameterized and how the setpoints and actual values
are to be transmitted. This enables drives from different vendors to be exchanged. The profile
contains necessary specifications for speed control and positioning. It specifies the basic drive
functions while leaving sufficient freedom for application-specific expansions and further developments.
3
.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Layout, connections and installationvacon • 9
4.LAYOUT, CONNECTIONSANDINSTALLATION
Vacon LonWorks Fieldbus Board is connected to the fieldbus through 3-pin pluggable bus connector. The communication with the control board takes place through the standard Vacon Interface Board Connector.
4.1LonWorks OPT-C4 option board
H3
H2
H1
21
X5
22
23
Figure 2.
4.1.1Connections
SignalConnectorDescription
A121Data
A222Data
Shield23Shield
Table 4.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
vacon • 10Layout, connections and installation
4.1.2LED indications
The three LED indications (see Figure 2) next to the connector show the present statuses of the
Neuron (green H3), the LonWorks board (yellow H2) and the Fieldbus Module (green H1). From
the user's viewpoint, the first two are the most significant.
Neuron status (H3) GREEN
LED isMeaning:State code
OFFConfigured4
ONApplicationless and Unconfigured3
FlashingUnconfigured2
Board status LED (H2) YELLOW
LED isMeaning:
OFFOption board not activated
ON
Blinking fast
(once/1 s)
Blinking slow
(once/5 s)
Option board in initialisation state waiting for activation command from the frequency converter
Option board is activated and in RUN state
Option board is ready for external communication
Option board is activated and in FAULT state
Internal fault on option board
Bus status LED (H1) GREEN
LED isMeaning:
Fieldbus module is activated
OFF
ON
Blinking very fast
for 5s (once/0.2 s)
Blinking fast
(once/1 s)
Blinking slow
(once/5 s)
Parameters received and module activated
Module is waiting for messages from the bus
Fieldbus module is activated
Parameters received and module activated
Module is waiting for messages from the bus
Fieldbus module has received a wink request
Module is activated and receiving messages from the bus
Module is in FAULT state
No messages from Net within the watchdog time
Bus broken, cable loose
4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Layout, connections and installationvacon • 11
4.2 Installation
Open the cover of the AC drive.
1
DANGER
The relay outputs and other I/O-terminals may have a dangerous control voltage
present even when Vacon 100 is disconnected from mains.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
vacon • 12Layout, connections and installation
Make sure that the sticker on the connector of the board says “dv” (dual voltage).
This indicates that the board is compatible with Vacon 100. See below:
2
21
22
23
Slot coding
NOTE: Incompatible boards cannot be installed on Vacon 100. Compatible
boards have a slot coding that enable the placing of the board (see above)
Open the inner cover (1) to reveal the option board slots (D,E) and install the
fieldbus board (2) into slot D or E. Close the inner cover. See Figure below.
1
2
D
E
3
4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Layout, connections and installationvacon • 13
4.3Prepare for use through LonWorks
Strip about 15 mm of the fieldbus cable (see specification on page 9) and cut off
the grey cable shield. Remember to do this for both bus cables (except for the
last device).
Leave no more than 10 mm of the cable outside the terminal block and strip the
cables at about 5 mm to fit in the terminals. See picture below.
10
5
4
Also strip the cable now at such a distance from the terminal that you can fix it to
the frame with the grounding clamp. Strip the cable at a maximum length of 15
mm. Do not strip the aluminum cable shield!
5
Then connect the cable to its appropriate terminals on LonWorks Option Board
terminal block.
21 22 23
Data 1
Shield
Data 2
Fieldbus cable
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
vacon • 14Layout, connections and installation
Using the cable clamp included in the delivery of the drive, ground the shield of
the LonWorks cable to the frame of the AC drive.
Cable clamp
6
If Vacon 100 is the last device on the bus, the bus termination must be set. To
assure a proper data transmission, termination of the network segments is
required. Depending on the type of network, either one or two terminations are
necessary. Free topology network segment requires only one termination
whereas a doubly terminated bus topology requires two.
