Danfoss vacon 100 User guide

vacon • 2
INDEX
Document: DPD00169A
Version release date: 13.8.09
Safety ....................................................................................................................... 3
Danger ......................................................................................................................................... 3
Warnings ..................................................................................................................................... 4
LonWorks - general info ..........................................................................................6
LonWorks technical data ..........................................................................................7
General ........................................................................................................................................ 8
Physical media and wiring .......................................................................................................... 9
Profiles ........................................................................................................................................ 9
Variable speed profile ................................................................................................................. 9
Layout, connections and installation ...................................................................... 9
LonWorks OPT-C4 option board ............................................................................................... 9
Connections .............................................................................................................................. 9
LED indications ......................................................................................................................... 10
Installation ............................................................................................................................... 11
Prepare for use through LonWorks ......................................................................................... 13
Commissioning ...................................................................................................... 16
I/O and Hardware menu (M5) ................................................................................................... 16
LonWorks board parameters ................................................................................................... 16
LonWorks interface ...............................................................................................17
XIF file .......................................................................................................................................17
General ......................................................................................................................................17
Input Network Variables ...........................................................................................................19
Output network variables .........................................................................................................22
Network configuration variables ..............................................................................................24
Fault tracing ..........................................................................................................26
Typical fault conditions .............................................................................................................26
Quick Setup ............................................................................................................27
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Safety vacon • 3
1. SAFETY
This manual contains clearly marked cautions and warnings which are intended for your per­sonal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
= DANGER! Dangerous voltage
= WARNING or CAUTION
= Caution! Hot surface
Table 1. Warning signs
1.1 Danger
The components of the power unit of Vacon 100 are live when the AC drive is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when Vacon 100 is connected to mains, even if the motor is not running.
After disconnecting the AC drive from the mains, wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes before doing any work on the connections of Vacon100. Do not open the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no
ensure absence of voltage before starting any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O-terminals may have a dangerous control voltage present even when Vacon 100 is disconnected from mains.
Before connecting the AC drive to mains make sure that the front and cable cov­ers of Vacon 100 are closed.
voltage is present.
Always
During a ramp stop (see the Application Manual), the motor is still generating voltage to the drive. Therefore, do not touch the components of the AC drive before the motor has completely stopped. Wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait additional 5 minutes before starting any work on the drive.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
1
vacon • 4 Safety
1.2 Warnings
Vacon 100 AC drive is meant for fixed installations only.
Do not perform any measurements when the AC drive is connected to the mains.
The earth leakage current of Vacon 100 AC drives exceeds 3.5mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured. See chapter 1.3.
If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN 60204-1).
Only spare parts delivered by Vacon can be used.
At power-up, power brake or fault reset the motor will start immediately if the start signal is active, unless the pulse control for Futhermore, the I/O functionalities (including start inputs) may change if param­eters, applications or software are changed.Disconnect, therefore, the motor if an unexpected start can cause danger.
Start/Stop logic has been selected
.
The motor starts automatically after automatic fault reset if the auto restart function is activated. See the Application Manual for more detailed information.
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the AC drive.
Do not touch the components on the circuit boards. Static voltage discharge may damage the components.
Check that the EMC level of the AC drive corresponds to the requirements of your supply network.
1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Safety vacon • 5
1.3 Earthing and earth fault protection
CAUTION!
The Vacon 100 AC drive must always be earthed with an earthing conductor connected to the earthing terminal marked with .
The earth leakage current of Vacon 100 exceeds 3.5mA AC. According to EN61800-5-1, one or more of the following conditions for the associated protective circuit shall be satisfied:
a) The protective conductor shall have a cross-sectional area of at least 10 mm2 Cu or 16
mm2 Al, through its total run.
b) Where the protective conductor has a cross-sectional area of less than 10 mm2 Cu or
16 mm2 Al, a second protective conductor of at least the same cross-sectional area shall be provided up to a point where the protective conductor has a cross-sectional area not less than 10 mm2 Cu or 16 mm2 Al.
c) Automatic disconnection of the supply in case of loss of continuity of the protective
conductor.
