Danfoss RLV 10, RLV 15, RLV 20, RLV Data sheet

0 (0)

Data Sheet

Lockshield Valve Type RLV - with Facility for Connection to Drain Tap

Application

RLV straight

RLV angle

Drain tap

By means of a RLV lockshield valve every radiator can be shut off individually to allow trouble-free maintenance or repair without affecting other radiators in the system.

RLV lockshield valves are available in angle versions as well as straight versions. Finish: Nickel plated.

RLV lockshield valves can be preset to limit the max. water flow within the following setting area:

RLV 10:

kvs = 1.8 m³/h

RLV 15:

kvs = 2.5 m³/h

RLV 20:

kvs = 3.0 m³/h

Factory setting is fully open valve. Dimensions correspond to DIN 3842-1.

Accessories for RLV:

a drain tap for draining or filling of the radiator

a brass handwheel, used when radiators with RLV lockshield valves are removed.

In order to avoid deposition and corrosion the composition of the hot system water must be in accordance to the VDI 2035 guide line (Verein Deutscher Ingenieure).

Principle

Data and Ordering

 

Connections

Flow limitation: kv-values (m³/h) for number of turns

 

 

Type

ISO 7-1

Code no.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Syst.

Rad.

0.25

0.5

0.75

1.0

1.5

2

2.5

3.0

3.5

4.0

kvs

 

 

DN 10 angle

3/8

3/8

0.15

0.35

0.45

0.6

0.9

1.2

1.5

1.6

1.7

1.8

1.9

003L0141

 

 

 

 

DN 10 straight

003L0142

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DN 15 angle

1/2

1/2

0.2

0.4

0.5

0.65

1.0

1.3

1.7

1.9

2.1

2.3

2.5

003L0143

 

 

 

 

DN 15 straight

003L0144

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DN 20 angle

3/4

3/4

0.2

0.4

0.6

0.8

1.3

1.8

2.2

2.4

2.6

2.8

3

003L0145

 

 

 

 

DN 20 straight

003L0146

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Danfoss Heating Solutions

VDQBH302

© Danfoss

03/2011

1

Data Sheet

Lockshield Valve Type RLV - with Facility for Connection to Drain Tap

 

 

 

 

 

Max. working pressure: 10 bar.

RLV can be connected to PEX, AluPEX, steel or

 

Test pressure: 16 bar.

copper tubings by Danfoss compression fittings.

 

Max. water temperature: 120 ˚C.

 

 

Accessories

 

 

 

Product

 

Code no.

 

 

 

 

 

Drain tap with 3/4" hose nozzle

 

003L0152

 

 

 

 

Brass handwheel - temporarily replacement for the thermostat when the

013G3300

 

radiator is drained

 

 

 

 

Mounting

 

 

 

 

 

 

 

RLV

 

The RLV lockshield valve is intended for

 

mounting on the outlet of the radiator.

 

To enable subsequent draining of the radiator

 

water, the lockshield valve should be mounted

 

with its cover towards the front.

 

Drain tap

 

For mounting and operation of the drain tap, the

 

following procedure is recommended:

Setting

Setting of max. water flow:

 

▪ Close the valve by means of a 6 mm Allen

 

key.

 

▪ Regulate the water flow by opening the

 

valve. The capacity diagrammes on page 3

 

show the water flow at 1/4 - 4 turns and for

 

fully open valve (kvs).

1.Shut off the radiator inlet valve. As a safety precaution the thermostatic sensor should be replaced by a Danfoss manual shut off handle, code no. 013G3300.

2.Remove the cover and shut off the valve by means of a 6 mm Allen key.

3.Mount the drain tap and align the drain branch, which can revolve in any direction.

4.Open the valve for draining.

2

VDQBH302

© Danfoss

03/2011

Danfoss Heating Solutions

Danfoss RLV 10, RLV 15, RLV 20, RLV Data sheet

Data Sheet

Lockshield Valve Type RLV - with Facility for Connection to Drain Tap

 

 

Capacities

RLV DN 10

[mWg]

Q [l/h]

RLV DN 15

[mWg]

Q [l/h]

Danfoss Heating Solutions

VDQBH302

© Danfoss

03/2011

3