The jumper X5 on the Vacon LonWorks board must be set accordingly.
•Use 94-ohm termination resistance when only one termination is needed
•47-ohm termination resistance for two terminations
See also step 10 on page 17.
7
21
22
23
H3
H2
H1
X5
47
94
no termination
Ω
Ω
X5
4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Layout, connections and installationvacon • 15
Unless already done for the other control cables,
cut free the opening on the AC drive cover for the
fieldbus cable (protection class IP21).
NOTE: Cut the opening on the same side you
have installed the board in!
8
Remount the AC drive cover and run the cable as
shown in picture.
NOTE: When planning the cable runs, remember
to keep the distance between the fieldbus cable
and the motor cable at a minimum of 30 cm.
9
10
Fieldbus
cable
The bus termination must be set for the first and the last device of the fieldbus
line. See picture below. See also step 7 on page 16. We recommend that the first
device on the bus and, thus, terminated was the Master device.
Vacon 100 Vacon 100 Vacon 100 Vacon 100Vacon 100
Terminat ion
activated
LonWorks cable
= Bus termination
Terminatio n
deactivated
Termination
activated
jum per X5
with
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
vacon • 16Commissioning
5.COMMISSIONING
Please read first the commissioning chapter in Vacon 100 HVAC Installation manual (Download the latest version of the manual on www.vacon.com).
5.1I/O and Hardware menu (M5)
The I/O and Hardware menu makes it possible for the user
1) to see what expander boards are connected to the control board and
2) to reach and edit the parameters associated with the expander board.
3) Software information
The navigation path to the fieldbus parameters may differ from application to application. The
exemplary paths below apply to the Vacon 100 HVAC drive.
1.Set fieldbus parameters (M5.x.3). See below.
Navigate: Main Menu > I/O and Hardware (M5) > OPTC4 (M5.x) > parame-
ters (M.x.3) > Select parameter > Edit
2.Select
OR
3.Choose source of reference.
‘Fieldbus control’ as the Remote Control Place.
Navigate: Main Menu > Quick Setup (M1) > Rem. Ctrl. Place (P1.15)
Navigate: Main Menu > Parameters (M3) > Start/Stop Setup (M3.2) > Rem.
Ctrl. Place (P3.2.1)
Navigate: Main Menu > Parameters (M3) > References (M3.3)
5.2LonWorks board parameters
CodeParameterMinMaxUnitDefaultIDDescription
M5.x.3.1Service Pin010
Broadcasts a service pin
message to the network
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interfacevacon • 17
6.LONWORKSINTERFACE
Features of the LonWorks interface:
•Direct control of Vacon 100 (e.g. Run, Stop, Direction, Speed reference, Fault reset)
XIF file tells network-management tools how to communicate and recognize a device. It can be
downloaded from www.vacon.com, and it is also included with the shipped Support CD. It contains Program ID, NVs, CPs, functional blocks, etc.
6.2General
Node Object:0
nviRequest
nv1
SNVT_obj_request
Mandatory
nv oSta tus
Network
nv2
SNV T_o bj_s tatu s
Variables
Figure 3. The node object diagram
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
Figure 4. The Variable Speed Motor Drive object diagram
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interfacevacon • 19
6.3Input Network Variables
FunctionVariable NameSNVT TypeMin. value
Node Object requestnviRequestSNVT_obj_request
Driver speed setpointnviDrvSpeedStptSNVT_switchn / an / a
Driver set point speed
scaling
Reset faultnviRstFaultSNVT_switchn / an / a
Clear kWh trip or Drive
total running hours trip
counters
Process In DatanviProcessIn1..8SNVT_lev_percent065535
Digital InputsnviDigitalIn1..8SNVT_switch04
Parameter SetnviParCmdSNVT_presetn / an / a
nviDrvSpeedScaleSNVT_lev_percent-163.840%163.830%
nviClrCntrSNVT_switch12
Table 5. Input network variables
Max.
value
nviRequest
This input network variable provides the mechanism to request a particular mode for the Node
object or the Variable Speed Motor Drive object within a node. Supported requests are
RQ_NORMAL, RQ_UPDATE_STATUS, RQ_CLEAR_STATUS, RQ_REPORT_MASK,
RQ_DISABLED, RQ_ENABLE and RQ_CLEAR_ALARM.
nviDrvSpeedStpt
This input network variable provides control and a low resolution speed setpoint.