The cross-sectional area of every protective earthing conductor which does not form part of the supply cable or cable enclosure shall, in any case, be not less than:
-2.5mm
-4mm The earth fault protection inside the AC drive protects only the drive itself against earth faults in the motor or the motor cable. It is not intended for personal safety.
Due to the high capacitive currents present in the AC drive, fault current protective switches may not function properly.
2
if mechanical protection is provided or
2
if mechanical protection is not provided.
Do not perform any voltage withstand tests on any part of Vacon 100. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
1
vacon • 6 LonWorks - general info
2. LONWORKS - GENERAL INFO
Vacon 100 frequency converters can be connected to the LonWorks® network using a fieldbus board. The converter can then be controlled, monitored and programmed from the Host sys­tem.
LONWORKS technology has been developed by Echelon Corporation. LONWORKS network is used in applications like industry and building automation, controlling household electronics, medical instrumentation and many others. The target of the LONWORKS network is to provide a common vendor independent communication network for intelligent devices.
In a LONWORKS network, no central control or master-slave architecture is needed. Nodes on a network communicate with each other using LonTalk® protocol. Interoperable nodes use Standard Network Variable Types (SNVT) for communicating over the network. The definition of an SNVT includes units, a range, and an increment. Vacon option board uses only Standard Network Variable Types for the data types.
All network variables are either input (data is coming from the network to the device) or output (data is sent to the network by the device) network variables. When network variables on dif­ferent nodes on the network have been bound together by an installation tool, passing of data is automatic between the right nodes. Only the same type of network variables can be bound together, so it is very important to have compatible interfaces.
2
If you need further information related to LonWorks, please contact fieldbus@vacon.com
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks technical data vacon • 7
3. LONWORKS TECHNICAL DATA
3.1 General
Interface Pluggable connector (5 mm)
Connections and communications
Environment
Safety Fulfils EN50178 standard
Channel type TP/FT-10 Transfer cable Shielded Twisted Pair Baud rate 78 Kbit/s Ambient operating temperature Storing temperature -40°C…70°C Humidity <95%, no condensation allowed Altitude Max. 1000 m Vibration 0.5 G at 9…200 Hz
-10°C…50°C
Table 2.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
3
vacon • 8 LonWorks technical data
3.2 Physical media and wiring
LONWORKS networks can be implemented on many different physical media. Vacon OPT-C4 option board is equipped with an FT-X1 transceiver supporting the Free Topology transformer coupled net­work, which allows the network wire to be connected as bus, star, loop or combination of these. This media reaches a communication speed of 78kBits/s. The FT-X1 transceiver is compatible with Eche­lon's LPT-10 Link Power Transceiver, and these transceivers can communicate with each other on a single twisted pair cable.
Termination Termin ation
Figure 1. Doubly terminated bus topology
The doubly terminated bus topology is recommended to be used. However, also singly termi­ated, star or loop topologies can be used with OPT-C4 option board.
Up to 64 FTT-10 transceiver nodes are allowed per network segment, the individual segments can be connected together by a router. See Table 3 for possible cable types and cable lengths for FTT-10. Even if unshielded cable types are possible to be used with this type of transceiver, it is still highly recommended to use only shielded cables with frequency converters. Atten­tion should be paid to proper grounding of the shield to ensure bus operation. Grounding of the shield should be done at both ends of the cable.
Cable type
JY (St) Y 2x2x0.8mm
LONAK 2x2x0,8 (shielded)
Max. doubly
terminated bus
length
900 m 500 m 320 m
Table 3.
Max. free
topology wire
length
Max. node-to-
node
distance
3.3 Profiles
LonMark Functional Profiles describe in detail the application layer interface, including the network variables, configuration properties, and default and power-up behaviors required on LonMark devices for specific, commonly used control functions.
