Danfoss SH090, SH485, SH184, SH161, SH180 Application Manuallines

...
MAKING MODERN LIVING POSSIBLE
Application guidelines
Danfoss scroll compressors
SH090 to SH485 - single
50 Hz - 60 Hz - R410A
www.danfoss.com
Scroll compression principle ........................................... 4
Features ............................................................................. 5
Compressor model designation ...................................... 6
Nomenclature ...............................................................................................6
Technical speci cations ................................................... 7
50-60 Hz data ................................................................................................7
Dimensions ....................................................................... 8
SH090-105-120-140* & 161* ..................................................................8
SH 140 & 161 code 3 & SH184 .................................................................9
SH180-240-295 ..........................................................................................10
SH300............................................................................................................11
SH380-485 ...................................................................................................12
Connection details ...................................................................................13
Electrical data, connections and wiring ........................ 14
Motor voltage ............................................................................................ 14
Wiring connections .................................................................................14
IP rating ........................................................................................................15
Terminal box temperature ....................................................................15
Three phase electrical characteristics ............................................... 16
Danfoss MCI soft-start controller ........................................................17
General wiring information .................................................................. 18
Motor protection ......................................................................................20
Voltage imbalance ................................................................................... 21
Approval and certi cations ........................................... 22
Approvals and certi cates..................................................................... 22
Pressure Equipment ................................................................................ 22
Low voltage directive .............................................................................22
Machines directive ...................................................................................22
Internal free volume ................................................................................22
Operating conditions ..................................................... 23
Refrigerant and lubricants ....................................................................23
Motor supply ..............................................................................................24
Compressor ambient temperature .................................................... 24
Application envelope .............................................................................24
Discharge temperature protection ...................................................25
High and low pressure protection .....................................................25
Cycle rate limit ...........................................................................................26
System design recommendations ................................. 27
General ......................................................................................................... 27
Essential piping design considerations ............................................27
Refrigerant charge limit ......................................................................... 28
O -cycle migration ..................................................................................29
Liquid  ood back ......................................................................................31
Speci c application recommendations ........................32
Low ambient application ......................................................................32
Low load operation .................................................................................33
Brazed plate heat exchangers .............................................................33
Electronic expansion valve ...................................................................33
Reversible heat pump systems............................................................33
Water utilizing systems ..........................................................................35
Sound and vibration management ............................... 36
Starting sound level ................................................................................36
Running sound level ...............................................................................36
Stopping sound level ..............................................................................36
Sound generation in a system .............................................................36
Installation ...................................................................... 38
Compressor handling and storage ....................................................38
Compressor mounting ........................................................................... 38
Compressor holding charge .................................................................39
System cleanliness ................................................................................... 40
Tubing ..........................................................................................................40
Brazing and soldering .............................................................................40
System pressure test ............................................................................... 41
Leak detection ...........................................................................................42
Vacuum evacuation and moisture removal ....................................42
Filter driers ..................................................................................................42
Refrigerant charging ............................................................................... 43
Insulation resistance and dielectric strength ................................. 43
Commissioning ......................................................................................... 43
Oil level checking and top-up .............................................................43
Ordering information and packaging ...........................44
Packaging .................................................................................................... 44
Ordering information..............................................................................45
Accessories ...................................................................... 47
FRCC.PC .007.B8.02
3
Application guidelines
Scroll compression principle
In a Danfoss SH scroll compressor, the compression is performed by two scroll elements located in the upper part of the compressor.
Suction gas enters the compressor at the suction connection. As all of the gas  ows around and through the electrical motor, thus ensuring complete motor cooling in all applications, oil droplets separate and fall into the oil sump. After exiting the electrical motor, the gas enters the scroll elements where compression takes place. Ultimately, the discharge gas leaves the compressor at the discharge connection.
