Danfoss TCI 25 CH-C Data sheet

Data sheet

CI-tronicTM Single-phase Soft Starters for commercial compressor applications

Types TCI CH-C

The TCI CH-C single-phase soft starters are designed for starting/stopping

of single-phase CSR motor compressors for residential pumps, refrigeration and A/C units.

The controller is optimised to create softstart within 200 ms.

Features

yy Control voltage 208 – 240 V AC

yy IP20 protection

 

yy SCR controlled soft cut-in and cut-out

yy Compact modular design

 

of the start capacitor

 

 

 

yy DIN rail mountable

 

yy LED status indication

 

 

 

yy Ramp-up time < 200 ms (factory set-up)

 

yy Automatic adaptation to 50/60 Hz

 

 

 

yy EN 60947-4-2

 

yy Easy and quick installation

 

 

yy Built in varistor protection

 

© Danfoss | DCS (az) | 2018.02

DKRCC.PD.LD0.A3.02 | 1

Danfoss TCI 25 CH-C Data sheet

Data sheet | Single-phase Soft Starters for commercial compressor applications, Types TCI - CH - C

Technical data

Output specifications

 

 

 

 

 

 

 

 

Type

 

TCI 25 CH-C

 

Operational voltage

 

208 – 240 V AC

 

Operational current (AC-58b)

 

max. 25 A

 

Ramp-up time (preset)

 

max. 0.2 s

 

Leakage current

 

max. 5 mA

 

Operational current

 

min. 50 mA

 

Overload relay trip class

 

Class 10

 

Semiconductor protection

 

Type 1 1) co-ordination

63 A gL/gG

 

fusing Pt (t=10 ms)

 

Type 2 2) co-ordination

6300 A2s

 

Rating index AC-58b:

 

25 A: AC-58b:

 

Hermetic refrigerant compressor 3) motor with bypass

 

6-2:600

1) Type 1 co-ordination require that, under short-circuit conditions, the device shall cause no danger to persons

or installation and may not be suitable for further use without repair and replacement of parts.

2) Type 2 co-ordination require that, under short-circuit conditions, the device shall cause no danger to persons or installation and shall be suitable for further use.

3) 12A: AC-58b: 6-2:300 means max. load 6 × 12 A for 2 seconds: Min. 300 seconds between starts.

Control circuit specifications

Control voltage range

208 – 240 V AC

Pick-up voltage

max. 177 V AC

Drop-out voltage

min. 50 V AC

Control current for no operation

max. 1.5 mA AC

Control current / power

max. 3 VA

Response time

max. 100 ms

Fuse

max. 10 A gL/gG

EMC immunity

Tested acc. to Art. 9.3.5 EN 60947-4-2

Insulation

Rated insulation voltage [Ui]

660 V AC

Rated impulse withstand voltage [Uimp]

4 kV

Installation category

III

Thermal specification

Cooling method

Natural convection

Storage temperature range

-20 – 80 °C

Ambient temperature

-20 – 40 °C

Enclosure degree / pollution degree

IP20 / 3

Power dissipation, continuous duty

max. 4 – 5 W

Power dissipation, intermittent duty

max. 4 – 5 W × duty cycle

Materials

Housing self extinguishing: PC/ ABS

© Danfoss | DCS (az) | 2018.02

DKRCC.PD.LD0.A3.02 | 2