3.3.1 Variable speed profile
Leading manufacturers of drive technology have jointly defined the LonMark profile. The pro­file specifies how the drives are to be parameterized and how the setpoints and actual values are to be transmitted. This enables drives from different vendors to be exchanged. The profile contains necessary specifications for speed control and positioning. It specifies the basic drive functions while leaving sufficient freedom for application-specific expansions and further de­velopments.
3 .
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Layout, connections and installation vacon • 9
4. LAYOUT, CONNECTIONS AND INSTALLATION
Vacon LonWorks Fieldbus Board is connected to the fieldbus through 3-pin pluggable bus con­nector. The communication with the control board takes place through the standard Vacon In­terface Board Connector.
4.1 LonWorks OPT-C4 option board
H3 H2 H1
21
X5
22
23
Figure 2.
4.1.1 Connections
Signal Connector Description
A1 21 Data A2 22 Data
Shield 23 Shield
Table 4.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
vacon • 10 Layout, connections and installation
4.1.2 LED indications
The three LED indications (see Figure 2) next to the connector show the present statuses of the Neuron (green H3), the LonWorks board (yellow H2) and the Fieldbus Module (green H1). From the user's viewpoint, the first two are the most significant.
Neuron status (H3) GREEN
LED is Meaning: State code
OFF Configured 4
ON Applicationless and Unconfigured 3
Flashing Unconfigured 2
Board status LED (H2) YELLOW
LED is Meaning:
OFF Option board not activated
ON
Blinking fast
(once/1 s)
Blinking slow
(once/5 s)
Option board in initialisation state waiting for activation com­mand from the frequency converter Option board is activated and in RUN state Option board is ready for external communication Option board is activated and in FAULT state Internal fault on option board
Bus status LED (H1) GREEN
LED is Meaning:
Fieldbus module is activated
OFF
ON
Blinking very fast
for 5s (once/0.2 s)
Blinking fast
(once/1 s)
Blinking slow
(once/5 s)
Parameters received and module activated Module is waiting for messages from the bus Fieldbus module is activated Parameters received and module activated Module is waiting for messages from the bus
Fieldbus module has received a wink request
Module is activated and receiving messages from the bus
Module is in FAULT state No messages from Net within the watchdog time Bus broken, cable loose
4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Layout, connections and installation vacon • 11
4.2 Installation
Open the cover of the AC drive.
1
DANGER
The relay outputs and other I/O-terminals may have a dangerous control voltage present even when Vacon 100 is disconnected from mains.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
vacon • 12 Layout, connections and installation
Make sure that the sticker on the connector of the board says “dv” (dual voltage). This indicates that the board is compatible with Vacon 100. See below:
2
21
22
23
Slot coding
NOTE: Incompatible boards cannot be installed on Vacon 100. Compatible boards have a slot coding that enable the placing of the board (see above)
Open the inner cover (1) to reveal the option board slots (D,E) and install the fieldbus board (2) into slot D or E. Close the inner cover. See Figure below.
1
2
D
E
3
4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Layout, connections and installation vacon • 13
4.3 Prepare for use through LonWorks
Strip about 15 mm of the fieldbus cable (see specification on page 9) and cut off the grey cable shield. Remember to do this for both bus cables (except for the last device). Leave no more than 10 mm of the cable outside the terminal block and strip the cables at about 5 mm to fit in the terminals. See picture below.
10
5
4
Also strip the cable now at such a distance from the terminal that you can fix it to the frame with the grounding clamp. Strip the cable at a maximum length of 15 mm. Do not strip the aluminum cable shield!
5
Then connect the cable to its appropriate terminals on LonWorks Option Board terminal block.
21 22 23
Data 1
Shield
Data 2
Fieldbus cable
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
vacon • 14 Layout, connections and installation
Using the cable clamp included in the delivery of the drive, ground the shield of the LonWorks cable to the frame of the AC drive.
