Danfoss RLV-D Installation guide

INSTRUCTIONS
RLV-D lockshield valve
Plastic pipes Copper pipes
According to BS 7291: According to BS 2871 Max. 92 °C, 3 bar. part 1 / BS EN 1057:
013R9330
Cutting the pipes
1. Cut the pipe square ensuring it is free of score marks. For plastic pipes we recommend the use of a plastic pipe cutter. Do not use a hacksaw.
2. To avoid damage to the pipe insert make sure burrs and sharp edges are removed.
3. Insert the pipe insert into the plastic pipe. Do not use any lubricant.
Mounting
Max. 92 °C, 3 bar.
with push-fit elbow
013R9330
IMPORTANT: Always use inserts of same make/brand as the pipe.
Ensure the pipe is pushed to the pipe stop.
Dismounting IMPORTANT:
DKCD VI.35.C1.02 09-2001
IMPORTANT: Both nuts have to be tightened.
It is good practice to check the fitting before use; pull the pipe back to check it is secure.
Ensure system is depressurised before removing fitting. Push in collet squarely against face of fitting. With the collet held in this position, the pipe can be removed. The fitting can then be re-used.
Collet cover and collet clip
Collet covers or collet clips provide added security against unintended pipe disconnection.
Removal of protective cap
Blocking
Collet clip, code no. 013G4913 (10 pcs.)
6 mm Allen key
Collet cover, code no. 013G4912 (10 pcs.)
Setting and regulation
¼ - 4
6 mm Allen key
Turn till stop. Turn back: ¼ - 4 rev.
DKCD VI.35.C1.02 09-2001