Danfoss Solar S Fact sheet

Fact sheet
Termix Solar S+
Wall-mounted domestic hot water module for flats, single-family houses and apartment buildings
Application
The Termix Solar S+ is an instanta­neous water heater, featuring good heat extraction and performance by means of a plate heat exchanger and a high-performance charging pump. The heat exchanger is made solely of stainless steel, thereby making this station the perfect choice for areas where copper corrosion is known to occur. Termix Solar S+ is applicable for heating systems with buffer accumu­lators, solar systems or for other heat sources, where a low return tempera­ture is preferred. The primary source is cooled out efficiently by the heat exchanger, thereby creating a good operation economy. A flow switch in the domestic hot water pipe is con­trolling the primary pump. An option­al circulation pump can maintain the circulating temperature at a desired temperature.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and the tempera­ture is regulated with a thermostatic control valve. The AVTB valve ensures a stable hot water temperature by varying loads, flow temperatures and differential pressure, without the need for readjusting the valve. There is no additional pressure loss on the secondary side of the heat exchanger with a thermostatic control. There­fore this unit is suitable in systems with low pressure in the cold water mains.
Options
The water heater can be provided with a circulation pump with safety valve, a white-laquered steel cover and two different ball valve sets (one set is with DVGW approval for DHW).
FEATURES AND BENEFITS
• Domestic hot water module with tap capacity of up to 30l/min. at 84 kW
• Thermostatic control
• Operates independently of differential pressure and flow temperature
• Heat exchanger made of stainless steel; ideal for areas with known copper corrosion
• High efficiency pump capable of 7m head
• Reliable long-life AVTB regulation valve
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The gasketed heat exchanger is made of stainless steel plates.
www.danfoss.com
CIRCUIT DIAGRAM – EXAMPLE
BT
21
supply
supply
return
return
1
BT
35
BT
21
1 13
BT
35
13
230 V
M
Termix Solar S+ B Heat exchanger DHW
21
45
1A
DHW
M Electrical wiring box 1 Ball valve 1A Ball valve, DVGW 7 Thermostatic valve 13 Charging pump 21 To be ordered separately 35 Ball valve / non-return valve 45 Flow switch
7
1A
DCW
B
230 V
M
Termix Solar S+
21
45
1A
DHW
with circulation B Heat exchanger DHW M Electrical wiring box 1 Ball valve 1A Ball valve, DVGW
7
21
2
1A
DCW
B
4
11 A
230 V
Circ.
1
2 Single check valve 4 Safet valve 7 Thermostatic valve 11A Domestic hot water pump
with built in check valve 13 Charging pump 21 To be ordered separately 35 Ball valve / non-return valve 45 Flow switch
Technical parameters:
Nominal pressure: PN 10 DH supply temperature: T DCW static pressure: P HEX material: Stainless steel
= 120 °C
max
= 0.5 bar
min
Weight incl. cover: 18 kg (incl. packing)
Dimensions (mm):
Without cover: H 655 × W 440 × D 140 With cover: H 715 × W 450 × D 150 With circulation: H 940 × W 440/450 × D 140/150
Connections:
1. Buffer tank (BT) supply
2. Domestic hot water (DHW)
3. Buffer tank (BT) return
4. Domestic cold water (DCW)
5. Circulation (optional)
DHW: CAPACITY EXAMPLES
DHW temperature
[°C]
10 / 45 57
10 / 50
Tap capacity
[kW]
84
440 45
246 100
655
940
303 100
5
135 168
Supply flow primary
[°C]
55 35 70 35
1 2
3 4
45
138
45
Pressure loss primary
[kPa]
Connections sizes:
All connections: G ¾“(int. thread)
Module code number: 144H2346
Options:
• Circulation pump with 10 bar safety valve (144H0936)
• White-laquered steel cover (144H1282)
• Ball valve set with 4 ball valves (144H0930)
• Ball valve set with 4 ball valves, of which two are with DVGW approval (144H0932)
Tap flo w
[l/min]
23 30
© Danfoss | DHS-SRMT/ PL | 2018 . 04
VL.MG.Y1.02