Cable clamp
6
If Vacon 100 is the last device on the bus, the bus termination must be set. To
assure a proper data transmission, termination of the network segments is required. Depending on the type of network, either one or two terminations are necessary. Free topology network segment requires only one termination whereas a doubly terminated bus topology requires two. The jumper X5 on the Vacon LonWorks board must be set accordingly.
Use 94-ohm termination resistance when only one termination is needed
47-ohm termination resistance for two terminations
See also step 10 on page 17.
7
21
22
23
H3 H2 H1
X5
47
94
no termination
X5
4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Layout, connections and installation vacon • 15
Unless already done for the other control cables, cut free the opening on the AC drive cover for the fieldbus cable (protection class IP21). NOTE: Cut the opening on the same side you have installed the board in!
8
Remount the AC drive cover and run the cable as shown in picture. NOTE: When planning the cable runs, remember to keep the distance between the fieldbus cable and the motor cable at a minimum of 30 cm.
9
10
Fieldbus cable
The bus termination must be set for the first and the last device of the fieldbus line. See picture below. See also step 7 on page 16. We recommend that the first device on the bus and, thus, terminated was the Master device.
Vacon 100 Vacon 100 Vacon 100 Vacon 100 Vacon 100
Terminat ion
activated
LonWorks cable
= Bus termination
Terminatio n
deactivated
Termination
activated
jum per X5
with
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
vacon • 16 Commissioning
5. COMMISSIONING
Please read first the commissioning chapter in Vacon 100 HVAC Installation manual (Download the lat­est version of the manual on www.vacon.com).
5.1 I/O and Hardware menu (M5)
The I/O and Hardware menu makes it possible for the user
1) to see what expander boards are connected to the control board and
2) to reach and edit the parameters associated with the expander board.
3) Software information
The navigation path to the fieldbus parameters may differ from application to application. The exemplary paths below apply to the Vacon 100 HVAC drive.
1. Set fieldbus parameters (M5.x.3). See below.
Navigate: Main Menu > I/O and Hardware (M5) > OPTC4 (M5.x) > parame-
ters (M.x.3) > Select parameter > Edit
2. Select
OR
3. Choose source of reference.
‘Fieldbus control’ as the Remote Control Place.
Navigate: Main Menu > Quick Setup (M1) > Rem. Ctrl. Place (P1.15)
Navigate: Main Menu > Parameters (M3) > Start/Stop Setup (M3.2) > Rem.
Ctrl. Place (P3.2.1)
Navigate: Main Menu > Parameters (M3) > References (M3.3)
5.2 LonWorks board parameters
Code Parameter Min Max Unit Default ID Description
M5.x.3.1 Service Pin 0 1 0
Broadcasts a service pin message to the network
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interface vacon • 17
6. LONWORKS INTERFACE
Features of the LonWorks interface:
Direct control of Vacon 100 (e.g. Run, Stop, Direction, Speed reference, Fault reset)
Full access to all Vacon 100 parameters
Monitor Vacon 100 status (e.g. Output frequency, Output current, Fault code)
6.1 XIF file
XIF file tells network-management tools how to communicate and recognize a device. It can be downloaded from www.vacon.com, and it is also included with the shipped Support CD. It con­tains Program ID, NVs, CPs, functional blocks, etc.