The  gure below illustrates the entire compression process. The centre of the orbiting scroll (in grey) traces a circular path around the centre of the  xed scroll (in black). This movement creates symmetrical compression pockets between the two scroll elements. Low-pressure suction gas is trapped within each crescent-shaped pocket as it gets formed; continuous motion of the orbiting scroll serves to seal the pocket, which decreases in volume as the pocket moves towards the centre of the scroll set increasing the gas pressure. Maximum compression is achieved once a pocket reaches the centre where the discharge port is located; this stage occurs after three complete orbits. Compression is a continuous process: the scroll movement is suction, compression and discharge all at the same time.
SUCTION
COMPRESSION
DISCHARGE
4
FRCC.PC .007.B8.02
Application guidelines
Features
SH range is composed of SH090-105-120­140-161-184 (light commercial platform) and SH180-240-295-300-380-485 (large commercial platform).
The SH090-105-120-140-161-184 compressors bene t from a further improved design to achieve the highest e ciency.
• Gas circulation, motor cooling and oil behaviour are improved on light commercial platform models by a new patented motor cap design.
• Part protection and assembly reduces internal leaks and increases life durability.
Heat shield that lowers the heat transfer between discharge and suction gas and the acoustic level
• Improved part isolation reduces greatly acoustic levels.
• Gas intake design induces higher resistance to liquid slugging.
The SH485 compressors include additional features for enhanced protection and e ciency:
• integrated discharge gas temperature protection,
• intermediate discharge valves for higher seasonal e ciency.
• patented gas path  ow.
Integrated discharge gas temperature protection (SH485)
New PTFE spring seal for even lower leaks
Intermediate discharge valves (SH485)
R410A optimized and dedicated scroll pro le
Patented motor cap
Liquid slug protection per suction  tting in upper position
Patented gas path  ow (SH485)
Patented motor centring spacer
Improved lower bearing centring
SH180-240-295-300-380-485SH090-105-120-140-161-184
FRCC.PC .007.B8.02
5
Application guidelines
Compressor model designation
Danfoss SH scroll compressors for R410A are available as single compressors. The example below presents the compressor nomenclature which equals the technical reference as shown on the compressor nameplate.
Nomenclature
Family,
lubricant
& refrigerant
Family, lubricant & refrigerant SH: Scroll, POE lubricant,
for R410A
Nominal capacity
in thousand Btu/h at 60 Hz, R410A, ARI conditions
UL index
Motor voltage code
3: 200-230V/3~/60 Hz 4: 380-400V/3~/50 Hz - 460V/3~/60 Hz
for SH295 & SH485: 380-415V/3~/50Hz - 460V/3~/60Hz
6: 230V/3~/50 Hz 7: 500V/3~/50 Hz - 575V/3~/60 Hz 9: 380V/3~/60 Hz
Nominal capacity
Code numbers for ordering are listed section "Ordering information and packaging".
For tandem and trio assemblies, please refer to the Danfoss SH scroll compressor Parallel Application Guidelines, FRCC.EC.008.
Approvals Voltage Version Evolution
index
A4SHAAB485
Evolution index
A~Z
Motor protection
L: Internal overload protector
A: Electronic, 24V AC
B: Electronic, SH180: 230V SH240-300-380-485: 115/230V C: Customized electrical box
J: Operating control system 24V AC* K: Operating control system 230V AC*
Suction and discharge connections
A: Brazed connections
* for SH485 only. For further information refer to application guidelines FRCC.PC.027.