StateValueCommand
0NAStop
100%
11 to 2000.5 to 100%
1201 to 255100.0%
0xFFNAAuto
Table 6.
nviDrvSpeedScale
This input netork variable provides scaling for nviDrvSpeedStpt. Negative values indicate a motor direction in reverse. For example, if the nviDrvSpeedStpt value is 50% and nviDrvSpeedScale -150%, then the actual speed setpoint is -75%, or 0.75 times the nominal speed in
reverse direction. The valid range is -163,840% to 163,830. The value 0x7FFF (+163,835%) will
be handled as an invalid value. Default value is determined by nciDrvSpeedScale. This value
will be adopted at power-up and in case of not receiving an update within the specified Receive
Heartbeat time.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
vacon • 20LonWorks interface
nviRstFault
This input network variable provides a fault reset. Setting value 1 for State and a non-zero value for Value will reset an active fault in Vacon 100. Default value is 0; 0
StateValueCommand
0anyno action (0; 0)
10no action (0; 1)
1> 0reset fault (200 ; 0)
-1(0xFF)anyinvalid (no action)
Table 7.
nviClrCntr
This input network variable provides a mechanism to clear the kWh trip counter or the Drive
total running hours trip counter.
1 = MWh trip counter
2 = Operation day trip counter
nviProcessIn1..8
These input network variables are sent directly to the application (see more detailed explanation in chapter 6.5 Process data) The valid range is 0 to 65535 (-163,840 to 163,835).
nviDigitalIn1..8
These input network variables are sent directly to the application (see more detailed explanation in chapter 6.5 Process data) Default value is 0; 0.
StateValueCommand
0anyoff (0; 0)
10off (0; 1)
1> 0on (200 ; 0)
-1(0xFF)anyinvalid (no action)
Table 8.
6
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interfacevacon • 21
nviParCmd
This input network variable is used to read and write the parameters. The parameter addresses are determined in the application. Every parameter and actual value has been given an ID
number in the application. The ID numbering of the parameter as well as the parameter ranges
and steps can be found in the application manual in question. The parameter value must be given without decimals. Find the ID numbers of each parameter/actual value in the application
manual. The ID numbers are grouped as follows:
Parameter IDGroupDescription
0Not used
1 … 98Actual Values
37Active Fault Code
100Not used
101… 899Parameter
900 … 999Reserved
1000Not used
1001…1999Parameter
Reserved for LonWorks board
internal usage
Table 9.
Examples
Data format in examples is:
- learn selector <byte(3) byte(2) byte(1) byte(0)> day hour minute second millisecond
x = meaningless
Example1
Write to parameter number 102 (Max frequency "HVAC Application par. ID102") value 4500
(45Hz).
Write command to nviParSet
- LN_LEARN_CURRENT 102 <x x 11 94> x x x x
If the write command is successful then nvoParOut value is
- LN_LEARN_CURRENT 102 <0 0 11 94> 0 0 0 0
If the write command fails then nvoParOut value is
- LN_NUL 102 <0 0 11 94> 0 0 0 0
Example2
Read parameter number 112 (Nominal speed of the motor "HVAC Application par. ID112") default value 1440 (1440 rpm).