6.2 General
Node Object:0
nviRequest
nv1
SNVT_obj_request
Mandatory
nv oSta tus
Network
nv2
SNV T_o bj_s tatu s
Variables
Figure 3. The node object diagram
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
vacon • 18 LonWorks interface
Variable Speed Motor drive:
6010
nv iDrv Spee dStp t
nv1
SNV T_o bj_r equ est
nviDrvSpeedScale
nv2
SNVT _levP erce nt
nviRstFault
nv8
SNVT_switch
nviCrlCntr
nv9
SNVT_switch
nviProc essIN1
nv1 0
SNVT_lev_percent
nviProcessIN2
nv11
S NVT_ lev _per cent
nviProcessIN3
nv12
S NVT_ lev _per cent
nviProcessIN4
nv13
S NVT_ lev _per cent
nviProcessIN5
nv1 4
SNVT_lev_percent
nviProcessIN6
nv1 5
SNVT_lev_percent
nviProcessIN7
nv16
S NVT_l ev _per cent
nviProcessIN8
nv17
S NVT_l ev _per cent
nv18
nv19
nv20
nv21
nv22
nv23
nv2 4
nv25
nv26
nviDigitalIn1 SNVT_switch
nviDigitalIn2 SNVT_switch
nviDigitalIn3 SNVT_switch
nviDigitalIn4 SNVT_switch
nviDigitalIn5 SNVT_switch
nviDigitalIn6 SNVT_switch
nviDigitalIn7 SNV T_swi tch
nviDigitalIn8 SNVT_switch
nviParCmd SNVT_reset
Mandatory
Network
Variables
Optional
Network
Variables
Configuration properties
nc50 nciMaxSpeed nc53 nciMinSpeed nc48 nciRcvHrtBt nc49 nciSndHrtBt nc52 nciMinOutTm nc158 nciNmlSpeed nc158 nciNmlFreq nc160 nciRampUpTm nc161 nciRampDownTm nc162 nciDrvSpeedScal e
Manufacturer
Defined
Network
Variables
nvoDrvSpeed
nv4
SNVT_levPercent
nviRequest
nv1
SNVT_obj_request
nviRequest
nv1
SNVT_obj_request
nvi Req uest
nv1
SNVT _ob j_r eque st
nv2 7
nv2 8
nv2 9
nv oPro cess Out1
nv30
SNVT_lev_percent
nv oPro cess Out2
nv3 1
SNV T_l ev_ per cent
nvoProcessOut3
nv3 2
S NVT_l ev _per cent
nvoProcessOut4
nv3 3
S NVT_ lev _per cent
nvoProcessOut5
nv3 4
S NVT_l ev _per cent
nvoProcessOut6
nv3 5
S NVT_l ev _per cent
nvo Proc ess Out7
nv36
SNVT_lev_percent
nvo Proc ess Out8
nv37
SNVT_lev_percent
nvoDigitalOut1
nv3 8
SNVT_switch
nvoDigitalOut2
nv3 9
SNVT_switch
nvoDigitalOut3
nv40
SNVT_switch
nv oDi gita lOut 4
nv41
SNV T_swi tch
nvoDigitalOut5
nv42
SNVT_switch
nv oDi gita lOut 6
nv43
SNV T_swi tch
nvoDigitalOut7
nv44
SNVT_switch
nvo Dig italO ut8
nv4 5
SNVT_ swi tch
nv oPar Resp
nv46
SNVT_preset
nvo DrvSt atu s SNVT_ sta te
nvoDrvStatus SNVT_stat e
nvoActFault SNVT_count
6
Figure 4. The Variable Speed Motor Drive object diagram
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interface vacon • 19
6.3 Input Network Variables
Function Variable Name SNVT Type Min. value
Node Object request nviRequest SNVT_obj_request
Driver speed setpoint nviDrvSpeedStpt SNVT_switch n / a n / a
Driver set point speed scaling
Reset fault nviRstFault SNVT_switch n / a n / a
Clear kWh trip or Drive total running hours trip counters
Process In Data nviProcessIn1..8 SNVT_lev_percent 0 65535
Digital Inputs nviDigitalIn1..8 SNVT_switch 0 4
Parameter Set nviParCmd SNVT_preset n / a n / a
nviDrvSpeedScale SNVT_lev_percent -163.840% 163.830%
nviClrCntr SNVT_switch 1 2
Table 5. Input network variables
Max.
value
nviRequest
This input network variable provides the mechanism to request a particular mode for the Node object or the Variable Speed Motor Drive object within a node. Supported requests are RQ_NORMAL, RQ_UPDATE_STATUS, RQ_CLEAR_STATUS, RQ_REPORT_MASK, RQ_DISABLED, RQ_ENABLE and RQ_CLEAR_ALARM.
nviDrvSpeedStpt
This input network variable provides control and a low resolution speed setpoint.
