Danfoss RT 6W, RT 6B, RT 6S, RT 6AW, RT 6AB Installation guide [da]

...
Installation guide
Pressure switch RT 6W, RT 6B, RT 6S, RT 6AW, RT 6AB, RT 6AS, RT 30AW, RT 30AB, RT 30AS with EN 12263 approval and CE marked acc. to PED (Pressure Equipment Direc
017-403066
017-404166
017-404266
Danfoss17-5027.10
Refrigerants*):
R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R507A, R717**)
017R9504
RT 6W, RT 6B, RT 6S
Fig. 1 Fig. 3
RT 6AW, RT 6AB, RT 6AS
017R9504
Fig. 2
RT 30AW, RT 30AB, RT 30AS
Fig. 4 Fig. 5 Fig. 6 Fig. 7 RT 6, RT 36:
1m, ¼ in x ¼ in are
Code no. 060-007166
RT 6, RT 36:
1m, ⁄ in x M10 – 0.75
Code no. 060-008266
Fig. 8a Fig. 8b Fig. 9
Enclosure*
Type / Typ
RT 6W IP66 automat. 5 – 25 3.0 RT 6B IP54 man. ext.
RT 6S IP66 man. int.
RT 6AW IP66 automat. 5 – 25 3.0 RT 6AB IP54 man. ext. RT 6AS IP66 man. int.
RT 30AW
RT 30AB IP54 man. ext. RT 30AS IP66 man. int.
Tæthedsgrad*
Schutzart*
Degré
d’étanchéité*
IP66 automat.
Reset
Pressure range
Trykområde
Druckbereich
Plage de pression
[bar]
10 – 28 max. 1.0
10 – 28 max. 1.5
1 – 10
Dierential (xed)
Dierens (fast) Dierenz (fest) Diérence (x)
Δp
[bar]
0.8
max. 0.4
Refrigerants
Kølemidler Kältemittel
Réfrigérants
uorinated refrigerants uoreded kølemidler uorierte Kältemittel réfrigérants uorés
R 717 (NH3)
+ uorinated refrigerants + uorerede kølemidler + uorierte Kältemittel + réfrigérants uorés
Fig. 10 * according to / i.h.t. / nach / conformément à EN 60529 / IEC 529
© Danfoss | DCS (jmn) | 2017.02
Code no. 017-425166
Max. working press.
Till. driftstryk
Zul. Betriebsüberdruck
Press. de service max.
PB / MWP
[bar] / [psig]
28 / 406 38 / 551
22 / 319 25 / 363
Max. test press. Max. prøvetryk Max. Prüfdruck
Press. d’essai
[bar] / [psig]
Ambient temp.
Omgivelsestem.
Umgebungstemp.
Temp. ambiante
[°C]
-50 – 70
DKRCC.PI.CF0.A3.52 | 520H11634 | 1
ENGLISH
Pressure switches
*) For complete list of approved refrigerants, www.products.danfoss.com and search for
individual code numbers, where refrigerants
are listed as part of technical data.
**) Only for RT 6AW, RT 6AB, RT 6AS, RT 30AW, RT 30AB, RT 30AS
Tested and approved by TÜV (Technischer Überwachungs Verein). W = Druckwächter (pressure control) B = Druckbegrenzer (pressure limiter) S = Sicherheitsdruckbegrenzer (safety pressure limiter)
In accordance with EN 12263 regulations, rupture of the control regulating bellows will have the eect that the refrigeration compressor stops, and cannot be restarted until the pressure control has been replaced. If the outer bellows ruptures, the control cut-out pressure falls by approx. 4 bar below the setting. The control therefore breaks the circuit at a normal condensing pressure, resulting in fail-safe function.
Common features of all designs
When the pressure in the system exceeds the setting, the control automatically stops the system.
In particular
RT 6W, RT 6AW, RT 30AW cut in automatically when the pressure has fallen below setting with ∆p dierential (xed) value.
RT 6B, RT 6AB, RT 30AB can be reset by depressing the external reset button when the pressure has fallen below the setting with ∆p dierential value (xed).
RT 6S, RT 6AS, RT 30AS can be reset by depressing the internal reset button when the pressure has fallen below the setting with ∆p dierential value (xed). ∆p - dierential values (xed) - according to the table g. 10 (see also g. 5).
Technical data
See g. 10. Contact load: see switch cover or g. 4. E.g. marking 10 (4) A, 400 V ~ means that a max. Ioad of 10 A ohmic and 4 A inductive may be connected on 400 V. The max. starting current on motor cutin (L.R.) may be up to seven times the inductive load, RT complies with conditions as specied in VDE* 0660, Test Class II.
