Danfoss Solar A, Solar B, Solar S Operating guide

OperatingGuide
TermixSolarA+/B+/S+

1.0TableofContents

1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotes–general............................................4
4.0Mounting........................................................5
4.2Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.3Design...............................................................10
5.4Schematicdiagram................................................11
6.0Controls..........................................................12
6.1DHWtemperaturecontrol........................................12
6.2Maintenance........................................................15
7.0Troubleshooting..............................................16
7.1Troubleshootingingeneral......................................16
7.2TroubleshootingDHW............................................17
7.3Disposal.............................................................18
8.0Declaration......................................................19
8.1Declarationofconformity........................................19
©Danfoss|2019.04VI.JV.I4.02/LUK38016|1
OperatingGuideTermixSolarA+/B+/S+
2|©Danfoss|2019.04
VI.JV.I4.02/LUK38016
OperatingGuideTermixSolarA+/B+/S+

2.0Functionaldescription

Domestichotwatermodulewithheatexchangerand thermostaticcontrol.Designedforwall-mounting.
Application
TheT ermixSolarA+/B+/S+isaninstantaneouswaterheater, featuringsuperbheatextractionandhighperformance.The TermixSolarA+/B+/S+isapplicableforheatingsystemswithbuffer accumulators,solarsystemsorforotherheatsources,whereavery lowreturntemperatureispreferred.Thelargeheatexchanger coolsoutthewaterintheprimaryreturnlineveryefficiently, therebycreatingaverygoodoperationeconomy.Aflowswitchin thedomestichotwaterpipeiscontrollingtheprimaryheating pump.Anoptionalcirculationpumptogetherwithathermostat canmaintainthecirculatingtemperatureatadesiredtemperature.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerandthe temperatureisregulatedwithathermostaticcontrolvalve.There isnoadditionalpressurelossonthesecondarysideoftheDHW heatexchangerwithathermostaticcontrol.Thereforethistypeof regulationcanbeusedbylowpressureinthecoldwatermains.
VI.JV.I4.02/LUK38016
©Danfoss|2019.04|3
OperatingGuideTermixSolarA+/B+/S+

3.0Safetynotes

3.1SafetyNotes–general

Thefollowinginstructionsrefertothestandarddesignof substation.Specialversionsofsubstationsareavailableon request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation andstart-upofthesubstation.Themanufactureracceptsno liabilityfordamageorfaultsthatresultfromnon-compliancewith theoperatingmanual.Pleasereadandfollowalltheinstructions carefullytopreventaccidents,injuryanddamagetoproperty. Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly. Pleasecomplywiththeinstructionsissuedbythesystem manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass. Themaximumchloridecompoundsoftheflowmediumshouldnot behigherthan150mg/l. Theriskofequipmentcorrosionincreasesconsiderablyifthe recommendedlevelofpermissiblechloridecompoundsis exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary sourceofenergy.However,alsootherenergysourcescanbeused wheretheoperatingconditionsallowitandalwaysarecomparable todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse installationinafrost-freeroom,wherethetemperaturedoesnot exceed50°Candthehumiditydoesnotexceed60%.Donotcover orwallupthesubstationorinanyotherwayblocktheentrance tothestation.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis 120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16 versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases considerablyiftherecommendedpermissibleoperatingparameters areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves, however,alwaysinaccordancewithlocalregulations.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat thesubstationcanbeseparatedfromallenergysources(also powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous circumstances-interruptallenergysourcestothestationif possible,andseekexperthelp. Incaseofdiscolouredorbad-smellingdomestichotwater,closeall shut-offvalvesonthesubstation,informtheoperatingpersonnel andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH. OneoftheobligationsinREACHistoinformcustomersabout presenceofCandidatelistsubstancesifany,weherebyinform youaboutonesubstanceonthecandidatelist:Theproduct containsbrasspartswhichcontainslead(CASno:7439-92-1)ina concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto installationshouldbeinconditionswhicharedryandheated.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns. Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen position.Thesurfacesofthesubstationcangethot,whichcancause skinburns.Theballvalvesondistrictheatingsupplyandreturnshould beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints andelectricalclampandscrewconnectionsmustbecheckedand tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen addedtothesystemandthesystemhasbeenputintooperation, re-tightenALLconnections.
4|©Danfoss|2019.04
VI.JV.I4.02/LUK38016
OperatingGuideTermixSolarA+/B+/S+

4.0Mounting

4.1Mounting

Installationmustbeincompliancewithlocalstandardsand regulations. Districtheating(DH)-Inthefollowingsections,DHreferstothe heatsourcewhichsuppliesthesubstations.Avarietyofenergy sources,suchasoil,gasorsolarpower,couldbeusedasthe primarysupplytoDanfosssubstations.Forthesakeofsimplicity, DHcanbetakentomeantheprimarysupply.
Connections:
1.BufferTank(BT)supply
2.Domestichotwater(DHW)
3.BufferTank(BT)return
4.Domesticcoldwater(DCW)
5.Hotwatercirculation(HWC)-(Optional)
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby qualifiedandauthorizedpersonnelonly.
Connectionsizes:
BT: DCW+DHW+HWC:
Dimensions(mm):
Withoutcirculationandcover: H655xW440xD138 Withoutcirculationandwithcover: H715xW450xD150 Withcirculationandwithoutcover: H940xW440xD138 Withcirculationandcover: H940xW450xD150
Weight(approx.):
BrazedHEX(A+/S+): GasketedHEX(B+):
G¾”(int.thread) G¾”(int.thread)
14kg 17kg
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote themarkingsonthestation.
VI.JV.I4.02/LUK38016
©Danfoss|2019.04|5
OperatingGuideTermixSolarA+/B+/S+
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes andlabelsareplacedcorrectly.Ifyouwishtomountthestation differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe cleanedandrinsed.
Keyholeformounting.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha plug.Shouldtheplugsrequireremoval,thismustonlybedoneby anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording toschematicdiagram.Pleasenotethatthestrainermaybe suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe madeusingthreaded,flangedorweldedconnections.
6|©Danfoss|2019.04