Danfoss SonoSelect 10, SonoSafe 10 Data sheet

Data sheet
SonoSelect 10 and SonoSafe 10 Energy Meters
Description
The Danfoss SonoSelect 10 and SonoSafe 10 are ultrasonic compact energy meters intended for measuring energy consumption in heating, cooling and combined heating and cooling applications for billing purposes. The meters are
The energy meters consist of an ultrasonic flow sensor, a pair of Pt1000 temperature sensors and a calculator with integrated circuits for temperature measurement, flow calculation and energy calculation.
designed for remote meter read-out (AMR).
Feature highli ghts:
• Proven ultrasonic measuring principle designed for long operating life time
• No calming section or inlet/outlet restrictions
• Large 85 x 35 mm LCD display with 8 digits (11.5 mm high), guiding menu and info panel
• Compact design
• Extensive change and error log
• Memory: 4 years of data, yearly and monthly values stored (incl. pulse input)
• Upgradable with communication modules in bracket (dual M-Bus, connection with water meter)
• Power supply 3.6V batter y (replacable) or 230V mains power
• Communication baud rate 300, 2400, 4800 and 9600 bps
• SonoApp usable for Android (Bluetooth LE via dongle)
Special features:
Battery • 16 + 1 years batter y life (from production date) • 10 + 1 years battery life
Flexibility
Safety
SonoApp
SonoSelect 10 SonoSafe 10
• Heating or cooling or combined heating and cooling
• Supply and return can be configured on site
• Energy units can be conf igured on site
• Slot for communication upgrade
• 1.5m PUR or silicone cable bet ween calculator and f low sensor allow for flexible installation, e.g. in flat stations
• EN1434 class 2 + flow and energy calculated every 0.5 second
• Tamper monitor sets alarm if meter is opened by unauthorized personnel
• Diagnostic function to secure confidence in meter data
• IP65 calculator
• Reverse flow indication
• Installer tool (Guides and configure e.g. AMR , Pulse, units, supply/return)
• Commissioning tool (Link location to serial number)
• Operation tool (walk by + diagonstics)
p
• Heating
• Energy units can be conf igured on site
• Slot for communication upgrade
• 0.5 m cable PVC between calculator and flow sensor
• EN1434 class 2 + flow and energy calculated every 2 seconds
• IP54 calculator
• Installer tool (Guides and configure e.g. AMR, Pulse, units)
• Operation tool (walk-by)
• Commissioning tool (Link location to serial number)
© Danfoss | 2021.07 AI191586476414en-011003 | 1
Data sheet SonoSelect 10 and SonoSafe 10 energy meters
Technical specifications, Complete energy meter
* Bifunctio nal energy meters avail able only in appro ved meteorological range 5-95 °C
Technical specifications, Calculator
* Batter y life time measured under following pre conditions: enclosure temp. 45° C, communicatio n every 15 min. at 2400 baud or faster, 80 me ters on bus. Please contac t Danfoss for further information.
Application Heating, cooling or combined heating and cooling* Medium Water quality with pH 7 to 9.5 VDI 2035, VdTÜV TCh 1466 Approvals, heating EN1434 class 2 and 3, MID (DK-0200-MI004-034), CPA according to JJG225 -2010
Approvals, cooling
Measuring cycle
Approved meteorological range
Temp. limits (energy calculation)
IP 65 (SonoSelect 10), 54 (SonoSafe 10) Cable strain relief Withstand more than 5 kg Ambient operating temperature Class A: 5 - 55° C indoor installation non condensing Ambient storage temperature -25 - 60° C
Temperature media
Mechanical environment Class M2 Electromagnetic environment Class E1
Power supply 3.6 V DC lithium batter y (2 AA SonoSelect 1 AA SonoSafe), Mains supply 230V AC Battery life time* 16+1 years (SonoSelect 10), 10+1 years (SonoSafe 10)
Voltage of Alternating Current 230V AC Upper and lower voltage tolerance +10 %/-15% Alternating current voltage frequency 50/60 Hz Power consumption < 2. 5VA
Mains Supply
Display
Units MWh - kWh - GJ - Gcal - °C - K - m3 - m3/h - l/h
Memory
Optical interface
Communication
Additional communication 1 slot for communication module (delivered from factory or later upgrade)
Output 3.6V DC
Backup supply
Cable gland M12
Mains supply cable
Denmark: TS 27.02 010, Switzerland: METAS CH-T2-17763-01,
Germany: PTB 17-22.001-DK, Austria: BEV-13.426_0078-E2_ 2017
Flow: 0.5 sec. (SonoSelect 10), 2 sec. (SonoSafe 10)
Energy: 0. 5 sec. (SonoSelect 10), 2 sec. (SonoSafe 10)
Temperature: 4 sec. (SonoSelect 10), 10 sec. (SonoSafe 10)
SonoSafe SonoSelect ΔΘ: 3- 90K ΔΘ: 3 - 90K ΔΘ: 3 - 125K Θ: 5- 95 °C Θ: 5 - 95 °C Θ: 5 - 130 °C
SonoSafe SonoSelect
ΔΘ: 0.25 - 100K ΔΘ: 0.25 - 100K ΔΘ: 0.25 - 130K
Θ: 0 - 105 °C Θ: 0 - 105 °C Θ: 0 - 140 °C
SonoSafe SonoSelect
5-95 °C 5-95 °C 5-130 °C
Integral SuperCap eliminates interruptions of Energy meter due to power failures for up to 60 Min.
