Datasheet
RET230 Electronic Room Thermostats with
Function Switches
Features
RET230 C01
• Wide range of application options
• Compact design
• Electronic accuracy
• Wallplate construction
• LED status indicators
This range of thermostats is aimed primarily
at the heating and air conditioning market,
where there is a demand for enhanced
functionality. All models feature dierent
combinations of supplementary function
switches which are accessible to the user.
RET230 LS: This thermostat, which can be
used in either heating or cooling systems,
incorporates a manual switch which allows
the thermostat output to be switched o.
RET230 C3: Designed for use with cooling
only fan coil units, the RET230 C3 incorporates
a combined system isolation switch and
Fan Auto/Fan Continuous switch. The latter
allows the user to decide if the fan should run
continuously or only when there is a demand
for cooling. A second three position switch
allows the user to select one of three fan
speed settings.
RET230 C03
RET230 C02: Designed for use in two-pipe
changeover fan coil unit systems, the RET230
C02 incorporates a manual Heating/Cooling
(Winter/Summer) switch which allows the
thermostat to operate as a cooling thermostat
in the summer and a heating thermostat in
the winter. A second two position switch
allows the user to turn the thermostat output
o if so desired.
RET230C03: Designed for use in two-pipe
changeover fan coil unit systems, the RET230
C03 incorporates a manual Heating/O/
Cooling (Winter/O/Summer) switch which
allows the thermostat to operate as a cooling
thermostat in the summer and a heating
thermostat in the winter. A second three
position switch allows the user to select one
of three fan speed settings.
© Danfoss HS | 09/2015 | 284v12 VDRKI202
1

Datasheet RET230 Electronic Room Thermostat with Switches
Specications Thermostat for use in systems having central changeover from heating to cooling
RET230 Electronic Thermostats with function switches RET230C02 RET230C03
Order Codes 087N702200 087N703200
Heating/Cooling thermostat for changeover systems • •
System O/Auto Selector •
Summer/O/Winter (Heating/O/Cooling) selector • (1)
Summer/Winter (Heating/Cooling) selector •
3 speed fan switch output terminals •
Single speed fan output terminal •
Switching Dierential <1K
Operating Voltage 220/240 Vac, 50/60 Hz
Switch Rating 2 (1) A
Temperature Range 5-30°C
Dimensions (mm) 85 wide x 87 high x 42 deep
(1) Switch label based on symbols
Thermostat for use in non-changeover systems
RET230 Electronic Thermostats with function switches RET230C3 RET230LS
Order Codes 087N702300 087N700700
Cooling thermostat •
Heating or Cooling thermostat • (2)
Fan Auto/Continuous switch with system O selector •
System O/Auto selector •
Power On and thermostat calling LEDs • •
3 speed fan switch output terminals •
Switching Dierential <1K
Operating Voltage 220/240 Vac, 50/60 Hz
Switch Rating 2 (1) A
Temperature Range 5-30°C
Dimensions (mm) 85 wide x 87 high x 42 deep
(2) RET230LS has SPDT contacts and can be used in heating or cooling systems
ErP Class
ERP Class
The products represented within this document are classied according to, and allow completion of, the Energy Related Product
(ErP) Directive System Package che and the ErP system data label. ErP Labelling obligation is applicable from 26th September
2015.
ErP Class Product Function and ErP Description Additional eciency gain
I
On/Off Room Thermostat
A room thermostat that controls the on/o operation of a heater.
1%
Product
Class
Dimensions
2
© Danfoss HS | 09/2015 | 284v12 VDRKI202
85
3
87 78
42