6
FRCC.PC .007.B8.02
Application guidelines
50-60 Hz data
Technical specifications
Nominal tons
Model
SH090 7.5 22 300 76 100 7.19 3.10 10.59 88.40 15.40 3.0 58.0
SH105 9 26 850 91 600 8.47 3.17 10.80 103.50 18.00 3.3 64.0
SH120 10 30 000 102 200 9.46 3.17 10.80 116.90 20.30 3.3 64.0
SH140 12 34 700 118 400 10.86 3.19 10.90 133.00 23.12 3.3 67.0
SH161 13 38 800 132 400 12.15 3.19 10.90 151.70 26.40 3.3 69.0
50 Hz
60 Hz
Displacement at nominal speed: 2900 rpm at 50 Hz, 3500 rpm at 60 Hz Net weight with oil charge
TR: Ton of Refrigeration, Standard rating conditions: ARI standard Evaporating temperature: 7.2 °C Superheat: 11.1 K EER: Energy E ciency Ratio Refrigerant: R410A Condensing temperature: 54.4 °C Subcooling: 8.3 K COP: Co e cient Of Performance,
Subject to modi cation without prior noti cation. For full data details and capacity tables refer to Online Datasheet Generator: ww w.danfoss.com/odsg
SH184 15 44 650 152 500 13.73 3.25 11.10 170.30 29.60 3.6 71.5
SH180 15 44 500 151 800 13.73 3.21 10.95 170.20 29.60 6.7 108.0
SH240 20 60 400 206 300 18.77 3.22 11.00 227.60 39.60 6.7 108.0
SH295 25 73 200 249 800 22.50 3.25 11.10 276.2 48.10 6.7 111.0
SH300 25 75 200 256 400 23.32 3.22 11.00 285.50 49.70 6.7 153.0
SH380 30 90 400 308 700 28.19 3.21 10.95 345.00 60.00 7.2 159.0
SH485 40 116 300 396 900 35.75 3.25 11.10 442.60 77.00 6.7 175.0
SH090 7.5 27 100 92 500 8.57 3.16 10.79 88.40 18.60 3.0 58.0
SH105 9 32 100 109 500 9.96 3.22 11.00 103.50 21.80 3.3 64.0
SH120 10 36 800 125 400 11.25 3.27 11.15 116.90 24.60 3.3 64.0
SH140 12 42 300 144 300 12.94 3.27 11.15 133.00 27.90 3.3 67.0
SH161 13 47 200 160 900 14.43 3.27 11.15 151.70 31.90 3.3 69.0
SH184 15 54 000 184 400 16.45 3.28 11.20 170.30 35.80 3.6 71.5
SH180 15 54 300 185 300 16.45 3.27 11.15 170.20 35.70 6.7 108.0
SH240 20 73 500 251 000 22.48 3.27 11.15 227.60 47.80 6.7 108.0
SH295 25 88 500 302 000 27.20 3.25 11.10 276.20 58.00 6.7 111.0
SH300 25 91 300 311 500 28.19 3.24 11.05 285.50 60.00 6.7 153.0
SH380 30 109 600 374 300 34.02 3.22 11.00 345.00 72.30 7.2 159.0
SH485 40 140 600 479 600 43.28 3.25 11.10 442.60 92.90 6.7 175.0
60 Hz
TR W Btu/h kW W/W Btu/h/W cm3/rev m3/h dm3 kg
Nominal cooling
capacity
Power
input
COP E.E.R. Swept volume
Displacement
Oil charge
Net weight
FRCC.PC .007.B8.02
7
Application guidelines
SH090-105-120-140* & 161*
(* except code 3)
117
(1)
235
(2)
278
(1)
137
(2)
189
Dimensions
Ø 224
Oil sight glass
(1)
94
(2)
101
Equalisation line
(1)
482
(2)
540
(1)
451
(2)
509
Ø 243
(1)
94
(2)
101
4 x hole Ø 19.05
230
(1)
(2)
60°
Ø 29
Ø 35
190.5
30°
30°
230
190.5
Ø 22
180
154
(1)
SH090
(1)
158
(2)
173
(2)
SH105 - 120 - 140* & 161*
* except code 3
All dimensions in mm
Flexible grommet
HM 8 bolt
Lock washer
Flat washer
Steel mounting sleeve
Rubber grommet
15 mm
Nut
8
FRCC.PC .007.B8.02
Application guidelines
SH 140 & 161 code 3 & SH184
(1) 278 (2) 300
Dimensions
Ø 243
Oil sight glass
(1) 101 (2) 108
157
(1) 155 (2) 170
Equalisation line
(1) 101 (2) 108
Ø 243
(1) 509 (2) 525
(1) 540 (2) 555
230
4 x holes Ø19.05
190.5
Ø 35
60°
Ø 22
30°
30°
230
190.5
173
200
(1) 154 (2) 159
(1) SH140 & 161 code 3 (2) SH184