Read command to nviParSet
- LN_RECALL 112 <x x x x> x x x x
If the read command is successful then nvoParOut value is
- LN_RECALL 112 <0 0 5 A0> 0 0 0 0
If the read command fails then nvoParOut value is
- LN_ LN_NUL 112 <0 0 0 0> 0 0 0 0
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
vacon • 22LonWorks interface
6.4Output network variables
FunctionVariable NameSNVT TypeMin. ValueMax. Value
Process OutnvoProcessOut1..8 SNVT_ lev_percent 065535
Digital OutnvoDigitalOut1..8SNVT_switch04
Parameter OutnvoParRespSNVT_preset
NvoStatus
This output network variable reports the status for Node object or Variable Speed Motor Drive
object
nvoDrvRunHoursSNVT_time_hour0 h65535
Table 10. Output network variables
FieldDescription
object_idID of object within node
invalid_id
invalid_request
disabled1 means object disabled
1 means requested ID is not
implemented in this node
1 means request for unimplemented function
6
electrical_fault1 means drive is faulted
in_alarm1 means drive is in alarm
report_mask1 means status is an event mask
Table 11.
nvoDrvSpeed
This output network variable provides the speed of the drive as a percentage of the nominal
speed.
nvoDrvCurnt
This output network variable provides the drive output current in amperes.
nvoDrvPwr
This output network variable provides the drive output power in kW.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interfacevacon • 23
nvoDrvRunHours
This output network variable provides the drive resettable operation time counter for the motor in running hours. The maximum value for used SNVT is 65535 h. On the frequency converter
the value can go much higher. If the counter exceeds the SNVT's maximum value, the network
variable stays at its maximum. In such cases the real value can be seen on Vacon 100 HVAC
operating keypad.
nvoDrvStatus
This output network variable provides the drive status.
BitDescription
Value = 0Value = 1
0Not ReadyReady
1FC stoppedRunning
2ClockwiseCounterclockwise
3No faultFault active
4No warningWarning active
5Reference not Actual value Reference = Actual value
Table 12. Status word bit descriptions
nvoDrvEnrgy
This output network variable provides the drive resettable energy consumption counter. The
maximum value for used SNVT is 65535 kWh. On the frequency converter the value can go
much higher. If the counter exceeds the SNVT's maximum value, the network variable stays at
its maximum. In such cases the real value can be seen on Vacon 100 HVAC operating keypad.
nvoActFault
This output network variable provides the drive active fault code. If the value is 0 the frequency
converter has no fault. See the fault code list in Vacon 100 HVAC User's Manual for fault identification.
nvoProcessOut1..8
These output network variables are sent directly from the application (see more detailed explanation in chapter 6.5 Process data) The valid range is 0 to 65535 (-163,840 to 163,835)
nvoDigitalOut1..8
These output network variables are sent directly from the application (see more detailed explanation in chapter 6.5 Process data).
statevaluecommand
00off (0; 0)
1200 (0xC8)on (200; 1)
-1 (0XfF)anyinvalid (NULL)
Table 13.
nvoParResp
explained in chapter nviParSet.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
vacon • 24LonWorks interface
6.5Network configuration variables
FunctionVariable NameSNVT Type
Maximum motor speednciMaxSpeedSCPTmaxSetpoint
Minimum motor speednciMinSpeedSCPTminSetpoint
Receive heartbeat timenciRcvHrtBtSCPTmaxRcvTime
Send heartbeat timenciSndHrtBtSCPTmaxSndTime
Minimum output timenciMinOutTimeSCPTminSndTime
Nominal motor speed in RPMnciNmlSpeedSCPTnomRPM
Nominal motor frequencynciNmlFreqSCPTnomFreq
Minimum ramp up timenciRampUpTmSCPTrampUpTm
Minimum ramp down timenciRampDownTmSCPTrampDownTm
Default value for nviDrvSpeedScalenciRampDownTmSCPTdefScale
Table 14. Network configuration variables
nciMaxSpeed
This configuration property is used to define the maximum speed of a motor. The value is entered as a percentage of nominal speed in RPM, as defined by the Nominal Speed (nciNmlSpeed) configuration value. The value of the maximum speed must be validated against the
value of the minimum speed as follows:
-163.840 < minimum speed < maximum speed < 163.830
nciMinSpeed
This configuration property is used to define the minimum speed of the motor. The value is entered as a percentage of nominal speed in RPM, as defined by the Nominal Speed (nciNmlSpeed) configuration value. The value of the minimum speed must be validated against the
value of the maximum speed as follows:
-163.840 < minimum speed < maximum speed < 163.830
nciRcvHrtBt
This configuration property is used to control the maximum time that elapses after the last update of the network variables nviDrvSpeedStpt or nviDrvSpeedScale before the VSD object
starts to use the default values.
