Data Sheet
High Capacity Valve Body, Type RTD-G (Internal
Thread)
Application
Systems
The RTD-G high capacity on/off valves are used in
zone control applications. The valves can be combined with Danfoss TWA-D thermal actuator.
RTD-G valves are fitted with a grey protective
cap. This cap must not be used as a manual shut
off device.
Zone control application
A special manual shut off device is available
(code no. 013G3305).
The pressure pin in the gland seal is of chromium
steel and works in a lifetime lubricated O-ring.
The complete gland seal assembly can be replaced without draining the system.
In order to avoid depositions and corrosion the
composition of the hot water must be in accordance with the VDI 2035 Guidelines.
It is recommended that formulations containing
mineral oil are avoided.
Ordering and Specifications
Accessories
Thermal actuator TWA in combination with room thermostat/programme in radiator or floor heating
systems.
Type
RTD-G 20
straight
RTD-G 25
straight
1)
The kVS-value states the water flow (Q) in m³/h at a pressure drop (∆p) across the valve of 1 bar at fully open valve.
2)
Working pressure = static + differential pressure. The maximum differential pressure specified is the maximum pressure at which
the valves give satisfactory regulation. As with any device which imposes a pressure drop in the system, noise may occur under
certain flow/pressure conditions. To ensure quiet operation, maximum pressure drop should not exceed 30 to 35 kPa. The differential pressure can be reduced by the use of the Danfoss differential pressure regulators.
Product Units Code no.
Gland seal (can be replaced with the heating system in operation) 10 pcs. 013G0290
Connection
ISO 7-1
RP 3/4
RP 1
kVS-value
[m3/h]
3.81
4.58 013G1828
working
pressure
16 bar 1.8 bar 1.9 bar 25 bar 120 °C
Max.
1)
Differential pressure
TWA NC TWA NO
2)
Test
pressure
Max.
flow
temp.
Code no.
013G1826
Danfoss Heating Solutions VDGWF102 © Danfoss 02/2012 1
RTD-G DN20
[l/h]
kvs
∆p
[kPa]
∆p
[mwg]
∆p
[bar]
∆t = 15˚C
∆t = 20˚C
kW
kW
RTD-G DN25
[l/h]
kvs
∆p
[kPa]
∆p
[mwg]
∆p
[bar]
∆t = 15˚C
∆t = 20˚C
kW
kW
Data Sheet High Capacity Valve Body, Type RTD-G (Internal Thread)
Capacities
RTD-G DN20
RTD-G DN25
2 VDGWF102 © Danfoss 02/2012 Danfoss Heating Solutions