All dimensions in mm
Flexible grommet
Lock washer
Flat washer
HM 8 bolt
FRCC.PC.007.B8.02
Steel mounting sleeve
Rubber grommet
Nut
15 mm
9
Application guidelines
SH180-240-295
Ø257.4
Dimensions
Ø265.9
Discharge 1"1/8
370.8
187
214
4x rigid spacer 29.5
304.8
301.5
195
170
Ø317.5
345.4
279.4
183
76.6
6
531.5 ±1.2
92.5
4x holes Ø19
428
Suction 1"5/8
All dimensions in mm
618
653
6
109
212
353
Flexible grommetRigid spacer
HM 8 bolt Lock washer
Nut
Flat washer
Steel mounting sleeve
29.5 mm
Rigid spacer
10
FRCC.PC.007.B8.02
Rubber grommet
HM 8 bolt
Lock washer
Flat washer
Nut
Compressor base plate
28 mm
Application guidelines
SH300
693.5
634.5 187
301.5
214
Dimensions
Ø333.2
Ø318.1
76.6
Discharge 1"1/8
Suction 1"5/8
492.5 ±1.2
92.5
4x rigid spacer
370.8
304.8
202
195
6
345.4
279.4
183
212
356
All dimensions in mm
4xholes Ø19
6
428
109
Rigid spacer
29.5 mm
FRCC.PC.007.B8.02
HM 8 bolt Lock washer
Nut
Flat washer
Rigid spacer
Flexible grommet
HM 8 bolt
Lock washer
Flat washer
Steel mounting sleeve
Rubber grommet
Nut
Compressor base plate
28 mm
11
Application guidelines
SH380-485
Dimensions
Ø333.2
Ø318.1
Discharge: SH380: 1"1/8 SH485: 1"3/8
370.8
187
214
304.8
301.5
202
195
345.4
279.4
183
76.6
6
524.8 ±1.2
92.5
4 holes Ø19
428
Suction 1"5/8
725.8
667
All dimensions in mm
6
109
212
356
Rigid spacer
HM 8 bolt Lock washer
Nut
Flat washer
29.5 mm
Rigid spacer
12
FRCC.PC.007.B8.02
Flexible grommet
HM 8 bolt
Lock washer
Flat washer
Steel mounting sleeve
Rubber grommet
Nut
Compressor base plate
28 mm
Application guidelines
Dimensions
Connection details
Suction and discharge connections
SH 090 - 105 - 120 -
140 - 161 - 184
Version AL
Suction and discharge connections Brazed Brazed
Oil sight glass Threaded Threaded
Oil equalisation connection rotolock 1"3/4 rotolock 2"1/4
Oil drain connection none 1/4’’  are
Low pressure gauge port (schrader) 1/4"  are 1/4’’  are
SH090
SH105 -120-140-161-184
SH180-240-295-300-380
SH485
Suction
Discharge 7/8"
Suction 1"3/8
Discharge 7/8"
Suction 1’’ 5/8
Discharge 1’’ 1/8
Suction 1”5/8
Discharge 1”3/8
SH 180 - 240 - 295 -
300 - 380 - 485
Brazed version
Tube ODF
Brazed
1"1/8
Oil sight glass All Danfoss SH scroll compressors come equipped
with a sight glass (1"1/8 - 18 UNF) which may be used to determine the amount and condition of the oil contained within the sump.
Oil equalisation connection
SH090-105-120-140-161-184: 1"3/4 rotolock connector allowing use of 1”3/4 - 7/8" or 1”3/4 ­1”1/8 sleeve. SH180-240-295-300-380-485: 2”1/4 rotolock connector allowing the use of 2”1/4 - 1”3
/8 or 2”1/4 - 1”5/8 sleeve. This connection must be used to mount an oil equalisation line when two or more compressors are mounted in parallel (please refer to Danfoss SH Parallel Application Guide l ines FRCC.
EC.008.
for details).
Oil drain connection
The oil drain connection allows oil to be removed from the sump for changing, testing, etc. The  tting contains an extension tube into the oil sump to more e ectively remove the oil. The connection is a
female 1/4"  are  tting incorporating a schrader valve and is mounted on SH180 - 240 - 295 - 300 - 380 - 485 models only.