nciSndHrtBt
This configuration property defines the maximum period that expires before the network variables nvoDrvSpeed, nvoDrvCurnt and nvoDrvPwr are automatically updated.
nciMinOutTime
This configuration property defines the minimum period of automatic network variable tansmission.
6
nciNmlSpeed
This configuration property is used to provide the nominal speed of the motor in RPM. This value is necessary to determine the minimum and maximum speeds for the motor, based on the
configuration properties nciMinSpeed, nciMaxSpeed (entered as a percentage of nominal
speed).
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interfacevacon • 25
nciNmlFreq
This configuration property is used to provide the nominal frequency for the motor.
nciRampUpTm
Defines the acceleration time for Vacon 100 HVAC. The valid range is 0.0 to 6,553.4 sec (0.1 sec).
nciRampDownTm
Defines the deceleration time for Vacon 100 HVAC. The valid range is 0.0 to 6,553.4 sec (0.1
sec).
nciDrvSpeedScale
This configuration property is used as the default value for nviDrvSpeedScale. This value will
be adopted at power-up and in case no input variable within the specified Receive Heartbeat
time is received.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
vacon • 26Fault tracing
7.FAULTTRACING
When an unusual operating condition is detected by the AC drive control diagnostics, the drive
initiates a notification visible, for example, on the keypad. The keypad will show the ordinal
number of the fault, the fault code and a short fault description.
The fault can be reset with the Reset button on the control keypad or via the I/O terminal. The
faults are stored in the Fault history menu which can be browsed. The different fault codes you
will find in the table below. This fault table presents only the faults related to the fieldbus in
use.
The LonWorks option board status LEDs are described in more detail in Chapter 4.1.2
NOTE: When contacting distributor or factory because of a fault condition, always write down
all texts and codes on the keypad display and send a description of the problem together with
the
Drive Info File to fieldbus@vacon.com.
7.1Typical fault conditions
Fault conditionPossible causeRemedy
Termination
resistor
Cabling
GroundingInadequate grounding.
Connections
Parameter
Missing or excessive termination resistor.
• Supply or motor cables are located
too close to the fieldbus cable
• Wrong type of fieldbus cable
• Too long cabling
Faulty connections.
• Excessive stripping of cables
• Conductors in wrong terminals
• Too loose connections of conductors
• Faulty address
• Overlapping slave addresses
• Wrong baud rate
• Wrong control place selected
Table 15. Typical fault conditions
Install termination resistors at both ends of the
fieldbus line.
Ensure grounding in all
points on the net
7
If you need to contact Vacon service in problems related to LonWorks, please send a description of the
problem together with the Drive Info File to fieldbus@vacon.com.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Quick Setupvacon • 27
8.QUICK SETUP
Frequency converter application
Choose Fieldbus (Bus/Comm) for the active control place (see Chapter 5.1).
Master software
1 = Write 100.0 1 to nviDrvSpeedStpt.
2 = Frequency converter status is RUN and output frequency is 1.00 * nviDrvSpeedScale
3 = Write 0.0 0 to nviDrvSpeedStpt
4 = Frequency converter status is STOP.
If nvoDrvStats bit 3 = 1 Status of frequency converter is FAULT.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.