Datasheet
Electronic Solar Heat Regulator
SH-E01
Application The regulator is used for utility water management
in solar heating systems. The solar heat circuit
circulation pump is controlled on the basis of
the dierential temperature between the solar
collector and the hot-water tank.
If the dierential temperature is higher than
the preset start-up temperature dierential, the
circulation pump will be in operation. The pump
will run until the temperature dierential is 2°C.
Functions The regulator is simple to install and easy to
operate for the end-user:
• Electrical connections on wall plate
• Installer settings on regulator back
• Pump exercise
Ordering
Product Typ e Code Number
Regulator including 2 temperature sensors SH-E01 088H2001
Regulator excluding temperature sensors 088H2000
Pack of 2 temperature sensors - 088H2050
• User settings on regulator front
• Design suitable for use in any room
• Fault indication in display
• Forced cooling in case of overtemperature
• 24-hour backup in case of power failure
Data - Electronic Regulator
Accessories
Sensor pocker, brass length 111 mm 017-437000
Sensor pocker, brass length 180 mm 017-436766
Heat-conductive paste, aluminium - 041E0114
Supply voltage 230 V AC ±10%
Power consumption 25-42 mA
Switching action Type 1B
Pump output 230 V AC, max. 2(1)A
Alarm output 230 V AC, max. 2(1)A
Connections 2 x NTC sensor, pump, external alarm
Enclosure IP40
Ambient temperature 0 to 45 °C
Transport temperature -20 to 60 °C
Min. operating value 0.5 °C/minute
Control pollution situation Pollution degree 2
Ball pressure T 75 °C
Rated impulse voltage 2.5 KV
Software classication Class A
Dimensions, H x W x D 90 x 135 x 26 mm
Weight 215 g
Temperature display T1, solar collector: -9 to 150 °C. T2, tank bottom: 0 to 99 °C
Approvals EN60730-2-9, LVD, 2006/95/EC, EN60730-1, DTI type approval obtained,
EMC 2004/108/EC
Part No. 502v04 06/16
1
Datasheet
Solar Heat Regulator - SH-E01
Data - Temperature Sensor
Type NTC
Temperature Range -20 to 200 °C
Sensor Accuracy Max. 2% of full scale: -40 til 90 °C: ±1.0 °C,
Sensor diameter x length Ø 6 mm x 50 mm
Cable 3 m. 0.5 m approved for 200 °C, the rest for 105 °C
Sensor cables can be extended by double-insulated cable, min. 2 x 0.75 mm
90 til 150 °C: ±2.5 °C
150 til 200 °C: ±3.5 °C
2
, max. length 50 m.
Operating Principle T1: Temperature sensor in solar collector
T2: Temperature sensor in hot water tank
Circulation pump
Solar heat controller
Installer Settings
Position ON
Position OFF
Switch No.
Switch No. Start temp.
3 4
OFF OFF 5°C
OFF ON 10°C
ON OFF 15°C
ON ON 20°C
dierential
System
Reset
Pump
Exercise
Setting of start
temperature dierential
Dimensions
User Settings A) Setting of pump operation pattern:
AUTO, MAN or STOP.
B) Display mode:
Temperature, output or fault in alarm mode.
C) Indication of pump operating mode and alarm
- Green lamp is lit when pump is running
- Red lamp indicates alarm
D) Shift between display modes:
Temperature or solar heat output
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already
on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2