Danfoss TE 5, TE 12, TE 20, TE 55 Installation guide

Installation guide
Thermostatic expansion valves
Type TE 5, TE 12, TE 20 and TE 55
Refrigerants:
See product label For all approved list of refrigerants, visit
067R9608
http://store.danfoss.com/
Max. working pressure PS / MWP:
28 bar / 400 psig
Max. test pressure P
32 bar / 465 psig
:
test
067R9608
Solder
Min. 5% Ag
Allen key M6
1
Type
TE 5 10 1.1 7.4 TE 12 13 1.4 9.6 TE 20 13 1.4 9.6 TE 55 15 1.6 11.1
Torque ± 5%
Nm kpm ft-lbs
2
3
Flange
45 ± 5 Nm / 33.2 ± 3.7 ft-lbs
2
© Danfoss | DCS (az) | 2020.07
1
Torx T25 Max. 4 Nm / 3 ft-lbs
Superheat = t1- t
Danfoss
67B23.20
3
ps~ t
s
Danfoss
67B51.20
s
AN02018 6412218en- 000706 | 1
Danfoss
67B27.20
06 12
12 11
11
06 05
05
Danfoss
67B27.20
12
12 11
11
Static superheat = 4 K / 7.2 °F
For range B, the static superheat need to be adjusted
(A)
10 Nm / 7.4 ft-lbs
Temperature ranges:
Range N: -40 − 10 °C / -40 – 50 °F
Range NL: -40 − -5 °C / -40 – 25 °F
Range NM: -40 − -15 °C /-40 – 5 °F
Range B: -60 − -25 °C / -75 – -15 °F
TE 5 TE 12 / TE 20 TE 55
04
03
04 03
TE 5, TE 12
TE 20, TE 55
06
06 05
SH / 360
°
N, NL, NM ~0.5 K / 1 °F
B ~1.5 K / 3 °F
N, NL, NM ~0.5 K / 1 °F
B ~1 K / 2 °F
05
12
11
12 11
Danfoss
67B27.20
Cross reference
Type Code no.
067B2788 0.5 11 9 9 7 7 9 5 5 11 3 2.5 2.5 2 2 2.5 1.5 1.5 3
067B2789 01
067B2790 02 067B2090 28 25 25 21 19 25 14 16 25 8 7 7 6 5.5 7 4 4.5 7
TE 5
067B2791 03
067B2792 04
067B2708 05 067B2008 70 56 53 46 49 56 30 35 53 20 16 15 13 14 16 8.5 10 15
TE 12
067B2709 06 95 74 70 63 63 74 39 49 74 27 21 20 18 18 21 11 14 21
067B2710 07 113 95 91 81 81 95 49 63 91 32 27 26 23 23 27 14 18 26
067B2771 08
TE 20
067B2773 09 158 148 141 98 102 148 81 91 134 45 42 40 28 29 42 23 26 38
067G2705 9B 123 109 113 84 84 113 70 74 109 35 31 32 24 24 32 20 21 31
067G2701 10 172 165 155 116 127 169 98 109 162 49 47 44 33 36 48 28 31 46
067G2704 11
TE 55
067G2707 12 208 200 186 141 151 200 116 134 190 59 57 53 40 43 57 33 38 54
067G2710 13
) Part of old TE 12 valve assembly. Need to change to TE 5 valve body and element for replacement
Orifice
Old code no. R407F R407A
no.
067B2089
067B2005 )
067B2091
067B2006 )
067B2092
067B2007 )
067B2172 067B2170 067B2175
067G2005 067G2001 067G2011
067G2006 067G2002 067G2012
18 18 18 14 14 16 11 11 18 5 5 5 4 4 4.5 3 3 5
35 32 32 28 25 32 18 21 32 10 9 9 8 7 9 5 6 9
46 42 46 39 35 42 25 28 46 13 12 13 11 10 12 7 8 13
141 127 123 84 84 127 74 77 116 40 36 35 24 24 36 21 22 33
186 183 169 127 137 183 106 120 176 53 52 48 36 39 52 30 34 50
250 243 225 172 183 246 144 165 232 71 69 64 49 52 70 41 47 66
R448A/
R449A
[kW] [TR]
R404A/
R452A
R22 R513A R134a R407C R407F R407A
R507
Rated capacity )
R448A/
R449A
R452A
R404A/
R22 R513A R134a R407C
R507
) The rated capacity is based on:
- Evaporating temperature te = 4.4 °C / 40 °F
- Condensing temperature tc = 38 °C / 100 °F
- Refrigerant temperature ahead of valve tl = 37 °C / 98 °F
© Danfoss | DCS (az) | 2020.07
AN02018 6412218en- 000706 | 2