2 wire with PHR3-2 connector for Mains supply
85 x 35 mm LCD display with 8 digits (11.5 mm high main characters)
16 years of operation at qp, 45 °C without display overflow
4 years of data, yearly and monthly values stored (incl. pulse input)
Data protocol acc. to EN13757-3, supports 2400 or 4800 baud.
Wired M- Bus to EN13757-3, supports 300, 2400, 4800, 9600 baud. Delivered with 1 m cable (SonoSelec t 10: PUR, SonoSafe 10: PVC)
ss: Primary address, yWWsssss: Secondary address
Menu guide and info panel
available as of FW01.06.00
Optic al acc . to EN6 2056-21.
Serial number: sssssvvNNyyWW (addressing)
Technical specifications, Flow sensor
* Technically prepa red for 1:250 qi
DN 15 15 20 20 25 25 25 32 Nominal flow q Max flow q Minimum flow (1:100) qi* Cut off flow q Overf low q Pressure drop (at qp 50 °C) (mBar) 30 150 150 160 13 0 130 220 220 Kvs values (Δp=Q2/Kvs2
Connection
Pressure PN (bar) 16 (SonoSafe); 16 and 25 (SonoSelect) IP [EN60529] 65 Temperature limits (°C) 0 to 105 (SonoSafe); 0 to 105 and 0 to 130 (SonoSelect) Cable length 1.5m (SonoSelect 10: PUR or silicone), 0.5m (SonoSafe 10: PVC) Mounting Any position, no inlet or outlet restrictions
p
s
c
ss
(m3/h) 0.6 1.5 1.5 2.5 3.5 3.5 6.0 6.0 (m3/h) 1.2 3 3 5 7 7 12 12 (m3/h) 0.006 0. 015 0. 015 0.025 0.035 0.035 0.06 0.06 (m3/h) 0. 0012 0.003 0.003 0.005 0.007 0.007 0 .012 0. 012 (m3/h) 1.32 3.3 3.3 5.5 7. 7 7.7 12. 3 12 .3
)
3.46 3.87 6.25 9.71 9.71 12. 79 G¾A”
110 mm
G1A”
130 mm
G1¼A”
160mm
G1¼A”
260mm
G1¼A”
260mm
G1½A”
260mm
2 | AI191586476414en-011003 © Danfoss | 2021.07
Data sheet SonoSelect 10 and SonoSafe 10 energy meters
Technical specifications, Temperature sensor
Communication modules
* See section w ith data telegram.
* Suitable for bot h electronic switch and Reed conta ct.
Typ e Pt1000 direct short, 2 wire Size Diameter: Ø5.2 mm, length: 26 mm Nipple M10 x 1 mm brass, with pin lock Cable length 1.5 m Accuracy Class B (EN60751)
Temperature range
IP 65
Approved temp. range to EN60751
Difference temp. EN60751
Pressure 25 bar
SonoSafe SonoSelect 5 to 95 °C 0 to 105 °C 0 to 150 °C
SonoSafe SonoSelect
Θ: 0 - 105 °C Θ: 0 - 105 °C Θ: 0 - 150 °C
SonoSafe SonoSelect
ΔΘ:3 - 105 K ΔΘ:3 - 105 K ΔΘ:3 - 150 K
Modules in general
To adapt the meter for various applications SonoSelect 10 and SonoSafe 10 features a slot for mounting communication modules. Each module features its own µ-controller and is powered by its own battery. Modules have their own parameter set which is saved in the module µ-controller flash memory. A local copy of the energy meter parameters used for communication is stored in the module. Data from module is updated in meter every 10 minutes. Power: Lithium Thionyl Chloride battery (half of AA size) or Mains power supply (230 V). 2 pulse in/outputs have common ground. Modules are galvanically isolated from main Energy Meter circuitry.
Wired M-Bus module with 2 pulse inputs
Once installed the meter will display the icon for wired communication and pulse inputs in loop 2 of the display. Wired M-Bus is galvanically isolated from µ-controller and pulse inputs. The two pulse inputs can be programmed independently of each other (see specification for pulse input module).
M-Bus (primary) Lithium Thionyl Chloride batter y (half of AA size) M-Bus (secondary) M-Bus supply Baud rate supported 300, 2400, 4800, 9600 Communication protocol According to EN1434-3 & EN13757-3 Battery life time 16 +1 ye ar
Addressing
Serial number: sssssvvNNyyWW
ss: Primary address, yWWsssss: Secondary address
Wireless OMS communication module, 868.95MHz with 2 pulse inputs
Once installed the meter will display the icon for wireless communication and pulse inputs in loop 2 of the display. The two pulse inputs can be programmed independently of each other (see specification for pulse input module).
