Danfoss SVA-S 100-200 Installation guide

Danfoss SVA-S 100-200 Installation guide

Installation Guide

Shut-off valves, SVA-S 100-200

Max permissible pressure difference for closing/opening

<![if ! IE]>

<![endif]>148R9629

<![if ! IE]>

<![endif]>148R9629

P1

P2

P2

P1

ENGLISH

The SVA 100-200 stop valve has a limitation on the operating pressure differential, when the valve has to close/open. This differential closing pressure is according to EN12284 which is a part of EN378-1.

The table below states the maximum pressures at which the valves can be operated manually and tightness can be achieved.

 

 

Flow direction

 

 

 

 

 

 

P1 P2

P2 P1

P2 P1

Valve size

Closing and opening pressure

Closing pressure

Opening pressure

[DN]

ΔP max. (P1-P2)

ΔP max. (P2-P1)

ΔP max. (P2-P1)

 

 

 

 

100

44 bar / 638 psi

52 bar / 754 psi

44 bar / 638 psi

125

33 bar / 478 psi

52 bar / 754 psi

33 bar / 478 psi

150

21 bar / 304 psi

52 bar / 754 psi

21 bar / 304 psi

200

14 bar / 203 psi

52 bar / 754 psi

14 bar / 203 psi

© Danfoss | DCS (MWA) | 2018.09

AN146986431184en-000102 | DKRCI.PI.KD2.M2.02 | 1