Oil  ll connection and gauge port
Oil drain connection
Schrader
The oil  ll connection and gauge port is a 1/4"
leare connector incorporating a schrader
ma
valve.
FRCC.PC.007.B8.02
13
Application guidelines
Electrical data, connections and wiring
Motor voltage
Wiring connections
SH090-105-120-140-161
Except SH140-161 code 3
Danfoss SH scroll compressors are available in  ve di erent motor voltages as listed below.
Motor voltage code Code 3 Code 4Code 6Code 7 Code 9
Nominal voltage -
50 Hz
Voltage range -
Nominal voltage 200-230V - 3 ph 460
60 Hz
Voltage range 180-253 V 414-506 V - 517-632 V 342-418 V
* SH295 & 485
Electrical power is connected to the compressor terminals by Ø 4.8 mm (3/16”) screws.
The terminal box is provided with a Ø 25.5 mm
380-400V - 3 ph
380-415V - 3 ph *
340-440 V
340-457V *
V - 3 ph - 575 V-3 ph 380V- 3 ph
230V - 3 ph 500V - 3 ph -
207-253 V450 - 550 V-
The maximum tightening torque is 3 Nm. Use a
ring terminal on the power leads.
1/4’’
Terminal box
(ISO25) and a Ø 29 mm (PG21) knockouts.
Ø 25.5 mm knockout
Ø 29 mm knockout
SH140&161 code 3 & SH184
SH180
The terminal box is provided with a Ø40.5 mm hole (ISO40) for power supply and
a
Ø16.5 mm knockout (ISO16).
The terminal box is provided with 2 triple knockouts and 1 single knockout for power supply and 4 double knockouts for the safety control circuit.
The 3 power supply knockouts accommodate the following diameters:
Ø 50.8 mm
(UL 1"1/2 conduit) & Ø 43.7 mm (UL
1"1/4 conduit) & Ø 34.5 mm (UL 1" conduit)
Ø 40.5 mm (ISO40) & Ø 32.2 mm (ISO32) & Ø
25.5 mm (ISO25)
Ø 25.5 mm (ISO25)
Power supply
Ø 40.5 mm hole
Ø 16.5 mm knockout
Power supply
The 4 others knockouts are as follows:
• Ø 22.5 mm (PG16) (UL 1/2")
& Ø 16.5 mm
(ISO16) (x2)
20.7 mm (ISO20 or PG13.5) (x2)
Terminal box
Safety circuit Module power supply
Sump heater
Faston 1/4" tabs
Power supply
14
FRCC.PC.007.B8.02
Application guidelines
Electrical data, connections and wiring
SH240-295-300-380-485
The motor protection module comes pre­installed within the terminal box and has pre-wired thermistor connections. The module must be connected to a power supply of the appropriate voltage. The module terminals are
6.3 mm size.
The terminal box is
provided with 2 triple
knockouts and 1 single knockout for power supply and 4 double knockouts for the safety control circuit.
The 3 power supply knockouts accommodate the following diameters:
Ø 50.8 mm (UL 1"1/2 conduit) &
Ø 43.7 mm (UL
1"1/4 conduit) & Ø 34.5 mm (UL 1" conduit)
Ø 40.5 mm (ISO40) & Ø 32.2 mm (ISO32) & Ø
25.5 mm (ISO25)
Ø 25.5 mm (ISO25)
The 4 others knockouts are as follows:
• Ø 22.5 mm (PG16) (UL 1/2") & Ø 16.5 mm
(ISO16) (x2)
20.7 mm (ISO20 or PG13.5) (x2)
Internal control contac t
LN1 2 1412 11
Module power
Black
Faston 1/4” tabs
Power supply
Blue
Brown
Thermistor
connection
Safety circuit
M1 - M2 Control circuit
Module
}
power supply
}
Sump heater
IP rating
Terminal box temperature
The motor protection module comes preinstalled
Phase sequence input
within the terminal box. Phase sequence protection connections and thermistor connections are pre-wired. The module must be connected to a power supply of the appropriate
vo
ltage. The module terminals are 6.3-mm size
Faston type.
