Danfoss TD 1, TDE 1 Data sheet

Data Sheet
Thermostatic expansion valve Type TD 1 / TDE 1
Version 2
TD 1 / TDE 1 is a thermostatic expansion valve designed to regulate refrigerant injection into evaporators. The injection depends on the refrigerant superheat at the evaporator outlet, where the bulb must be placed.
TD 1 / TDE 1 is constructed for hermetic sealed systems and supplied as angleway and straightway version.
• GDM (Glass Door Merchandiser)
• Commercial fridge and freezer
• Heat Pump
AI218286432213en-000801
Thermostatic expansion valve, Type TD 1 / TDE 1
Features
• Refrigerants: R134a, R1234yf, R22, R290, R404A, R407C, R452A, R454C, R455A, R513A. Other refrigerants are on request.
• Rated capacity from 0.87 to 6.86kW / 0.25 to 1.95TR for R290.
• Stainless steel bulb and Danfoss patented bulb strap:
1.
Fast and easy to install
2.
Good temperature transfer from pipe to bulb.
• Supplied with xed superheat setting as well as adjustable straightway version for setting customization.
• Permanent lter at inlet.
• Optional bleed function.
• Compact and hermetic construction.
• Stainless steel capillary tube
1.
Flexible lightweight capillary tube, tolerates more bending for trouble-free installation and longer life.
2.
Greater resistance to vibration during operation because of low weight
• Laser welded stainless steel power element, capillary tube and bulb:
1.
optimum regulation properties
2.
long life of diaphragm
3.
high pressure strength
• MOP (Max. Operating Pressure) function is available.
• UL Certied
© Danfoss | Climate Solutions | 2022.03 AI218286432213en-000801 | 2
1
2
3
4
5
Danfoss
68N242
12345
Thermostatic element (diaphragm)
Strainer
Fixed orice assembly
Bulb with capillary tube
Locked setting screw
Thermostatic expansion valve, Type TD 1 / TDE 1
Functions
Figure 1: Angle way xed superheat setting
TD 1 / TDE 1 valves have a xed orice assembly. Both straight way and angle way conguration are available and the angle way version is designed with xed superheat setting only.
The valves are available with internal or external pressure equalization. External pressure equalization should always be used on systems with liquid distributors.
The stainless steel capillary tube and bulb with Danfoss patent bulb strap give reliable connection. It gives fast and precise reaction to temperature changes in the evaporator.
© Danfoss | Climate Solutions | 2022.03 AI218286432213en-000801 | 3