Danfoss RLV 10, RLV 15, RLV 20, RLV Data sheet

Data Sheet
Lockshield Valve Type RLV - with Facility for Connection to Drain Tap
Application
RLV straight RLV angle Drain tap
Principle
By means of a RLV lockshield valve every radiator can be shut off individually to allow trouble-free maintenance or repair without affecting other radiators in the system.
RLV lockshield valves are available in angle versions as well as straight versions. Finish: Nickel plated.
RLV lockshield valves can be preset to limit the max. water flow within the following setting area:
RLV 10: kvs = 1.8 m³/h RLV 15: kvs = 2.5 m³/h RLV 20: kvs = 3.0 m³/h
Factory setting is fully open valve. Dimensions correspond to DIN 3842-1.
Accessories for RLV:
a drain tap for draining or filling of the
radiator a brass handwheel, used when radiators
with RLV lockshield valves are removed.
In order to avoid deposition and corrosion the composition of the hot system water must be in accordance to the VDI 2035 guide line (Verein Deutscher Ingenieure).
Data and Ordering
Type
DN 10 angle DN 10 straight 003L0142 DN 15 angle DN 15 straight 003L0144 DN 20 angle DN 20 straight 003L0146
Danfoss Heating Solutions VDQBH302 © Danfoss 03/2011 1
Connections
ISO 7-1
Syst. Rad. 0.25 0.5 0.75 1.0 1.5 2 2.5 3.0 3.5 4.0
3/8 3/8 0.15 0.35 0.45 0.6 0.9 1.2 1.5 1.6 1.7 1.8 1.9
1/2 1/2 0.2 0.4 0.5 0.65 1.0 1.3 1.7 1.9 2.1 2.3 2.5
3/4 3/4 0.2 0.4 0.6 0.8 1.3 1.8 2.2 2.4 2.6 2.8 3
Flow limitation: kv-values (m³/h) for number of turns
k
vs
Code no.
003L0141
003L0143
003L0145
Data Sheet Lockshield Valve Type RLV - with Facility for Connection to Drain Tap
Accessories
Mounting
Max. working pressure: 10 bar. Test pressure: 16 bar. Max. water temperature: 120 ˚C.
Product Code no.
Drain tap with 3/4" hose nozzle 003L0152
Brass handwheel - temporarily replacement for the thermostat when the radiator is drained
RLV can be connected to PEX, AluPEX, steel or copper tubings by Danfoss compression fittings.
013G3300
Setting
RLV
The RLV lockshield valve is intended for mounting on the outlet of the radiator. To enable subsequent draining of the radiator water, the lockshield valve should be mounted with its cover towards the front.
Drain tap
For mounting and operation of the drain tap, the following procedure is recommended:
Setting of max. water flow:
Close the valve by means of a 6 mm Allen
key. Regulate the water flow by opening the
valve. The capacity diagrammes on page 3 show the water flow at 1/4 - 4 turns and for fully open valve (kvs).
1. Shut off the radiator inlet valve. As a safety precaution the thermostatic sensor should be replaced by a Danfoss manual shut off handle, code no. 013G3300.
2. Remove the cover and shut off the valve by means of a 6 mm Allen key.
3. Mount the drain tap and align the drain branch, which can revolve in any direction.
4. Open the valve for draining.
2 VDQBH302 © Danfoss 03/2011 Danfoss Heating Solutions
Q [l/h]
[mWg]
Q [l/h]
[mWg]
Data Sheet Lockshield Valve Type RLV - with Facility for Connection to Drain Tap
Capacities
RLV DN 10
RLV DN 15
Danfoss Heating Solutions VDQBH302 © Danfoss 03/2011 3