Data Sheet
Lockshield Valve Type RLV - with Facility for
Connection to Drain Tap
Application
RLV straight RLV angle Drain tap
Principle
By means of a RLV lockshield valve every radiator
can be shut off individually to allow trouble-free
maintenance or repair without affecting other
radiators in the system.
RLV lockshield valves are available in angle
versions as well as straight versions.
Finish: Nickel plated.
RLV lockshield valves can be preset to limit the
max. water flow within the following setting area:
RLV 10: kvs = 1.8 m³/h
RLV 15: kvs = 2.5 m³/h
RLV 20: kvs = 3.0 m³/h
Factory setting is fully open valve. Dimensions
correspond to DIN 3842-1.
Accessories for RLV:
a drain tap for draining or filling of the
▪
radiator
a brass handwheel, used when radiators
▪
with RLV lockshield valves are removed.
In order to avoid deposition and corrosion the
composition of the hot system water must be in
accordance to the VDI 2035 guide line (Verein
Deutscher Ingenieure).
Data and Ordering
Type
DN 10 angle
DN 10 straight 003L0142
DN 15 angle
DN 15 straight 003L0144
DN 20 angle
DN 20 straight 003L0146
Danfoss Heating Solutions VDQBH302 © Danfoss 03/2011 1
Connections
ISO 7-1
Syst. Rad. 0.25 0.5 0.75 1.0 1.5 2 2.5 3.0 3.5 4.0
3/8 3/8 0.15 0.35 0.45 0.6 0.9 1.2 1.5 1.6 1.7 1.8 1.9
1/2 1/2 0.2 0.4 0.5 0.65 1.0 1.3 1.7 1.9 2.1 2.3 2.5
3/4 3/4 0.2 0.4 0.6 0.8 1.3 1.8 2.2 2.4 2.6 2.8 3
Flow limitation: kv-values (m³/h) for number of turns
k
vs
Code no.
003L0141
003L0143
003L0145
Data Sheet Lockshield Valve Type RLV - with Facility for Connection to Drain Tap
Accessories
Mounting
Max. working pressure: 10 bar.
Test pressure: 16 bar.
Max. water temperature: 120 ˚C.
Product Code no.
Drain tap with 3/4" hose nozzle 003L0152
Brass handwheel - temporarily replacement for the thermostat when the
radiator is drained
RLV can be connected to PEX, AluPEX, steel or
copper tubings by Danfoss compression fittings.
013G3300
Setting
RLV
The RLV lockshield valve is intended for
mounting on the outlet of the radiator.
To enable subsequent draining of the radiator
water, the lockshield valve should be mounted
with its cover towards the front.
Drain tap
For mounting and operation of the drain tap, the
following procedure is recommended:
Setting of max. water flow:
Close the valve by means of a 6 mm Allen
▪
key.
Regulate the water flow by opening the
▪
valve. The capacity diagrammes on page 3
show the water flow at 1/4 - 4 turns and for
fully open valve (kvs).
1. Shut off the radiator inlet valve. As a safety
precaution the thermostatic sensor should
be replaced by a Danfoss manual shut off
handle, code no. 013G3300.
2. Remove the cover and shut off the valve by
means of a 6 mm Allen key.
3. Mount the drain tap and align the drain
branch, which can revolve in any direction.
4. Open the valve for draining.
2 VDQBH302 © Danfoss 03/2011 Danfoss Heating Solutions
Data Sheet Lockshield Valve Type RLV - with Facility for Connection to Drain Tap
Capacities
RLV DN 10
RLV DN 15
Danfoss Heating Solutions VDQBH302 © Danfoss 03/2011 3