*VDE = Verband Deutscher Elektrotechniker
Fitting
A set of Pg13.5 cable gland is attached to the RT in a separate bag. To ensure IP66 (units with automatic reset) or IP54 (units with external reset) grade of RT enclosure it is necessary to assemble this gland as shown in the g. 7. If this gland is not used with a cable, a metal blinding should be also assembled.
Use the mounting holes 25, ø5 mm. The pressure control can be mounted on the valve panel or on the compressor itself. If the control is likely to be subjected to vibration, it should be mounted on a resilient base.
the
If pressure pulsations occur in the system at the point where the pressure control is connected, these should be eectively damped, as for example, by
connecting the RT unit to the system via capillary tubing. See g. 8.
Electrical connection
See g. 6. FASE = phase. Cable diameter: 6 – 14 mm. Earth connection to earth terminal 38.
Setting
After removing the seal cap 7, set the cut out pressure with the uncovered range spindle while reading the scale 9. Turning the range screw clockwise increases setting of the cut out pressure, turning it anticlockwise decreases setting of the cut out pressure.
Accessories See gs. 8 and 9.
DANSK
Pressostater
*)
For komplet liste over godkendte kølemidler,
besøge www.products.
efter individuelle bestillingsnumre, hvor kølemidler er opført som en del af tekniske data.
**) kun for RT 6AW, RT 6AB, RT 6AS, RT 30AW, RT 30AB, RT 30AS
Afprøvet og godkendt af TÜV (Technischer Überwachungs Verein). W = Druckwächter B = Druckbegrenzer S = Sicherheitsdruckbegrenzer
I overensstemmelse med EN 12263 bestemmelser vil brud på apparatets reguleringsbælg medføre, at køleanl-æggets kompressor standser og vil først kunne genstartes, når pressostaten er udskiftet. Ved brud på den ydre bælg falder apparatets brydetryk ca. 4 bar under den indstillede værdi. Apparatet afbryder således ved normalt kondensatortryk. Herved opnås fail­safe funktion.
Fælles for alle udførelser
Når trykket i anlægget overskrider den indstillede værdi, vil apparatet automatisk stoppe anlægget.
Specielt
RT 6W, RT 6AW, RT 30AW indkobler automatisk, når trykket er faldet under den indstillede dierensværdi ∆p (fast).
RT 6B, RT 6AB, RT 30AB kan indkobles med udvendig resetknap, når trykket er faldet under den indstillede dierensværdi ∆p (fast).
RT 6S, RT 6AS, RT 30AS kan indkobles med indvendig resetknap, når trykket er faldet under den indstillede dierensværdi ∆p (fast).
p - dierensværdier (fast) - i.h.t. tabel g. 10 (se også g. 5).
Tekniske data
Se g. 10. Kontaktbelastning: Se kontaktdækslet eller g. 4.
danfoss.com og søg
Mærkningen, f.eks. 10 (4) A, 400 V ~ angiver, at der maks. må tilsluttes 10 A ohmsk og 4 A induktiv belastning ved 400 V. Den maksimale startstrøm ved indkobling af motor (L.R.) må være op til syv gange den induktive belastning. RT opfylder betingelserne som anført i VDE* 0660, Prüfklasse II.
*VDE = Verband Deutscher Elektrotechniker
Montering
Et sæt Pg13,5 kabelforskruning er vedlagt produktet i en separat pose. For at sikre kapslingsgrad IP66 (enheder med automatisk reset) eller IP54 (enheder med ekstern DANSK RESET) er det nødvendigt at montere denne kabelforskruning som vist i g. 7. Hvis denne kabelforskruning ikke bruges sammen med et kabel, bør der monteres en blindprop (metal skive).
Benyt monteringshullerne 25, ø5 mm. Pressostaten kan monteres på ventiltavlen eller på selve kompressoren. Hvis apparatet kan blive udsat for vibrationer, bør det monteres på et blødt underlag.
Forekommer der trykpulsationer i anlægget på det sted, hvor pressostaten er tilsluttet, skal disse dæmpes eektivt, f.eks.
ved at tilslutte apparatet til anlægget ved hjælp af et kapillarrør. Se g. 8.
El-tilslutning
Se g. 6. Kabeldiameter: 6 – 14 mm. Jordforbindelse tilsluttes jordskruen 38.
Indstilling
Efter at dækknappen 7 er ernet, indstilles brydetrykket med områdespindelen under samtidig aæsning af skalaen 9. Ved drejning af områdespindelen højre om (med uret) opnås højere brydetryk, ved drejning venstre om (mod uret) sænkes brydetrykket.
Tilbehør Se g. 8 og 9.