State Value Command
0NA Stop
10 0%
1 1 to 200 0.5 to 100%
1 201 to 255 100.0%
0xFF NA Auto
Table 6.
nviDrvSpeedScale
This input netork variable provides scaling for nviDrvSpeedStpt. Negative values indicate a mo­tor direction in reverse. For example, if the nviDrvSpeedStpt value is 50% and nviDrvSpeed­Scale -150%, then the actual speed setpoint is -75%, or 0.75 times the nominal speed in reverse direction. The valid range is -163,840% to 163,830. The value 0x7FFF (+163,835%) will be handled as an invalid value. Default value is determined by nciDrvSpeedScale. This value will be adopted at power-up and in case of not receiving an update within the specified Receive Heartbeat time.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
vacon • 20 LonWorks interface
nviRstFault
This input network variable provides a fault reset. Setting value 1 for State and a non-zero val­ue for Value will reset an active fault in Vacon 100. Default value is 0; 0
State Value Command
0 any no action (0; 0)
1 0 no action (0; 1)
1 > 0 reset fault (200 ; 0)
-1(0xFF) any invalid (no action)
Table 7.
nviClrCntr
This input network variable provides a mechanism to clear the kWh trip counter or the Drive total running hours trip counter.
1 = MWh trip counter
2 = Operation day trip counter
nviProcessIn1..8
These input network variables are sent directly to the application (see more detailed explana­tion in chapter 6.5 Process data) The valid range is 0 to 65535 (-163,840 to 163,835).
nviDigitalIn1..8
These input network variables are sent directly to the application (see more detailed explana­tion in chapter 6.5 Process data) Default value is 0; 0.
State Value Command
0 any off (0; 0)
1 0 off (0; 1)
1 > 0 on (200 ; 0)
-1(0xFF) any invalid (no action)
Table 8.
6
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interface vacon • 21
nviParCmd
This input network variable is used to read and write the parameters. The parameter address­es are determined in the application. Every parameter and actual value has been given an ID number in the application. The ID numbering of the parameter as well as the parameter ranges and steps can be found in the application manual in question. The parameter value must be giv­en without decimals. Find the ID numbers of each parameter/actual value in the application manual. The ID numbers are grouped as follows:
Parameter ID Group Description
0 Not used
1 … 98 Actual Values
37 Active Fault Code
100 Not used
101… 899 Parameter
900 … 999 Reserved
1000 Not used
1001…1999 Parameter
Reserved for LonWorks board internal usage
Table 9.
Examples
Data format in examples is:
- learn selector <byte(3) byte(2) byte(1) byte(0)> day hour minute second millisecond x = meaningless
Example1
Write to parameter number 102 (Max frequency "HVAC Application par. ID102") value 4500 (45Hz).
Write command to nviParSet
- LN_LEARN_CURRENT 102 <x x 11 94> x x x x
If the write command is successful then nvoParOut value is
- LN_LEARN_CURRENT 102 <0 0 11 94> 0 0 0 0
If the write command fails then nvoParOut value is
- LN_NUL 102 <0 0 11 94> 0 0 0 0
Example2
Read parameter number 112 (Nominal speed of the motor "HVAC Application par. ID112") de­fault value 1440 (1440 rpm).
