Danfoss RTD-CB, RTD-BR Data sheet

Data Sheet

Flow Restrictors for One-Pipe Systems

Application

RTD-CB back-flow restrictor

RTD-BR bypass restrictor

Principle

Heat Transfer

The RTD-CB back-flow restrictor prevents radiator back-flow and heat transfer at the return pipe in a one-pipe system.

The back-flow restrictor is installed in the radiator return pipe with the bow pointing upwards.

Radiator

The RTD-BR bypass restrictor decreases flow through the bypass in a one-pipe system, thus forcing the correct amount of system water to pass through the radiator.

The bypass restrictor will decrease the bypass with one dimension ( e.g. DN 20 > DN 15).

The bypass restrictor is installed in the bypass by the radiator.

Convector

90 ˚C

90 ˚C

TRV

TRV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RTD-BR

 

 

 

 

 

 

 

 

 

 

RTD-BR

 

 

 

 

 

RTD-CB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN. 175 MM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN. 175 MM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RTD-CB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Heat cost allocator (the heat cost allocator is placed according to the manufacturer’s instructions.)

The RTD-CB back-flow restrictor reduces heat transfer from system pipes to radiator, when the TRV is closed.

With the bypass placed 175 mm from the radiator, a flow temperature of 90 ˚C and a room temperature of 20 ˚C, the max. detected temperature is:

Heat cost allocators with a single

28 ˚C

sensor for radiator surface

 

 

 

Heat cost allocators with two

room temp.

sensors for radiator surface / room

+ 5 °C

temperature

 

 

 

Danfoss Heating Solutions

VDCHA202

© Danfoss

02/2011

1

Danfoss RTD-CB, RTD-BR Data sheet

Data Sheet

Flow Restrictors for One-Pipe Systems

 

 

 

 

 

 

Data and Ordering

 

 

 

Connections

Kvs

Max.

Test

Max.

 

 

Type

Size

 

 

 

work.

work.

Code no.

 

 

Inlet

Outlet

press.

 

 

 

 

 

press.

temp.

 

 

 

 

 

 

 

 

 

 

 

RTD-CB back-flow

DN 15

 

R 1/2

Rp 1/2

4.54 m³/h

10 bar

16 bar

120 °C

013L1925

 

restrictor

 

 

 

 

 

 

 

 

 

 

 

 

RTD-CB back-flow

DN 20

 

R 3/4

Rp 3/4

8.06 m³/h

10 bar

16 bar

120 °C

013L1926

 

restrictor

 

 

 

 

 

 

 

 

 

 

 

 

RTD-CB back-flow

DN 25

 

R 1

Rp 1

17.0 m³/h

10 bar

16 bar

120 °C

013L1927

 

restrictor

 

 

 

 

 

 

 

 

 

 

 

 

RTD-BR bypass

DN 15/10

G 1/2

G 1/2

6.80 m³/h

10 bar

16 bar

120 °C

013L1915

 

restrictor

 

 

 

 

 

 

 

 

 

 

 

RTD-BR bypass

DN 20/15

G 3/4

G 3/4

15.1 m³/h

10 bar

16 bar

120 °C

013L1916

 

restrictor

 

 

 

 

 

 

 

 

 

 

Dimensions

Back-flow restrictor

 

 

 

 

 

 

 

 

 

 

RTD-CB

 

 

S1

 

 

S2

 

 

 

 

 

 

<![if ! IE]>

<![endif]>L3

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D2

 

 

 

 

 

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

L2

 

 

 

 

 

 

 

 

Material: Stainless steel, AISI 316

 

 

 

Type

L1

L2

 

L3

D

d2

S1

S2

Code no.

 

RTD-CB DN 15

69

96

 

32

Rp 1/2

R 1/2

27

30

013L1925

 

RTD-CB DN 20

76

106

48

Rp 3/4

R 3/4

32

37

013L1926

 

RTD-CB DN 25

90

126

48

Rp 1

R 1

41

46

013L1927

Bypass restrictor RTD-BR

S1

S2

<![if ! IE]>

<![endif]>D1

<![if ! IE]>

<![endif]>D4

<![if ! IE]>

<![endif]>D2

<![if ! IE]>

<![endif]>D3

 

 

 

 

 

L2

 

 

 

 

 

L1

 

 

 

 

 

L3

 

Material: Black steel, ASTM A 216 WCB

Type

L1

L2

L3

D1

D2

D3

D4

S1

S2

Code no.

RTD-BR DN 15/10

27.3

24

47.5

G 1/2

G 1/2

G 1

Ø11

26

40

013L1915

 

 

 

 

 

 

 

 

 

 

 

RTD-BR DN 20/15

32

25.5

51.5

G 3/4

G 3/4

G 5/4

Ø16

32

50

013L1916

 

 

 

 

 

 

 

 

 

 

 

2

VDCHA202

© Danfoss

02/2011