Danfoss RET MD Data sheet

Datasheet
RET MD Intelligent Room Thermostat
Features
RET-M series of room thermostats combine the ease of use of a setting dial with accuracy and advanced features, including LCD display, that are only available from micro-processor based controller. The LCD display, that normally shows actual room temperature, changes momentarily to show set temperature whenever the setting dial is moved. Styled upon the RET room thermostat, the RET-M series can be set up by the installer to provide either traditional on/o control or more sophisticated chrono-proportional control for increased comfort and economy.
If set in chrono-proportional mode, the thermostat imposes a xed cycle rate on the system and then determines the duration of the On and O periods
within each cycle in proportion to load. The control algorithm used to determine the on/o periods uses a proportional + integral (PI) routine to eliminate oset normally associated with on/o or simple proportional control. Chrono-proportional control also signicantly improves comfort and generally improves boiler eciency by reducing mean water temperature.
The RET-MD is an intelligent room thermostat that incorporates an energy saving delay start feature, which delays the start-up of the heating dependent upon how close to set-point the room temperature is at the time heating time switch is scheduled to turn on the heating system.
Under most load conditions, this feature reduces the number of hours per day that the system runs, without creating any discomfort. This feature can, if necessary, be cancelled if the user wishes to override the delay period.
A version without delayed start, type RET-M, is also available. This model oers all the features of the battery powered RET-B but is mains powered.
Both models are ideal for use with combination boilers and can be installed without the need for complicated wiring or commissioning.
Intelligent heating control for increased fuel
economy.
Micro-processor accuracy. Setting dial with LCD temperature display. Wallplate construction for ease of installation.
Installer Settings
RET-MD with Delay Start
Sw. Setting Function
1 2 3 4
or 1
2 3 4
or 1
2 3 4
* Change to disable
© Danfoss HS | 09/2015 | 608v03 VDRKE202
Delay Start enabled*
On/O
Not active
°C (change for °F)
Delay Start enabled*
Chrono 3 cycles per hour °C (change for °F)
Delay Start enabled*
Chrono 6 cycles per hour °C (change for °F)
Set for cooling operation Set for heating operation
RET-M (no Delay Start Feature)
Sw. Setting Function
1 2 3 4
or 1
2 3 4
or 1
2 3 4
Cool
No compressor delay
Not active
°C (change for °F)
Cool
Compressor delay active
2 min compressor delay
°C (change for °F)
Cool
Compressor delay active
4 min compressor delay
°C (change for °F)
Sw. Setting Function
1 2 3 4
or 1
2 3 4
or 1
2 3 4
Heat
On/O
Not active
°C (change for °F)
Heat
Chrono 3 cycles per hour °C (change for °F)
Heat
Chrono 6 cycles per hour °C (change for °F)
1
Datasheet
45.0
Time delay after time control switch-on, minutes
ErP
4
RET MD Intelligent Room Thermostat
Specication and Ordering Details
ErP Class
Features RET-MD RET-M
Code No 087N726200 087N726400
Temperature Range 5 - 30°C
Setting knob and LCD display
Delay start feature dependent upon proximity to set-point
Delay start override button and LED status indicator
Chrono-proportional or On/O control
Heat or cool operation, including compressor delay timer
Selectable Fahrenheit or Centigrade scaling
Delay start select / disable feature
Output relay contact rating 10-250 Vac, 50/60 Hz, 3 (1) A
Switching action 1 SPDT
Power supply 230 Vac ± 10%, 50/60 Hz
Maximum ambient temperature 45°C
Dimensions (mm) 85 wide x 86 high x 42 deep
(1) Compressor delay only available if thermostat is set to cool operation.
(1)
ERP Class
The products represented within this document are classied according to, and allow completion of, the Energy Related Product (ErP) Directive System Package che and the ErP system data label. ErP Labelling obligation is applicable from 26th September 2015.
ErP Class Product Function and ErP Description
TPI Room Thermostat, for use with on/off output heaters
An electronic room thermostat that controls both thermostat cycle rate and in-cycle on/o ratio of the heater proportional
IV
to room temperature. TPI control strategy reduces mean water temperature, improves room temperature control accuracy and enhances system eciency.
Product
Class
Additional eciency
gain
2%
Delay Curve
Wiring
The RET-MD intelligent room thermostat delays the start-up of the heating system by a variable time period that is determined by the dierence in the room temperature compared to the temperature set on the thermostat. The smaller the dierence, the longer the delay before the heating is allowed to turn on. A built-in limit ensures that the delay period cannot exceed 45 minutes.
40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0
0.0 1.0
RET-MD RET-M
NO
3
4
ON
N
N L
ELECTRONICS
L
NC
1
2
OFF
COM
3.0 4.0 5.0
2.0
Temperature below thermostat setting, °K
NC
ELECTRONICS
1
N
N L
L
2
COM
Input from Time Control
Danfoss Ltd.
Ampthill Road Bedford MK42 9ER Tel: 01234 364621 Fax: 01234 219705 Email: ukheating@danfoss.com Website: www.heating.danfoss.co.uk
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
3
OFF
6.0 7.0
NO
4
ON
2
© Danfoss HS | 09/2015 | 608v03 VDRKE202