Read command to nviParSet
- LN_RECALL 112 <x x x x> x x x x
If the read command is successful then nvoParOut value is
- LN_RECALL 112 <0 0 5 A0> 0 0 0 0
If the read command fails then nvoParOut value is
- LN_ LN_NUL 112 <0 0 0 0> 0 0 0 0
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
vacon • 22 LonWorks interface
6.4 Output network variables
Function Variable Name SNVT Type Min. Value Max. Value
Node Object status nvoStatus SNVT_obj_status
Drive speed feedback nvoDrvSpeed SNVT_lev_percent -163.840% +163.830%
Actual motor current nvoDrvCurnt SNVT_amp 0.0A 3276.7A
Actual drive power nvoDrvPwr SNVT_power_kilo 0,0 kW 6553,5 kW Drive total running
hours
Status word nvoDrvStatus SNVT_state n/a n/az
kWh trip counter nvoDrvEnrgy SNVT_elect_kwh 0kWh 65535kWh
Active fault code nvoActFault SNVT_count 0 41
Process Out nvoProcessOut1..8 SNVT_ lev_percent 0 65535
Digital Out nvoDigitalOut1..8 SNVT_switch 0 4
Parameter Out nvoParResp SNVT_preset
NvoStatus
This output network variable reports the status for Node object or Variable Speed Motor Drive object
nvoDrvRunHours SNVT_time_hour 0 h 65535
Table 10. Output network variables
Field Description
object_id ID of object within node
invalid_id
invalid_request
disabled 1 means object disabled
1 means requested ID is not implemented in this node
1 means request for unimple­mented function
6
electrical_fault 1 means drive is faulted in_alarm 1 means drive is in alarm report_mask 1 means status is an event mask
Table 11.
nvoDrvSpeed
This output network variable provides the speed of the drive as a percentage of the nominal speed.
nvoDrvCurnt
This output network variable provides the drive output current in amperes.
nvoDrvPwr
This output network variable provides the drive output power in kW.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interface vacon • 23
nvoDrvRunHours
This output network variable provides the drive resettable operation time counter for the mo­tor in running hours. The maximum value for used SNVT is 65535 h. On the frequency converter the value can go much higher. If the counter exceeds the SNVT's maximum value, the network variable stays at its maximum. In such cases the real value can be seen on Vacon 100 HVAC operating keypad.
nvoDrvStatus
This output network variable provides the drive status.
Bit Description
Value = 0 Value = 1
0 Not Ready Ready 1 FC stopped Running 2 Clockwise Counterclockwise 3 No fault Fault active 4 No warning Warning active 5 Reference not Actual value Reference = Actual value
Table 12. Status word bit descriptions
nvoDrvEnrgy
This output network variable provides the drive resettable energy consumption counter. The maximum value for used SNVT is 65535 kWh. On the frequency converter the value can go much higher. If the counter exceeds the SNVT's maximum value, the network variable stays at its maximum. In such cases the real value can be seen on Vacon 100 HVAC operating keypad.
nvoActFault
This output network variable provides the drive active fault code. If the value is 0 the frequency converter has no fault. See the fault code list in Vacon 100 HVAC User's Manual for fault iden­tification.
nvoProcessOut1..8
These output network variables are sent directly from the application (see more detailed ex­planation in chapter 6.5 Process data) The valid range is 0 to 65535 (-163,840 to 163,835)
nvoDigitalOut1..8 These output network variables are sent directly from the application (see more detailed ex­planation in chapter 6.5 Process data).
state value command
00off (0; 0) 1 200 (0xC8) on (200; 1)
-1 (0XfF) any invalid (NULL)
Table 13.
nvoParResp
explained in chapter nviParSet.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
vacon • 24 LonWorks interface
6.5 Network configuration variables
Function Variable Name SNVT Type
Maximum motor speed nciMaxSpeed SCPTmaxSetpoint Minimum motor speed nciMinSpeed SCPTminSetpoint Receive heartbeat time nciRcvHrtBt SCPTmaxRcvTime Send heartbeat time nciSndHrtBt SCPTmaxSndTime Minimum output time nciMinOutTime SCPTminSndTime Nominal motor speed in RPM nciNmlSpeed SCPTnomRPM Nominal motor frequency nciNmlFreq SCPTnomFreq Minimum ramp up time nciRampUpTm SCPTrampUpTm Minimum ramp down time nciRampDownTm SCPTrampDownTm Default value for nviDrvSpeedScale nciRampDownTm SCPTdefScale
Table 14. Network configuration variables
nciMaxSpeed
This configuration property is used to define the maximum speed of a motor. The value is en­tered as a percentage of nominal speed in RPM, as defined by the Nominal Speed (nciNml­Speed) configuration value. The value of the maximum speed must be validated against the value of the minimum speed as follows:
-163.840 < minimum speed < maximum speed < 163.830
nciMinSpeed
This configuration property is used to define the minimum speed of the motor. The value is en­tered as a percentage of nominal speed in RPM, as defined by the Nominal Speed (nciNml­Speed) configuration value. The value of the minimum speed must be validated against the value of the maximum speed as follows:
-163.840 < minimum speed < maximum speed < 163.830
nciRcvHrtBt
This configuration property is used to control the maximum time that elapses after the last up­date of the network variables nviDrvSpeedStpt or nviDrvSpeedScale before the VSD object starts to use the default values.