L1 L2 L3
Black Blue Brown
L N S1 S2 M1 M2
Module power
Internal control contac t
Safety
Thermistor
connection
circuit
The compressor terminal box according to IEC529 is IP54 for all models when correctly sized IP54 rated cable glands are used.
First numeral, level of protection against contact and foreign objects
5 - Dust protected
Second numeral, level of protection against water
4 - Protection
The temperature inside the terminal box may not
exceed 70°C. Consequently, if the compressor is installed in an enclosure, precautions must be taken to avoid that the compressor and in the terminal box would rise too much. The installation of ventilation on the
against water splashing
temperature around the
electronic protection module may not operate properly. Any compressor damage rel
ated to this will not be covered by Danfoss warranty. In the same manner, cables must be selected in a way to insure that terminal box temperature does not exceed 70°C.
enclosure panels may be necessary. If not, the
FRCC.PC.007.B8.02
15
Application guidelines
Electrical data, connections and wiring
Three phase electrical characteristics
Compressor model
SH090 203 43 38 0.39 SH105 267 46 45 0.27 SH120 267 61 48 0.27 SH14030464 56 0.24 SH161 315 69 64 0.22 SH184 351 75 71 0.22 SH180 320 78 71 0.19
Motor voltage code 3
200-230V / 3ph / 60 Hz
460V / 3ph / 60hZ
Motor voltage code 4
380-400 V / 3ph / 50 Hz *
code 6
230 V / 3ph /
Motor voltage
500 V / 3ph / 50 Hz
575 V / 3 ph / 60 Hz
Motor voltage code 7
380 V / 3ph / 60 Hz
Motor voltage code 9
* 380-415V/3ph/50Hz for
SH240 485 105 103 0.16 SH295 560 128 1120.13 SH300 560 132 125 0.13 SH090 98 20 19 1.47 SH105 14225 221.05 SH120 14229 241.05 SH140 147 30 28 0.92 SH161 158 33 31 0.83 SH184197 38.6 36 0.83 SH180 170 38 34 0.8 SH24021551490.62 SH295 260 6256 0.52 SH300 260 65580.48 SH380 320 79 72 0.42 SH485 413 90 89 0.23 SH090 157 40 32 0.5 SH105 223 43 38 0.35 SH120 223 51410.35 SH140236 53 49 0.31
50 Hz
SH161 236 57 53 0.31 SH184 236 57 56 0.31 SH090 8418 14 2.34 SH105 103 22 17 1.57 SH120 103 2419 1.57 SH140 122 26 22 1.38 SH161 136 29 241.32 SH184135 35 28 1.32 SH180 135 30 28 1.20 SH240 175 41 38 0.94 SH295 210 45 44 0.82 SH300 21053 48 0.82 SH380 235 60 55 0.56 SH090 124 26 23 1.05 SH105 16030 26 0.72 SH120 160 35 29 0.72 SH140 16837 330.62 SH161 177 41 37 0.57 SH184 239 51410.57 SH180 210 46 44 0.52 SH240260 60580.42 SH295 31072 69 0.36 SH300 310 85 72 0.36 SH380 360 90 85 0.24 SH485 491 111 106 0.16
LRA MCC Max. operating current Winding resistance
AAAΩ
SH295 and SH485
LRA (Locked Rotor Amp)
MCC (Maximum Continuous Current)
16
Locked Rotor Amp value is the higher average
current as measured on mechanically blocked compressor tested under nominal voltage. T
he
LRA value can be used as rough estimation for
The MCC is the current at which the motor protection trips under maximum load and low voltage conditions. This MCC value is the
maximum at which the compressor can be operated in transient conditions and out of
FRCC.PC.007.B8.02
the starting current. However in most cases, the real starting current will be lower. A soft starter can be applied to reduce starting current.
the application envelope. Abo
ve this value, the internal motor protection or external electronic module will cut-out the compressor to protect the motor.