Standard Open Metering System (OMS) issue 4.0.2 Frequency 868.95 MHz Antenna Internal Transmission power 10mW (Max. 25mW; 13,9 dBm) Mode T1 mode Encryption AES 128 bit encryption (mode 5), Parameterized Static key Sending interval Fixed network: 15 min. Tel egram Standard telegram* Battery life time 12+1 year (with pulse inputs off)
Addressing
Serial number: sssssvvNNyyWW
yWWsssss: Secondary address
2 pulse input module
Once installed the meter will display the icon for pulse inputs in loop 2 of the display. Accumulated volume is only readable by communication. The two pulse inputs can be programmed independently of each other.
Pulse value 0.001 m³ to 1 m³ per pulse Voltage supply ≤ 6.0 V Source current ≤ 0.1 mA High level input threshold ≥ 2 V Low level input threshold ≤ 0.5 V Pull-up resistor 100 k Ω Pulse length ≥10 0 ms Maximum frequency ≤ 5 Hz Pulse inputs According to EN1434-2, section 7.1.5 (Classification of pulse input devices Class IB)* Battery life time 16+1 year
AI191586476414en-011003 | 3© Danfoss | 2021.07
Data sheet SonoSelect 10 and SonoSafe 10 energy meters
-∆
∆Θ
∆Θ
θ
No energy accumulation
Communication modules (continuous)
*Default set ting. Can be changed via SonoApp
Note! Default set ting can be changed via SonoApp
2 pulse output module
Once installed the meter will display the icon for wired communication in loop 2 of the display.
Pulse 1 (energy*) + terminal 16, - terminal 17 Pulse 2 (volume*) + terminal 18, - terminal 19
Pulse value*
Pulse timing
Polarity reversal: Not possible, but can withstand -30V, max 27 mA without damage Pulse length ≥10 0 ms Pulse Pause: ≥10 0 ms Voltage supply 3-30 V Source current ≤ 27 mA “ON” condition U<2,0 @ 27 mA “OFF” condition R>= 6 MΩ Maximum frequency ≤ 5 Hz
Pulse outputs
Battery life time 16+1 y ear Cable length Max 25 m
Alarms
Unit follow the display. Scaling follow least significant digit of the display (default
setting can be changed via SonoApp)
Updates ever y 15 seconds
According to EN1434-2, section 8.2.3
(Classification of pulse output devices Class OB)
E32 is activated in meter if:
1) Module battery is empty
2) When no. of delayed pulses exceeds 500 0 (incorrect scaling)
Data telegram
Wired M-bus
Standard telegram (16 seconds if main powered):
• Accumulated Energy (heat and cooling for bifunctional)
• Accumulated Volume (heat and cooling for bifunctional)
• Current flow
• Current power
• Supply temperature
• Return temperature
• Difference temperature
• Enclosure temperature
• Current time
• Hour counter factory
• Hour counter OK
Wireless M-bus (OMS)
Standard telegram fixed network (15 minutes sending inter val, 16 seconds if mains powered):
• Accumulated Energy (heat and cooling for bifunctional)
• Accumulated Volume (heat and cooling for bifunctional)
• Current flow
• Current power
• Supply Temperature
• Return Temperature
• Current Time
Wireless M-Bus (Walk -by)
Standard telegram Walk by (2 minutes sending interval, 16 seconds if mains powered):
• Accumulated Energy (heat and cooling for bifunctional)
• Accumulated Volume (heat and cooling for bifunctional)
• Current Time
• Hour counter factory
• Month log 1 (last month log)
Bifunctional meters Bifunctional meters are for combined heating and cooling applications. Θhc default value is
30 °C it can be configured with SonoApp. Bifunctional energy meters available only in approved meteorological range 5-95 °C.
Inlet
Key
θ
hc
Θ
min
0
hc
min
θ
hc
+∆Θ
Heating
Cooling
Θhc = Θcuto = 0 .25K
ΔΘhc = ΔΘcutoff = 0.25K
∆Θhc∆Θ
4 | AI191586476414en-011003 © Danfoss | 2021.07
Data sheet SonoSelect 10 and SonoSafe 10 energy meters
0 10 20 30 40 50 60 70 80 90 100
5.5
-0.5
-1.0
-1.5
-2.0
-2.5
-3.0
-3.5
-4.0
-4.5
-5.0
-5.5
Application drawings
Heat meters have red temp sensor in supply pipe and all cooling meters have blue temp sensor in supply pipe
Supply
Return
Accuracy
Flow sensor error
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
Err or [%]
Production accuracy limits @ 50° CEN1434 Class 2'
Flow rate [%]
Note: In accordance with EN 1434.
AI191586476414en-011003 | 5© Danfoss | 2021.07