nciSndHrtBt
This configuration property defines the maximum period that expires before the network vari­ables nvoDrvSpeed, nvoDrvCurnt and nvoDrvPwr are automatically updated.
nciMinOutTime
This configuration property defines the minimum period of automatic network variable tans­mission.
6
nciNmlSpeed
This configuration property is used to provide the nominal speed of the motor in RPM. This val­ue is necessary to determine the minimum and maximum speeds for the motor, based on the configuration properties nciMinSpeed, nciMaxSpeed (entered as a percentage of nominal speed).
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
LonWorks interface vacon • 25
nciNmlFreq
This configuration property is used to provide the nominal frequency for the motor.
nciRampUpTm Defines the acceleration time for Vacon 100 HVAC. The valid range is 0.0 to 6,553.4 sec (0.1 sec).
nciRampDownTm
Defines the deceleration time for Vacon 100 HVAC. The valid range is 0.0 to 6,553.4 sec (0.1 sec).
nciDrvSpeedScale
This configuration property is used as the default value for nviDrvSpeedScale. This value will be adopted at power-up and in case no input variable within the specified Receive Heartbeat time is received.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
vacon • 26 Fault tracing
7. FAULT TRACING
When an unusual operating condition is detected by the AC drive control diagnostics, the drive initiates a notification visible, for example, on the keypad. The keypad will show the ordinal number of the fault, the fault code and a short fault description.
The fault can be reset with the Reset button on the control keypad or via the I/O terminal. The faults are stored in the Fault history menu which can be browsed. The different fault codes you will find in the table below. This fault table presents only the faults related to the fieldbus in use.
The LonWorks option board status LEDs are described in more detail in Chapter 4.1.2
NOTE: When contacting distributor or factory because of a fault condition, always write down all texts and codes on the keypad display and send a description of the problem together with the
Drive Info File to fieldbus@vacon.com.
7.1 Typical fault conditions
Fault condition Possible cause Remedy
Termination
resistor
Cabling
Grounding Inadequate grounding.
Connections
Parameter
Missing or excessive termination resistor.
• Supply or motor cables are located too close to the fieldbus cable
• Wrong type of fieldbus cable
• Too long cabling
Faulty connections.
• Excessive stripping of cables
• Conductors in wrong terminals
• Too loose connections of conduc­tors
• Faulty address
• Overlapping slave addresses
• Wrong baud rate
• Wrong control place selected
Table 15. Typical fault conditions
Install termination resis­tors at both ends of the fieldbus line.
Ensure grounding in all points on the net
7
If you need to contact Vacon service in problems related to LonWorks, please send a description of the problem together with the Drive Info File to fieldbus@vacon.com.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Quick Setup vacon • 27
8. QUICK SETUP
Frequency converter application
Choose Fieldbus (Bus/Comm) for the active control place (see Chapter 5.1).
Master software
1 = Write 100.0 1 to nviDrvSpeedStpt.
2 = Frequency converter status is RUN and output frequency is 1.00 * nviDrvSpeedScale
3 = Write 0.0 0 to nviDrvSpeedStpt
4 = Frequency converter status is STOP.
If nvoDrvStats bit 3 = 1 Status of frequency converter is FAULT.
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
Loading...