Danfoss Solar A Fact sheet

Fact sheet
Termix Solar A+
Wall-mounted domestic hot water module for flats, single-family houses and apartment buildings
Application
The Termix Solar A+ is an instanta­neous water heater, featuring superb heat extraction and high performance – due to the patented Micro PlateTM echnology and a high performance charging pump. Termix Solar A+ is ap­plicable for heating systems with buf­fer accumulators, solar systems or for other heat sources, where a very low return temperature is preferred. The primary source is cooled out very e­ciently by the heat exchanger, thereby creating a very good operation econo­my. A ow switch in the domestic hot water pipe is controlling the primary pump. An optional circulation pump can maintain the circulating tempera­ture at a desired temperature.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and the tempera­ture is regulated with a thermostatic control valve. The AVTB valve ensures a stable hot water temperature by varying loads, ow temperatures and dierential pressure, without the need for readjusting the valve. There is no additional pressure loss on the secondary side of the heat exchanger with a thermostatic control. There­fore this unit is suitable in systems with low pressure in the cold water mains.
Options
The water heater can be provided with a circulation pump with safety valve, a white-laquered steel cover and two dierent ball valve sets (one set is with DVGW approval for DHW).
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The brazed heat ex­changer is made of copper and stain­less steel with copper brazing.
FEATURES AND BENEFITS
• Domestic hot water module with tap capacity of up to 35l/min. at 90 kW
• Thermostatic control
• Operates independently of dierential pressure and ow temperature
• XB06H+ Micro PlateTM heat exchanger:
- Low pressure loss
- Superior heat transfer
• High eciency pump capable of 7m head
• Reliable long-life AVTB regulation valve
heating.danfoss.com
CIRCUIT DIAGRAM – EXAMPLE
BT
21
supply
supply
return
return
1
BT
35
BT
21
1 13
BT
35
13
230 V
M
Termix Solar A+ B Heat exchanger DHW
21
45
1A
DHW
M Electrical wiring box 1 Ball valve 1A Ball valve, DVGW 7 Thermostatic valve 13 Charging pump 21 To be ordered separately 35 Ball valve / non-return valve 45 Flow switch
7
1A
DCW
B
230 V
M
Termix Solar A+
21
45
1A
DHW
with circulation B Heat exchanger DHW M Electrical wiring box 1 Ball valve 1A Ball valve, DVGW
7
21
2
1A
DCW
B
4
11 A
230 V
Circ.
1
2 Single check valve 4 Safet valve 7 Thermostatic valve 11A Domestic hot water pump
with built in check valve 13 Charging pump 21 To be ordered separately 35 Ball valve / non-return valve 45 Flow switch
Technical parameters:
Nominal pressure: PN 10 DH supply temperature: T DCW static pressure: P Brazing material (HEX): Copper
= 120 °C
max
= 0.5 bar
min
Weight incl. cover: 15 kg (incl. packing)
Dimensions (mm):
Without cover: H 655 × W 440 × D 140 With cover: H 715 × W 450 × D 150 With circulation: H 940 × W 440/450 × D 140/150
Connections:
1. Buer tank (BT) supply
2. Domestic hot water (DHW)
3. Buer tank (BT) return
940
655
440 45
246 100
1 2
3 4
303 100
5
45
138
Connections sizes:
All connections: G ¾“(int. thread)
Module code number: 144H1277
Options:
• Circulation pump with 10 bar safety valve (144H0936)
• White-laquered steel cover (144H1282)
• Ball valve set with 4 ball valves (144H0930)
• Ball valve set with 4 ball valves, of which two are with DVGW approval (144H0932)
4. Domestic cold water (DCW)
5. Circulation (optional)
135 168
45
DHW: CAPACITY EXAMPLES
DHW temperature
[°C]
10 / 45 65
10 / 50
Tap capacity
[kW]
95
Supply flow primary
[°C]
55 40 70 40
Pressure loss primary
[kPa]
Gemina Termix A/S · Member of the Danfoss Group · Navervej 15-17 · DK-7451 Sunds · Denmark Tel.: +45 9714 1444 · Fax: +45 9714 1159 · mail@termix.dk · www.heating.danfoss.com
Tap fl ow
[l/min]
27 35
© Danfoss | DHS-SRMT/ PL | 2016 . 02