Danfoss RET2000 MD Installation guide

RET2000 MD
Electronic digital thermostat with LCD, delayed start
Danfoss Heating
Installation Guide
For a large print version of these instructions
please call Marketing on 0845 121 7400.
2
RET2000MD
Installation Instructions
Speci cations RET2000MD
Operating Voltage 230Vac 50/60Hz
Output Volt free
Setting temp. range 5-30°C
Operating temp. range 0-45°C
Switch rating 3A (1) at 230Vac
Switch type 1 x SPDT Type 1B
IP rating IP20
On/o control Yes
Chrono-proportional control Yes
Delayed start Yes
Construction EN 60730-2-9
GBGB
Control pollution situation Degree 2
Rated impulse voltage 2.5kV
Ball pressure test 75°C
Dimensions (mm) H84 x W84 x D35
Software Classi cation A
Danfoss Heating
3
GBGB
Mounting
Fix at a height of 1.5m approx from the  oor, away from draughts or heat sources such as radiators, open  res or direct sunlight.
Please Note:
This product should only be installed by a quali ed electrician or competent heating installer and should be in accordance with the current edition of the IEEE wiring regulations.
4
RET2000MD
Mounting
GBGB
Danfoss Heating
5
GBGB
Wiring
RET2000MD
ELECTRONICS
N
N
230Vac
Note: For RET2000 MD live supply is from the Time Control output.
6
L
L
1
COM
2
ON
3
OFF
RET2000MD
DIL switch settings
Slide the DIL switches to the settings required.
ON/OFF - output switches ON when below set temperature and OFF when above.
GBGB
CHRONO -
intervals to maintain a set temperature, achieving a constant ambient environment for the user.
o
use 6 Cycles for radiator systems
o
use 3 Cycles for under oor heating
Danfoss Heating
energy saving feature which  res the boiler at regular
7
DIL switch settings
GBGB
DELAYED START -
energy saving feature which automatically delays the heating start time, depending on how close to set-point the ambient room temperature already is (see chart opposite). For example during milder weather the heating start time can be delayed to avoid wasting fuel by bringing rooms up to temperature earlier than necessary.
Delayed start only operates when switched from a timer control.
CHRONO 6 CYCLES 3 CYCLES
ON/OFF 3/12 CYCLES 12 CYCLES
DELAYED START ON
°C
KEYS UNLOCKED
8
DELAYED START OFF °F KEYS LOCKED
RET2000MD
DIL Switch Settings
switch on, minutes
GBGB
Time delay after time control
Danfoss Heating
Temperature below thermostat setting, ⁰C
9
Locking and Limiting
GBGB
The RET2000 has an Advance Programming Mode in order to set up temperature lock and limit settings.
• Press the V button until the standby mode is reached.
• The V button should then be released and then pressed and held for a further 5 seconds to enter the Advanced Programming Mode.
• To indicate that the unit is in Advanced Programming Mode the Standby Indicator will  ash and the display will show the setting number alternating with the current value for that setting.
• To change the setting press either the Λ or V button.
10
RET2000MD
• A simultaneous push and release of both buttons will scroll through the steps S1 to S3 and will save the current set value if altered.
• To exit Advanced Programming Mode and return to Standby Mode press and hold both buttons for more than 5 seconds.
• While in Advanced Programming Mode if no buttons are pressed for more than 2 minutes the unit will automatically return to Standby mode, and the value on the current setting will not be saved.
S1 – Lower Temperature Limit
GBGB
This setting allows for a Lower Temperature Limit to be set. The Lower Limit can be set between 5°C (41°F) and 30°C (86°F).
Default – 5°C/41°F
Danfoss Heating
11
S2 – Upper Temperature Limit
This setting allows for a Upper Temperature Limit to be set.
GBGB
The Upper Limit can be set between 5°C (41°F) and 30°C (86°F). However, this will be limited by the Lower Temperature Limit set in S1 therefore the Upper Temperature Limit cannot be less than the Lower Temperature Limit.
Default – 30°C/86°F
S3 – Set Point Power-Up Temperature
This setting de nes the set point at power up when Button Lock is enabled on the DIL switch. This can be set between the Lower and Upper Temperature Limits set in S1 and S2.
Default – 21°C/70°F
12
RET2000MD
GBGB
Danfoss Heating
13
GB
14
RET2000MD
GB
Danfoss Heating
15
Danfoss Ltd
Ampthill Road Bedford MK42 9ER
Tel: 01234 364621 Fax: 01234 219705 Email: ukheating@danfoss.com Website: www.heating.danfoss.co.uk
Part No 44076v01 03/15
VIJTD102
Loading...